ADDENDUM NO. TWO To the Plans and Specifications for: PALM COAST READINESS CENTER PALM COAST, FL For FLORIDA DEPT. OF MILITARY AFFAIRS Prepared By: ARCHITECT Bhide & Hall Architects, P.A. 1329-C Kingsley Ave. Orange Park, FL 32073 Certificate No. AAC000569 Date: June 28, 2016 Index: Number Discipline Topic 1 Non-Technical RFI #001 Reply 2 Architectural Architectural drawing revisions Attachment A 3 Civil Civil Engineering drawing revisions Attachment B 4 Structural Structural Engineering drawing revisions Attachment C 5 Mechanical Mechanical Engineering drawing revisions Attachment D 6 Fire Protection Fire Protection Engineering drawing revisions Attachment E 7 Electrical Electrical Engineering drawing revisions Attachment F 8 Technology Technology Engineering drawing revisions Attachment G 9 Specifications Specification Section 07 84 00, Firestopping added 10 Specifications Specification Section 33 32 19, City of Palm Coast Standard Pump Station added 11 Specifications Multiple Electrical specification sections modified. 12 Specifications Specification Section 27 00 10 revised. 13 Specifications Specification Section 27 05 00 revised. 10 ITEMS TOTAL Item No. 1, RFI #001 reply. Responses to RFI #001 submitted by Bidders is attached. Question: What are the sizes of the utility pipes, what is the method of insulation, what is the method of excavation depth? Answer: The sizes of the utility pipes are in question are specified on the Civil Engineering drawings. The means and methods for the installation of these utilities shall be determined by the Contractor. Page 1 of 3
Item No. 2, Architectural drawing revisions Attachment A See attached revised architectural drawings and Revision Summary (Attachment A ) for modifications and/or clarifications to select drawings. Item No. 3, Civil Engineering drawing revisions Attachment B See attached revised civil engineering drawings and Revision Summary (Attachment B ) for modifications and/or clarifications to select drawings. Item No. 4, Structural Engineering drawing revisions Attachment C See attached revised structural engineering drawings and Revision Summary (Attachment C ) for modifications and/or clarifications to select drawings. Item No. 5, Mechanical Engineering drawing revisions Attachment D See attached revised mechanical engineering drawings and Revision Summary (Attachment D ) for modifications and/or clarifications to select drawings. Item No. 6, Fire Protection Engineering drawing revisions Attachment E See attached revised fire protection engineering drawings and Revision Summary (Attachment E ) for modifications and/or clarifications to select drawings. Item No. 7, Electrical Engineering drawing revisions Attachment F See attached revised electrical engineering drawings and Revision Summary (Attachment F ) for modifications and/or clarifications to select drawings. Item No. 8, Technology Engineering drawing revisions Attachment G See attached revised electrical engineering drawings and Revision Summary (Attachment G ) for modifications and/or clarifications to select drawings. Item No. 9, Specification Section 07 84 00, Firestopping added. Specification Section 07 84 00, Firestopping has been added to the specifications. The added Section is attached herewith. Item No. 10, Specification Section 33 32 19, City of Palm Coast Standard Pump Station added. Specification Section 33 32 19, City of Palm Coast Standard Pump Station has been added to the specifications to provide additional information regarding the Sanitary Sewer Lift Station included as part of Section 01 97 20, Allowances. The added Section is attached herewith. Item No. 11, Multiple electrical specification sections modified. The following electrical specification sections have been modified to correct and/or deleted erroneous specification section references: Section 26 05 19, Section 26 05 26, Section 26 24 13, Section 26 24 16, Section 26 28 13, Section 26 29 23, Section 26 32 13 and Section 26 36 00. The revised Sections are attached herewith. Page 2 of 3
Item No. 12, Specification Section 27 00 10, General Technology Provisions revised. Specification Section 27 00 10, General Technology Provisions has been revised to accommodate the G6 standards required by FLARNG. The revised Section is attached herewith. Item No. 13, Specification Section 27 05 00, Structured Cabling revised. Specification Section 27 05 00, Structured Cabling has been adjusted to change the cabling standard. END OF ADDENDUM NO. TWO Page 3 of 3
ADDENDUM NO. TWO Attachment A Architectural Drawing Revision Summary: G0.1 1. Revised and updated list of drawings for Mechanical, Electrical and Technology (Vol 2) disciplines to match sheets contained within the Volume 2 set of drawings. 1LS1 1. Symbol and notation for Type K fire extinguisher added to Life Safety Legend. 2. Removed northern fire alarm annunciator panel from Room 100, Lobby. A1.1 1. Gate access control keypad has been relocated to north side of roadway. 2. Dumpster enclosure size increased to allow for two dumpsters 3. Loading ramp on east side of property moved to west approximately 10 feet 4. Asphalt apron at loading ramp increased approximately 10 feet to the north 5. 12 foot wide asphalt driveway added at LP tank enclosure A1.2 1. Notation for gate latch and keeper hardware added to elevation of dumpster enclosure on Detail 9. 2. Elevation of dumpster enclosure on Detail 9 updated to match plan 3. Dumpster enclosure shown on Detail 8 enlarged to accommodate two dumpsters. A1.3 1. Detail 4 added to sheet to provide scope of work for gate access control keypad. 2. Proposed location of gate access control keypad has been added to gate plan located on this sheet. 1A2.3 1. Door 126A removed from the project. 2. Fire extinguisher cabinet located at door 136A has been relocated to the adjacent Corridor 5 (Room 134) wall. 3. Door 186B has been renumbered to Door 186A. 1A2.4 1. Exterior door 145B has been renumbered to door 145A. 1A2.5 1. Addition information added to steel columns at Room 137, Gear Lockers. 1A2.7 1. Door 186C has been renumbered to Door 186B. 1A2.8 1. Door 250A added to Room 250, Electrical 3. 1A3.1 1. Detail 2/Sheet 1A3.2 callout added to Elevation 1. 1A5.2 1. Elevation notation on Section 7 changed from SECOND FLOOR to TOP OF VAULT. 1A5.4 1. Pipe bollard and wall finish information added to Section 2. 1A6.1 1. Additional information included at Details 1 and 5 regarding extents of wall and valley flashing/underlayment. 2. Detail 5 in bottom right corner of drawing renumbered to Detail 6. 1A7.1 1. Additional dimensions included at ceiling dome in Room 101, Lobby. 2. Motorized projection screens added to Room 121. 1A7.2 1. Motorized projection screens added to Rooms 177 and 179. Page 1 of 2 1329-C Kingsley Avenue Orange Park Florida 32073
1A7.4 1. Decorative star medallion removed from Detail 5. 2. Additional dimensions included at ceiling Details 1 and 2. 1A7.5 1. Motorized projection screens added to Rooms 203, 226, 227, and 106 (Assembly Hall). 2. Adjusted location of Room 220 room number for clarity. 3. Decorative star medallions removed (16 locations) from ceiling of Room 106, Assembly Hall. 1A7.6 1. Motorized projection screens added to Rooms 235, 238, and 258. 1A11.1 1. Door 126A eliminated from Door Schedule. 2. Door 168B renamed to Door 168A. 3. Finish of doors and frames for Doors 149A, 153A, and 157A have been changed from P, paint to FF, factory finish to match specifications. 1A11.2 1. Door 250A added to Door Schedule. 1A13.4 1. Added Type V designation to Detail 1 drawing title. 3A2.1 1. Additional dimensions included regarding distance between Unheated Storage Building and Loading Ramp shown on plan. END OF ADDENDUM NO. TWO ATTACHMENT A Page 2 of 2 1329-C Kingsley Avenue Orange Park Florida 32073
ADDENDUM NO. TWO Attachment B Civil Engineering Drawing Revision Summary: C2.0 1. Loading ramp on east side of property moved to west approximately 10 feet. 2. Asphalt apron at loading ramp increased approximately 10 feet to the north. 3. Addition dimensions added to loading ramp area. 4. 12 foot wide asphalt driveway added at LP tank enclosure. 5. Concrete equipment pad added at southwest corner of Maintenance Building for electrical transformer. C4.0 1. Loading ramp on east side of property moved to west approximately 10 feet. 2. Asphalt apron at loading ramp increased approximately 10 feet to the north. C5.0 1. Additional notation regarding sanitary sewer lift station scope of work added for clarity. 2. Location of water service entering Readiness Center has been moved slightly east to avoid conflict with fire protection water line in the affected area. END OF ADDENDUM NO. TWO ATTACHMENT B Page 1 of 1
ADDENDUM NO. TWO Attachment C Structural Engineering Drawing Revision Summary: 1S1.1A 1S1.1B 1S1.1C 1S1.1D 1S1.2A 1S1.2B 1. Add section cut 10/S3.8 near column grid A.6-4. 2. Add Plan Note 21, Refer to Sheet S3.3 for Contractor Selected options for pipes crossing footings. 3. Delete door 126A into Women Shower room. 1. Add section cut 10/S3.8 near column grid F-3. 2. Add Plan Note 21, Refer to Sheet S3.3 for Contractor Selected options for pipes crossing footings. 1. Add Plan Note 21, Refer to Sheet S3.3 for Contractor Selected options for pipes crossing footings. 1. Add Plan Note 21, Refer to Sheet S3.3 for Contractor Selected options for pipes crossing footings. 1. Add section cut 10/S3.8 near column grid A.6-4. 1. Add section cut 10/S3.8 near column grid F-3. 2. Add door to Electrical room neat column grid F-3. 2S1.1 1. Add Plan Note 8, Refer to Sheet S3.3 for Contractor Selected options for pipes crossing footings. END OF ADDENDUM NO. TWO ATTACHMENT C Page 1 of 1
ADDENDUM NO. TWO Attachment D Mechanical Engineering Drawing Revision Summary: M0.3 1. Revised VTU notes to indicate all 24V control power to the boxes from the transformers are by the controls contractor. M1.1 1. Added clearance dimensions for the chiller yard. M2.1 1. Added notes to clarify where ducts route into the attic space. M2.2 1. Added notes to clarify where ducts route into the attic space. M2.3 1. Relocate fan coil FCU-1S-1 to be located above the door. 2. Added note that all dampers are to be 24V and all 24V control power will be provided by the controls contractor. M2.5 1. Rerouted ductwork through the attic space. Clarified ducts located in the attic. M2.6 1. Rerouted ductwork through the attic space. Clarified ducts located in the attic. M2.7 1. Provided sizes for the VRF piping. M2.8 1. Provided sizes for the VRF piping. M2.9 1. Provided sizes for the VRF piping. M2.10 1. Provided sizes for the VRF piping. M2.11 1. Provided sizes for the VRF piping. M2.12 1. Provided sizes for the VRF piping. M2.14 1. Located AHU-2M above door. M3.1 1. Provided clarification for ductwork routed through the attic. M3.2 1. Provided clarification for ductwork routed through the attic. M3.4 1. Duct/structural coordination. M4.3 1. Boiler Detail added showing housekeeping pad. END OF ADDENDUM NO. TWO ATTACHMENT D Page 1 of 1
ADDENDUM NO. TWO Attachment E Fire Protection Engineering Drawing Revision Summary: F2.1 1. Added ansul system scope for second kitchen hood. END OF ADDENDUM NO. TWO ATTACHMENT E Page 1 of 1
ADDENDUM NO. TWO Attachment F Electrical Engineering Drawing Revision Summary: E1.1 1. Relocated irrigation pump and the controller. 2. Revised site lighting circuit. E2.1 1. All homerun circuit designations were revised to provide more appropriate breaker layout in panels. E2.2 1. All homerun circuit designations were revised to provide more appropriate breaker layout in panels. E2.3 1. All homerun circuit designations were revised to provide more appropriate breaker layout in panels. E2.4 1. All homerun circuit designations were revised to provide more appropriate breaker layout in panels. E2.5 1. All homerun circuit designations were revised to provide more appropriate breaker layout in panels. E2.6 1. All homerun circuit designations were revised to provide more appropriate breaker layout in panels. E2.9 1. Revised circuits for kitchen equipment. Revised circuit for coffee urn to match cutsheet. E2.10 1. Added note for coordination location water proof disconnect in elevator pit. E3.1 1. Revised and added general lighting notes. E3.2 1. Revised and added general lighting notes. 2. Correct lighting circuiting E3.3 1. Revised and added general lighting notes. 2. Relocated lighting relays E3.4 1. Revised and added general lighting notes. E3.5 1. Revised and added general lighting notes. E3.6 1. Revised and added general lighting notes. E4.1 1. Relocated fire alarm speakers E4.2 1. Relocated fire alarm speakers E4.3 1. Relocated fire alarm speakers E4.5 1. Relocated fire alarm speakers E4.6 1. Relocated fire alarm speakers E5.4 1. Panel changes per plan circuiting revisions. E5.5 1. Panel changes per plan circuiting revisions. E5.6 1. Panel changes per plan circuiting revisions. Page 1 of 2
Sheet Revision E5.7 1. Panel changes per plan circuiting revisions. E5.8 1. Panel changes per plan circuiting revisions. E5.9 1. Panel changes per plan circuiting revisions. E5.10 1. Panel changes per plan circuiting revisions. END OF ADDENDUM NO. TWO ATTACHMENT F Page 2 of 2
ADDENDUM NO. TWO Attachment G Technology Engineering Drawing Revision Summary: T2.2 1. Vault cable tray segments have been reduced due to a comment from owner. Note added to Technology symbol legend to refer to technology specifications for the guards G6 standard.2. T2.5 1. Vault cable tray segments have been reduced due to a comment from owner. Note added to Technology symbol legend to refer to technology specifications for the guards G6 standard. END OF ADDENDUM NO. TWO ATTACHMENT G Page 1 of 1