Embedded autmatin equipment (Shanghai) Limited Rm 305. Twer B.NO.18Talin rad Pudng District, Shanghai Phne: +86-21-51090839/50750355, fax: +86-21-50758598, e-mail: sales@stammkn.cm Universal input/utput cntrller Universal 8 channel input/utput device is the nly prduct n the market with pssibility t switch each channel frm input t utput therefre making the device extremely flexible. It makes life fr installers and system designers mre accurate and headache-free. ENG - Data sheet Issue date 10.10.2013 Applicatin Lighting, lad cntrl, security Each f 8 prts can be used as: - Analg input 0-30V - Binary input 0/30 V - Impulse cunter - Shrt/lng press key - Step dimmer - Open cllectr utput e.g. fr external relay mdule cnnectin Types f prduct Universal 8 channel IO mdule UIO82M Standards and nrms cmpliance EMC: PCT EN61000-6-1 EN61000-6-3 Certificate Technical data: Pwer supply: Pwer cnsummatin: 0.25W 29V DC frm KNX/EIB bus Interface: KNX/EIB 1 Input/utput channels 8
Inputs Cunt up t 8 Type Analg input 0-30V Binary input 0/30 V Impulse cunter Shrt/lng press key Step dimmer Outputs Cunt up t 8 Type Digital Maximal current n utput 380mA Cnnectins: KNX/EIB Bus Cnnectin Terminal 0.8mm2 IO Clamp, 1.5mm2 Operating elements LED 1 - Activity Enclsure: Material: Plyamide Clr: Gray Dimensins: 36(W)x91(H)x56(L) mm Usage temperature: 0C... +45C Strage temperature: -15C... +55C Weight: 50g Warranty: 2 years Relative Humidity: 10...95 % withut cndensatin Cautin Security advice The installatin and assembly f electrical equipment may nly be perfrmed by skilled electrician. The devices must nt be used in any relatin with equipment that supprts, directly r indirectly, human health r life r with applicatin that can result danger f peple, animals r real value Munting advice The devices are supplied in peratinal status. The cables cnnectins included can be clamped t the husing if required. Electrical cnnectin The devices are cnstructed fr the peratin f prtective lw vltage (SELV). Grunding f device is nt needed. When switching the pwer supply n r ff, pwer surges must be avided.
1. Cnnectin diagrams 1.1. External relays
1.2. Binary push-buttn
1.3. Vltage sensr
2. Default settings T reset the device t default settings, press and hld prgramming buttn fr mre than 10 secnds. Prgramming LED will blink several times after releasing the prgramming buttn. The device will restart autmatically after the reset is cmplete. 3. Default state f the device Factry-new devices have the physical address 1.1.255, n grup addresses. 4. ETS cnfiguratin 4.1. General settings Start-up delay (secnd) delay n device bt up Heartbeat send interval [Disabled.. 10minutes] time interval after which the device sends the telegram infrming that it is alive
4.2. Channel settings Output Open drain / Binary Input Binary edge detect Input Binary shrt/lng press Input Binary impulse cunter Input Step dimmer Input Analgue vltage sensr (0 30 V) 4.2.1. Output Open drain / Binary Output mde [Nrmally pen / Nrmally clse] default utput mde nrmally pen (0 ff, 1 - n), nrmally clse (0 n, 1 - ff) Status bject mde [Nrmal / Inverted] mde f the status bject Start-up value [0 / 1 / last knwn value] start-up value fr the bject On-timer [Disabled / Enabled] defines if the n timer is enabled Off-timer [Disabled / Enabled] defines if the ff timer is enabled Additinal bject additinal lgic bject fr the utput Lgical OR ne f bject r lgical bject shuld be 1 fr actin t perfrm Lgical OR initial value [0 / 1 / Lat knwn value]
Object A Object B Result 0 0 0 1 0 1 0 1 1 1 1 1 Lgical AND bth bject and lgical bject shuld be equal fr actin t perfrm Lgical AND initial value [0 / 1 / Lat knwn value] Object A Object B Result 0 0 0 1 0 0 0 1 0 1 1 1 Fault detectin status bject fr fault detectin (e.g. when there is n current flwing frm pen drain while it s status is OPEN) Fault detectin bject mde [Nrmal (0 n errr, 1 errr ) / Inverted (0 errr, 1 n errr)]
Output On / Off Timer In case On r Off timer is enabled in Output cnfiguratin, apprpriate submenu appears. Delay time [130 ms.. 10 m] delay time fr changing the status f the bject Delay multiplier [x1.. x10] e.g. if delay is set t 10 min and multiplier x5, the delay will be 50 min Reactin t ff/n telegram [Ignre / Set bject t n state] actin t perfrm n n/ff telegram
4.2.2. Input Binary edge detect Rising edge [D nthing / Send 0 / Send 1 / Tggle value] actin t perfrm n rising edge Falling edge [D nthing / Send 0 / Send 1 / Tggle value] actin t perfrm n falling edge
4.2.3. Input Binary shrt/lng press Shrt press [Send 0 / Send 1, Tggle value] Actin n shrt press Lng press [Send 0 / Send 1, Tggle value] Actin n lng press Lng press delay [250 ms.. 10 s] delay interval t detect lng press
4.2.4. Input Binary impulse cunter Cunter pulse edge [Rising edge / Falling edge / Bth] - which part f the impulse t cunt Cunter directin [Up / Dwn] directin f the cunter Number f pulses per cunter increment [1..100] number f pulses fr cunter increase by 1 (e.g. 10 pulses infrms abut 1 liter f water increase cunter by 1) Cunter step per each pulse [1..100] cunter step fr each pulse (e.g. 1 pulse means 10 liters f water increase cunter by 10) Send telegram n cunter update [Disabled / Enabled] send telegram int the bus n each cunter update Peridical send interval [10 s.. 10 min] time interval after which t send the reading f pulses t the bus Input Analgue vltage sensr (0 30 V) Input Analgue vltage sensr (0 30 V) Input Analgue vltage sensr (0 30 V)
4.2.5. Input Step dimmer Dimmer step [1..127] value n which the brightness will be changed n each step Dimmer ON preset (0 use previus) [0..255] preset when dimmer is switched ON
4.2.6. Input Analgue vltage sensr (0-30V) Object type [Analg vltage sensr /Binary vltage sensr] type f input vltage. In case f Analg vltage sensr, the fllwing parameters appear: Analg bject type [Scale (0-100%/1 Byte / Vltage (2 Byte)] mde f the status bject Minimum vltage minimum vltage value Maximum vltage maximum vltage value Send mde (Value change / Timer) when t send the telegram int the bus Value change threshld (0.1V step) (1..100) determine when the value is changed
In case f Binary vltage sensr, the fllwing parameters appear: Lw/high threshld (1..30) threshld level belw which the value is determined as Lw, and abve it is High Hysteresis (2..30) level f hysteresis during which value keeps unchanged Output value (Lw=0; High=1 / Lw=1; High=0) utput value in the bus
4.3. Lck bject Fr each f the prts yu can lck the bject. Input 1 Lck [1 bit] sending 1 disables 1 channel, sending 0 enables it again Input 8 Lck [1 bit] - sending 1 disables 8 channel, sending 0 enables it again