1 BAR--N-N-EX Antenna barrier for the hazardous area Data sheet 060_en_00 PHOENIX CONTACT Description Using an antenna barrier, you can execute HF outputs of wireless modules with intrinsic safety. The antenna barrier limits the ignition energy in the event of an error. You can connect selected standard antennas from the range of accessories from Phoenix Contact. Features Coax connection with N connectors For earthbound transceiver systems International approvals (ATEX, IECEx) Installation in zone or in the safe area Frequency range 0.7 GHz... 6 GHz Cost-effective use of selected standard antennas in zones 0, and Easy and space-saving installation, wide variety of mounting options inside or outside the control cabinet Follow the instructions described here during installation and observe the safety notes at all times! Make sure you always use the latest documentation. It can be downloaded from the product at phoenixcontact.net/products.

2 BAR--N-N-EX Table of contents Description... Table of contents... Ordering data... Technical data... 5 Structure Mounting options Safety notes Installation notes Intrinsic safety Installation in Zone Example: installing the antenna barrier in zone Example: installing the antenna barrier in zone Installation in potentially explosive area Installation in zone Installation in zone Installing the devices in zone and the antennas in zone or zone Installing the devices in zone and the antennas in zone _en_00 PHOENIX CONTACT

3 BAR--N-N-EX Ordering data Description Type Order No. Pcs./Pkt. Antenna barrier for installation in Ex zone, separates and transmits HF signals with intrinsic safety (Ex i) to an antenna in zone 0, or, 0.7 GHz... 6 GHz frequency range, N (female) -> N (female), ATEX & IECEx approval BAR--N-N-EX 7098 Accessories Type Order No. Pcs./Pkt. Omnidirectional antenna, 868 MHz, dbi, linear vertical, N (female), opening angle h/v 60 /0, IP67, salt water resistant, incl. mounting bracket and mast clips for 0 mm... 5 mm diameter, stainless steel, ATEX & IECEx approval Omnidirectional antenna,. GHz, 6 dbi, linear vertical, opening angle h/v 60 /0, N (female), IP55, incl. mounting bracket and mast clips for 5 mm - 00 mm diameter, stainless steel, ATEX & IECEx approval Panel antenna, 868 MHz,.5 dbi, circular polarized, N (female), IP67, incl. mounting bracket and mast clips for 5 mm mm diameter, stainless steel, ATEX & IECEx approval Panel antenna,./5 GHz, 9 dbi, linear vertical, N (female), IP67, incl. mounting bracket and mast clips for 5 mm - 85 mm diameter, stainless steel, ATEX & IECEx approval -OMNI RAD-ISM-00--OMNI DIR DIR Antenna cable, 0.5 m in length; N (male) -> RSMA (male), 50 Ω impedance RAD-PIG-RSMA/N Antenna cable, m in length; N (male) -> RSMA (male), 50 Ω impedance RAD-PIG-RSMA/N- 906 Antenna cable, m in length; N (male) -> RSMA (male), 50 Ω impedance RAD-PIG-RSMA/N Antenna cable, m in length; N (male) -> RSMA (male), 50 Ω impedance RAD-PIG-RSMA/N Antenna cable, 5 m in length; N (male) -> RSMA (male), 50 Ω impedance RAD-PIG-RSMA/N Antenna cable, m in length, N (male) -> N (male), 50 Ω impedance RAD-CAB-EF9- M Antenna cable, 5 m in length, N (male) -> N (male), 50 Ω impedance RAD-CAB-EF9-5M Antenna cable, 0 m in length, N (male) -> N (male), 50 Ω impedance RAD-CAB-EF9-0M Antenna extension cable, 5 m in length, N (male) -> N (male), RAD-CAB-EF9-5M Ω impedance 00 MHz wireless transceiver with RS-, RS-85 -wire interface, expandable with I/O extension modules, with screw connection, antenna connection: RSMA (female), including DIN rail connector, without antenna 868 MHz wireless transceiver with RS-, RS-85 -wire interface, expandable with I/O extension modules, with screw connection, antenna connection: RSMA (female), including DIN rail connector, without antenna. Vulcanizing sealing tape for external protection of adapters, cable connections, etc. against the effects of weather, roll length: m Angled bracket for individually fixing CN-UB... to housing panels, for example. Primary-switched power supply MINI POWER for DIN rail mounting, input: -phase, output: V DC/,5 A, for the potentially explosive area RAD-00-IFS 905 RAD-868-IFS RAD-TAPE-SV CN-UB/MP-90DEG MINI-PS-00-0AC/DC/.5/EX _en_00 PHOENIX CONTACT

4 BAR--N-N-EX Technical data Electrical data Frequency range Maximum HF output power P i Maximum error voltage U m Insulation voltage input/output Impedance 700 MHz MHz W 5 V AC/DC 75 V AC/DC 50 Ω Attenuation <. db (868 MHz) < 0.9 db (900 MHz) < 0. db (. GHz) < 0.5 db (5. GHz) <.8 db (5.8 GHz) Test voltage. kv AC (50 Hz / s) Maximum capacity 5.6 nf General data Degree of protection Connection method Housing material Dimensions (W/H/D) IP65 N (female) Nickel-plated brass 5 mm x 5 mm x 68.8 mm Ambient conditions Ambient temperature (operation) -0 C C Ambient temperature (storage/transport) -0 C C Approvals / Certificates Conformance IECEx ATEX Please follow the special installation instructions in the documentation! CE-compliant [Ex ia Ma] I [Ex ia Ga] IIC [Ex ia Da] IIIC Ex na [ia Ga] IIC T6 Gc X I (M) [Ex ia Ma] I II () G [Ex ia Ga] IIC II () D [Ex ia Da] IIIC II () G Ex na [ia Ga] IIC T6 Gc X D [db] 0-0,5 - -,5 - -, f [MHz] Figure Attenuation 060_en_00 PHOENIX CONTACT

5 BAR--N-N-EX 5 Structure 68,8 9 Ø5 5. Mounting options 5,8 6,8 Figure Dimensions Figure Control cabinet feed-through Figure Mounting plate Using the CN-UB mounting plate, which is available as an accessory, you can securely mount the antenna barrier, e. g. in the switch cabinet. 060_en_00 PHOENIX CONTACT 5

6 BAR--N-N-EX 6 Safety notes Please make sure that the following notes and instructions are observed. 6. Installation notes The device is a piece of equipment (category ) which belongs to the "Intrinsic Safety" ignition protection class and can be installed in Ex zone as a category device. It meets the requirements of EN :0, EN :0, EN :00, IEC ed. 6.0, IEC ed. 6.0, and IEC ed..0. Installation, operation, and maintenance may only be carried out by qualified electricians. Follow the installation instructions as described. When installing and operating the device, the applicable regulations and safety directives (including national safety directives), as well as general technical regulations, must be observed. For the safety technology data, see this packing slip and the certificates (EC examination certificate and other approvals if appropriate). The device must not be opened or modified. Do not repair the device yourself, replace it with an equivalent device. Repairs may only be carried out by the manufacturer. The manufacturer is not liable for damage resulting from violation. The device must be stopped and immediately removed from the Ex area if it is damaged, was subject to an impermissible load, stored incorrectly or if it malfunctions. Do not subject the device to mechanical and/or thermal loads that exceed the specified limits. The device is not designed for use in atmospheres with a danger of dust explosions. When using the antenna in a non-intrinsically safe circuit, the Ex markings should be obscured. The device can then no longer be operated in intrinsically safe circuits. Observe the specified conditions for use in potentially explosive areas! Install the device in a suitable approved housing (with a minimum of IP5 protection) that meets the requirements of EN Observe the requirements of EN Connection to the intrinsically safe circuit in areas with a danger of dust explosions (zone 0, or ) is only permitted if the equipment connected to this circuit is approved for this zone (e.g., category D, D or D). 6. Intrinsic safety The device may only be operated when the specified atmospheric conditions are met. Check the safety technology data of the power supply device and the antenna and ensure intrinsic safety. The technical data can be found in this package insert and in the approval documents and certificates. Only use devices approved for intrinsically safe circuits. Ground metallic parts or attachments on the antenna barrier and the antenna. The antenna barrier's input power must not exceed P i = W; the approved maximum input voltage is U m = 5 V AC. 6. Installation in Zone Only devices which are designed for operation in Ex zone and are suitable for the conditions at the installation location may be connected to the circuits in the Ex zone. In potentially explosive areas, it is only permitted to disconnect cables when the power is disconnected. Intrinsically safe cables are an exception. 060_en_00 PHOENIX CONTACT 6

7 V OUT DC V.5A V 0V 0V DC OK IN AC 00-0V L NC N If the connector is subject to too high tensile and bending forces, the HF cable must be secured. + V 0V GND CO CO NC L H DIL DIH DI UL +I -I DIP- DI DO DO U I COM NO COM NO NC NC BAR--N-N-EX 7 Example: installing the antenna barrier in zone Observe the specified conditions for use. When installing and connecting the supply and signal circuits observe the requirements of EN/IEC Access to circuits within the device is not permitted. Do not repair the device yourself; replace it with an equivalent device instead. Repairs may only be carried out by the manufacturer. The device must be stopped and immediately removed from the Ex area if it is damaged, has been subjected to an impermissible load, has been stored incorrectly, or if it malfunctions. Ex d MINI SYS POWER 0 RAD-00-IFS 5 6 RAD-DAIO6-IFS Ex i Install the antenna barrier directly in front of the device which requires protection. Installation in a housing with flameproof enclosure type of protection (EN ) Feed the adapter cable of the antenna barrier through the opening provided in the Ex housing. Mount the antenna barrier in the control cabinet with the CN-UB mounting plate (Order No. 807). Connect the adapter cable (5) directly to the wireless module (). Connect the ground connection (screw) via the shortest possible route to the local equipotential bonding using a suitable cable. Cut the leads to the required length. Do not lay protected and unprotected lines immediately parallel to one another. Potential equalization cables are also considered unprotected cables. Connect the antenna barrier to the antenna (8) using an antenna cable (7). Install the antenna cable so that it is fixed in place and screw it in securely at both ends so as to prevent accidental disconnection of the antenna cable. Figure 5 Installation in a housing with flameproof enclosure type of protection (EN ) Key: Flameproof Ex d housing Ex e wiring space 0 V AC/ V DC power supply, MINI-PS-0AC/DC/.5/EX, Order No Wireless module 5 Adapter cable 6 Antenna barrier 7 Antenna cable 8 Antenna 9 Connection for equipotential bonding system 060_en_00 PHOENIX CONTACT 7

8 V OUT DC V.5A V 0V 0V DC OK L NC N IN AC 00-0V If the connector is subject to too high tensile and bending forces, the HF cable must be secured. + V 0V GND CO CO NC L DIL DI DO DO H DIH DIP- DI UL +I -I U I COM NO COM NO NC NC L DIL H DIH DI DI DO DO DIL DIH DI DIL DIH DI COM NO COM NO DI DO DO DIP- COM NO COM NO NC NC +I -I +I -I NC NC DIP- +I -I +I -I BAR--N-N-EX 8 Example: installing the antenna barrier in zone Observe the specified conditions for use. Install the device in a suitable approved housing (with at least IP5 degree of protection) that meets the requirements of EN Observe the requirements of EN In zone, only connect devices to the supply and signal circuits that are suitable for operation of zone and the conditions at the installation location. Access to circuits within the device is not permitted. Do not repair the device yourself; replace it with an equivalent device instead. Repairs may only be carried out by the manufacturer. The device must be stopped and immediately removed from the Ex area if it is damaged, has been subjected to an impermissible load, has been stored incorrectly, or if it malfunctions. Install the antenna barrier directly in front of the device which requires protection. Installation in a housing approved for zone The bore hole in the switch cabinet must have a diameter of 5.9 mm mm. The maximum diameter of the 6. millimeters must not be exceeded! Feed the adapter cable of the antenna barrier through the opening provided in the housing. Screw the antenna barrier (5) to the housing. Connect the adapter cable () directly to the wireless module (). Connect the ground connection (screw) via the shortest possible route to the local equipotential bonding using a suitable cable. Cut the leads to the required length. Do not lay protected and unprotected lines immediately parallel to one another. Potential equalization cables are also considered unprotected cables. Connect the antenna barrier to the antenna (7) using an antenna cable (6). Install the antenna cable so that it is fixed in place and screw it in securely at both ends so as to prevent accidental disconnection of the antenna cable. Tighten all screw connections with 0. Nm. MINI SYS POWER 0 RAD-00-IFS RAD-DAIO6-IFS 8 8 RAD-DI-IFS 8 8 RAD-DOR-IFS RAD-AI-IFS Key: Housing that meets the requirements of EN and EN and at least IP5 (EN 6059) degree of protection Power supply Wireless module and I/O extension modules Adapter cable 5 Antenna barrier 6 Antenna cable 7 Antenna _en_00 PHOENIX CONTACT 8

9 V OUT DC V.5A V 0V 0V DC OK IN AC 00-0V L NC N + V 0V 0 GND CO CO NC L DIL DI DO DO H DIH DIP- DI UL +I -I U I COM NO NC COM NO NC + V 0 V Pwr Dat Err 0 GND CO CO NC + V 0 V Pwr Dat Err 0 GND CO CO NC V OUT DC V.5A V 0V 0V DC OK IN AC 00-0V L NC N + V 0V 0 GND CO CO NC + V 0V Pwr L DIL Dat Err 0 GND CO CO NC DI DO DO H DIH DIP- DI UL +I -I U I COM NO NC COM NO NC + V 0V Pwr Dat Err BAR--N-N-EX 9 Installation in potentially explosive area 9. Installation in zone 9. Installing the devices in zone and the antennas in zone or zone 0 RAD-00-IFS 0 0/ RAD-00-IFS 5 5 RAD-00-IFS GND CO CO NC 5 RAD-00-IFS 5 Figure 6 Installing the devices and antennas in zone Key: Omnidirectional antenna Directional antenna Antenna cable Antenna barrier 5 Adapter cable to the wireless module 9. Installation in zone Figure 8 Installing the devices in zone and the antennas in zone or zone 0 Key: Directional antenna Directional antenna Antenna cable Antenna barrier 5 Adapter cable to the wireless module 9. Installing the devices in zone and the antennas in zone 0 MINI SYS POWER RAD-00-IFS RAD-DAIO6-IFS 0 Figure 7 Installing the devices and antennas in zone MINI SYS POWER RAD-00-IFS RAD-DAIO6-IFS Figure 9 Installing the devices in zone and the antennas in zone 0 060_en_00 PHOENIX CONTACT GmbH & Co. KG 8 Blomberg Germany 9 phoenixcontact.com

MINI MCR-SL-UI-I-LP-NC

MINI MCR-SL-UI-I-LP-NC 2-way isolation amplifier Data sheet 105263_en_02 PHOENIX CONTACT 2013-12-13 1 Description The configurable 2-way isolation amplifiers are used to electrically isolate, convert and filter standard signals.

More information

RAD-IN/OUT-8D. Digital extension modules for the bidirectional wireless system. INTERFACE Data sheet _en_05. 1 Description

RAD-IN/OUT-8D. Digital extension modules for the bidirectional wireless system. INTERFACE Data sheet _en_05. 1 Description RAD-IN/OUT-D Digital extension modules for the bidirectional wireless system INTERFACE Data sheet 102122_en_0 PHOENIX CONTACT 2010-02-2 1 Description The RAD-ISM-...-SET-BD-BUS-ANT bidirectional wireless

More information

TC ANT MOBILE... Mobile communication antennas and antenna cables. Data sheet _en_00. 1 Description

TC ANT MOBILE... Mobile communication antennas and antenna cables. Data sheet _en_00. 1 Description Mobile communication antennas and antenna cables Data sheet 106760_en_00 PHOENIX CONTACT 2015-08-11 1 Description This data sheet describes the accessories for mobile communication products. All mobile

More information

WIRELESS ACCESSORIES. Accessories for wireless transmission systems. INTERFACE Data sheet _en_06. 1 Description

WIRELESS ACCESSORIES. Accessories for wireless transmission systems. INTERFACE Data sheet _en_06. 1 Description Accessories for wireless transmission systems INTERFACE Data sheet 101580_en_06 PHOENIX CONTACT 2010-07-07 1 Description The aim of Phoenix Contact wireless transmission solutions is to provide users with

More information

MACX MCR-EX-SL-RPSSI-I-UP(-SP)

MACX MCR-EX-SL-RPSSI-I-UP(-SP) Supply and input signal conditioner, Ex-i, with wide range supply Data sheet 103561_en_00 PHOENIX CONTACT 2014-08-19 1 Description The MACX MCR-EX-SL-RPSSI-I-UP(-SP) repeater power supply and input signal

More information

Extract from the online catalog

Extract from the online catalog Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation at http://www.download.phoenixcontact.com. The

More information

MACX MCR-UI-UI-UP(-SP)(-NC)

MACX MCR-UI-UI-UP(-SP)(-NC) Configurable 3-way isolating amplifier with safe isolation and wide-range power supply Data sheet 04247_en_02 PHOENIX CONTACT 203-04-0 Description MACX MCR-UI-UI 3-way isolating amplifiers are used to

More information

iant101 Zone 1 Omni Directional Antenna

iant101 Zone 1 Omni Directional Antenna iant101 Zone 1 Omni Directional Antenna External Antenna offering increased flexibility for positioning and greatly enhanced RF Propagation. ATEX Ex t IIIC T85 C Db IECEx Ex t IIIC T85 C Db -40 C to 60

More information

Operating Manual. isolate501

Operating Manual. isolate501 Operating Manual isolate501 Document Number 413569 (See Last Page for Revision Details). Copyright Extronics Ltd, 2015 Page 2 of 21 Contents 1 Introduction... 4 2 Safety Information and Notes... 5 2.1

More information

MCR-SL-CUC Universal current transducer. Data sheet _en_05. 1 Description

MCR-SL-CUC Universal current transducer. Data sheet _en_05. 1 Description Universal current transducer Data sheet 104059_en_05 PHOENIX CONTACT 2011-03-09 1 Description MCR-SL-CUC-...-I and MCR-SL-CUC-...-U active current transducers convert DC, AC, and distorted currents into

More information

MINI MCR-SL-UI-f(-SP)

MINI MCR-SL-UI-f(-SP) Configurable Analog Frequency Transducer INTERFACE Data Sheet PHOENIX CONTACT - 02/2006 Description The configurable analog frequency transducer MINI MCR-SL-UI-f(-SP) is used to convert analog standard

More information

Antennas and Accessories RAD-ISM

Antennas and Accessories RAD-ISM Antennas and Accessories RAD-ISM-24-... 1. Antennas The goal of Phoenix Contact radio transmission solutions is to provide users with the simplest possible access to the radio transmission medium. This

More information

INSTRUCTION MANUAL (ATEX / IECEx)

INSTRUCTION MANUAL (ATEX / IECEx) INSTRUCTION MANUAL (ATEX / IECEx) STExS1 & STExS2 Sounder For use in Flammable Gas and Dust Atmospheres 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT POTENTIAL ELECTROSTATIC CHARGING

More information

Intrinsically Safe Pressure Transmitter for highest pressure applications in hazardous environments Model IS-20-H

Intrinsically Safe Pressure Transmitter for highest pressure applications in hazardous environments Model IS-20-H Replacement product: Model IS-3 Electronic Pressure Measurement Intrinsically Safe Pressure Transmitter for highest pressure applications in hazardous environments WIKA Data Sheet PE 81.51 Applications

More information

Isolators A3/1.

Isolators A3/1. > Compact limit value switch with 2 configurable limiting values and 4... 20 ma output > Suitable for 2-, 3-wire transmitters, 2-wire HART transmitters and ma sources > Intrinsically safe input [Ex ia]

More information

Analog Universal Module HART for Zone 2 Series 9468/33

Analog Universal Module HART for Zone 2 Series 9468/33 > 8 channels can be adjusted individually as analog inputs or outputs > Intrinsically safe inputs/outputs Ex ia > For 0/4 20 ma + HART signals > Line fault monitoring per channel > Diagnostics based on

More information

Signal conditioner - MACX MCR-UI-UI-NC

Signal conditioner - MACX MCR-UI-UI-NC Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid

More information

Isolators A3/1. Vibration Transducer Supply Unit Series

Isolators A3/1. Vibration Transducer Supply Unit Series > For vibration, acceleration and speed sensors in 2- and 3-wire design > Space-saving dual-channel version > Signal frequencies up to 50 khz > Easy setting by means of front-side rotary switch > Galvanic

More information

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted Electrical temperature measurement Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted WIKA data sheet TE 60.34 Applications Machine building, plant and vessel construction

More information

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Switching Repeater Series 9170 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit / short-circuit monitoring and messaging (can be switched

More information

PSD-S AE SM DB/1

PSD-S AE SM DB/1 Siren element, 8 tones, 24 V AC/DC, max. 100 db(a) Data sheet 7944_en_02 PHOENIX CTACT 2015-05-04 1 Description This audible signal element is designed as a component of a modular signal tower. According

More information

Isolators A3/1. Ex i Power Supply Field Circuit Ex i Series

Isolators A3/1. Ex i Power Supply Field Circuit Ex i Series > Intrinsically safe output [Ex ib] IIC/IIB > Stable output voltage > Galvanic isolation between output and power supply > Power supply or 85... 230 V AC > Compact design www.stahl.de 07673E00 Basic function:

More information

MINI-PS AC/24DC/1.3

MINI-PS AC/24DC/1.3 Power supply unit INTERFACE Data sheet 102894_en_03 1 Description PHOENIX CONTACT 2015-11-17 Features MINI POWER power supplies for MCR technology In measurement and control technology (MCR), modular electronics

More information

Inductive sensor slot-type SI2-K08-AP7

Inductive sensor slot-type SI2-K08-AP7 SI2-K08-AP7 Slot sensor, height 8 mm Plastic, polypropylene Mechanical end stop, removable, for analog pointer instruments 3-wire DC, 10 30 VDC NO contact, PNP output Cable connection Wiring diagram Type

More information

Solexy USA, LLC International Blvd Cincinnati, Ohio Phone: Fax:

Solexy USA, LLC International Blvd Cincinnati, Ohio Phone: Fax: OVERVIEW The Solexy RX series explosion proof and intrinsically safe antenna coupler is an integrated protection device that facilitates non-ex certified radio antenna installation in hazardous areas.

More information

Temperature Input Module for Zone 1 Series 9482/32

Temperature Input Module for Zone 1 Series 9482/32 www.stahl.de > 8 channels for temperature sensors > Intrinsically safe inputs Ex ia > For Pt-, Ni- and Cu-resistance temperature detectors according to DIN, IEC and GOST in 2-, 3- and 4-wire circuits >

More information

Intrinsically Safe Pressure Transmitter for applications in hazardous environments and shipbuilding industry Model IS-20-S, IS-21-S, IS-20-F, IS-21-F

Intrinsically Safe Pressure Transmitter for applications in hazardous environments and shipbuilding industry Model IS-20-S, IS-21-S, IS-20-F, IS-21-F Replacement product: Model IS-3 Electronic Pressure Measurement Intrinsically Safe Pressure Transmitter for applications in hazardous environments and shipbuilding industry Model IS-20-S, IS-21-S, IS-20-F,

More information

Digital Input Output Module for Zone 2 Series 9470/33

Digital Input Output Module for Zone 2 Series 9470/33 www.stahl.de > 16 channels can be adjusted in pairs as digital input or output > Intrinsically safe inputs/outputs Ex ia > For contacts, NAMUR proximity switches and low-power solenoid valves > Up to 8

More information

Rosemount 848L Logic Transmitter with FOUNDATION Fieldbus

Rosemount 848L Logic Transmitter with FOUNDATION Fieldbus Logic Transmitter with FOUNDATION Fieldbus Integrates Discrete I/O on a FOUNDATION Fieldbus H1 Segment Reduces Installation and Maintenance Costs with a Single Network for Analog and Discrete devices Easily

More information

PSD-S CE-TM SPRING. Connection element with spring-cage terminal blocks for tube mounting. Data sheet. 1 Description

PSD-S CE-TM SPRING. Connection element with spring-cage terminal blocks for tube mounting. Data sheet. 1 Description Connection element with spring-cage terminal blocks for tube mounting Data sheet 7958_en_02 PHOENIX CONTACT 2015-05-04 1 Description This connection element is provided as a component of a modular signal

More information

Field indicator for current loops with HART communication Models DIH50, DIH52

Field indicator for current loops with HART communication Models DIH50, DIH52 Accessories Field indicator for current loops with HART communication Models DIH50, DIH52 WIKA data sheet AC 80.10 for further approvals see page 6 Applications Process engineering Plant construction General

More information

Incremental encoders Redundant sensing, isolated blind hollow shaft ø mm, cone shaft ø17 mm pulses per revolution

Incremental encoders Redundant sensing, isolated blind hollow shaft ø mm, cone shaft ø17 mm pulses per revolution Features Robust, compact housing Two bearings with large distance, one at each end High shaft load up to 450 N Shock resistant up to 250 g Shaft insulation up to 2.8 kv Highest operating speed 10000 rpm

More information

Installation & Operating Manual. iwap202

Installation & Operating Manual. iwap202 Installation & Operating Manual iwap202 This page is intentionally left blank. Document Number 409345 (based on 407655) (See Last Page for Revision Details) For warranty information, refer to Terms and

More information

Intrinsically safe pressure transmitter MBS 4201, MBS 4251, MBS 4701 and MBS 4751

Intrinsically safe pressure transmitter MBS 4201, MBS 4251, MBS 4701 and MBS 4751 Data sheet Intrinsically safe pressure transmitter MBS 420, MBS 425, MBS 470 and MBS 475 The intrinsically safe pressure transmitter program is designed for use in hazardous environments and offers a reliable

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F

Isolators A3/1.  Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F Series 9160 Rev. F > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de

More information

Assembly. Front view. HiC2441. SL2 1b. Termination Board

Assembly. Front view. HiC2441. SL2 1b. Termination Board SMART Universal Barrier HiC Features Assembly channel isolated barrier V DC supply (bus powered) Analog input, digital input, analog output, digital output No configuration required, device is selfadapting

More information

Binary Output without Power Supply Series 9176

Binary Output without Power Supply Series 9176 Binary Output without Power Supply Series 9176 > For intrinsically safe operation of Ex i solenoid valves, indicators and horns > Power supply by control circuit, loop powered > Intrinsically safe output

More information

Binary Output Series 9175

Binary Output Series 9175 Binary Output > Intrinsically safe output [Ex ia] IIC / [Ex ib] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring (can be switched off) > For use

More information

UNO-PS/1AC/24DC/150W. Primary-switched power supply unit. Data sheet. 1 Description

UNO-PS/1AC/24DC/150W. Primary-switched power supply unit. Data sheet. 1 Description Primary-switched power supply unit Data sheet 106261_en_02 PHOEIX COTACT 2015-05-13 1 Description The power supply makes a worldwide impression thanks to maximum energy efficiency. ow idling losses (o

More information

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted Electrical temperature measurement OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted WIKA data sheet TE 60.31 further approvals see page 10 Applications Machine building, plant

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160

Isolators A3/1.  Transmitter Supply Unit Field Circuit Ex i Series 9160 Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de

More information

D1061S INSTRUCTION MANUAL. RS422/RS485 Fieldbus Isolating Repeater Din-Rail Model D1061S. D RS422 / RS485 Fieldbus Isolating Repeater

D1061S INSTRUCTION MANUAL. RS422/RS485 Fieldbus Isolating Repeater Din-Rail Model D1061S. D RS422 / RS485 Fieldbus Isolating Repeater DS INSTRUCTI MANUAL RS/RS Fieldbus Isolating Repeater Din-Rail Model DS D - RS / RS Fieldbus Isolating Repeater ISM00- Characteristics General Description: The single channel DIN Rail RS / RS Fieldbus

More information

Technical Data. General specifications. Rated operating distance s n 3 mm

Technical Data. General specifications. Rated operating distance s n 3 mm 0102 Model Number Features Direct mounting on standard actuators Compact and stable housing with terminal compartment connection Fixed setting EC-Type Examination Certificate TÜV99 ATEX 1479X Usable up

More information

Isolating Repeater Input Series 9163

Isolating Repeater Input Series 9163 > For 4-wire HART transmitters and voltage sources > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2 (IEC 61508) > High accuracy www.stahl.de

More information

MCR-VAC-UI-0-DC. Voltage transducer for AC voltages. INTERFACE Data sheet _en_02. 1 Description

MCR-VAC-UI-0-DC. Voltage transducer for AC voltages. INTERFACE Data sheet _en_02. 1 Description Voltage transducer for AC voltages TERFACE Data sheet 006_en_0 PHOENIX CONTACT 00-0- Description The MCR voltage transducer measures AC voltages in several signal ranges from 0... ±4 V AC to 0... ±30 V

More information

Pressure transmitters MBS 4201, MBS 4251, MBS 4701 and MBS 4751

Pressure transmitters MBS 4201, MBS 4251, MBS 4701 and MBS 4751 060R9345 Instructions Pressure transmitters MBS 4201, MBS 4251, MBS 4701 and MBS 4751 Content Page 1 Description/application 2 Identification 3 Specifications 4 Safety instructions 5 Installation/dimensions

More information

Isolators Isolating Repeater Field Circuit Ex i ISpac 9165/ s Art. No

Isolators Isolating Repeater Field Circuit Ex i ISpac 9165/ s Art. No 9165/16-11-10s 207909 Compact one- and two-channel Ex i output isolating repeater wire-breakage and short-circuit monitoring system, which can be disconnected and features a signalling contact can be used

More information

D1061S INSTRUCTION MANUAL. RS422/RS485 Fieldbus Isolating Repeater Din-Rail Model D1061S. D RS422 / RS485 Fieldbus Isolating Repeater

D1061S INSTRUCTION MANUAL. RS422/RS485 Fieldbus Isolating Repeater Din-Rail Model D1061S. D RS422 / RS485 Fieldbus Isolating Repeater DS INSTRUCTI MANUAL RS/RS Fieldbus Isolating Repeater Din-Rail Model DS D - RS / RS Fieldbus Isolating Repeater ISM00- Characteristics General Description: The single channel DIN Rail RS / RS Fieldbus

More information

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series Transmitter Supply Unit Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring and messaging for input

More information

Digital Input Output Module 24 V for Ex n Zone 2 Series 9472/35

Digital Input Output Module 24 V for Ex n Zone 2 Series 9472/35 www.stahl.de > 16 channels can be adjusted in pairs as digital inputs or outputs > Suitable for NAMUR proximity switches, 3-wire PNP proximity switches, contacts and solenoid valves (24 V / 0.5 A). > Up

More information

Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

Single-Channel Safety Barriers with Electronic Current Limitation Series 9004 Single-Channel Safety Barriers with Electronic Current Limitation > Broad product range for all standard applications in the world of automation > Flexible and space saving > Time saving installation due

More information

PRetrans Table of contents

PRetrans Table of contents HART TRANSPARENT REPEATER PRetrans 5106 Table of contents Warnings 16 Safety instructions 17 EC Declaration of Conformity 19 How to demount SYSTEM 5000 20 Application 21 Technical characteristics 21 Mounting

More information

4-Port Antenna Frequency Range Dual Polarization HPBW Adjust. Electr. DT set by

4-Port Antenna Frequency Range Dual Polarization HPBW Adjust. Electr. DT set by 4-Port Antenna Frequency Range Dual Polarization HPB Adjust. Electr. DT set by R1 698 960 X 65 2 12 R2 698 960 X 65 2 12 4-Port Antenna 698 960/698 960 65 /65 15.5/15.5dBi 2 12 /2 12 T Type No. 80010901

More information

Transducer transmitter BILT 4 II 2(1) G. Technical Manual

Transducer transmitter BILT 4 II 2(1) G. Technical Manual GB Transducer transmitter BILT 4 II 2(1) G Technical Manual Transducer transmitter BILT 4 Contents Introduction General... 3 Ex.safety description... 4 Technical data... 5 Installation General... 6 Mechanical

More information

Incremental encoders Blind hollow shaft or cone shaft pulses per revolution

Incremental encoders Blind hollow shaft or cone shaft pulses per revolution Features TTL output driver for cable length up to 550 m Very high resistance to shock and vibrations Hybrid bearing for extended service life Shaft insulation up to.8 kv Large terminal box, turn by 80

More information

Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version

Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version Temperature Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version WIKA data sheet TE 15.01 for further approvals see page 10 Applications

More information

A6500-UM Universal Measurement Card

A6500-UM Universal Measurement Card Specifications Sheet A6500-UM Universal Measurement Card The A6500-UM Universal Measurement Card is a component of the CSI 6500 ATG machinery protection system. The card is equipped with 2 sensor input

More information

Operator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique

Operator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique Operator Manual Transmitters Series KAT-... Analog transmitters in 2-wire technique Important Safety Notes! In the case of non-observance of the installation and safety notes or improper use of the transmitter

More information

Fieldbus Isolating Repeater Series 9185/11

Fieldbus Isolating Repeater Series 9185/11 www.stahl.de > For operation of the intrinsically safe Profibus DP (RS-485 IS to PNO standard) > Intrinsically safe fieldbus RS-422, RS-485 [Ex ib] IIC > Galvanic isolation between RS-422 / RS-485, RS-232,

More information

Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version

Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version Electrical temperature measurement Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version WIKA data sheet TE 15.01 Applications Process industry Machine building

More information

58 SERIES. Relay interface modules 7-10 A 58.P3 58.P4

58 SERIES. Relay interface modules 7-10 A 58.P3 58.P4 58 58 3 & 4 CO relay interface modules, 31 mm wide with Push-in terminals Ideal interface for PLC and electronic systems 58.P3 58.P4 Type 58.P3 3 CO 10 A Push-in terminals Type 58.P4 4 CO 7 A Push-in terminals

More information

Digital Input Output Module for Zone 2 Series 9470/33

Digital Input Output Module for Zone 2 Series 9470/33 www.stahl.de > 16 can be adjusted in pairs as digital input or output > Intrinsically safe inputs/outputs Ex ia > For contacts, NAMUR proximity switches and low-power solenoid valves > Up to 8 can be used

More information

Digital I/O Coupler (4-wire) Series 9413/21

Digital I/O Coupler (4-wire) Series 9413/21 Digital /O Coupler (4wire) > The digital /O coupler is used to connect 8 intrinsically safe contacts or proximity initiators and 4 intrinsically safe solenoid valves to a FOUNDATON TM fieldbus H1. > Galvanic

More information

Pressure transmitter AKS 32 and AKS 33

Pressure transmitter AKS 32 and AKS 33 Data sheet Pressure transmitter AKS 32 and AKS 33 AKS 32 and AKS 33 are pressure transmitters that measure a pressure and convert the measured value to a standard signal: y 1 5 V DC or 0 10 V DC for AKS

More information

12-Port Antenna Frequency Range Dual Polarization HPBW Adjust. Electr. DT set by

12-Port Antenna Frequency Range Dual Polarization HPBW Adjust. Electr. DT set by 12-Port Antenna Frequency Range Dual Polarization HPB Adjust. Electr. DT set by R1 R2 Y1 Y2 Y3 Y4 698 803 824 894 1695 2690 1695 2690 1695 2690 1695 2690 X X X X X X 65 65 65 65 65 65 1.5 10 1.5 10 2.5

More information

12-Port Antenna Frequency Range Dual Polarization HPBW Adjust. Electr. DT set by

12-Port Antenna Frequency Range Dual Polarization HPBW Adjust. Electr. DT set by 12-Port Antenna Frequency Range Dual Polarization HPB Adjust. Electr. DT set by R1 R2 Y1 Y2 Y3 Y4 698 803 824 894 1695 2690 1695 2690 1695 2690 1695 2690 X X X X X X 65 65 65 65 65 65 2 12 2 12 2 14 2

More information

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/ > 4 channels for 2-wire HART transmitters and 4 channels for 4-wire HART transmitters > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit

More information

Process transmitter Model UPT-20, with pressure port Model UPT-21, with flush diaphragm

Process transmitter Model UPT-20, with pressure port Model UPT-21, with flush diaphragm Electronic pressure measurement Process transmitter Model UPT-20, with pressure port Model UPT-21, with flush diaphragm WIKA data sheet PE 86.05 Applications Process technology Machine building and plant

More information

100/200/400 t. Self-centering pendulum lead cells. Data sheet. Special features

100/200/400 t. Self-centering pendulum lead cells. Data sheet. Special features C16A 100/200/400 t Self-centering pendulum lead cells Special features - Self restoring function - Nominal (rated) loads: 100 t, 200t and 400t - Simple installation - Rust resistant materials, laser welded,

More information

6-Port Antenna Frequency Range Dual Polarization HPBW Adjust. Electr. DT set by

6-Port Antenna Frequency Range Dual Polarization HPBW Adjust. Electr. DT set by 6-Port Antenna Frequency Range Dual Polarization HPBW Adjust. Electr. DT set by R1 Y1 Y2 698 960 1710 2690 1710 2690 X X X 65 65 65 1 10 2.5 12 2.5 12 6-Port Antenna 698 960/1710 2690/1710 2690 65 /65

More information

OPTIWAVE 7300 C Supplementary instructions

OPTIWAVE 7300 C Supplementary instructions OPTIWAVE 7300 C Supplementary instructions Radar (FMCW) Level Transmitter for agitated liquids in process applications Supplementary Instructions for ATEX applications KROHNE CONTENTS OPTIWAVE 7300 C General

More information

CE620. Piezoelectric accelerometer with integrated electronics. IECEx

CE620. Piezoelectric accelerometer with integrated electronics. IECEx Piezoelectric accelerometer with integrated electronics FEATURES» From the Vibro-Meter product line» Voltage output signal: 100 or 500 mv/ g» Frequency response: 2 Hz to 10 khz» Temperature range: 55 to

More information

OPTIWAVE 1010 Technical Datasheet

OPTIWAVE 1010 Technical Datasheet OPTIWAVE 1010 Technical Datasheet Radar (FMCW) Level Transmitter for bypass chambers and magnetic level indicators (BM 26 Advanced) Device welded to a bypass chamber with an optional IP68 level indicator

More information

MACX MCR-EX-T-UI-UP. Extract from the online catalog. Order No.:

MACX MCR-EX-T-UI-UP. Extract from the online catalog. Order No.: Extract from the online catalog MACX MCR-EX-T-UI-UP Order No.: 2865654 Freely programmable Ex-i temperature transducer with analog output and 1 limit value relay, standard configuration, resistance thermometer

More information

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted Temperature OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted WIKA data sheet TE 60.31 further approvals see page 11 Applications Machine building, plant and vessel construction

More information

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1. General data Mounting On linear actuators On quarter turn actuators ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR) Range of stroke: 3... 130 mm Integrated to VDI/VDE 3847-2 or VDI/VDE 3845 Angle

More information

TRIO-PS-2G/1AC/24DC/5

TRIO-PS-2G/1AC/24DC/5 TRIOPS2G/1AC/24DC/5 Power supply unit Data sheet 105900_en_01 PHOENIX CONTACT 20150831 1 Description TRIO POWER power supplies with standard functionality The power supplies of the TRIO POWER family convince

More information

QUINT-PS/ 3AC/24DC/10

QUINT-PS/ 3AC/24DC/10 Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system

More information

Digital Input Module NAMUR Ex i / I.S. Inputs, 16 Channels for Zone 1 / Div. 1 Series 9470/22

Digital Input Module NAMUR Ex i / I.S. Inputs, 16 Channels for Zone 1 / Div. 1 Series 9470/22 www.stahl.de > 16 channels for contacts and NAMUR proximity switches (EN 60947-5-6) > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit

More information

Two-channel safety barriers Series 9002

Two-channel safety barriers Series 9002 Two-channel safety s Series 00 > Wide product range for all standard applications of the automation > Flexible and space-saving available in single and double channel versions > Time-saving installation

More information

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5.

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5. General data Mounting On linear actuators On quarter turn actuators ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR) Range of stroke: 3... 130 mm Integrated to VDI/VDE 3847-2 or VDI/VDE 3845 Angle

More information

STEP-UPS/24DC/24DC/3. Uninterruptible power supply. Data sheet. 1 Description. Features

STEP-UPS/24DC/24DC/3. Uninterruptible power supply. Data sheet. 1 Description. Features Uninterruptible power supply Data sheet 105623_en_00 PHOENIX CTACT 2013-06-07 1 Description Uninterruptible power supply units continue to deliver power even in the event of mains breakdowns or failures.

More information

OPTITEMP TT 10 C/R Technical Datasheet

OPTITEMP TT 10 C/R Technical Datasheet OPTITEMP TT 10 C/R Technical Datasheet Analogue 2-wire temperature transmitter Temperature linear 4...20 ma output Rangeable with solder pads and potentiometers Easy wiring through large center hole The

More information

ICARUS ELECTRONIC GAS VOLUME CONVERTER

ICARUS ELECTRONIC GAS VOLUME CONVERTER ICARUS ELECTRONIC GAS VOLUME CONVERTER 1. INTRODUCTION 2. TECHNICAL DETAILS ICARUS is an electronic volume converter which, combined with a gas meter, provides the gas measurement in Sm3, calculated at

More information

LTE: 6 dbi GPS: 21 dbi Wi-Fi: 7.5 dbi. IoT. 2x2 MIMO GPS included IP 68

LTE: 6 dbi GPS: 21 dbi Wi-Fi: 7.5 dbi. IoT. 2x2 MIMO GPS included IP 68 A P P L I C A T I O N A R E A S ANTENNAS 3-IN-1 TRANSPORTATION & IOT/M2M ANTENNA 2X2 LTE (MIMO), GPS/GLONASS 690-960; 1710-2700 & 3200-3800 MHz LTE: 6 dbi GPS: 21 dbi Wi-Fi: 7.5 dbi IoT 2x Omnidirectional

More information

Digital Input Output Module for Zone 1 Series 9470/32

Digital Input Output Module for Zone 1 Series 9470/32 www.stahl.de > 16 can be adjusted in pairs as digital input or output > Intrinsically safe inputs/outputs Ex ia > For contacts, NAMUR proximity switches and low-power solenoid valves > Up to 8 can be used

More information

Two-channel safety barriers Series 9002

Two-channel safety barriers Series 9002 Two-channel safety s Series 00 > Wide product range for all standard applications of the automation > Flexible and space-saving available in single and double channel versions > Time-saving installation

More information

Resistance thermometer Model TR30, compact design

Resistance thermometer Model TR30, compact design Electrical temperature measurement Resistance thermometer Model TR30, compact design WIKA data sheet TE 60.30 Applications Machine building, plant and vessel construction Propulsion technology, hydraulics

More information

SINEAX B 811 Power Pack with additional Functions

SINEAX B 811 Power Pack with additional Functions SINEA B 8 for intelligent and conventional s, in housing S7 for rail and wall mounting 002 II () G Application The power supply unit SINEA B 8 (Figure ) provides the DC power supply for s and transfers

More information

MJK Expert 700 / 800 / 900 / 1100 / 2100 MJK Expert 1400 / 3400

MJK Expert 700 / 800 / 900 / 1100 / 2100 MJK Expert 1400 / 3400 Data Sheet MJK Expert 700 / 800 / 900 / 1100 / 2100 MJK Expert 1400 / 3400 Submersible Hydrostatic s Rugged and versatile We reserve the right to continuously improve our products and make any change in

More information

Extract from the online catalog

Extract from the online catalog Please note that the data given here has been taken from the online catalog. For comprehensive information and data, please refer to the user documentation at http://www.download.phoenixcontact.com. The

More information

MINI-PS AC/2X15DC/1

MINI-PS AC/2X15DC/1 MII-PS-100-240AC/2X15DC/1 Power supply unit ITERFACE Data sheet 100299_en_04 1 Description PHOEIX COTACT - 2010-10-20 Features MII POWER is the extremely slim power supply unit with constructional widths

More information

Rosemount 148 Temperature Transmitter

Rosemount 148 Temperature Transmitter Product Data Sheet Rosemount 148 Rosemount 148 Temperature Transmitter Provides an installation-ready solution for temperature monitoring applications using Complete Point Solutions (CPS) Increases measurement

More information

iant200 iant212 iant213 iant214 iant215 iant216 iant217 iant218 iant219 iant220 iant221 iant222 Operating Manual iant2xx Series of Antennas

iant200 iant212 iant213 iant214 iant215 iant216 iant217 iant218 iant219 iant220 iant221 iant222 Operating Manual iant2xx Series of Antennas iant200 iant212 iant213 iant214 iant215 iant216 iant217 iant218 iant219 iant220 iant221 iant222 Operating Manual iant2xx Series of Antennas This page is intentionally left blank. Document Number 403449

More information

Engineering Guideline. pac-carriers Type for Yokogawa Centum VP

Engineering Guideline. pac-carriers Type for Yokogawa Centum VP Engineering Guideline pac-carriers Type 9195 for Yokogawa Centum VP pac-carrier Type 9195 2 Engineering Guideline / Yokogawa Centum VP 26.0.2018 pac-carrier Type 9195 Integrated solutions for Yokogawa

More information

ED701 General Industry Pressure Transmitter

ED701 General Industry Pressure Transmitter ED701 General Industry Pressure Transmitter Standard industrial process connections Complete range of electrical connections 4... 20 ma and Voltage outputs Accuracy: 0.1%, 0.2% and 0.4% FS Quick response

More information

Intrinsically safe pressure transmitter For applications in hazardous areas Models IS-20-S, IS-21-S, IS-20-F, IS-21-F

Intrinsically safe pressure transmitter For applications in hazardous areas Models IS-20-S, IS-21-S, IS-20-F, IS-21-F Replacement product: Model IS-3 Electronic pressure measurement Intrinsically safe pressure transmitter For applications in hazardous areas Models IS-20-S, IS-21-S, IS-20-F, IS-21-F WIKA data sheet PE

More information

Wireless Multi Discrete Input Transmitter Series XYR 6000, Model STXW500 Specifications

Wireless Multi Discrete Input Transmitter Series XYR 6000, Model STXW500 Specifications Wireless Multi Discrete Input Transmitter Series XYR 6000, Model STXW500 Specifications 34-XY-03-33 February 2010 Model STXW500 - Up to 3 discrete inputs) Introduction Building upon the tremendously successful

More information

Safety Manual. Omni-ID UHF Tags

Safety Manual. Omni-ID UHF Tags Safety Manual Omni-ID UHF Tags This page is intentionally left blank. Document Number 330556 (See Last Page for Revision Details) 2012 Extronics Limited. This document is Copyright Extronics limited. Extronics

More information

INSTRUCTION MANUAL. SIL 3 - SIL 2 Digital Output Loop/Bus Powered DIN-Rail Models D1040Q, D1041Q, D1042Q, D1043Q, D1040Q - D1041Q - D1042Q - D1043Q

INSTRUCTION MANUAL. SIL 3 - SIL 2 Digital Output Loop/Bus Powered DIN-Rail Models D1040Q, D1041Q, D1042Q, D1043Q, D1040Q - D1041Q - D1042Q - D1043Q DQ DQ DQ D3Q INSTRUCTION MANUAL SIL 3 SIL Digital Output Loop/Bus Powered DINRail Models DQ, DQ, DQ, D3Q, D* SIL 3 SIL Digital Output Loop / Bus Powered ISM SIL Applications For Safety Related System and

More information