2 SECTION ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions and Division 1 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes the following: 1. Wood blocking and nailers. 2. Miscellaneous plywood. B. Related Sections include the following: 1. Division 05 Section Metal Fabrications for post-installed anchors. 2. Division 06 Section "Sheathing" for sheathing, subflooring, and underlayment. 3. Division 26 Section General Electrical Panels for plywood backing panels. 1.3 DEFINITIONS A. Exposed Framing: Framing not concealed by other construction. B. Dimension Lumber: Lumber of 2 inches nominal or greater but less than 5 inches nominal in least dimension. C. Timber: Lumber of 5 inches nominal or greater in least dimension. D. Boards or Strips: Lumber of less than 2 inches nominal size in least dimension. E. Lumber grading agencies, and the abbreviations used to reference them, include the following: 1. NeLMA: Northeastern Lumber Manufacturers' Association. 2. NLGA: National Lumber Grades Authority. 3. RIS: Redwood Inspection Service. 4. SPIB: The Southern Pine Inspection Bureau. 5. WCLIB: West Coast Lumber Inspection Bureau. 6. WWPA: Western Wood Products Association. 1.4 SUBMITTALS A. Informational/Quality Assurance/Control Submittals: 1. Product Data: For each type of process and factory-fabricated product. Indicate component materials and dimensions and include construction and application details. a. Include data for wood-preservative treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. Indicate type of preservative used and net amount of preservative retained. 1) Indicate compliance with AWPA requirements. 2) Indicate products contain no arsenic or chromium. b. Include data for fire-retardant treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. Include physical properties of treated materials based on testing by a qualified independent testing agency. c. For products receiving a waterborne treatment, include statement that moisture content of treated materials was reduced to levels specified before shipment to Project site ROUGH CARPENTRY

3 1.5 QUALITY ASSURANCE A. Testing Agency Qualifications: For testing agency providing classification marking for fireretardant-treated material, an inspection agency acceptable to authorities having jurisdiction that periodically performs inspections to verify that the material bearing the classification marking is representative of the material tested. B. Environmental Conditions: Preservative treatment shall not contain hazardous materials as arsenic or chromium. Chromated copper arsenate (CCA) and ammoniacal copper zinc arsenate (ACZA) shall not be used C. Preinstallation Conference: Conduct conference at Project site, unless otherwise noted. Attendees shall include installers whose work requires in-wall blocking. 1. Review in-wall blocking. 2. Distribute information on items furnished by the Owner and installed by the Contractor. 1.6 DELIVERY, STORAGE, AND HANDLING A. Stack lumber flat with spacers between each bundle to provide air circulation. Provide for air circulation around stacks and under coverings. 1.7 PROJECT CONDITIONS A. Installer must examine the substrates and supporting structure and the conditions under which the Carpentry Work is to be installed; and notify the A/E in writing of conditions detrimental to the Work. Do not proceed with the installation until unsatisfactory conditions have been corrected. B. Coordination: Fit Carpentry Work to other work; scribe and cope as required for accurate fit. Correlate location of furring, nailers, blocking, grounds, and similar supports to allow proper attachment of other work. 1. Contractor shall confirm with roofing system manufacturer that adhesives come into contact with roof membrane are compatible and acceptable. PART 2 - PRODUCTS 2.1 WOOD PRODUCTS, GENERAL A. Lumber: DOC PS 20 and applicable rules of grading agencies indicated. If no grading agency is indicated, provide lumber that complies with the applicable rules of any rules-writing agency certified by the ALSC Board of Review. Provide lumber graded by an agency certified by the ALSC Board of Review to inspect and grade lumber under the rules indicated. 1. Factory mark each piece of lumber with grade stamp of grading agency. 2. For exposed lumber indicated to receive a stained or natural finish, mark grade stamp on end or back of each piece. 3. Where nominal sizes are indicated, provide actual sizes required by DOC PS 20 for moisture content specified. Where actual sizes are indicated, they are minimum dressed sizes for dry lumber. 4. Provide dressed lumber, S4S, unless otherwise indicated. B. Maximum Moisture Content of Lumber: 19 percent. 2.2 WOOD-PRESERVATIVE-TREATED LUMBER (WPTL) A. Preservative Treatment by Pressure Process: AWPA U1; Use Category UC2 for interior construction not in contact with the ground, Use Category UC3b for exterior construction not in contact with the ground, and Use Category UC4a for items in contact with the ground. 1. Preservative Chemicals: Acceptable to authorities having jurisdiction and containing no arsenic or chromium. a. Unless otherwise noted: Use one of the following formulations of inorganic boron. 1) Sodium-octaborate (SBX) or disodium-octaborate-tetrahydrate (DOT) ROUGH CARPENTRY

4 2) Zinc borates (ZB) for treating engineered wood or wood composites during the manufacturing process. b. For sleepers sill plates and for wood that will be installed in a location where it will be in contact with the ground or will be exposed to liquid water (continuously or periodically), use one of the following copper formulations: 1) Alkaline-copper-quat (quaternary ammonium) (ACQ) 2) Copper azole, Type B (CA-B). 3) Micronized Copper Azole (MCA). B. Kiln-dry or air-dry lumber after treatment to a maximum moisture content of 19 percent. Do not use material that is warped or that does not comply with requirements for untreated material. C. Mark lumber with treatment quality mark of an inspection agency approved by the ALSC Board of Review. D. Application: Treat items indicated on Drawings, and the following: 1. Wood cants, nailers, curbs, equipment support bases, blocking, stripping, and similar members in connection with roofing, flashing, vapor barriers, and waterproofing. 2. Wood sills, sleepers, blocking, furring, and similar concealed members in contact with masonry or concrete. 2.3 FIRE-RETARDANT-TREATED MATERIALS (FRTM) A. General: Where fire-retardant-treated materials are indicated, use materials complying with requirements in this article, that are acceptable to authorities having jurisdiction, and with firetest-response characteristics specified as determined by testing identical products per test method indicated by a qualified testing agency. B. Fire-Retardant-Treated Lumber and Plywood by Pressure Process: Products with a flame spread index of 25 or less when tested according to ASTM E 84, and with no evidence of significant progressive combustion when the test is extended an additional 20 minutes, and with the flame front not extending more than 10.5 feet beyond the centerline of the burners at any time during the test. 1. Use treatment that does not promote corrosion of metal fasteners. 2. Exterior Type: Treated materials shall comply with requirements specified above for fireretardant-treated lumber and plywood by pressure process after being subjected to accelerated weathering according to ASTM D Use for exterior locations and where indicated. 3. Design Value Adjustment Factors: Treated lumber shall be tested according ASTM D 5664 and design value adjustment factors shall be calculated according to ASTM D C. Kiln-dry lumber after treatment to a maximum moisture content of 19 percent. Kiln-dry plywood after treatment to a maximum moisture content of 15 percent. D. Identify fire-retardant-treated wood with appropriate classification marking of qualified testing agency. E. Application: Treat 1. Concealed blocking. 2. Plywood backing panels. 2.4 DIMENSION LUMBER FRAMING A. Non-Load-Bearing Interior Partitions: Construction, Stud, or No. 3 grade of any species. B. Framing Other Than Non-Load-Bearing Interior Partitions: Any species and grade with a modulus of elasticity of at least 1,500,000 psi and an extreme fiber stress in bending of at least 850 psi for 2-inch nominal thickness and 12-inch nominal width for single-member use ROUGH CARPENTRY

5 2.5 MISCELLANEOUS LUMBER A. General: Provide miscellaneous lumber indicated and lumber for support or attachment of other construction, including the following: 1. Blocking. 2. Nailers. 3. Furring. B. For items of dimension lumber size, provide Standard, Stud, or No. 3 grade lumber with 19 percent maximum moisture content of any species. 1. Provide No. 2 grade Douglas Fir or Southern Yellow Pine nailers associated with roofing and roof flashing. C. For concealed boards, provide lumber with 19 percent maximum moisture content and any of the following species and grades: 1. Mixed southern pine, No. 3 grade; SPIB. 2. Hem-fir or hem-fir (north), Standard or 3 Common grade; NLGA, WCLIB, or WWPA. 3. Spruce-pine-fir (south) or spruce-pine-fir, Standard or 3 Common grade; NeLMA, NLGA, WCLIB, or WWPA. D. For blocking not used for attachment of other construction, Utility, Stud, or No. 3 grade lumber of any species may be used provided that it is cut and selected to eliminate defects that will interfere with its attachment and purpose. E. For blocking and nailers used for attachment of other construction, select and cut lumber to eliminate knots and other defects that will interfere with attachment of other work. 2.6 MISCELLANEOUS PLYWOOD PANELS A. General: Where plywood panels will be used for the following concealed types of applications, provide APA performance rated panels complying with requirements indicated for grade designation, span rating, exposure durability classification, edge detail (where applicable), and thickness. 1. Plywood Shims, Nailers, and Blocking for Roof Insulation Stops: Shall be APA UNDERLAYMENT C-C PLUGGED EXT. 2.7 FASTENERS A. General: Provide fasteners of size and type indicated that comply with requirements specified in this Article for material and manufacture. 1. Where rough carpentry is exposed to weather, in ground contact, preservative treated, or in area of high relative humidity, provide fasteners with hot-dip zinc coating complying with ASTM A 153 or of Type 304 stainless steel. a. Provide Class D coating for fasteners 3/8-inch diameter and less. Provide Class C coating for larger fasteners. B. Nails, Brads, and Staples: ASTM F C. Power-Driven Fasteners: ICC-ES AC Exception: Powder-activated/actuated fasteners that involve a projectile propelled by a charge of carbon-dioxide or gun powder are not allowed. D. Wood Screws: ASME B E. Lag Bolts: ASME B F. Bolts: Steel bolts complying with ASTM A 307, Grade A; with ASTM A 563 hex nuts and, where indicated, flat washers ROUGH CARPENTRY

6 G. Expansion Anchors: Anchor bolt and sleeve assembly of material indicated below with capability to sustain, without failure, a load equal to 6 times the load imposed when installed in unit masonry assemblies and equal to 4 times the load imposed when installed in concrete as determined by testing per ASTM E 488 conducted by a qualified independent testing and inspecting agency. 1. Material: Carbon-steel components, zinc plated to comply with ASTM B 633, Class Fe/Zn 5. H. Post-Installed Anchors: Refer to Division 05 Section Metal Fabrications. 2.8 MISCELLANEOUS MATERIALS A. Adhesives for Gluing Furring and Sleepers to Concrete or Masonry: Formulation complying with ASTM D 3498 that is approved for use indicated by adhesive manufacturer. B. Water-Repellent Preservative: NWWDA-tested and -accepted formulation containing 3-iodo-2- propynyl butyl carbamate, combined with an insecticide containing chlorpyrifos as its active ingredient. PART 3 - EXECUTION 3.1 INSTALLATION, GENERAL A. Set rough carpentry to required levels and lines, with members plumb, true to line, cut, and fitted. Fit rough carpentry to other construction; scribe and cope as needed for accurate fit. Locate furring, nailers, blocking, and similar supports to comply with requirements for attaching other construction. B. Framing Standard: Comply with AF&PA's WCD1, "Details for Conventional Wood Frame Construction," unless otherwise indicated. C. Do not splice structural members between supports, unless otherwise indicated. D. Install plywood backing panels by fastening to studs; coordinate locations with utilities requiring backing panels. Install fire-retardant-treated plywood backing panels with classification marking of testing agency exposed to view. E. Provide blocking and framing as indicated and as required to support facing materials, fixtures, specialty items, and trim. F. Provide fire blocking in furred spaces, stud spaces, and other concealed cavities as indicated and as follows: 1. Fire block furred spaces of walls, at each floor level, at ceiling, and at not more than 96 inches o.c. with solid wood blocking or noncombustible materials accurately fitted to close furred spaces. 2. Fire block concealed spaces of wood-framed walls and partitions at each floor level, at ceiling line of top story, and at not more than 96 inches o.c. Where fire blocking is not inherent in framing system used, provide closely fitted solid wood blocks of same width as framing members and 2-inch nominal- thickness. 3. Fire block concealed spaces between floor sleepers with same material as sleepers to limit concealed spaces to not more than 100 sq. ft. and to solidly fill space below partitions. 4. Fire block concealed spaces behind combustible cornices and exterior trim at not more than 20 feet o.c. G. Sort and select lumber so that natural characteristics will not interfere with installation or with fastening other materials to lumber. Do not use materials with defects that interfere with function of member or pieces that are too small to use with minimum number of joints or optimum joint arrangement. 1. Partial boards shall be fastened at a rate commensurate with full boards and shall have not less than two (2) fasteners per piece ROUGH CARPENTRY

7 H. Comply with AWPA M4 for applying field treatment to cut surfaces of preservative-treated lumber. 1. Use inorganic boron for items that are continuously protected from liquid water. 2. Use copper naphthenate for items not continuously protected from liquid water. I. Securely attach rough carpentry work to substrate by anchoring and fastening as indicated, complying with the following: 1. ICC-ES ESR-1539 for power-driven fasteners. J. Use common wire nails, unless otherwise indicated. Select fasteners of size that will not fully penetrate members where opposite side will be exposed to view or will receive finish materials. Make tight connections between members. Install fasteners without splitting wood; do not countersink nail heads, unless otherwise indicated. K. For exposed work, arrange fasteners in straight rows parallel with edges of members, with fasteners evenly spaced, and with adjacent rows staggered. 1. Use finishing nails, unless otherwise indicated. Countersink nail heads and fill holes with wood filler. 3.2 WOOD SLEEPER, BLOCKING, AND NAILER INSTALLATION A. Install where indicated and where required for attaching other work. Form to shapes indicated and cut as required for true line and level of attached work. Coordinate locations with other work involved. 1. Install additional fasteners, as required to counteract minor warpage or variances in substrate, and to hold tight and true to lines. 2. When using multiple nailer courses, weave corners and stagger end joints a minimum of 3 feet from underlying course. B. Attach items to substrates to support applied loading. Recess bolts and nuts flush with surfaces, unless otherwise indicated. Build into masonry during installation of masonry work. Where possible, anchor to formwork before concrete placement. C. Where wood-preservative-treated lumber is installed adjacent to metal decking, install continuous flexible flashing separator between wood and metal decking. D. Wood Nailers at Low Slope Roof: Minimum thickness of nailers must be such that the top of the nailer is flush with the top of the membrane underlayment. Wood nailers are required in any situation where 1 inch or greater of insulation is added to the roof perimeter edge. 1. Wood nailers shall be #2 treated lumber or better and shall be fastened to the deck, wall, or existing secure nailer in such a manner that they resist 200 lbs. of force per ft. of nailer in any direction. Fasteners used to attach wood nailers shall be spaced no greater than 18 inches apart and no less than 6 inches from end. Nailer attachment shall meet hereinbefore requirements and those of Factory Mutual Loss Prevention Data Sheet E. Wood Nailers at Flashing and Sheet Metal at Low Slope Roof: Minimum thickness of the nailers must be such that the top of the nailers are flush with the top of the membrane underlayment. 1. Wood nailers are required for securement of metal edgings, scuppers, insulated pipes. a. The width of the wood nailers shall be 5-1/2 inches minimum, and must exceed the width of the metal flange of edgings and insulated metal collars by 1/2 inch. 2. Lumber shall be preservative treated with inorganic boron. 3. Wood nailers must be #2 grade lumber or better and shall be fastened to the deck or wall in such a manner that they resist 200 pounds of force per linear foot of nailer in any direction. Fasteners used to attach wood nailers must be spaced no greater than 18 inches apart. Wood nailers are required in any situation where 1 inch or greater of insulation is added to the roof perimeter edge. Top of the nailers must be flush with the top of the roof membrane underlayment. Wood nailers are not required at a change of plane such as the intersection between a parapet wall and the decking ROUGH CARPENTRY

8 F. Wood blocking, nailers, and grounds shall be provided as necessary to receive woodwork, lockers, cabinets, and other finish items. 3.3 PROTECTION A. Protect wood that has been treated with inorganic boron (SBX) from weather. If, despite protection, inorganic boron-treated wood becomes wet, apply EPA-registered borate treatment. Apply borate solution by spraying to comply with EPA-registered label. B. Protect rough carpentry from weather. If, despite protection, rough carpentry becomes sufficiently wet that moisture content exceeds that specified, apply EPA-registered borate treatment. Apply borate solution by spraying to comply with EPA-registered label. END OF SECTION ROUGH CARPENTRY

9 SECTION SHEATHING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes the following: 1. Wall sheathing. 2. Sheathing joint-and-penetration treatment. B. Related Sections include the following: 1. Division 06 Section "Rough Carpentry" for miscellaneous plywood panels. 2. Division 07 Section Thermal Insulation for insulation within framing. 3. Division 07 Section Direct Applied Exterior Finish System. 4. Division 07 Roofing Sections for coordination of parapet insulation as substrate for roofing membranes. 1.3 SUBMITTALS A. Informational/Quality Assurance/Control Submittals: 1. Product Data: For each type of process and factory-fabricated product. Indicate component materials and dimensions and include construction and application details. a. Include data for wood-preservative treatment from chemical treatment manufacturer and certification by treating plant that treated plywood complies with requirements. Indicate type of preservative used and net amount of preservative retained. b. Include data for fire-retardant treatment from chemical treatment manufacturer and certification by treating plant that treated plywood complies with requirements. Include physical properties of treated materials. c. For products receiving a waterborne treatment, include statement that moisture content of treated materials was reduced to levels specified before shipment to Project site. 1.4 QUALITY ASSURANCE A. Source Requirements: For roofing applications, where insulation is installed in multiple courses, insulation must be from same manufacturer for all layers (complete system). B. Pre-Installation Conference; Convene prior to commencing work of this Section. Review installation procedures and coordination required with Related Work and the following: 1. Review wall assemblies for potential interference and conflicts and coordinate layout and support provisions for interfacing work. 2. Review continuous insulation wall panels installation methods and procedures related to application, including manufacturers, installation guidelines. 3. Review firestopping requirements and weather resistive membrane requirements and placement locations. 4. Review field quality control procedures. 1.5 DELIVERY, STORAGE, AND HANDLING A. Stack panels flat with spacers between each bundle to provide air circulation. Provide for air circulation around stacks and under coverings. Protect sheathing from weather by covering with waterproof sheeting, securely anchored SHEATHING

10 B. Store composite nail board sheathing products off the ground, in dry conditions, under cover and in manufacturer's unopened packaging until ready for installation. 1. The manufacturer's plastic wrapping is provided for protection during shipment only. Replace any panels that become wet before installation. C. Install no more insulation in one day than can be covered the same day with underlayment or membrane flashing. 1. Do not expose insulation to excessive heat, sparks, or open flame. 1.6 SEQUENCING A. Coordinate with installation of weather and air barrier systems. B. Ensure that products of this Section are supplied to affected trades in time to prevent interruption of construction progress. C. Do not install products under environmental conditions outside manufacturer s absolute limits. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. In other Part 2 articles where titles below introduce lists, the following requirements apply for product selection: 1. Manufacturers: Subject to compliance with requirements, provide product by the manufacturers specified. 2. Products: Subject to compliance with requirements, provide one of the products specified. B. Products of other manufacturers will be considered for acceptance provided they equal or exceed the material requirements and functional qualities of the specified product. Requests for A/E s approval must be accompanied by the Substitution Request Form and complete technical data for evaluation. All materials for evaluation must be received by the Project Manager and Specification Department at least 10 days prior to bid due date. Additional approved manufacturers will be issued by Addendum. 2.2 PERFORMANCE REQUIREMENTS A. Fire-Resistance Ratings: As tested according to ASTM E 119; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency. 1. Fire-Resistance Ratings: Indicated by design designations from UL s Fire Resistance Directory or from the listings of another qualified testing agency. B. Fire Resistance: Exterior wall system and component materials part of cold-formed metal framing assembly shall comply with the following requirements: 1. System complies with one of the following: NFPA 285, FM 4800, UL 1040, or UL 1715; Standard Method of Test for the Evaluation of Flammability Characteristics of Exterior Non-Load Bearing Wall Assemblies Containing Combustible Components using the Intermediate Scale, Multi-Story Test Apparatus. 2. Firestopping measures, per requirements of authorities with jurisdiction, shall be included at the floor line in the cold-formed stud cavity when the wall assembly extends beyond the floor line. C. Continuous Insulation (Wall Sheathing): Products shall meet the continuous insulation standards of ASHRAE 90.1 and applicable Building Codes for commercial exterior wall applications in accordance with requirements of authorities with jurisdiction. 2.3 WOOD PANEL PRODUCTS, GENERAL A. Plywood: Either DOC PS 1 or DOC PS 2, unless otherwise indicated SHEATHING

11 B. Thickness: As needed to comply with requirements specified, but not less than thickness indicated. C. Factory mark panels to indicate compliance with applicable standard. 2.4 PRESERVATIVE-TREATED PLYWOOD A. Preservative Treatment by Pressure Process: AWPA U1; Use Category UC2 [for interior construction not in contact with the ground, Use Category UC36 for exterior construction not in contact with ground, and Use Category UC4a for items in contact with the ground]. 1. Preservative Chemicals: Acceptable to authorities having jurisdiction and containing no arsenic or chromium. a. Unless otherwise noted: use one of the following formulations of inorganic boron. 1) Sodium-octaborate (SBX) or disodium-octaborate-tetrahydrate (DOT). 2) Zinc borates (ZB) for treating engineered wood or wood composites during the manufacturing process. b. For sleepers, sill plates and for wood that will be installed in a location where it will be in contact with the ground or will be exposed to liquid water (continuously or periodically), use one of the following copper formulations: 1) Alkaline-copper-quat (quaternary ammonium) (ACQ) 2) Copper acole, Type B (CA-B). B. Mark plywood with appropriate classification marking of an inspection agency acceptable to authorities having jurisdiction. C. Application: Treat only items indicated on Drawings and the following: 1. Plywood in contact with masonry or concrete. 2. Plywood used with roofing, flashing, vapor barriers, and waterproofing. 2.5 FIRE-RETARDANT-TREATED PLYWOOD A. General: Where fire-retardant-treated materials are indicated, use materials complying with requirements in this article that are acceptable to authorities having jurisdiction and with firetest-response characteristics specified as determined by testing identical products per test method indicated by a qualified testing agency. B. Fire-Retardant-Treated Plywood by Pressure Process: Products with a flame-spread index of 25 or less when tested according to ASTM E 84, and with no evidence of significant progressive combustion when the test is extended an additional 20 minutes, and with the flame front not extending more than 10.5 feet beyond the centerline of the burners at any time during the test. 1. Use treatment that does not promote corrosion of metal fasteners. 2. Exterior Type: Treated materials shall comply with requirements specified above for fire-retardant-treated plywood by pressure process after being subjected to accelerated weathering according to ASTM D Use for exterior locations and where indicated. 3. Interior Type A: Treated materials shall have a moisture content of 28 percent or less when tested according to ASTM D 3201 at 92 percent relative humidity. Use where exterior type is not indicated. 4. Design Value Adjustment Factors: Treated lumber plywood shall be tested according ASTM D 5516 and design value adjustment factors shall be calculated according to ASTM D Span ratings after treatment shall be not less than span ratings specified. C. Kiln-dry material after treatment to maximum moisture content of 15 percent. Do not use material that is warped or does not comply with requirements for untreated material. D. Identify fire-retardant-treated plywood with appropriate classification marking of qualified testing agency. E. Application: Treat plywood indicated on Drawings, and the following: 1. Wall sheathing within exterior wall assembly SHEATHING

12 2.6 WALL SHEATHING A. Plywood Wall/Soffit/Fascia Sheathing: Exterior, Structural I sheathing. 1. Span Rating: Not less than 24/0. 2. Nominal Thickness: Not less than 5/8 inch or as indicated. B. Glass-Mat Gypsum Wall Sheathing: ASTM C Type and Thickness: Regular, 1/2 inch thick, unless otherwise noted. Provide Type X, 5/8 inch thick, where required for thermal rating. C. Foil-Faced, Polyisocyanurate-Foam Wall Sheathing (Rigid Insulation): ASTM C 1289, Type I or Type II, Class 2, rigid, cellular, polyisocyanurate thermal insulation. Foam-plastic core and facings shall have a flame-spread index of 25 or less when tested individually. 1. Manufacturers: a. Atlas Roofing Corp. b. Dow Chemical Co. c. Remax, Inc. d. Johns Manville 2. Thickness: As indicated 3. Flame Propagation Test: Materials and construction shall be as tested according to NFPA FASTENERS A. General: Provide fasteners of size and type indicated that comply with requirements specified in this Article for material and manufacture. 1. For roof and wall sheathing, provide fasteners with hot-dip zinc coating complying with ASTM A 153 or Type 304 stainless steel. B. Nails, Brads, and Staples: ASTM F C. Power-Driven Fasteners: ICC-ES ESR D. Wood Screws: ASME B E. Screws for Fastening Wood Structural Panelsto Cold-Formed Metal Framing: ASTM C 954, except with wafer heads and reamer wings, length as recommended by screw manufacturer for material being fastened. 1. For wall and roof sheathing panels, provide screws with organic-polymer or other corrosion-protective coating having a salt-spray resistance of more than 800 hours according to ASTM B 117. F. Screws for Fastening Gypsum Sheathing to Cold-Formed Metal Framing: Steel drill screws, in length recommended by sheathing manufacturer for thickness of sheathing board to be attached, with organic-polymer or other corrosion-protective coating having a salt-spray resistance of more than 800 hours according to ASTM B For steel framing less than inch thick, attach sheathing to comply with ASTM C For steel framing from to inch thick, attach sheathing to comply with ASTM C SHEATHING JOINT-AND-PENETRATION TREATMENT MATERIALS A. Sealant for Glass-Mat Gypsum Sheathing Board: Silicone emulsion sealant complying with ASTM C 834, compatible with sheathing tape and sheathing, and recommended by tape and sheathing manufacturers for use with glass-fiber sheathing tape and for covering exposed fasteners SHEATHING

13 1. Sheathing Tape for Glass-Mat Gypsum Sheathing Board: Self-adhering glass-fiber tape, minimum 2 inches wide, 10 by 10 or 10 by 20 threads/inch, of type recommended by sheathing and tape manufacturers for use with silicone emulsion sealant in sealing joints in glass-mat gypsum sheathing board and with a history of successful in-service use. B. Sheathing Tape for Foam-Plastic Sheathing: Pressure-sensitive plastic tape recommended by sheathing manufacturer for sealing joints and penetrations in sheathing. PART 3 - EXECUTION 3.1 INSTALLATION, GENERAL A. Do not use materials with defects that impair quality of sheathing or pieces that are too small to use with minimum number of joints or optimum joint arrangement. Arrange joints so that pieces do not span between fewer than three support members. B. Cut panels at penetrations, edges, and other obstructions of work; fit tightly against abutting construction, unless otherwise indicated. C. Securely attach to substrate by fastening as indicated, complying with the following: 1. ICC-ES ESR-1539 for power-driven fasteners. 2. Table , "Fastening Schedule," in ICC's "International Building Code." D. Use common wire nails, unless otherwise indicated. Select fasteners of size that will not fully penetrate members where opposite side will be exposed to view or will receive finish materials. Make tight connections. Install fasteners without splitting wood. E. Coordinate wall and roof sheathing installation with flashing and joint-sealant installation so these materials are installed in sequence and manner that prevent exterior moisture from passing through completed assembly. F. Do not bridge building expansion joints; cut and space edges of panels to match spacing of structural support elements. G. Coordinate sheathing installation with installation of materials installed over sheathing so sheathing is not exposed to precipitation or left exposed at end of the workday when rain is forecast. 3.2 WOOD STRUCTURAL PANEL INSTALLATION A. General: Comply with applicable recommendations in APA Form No. E30S, "Engineered Wood Construction Guide," for types of structural-use panels and applications indicated. B. Fastening Methods: Fasten panels as indicated below: 1. Wall and Roof Sheathing: a. Screw to cold-formed metal framing. b. Space panels 1/8 inch apart at edges and ends. 3.3 GYPSUM SHEATHING INSTALLATION A. A. Comply with GA-253 and with manufacturer's written instructions. 1. Fasten gypsum sheathing to cold-formed metal framing with screws. 1. Install boards with a 3/8-inch gap where non-load-bearing construction abuts structural elements. 2. Install boards with a 1/4-inch gap where they abut masonry or similar materials that might retain moisture, to prevent wicking. B. Apply fasteners so heads bear tightly against face of sheathing boards but do not cut into facing SHEATHING

14 C. Vertical Installation: Install board vertical edges centered over studs. Abut ends and edges of each board with those of adjacent boards. Attach boards at perimeter and within field of board to each stud. 1. Space fasteners approximately 8 inches o.c. and set back a minimum of 3/8 inch from edges and ends of boards. 3.4 FOAM-PLASTIC SHEATHING INSTALLATION A. Comply with manufacturer's written instructions. 1. Install in exterior spaces without gaps or voids. Do not compress insulation. a. Fill voids with spray foam insulation. Refer to Division 07 Section Thermal Insulation. 2. Trim sheathing/insulation neatly to fit spaces. 3. Fasten insulation to substrate. Provide base support for the insulation panels as required for the exterior cladding to be installed over panels. Coordinate with the cladding or mason for the attachment requirements over sheathing/insulation. 4. Exposed insulation must be protected from open flame and kept dry at all times. 5. Exterior sheathing/insulation is not intended to be left exposed for extended periods of time in excess of 45 to 60 days without adequate protection. If extended exposure is anticipated all exposed foam surfaces including corners, windows and door openings, should be taped with a compatible waterproof tape. B. Foam-Plastic Wall Sheathing: Install vapor-relief strips or equivalent for permitting escape of moisture vapor that otherwise would be trapped in stud cavity behind sheathing. 3.5 SHEATHING JOINT-AND-PENETRATION TREATMENT A. Seal sheathing joints according to sheathing manufacturer's written instructions. 1. Apply glass-fiber sheathing tape to glass-mat gypsum sheathing board joints, and apply and trowel silicone emulsion sealant to embed entire face of tape in sealant. Apply sealant to exposed fasteners with a trowel so fasteners are completely covered. Seal other penetrations and openings. 2. Apply sheathing tape to joints between foam-plastic sheathing panels and at items penetrating sheathing. Apply at upstanding flashing to overlap both flashing and sheathing. 3.6 PROTECTION A. Protect installed products until finish materials can be applied. B. Cover the top and edges of unfinished roof panel work to protect it from the weather and to prevent accumulation of water in the cores of the panels. 1. Do not leave panels exposed to moisture. Wet panels shall be removed prior to application of roof covering. END OF SECTION SHEATHING

15 SECTION INTERIOR FINISH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes the following: 1. Interior standing and running trim. a. Top-of-wall cap and fascia(s) at kneewalls: 1) At front edges of stage. 2) At sides of access ramps and stairs 2. Locker wood tops. 3. Locker benches. B. Related Sections include the following: 1. Division 06 Section "Rough Carpentry" for furring, blocking, and other carpentry work not exposed to view. 2. Division 06 Section Plastic-Laminate-Faced Architectural Cabinets. 1.3 DEFINITIONS A. MDF: Medium-density fiberboard. B. MDO: Plywood with a medium-density overlay on the face. 1.4 SUBMITTALS A. Samples for Verification: 1. For each species and cut of lumber and panel products with non-factory-applied finish, with 1/2 of exposed surface finished, 50 sq. in. for lumber and 8 by 10 inches for panels. 1.5 QUALITY ASSURANCE A. Quality Standards: Except as otherwise shown or specified, comply with specified provisions of the Architectural Woodwork Institute (AWI) "Architectural Woodwork Standards." 1. Provide custom grade, unless otherwise noted. B. Optimum Moisture Content: Kiln-dry woodwork to average moisture content within the following ranges or as otherwise recommended by applicable AWI-Architectural Woodwork Standards for the regional climatic conditions involved. 1. Interior woodwork - 5 to 10 percent. 1.6 DELIVERY, STORAGE, AND HANDLING A. Protect materials against weather and contact with damp or wet surfaces. Stack lumber, plywood, and other panels flat with spacers between each bundle to provide air circulation. Provide for air circulation within and around stacks and under temporary coverings. B. Deliver interior finish carpentry materials only when environmental conditions meet requirements specified for installation areas. If interior finish carpentry materials must be stored in other than installation areas, store only where environmental conditions meet requirements specified for installation areas INTERIOR FINISH CARPENTRY

16 1.7 FIELD CONDITIONS A. Environmental Limitations: Do not deliver or install interior finish carpentry materials until building is enclosed and weatherproof, wet work in space is completed and nominally dry, and HVAC system is operating and maintaining temperature and relative humidity at occupancy levels during the remainder of the construction period. B. Do not install finish carpentry materials that are wet, moisture damaged, or mold damaged. 1. Indications that materials are wet or moisture damaged include, but are not limited to, discoloration, sagging, or irregular shape. 2. Indications that materials are mold damaged include, but are not limited to, fuzzy or splotchy surface contamination and discoloration. PART 2 - PRODUCTS 2.1 MATERIALS, GENERAL A. Lumber: DOC PS 20 and the following grading rules: 1. NeLMA: Northeastern Lumber Manufacturer s Association, Standard Grading Rules for Northeastern Lumber. 2. NHLA: National Hardwood Lumber Association, Rules for the Measurement and Inspection of Hardwood and Cypress. 3. NLGA: National Grades Authority, Standing Grading Rules for Canadian Lumber. 4. SPIB: The Southern Pine Inspection Bureau, Standard Grading Rules for Southern Pine Lumber. 5. WCLIB: West Coast Lumber Inspection Bureau, Standard No. 17, Grading Rules. 6. WWPA: Western Wood Products Association, Western Lumber Grading Rules. B. Factory mark each piece of lumber with grade stamp of inspection agency indicating grade, species, moisture content at time of surfacing, and mill. 1. For exposed lumber, mark grade stamp on end or back of each piece of omit grade stamp and provide certificates of grade compliance issued by inspection agency. C. MDF: ANSI A208.2, Grade 130, made with binder containing no urea-formaldehyde resin. D. Softwood Plywood: DOC PS 1. E. Particleboard: ANSI A208.1, Grade M-2, made with binder containing no urea-formaldehyde resin. 2.2 STANDING AND RUNNING TRIM A. Hardwood Standing and Running Trim for Stain or Clear: Shall be Custom grade, conforming to AWI Section 300, unless otherwise noted. 1. Species and Grade: Red Oak Clear; NHLA. a. White Maple at stage area and where indicated. 2. Finger Jointing: Not allowed. 3. Gluing for Width: Not allowed. 4. Veneered Material: Use for lumber trim wider than 6 inches. 5. Face Surface: Surfaced (smooth). 6. Backout or groove backs of flat trim members and kerf backs of other wide flat members, except for members with ends exposed in finished work. B. Locker benches and locker wood tops shall be Custom grade solid red oak conforming to AWI Section 100 and 300, unless otherwise noted. Edge gluing for width shall be permitted using Type 1 glue. Gluing for thickness is not acceptable. 1. Provide countersunk screw attachment to wood grounds 2. Fill screw holes with oak plugs glued in place. 3. Exposed edges to be rounded. 4. Edge glued joints shall be splined, doweled, or reinforced by biscuits INTERIOR FINISH CARPENTRY

17 2.3 MISCELLANEOUS MATERIALS A. Fasteners for Interior Finish Carpentry: Nails, screws, and other anchoring devices of type, size, material, and finish required for application indicated to provide secure attachment, concealed where possible. 1. Where galvanized finish is indicated, provide fasteners and anchorages with hot-dip galvanized coating complying with ASTM A 153. B. Glue: Aliphatic-resin, polyurethane, or resorcinol wood glue recommended by manufacturer for general carpentry use. C. Multipurpose Construction Adhesive: Formulation complying with ASTM D 3498 that is recommended for indicated use by adhesive manufacturer. 2.4 FABRICATION A. Back out or kerf backs of the following members except those with ends exposed in finished work: 1. Interior standing and running trim except shoe and crown molds. B. Ease edges of lumber less than 1 inch in nominal thickness to 1/16-inch radius and edges of lumber 1 inch or more in nominal thickness to 1/8-inch radius. 2.5 FACTORY OR SHOP FINISHING OF INTERIOR WOODWORK A. Quality Standard: Comply with AWI Section 1500 unless otherwise indicated. B. General: Finishing of interior finish carpentry is to be performed at factory or shop as specified in this section. 1. For painted finishes, refer to Division 09 Section Interior Painting for final finishing of installed architectural woodwork and for material and application requirements of prime coats for woodwork not specified to receive final finish in this section. C. Preparations for Finishing: Comply with referenced quality standard for sanding, filling countersunk fasteners, sealing concealed surfaces and similar preparations for finishing of architectural woodwork, as applicable to each unit of work. D. Transparent Finish: Comply with requirements indicated below for grade, finish system, staining, effect, and sheen, with sheen measured on 60-degree gloss meter per ASTM D Grade: Custom 2. Finish System: AWI System 11 - Catalyzed Polyurethane 3. Staining: Match approved sample for color 4. Effect: Open grain 5. Sheen: Semi gloss bright rubbed affects degrees. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance. B. Examine finish carpentry materials before installation. Reject materials that are wet, moisture damaged, and mold damaged. C. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 PREPARATION A. Clean substrates of projections and substances detrimental to application INTERIOR FINISH CARPENTRY

18 B. Before installing interior finish carpentry, condition materials to average prevailing humidity in installation areas for a minimum of 24 hours. 3.3 INSTALLATION, GENERAL A. Do not use materials that are unsound, warped, improperly treated or finished, inadequately seasoned, or too small to fabricate with proper jointing arrangements. 1. Do not use manufactured units with defective surfaces, sizes, or patterns. B. Install interior finish carpentry level, plumb, true, and aligned with adjacent materials. Use concealed shims where necessary for alignment. 1. Scribe and cut interior finish carpentry to fit adjoining work. Refinish and seal cuts as recommended by manufacturer. 2. Countersink fasteners, fill surface flush, and sand where face fastening is unavoidable. 3. Install to tolerance of 1/8 inch in 96 inches for level and plumb. Install adjoining interior finish carpentry with 1/32-inch maximum offset for flush installation and 1/16-inch maximum offset for reveal installation. 4. Install stairs with no more than 3/16-inch variation between adjacent treads and risers and with no more than 3/8-inch variation between largest and smallest treads and risers within each flight. 5. Coordinate interior finish carpentry with materials and systems in or adjacent to it. Provide cutouts for mechanical and electrical items that penetrate interior finish carpentry. 3.4 STANDING AND RUNNING TRIM INSTALLATION A. Install with minimum number of joints practical, using full-length pieces from maximum lengths of lumber available. Do not use pieces less than 24 inches long, except where necessary. Stagger joints in adjacent and related standing and running trim. Cope at returns and miter at corners to produce tight-fitting joints with full-surface contact throughout length of joint. Use scarf joints for end-to-end joints. Plane backs of casings to provide uniform thickness across joints where necessary for alignment. 1. Match color and grain pattern of trim for transparent finish (stain or clear finish) across joints. 2. Install trim after gypsum board joint finishing operations are completed. 3. Drill pilot holes in hardwood before fastening to prevent splitting. Fasten to prevent movement or warping. Countersink fastener heads on exposed carpentry work and fill holes. B. Locker benches and locker wood tops shall be installed where and as indicated. 3.5 ADJUSTING A. Replace interior finish carpentry that is damaged or does not comply with requirements. Interior finish carpentry may be repaired or refinished if work complies with requirements and shows no evidence of repair or refinishing. Adjust joinery for uniform appearance. 3.6 CLEANING A. Clean interior finish carpentry on exposed and semiexposed surfaces. Touch up factory or shop applied finishes to restore damaged or soiled areas. 3.7 PROTECTION A. Protect installed products from damage from weather and other causes during remainder of the construction period INTERIOR FINISH CARPENTRY

19 B. Remove and replace finish carpentry materials that are wet, moisture damaged, and mold damaged. 1. Indications that materials are wet or moisture damaged include, but are not limited to, discoloration, sagging, or irregular shape. 2. Indications that materials are mold damaged include, but are not limited to, fuzzy or splotchy surface contamination and discoloration. END OF SECTION INTERIOR FINISH CARPENTRY

20 SECTION PLASTIC-LAMINATE-FACED ARCHITECTURAL CABINETS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes the following: 1. Custom plastic-laminate cabinets, not included as work of Division 12. a. Office reception desk b. Circulation desk 2. Plastic-laminate countertops, not included as work of Division Solid-surfacing-material countertops. 4. Wood furring, blocking, shims, and hanging strips for installing architectural (custom) plastic-laminate-faced cabinets, unless concealed within other construction before cabinet installation. B. Related Sections include the following: 1. Division 06 Section "Rough Carpentry" for wood furring, blocking, shims, and hanging strips required for installing cabinets and concealed within other construction before cabinet installation. 2. Division 06 Section Interior Finish Carpentry for interior carpentry exposed to view that is not specified in this Section. 3. Division 07 Section Joint Sealants. 4. Division 12 Section Educational Casework for coordination with modular casework. a. At a minimum, casework scheduled in the same rooms, spaces, and areas shall have coordinated: 1) Plastic laminate selections. 2) Working surface heights. 3) Edge treatments. 4) Backsplash/end splash conditions. 5) Hardware finishes. 1.3 DEFINITIONS A. Interior architectural woodwork includes wood furring, blocking, shims, and hanging strips for installing woodwork items unless concealed within other construction before woodwork installation. B. Exposed Portions of Casework: Include surfaces visible when doors and drawers are closed. Bottoms of casework more than 4 feet above floor and tops less than 6 feet 6 inches above floor shall be considered as exposed. Visible members in open cases or behind glass doors also shall be considered as exposed portions. Any unit exterior side surface that is visible after installation. C. Semi-Exposed Portions of Casework: Includes those members behind opaque doors, such as shelves, divisions, interior faces of ends, case back, drawer sides, backs and bottoms, and back face of doors. Tops of casework 6 feet 6 inches or more above floor shall be considered semi-exposed. D. Concealed Portions of Casework: Include sleepers, web frames, dust panels, and other surfaces not usually visible after installation PLASTIC-LAMINATE-FACED ARCHITECTURAL CABINETS

A. Boards or Strips: Lumber of less than 2 inches nominal size in least dimension.

A. Boards or Strips: Lumber of less than 2 inches nominal size in least dimension. HIGGINSVILLE HABILITATION CENTER MISC. BUILDING RENOVATIONS STATE OF MISSOURI HIGGINSVILLE, MISSOURI SECTION 061000 - ROUGH CARPENTRY PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 06 1053 - MISCELLANEOUS ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Division 01 Specification

More information

FT DIX ELEMENTARY SCHOOL PHASE VII, CLASSROOM ADDITION PEMBERTON TOWNSHIP REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5349A

FT DIX ELEMENTARY SCHOOL PHASE VII, CLASSROOM ADDITION PEMBERTON TOWNSHIP REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5349A SECTION 061050 - MISCELLANEOUS CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

B. Related Requirements: 1. Section "Interior Painting" for priming and backpriming of interior finish carpentry.

B. Related Requirements: 1. Section Interior Painting for priming and backpriming of interior finish carpentry. 1 ~GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY

More information

SECTION INTERIOR FINISH CARPENTRY. A. Lumber grading agencies, and the abbreviations used to reference them, include the following:

SECTION INTERIOR FINISH CARPENTRY. A. Lumber grading agencies, and the abbreviations used to reference them, include the following: SECTION 06 2023 PART 1 GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Interior standing and running trim. 2. Interior stairs. 1.2 DEFINITIONS A. Lumber grading agencies, and the abbreviations

More information

SECTION INTERIOR FINISH CARPENTRY

SECTION INTERIOR FINISH CARPENTRY SECTION 06 20 23 PART 1 - GENERAL 1.01 SUMMARY A. Section includes the following items for field-applied paint finish: 1. Interior standing and running trim. 2. Interior plywood paneling. B. Related Sections

More information

SECTION INTERIOR FINISH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION INTERIOR FINISH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 062023 - INTERIOR FINISH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

DIVISION 6 WOODS AND PLASTICS SECTION ROUGH CARPENTRY

DIVISION 6 WOODS AND PLASTICS SECTION ROUGH CARPENTRY DIVISION 6 WOODS AND PLASTICS SECTION 06 10 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

DIVISION 6 WOODS AND PLASTICS SECTION FINISH CARPENTRY

DIVISION 6 WOODS AND PLASTICS SECTION FINISH CARPENTRY DIVISION 6 WOODS AND PLASTICS SECTION 06 20 23 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

ADDENDUM NO. 1 THOROUGHBRED ROOM RENOVATION PHASE II DINING AREA MURRAY STATE UNIVERSITY, MURRAY, KY PROJECT #

ADDENDUM NO. 1 THOROUGHBRED ROOM RENOVATION PHASE II DINING AREA MURRAY STATE UNIVERSITY, MURRAY, KY PROJECT # ADDENDUM NO. 1 THOROUGHBRED ROOM RENOVATION PHASE II DINING AREA MURRAY STATE UNIVERSITY, MURRAY, KY PROJECT #13-046 10-23-2013 Bidders shall acknowledge receipt of this Addendum on the Bid Form, in the

More information

Ash Brook Golf Course Scotch Plains, New Jersey

Ash Brook Golf Course Scotch Plains, New Jersey SECTION 062013 - EXTERIOR FINISH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION FINISH CARPENTRY

SECTION FINISH CARPENTRY SECTION 06200 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to

More information

DIVISION 6 WOOD AND PLASTICS

DIVISION 6 WOOD AND PLASTICS DIVISION 6 WOOD AND PLASTICS PART 1 - GENERAL 1.01 SUMMARY A. This Section includes the following: 1. Wood framing. 2. Wood supports. 3. Wood blocking. 4. Wood cants. 5. Wood nailers. 6. Wood furring.

More information

SECTION ROUGH CARPENTRY

SECTION ROUGH CARPENTRY SECTION 06 10 00- ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Contracting Requirements and Division 1 Specification Sections, apply

More information

2. Wood grounds, nailers, blocking, miscellaneous framing, sleepers, etc.

2. Wood grounds, nailers, blocking, miscellaneous framing, sleepers, etc. 06100 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 STIPULATIONS A. The specifications sections " General Conditions of the Construction Contract ", "Special Conditions", and "Division 1 - General Requirements"

More information

A. Rough carpentry includes but is not limited to the following:

A. Rough carpentry includes but is not limited to the following: SECTION 06100 ROUGH CARPENTRY PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification Sections,

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 06 2023 - INTERIOR FINISH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION CARPENTRY

SECTION CARPENTRY SECTION 06100 CARPENTRY PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Carpentry work including grounds, nailers, blocking, miscellaneous framing, plywood backing panels, plywood sheathing, preservative

More information

A. Provide all finish carpentry needed for a complete and proper installation.

A. Provide all finish carpentry needed for a complete and proper installation. SECTION 06200 - PART ONE GENERAL 1.1 SECTION INCLUDES A. Provide all finish carpentry needed for a complete and proper installation. B. Provide all wood, nails, bolts, screws, and all other items needed

More information

SECTION MISCELLANEOUS ROUGH CARPENTRY

SECTION MISCELLANEOUS ROUGH CARPENTRY SECTION 06 1053 - MISCELLANEOUS ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

A. Product Data: For each type of process and factory-fabricated product indicated.

A. Product Data: For each type of process and factory-fabricated product indicated. SECTION 06100 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Wood framing. 2. Wood supports. 3. Wood blocking. 4. Wood cants. 5. Wood nailers. 6. Wood furring.

More information

SECTION ROUGH CARPENTRY

SECTION ROUGH CARPENTRY SECTION 06 10 00 ROUGH CARPENTRY PART 1 - GENERAL 1.01 SUMMARY A. Section includes: 1. Framing with dimension lumber. 2. Wood blocking and nailers. 3. Plywood backing panels. 1.02 ACTION SUBMITTALS A.

More information

RAMAPO COLLEGE OF NEW JERSEY PHASE II HOUSING REHABILITATION 2012

RAMAPO COLLEGE OF NEW JERSEY PHASE II HOUSING REHABILITATION 2012 SECTION 06100 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

A. All trim that has been damages, broken, or missing shall be repaired or replaced with material of the same size, shape, and type.

A. All trim that has been damages, broken, or missing shall be repaired or replaced with material of the same size, shape, and type. SECTION 062000 - FINISH CARPENTRY PART 1 - GENERAL 1.1 SECTION REQUIREMENTS A. All trim that has been damages, broken, or missing shall be repaired or replaced with material of the same size, shape, and

More information

1. Section : Rough Carpentry 2. Section : Exterior Insulation and Finishing Systems 3. Section : Metal Roof Panels

1. Section : Rough Carpentry 2. Section : Exterior Insulation and Finishing Systems 3. Section : Metal Roof Panels SECTION 06 16 00 SHEATHING PART 1 GENERAL 1.1 SUMMARY A. Section includes: 1. Roof and Wall Sheathing. B. Related Sections: Documents relating to the work of this section include, but are not limited to,

More information

SECTION FINISH CARPENTRY PART 1 GENERAL. 1.1 SECTION INCLUDES A. Interior Finish Carpentry Work: 1. Refer to schedule at end of Section.

SECTION FINISH CARPENTRY PART 1 GENERAL. 1.1 SECTION INCLUDES A. Interior Finish Carpentry Work: 1. Refer to schedule at end of Section. SECTION 06200 - FINISH CARPENTRY PART 1 GENERAL 1.1 SECTION INCLUDES A. Interior Finish Carpentry Work: 1. Refer to schedule at end of Section. 1.2 RELATED SECTIONS A. Section 06100 - Rough Carpentry:

More information

Lindenwold Boro Hall Lindenwold, NJ. Bishop & Smith Architects Laurel Springs, NJ. August 2, 2012 PART 1 - GENERAL 1.1 SUMMARY. A.

Lindenwold Boro Hall Lindenwold, NJ. Bishop & Smith Architects Laurel Springs, NJ. August 2, 2012 PART 1 - GENERAL 1.1 SUMMARY. A. SECTION 061000 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Wood blocking and nailers. 2. Wood furring and grounds. 3. Plywood backing panels. 1.2 ACTION SUBMITTALS A. Product

More information

Project Specifications Section SECTION ROUGH CARPENTRY Issued Final:

Project Specifications Section SECTION ROUGH CARPENTRY Issued Final: Project Specifications Section 061000 ROUGH CARPENTRY SECTION 061000 - ROUGH CARPENTRY Issued Final: 02-01-17 PART 1 - GENERAL 1.1 SUMMARY A. Scope: 1. Provide rough carpentry items where shown on the

More information

A. Dimension Lumber: Lumber of 2 inches nominal or greater but less than 5 inches nominal in least dimension.

A. Dimension Lumber: Lumber of 2 inches nominal or greater but less than 5 inches nominal in least dimension. SECTION 06 10 53 - MISCELLANEOUS ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

SECTION ARCHITECTURAL WOOD CASEWORK

SECTION ARCHITECTURAL WOOD CASEWORK SECTION 06410 - ARCHITECTURAL WOOD CASEWORK PART 1 GENERAL 1.01 SECTION INCLUDES A. Wood cabinets for opaque finish. B. Flush wood paneling for transparent finish. C. Factory finishing. 1.02 RELATED REQUIREMENTS

More information

SECTION ROUGH CARPENTRY 1.1 DESCRIPTION OF WORK:

SECTION ROUGH CARPENTRY 1.1 DESCRIPTION OF WORK: SECTION 061000 - ROUGH CARPENTRY 1.1 DESCRIPTION OF WORK: A. Definition: Rough carpentry includes carpent~y work not specified as part of other sections and which is generally not exposed, except as otherwise

More information

Collins Engineers Palmetto Islands County Park Boardwalk Repairs 03/28/2014 SECTION ROUGH CARPENTRY

Collins Engineers Palmetto Islands County Park Boardwalk Repairs 03/28/2014 SECTION ROUGH CARPENTRY PART 1 GENERAL 1.1 RELATED SECTIONS SECTION 061000 ROUGH CARPENTRY A. Drawings and general provisions of the Construction Contract, including General Conditions and Division 1 Specification Sections, apply

More information

DIVISION 6 WOOD, PLASTICS AND COMPOSITES

DIVISION 6 WOOD, PLASTICS AND COMPOSITES DIVISION 6 WOOD, PLASTICS AND COMPOSITES PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 06 1000 ROUGH CARPENTRY A. Rough opening framing for doors, windows, and roof openings. B. Roofing nailers. C. Preservative

More information

Student Services & Classroom Addition

Student Services & Classroom Addition SECTION 105116 - WOOD LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 08 - OPENINGS

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 08 - OPENINGS SECTION 081433 - STILE AND RAIL WOOD DOORS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Exterior stile and rail wood doors and sidelites. 2. Interior stile and rail wood doors. 3. Interior fire-rated,

More information

E.M. Crouthamel Elementary School SECTION ROUGH CARPENTRY

E.M. Crouthamel Elementary School SECTION ROUGH CARPENTRY SECTION 061000 ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

B. Related Sections: The following Sections contain requirements that relate to this Section:

B. Related Sections: The following Sections contain requirements that relate to this Section: SECTION 06100 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

D. Product Certificates: Signed by manufacturers of casework certifying that products furnished comply with requirements.

D. Product Certificates: Signed by manufacturers of casework certifying that products furnished comply with requirements. SECTION 12356 - CASEWORK PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

SECTION ROUGH CARPENTRY

SECTION ROUGH CARPENTRY SECTION 06100 ROUGH CARPENTRY PART 1 GENERAL 1.1 DESCRIPTION OF WORK A. The work includes furnishing all labor, materials and equipment required to complete the Rough Carpentry work as shown on the Drawings

More information

A. Dimension Lumber: Lumber of 2 inches nominal or greater but less than 5 inches nominal in least dimension.

A. Dimension Lumber: Lumber of 2 inches nominal or greater but less than 5 inches nominal in least dimension. SECTION 061000- ROUGH CARPENTRY PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 I Specification Sections,

More information

SECTION ROUGH CARPENTRY

SECTION ROUGH CARPENTRY SECTION 06100 PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work of this Section shall include all materials and installation necessary to provide Rough Carpentry as shown and detailed on the Drawings and

More information

SECTION ARCHITECTURAL WOODWORK

SECTION ARCHITECTURAL WOODWORK SECTION 06400 ARCHITECTURAL WOODWORK PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Custom Cabinet Units a. Plastic Laminate b. Sound Barrier for Casework 2. Cabinet Hardware B. Related Sections:

More information

Chevy Chase Club June 30, 2008 Bowie Gridley Architects

Chevy Chase Club June 30, 2008 Bowie Gridley Architects SECTION 081433 - STILE AND RAIL WOOD DOORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

1. Division 6 Section "Rough Carpentry" for furring, blocking, and other carpentry work that is not exposed to view.

1. Division 6 Section Rough Carpentry for furring, blocking, and other carpentry work that is not exposed to view. SECTION 06402 INTERIOR ARCHITECTURAL WOODWORK PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II SECTION 061000 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The General Conditions, any Supplementary General Conditions and Division 1, General Requirements, are hereby made a part of

More information

PART 1 GENERAL FINISH CARPENTRY

PART 1 GENERAL FINISH CARPENTRY SECTION 06 20 00 (06200) PART 1 GENERAL 1.1 SUMMARY A. Section Includes:. 1. Wood Millwork a. Interior Standing and Running Trim 2. Wood Stairs 3. Shelving 4. Composition Siding and Soffits and Trim a.

More information

SECTION ARCHITECTURAL WOODWORK. B. Related Sections: 1. Section Paints and Coatings: Field applied painted finishes.

SECTION ARCHITECTURAL WOODWORK. B. Related Sections: 1. Section Paints and Coatings: Field applied painted finishes. PART 1 - GENERAL 1.1 SUMMARY SECTION 06 40 00 A. Provide architectural woodwork as shown and specified. Work includes: 1. Providing plastic laminate finished casework. 2. Providing plastic laminate clad

More information

A. Dimension Lumber: Lumber of 2 inches nominal (38 mm actual) or greater but less than 5 inches nominal (114 mm actual) in least dimension.

A. Dimension Lumber: Lumber of 2 inches nominal (38 mm actual) or greater but less than 5 inches nominal (114 mm actual) in least dimension. ROUGH CARPENTRY Section 06 1000 Page 1 of 6 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A. Product Data: For each type of process and factory-fabricated product. a. Include statement indicating costs for each certified wood product.

A. Product Data: For each type of process and factory-fabricated product. a. Include statement indicating costs for each certified wood product. Copyright 2003 and 2005 AIA MASTERSPEC Short Form 11/03 (R 05/07) SECTION 061000 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Framing with dimension lumber.

More information

1.03 QUALITY ASSURANCE A. Inspection Agencies: 1. SPIB: Southern Pine Inspection Bureau; for all structural framing of roof joists and headers.

1.03 QUALITY ASSURANCE A. Inspection Agencies: 1. SPIB: Southern Pine Inspection Bureau; for all structural framing of roof joists and headers. DIVISION 6 - WOOD AND PLASTICS SECTION 06100 - ROUGH CARPENTRY PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Rough carpentry for: a. Wood framing and sheathing for the new Rest Area building additions.

More information

SECTION WOOD ARCHITECTURAL CABINETS AND QUARTZ COUNTERTOPS

SECTION WOOD ARCHITECTURAL CABINETS AND QUARTZ COUNTERTOPS SECTION 064113- WOOD ARCHITECTURAL CABINETS AND QUARTZ COUNTERTOPS PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION BULLET- RESISTANT DOORS

SECTION BULLET- RESISTANT DOORS 1 SECTION 08 3950 BULLET- RESISTANT DOORS PART 1- GENERAL 1.01 SUMMARY A. This Section Includes: 1. Bullet- resistant steel door and frame systems. 2. Door hardware for bullet- resistant steel door and

More information

Music Area Casework General 1.01 Summary Related Sections Definitions Qualifications and Quality Assurance

Music Area Casework General 1.01 Summary Related Sections Definitions Qualifications and Quality Assurance 1.00 General 1.01 Summary Music Area Casework A. This section includes the following Scope of Work as referred to in the plans: 1. Thermally Fused Laminate manufactured casework, for use in music areas,

More information

ADDENDUM TO THE CONTRACT. for the GLACIER FIRE STATION KITCHEN AND CLASSROOM RENOVATION. Contract No. E16-181

ADDENDUM TO THE CONTRACT. for the GLACIER FIRE STATION KITCHEN AND CLASSROOM RENOVATION. Contract No. E16-181 ADDENDUM TO THE CONTRACT for the ENGINEERING DEPARTMENT GLACIER FIRE STATION KITCHEN AND CLASSROOM RENOVATION Contract No. E6-8 ADDENDUM NO.: ONE CURRENT DEADLINE FOR BIDS: May 9, 206 PREVIOUS ADDENDA:

More information

SECTION MANUFACTURED CASEWORK

SECTION MANUFACTURED CASEWORK 1 GENERAL 1.1 SECTION INCLUDES SECTION 12300 MANUFACTURED CASEWORK A. Work required to complete the manufactured casework indicated by the Contract Documents, and the items necessary for its proper installation.

More information

3 for handling, storing, installing, and finishing treated materials: 5 unless otherwise specified. 34. Air-infiltration barriers.

3 for handling, storing, installing, and finishing treated materials: 5 unless otherwise specified. 34. Air-infiltration barriers. SECTON 06100 - ROUGH CARPENTRY 3 PART -GENERAL 3 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

SECTION INTERIOR ARCHITECTURAL WOODWORK

SECTION INTERIOR ARCHITECTURAL WOODWORK SECTION 06402 - INTERIOR ARCHITECTURAL WOODWORK PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

DIVISON 6 WOODS AND PLASTICS SECTION PLASTIC LAMINATE FACED ARCHITECTUAL CABINETS

DIVISON 6 WOODS AND PLASTICS SECTION PLASTIC LAMINATE FACED ARCHITECTUAL CABINETS DIVISON 6 WOODS AND PLASTICS PART 1 - GENERAL 1:1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Load Tables, Technical Data and Installation Instructions

Load Tables, Technical Data and Installation Instructions W22. W22. W22. W22. W22 W22.. Simpson Strong-Tie Fastening Systems Structural Wood-to-Wood Connections Including Ledgers Designed to provide an easy-to-install, high-strength alternative to through-bolting

More information

On-Call General Contractor Specifications University of Maryland College Park June 2013

On-Call General Contractor Specifications University of Maryland College Park June 2013 SECTION 061053 - MISCELLANEOUS ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

B. Shop Drawings: For residential casework. Include plans. elevations, details, and attachments to other work.

B. Shop Drawings: For residential casework. Include plans. elevations, details, and attachments to other work. HVAC 1Sunporch 1Fire Alarm Renovation SECTION 123530 RESIDENTIAL CASEWORK PART 1 - GENERAL 1.1 SUMMARY A. Section includes laundry room cabinets. 1.2 ACTION SUBMITTALS A. Product Data: For each type of

More information

Section Rough Carpentry

Section Rough Carpentry Section 06 10 00 Rough Carpentry 06 10 00-1 PART 1 - GENERAL 1.01 SECTION INCLUDES A. Blocking in wall and roof openings; wood furring and grounds; electrical panel back boards, concealed wood blocking.

More information

WHITE W/OAK TRIM NATURAL MEDIUM NORTHPORT OAK

WHITE W/OAK TRIM NATURAL MEDIUM NORTHPORT OAK WHITE W/OAK TRIM NATURAL MEDIUM NORTHPORT OAK Accessories. We believe that functionality is at the heart of any great kitchen. Above are a few of the accessories available with Merillat Essentials. The

More information

The City of Winnipeg Section St. Vital Park Pavilion Page 1 of 1

The City of Winnipeg Section St. Vital Park Pavilion Page 1 of 1 The City of Winnipeg Section 06 10 13 WOOD BLOCKING AND CURBING St. Vital Park Pavilion Page 1 of 1 Part 1 General 1.1 SECTION INCLUDES.1 Roof curbs..2 Blocking in wall and roof openings..3 Wood furring

More information

B. Sequencing: Schedule installation to keep sheathing exposure to UV within the manufacturer s recommended limits.

B. Sequencing: Schedule installation to keep sheathing exposure to UV within the manufacturer s recommended limits. SECTION 06 16 43 GYPSUM SHEATHING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Exterior GMF gypsum sheathing. 2. Joint treatment materials. 3. Panel and penetration joint and fastener treatment.

More information

SECTION CUSTOM CASEWORK

SECTION CUSTOM CASEWORK PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 06 41 00 CUSTOM CASEWORK A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 specification sections,

More information

SECTION HOLLOW METAL DOORS AND FRAMES

SECTION HOLLOW METAL DOORS AND FRAMES SECTION 081113 HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: Include construction details, material

More information

Coliseum and Women's Building Interior/Exterior Improvements and Campground Utility Improvements Project# F

Coliseum and Women's Building Interior/Exterior Improvements and Campground Utility Improvements Project# F SECTION 060312- HISTORIC WOOD REPAIR PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION WOOD ARCHITECTURAL CABINETS AND LAMINATE COUNTERTOPS

SECTION WOOD ARCHITECTURAL CABINETS AND LAMINATE COUNTERTOPS SECTION 064113- WOOD ARCHITECTURAL CABINETS AND LAMINATE COUNTERTOPS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION SHEET METAL FLASHING AND TRIM

SECTION SHEET METAL FLASHING AND TRIM SECTION 07620 PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Formed roof drainage sheet metal fabrications. 2. Formed low-slope roof sheet metal fabrications. 1.2 SUBMITTALS A. Shop Drawings: Show

More information

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017

PASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017 SECTION 06100 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Coordinate installation of rough carpentry members specified in other sections.

Coordinate installation of rough carpentry members specified in other sections. 1 1.03 Preservative treated wood materials. Concealed wood blocking, nailers, and C. Miscellaneous wood nailers, furring, and grounds. PART2 2.01 See Section 01 30 00 =Administrative Requirements, for

More information

SECTION PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY

SECTION PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 07312 PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY A. This Section Includes the following: 1. Endureed Dominica PVC thatch shingles. 2. Self- adhering sheet underlayment. B. Related

More information

INSTALLATION SHOP DRAWINGS FOR MINNEAPOLIS, MN

INSTALLATION SHOP DRAWINGS FOR MINNEAPOLIS, MN MINNEAPOLIS, MN 2-0- 2-- General Notes Abbreviations Deviations from Architectural Specifications Deviations from Architectural Drawings ALUM. = ALUMINUM B.O. = BY OTHERS CONT. = CONTINUOUS. = CLEARANCE

More information

Tender No Section St. James - Assiniboia Centennial Pool Fitness Facility Addition Page 1

Tender No Section St. James - Assiniboia Centennial Pool Fitness Facility Addition Page 1 Fitness Facility Addition Page 1 PART 1 GENERAL 1.1 SECTION INCLUDES.1 Finish carpentry items including shop prefabricated casework and countertops..2 Hardware and attachment accessories..3 Wood Benches..4

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 06 WOOD, PLASTICS AND COMPOSITES

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 06 WOOD, PLASTICS AND COMPOSITES SECTION 064023 - INTERIOR ARCHITECTURAL WOODWORK PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Interior standing and running trim. 2. Interior frames and jambs. 3. Stairwork and

More information

SECTION PLASTIC-LAMINATE-FACED ARCHITECTURAL CABINETS

SECTION PLASTIC-LAMINATE-FACED ARCHITECTURAL CABINETS SECTION 064116 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Plastic-laminate-faced architectural cabinets. 2. Wood furring, blocking, shims, and hanging strips for installing plastic-laminatefaced

More information

Installation Instructions for Standard Lap and Self-Aligning Lap Siding

Installation Instructions for Standard Lap and Self-Aligning Lap Siding Installation Instructions for Standard Lap and Self-Aligning Lap Siding 7/16 in. Standard Laps Include: All Old Mill Widths, Cedar Shake Lap and Smooth Lap 1/2 in. Self-Aligning Include: 8 in. and 12 in.

More information

Product Guide Specification For Nonrated & 20-Minute Rated Doors

Product Guide Specification For Nonrated & 20-Minute Rated Doors Woodtech Trading Company 455 Fourth Avenue E.N. P.O. Box 2609 Columbia Falls, MT 59912 800-775-1352 (phone) 800-775-1353 (fax) www.woodtechdoor.com Product Guide Specification For Nonrated & 20-Minute

More information

A. Product Data: For each type of product indicated cabinet hardware and accessories, and finishing materials and processes.

A. Product Data: For each type of product indicated cabinet hardware and accessories, and finishing materials and processes. SECTION 06402 - INTERIOR ARCHITECTURAL WOODWORK PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

INTEX Millwork Solutions SECTION EXTERIOR PVC PERGOLAS (IBC Compliant)

INTEX Millwork Solutions SECTION EXTERIOR PVC PERGOLAS (IBC Compliant) SECTION 066030 EXTERIOR PVC PERGOLAS (IBC Compliant) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and other Contract Documents, listed in the agreement between the Owner and Contractor, apply to

More information

ESR-2648 Reissued May 1, 2012 This report is subject to renewal June 1, 2013.

ESR-2648 Reissued May 1, 2012 This report is subject to renewal June 1, 2013. ICC-ES Evaluation Report ESR-2648 Reissued May 1, 2012 This report is subject to renewal June 1, 2013. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION:

More information

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details. SECTION 081113 - HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: For each type of product indicated.

More information

SECTION CUSTOM CABINETS

SECTION CUSTOM CABINETS PART 1 GENERAL 1.01 SECTION INCLUDES A. Specially fabricated cabinet units. B. Countertops. C. Cabinet hardware. D. Preparation for installing utilities. 1.02 RELATED REQUIREMENTS SECTION 06410 - A. Section

More information

ICC-ES Evaluation Report Reissued June 1, 2010 This report is subject to re-examination in one year.

ICC-ES Evaluation Report Reissued June 1, 2010 This report is subject to re-examination in one year. ICC-ES Evaluation Report ESR-2648 Reissued June 1, 2010 This report is subject to re-examination in one year. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council

More information

Series Sloped glazed Curtain wall. Installation Instructions

Series Sloped glazed Curtain wall. Installation Instructions Series 5600 Sloped glazed Curtain wall Installation Instructions Part NO. Y308 February 2013 SECTION TABLE OF CONTENTS PAGE I. General Notes & Guidelines. 3-4 II. Gutter and Mullion Assembly.. 5 III. End

More information

FASTENERS BUILDING DEPARTMENT

FASTENERS BUILDING DEPARTMENT FASTENERS BUILDING DEPARTMENT 952-446-1660 WWW.CITYOFMINNETRISTA.COM This handout is intended only as a guide and is based in part on the 2015 Minnesota Residential Code, Minnetrista City ordinances, and

More information

Shapes Siding. Perfection Shingles. Chalk Line

Shapes Siding. Perfection Shingles. Chalk Line Snap a Chalk Line Shapes Siding Perfection Shingles Chalk Line To establish a straight reference line to guide the positioning of the starter strip and the first course of siding, snap a chalk line. starter

More information

PRIMED STRAND REVERSIBLE SHAKE

PRIMED STRAND REVERSIBLE SHAKE PRIMED STRAND REVERSIBLE SHAKE PRIOR TO INSTALLATION Inspect product for any issues before installing (breakage, surface defects, foreign objects). Do not install questionable product. Report any problems

More information

SECTION TRAFFIC SIGNAGE

SECTION TRAFFIC SIGNAGE SECTION 10 14 53 TRAFFIC SIGNAGE PART 1 - GENERAL 1.01 SECTION INCLUDES A. Furnishing and installing roadside traffic signage. B. Providing additional traffic signs as required in Sections 01 55 28 Controlling

More information

Kenai Courthouse Expansion 2007 Section 06100

Kenai Courthouse Expansion 2007 Section 06100 Kenai Courthouse Expansion 2007 Section 06100 Rough Carpentry SECTION 06100 - ROUGH CARPENTRY PART 1 GENERAL 1.01 SECTION INCLUDES A. Structural wall framing. B. Preservative treated wood materials. C.

More information

TENANT IMPROVEMENT 16 FEBRUARY WEST 27TH STREET, 4TH FLOOR 100% CD OWNER/BID ADD 1-03/08/2018

TENANT IMPROVEMENT 16 FEBRUARY WEST 27TH STREET, 4TH FLOOR 100% CD OWNER/BID ADD 1-03/08/2018 SECTION 055000 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Slate Shingle Specifications

Slate Shingle Specifications Slate Shingle Specifications California Slate is a proud member of the Slate Roofing Contractors Association of North America, Inc. (SRCA) which publishes Section 07310 Slate Shingles setting forth architectural

More information

AIA Specification. Section Slate Shingles PART 1 GENERAL

AIA Specification. Section Slate Shingles PART 1 GENERAL AIA Specification Section 07315 Slate Shingles PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Installation Instructions for Old Mill Shingle and Designer Shake Lap Siding

Installation Instructions for Old Mill Shingle and Designer Shake Lap Siding Installation Instructions for Old Mill Shingle and Designer Shake Lap Siding Includes: Cove, Craftsmen Staggered, Diamond, Fish Scale, Octagon, Round and Old Mill Shingle Lap Important: Read and understand

More information

B. Section Rough Carpentry: Support framing, grounds, and concealed blocking.

B. Section Rough Carpentry: Support framing, grounds, and concealed blocking. SECTION 06 41 00 - ARCHITECTURAL WOOD CASEWORK PART 1: GENERAL 1.1 SECTION INCLUDES A. Specially fabricated cabinet units. B. Cabinet hardware. C. Factory finishing. 1.2 RELATED REQUIREMENTS A. Division

More information

SECTION INTERIOR ARCHITECTURAL WOODWORK

SECTION INTERIOR ARCHITECTURAL WOODWORK SECTION 06 40 23 INTERIOR ARCHITECTURAL WOODWORK PART 1 GENERAL 1.01 SECTION INCLUDES A. Laminate clad cabinets and custom components. B. Laminate clad countertops. C. Cabinet hardware including countertop

More information

1.04 QUALITY ASSURANCE

1.04 QUALITY ASSURANCE SECTION 07312 ARCHITECTURAL ASPHALT SHINGLES PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Product Guide Specification

Product Guide Specification JELD-WEN, inc. November 2014 825 Shiner Road, PO Box 311 Towanda, Pennsylvania 18848 Toll Free 800-255-0785 Website www.miratectrim.com E-mail miratec@jeld-wen.com Product Guide Specification Specifier

More information

B. Related Sections: The following Sections contain requirements that relate to this Section:

B. Related Sections: The following Sections contain requirements that relate to this Section: SECTION 07311 - ASPHALT SHINGLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information