Interconnection-Wide Oscillation Analysis: Baselining Oscillation Modes in the North American Power System Objective Purpose

Size: px
Start display at page:

Download "Interconnection-Wide Oscillation Analysis: Baselining Oscillation Modes in the North American Power System Objective Purpose"

Transcription

1 Interconnection-Wide Oscillation Analysis: Baselining Oscillation Modes in the North American Power System NERC Synchronized Measurement Subcommittee (SMS) Scope Document Objective The objective of the work task to be performed by the NERC Synchronized Measurement Subcommittee (SMS) is to better understand the inter-area modes in each of the interconnections (Eastern, Western, ERCOT, and Quebec). The goal is to identify the modal characteristics (mode shape, mode frequency, mode damping ratio) of the interconnected bulk power system using high-resolution, time-synchronized measurement data during major grid disturbances. Purpose Some interconnections such as the Western Interconnection have spent significant effort to understand the oscillatory modes of their respective interconnections, particularly due the small signal stability risks posed to them. However, other interconnections have not cohesively analyzed the oscillatory modes of the system using wide-area synchrophasor data from Phasor Measurement Units (PMUs) or other types of high resolution, time-synchronized Disturbance Monitoring Equipment (DME). With the proliferation of PMUs across all interconnections in North America, in conjunction with the formation of the NERC SMS, the electric utility industry is equipped with the measurements and capability to perform such an analysis to better understand the inter-area modes on the system. The purpose and goals of this task include: 1. Use synchronized measurements across the interconnection during grid disturbances or abnormalities to baseline the oscillatory performance of the interconnection. 2. Provide the electric utility industry with a better fundamental understanding of inter-area modes and forced oscillations on the bulk power system. 3. Enable better monitoring of system behavior and identify oscillatory conditions or anomalies on the system if and when they occur. 4. Use actual data measured during system events to compare the modal characteristics of the planning models used in transient stability studies (compare model vs. actual) as a component of system-wide model validation.

2 Applicability Synchronized phasor measurement data will be collected through the Regional Entities, requested from the following applicable entities: Reliability Coordinators (RC) NERC may also request data for selected events using the University of Tennessee Knoxville (UTK) GridEye/FNET system. Data Collection Options & Event Selection Criteria Wide-area time synchronized data is required for this analysis. Currently, there are two primary options for collecting Dynamic Disturbance Recording (DDR) data. The plan to use these data sources is: 1. University of Tennessee-Knoxville FNET/GridEye System: The FNET system captures timesynchronized phasor data including voltage phasor magnitude and angle and frequency for distribution-connected wall outlet devices. These devices report phasor quantities at 10 samples per second, which limits the frequency range for which oscillations can be analyzed. FNET data will be analyzed on a larger set of events to understand if data quality and resolution are sufficient for oscillation analysis. 2. Bulk Power System Phasor Measurement Units (PMUs): The proliferation of PMU coverage over the past 5-10 years has resulted in a wide-area coverage of PMUs across each of the North American interconnections. PMUs report voltage and current phasors and frequency at rates of generally samples per second. This would enable a wider range of frequencies to be considered and analyzed. PMU data will be used on a very selective basis for analyzing key events of interest meeting the requirements laid out below. Events will be judiciously 1 selected by the NERC SMS based on a technically justified set of criteria for analyzing inter-area oscillatory modes or other oscillatory anomalies on the system. The events of interest to the SMS for these purposes will include: 1. Underfrequency events where all or most of the generators within the interconnection are perturbed by the event. Generally, the following low frequency deviation thresholds will be used (although subject to change): a. Eastern Interconnection: Hz b. Western Interconnection: Hz c. ERCOT Interconnection: Hz d. Quebec Interconnection: Hz 1 The purpose of this data request is to gather data useful for performing analyses that improve the interconnection s understanding of oscillatory behavior. Therefore, not all events meeting the criteria outlined will be collected. It is expected that key events of interest meeting the criteria will be used to gather sufficient data to perform the analysis. 2

3 2. Wide-area forced oscillations 2 on the system that are impacting multiple Balancing Authority Areas. 3. Identification of poorly damped local or inter-area oscillations on the system that warrant further analysis using wide-area measurement data. Data will be requested for a given event. An event time will be provided in Universal Coordinated Time (UTC), and will likely include the local times as well for clarity (local Standard Time). In addition, the start and end time of data to be collected will be explicitly defined for clarity. The duration of data to be requested will loosely follow the guidelines set forth below: Large underfrequency events: 10 minutes pre-contingency data 15 minutes post-contingency data Forced oscillation events: Pre- forced oscillation data to capture normal grid dynamics (10 minutes) During and/or post- forced oscillation data to capture the event in question (15 minutes) Poorly damped oscillation events: 10 minutes pre-contingency data 15 minutes post-contingency data Data Collection Location Requirements All available 3 synchronized phasor measurement data should be provided that meets the following requirements: Time synchronization: The data must be time synchronized to UTC with expected accuracy within +/- 2 milliseconds. Voltage Phasors: Any one positive sequence bus voltage phasor (voltage magnitude and phase angle) at a bulk power system substation with nominal voltage greater than 230 kv. Frequency: Any one frequency signal (ideally derived from the voltage signal above) at a bulk power system substation with nominal voltage greater than 230 kv. Active and Reactive Power: Active (P) and reactive (Q) power measured at the high-side or low-side of the generator step-up transformer or single Point of Interconnection (POI) for each generating resource that meets either of the following criteria: 2 Forced oscillations are caused by an external input or driving force to the interconnected power system that results in abnormal or forced conditions. Examples include malfunctioning steam valve cycling, arc furnace dynamics, and other harmonics. Forced oscillations are typically undamped and persist until the malfunctioning device or condition is removed from the system. 3 There are no location requirements for this data request (i.e., data must be provided at identified locations). The location requirements only apply to currently installed synchrophasor monitoring locations to provide a wide-are view of the system. 3

4 Gross individual nameplate rating greater than or equal to 100 MVA. Gross individual nameplate rating greater than or equal to 300 MVA where the gross plant/facility aggregate nameplate rating is 1000 MVA. Aggregate nameplate rating greater than or equal to 100 MVA connected at a single Point of Interconnection (POI) to the bulk power system (i.e., variable energy facilities such as wind farms and solar PV plants). Data Collection Formatting Requirements For all submitted data, it should incorporate the following formatting and data quality requirements: Bus voltage magnitude should be reported in units of kv (i.e. 535 kv) Bus voltage phase angles should be reported in units of degrees (bounded by +/- 180 degrees), and should be the raw phase angle reported by the PMU (not a referenced phase angle difference) Frequency should be reported in units of Hertz (i.e Hz), with the highest resolution available (at least three trailing decimal places). Data should be submitted in COMTRADE (C37.111), revision C or later, or submitted in.csv format. Attachment A provides the file structure for a.csv file submission. C allows 4 different data types ASCII, 16-bit signed integer, 32-bit signed integer, and single precision floating point (32-bit). Single precision floating point is the preferred data format. C allows the.dat file to be split into multiple sections e.g. D000 through D999. It is advisable to keep the individual file sizes below a maximum of 50 MB. To take full advantage of information available in the synchrophasor data stream it is advisable to use the PSRC H8 Application of COMTRADE for Synchrophasor Data Schema for Phasor Data Using the COMTRADE File Standard5. Bad data or data drop out: At a minimum, any one of the C Status Word bits as non-zero is considered bad data. Any individual data point with bad or missing data should be reported as NAN in the submitted.csv file, formatted according to Attachment A. Data Request and Submission Requirements Data requests and submitted data will be completed within the following timeframes: Data requests for a particular event will be sent within 45 calendar days of the actual event. Requested data will be submitted within 45 calendar days of the data request. 4 IEEE. C IEEE Standard Common Format for Transient Data Exchange (COMTRADE) for Power Systems, Available:

5 Analytical Techniques Pre- and post-contingency PMU data will be used to estimate the modal properties of the dominant interarea modes in the system using ambient modal estimation methods. This includes an estimation of the mode frequency, mode damping ratio, mode energy, and mode shape for each of the dominant inter-area modes that can be observed in the PMU data. The analysis will provide insight on the presence and nature of the dominant system modes, and how they evolve over time. PMU data during system events will be used to analyze the dominant modal properties using ringdown analysis methods. Again, the modal properties of each mode including the mode frequency, mode damping ratio, mode energy, and mode shape will be estimated. These results will be compared with the respective estimations from ambient methods above for cross-validation. Depending on the nature and location of the disturbance, the ringdown analysis will provide information on which modes get excited by different contingencies. PMU data collected for the periods prior to and during forced oscillation events can be used to determine the source location and nature of forced oscillations. The conclusions will be reported to the utility providing the data for validation and verification. The names of specific generation facilities as well as participating utilities will be kept confidential and all the analysis results will be reported in an anonymous fashion. 5

6 Analysis Strategy & Process Phase 1: Characterization of Modal Characteristics Phase 1 is the primary focus of this work task of the SMS. The following process will be followed for accomplishing this task: 1. Events meeting the criteria defined herein will be considered by the SMS. 2. The SMS will select events for data collection as they occur and judiciously execute data requests to gather PMU data for those respective events. 3. Data will be provided by Reliability Coordinators (RC) and University of Tennessee-Knoxville (UTK) 6 within the appropriate timeframes as defined herein. 4. All submitted data will be kept confidential. 5. Tools and expertise will be utilized by those willing and able to participate. This will likely include engaging with commercial vendors and subject matter experts. Non-disclosure agreements (NDAs) between each party supporting the special assessment and NERC will be put in place to ensure data is kept confidential and secure. 6. Collected data will be used for determining the modal characteristics of the interconnection. 7. Through this process, tools and analyses will be compared with each other to identify 1) modal characteristics and other attributes, and 2) considerations for improvement for the tools used. 8. Results will be explored by the SMS members as a whole; actual data will only be provided to the sub-team of analysis members who have signed appropriate NDAs. 9. Results will be published in a manner that only provides modal characteristic behavior of the bulk power system. Actual data and entities will be kept completely anonymous. The data will provide characteristic behavior only. 10. If anomalous data or other data of interest (i.e., forced oscillation events) NERC will work with the effected entities to explore identification of those oscillations for the purposes of improving reliability. Phase 2: Integrated Utilization and Further Development of Modal Analysis Tools Phase 2 is the expansion of this work, once modal characteristics have been identified, and is not the primary focus of this work task. Phase 2 is a longer-term vision in which this type of analysis can become a regular business practice for NERC and other operating entities. This includes: Comparison of tool performance, after initial utilization, to identify areas for improved results, usability, visualization, automation, etc. 6 UTK is not subject to comply with the 45 submittal. However, NERC will collaborate with UTK to get necessary data for select events in a timely manner. 6

7 Automate the identification of system modal characteristics using tools selected. Automatically detect anomalous oscillations (forced and inter-area) such that preemptive situational awareness can be achieved. Deliverables The following deliverables will be provided throughout the task: Analytical results on modal analysis using ambient data, ringdown analysis, and/or forced oscillation analysis; Description(s) of modal analysis techniques used to analyze interconnection-wide or regional oscillations; Characterization of inter-area modes in each interconnection analyzed; and A periodic report culminating in a description of the modal characteristics of the interconnection(s). 7

8 Attachment A -.CSV File Submission Formatting The.csv file will follow the Guideline for Data Format Used in Engineering Analysis Applications of Disturbance and Simulated Data 7. This simplified.csv (comma separated value) file structure effectively accommodates the extraction and compilation of synchrophasor data for disturbance analysis. Headers Lines The simplified header structure consists of four (4) header rows, as shown in Figure 1. The simplified requirements for these header rows are described here: Line 1: Signal Names Signal names should provide enough detail to discern the name of the substation or location where the measurement is located, as most PMU naming structures currently do. Signal names can contain any characters except commas. Special characters other than underscore ( _ ) should be avoided. Line 2: Signal Type Acceptable signal types include: Signal Type Voltage Magnitude Phase Angle Frequency Active Power Reactive Power Line 3: Units Acceptable units include: Signal Time Voltage Magnitude Phase Angle Frequency Active Power Reactive Power Line 4: Description Acceptable TYPE VM VA F P Q Acceptable UNITS SEC (Seconds) KV (Kilovolts) DEG (Degrees) HZ (Hertz) MW (Megawatts) MVAR (Megavars) Description of the signal can contain any alphanumerical values (except commas). The Description should clearly explain the signal and location of measurement. 7 WECC Joint Synchronized Information Subcommittee (JSIS). Guideline for Data Format Used in Engineering Analysis Applications of Disturbance and Simulated Data. August Salt Lake City, UT. Available: 8

9 The headers lines should be formatted to the following requirements: Cells A1:A3 will not change. Cell A4 should include the event start time, in UTC. See included.csv file data submission template. An example.csv file with dummy data is shown below. Figure 1: Sample.csv file format (opened in Microsoft Excel for clarity). Data Lines The data lines should be formatted to the following requirements: Times will monotonically increase, with no missing times (i.e., don t skip time stamps ). Times will be equally spaced, with 5 trailing decimal places (e.g., , , etc.). Frequency measurements should have at least 3 trailing decimal places; 5 trailing decimal places is preferable. 9

PRC Disturbance Monitoring and Reporting Requirements

PRC Disturbance Monitoring and Reporting Requirements Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed

More information

ReliabilityFirst Regional Criteria 1. Disturbance Monitoring and Reporting Criteria

ReliabilityFirst Regional Criteria 1. Disturbance Monitoring and Reporting Criteria ReliabilityFirst Regional Criteria 1 Disturbance Monitoring and Reporting Criteria 1 A ReliabilityFirst Board of Directors approved good utility practice document which are not reliability standards. ReliabilityFirst

More information

SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011

SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011 SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011 Baselining using large quantities of historical phasor data to identify and understand patterns in interconnection-wide grid behavior, to

More information

Use of Synchronized Phasor Measurements for Model Validation in ERCOT

Use of Synchronized Phasor Measurements for Model Validation in ERCOT Use of Synchronized Phasor Measurements for Model Validation in ERCOT NDR Sarma, Jian Chen, Prakash Shrestha, Shun-Hsien Huang, John Adams, Diran Obadina, Tim Mortensen and Bill Blevins Electricity Reliability

More information

Synchrophasor Technology PMU Use Case Examples

Synchrophasor Technology PMU Use Case Examples 1 IEEE Tutorial on Use of Synchrophasors in Grid Operations - Oscillation Source Detection and Operational Use of Synchrophasors Synchrophasor Technology PMU Use Case Examples Sarma (NDR) Nuthalapati,

More information

PRC Compliance Using Bitronics 70 Series Recorders

PRC Compliance Using Bitronics 70 Series Recorders PRC-002-2 Compliance Using Bitronics 70 Series Recorders Introduction The North American Electric Reliability Council (NERC) has defined standards for disturbance monitoring and reporting requirements

More information

generation greater than 75 MVA (gross aggregate nameplate rating) Generation in the ERCOT Interconnection with the following characteristics:

generation greater than 75 MVA (gross aggregate nameplate rating) Generation in the ERCOT Interconnection with the following characteristics: A. Introduction 1. Title: Verification of Models and Data for Turbine/Governor and Load Control or Active Power/Frequency Control Functions 2. Number: MOD-027-1 3. Purpose: To verify that the turbine/governor

More information

Sarma (NDR) Nuthalapati, PhD

Sarma (NDR) Nuthalapati, PhD SYNCHROPHASOR TECHNOLOGY PMU USE CASE EXAMPLES Sarma (NDR) Nuthalapati, PhD Research Scientist Texas A&M University, College Station, TX Control Room Solutions Task Team NASPI Work Group meeting and first

More information

Standard MOD Verification of Models and Data for Generator Excitation Control System or Plant Volt/Var Control Functions

Standard MOD Verification of Models and Data for Generator Excitation Control System or Plant Volt/Var Control Functions Standard MOD-026-1 Verification of Models and Data for Generator Excitation Control System or Plant Volt/Var Control Functions A. Introduction 1. Title: Verification of Models and Data for Generator Excitation

More information

1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report

1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report 1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report Rich Bauer Associate Director Reliability Risk Management / Event Analysis Mid C Seminar July 19, 2017 Western Interconnection

More information

Document C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting

Document C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting Document C-29 Procedures for System Modeling: January 5 th, 2016 TFSS Revisions Clean Open Process Posting Prepared by the SS-37 Working Group on Base Case Development for the Task Force on System Studies.

More information

Operationalizing Phasor Technology. Model Validation. Webinar. Ken Martin. March 4, Presented by. Page 0

Operationalizing Phasor Technology. Model Validation. Webinar. Ken Martin. March 4, Presented by. Page 0 Operationalizing Phasor Technology Model Validation Webinar March 4, 2014 Presented by Ken Martin Page 0 Model Use and Validation for Operations and Planning Compare System Performance with Model Prediction

More information

Update on the Creation of a Public Library of PMU Cases for Oscillatory Events

Update on the Creation of a Public Library of PMU Cases for Oscillatory Events 1 JSIS Meeting, May 17, 2018 Update on the Creation of a Public Library of PMU Cases for Oscillatory Events IEEE PES/PSDP/PSSC Task Force on Oscillation Source Location Slava Maslennikov ISO New England

More information

Real-time Monitoring of Power Oscillations and Modal Damping in the European ENTSO-E System

Real-time Monitoring of Power Oscillations and Modal Damping in the European ENTSO-E System Mats Larsson, ABB CRC Switzerland; Luis-Fabiano Santos, ABB SAS Switzerland; Galina Antonova, AB B SA Canada, Reynaldo Nuqui, ABB CRC USA NASPI meeting, February 20, 2013 Real-time Monitoring of Power

More information

Loss of Solar Resources during Transmission Disturbances due to Inverter Settings II

Loss of Solar Resources during Transmission Disturbances due to Inverter Settings II Loss of Solar Resources during Transmission Disturbances due to Inverter Settings II Informational Webinar on Level 2 NERC Alert Ryan Quint, Senior Manager, Advanced Analytics and Modeling Rich Bauer,

More information

1

1 Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive

More information

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 Purpose: To set load-responsive protective relays associated with generation Facilities at a level to prevent unnecessary tripping

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

GRID RELIABILITY MONITORING

GRID RELIABILITY MONITORING GRID RELIABILITY MONITORING Using Smart Grids WASS TM - A SynchroPhasor Technology based Real Time Wide Area Situational Awareness Software for Monitoring, Detection and Diagnosis of Power System Issues

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC A. Introduction 1. Title: Generator Frequency and Voltage Protective Relay Settings 2. Number: PRC-024-2 3. Purpose: Ensure Generator Owners set their generator protective relays such that generating units

More information

Synchronized Measurement Data for Frequency Response Analysis

Synchronized Measurement Data for Frequency Response Analysis Synchronized Measurement Data for Frequency Response Analysis Ryan D. Quint, North American Electric Reliability Corporation Pavel Etingov, Pacific Northwest National Laboratory Dao Zhou, University of

More information

Unit Auxiliary Transformer (UAT) Relay Loadability Report

Unit Auxiliary Transformer (UAT) Relay Loadability Report Background and Objective Reliability Standard, PRC 025 1 Generator Relay Loadability (standard), developed under NERC Project 2010 13.2 Phase 2 of Relay Loadability: Generation, was adopted by the NERC

More information

Use of Synchrophasors to Detect Control System and Circuit Breaker Reclosing Issues

Use of Synchrophasors to Detect Control System and Circuit Breaker Reclosing Issues Use of Synchrophasors to Detect Control System and Circuit Breaker Reclosing Issues Pramila Nirbhavane Senior Grid Operations Engineer September 26, 2017 Outline PMUs Locations in NYISO PMU Applications

More information

Bulk Electric System Definition Reference Document

Bulk Electric System Definition Reference Document Bulk Electric System Definition Reference Document Version 2 April 2014 This technical reference was created by the Definition of Bulk Electric System drafting team to assist entities in applying the definition.

More information

Uses of Synchrophasor BD NSF Workshop 2017

Uses of Synchrophasor BD NSF Workshop 2017 Uses of Synchrophasor BD NSF Workshop 2017 Bill Blevins Director Grid Coordination April 18,2017 2 ERCOT Control Room BD overview ERCOT 2001 ERCOT 2016 ERCOT PMU locations 76 PMUs at 35 locations 2014

More information

Definition of Bulk Electric System Phase 2

Definition of Bulk Electric System Phase 2 Definition of Bulk Electric System Phase 2 NERC Industry Webinar Peter Heidrich, FRCC, Standard Drafting Team Chair June 26, 2013 Topics Phase 2 - Definition of Bulk Electric System (BES) Project Order

More information

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 PRC-025-1 Generator Relay Loadability A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 Purpose: To set load-responsive protective relays associated with generation Facilities

More information

Bulk Electric System Definition Reference Document

Bulk Electric System Definition Reference Document Bulk Electric System Definition Reference Document JanuaryVersion 2 April 2014 This technical reference was created by the Definition of Bulk Electric System drafting team to assist entities in applying

More information

System Operating Limit Definition and Exceedance Clarification

System Operating Limit Definition and Exceedance Clarification System Operating Limit Definition and Exceedance Clarification The NERC-defined term System Operating Limit (SOL) is used extensively in the NERC Reliability Standards; however, there is much confusion

More information

Southern Company Interconnection Requirements for Inverter-Based Generation

Southern Company Interconnection Requirements for Inverter-Based Generation Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection

More information

Final ballot January BOT adoption February 2015

Final ballot January BOT adoption February 2015 Standard PRC-024-21(X) Generator Frequency and Voltage Protective Relay Settings Standard Development Timeline This section is maintained by the drafting team during the development of the standard and

More information

Standard MOD Verification of Models and Data for Generator Excitation Control Sys tem or Plant Volt/Var Control Functions

Standard MOD Verification of Models and Data for Generator Excitation Control Sys tem or Plant Volt/Var Control Functions Standard MOD-026-1 Verification of Models and Data for Generator Excitation Control Sys tem or Plant Volt/Var Control Functions Standard Development Roadmap This section is maintained by the drafting team

More information

Recent Progress on Forced Oscillation Detection and Source Locating Findings at Peak Reliability. NASPI Work Group Meeting

Recent Progress on Forced Oscillation Detection and Source Locating Findings at Peak Reliability. NASPI Work Group Meeting Recent Progress on Forced Oscillation Detection and Source Locating Findings at Peak Reliability NASPI Work Group Meeting Apr 25 2018 Jiawei Alex Ning, NetApps Engineer Hongming Zhang, NetApps Manager

More information

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction A. Introduction 1. Title: Generator Frequency and Voltage Protective Relay Settings 2. Number: PRC-024-1 3. Purpose: Ensure Generator Owners set their generator protective relays such that generating units

More information

Forced Oscillation Event Analysis

Forced Oscillation Event Analysis Forced Oscillation Event Analysis January 11, 2019 Event Ryan D. Quint, PhD, PE Senior Manager, Advanced System Analytics and Modeling, NERC February 2019 Background Oscillation observed across entire

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

SDG&E Transmission Synchrophasor Project Update

SDG&E Transmission Synchrophasor Project Update SDG&E Transmission Synchrophasor Project Update Joint Synchronized Information Subcommittee (JSIS) Meeting Tariq Rahman, May 22-25, 2017 2006 San Diego Gas & Electric Company. All copyright and trademark

More information

Transmission Interconnection Requirements for Inverter-Based Generation

Transmission Interconnection Requirements for Inverter-Based Generation Transmission Requirements for Inverter-Based Generation June 25, 2018 Page 1 Overview: Every generator interconnecting to the transmission system must adhere to all applicable Federal and State jurisdictional

More information

Alberta Electric System Operator (AESO) Oscillatory dynamics and corridor stress in the Alberta electric system

Alberta Electric System Operator (AESO) Oscillatory dynamics and corridor stress in the Alberta electric system Alberta Electric System Operator (AESO) Oscillatory dynamics and corridor stress in the Alberta electric system North American SynchroPhasor Initiative March 2015 Agenda Alberta Electrical System Overview

More information

Reliability Considerations for PPMV. Ryan Quint, NERC Dmitry Kosterev, BPA NASPI-NERC PPMV Tools Workshop October 2016

Reliability Considerations for PPMV. Ryan Quint, NERC Dmitry Kosterev, BPA NASPI-NERC PPMV Tools Workshop October 2016 Reliability Considerations for PPMV Ryan Quint, NERC Dmitry Kosterev, BPA NASPI-NERC PPMV Tools Workshop October 2016 MOD Standards Framework NERC MOD Standards Modeling, Data, and Analysis MOD-032 Data

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission

More information

Update on NERC Reliability Guideline: PMU Placement

Update on NERC Reliability Guideline: PMU Placement Update on NERC Reliability Guideline: PMU Placement Sarma (NDR) Nuthalapati, Ph.D., Principal Engineer, Grid Operations Support, ERCOT And Ryan D. Quint, Ph.D., P.E. Staff Coordinator, NERC SMS, SAMS SMS

More information

Generation and Load Interconnection Standard

Generation and Load Interconnection Standard Generation and Load Interconnection Standard Rev. 0 DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5

More information

Recently, the SS38 Working Group on Inter-Area Dynamic Analysis completed two study reports on behalf of the UFLS Regional Standard Drafting Team.

Recently, the SS38 Working Group on Inter-Area Dynamic Analysis completed two study reports on behalf of the UFLS Regional Standard Drafting Team. December 7 th, 2010 NPCC Full Member Committee; Please find attached a draft revised NPCC Regional Reliability Directory #12 Underfrequency Load Shedding Program Requirements and a draft revised NPCC UFLS

More information

Testing and Implementation of a Source Locating method at ISO New England

Testing and Implementation of a Source Locating method at ISO New England 1 Testing and Implementation of a Source Locating method at ISO New England Slava Maslennikov Principal Analyst Business Architecture and Technology Department ISO New England smaslennikov@iso-ne.com 2

More information

ROSE - Real Time Analysis Tool for Enhanced Situational Awareness

ROSE - Real Time Analysis Tool for Enhanced Situational Awareness ROSE - Real Time Analysis Tool for Enhanced Situational Awareness Marianna Vaiman V&R Energy Copyright 1997-2013 V&R Energy Systems Research, Inc. All rights reserved. WECC JSIS Salt Lake City, UT October

More information

Harmonizing the Changing Resource Mix Keeping the Grid Together

Harmonizing the Changing Resource Mix Keeping the Grid Together Harmonizing the Changing Resource Mix Keeping the Grid Together Robert W. Cummings Senior Director of Engineering and Reliability Initiatives i-pcgrid March 30, 2017 NERC-IEEE Memorandum of Understanding

More information

Measurement tools at heart of Smart Grid need calibration to ensure reliability

Measurement tools at heart of Smart Grid need calibration to ensure reliability Measurement tools at heart of Smart Grid need calibration to ensure reliability Smart grid; PMU calibration position 1 The North American interconnections, or electric transmission grids, operate as a

More information

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link. Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link. Mr.S.B.Dandawate*, Mrs.S.L.Shaikh** *,**(Department of Electrical Engineering, Walchand College of

More information

Lessons Learned in Model Validation for NERC Compliance

Lessons Learned in Model Validation for NERC Compliance Lessons Learned in Model Validation for NERC Compliance usa.siemens.com/digitalgrid NERC Modeling, Data, and Analysis MOD 025 2: Generator Real and Reactive Power Capability Demonstration MOD 026 1: Verification

More information

Standard PRC Coordination of Generating Unit or Plant Capabilities, Voltage Regulating Controls, and Protection

Standard PRC Coordination of Generating Unit or Plant Capabilities, Voltage Regulating Controls, and Protection A. Introduction 1. Title: Coordination of Generating Unit or Plant Capabilities, Voltage Regulating Controls, and Protection 2. Number: PRC-019-2 3. Purpose: To verify coordination of generating unit Facility

More information

Final ballot January BOT adoption February 2015

Final ballot January BOT adoption February 2015 Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed

More information

VAR Voltage and Reactive Control

VAR Voltage and Reactive Control VAR-001-4 Voltage and Reactive Control A. Introduction 1. Title: Voltage and Reactive Control 2. Number: VAR-001-4 3. Purpose: To ensure that voltage levels, reactive flows, and reactive resources are

More information

A. Introduction. VAR Voltage and Reactive Control

A. Introduction. VAR Voltage and Reactive Control A. Introduction 1. Title: Voltage and Reactive Control 2. Number: VAR-001-4.2 3. Purpose: To ensure that voltage levels, reactive flows, and reactive resources are monitored, controlled, and maintained

More information

VAR Voltage and Reactive Control. A. Introduction

VAR Voltage and Reactive Control. A. Introduction VAR-001-5 Voltage and Reactive Control A. Introduction 1. Title: Voltage and Reactive Control 2. Number: VAR-001-5 3. Purpose: To ensure that voltage levels, reactive flows, and reactive resources are

More information

At generating sites with 1200MW or greater of installed generating capacity.

At generating sites with 1200MW or greater of installed generating capacity. A. Introduction 1. 2. Number: 3. Purpose: To provide FRCC requirements for installation of Disturbance Monitoring Equipment (DME) and reporting of Disturbance data to facilitate analyses of events and

More information

Interconnection Oscillation Analysis

Interconnection Oscillation Analysis Interconnection Oscillation Analysis Reliability Assessment November 2018 NERC Report Title Report Date I Table of Contents Preface... iv Executive Summary... v Conclusions and Findings... v Recommendations...

More information

Bulk Electric System Definition Reference Document

Bulk Electric System Definition Reference Document Bulk Electric System Definition Reference Document January, 2014 This draft reference document is posted for stakeholder comments prior to being finalized to support implementation of the Phase 2 Bulk

More information

Testing model data usability Excitation Systems PSS Limiters

Testing model data usability Excitation Systems PSS Limiters 1 2016 IEEE/PES General Meeting July 17 th -21 st, 2016 Boston, MA Panel Session Use of the New Revisions of IEEE Std. 421.2 and 421.5 to Satisfy International Grid Code Requirements Testing model data

More information

Post-Event Analysis of a Compound Event in the ERCOT System Using Synchrophasor Data

Post-Event Analysis of a Compound Event in the ERCOT System Using Synchrophasor Data 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium Post-Event Analysis of a Compound Event in the ERCOT System Using Synchrophasor Data

More information

Use of the Power System Outlook (PSO) and SMART 1 Programs to View PSLF Dynamic Simulation Data Files

Use of the Power System Outlook (PSO) and SMART 1 Programs to View PSLF Dynamic Simulation Data Files 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium Use of the Power System Outlook (PSO) and SMART 1 Programs to View PSLF Dynamic Simulation

More information

Task Force on Synchrophasor Protection Applications NASPI Engineering Analysis Task Team Matthew Rhodes 3/22/16

Task Force on Synchrophasor Protection Applications NASPI Engineering Analysis Task Team Matthew Rhodes 3/22/16 NASPI White Paper: Integrating Synchrophasor Technology into Power System Protection Applications Update Report Task Force on Synchrophasor Protection Applications NASPI Engineering Analysis Task Team

More information

NPCC Regional Reliability Reference Directory # 12. Underfrequency Load Shedding Program Requirements

NPCC Regional Reliability Reference Directory # 12. Underfrequency Load Shedding Program Requirements NPCC Regional Reliability Reference Directory # 12 Under frequency Load Shedding Program Requirements Task Force on System Studies Revision Review Record: June 26 th, 2009 March 3 rd, 2010 Adopted by the

More information

Inverter-Based Resource Disturbance Analysis

Inverter-Based Resource Disturbance Analysis Inverter-Based Resource Disturbance Analysis Key Findings and Recommendations Informational Webinar February 15, 2018 August 16, 2016 Blue Cut Fire Disturbance Key Findings and Recommendations 2 Western

More information

Wide-Area Measurements to Improve System Models and System Operation

Wide-Area Measurements to Improve System Models and System Operation Wide-Area Measurements to Improve System Models and System Operation G. Zweigle, R. Moxley, B. Flerchinger, and J. Needs Schweitzer Engineering Laboratories, Inc. Presented at the 11th International Conference

More information

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements Section 502.8 SCADA Technical and Operating Requirements Applicability 1 Subject to subsections 2 and 3 below, section 502.8 applies to: (a) (c) (d) the legal owner of a generating unit or an aggregated

More information

Synchrophasor Solutions Deployment at PG&E Off-Line Analysis

Synchrophasor Solutions Deployment at PG&E Off-Line Analysis Synchrophasor Solutions Deployment at PG&E Off-Line Analysis Vahid Madani - PG&E Manu Parashar - ALSTOM Grid October 24, 2013 Outline Offline Engineering Applications at PG&E Post Event Analysis (May 30

More information

Wind Power Facility Technical Requirements CHANGE HISTORY

Wind Power Facility Technical Requirements CHANGE HISTORY CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical

More information

Industry Webinar. Reactive Power Planning. NERC System Analysis and Modeling Subcommittee (SAMS) March 2017

Industry Webinar. Reactive Power Planning. NERC System Analysis and Modeling Subcommittee (SAMS) March 2017 Industry Webinar Reactive Power Planning NERC System Analysis and Modeling Subcommittee (SAMS) March 2017 Webinar Topics Reliability Guideline on Reactive Power Planning Webinar Topics Fundamentals of

More information

Online Oscillation Management at ISO New England

Online Oscillation Management at ISO New England NASPI. SEPTEMBER 27,2017 Online Oscillation Management at ISO New England SLAVA MASLENNIKOV XIAOCHUAN LUO FRANKIE ZHANG IZUDIN LELIC EUGENE LITVINOV PMU Infrastructure at ISO New England Installed in 2012

More information

Robert W. Cummings - NERC Director of System Analysis and Reliability Initiatives William Herbsleb - Chairman of Frequency Response Standard Drafting

Robert W. Cummings - NERC Director of System Analysis and Reliability Initiatives William Herbsleb - Chairman of Frequency Response Standard Drafting Generator Governor and Information Settings Webinar Robert W. Cummings - NERC Director of System Analysis and Reliability Initiatives William Herbsleb - Chairman of Frequency Response Standard Drafting

More information

Real Time Stability Analysis at Peak Reliability. Slaven Kincic, Hongming Zhang JSIS May 2017, SLC

Real Time Stability Analysis at Peak Reliability. Slaven Kincic, Hongming Zhang JSIS May 2017, SLC Real Time Stability Analysis at Peak Reliability Slaven Kincic, Hongming Zhang JSIS May 2017, SLC Overview: Overview of Peak s DSA Application; o Set up o User Cases Transient Stability Criteria; TSAT

More information

CAISO Restricted - Do Not Distribute Outside of RC Project LOI and NDA Entities Page 1 of 24

CAISO Restricted - Do Not Distribute Outside of RC Project LOI and NDA Entities Page 1 of 24 RC0120A - RC IRO-010 Data Specification NOTE: Changes from Peak's Attachment A are highlighted in red in columns C through G Section Category Number Responsible Pa Data Item Data Transfer Method 1.1 Transmission

More information

Fault Induced Delayed Voltage Recovery (FIDVR) Advisory

Fault Induced Delayed Voltage Recovery (FIDVR) Advisory Fault Induced Delayed Voltage Recovery (FIDVR) Advisory NERC Synchronized Measurement Subcommittee (SMS) NASPI Engineering Analysis Task Team (EATT) July 2015 Why the Advisory? The goal of this advisory

More information

How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements

How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements Robert Nelson Senior Expert Engineering Manager and Manager of Codes, Standards, and Regulations Siemens Wind Turbines -

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements Section 502.8 SCADA Technical and Operating Applicability 1 Section 502.8 applies to: (a) the legal owner of a generating unit: (i) connected to the transmission facilities in the balancing authority area

More information

(Circuits Subject to Requirements R1 R5) Generator Owner with load-responsive phase protection systems as described in

(Circuits Subject to Requirements R1 R5) Generator Owner with load-responsive phase protection systems as described in A. Introduction 1. Title: Transmission Relay Loadability 2. Number: PRC-023-3 3. Purpose: Protective relay settings shall not limit transmission loadability; not interfere with system operators ability

More information

Events Captured and Findings To Date. John Ballance and Abhijeet Agarwal EPG John Adams and Jian Chen ERCOT

Events Captured and Findings To Date. John Ballance and Abhijeet Agarwal EPG John Adams and Jian Chen ERCOT Discovery Across Texas: Technology Solutions for Wind Integration in ERCOT Using Synchrophasor Technology for Wind Integration and Event Monitoring in ERCOT Events Captured and Findings To Date John Ballance

More information

Generation and Load Interconnection Standard

Generation and Load Interconnection Standard Generation and Load Interconnection Standard Rev. 0A DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5

More information

WECC Data Preparation Manual

WECC Data Preparation Manual WECC Data Preparation Manual for Interconnection-wide Cases Applicable to the 2017 Base Case Compilation Schedule System Review Work Group Technical Studies Subcommittee 155 North 400 West, Suite 200 Salt

More information

Test Cases Library and Real-life Oscillation Examples

Test Cases Library and Real-life Oscillation Examples Test Cases Library and Real-life Oscillation Examples Kai Sun 1, Bin Wang 2, Slava Maslennikov 3 1- University of Tennessee, 2- Texas A&M University, 3- ISO New England Paper No. 18PESGM0563 2018 IEEE

More information

Operationalizing Phasor Technology

Operationalizing Phasor Technology ELECTRIC POWER GROUP WEBINAR SERIES Operationalizing Phasor Technology Operationalizing Phasor Technology System Events Deciphering the Heartbeat of the Power Grid July 16, 2013 Webinar John W. Ballance

More information

Synchrophasors and the Smarter Grid

Synchrophasors and the Smarter Grid Synchrophasors and the Smarter Grid Synchrophasor A synchrophasor is a phasor measurement with respect to an absolute time reference. With this measurement we can determine the absolute phase relationship

More information

Endorsed Assignments from ERS Framework

Endorsed Assignments from ERS Framework ERSTF Completion Endorsed Assignments from ERS Framework Ref Number Title ERS Recommendatio n Ongoing Responsibility 1 Synch Inertia at Interconnection Level Measure 2 Initial Frequency Deviation Measure

More information

Standard PRC Coordination of Generating Unit or Plant Voltage Regulating Controls with Generating Unit or Plant Capabilities and Protection

Standard PRC Coordination of Generating Unit or Plant Voltage Regulating Controls with Generating Unit or Plant Capabilities and Protection Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed:

More information

Experiences of Using Synchrophasors at Duke Energy

Experiences of Using Synchrophasors at Duke Energy 1 Experiences of Using Synchrophasors at Duke Energy Tim Bradberry, Megan Vutsinas, Kat Sico Duke Energy IEEE PES Tutorial July 19 th, 2016 Duke Energy s Phasor Plans Carolinas West Currently have 125

More information

Mining Phasor Data To Find The Hidden Gems In Your Archive

Mining Phasor Data To Find The Hidden Gems In Your Archive Electric Power Group Presents Phasor Data Mining Application PDMA Mining Phasor Data To Find The Hidden Gems In Your Archive October 16, 2014 Presented by Vivek Bhaman & Frank Carrera Webinar Phone Number:

More information

Reliability Guideline

Reliability Guideline Reliability Guideline Power Plant Model Verification and Testing for Synchronous Machines December 2017 DRAFT NERC Report Title Report Date i Table of Contents Preface... iv Preamble... v Executive Summary...

More information

Synchrophasors: Definition, Measurement, and Application

Synchrophasors: Definition, Measurement, and Application 1. Abstract Synchrophasors: Definition, Measurement, and Application Mark Adamiak GE Multilin King of Prussia, PA William Premerlani GE Global Research Niskayuna, NY Dr. Bogdan Kasztenny GE Multilin Markham,

More information

Wide Area Monitoring with Phasor Measurement Data

Wide Area Monitoring with Phasor Measurement Data Wide Area Monitoring with Phasor Measurement Data Dr. Markus Wache Siemens E D EA, Nuremberg, Germany Content Content Basics of Phasor Measurement Realization of PMUs Power System Stability Standard IEEE

More information

Automated Event Analysis Tool using Synchrophasor Data in Indian Grid

Automated Event Analysis Tool using Synchrophasor Data in Indian Grid Automated Event Analysis Tool using Synchrophasor Data in Indian Grid NASPI Work Group Meeting March 2015 Rajkumar Anumasula Power System Operation Corporation Ltd. India Some Typical Numbers of Indian

More information

Standard PRC Coordination of Generating Unit or Plant Capabilities, Voltage Regulating Controls, and Protection

Standard PRC Coordination of Generating Unit or Plant Capabilities, Voltage Regulating Controls, and Protection Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed:

More information

An Introduction to Completing a NERC PRC-019 Study for Traditional and Distributed Generation Sources

An Introduction to Completing a NERC PRC-019 Study for Traditional and Distributed Generation Sources An Introduction to Completing a NERC PRC-019 Study for Traditional and Distributed Generation Sources Matthew Manley and Tony Limon POWER Engineers, Inc. Abstract -- NERC PRC standards have been implemented

More information

NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1

NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 Charles J. Mozina, Consultant Beckwith Electric Co., Inc. www.beckwithelectric.com I. Introduction During the 2003 blackout,

More information

Voltage and Reactive Procedures CMP-VAR-01

Voltage and Reactive Procedures CMP-VAR-01 Voltage and Reactive Procedures CMP-VAR-01 NERC Standards: VAR-001-2 VAR-002-1.1b Effective Date: 07/31/2012 Document Information Current Revision 2.0 Review Cycle Annual Subject to External Audit? Yes

More information

Evaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit

Evaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit Electrical Power and Energy Conference 2012 Resilient Green Energy Systems for a Sustainable Society Evaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit Dinesh

More information

Synchrophasor Technology at BPA: from Wide-Area Monitoring to Wide-Area Control

Synchrophasor Technology at BPA: from Wide-Area Monitoring to Wide-Area Control Synchrophasor Technology at BPA: from Wide-Area Monitoring to Wide-Area Control Presented by Jeff Dagle (PNNL) on behalf of BPA October 24, 2018 1 History of Synchrophasors at BPA BPA was one of the early

More information

LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS

LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS Giuseppe Di Marzio NTNU giuseppe.di.marzio@elkraft.ntnu.no Olav B. Fosso NTNU olav.fosso@elkraft.ntnu.no Kjetil Uhlen SINTEF

More information