Ultrasonic Level Measurement prosonic M FMU 40/41/43
|
|
- Scot Fisher
- 6 years ago
- Views:
Transcription
1 Technical Information TI 365F/24/ae Ultrasonic Level Measurement prosonic M FMU 40/41/43 Compact transmitters for non-contact level measurement of fluids, pastes and coarse bulk materials FMU 41 FMU 40 FMU 43 Application The compact Prosonic M transmitters are used for continuous, non-contact level measurement in fluids and coarse bulk materials. Additionally, the sensors can be used for flow measurement in open channels and measuring weirs. The following interfaces are available for system integration: HART (standard), 4 to 20 ma PROFIBUS-PA Foundation Fieldbus The maximum measuring range for Prosonic M sensors are: FMU 40: Fluids, 16 feet (5 m) Bulk solids, 6 feet (2 m) FMU 41: Fluids, 26 feet (8 m) Bulk solids, 12 feet (3.5 m) FMU 43: Fluids, 50 feet (15 m) Bulk solids, 23 feet (7 m) Features and benefits Simple, menu-guided on-site operation with four-line plain text display Envelope curves on the on-site display for simple diagnosis Easy operation, diagnosis and measuring point documentation with the supplied ToF Tool operating program Alignable NEMA 6P (IP 68) aluminum housing Optional remote display and operation Installation via 1-1/2 NPT, 2 NPT or 4 universal slip-on flange Integrated temperature sensor for Time-of-Flight correction provides accurate measurements, even with temperature changes Linearization function (up to 32 points) for measured value output in any unit of length, volume, or flow rate Non-contact measurement method, therefore almost independent of product properties The Power of Know How
2 Function and system design Measuring principle BD BD: Blocking Distance E: Empty calibration F: Full calibration (span) D: Distance from sensor membrane to product level L: Level E F D L 20 ma 100% Sensor FMU 40 FMU 41 FMU 43 BD 9.84" (250 mm) 15.7" (400 mm) 23.6" (600 mm) Max. range in liquids 16 ft (5 m) 26 ft (8 m) 50 ft (15 m) Max. range in solids 6.5 ft (2 m) 11.5 ft (3.5 m) 23 ft (7 m) 4 ma 0% Time-of-Flight method The Prosonic M sensor transmits ultrasonic pulses in the direction of the product surface. The ultrasonic pulse is reflected back and received by the sensor. The Prosonic M electronics measures the time t between pulse transmission and reception. Using the time t (and the velocity of sound c), the system calculates the distance D between the sensor membrane and the product surface D = c x t/2 As the device knows the empty distance E from the user entry, it can calculate the level as follows: L = E - D An integrated temperature sensor compensates for changes in the velocity of sound caused by temperature changes. Interference echo suppression The interference echo suppression feature ensures that interference echos (such as welded joints, internal ladder steps, edges and installations) are not interpreted as a level echo. Calibration Enter the empty distance E and the span F to calibrate the system. Blocking distance Span F may not extend into the blocking distance BD. Level echos within the blocking distance cannot be evaluated due to the transient characteristics of the sensor. Equipment architecture 4 to 20 ma ouput with HART protocol PLC - COMMUWIN II - ToF Tool - ToF Tool Commubox FXA 191 Service adapter FXA 193 Transmitter power supply unit RMA 422 or RN 221 N (communication resistor included) Operating and display module VU 331 FXA 191 or DXR 275 HART handheld DXR 275 The Prosonic M can be operated on-site using either the display module VU 331 or the supplied ToF Tool program. The system can also be operated remotely using the HART handheld terminal DXR 275 or using the ToF Tool. NOTE: If a HART communication resistor is not built into the power supply device, a 250Ω communication resistor in the 2-wire line must be inserted. 2
3 Profibus-PA protocol Personal computer e.t. with Commuwin II or ToF Tool and Profibard (Proficard) PLC Segment coupler PROFIBUS-DP PROFIBUS-PA Operating and display module VaU 331 Additional functions (valves, etc.) Levelflex Prosonic Micropilot FXA 193 ToF Tool A maximum of 32 transmitters (8 if mounted in an explosion hazardous area) can be connected to the bus. Both on-site as well as remote operation are possible. Foundation Fieldbus (FF) protocol Personal computer e.g. with NI-FBUS configurator Power supply Power conditioner T T Operating and display module VaU 331 Additional functions (valves, etc.) Levelflex Micropilot Prosonic FXA 193 ToF Tool A maximum of 32 transmitters (standard or hazardous) can be connected to the bus. For intrinsically safe circuits, the maximum number of transmitters depends on the established rules and standards for intrinsically safe circuits (EN ) and proof of instrinsic safety. Both on-site and remote operation are possible. 3
4 Input Measured variable Measuring range The distance D between the sensor membrane and the product surface is measured (page 2). Using the linearization function, the device uses D to calculate: Level L in any units Volume V in any units Flow Q across measuring weirs or open channels in any units The measuring range is limited by the range of a sensor. The sensor range is, in turn, dependent on operating conditions. The diagram below defines the effect that echo attenuation has on the sensor s measuring range. The ideal echo attenuation curves for each sensor are shown in the diagram. A number of echo attenuation sources that affect proper sensor selection are shown in the table. 1. Determine which of the influences shown are appropriate for your process. 2. Add the corresponding attenuation values. 3. From the total attenuation, use the diagram to calculate the sensor range. Fluid surface Calm Waves Strong turbulence (agitators, etc.) Foaming Bulk material surface Hard, rough (e.g. rubble) Soft (e.g. peat, dust-covered clinker) Dust No dust formation Little dust formation Heavy dust formation Filling curtain in detection range None Smalll quantities Large quantities Temperature difference between sensor and surface To 68 F (20 C) To 104 F (40 C) To 176 F (80 C) Attenuation 0 db 5 to 10 db 10 to 20 db Consult factory Attenuation 40 db 40 to 60 db Attenuation 0 db 5 db 5 to 20 db Attenuation 0 db 5 to 10 db 10 to 40 db Attenuation 0 db 5 to 10 db 10 to 20 db range in feet FMU 43 Example (for FMU 43) Approximate db Dust-covered rubble 50 Medium dust development 10 Not in filling curtain 0 Temperature differential < 68 F 0 FMU db Approximate range = 15.5 ft. FMU Attenuation / db Operating frequency Sensor FMU 40 FMU 41 FMU 43 Frequency approx. 70 khz approx. 50 khz approx. 35 khz Pulse frequency 2-wire devices, maximum 0.5 Hz 4-wire devices, maximum 2 Hz The exact values are dependent on the type of device and supply voltage. 4
5 Output Output signal Signal on alarm Load HART Output damping Linearization 4 to 20 ma with HART protocol Profibus-PA Foundation Fieldbus (FF) Error information can be accessed via the following interfaces: On-site display (error symbol, error code and plain text description) Current output (configurable) Digital interface Minimum load for HART communication, 250Ω Freely selectable, 0 to 255 seconds The linearization function of the Prosonic M allows conversion of the measured value into any unit of length or volume. In open channels or measuring weirs, it is also possible to linearize the flow. Linearization tables for calculating volume in horizontal cylindrical tanks are preprogrammed. You can also enter any number of other tables containing up to 32 value pairs either manually or semi-automatically (by filling the vessel under controlled conditions). You can use the ToF Tool operating program to calculate the table automatically for any tank form and then enter it into the device. Power supply Terminal compartment F 12 Housing T 12 Housing Sealed terminal compartment In the F 12 housing, the terminals are located underneath the housing cover. In the T 12 housing, they are under the cover of the separate terminal compartment. Fieldbus plug connector Foundation Fieldbus 7/8" plug Profibus M 12 plug For the Foundation Fieldbus version, a 7/8 plug connector is available. For the Profibus-PA version, an M12 plug connector is available Both versions are supplied fully wired. 5
6 Terminal assignment 4 to 20 ma with HART, 2-wire 4 to 20 ma with HART, active, 4-wire Power: 4 to 20 ma 0 to 20 ma AC / DC Auxiliary power Communication resistor (> 250 Ω) alternative Commubox FXA 191 DXR 275 Test sockets (via interlock diode) alternative Commubox FXA 191 DXR 275 Communication resistor (> 250 Ω) L- L+ I+ I- Plant ground I+ I- L1/L+ N/L- Plant ground Connect the connecting line to the screw terminals (up to 18 AWG) in the terminal compartment Use 2-wire twisted pair cable with shield for the connection Units are internally protected against reverse polarity, RFI and over-voltage peaks PROFIBUS-PA Foundation Fieldbus T-Box 1 2 PA+ PA- 3 4 Plant ground FF+ FF- Plant ground The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also provides the auxiliary power. Please use 2-wire twisted pair cable with shield. Refer to the following operating manuals for information on cable types, and how to set and ground the network: BA 198F/00/en PROFIBUS-DP/-PA: Guidelines for planning and commissioning BA 013S/04/en Foundation Fieldbus, Installation and Commissioning Guidelines Cable entry Power supply Cable gland: M20x1.5, recommended cable diameter 0.23 to 0.39 (6 to 10 mm) Cable entry 1/2 NPT or G 1/2 PROFIBUS-PA M12 plug Foundation Fieldbus 7/8 plug The following values are the voltages across the terminals directly at the instrument. Version 2-wire HART Fixed current (measured value transmitted by HART) 4-wire Standard IS XP Standard IS DC AC Current consumption 4 ma 20 ma 4 ma 20 ma 4 ma 20 ma 11 ma 11 ma Terminal voltage Min. Max. 14 V 8V 14 V 8V 14 V 11 V 36 V 36 V 30 V 30 V 30 V 30 V 10 V 36 V 10 V 30 V 10.5 VDC 32 VDC 90 VAC 253 VAC 6
7 Power consumption Current consumption (2-wire units) HART ripple Maximum noise HART Galvanic isolation 2-wire, 51 mw to 800 mw 4-wire AC, maximum 7W 4-wire DC FMU 40/41, 330 mw to 830 mw 4-wire DC FMU 43, 600 mw to 1 W HART, 3.6 to 22 ma PROFIBUS-PA, maximum 13 ma Foundation Fieldbus, maximum 15 ma 47 to 125 Hz: Vpp = 200 mv (measured at 500 W) 500 Hz to 10 khz: Vrms = 2.2 mv (measured at 500 W) With 4-wire units, the evaluation electronics and power supply voltage are galvanically isolated from each other Performance characteristics Reference operating conditions Measuring error Measured value resolution Reaction time Temperature = 68 F (20 C) Pressure = 14.7 psia (1013 mbar abs.) Humidity = 50% Ideal reflective surface (calm, smooth fluid surface) No interference reflections within signal beam area Set application parameters: Tank shape = flat ceiling Medium property = liquid Process conditions = calm surface Typical specifications for reference operating conditions (include linearity, repeatability, and hysteresis): FMU 40 / 41: ± 0.08 (2 mm) or 0.2% of set measuring range, which ever is greater FMU 43: ± 0.15 (4 mm) or 0.2% of set measuring range, which ever is greater FMU 40 / 41: 0.04 (1 mm) FMU 43: 0.08 (2 mm) The reaction time depends on the parameter settings (minimum 0.5 seconds for 4-wire devices, minimum 2 seconds for 2-wire devices) 7
8 ENDRESS+HAUSER Prosonic M Prosonic M FMU 40/41 installation variants Installation conditions Installation with counter nut Installation with sleeve EPDM sealing ring supplied Counter nut supplied for G 1-1/2 and G2 instruments Installation with extension bracket Installation with adapter flange Adapter flange EPDM sealing ring supplied Sensor Nozzle FMU 43 installation variants Installation with universal slip-on flange Installation with mounting bracket ENDRESS+HAUSER Prosonic M Slip-on flange Nozzle Sensor Hazardous area or non-hazardous Non-hazardous area 8
9 ENDRESS+HAUSER Prosonic M ENDRESS+HAUSER Prosonic M Prosonic M Installation conditions for level measurement /6D 5 7 D 6 α L r α r = L tan 2 Sensor FMU 40 FMU 41 FMU 43 α L 16 ft (5 m) 26 ft (8 m) 50 ft (15 m) r 18.9" (480 mm) 30.3" (770 mm) 31.1" (790 mm) Do not install the sensor in the middle of the tank (3). Mounting distance between vessel wall and sensor (1) should be 1/6 of the tank diameter. Use a protective cover (see accessories, page 18), to protect the sensor from rain or direct sunlight (2). Avoid measurements in the filling stream area (4). Make sure that equipment (5) such as limits swtiches, temperature sensors, etc. are not located in the beam angle α. In particular, symmetrical equipment (6) such as heating coils, baffles, stationary ladder rungs etc. can influence measurement. Align the sensor so that it is vertical to the product surface (7). Never install two ultrasonic measuring devices in the same vessel, as the two signals may affect each other. To estimate the transmitted echo beam and its detection range, use the 3 db emitting angle α (see Figure above). Installation in narrow shafts In narrow shafts with strong interference echoes, we recommend using an ultrasound guide pipe (e.g. PE or PVC wastewater pipe) with a minimum diameter of 4 (100 mm). Make sure that the pipe does not accumulate dirt, clean pipe at regular intervals. Venting hole 9
10 Installation conditions for flow measurements Install the Prosonic M at the inflow side, as close above the maximum water level H max as possible, plus the blocking distance BD. Position the Prosonic M in the middle of the channel or weir. Align the sensor membrane parallel to the water surface. Keep to the installation distance of the channel or weir. The Flow to Level linearization curve ( Q/h curve ) can be entered using the ToF Tool or manually via the on-site display. Example: Khafagi-Venturi flume BD inflow outflow Khafagi - Venturi - flume H max direction of flow 1 x b o b o Blocking distance with nozzle installation BD SD FMU 40/41 FMU 43 FMU 40 D (mm) max. L (mm) 1.97" (50) 3.15" (80) 3.94" (100) approx. 3.15" (80) approx. 7.87" (200) approx (250) E F L D D L D (mm) 3.15" (80) 3.94" (100) FMU 41 max. L (mm) approx. 7.87" (200) approx (250) FMU 43 D > approx. 3.94" (100) L < approx. 11.8" (300) BD: Blocking Distance SD: Safety Distance E: Empty calibration F: Full calibration (span) Sensor BD Max. range FMU 40 FMU 41 FMU " (250) 15.7" (400) 23.6" (600) in liquids 16 ft (5 m) 26 ft (8 m) 50 ft (15 m) Max. range in solids 6.5 ft (2 m) 11.5 ft (3.5 m) 23 ft (7 m) Install the Prosonic M at a height so that the blocking distance BD is not interferred with, even at the maximum fill level. Usa a pipe nozzle if you cannot maintain the sensor blocking distance in any other way. The interior of the nozzle must be smooth and cannot contain any edges or welded joints. In particular, remove any burr on the inside of the tank side nozzle end. Note the specified limits for nozzle diameter to length. Nozzles which extend into the vessel should be cut at an angle of 45 to minimize echo disturbances. Caution! The sensor may malfunction if the blocking distance is not above the maximum level. NOTE: In order to prevent the level from entering the blocking distance, a safety distance (SD) can be specified. If the level is within the safety distance, the Prosonic outputs a warning or alarm message. 10
11 Ambient conditions Ambient temperature Storage temperature Resistance to alternating temperature cycles Climate class Ingress protection Vibration resistance Electromagnetic compatibility (EMC) -40 to F (-40 to + 80 C) The function of the LCD becomes restricted at T amb < -5 F and T amb > 140 F (-20 C and 60 C). If the device is operated outdoors in strong sunlight, a protective cover should be used. -40 to +176 F (-40 to +80 C) To DIN EN ; Nb test: 176 F / -40 F (+80 C / -40 C), 1 K/min, 100 cycles DIN EN (Test Z/AD) EIN/IEC 68 T2-30Db With closed housing, tested according to NEMA 6P (IP 68), 24 hours at 6 feet (1.83 m) under water surface. NEMA 4X (IP 66) With open housing, NEMA 1 (IP 20) DIN EN / IEC : 20 to 2000 Hz, 1 (m/x 2 ) 2 /Hz; 3 x 100 min Interference emission to EN 61326, Equipment Class B Interference immunity to EN 61326, Appendix A (Industrial) and NAMUR Recommendation NE 21 (EMC) A standard installation cable is sufficient if only the analog signal is used. Use shielded cable when working with a superimposed communication signal (HART ) Process conditions Process temperature Process pressure -40 to +176 F (-40 to +80 C) A temperature sensor is integrated in the sensor for temperature-dependent time-of-flight correction. FMU 40/41: 44 psia (3 bar abs.) FMU 43: 36 psia (2.5 bar ads.) Mechanical construction FMU 40 / 41 dimensions 3.38" (86) F12 housing 2.26" (65) 3.07" (78) 2.68" (68) 3.70" (94) T12 housing 2.26" (65) 1.26" (32) 3.07" (78) 5.08" (129) 5.91" (150) 5.08" (129) 6.38" (162) 3.35" (85) 3.35" (85) FMU 40 FMU AF 60 AF 1-1/2" NPT (G 1-1/2) 0.87" (22) 3.43" (87) 5.83" (148) 2" NPT (G 2) 0.87" (22) 3.27" (83) 5.83" (148) Dimensions are in inches (mm) 1.54" (39) 1.97" (50) 11
12 FMU 43 dimensions 3.39" (80) 2.56" (65) 3.07" (78) 5.08" (129) 5.90" (150) 3.50" (89) 2 x M8 3.35" (85) 9.76" (248) 4.68" (119) 0.98" (25) 9.05" (230) 4.72" (120) 4.84" (123) 1.57" (40) 0.08" (2) 1.57" (40) 0.98" (25) 0.43" (11) Dimensions are in inches (mm) Weight Housing Process connection and sensor material FMU 40: Approximately 5.5 lb (2.5 kg) FMU 41: Approximately 6 lb (2.6 kg) FMU 43: Approximately 8 lb (3.5 kg) Types of housings: F 12 housing with sealed terminal compartment for standard or hazardous areas T 12 housing with separate terminal compartment for explosion proof areas Material: Aluminum, chromed, powder-coated, seawater resistant Cover: Aluminum, for version without on-site display Inspection glass for version with on-site display (this version cannot be specified with the ATEX II 1/2 D certificate) FMU 40: 1-1/2 NPT or G1-1/2, PVDF sensor material with EPDM seal FMU 41: 2 NPT or G 2, PVDF sensor material with EPDM seal FMU 43: Universal slip-on flange, 4 ANSI or mounting bracket, PVDF sensor material, 316 Ti SS diaphragm 12
13 Order Code: Ser.-No.: Messbereich Measuring range U V DC ma ENDRESS+HAUSER MICROPILOT II max. 20 m T >70 C : IP 65 A t >85 C Made in Ger man y Maulburg Prosonic M Human interface Display elements The LCD module VU 331 for display and operation is located beneath the housing cover. The measured value is legible through the glass in the cover. Open the cover to operate the device. LCD ENDRESS+HAUSER + E Symbols 3 keys Displayed Symbol Meaning ALARM symbol Symbol appears when the instrument is in an alarm state. Flashing indicates warning, steady ON indicates alarm. LOCK symbol The lock symbol appears when the instrument is locked; input is not possible during the locked state. COMMUNICATION symbol Communication symbol appears when data transmission via HART, PROFIBUS, or Foundation Fieldbus is in progress. + Key (s) Or Meaning Navigate upwards in the selection list Edit numeric value within a function - Or Navigate downwards in the selection list Edit numeric value within a function - Esc + Or Navigate to the left within a function group E Or E Navigate to the right within a function group, confirmation + - and or and E E + and - and E Contrast settings of the LCD Hardware lock / unlock After a hardware lock, an operation via the display or communication is not possible. The hardware can only be unlocked via the display. An unlock parameter must be entered to do so. 13
14 On-site operation Operation with VU 331 The LC-Display VU 331 allows configuration via 3 keys directly at the instrument. All device functions can be set through a menu system. The menu consists of function groups and functions. Within a function, application parameters can be read or adjusted. The user is guided through a complete configuration procedure. Headline Position indicator ENDRESS + HAUSER + E Symbol Main value Bar graph Unit Selection list Function groups -> Functions HOME E E Esc FG F000 F001 F002 F003 F FG01 Esc E E FG FG03 + FG04 - FG05 Esc FG FG07 Envelope... curve Help text 13 Operation with DXR 275 HART terminal On units with HART communication, access to the programming matrix can be done using a handheld DXR 275 terminal. FMR 231:LIC0001 Online 1 >Group Select 2 PV 8.7 m FMU43: LIC0001 Online 1->Group Select 2 PV 8.7m HELP I O HELP F1 F2 FMU43 : LIC0001 F3 F4 Group Select 1->Calibration 2 Safety settings 3 Temperature 4 Linearization 5 Extended calibr. HOME FMU43: LIC0001 F1 F2 Calibration F3 F4 1 Measured Value 2->Tank shape 3 Medium property 4 Process cond. 5 Empty calibr. HOME F1 F2 F3 F4 14
15 Remote operation Operation with ToF Tool The ToF Tool is a graphical operation software for instruments from that operate based on the time-of-flight principle. It is used to support commissioning, securing of data, signal analysis and documentation of the instruments. It is compatible with the following operating systems: Win95, Win98, WinNT4.0 and Win2000. The ToF Tool supports the following functions: Online configuration of transmitters Signal analysis via envelope curve Loading and saving of instrument data (Upload/Download) Documentation of measuring point Menu-guided commissioning Navigation bar Main window Help pages Functions Function groups Device list Signal analysis via envelope curve Evaluated echo Parameter list Envelope curve Envelope list Data at cursor position Curve data Device data Connection options (page 2 and 3): HART with Commubox FXA 191 (available as accessory) PROFIBUS-PA Service-interface with adapter FXA 193 (available as accessory) 15
16 Operation with Commuwin II (for communication versions HART or PROFIBUS-PA) Commuwin II is an operating software with graphical support (MS Windows) for intelligent transmitters with the communication protocols Rackbus, Rackbus RS-485, HART and PROFIBUS-PA. Commuwin II supports the following functions: Online configuration of transmitters Loading and saving of instrument data (Upload/Download) Orderly visulization of measured values and limit values Display and recording of measured values with a line recorder NOTE: It is not possible to display envelope curves with Commuwin II. To display curves, use the ToF Tool program supplied. Connections (page 3): HART with Commubox FXA 191 (available as accessory) PROFIBUS-PA Operation with NI-FBUS Configurator (only with Foundation Fieldbus) The NI-FBUS Configurator is an easy-to-use graphical environment for creating linkages, loops, and a schedule based on the fieldbus concepts. The NI-FBUS Configurator is used to configure a fieldbus network as follows: Set block and device tags Set device addresses Create and edit function block control strategies (function block applications) Configure vendor-defined function and transducer blocks Create and edit schedules Read and write to function block control strategies (function block applications) Invoke Device Description (DD) methods Download a configuration Verify a configuration and compare it to a saved configuration Monitor a downloaded configuration Replace devices Save and print a configuration 16
17 Certificates and Approvals CE mark Hazardous areas By attaching the CE mark, confirms that the instrument fulfills all the requirements of the relevant EC directives. FMU 40 / 41: FM approved Intrinsically safe Class I, II, III; Division 1, Groups A-G / Nonincendive Class I, Division 2 FM approved explosion proof Class I, II, III; Division 1, Groups A-G CSA approved Intrinsically safe Class I, II, III; Division 1, Groups A-G / Nonincendive Class I, Division 2 CSA approved explosion proof Class I, II, III; Division 1, Groups A-G FMU 43: FM approved dust-ignition proof Class I, Division 2, Groups E-G, non-incendive CSA approved dust-ignition proof Class I, Division 2, Groups E-G, non-incendive Ordering Information FMU 40 FMU 41 FMU 43 FMU FMU FMU 43-1 Certificate A Non-hazardous version S FM IS Cl. I, II, III; Div. 1, Grps. A-G FM NI Cl. I, Div. 2 T FM XP Cl. I, II, III; Div. 1, Grps. A-G U CSA IS Cl. I, II, III; Div. 1, Grps. A-G CSA NI Cl. I, Div. 2 V CSA XP Cl. I, II, III; Div. 1, Grps. A-G N CSA General purpose 2 Process connection R G 1-1/2, ISO 228 N 1-1/2 NPT 3 Power supply / communication B 2-wire, 4 to 20 ma loop-powered / HART H 4-wire, 10.5 to 32 VDC / 4 to 20 ma HART G 4-wire, 90 to 253 VAC / 4 to 20 ma HART D 2-wire PROFIBUS-PA F 2-wire Foundation Fieldbus 4 Display / operation 1 Without LCD 2 With LCD VU 331 / on-site operation 5 Housing A F12 aluminum housing, coated, NEMA 6P C T12 aluminum housing with separate terminal compartment, coated, NEMA 6P 6 Cable entry 2 M 20 x G 1/2 4 1/2 NPT 5 M 12 PROFIBUS-PA plug-in connector 6 7/8 Foundation Fieldbus plug-in connnector 1 Certificate A Non-hazardous version S FM IS Cl. I, II, III; Div. 1, Grps. A-G FM NI Cl. I, Div. 2 T FM XP Cl. I, II, III; Div. 1, Grps. A-G U CSA IS Cl. I, II, III; Div. 1, Grps. A-G CSA NI Cl. I, Div. 2 V CSA XP Cl. I, II, III; Div. 1, Grps. A-G N CSA General purpose 2 Process connection R G 2, ISO 228 N 2 NPT 3 Power supply / communication B 2-wire, 4 to 20 ma loop-powered / HART H 4-wire, 10.5 to 32 VDC / 4 to 20 ma HART G 4-wire, 90 to 253 VAC / 4 to 20 ma HART D 2-wire PROFIBUS-PA F 2-wire Foundation Fieldbus 4 Display / operation 1 Without LCD 2 With LCD VU 331 / on-site operation 5 Housing A F12 aluminum housing, coated, NEMA 6P C T12 aluminum housing with separate terminal compartment, coated, NEMA 6P 6 Cable entry 2 M 20 x G 1/2 4 1/2 NPT 5 M 12 PROFIBUS-PA plug-in connector 6 7/8 Foundation Fieldbus plug-in connnector 1 Certificate M FM DIP CI. 1, Div. 2, Grps. E-G, NI N CSA General purpose P CSA DIP CI. 1, Div. 2, Grps. E-G, NI 2 Process connection P 4 ANSI flange, PP (universal slip-on flange included) S 4 ANSI flange, 316Ti SS (universal slip-on flange included) 3 Power supply / communication H 4-wire, 10.5 to 32 VDC / 4 to 20 ma HART G 4-wire, 90 to 253 VAC / 4 to 20 ma HART D 2-wire PROFIBUS-PA F 2-wire Foundation Fieldbus 4 Display / operation 1 Without LCD 2 With LCD VU 331 / on-site operation 5 Housing A F12 aluminum housing, coated, NEMA 6P 6 Cable entry 2 M 20 x G 1/2 4 1/2 NPT 5 M 12 PROFIBUS-PA plug-in connector 6 7/8 Foundation Fieldbus plug-in connnector 17
18 Order Code: Ser.-No.: ENDRESS+HAUSER Prosonic M Prosonic M Accessories Protective cover A protective cover made of stainless steel is available for outdoor installation. Cover, mounting ring and hardware inlcuded. Part Number: F12 / T 12 housing ENDRESS+HAUSER MICROPILOT II Messbereich Measuring range U V DC ma max. 20 m T >70 C : IP 65 A t >85 C Made in Germany Maulburg FHX 40 remote display and operating unit F 12 housing FHX 40 separate housing 5.9" (150) Order Code: Ser.-No.: Messbereich Measuring range ENDRESS+HAUSER U V DC ma max. 20 m T >70 C : IP 65 A t >85 C Made in Germany Maulburg 4.8" (122) 3.15" (80) Cable The FHX 40 provides remote display and operation for the FMU 40/41/43 units. The display unit must be specified when ordering the Prosonic M sensors, it cannot be retrofited due to the preinstallation of the plug connectors. Maximum cable length is 65 feet (20 m). Temperature range: -22 to +158 F (-30 to +70 C) Protection: NEMA 4 (IP 65) Material: Aluminium alloy AL Si 12 Maximum cable length: 65 ft. (20 m) Consult factory for ordering information. Installation bracket for FMU 40/ " (400) 4.72" (120) 9.84" (250) 4.72" (120) 0.63" (16) 0.12" (3) 1.18" (30) For FMU 40, order no For FMU 41, order no
19 Adapter flange for FMU 40/41 Adapter flange for the FMU 40/41 threaded Prosonic M units for mounting on existing nozzles or applications requiring a nozzle mount. FAU 70 A Version 12 2 ANSI, Class ANSI, Class ANSI, Class Thread 3 1-1/2 NPT 4 2 NPT 3 Material 2 317L SS 7 PPS (Polypropylene) Sealing ring EPDM (supplied) Sensor Adapter flange Nozzle FXA 191 commubox FXA 193 service adapter For intrinsically safe communication between HART protocol and Personal Computer (refer to page 2). The Prosonic M can be operated either with the ToF Tool or the Commuwin II program. The commubox coverts HART protocol signals into RS 232C signals. Additional information is available in Technical Information TI 237F/00/en. For comunication with ToF Tool via the display connector (refer to page 3). Order No.:
20 Supplemental documentation Device function description Operating manual BA 240F/00/en This document contains detailed descriptions of all Prosonic M functions and is valid for all communication variants Communication operating manuals The following operating manuals are supplied with the unit depending on the communication version ordered. 4 to 20 ma, HART BA 237F/00/en PROFIBUS-PA BA 238F/00/en Foundation Fieldbus BA 239F/00/en These manuals describe the installation and initial commissioning of the Prosonic M. From the operating menu, all functions are included, which are required for standard measurement tasks. Additional functions are not contained in the manual. For application and selection assistance, in the U.S. call 888-ENDRESS For total support of your installed base, 24 hours a day, in the U.S. call Visit us on our web site, United States, Inc Endress Place Greenwood, IN Phone: (317) ENDRESS FAX: (317) Canada Canada Ltd Graham s Lane Unit 1, Burlington ON, L7S 1W3 Phone: (905) FAX: (905) Mexico Paseo del Pedregal No. 610 Col. Jardines del Pedregal 01900, Mexico D.F. Mexico Phone: (525) FAX: (525) The Power of Know How TI 365F/24/ae/ , Inc.
prosonic T FMU230, FMU231
Technical Information prosonic T FMU230, FMU231 Ultrasonic Level Measurement Compact transmitters for non-contact level measurement of fluids and coarse bulk materials Application The compact transmitters
More informationRadar Level Measurement micropilot FMR 130 for stilling wells
Technical Information TI 258F/24/ae Radar Level Measurement micropilot FMR 130 for stilling wells Smart transmitter for non-contact measurement in metallic by-pass pipes and stilling wells Suitable for
More informationLevel Limit Switch nivotester FTL 325 P
Technical Information TI 350F/24/ae Level Limit Switch nivotester FTL 325 P With intrinsically safe signal circuit for connection to the Liquiphant and Soliphant measuring sensor Application Level limit
More informationProcess display RIA 261
Technical Information TI 083R/24/ae Process display RIA 261 Digital loop powered field display for 4 to 20 ma current loops Features and Benefits Loop powered display, no additional power supply cable
More informationTemperature transmitter with local display RIT 261
Technical Information TI 091R/2/ae Temperature transmitter with local display RIT 261 Universal field mounted transmitter provides an exceptional backlit temperature indication with five large digits and
More informationph / ORP Measurement mypro CPM 431
Technical Information TI 173C/24/ae ph / ORP Measurement mypro CPM 431 Two-wire transmitter for ph and ORP with HART communication for use in hazardous or non-hazardous areas Areas of application The analysis
More informationTemperature transmitter itemp RTD DIN rail TMT 127
Technical information TI 095R/24/ae Nr. 510 06165 Temperature transmitter itemp RTD DIN rail TMT 127 Pt100 transmitter for an economical, high accuracy temperature monitoring. Fixed range measurement,
More informationConductivity measurement SmarTec S CLD 132
Technical Information TI 207C/24/ae Conductivity measurement SmarTec S CLD 132 Transmitter for measurement of conductivity and concentration with inductive sensor Areas of application Alkali/acid concentration
More informationProsonic M FMU40/41/42/43/44
Operating Instructions Prosonic M FMU40/41/42/43/44 Ultrasonic Level Measurement BA00237F/00/EN/13.12 71164384 Valid as of software version: V 01.04.00 (amplifier) V 01.04.00 (communication) Brief operating
More informationProsonic M FMU40/41/42/43
Technical Information FMU40/41/42/43 Ultrasonic Level Measurement Compact transmitters for non-contact level measurement of fluids, pastes and coarse bulk materials Application Continuous, non-contact
More informationUltrasonic level transmitter, non-contact
Ultrasonic level transmitter, non-contact Type 8175 can be combined with... Compact, remote versions for level measurement up to 10 m Multi language menu control Interference echo filter Automatic calibration:
More informationProsonic M FMU40/41/42/43
Operating Instructions Prosonic M FMU40/41/42/43 Ultrasonic Level Measurement 6 BA237F/00/en/08.06 52010990 Valid as of software version: V 01.04.00 (amplifier) V 01.04.00 (communication) Short instructions
More informationPROGRAMMABLE FIELD TEMPERATURE TRANSMITTER
Configuration Code TM01 Series 642 Programmable HART Field Temperature The Series 642 programmable HART field temperature transmitter is a 2-wire unit with analog output. It includes input for RTDs; resistance
More informationLST400 Ultrasonic level / open channel flow transmitter
Data sheet DS/LST400 EN Rev.C LST400 Ultrasonic level / open channel flow transmitter Measurement made easy Reduced installation cost Easy access terminations Integrated echo display makes for easy troubleshooting
More informationABB MEASUREMENT & ANALYTICS DATA SHEET. Ultrasonic level LST400 Open channel flow transmitter
ABB MEASUREMENT & ANALYTICS DATA SHEET Ultrasonic level LST400 Open channel flow transmitter 2 ULTRASONIC LEVEL LST400 / OPEN CHANNEL FLOW TRANSMITTER DS/LST400 EN REV. D Measurement made easy Reduced
More informationMicropilot M FMR250. Technical Information
Technical Information Micropilot M FMR250 Level-Radar Continuous and non-contact level measurement in solids. Cost-effective 4 to 20 ma 2-wire technology. Application The Micropilot M performs continuous,
More informationDigital inductive conductivity transmitter
Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections
More informationMiniature resistance thermometer Explosion-protected version Model TR34, thread-mounted
Electrical temperature measurement Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted WIKA data sheet TE 60.34 Applications Machine building, plant and vessel construction
More informationUltrasonic level measuring device, non-contact
Ultrasonic level measuring device, non-contact For level measurement up to 8 m 4... 20 ma/hart - 2 wires Suitable for solids ATEX approvals Type 8177 can be combined with... Type 8611 Type 8793 Type 8802-GB
More information3DLevelScanner. Technical Data Sheet. Level Sensor. Non-Contact, Multiple-Point Measurement
Technical Data Sheet Non-Contact, Multiple-Point Measurement The 3DLevelScanner is a noncontact, dust-penetrating bin measurement device that detects irregular surfaces in powder or solid materials and
More informationLevel Measurement Continuous level measurement Radar transmitters
Overview Configuration Mounting on a nozzle is a 2-wire 25 GHz pulse radar level transmitter for continuous monitoring of solids and liquids in storage vessels including extreme levels of dust and high
More informationRMA42. Technical Information
Technical Information RMA42 Process transmitter with control unit Digital process transmitter for mounting on a top-hat rail for monitoring and visualizing analog measured values Application Plant and
More informationSoliphant T FTM20, FTM21
Technical Information Soliphant T FTM20, FTM21 Level limit switch Robust vibration limit switch for bulk solids, also for dust incendive hazardous areas Application Soliphant T is a robust level limit
More informationNUS-4. Ultrasonic Level Transmitter. for Liquids and Solids
Ultrasonic Level Transmitter for Liquids and Solids measuring monitoring analyzing 4 Measuring Ranges: Liquids: Up to 25 meters (80 feet) Solids: Up to 10 meters (32 feet) Accuracy: ± 0.2 % of Reading
More informationProcess transmitter Model UPT-20, with pressure port Model UPT-21, with flush diaphragm
Electronic pressure measurement Process transmitter Model UPT-20, with pressure port Model UPT-21, with flush diaphragm WIKA data sheet PE 86.05 Applications Process technology Machine building and plant
More informationLST100 Ultrasonic level transmitter for upstream oil and gas
Data sheet DS/LST100-EN LST100 Ultrasonic level transmitter for upstream oil and gas Accurately track and measure the most expensive consumable on your site chemicals. Measurement made easy Features Keep
More informationTransit Time Ultrasonic Flow Measuring System PROline prosonic flow 93 P
Technical Information TI 056D/24/ae Transit Time Ultrasonic Flow Measuring System PROline prosonic flow 93 P Volume flow measurement of liquids in chemical or process applications Features and benefits
More informationUltrasonic level meters ULM 70
průmyslová elektronika Ultrasonic level meters ULM 70 For continuous level measurement of liquids (even if polluted), mash and paste materials in open or closed vessels, sumps, open channels, drains, etc.
More informationOEM radar transmitter, for aggressive media level measurement
OEM radar transmitter, for aggressive media level measurement C ompact for level measurement up to 20 m 4... 20 ma/hart - 2 wires Adjustable with P C ATEX approvals Type 8136 can be combined with... Type
More informationitemp HART DIN rail TMT112
Temperature transmitter itemp HART DIN rail TMT112 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage transmitters, incorporating HART protocol Application
More informationRosemount 3101, 3102, and 3105
Product Data Sheet February 2013 00813-0100-4840, Rev DA Rosemount 3101, 3102, and 3105 Ultrasonic Liquid Level Transmitters Non-contacting measurement with no moving parts Integral LCD and buttons as
More informationTEK-TEMP 2100A. Explosion-Proof Temperature Transmitter. TEMPERATURE. Technology Solutions
Technology Solutions TEK-TEMP 2100A Explosion-Proof Temperature Transmitter TEMPERATURE www.tek-trol.com Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys Introduction Tek-Trol s Explosion-Proof
More informationSystem Components Liquiphant M (NAMUR)/PROFIBUS-PA interface FXA 164
Technical Information TI 343F/00/en Operating Instructions 52004947 System Components Liquiphant M (NAMUR)/PROFIBUS-PA interface FXA 164 With intrinsically safe signal circuits for the connection of up
More informationSTT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C
STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C 6/07 PRODUCT SPECIFICATION SHEET OVERVIEW The Honeywell STT170 series of programmable temperature transmitters
More informationType PLC Fitting. Valve for Continuous control. Diaphragm valve. Output
Digital Inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections
More informationOEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted
Electrical temperature measurement OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted WIKA data sheet TE 60.31 further approvals see page 10 Applications Machine building, plant
More informationMobrey Ultrasonic. MSP422, MSP400RH, and MSP900GH Level Transmitters. Product Data Sheet February 2015 IP2045, Rev EA
Mobrey Ultrasonic Product Data Sheet February 215 IP245, Rev EA MSP422, MSP4RH, and MSP9GH Level Transmitters Non-contacting measurement with no moving parts Integral LCD and push-buttons as standard for
More informationSonicont USG. Ultrasonic filling level transmitter Non-contact measurement of filling levels in liquids, pastes and coarse bulk materials
Sonicont USG Ultrasonic filling level transmitter Non-contact measurement of filling levels in liquids, pastes and coarse bulk materials Technical manual 04.14 Main features Non-contact filling level measurement
More informationSITRANS F flowmeters SITRANS F US. Transmitter FUS060. Overview
Overview Function Displays and keypad Operation of the SITRANS FUS060 transmitter can be carried out using: Keypad and display unit HART communicator PC/laptop and SIMATIC PDM software via HART communication
More information3DLevelScanner. Technical Data Sheet. Level Sensor. Non-Contact, Multiple-Point Measurement
Technical Data Sheet Distribué par : Contact : hvssystem@hvssystem.com Tél : 0326824929 Fax : 0326851908 Non-Contact, Multiple-Point Measurement The 3DLevelScanner is a noncontact, dust-penetrating bin
More informationUlt r a s o n i c le v e l me t e r s ULM 70
preliminary data průmyslová elektronika Ult r a s o n i c le v e l me t e r s ULM 70 For continuous non-contact level measurement Suited to level measurement of various liquid and bulk-solid materials
More informationDigital flow transmitter for continuous flow measurement
Digital flow transmitter for continuous flow measurement Compact or remote version for DN 06 to 400, PN10 Shows both flow rate and volume (with two totalizers) Automatic-calibration: TEACH-IN Simulation:
More informationLevelflex M FMP 41 C, FMP 45 Smart transmitter with guided level radar for continuous level measurement in liquids
Technical Information Levelflex M FMP 41 C, FMP 45 Smart transmitter with guided level radar for continuous level measurement in liquids FMP 41 C FMP 45 Applications The Levelflex M is used for the continuous
More informationUltrasonic Measurement prosonic Universal transmitter with rugged sensors for level or open channel flow measurement
Technical Information TI 013F/24/ae Ultrasonic Measurement prosonic Universal transmitter with rugged sensors for level or open channel flow measurement FDU 80 FDU 81 FMU Prosonic Transmiiter FDU 82 FDU
More informationMiniature resistance thermometer Model TR33, thread-mounted
Electrical temperature measurement Miniature resistance thermometer Model TR33, thread-mounted WIKA data sheet TE 60.33 Applications Machine building, plant and vessel construction Propulsion technology,
More informationConductive conductivity measurement mypro CLM 431 / CLD 431 conductive
Technical Information TI 202C/07/en No. 51500563 Conductive conductivity measurement mypro CLM 431 / CLD 431 conductive Two-wire transmitter for conductive measurement of conductivity and specific resistance
More informationRHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits
RHE12 Hazardous Area Coriolis Mass Flow Transmitter Features Field mounting Compact, pressure safe housing ATEX and CSA approvals for installation in hazardous areas 24 VDC power supply Configurable analog
More informationSITRANS F flowmeters SITRANS F M. Transmitter Transmag 2 with sensor 911/E 4/77. Overview
Overview Design The complete flowmeter consists of a flow sensor and an associated transmitter from the Transmag 2 for pulsed alternating field. These are available as remote and compact versions ( 911/E
More informationThe transducer component converts the measured signal and displays the actual value.
Digital inductive conductivity transmitter System Integration Provides low Total Cost of Ownership PEEK/PPA version for CIP applications TEACH IN and SIMULATION Function Approval PVDF Version PEEK Version
More informationâ itemp Pt100 TMT127 Technical information Pt100 transmitter for DIN rail mounting for high accuracy temperature monitoring
Technical information itemp Pt100 TMT127 Pt100 transmitter for DIN rail mounting for high accuracy temperature monitoring Application Temperature transmitter with fixed measuring range for converting a
More informationCondumax W CLS19. Technical Information. Conductivity sensors Two-electrode sensors with cell constants k = 0.01 cm 1 or k = 0.
Technical Information Condumax W CLS9 Conductivity sensors Two-electrode sensors with cell constants k = 0.0 cm or k = 0. cm Application Measurement in pure and ultrapure water: Monitoring ion exchangers
More informationUltrasonic Sensor (HART)
Characteristics 500 - LEVEL - DISTANCE - MODULAR - ECONOMIC - Input: - Ranges - Output: - Voltage supply: - Accuracy: - Process connection: - Electrical connection: - Temperature range: - Limit value contacts:
More information0 2 1 â Ó. itemp HART TMT182. Technical Information
Technical Information itemp HART TMT182 Temperature head transmitter Head transmitter for resistance thermometers (RTD), thermocouples (TC), resistance and voltage transmitters (mv), HART -protocol, for
More informationprosonic M FMU 40/41/42/43 with HART and ma Ultrasonic Level Measurement
BA 237F/00/en/02.04 52010990 Valid as of software version: V 01.02.00 (amplifier) V 01.02.00 (communication) prosonic M FMU 40/41/42/43 with HART and 4... 20 ma Ultrasonic Level Measurement Operating Instructions
More informationInductive conductivity measurement mypro CLM 431 / CLD 431 inductive
Technical Information TI 195C/07/en No. 51500053 Inductive conductivity measurement mypro CLM 431 / CLD 431 inductive Two-wire transmitter for inductive measurement of conductivity in Ex and non-ex areas
More informationph or ORP Transmitter
ph or ORP Transmitter Programmable outputs: two transistor and single or dual analog 4-20 ma (Process + Temp) Removable backlighted display Universal process connection Compatible with 120 mm ph/ ORP probes
More informationLevel Measurement. Continuous level measurement - Radar transmitters SITRANS LR400 5/229. Overview
Overview Application It provides excellent results on low dielectric media. is available for standard applications and for applications that require explosion proof protection. features robust enclosure,
More informationLevel Measurement Continuous level measurement Radar transmitters
Overview Benefits Process Intelligence for advanced signal processing and quick and easy adjustment Self-guided quick start wizard for plug and play startup 2 GHz provides superior reflective properties
More informationResistance thermometer Model TR30, compact design
Electrical temperature measurement Resistance thermometer Model TR30, compact design WIKA data sheet TE 60.30 Applications Machine building, plant and vessel construction Propulsion technology, hydraulics
More informationitemp PA TMT184 Technical information
Technical information itemp PA TMT184 Temperature head transmitter with PROFIBUS-PA interface. Supply and digital communication using PROFIBUS-PA, for installation in a Form B sensor head. Features and
More informationLevel Measurement. Continuous level measurement - Radar transmitters SITRANS LR400 5/229. Overview
Overview Application It provides excellent results on low dielectric media. is available for standard applications and for applications that require explosion proof protection. features robust enclosure,
More informationDREXELBROOK. IMPULSE Series Guided Wave Radar (TDR) for Total Level and Volumetric Measurements. Easy to install, Easy to use. Dependable performance
DREXELBROOK A Leader In Level Measurement Solutions IMPULSE Series Guided Wave Radar (TDR) for Total Level and Volumetric Measurements TDR Level Measurement Easy to install, Easy to use TDR Level Measurement
More informationTEK-F LEX 4100A. Guided Wave Radar Level Transmitter. LEVEL. Technology Solutions
Technology Solutions TEK-F LEX 4100A Guided Wave Radar Level Transmitter LEVEL www.tek-trol.com Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys Introduction Featuring TDR (Time Domain
More informationTechnical Information Nivector FTC968, FTC968Z
TI0007F/00/EN/7.6 7494 Products Solutions Services Technical Information Nivector FTC968, FTC968Z Capacitance Point level switch for powder and fine-grained bulk solids Application The Nivector is a small-sized
More informationUltrasonic Level Sensor LUC-M** with HART/4 ma ma
BA237O/98/en/01.10 52027986 185564 01/10 01 Ultrasonic Level Sensor Operating instructions LUC-M40 LUC-M10 LUC-M20 LUC-M30 HARTR FIELD COMMUNICATION PROTOCOL Valid as of software version V 01.04.00 (amplifier)
More informationTemperature measurement TMD 832 head transmitter
Technical information TI 062R/09/en Mat.-Nr. 510 00782 Temperature measurement TMD 832 head transmitter SMART head transmitter with HART protocol for RTD, Thermocouple and mv input signals Applications
More informationDREXELBROOK. IMPULSE Series. Guided Wave Radar (TDR) Easy to install, Easy to use. Dependable performance. The New Impulse Guided Wave Radar
DREXELBROOK A Leader In Level Measurement Solutions IMPULSE Series Guided Wave Radar (TDR) and Volumetric for Total Level Measurements TDR Level Measurement Easy to install, Easy to use TDR Level Measurement
More information0 2 1 â Ó. itemp HART TMT182. Technical Information
Technical Information itemp HART TMT182 Temperature head transmitter Head transmitter for resistance thermometers (RTD), thermocouples (TC), resistance and voltage transmitters (mv), HART -protocol, for
More informationTechnical Information Barrier RB223
TI00132R/09/EN/13.14 71275790 Products Solutions Services Technical Information Barrier RB223 One or two-channel barrier Loop-powered barrier for the safe separation of 4 to 20 ma standard signal circuits
More informationField indicator for current loops with HART communication Models DIH50, DIH52
Accessories Field indicator for current loops with HART communication Models DIH50, DIH52 WIKA data sheet AC 80.10 for further approvals see page 6 Applications Process engineering Plant construction General
More informationDissolved Oxygen Measurement liquisys M COM 223 F / 253 F
Technical Information TI 246C/24/ae Dissolved Oxygen Measurement liquisys M COM 223 F / 253 F Oxygen Controller Benefits at a glance Liquisys M COM 223 F Liquisys M COM 253 F Due to the modularity of its
More informationEchotel Model 338 Non-Contact Ultrasonic Two-Wire Transmitter for Level, Volume, or Open Channel Flow
Echotel Model 338 Non-Contact Ultrasonic Two-Wire Transmitter for Level, Volume, or Open Channel Flow DESCRIPTION Echotel Model 338 is a two-wire, loop-powered noncontact transmitter for liquid level,
More informationCondumax W CLS15 and CLS15D
Technical Information Condumax W CLS15 and CLS15D Conductivity sensors, analog or digital with Memosens technology, Cell constant k = 0.01 cm -1 or k = 0.1 cm -1 Application Measurement in pure and ultrapure
More informationOEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted
Electrical temperature measurement OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted WIKA data sheet TE 60.31 Applications Machine building, plant and vessel construction Propulsion
More informationRosemount 848L Logic Transmitter with FOUNDATION Fieldbus
Logic Transmitter with FOUNDATION Fieldbus Integrates Discrete I/O on a FOUNDATION Fieldbus H1 Segment Reduces Installation and Maintenance Costs with a Single Network for Analog and Discrete devices Easily
More informationTemperature transmitter itemp PCP DIN rail TMT 121
Technical information TI 087R/09/en 510 03671 Temperature transmitter itemp PCP DIN rail TMT 121 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage
More informationProsonic M FMU40/41/42/43/44
Operating Instructions Prosonic M FMU40/41/42/43/44 Ultrasonic Level Measurement BA00238F/00/EN/13.12 71164389 Valid as of software version: V 01.02.00 (amplifier) V 01.02.00 (communication) Brief operating
More informationRemote Switching Unit nivotester FTL 320
Technical Information TI 203F/24/ae Remote Switching Unit nivotester For connection to intrinsically safe Liquiphant level limit switches Applications Limit detection of fluids and bulk solids in tanks
More informationTechnical Information Gammapilot M FMG60
TI00363F/00/EN/5.4 756385 Products Solutions Services Technical Information Gammapilot M FMG60 Radiometric Measurement Compact transmitter for non-contact level, point level and density detection Application
More informationDigital conductivity transmitter
Digital conductivity transmitter Compact version with integrated conductivity electrodes Remote version with seperated transmitter for short (15 ft.) or long (1500 ft.) distance Commissioning is easy due
More informationd = c 10/20/2017 Level Measurement Transmitters Applying Level Measurement p C T 273K Ultrasonic The Principle Time of Flight (TOF)
Products Solutions Services Level Measurement Transmitters Applying Level Measurement Ultrasonic FDU95 FDU93 FDU92 FDU91 FDU90 Slide 1 Slide 2 The Principle Time of Flight (TOF) Emission of ultrasound
More informationConductivity Measuring Cells for High-Temperature Applications ConduMax H CLS 16
Technical Information TI 7C//ae Conductivity Measuring Cells for High-Temperature Applications Two-electrode measuring sensors with fixed cable or connector version with integrated temperature sensor Cell
More informationLevel Measurement. Continuous level measurement Radar transmitters SITRANS LR460. 4/258 Siemens FI
Overview The is a -wire, 2 GHz FMCW radar level transmitter with extremely high signal-to-noise ratio and advanced signal processing for continuous monitoring of solids up to 100 m (328 ft). It is ideal
More informationPressure transmitter with flameproof enclosure For applications in explosion-protected areas Models E-10 and E-11
Electronic pressure measurement Pressure transmitter with flameproof enclosure For applications in explosion-protected areas Models E-10 and E-11 WIKA data sheet PE 81.27 for further approvals see page
More informationTechnical Information RMA42
TI00150R/09/EN/05.16 71315973 Products Solutions Services Technical Information RMA42 Process transmitter with control unit Digital process transmitter for monitoring and visualizing analog measured values
More informationMHPS MHPS. Modular pressure transmitter. Technical documentation. Table of content. Characteristics - applications - technical data
Technical documentation Table of content Page 2: Page 3: Page 4: Page 5: Page 6: Page 7: Page 8: Characteristics - applications - technical data Technical data - input quantity - output quantity Electrical
More informationElectro-Magnetic Flowmeters COPA-XE
Data Sheet Electro-Magnetic Flowmeters COPA-XE 10DX4311 Flowmeter system utilizes a smart microprocessor converter System accuracy of ± 0.5% of rate Field configurable via integral pushbuttons, eliminates
More informationInstruction Manual Ultrasonic Level Meter Model: NUS
Instruction Manual Ultrasonic Level Meter Model: NUS KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh PA 15205 Phone (412) 788-2830 Fax (412)-788-4890 www.koboldusa.com Manual-NUS-8-13-02 Contents
More informationRTD Temperature Sensor omnigrad T -TSM 480, TR 480. Hygienic RTD sensor with Pt 100, class A TSM 480 with electronics programmable via PC
Technical Information TI 273T/02/en 60021667 RTD Temperature Sensor omnigrad T -TSM 480, TR 480 Hygienic RTD sensor with Pt 100, class A TSM 480 with electronics programmable via PC Application The Omingrad
More informationRosemount Specifications. Product Data Sheet , Rev BA February 2009 PERFORMANCE SPECIFICATIONS
Rosemount 2051 Product Data Sheet PERFORMANCE SPECIFICATIONS Specifications For zero based spans, reference conditions, silicone oil fill, SST materials, Coplanar flange () or 1 /2 in. - 14 NPT () process
More informationDigital flowmeter for continuous flow measurement
8025 Flowmeter INSERTION Digital flowmeter for continuous flow measurement Compact or remote version for DN06 to DN400, PN10 Displays both flow rate and volume (with two totalizers) On site calibration
More informationomnigrad T - TSM 480, TR 480. Technical Information. RTD Temperature Sensor Hygienic design TSM 480 with electronics programmable via PC
Technical Information omnigrad T - TSM 480, TR 480 RTD Temperature Sensor Hygienic design TSM 480 with electronics programmable via PC Application areas The onmigrad T easytemp TSM 480 and TR 480 thermometers
More informationXperience The Future in Level Measurements
Products Solutions Services Xperience The Future in Level Measurements The right answer for any application Slide 2 Xperience The Future 113GHz + Wavelength. Micropilot FMR10/20 Liquipoint FTW33 Simple
More informationOPTIWAVE 1010 Technical Datasheet
OPTIWAVE 1010 Technical Datasheet Radar (FMCW) Level Transmitter for bypass chambers and magnetic level indicators (BM 26 Advanced) Device welded to a bypass chamber with an optional IP68 level indicator
More informationValve Island with Electronic I/O
Screw in Temperature /Switch with display for ON/OFF Control Indication, monitoring, transmission and ON/OFF control in one device Extra large display Menu guided parametrisation Complete communication
More informationTemperature Transmitter itemp RTD DIN rail TMT 127
Technical Information TI 095R/09/en No. 51004790 Temperature Transmitter itemp RTD DIN rail TMT 127 Temperature Transmitter for Pt100 Resistance Thermometer Application Temperature transmitter with fixed
More information600T Series Transmitters. Specification Sheet. Model 653T Electronic temperature transmitter (PC programmable)
Specification Sheet 600T Series Transmitters Model 65T Electronic temperature transmitter (PC programmable) High flexibility and wide rangeability Single transmitter accepts RTD/THC/mV/ohm Galvanically
More informationSTT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C
STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C 34-TT-03-07 3/06 PRODUCT SPECIFICATION SHEET OVERVIEW The Honeywell STT170 series of programmable temperature
More informationLevel Transmitter / Controller / Indicator. 3-in-1 package that is simple to install and use. With expanded ranges and improved chemical resistance.
Level Transmitter / Controller / Indicator 3-in-1 package that is simple to install and use. With expanded ranges and improved chemical resistance. 2.1 NEW Class 1, Division 1 Hazardous Areas Approved
More informationCondumax W CLS19. Technical Information. Conductivity sensors Two-electrode sensors with cell constants k = 0.01 cm 1 or k = 0.
Technical Information Condumax W CLS9 Conductivity sensors Two-electrode sensors with cell constants k = 0.0 cm or k = 0. cm Application Measurement in pure and ultrapure water: Monitoring ion exchangers
More information