BY JASON SOUCHAK, Megger

Size: px
Start display at page:

Download "BY JASON SOUCHAK, Megger"

Transcription

1 IMPROVING SYSTEM RELIABILITY WITH OFFLINE PD TESTING BY JASON SOUCHAK, Megger Partial discharge (PD) testing is a new generation of diagnostic testing for medium- and high-voltage underground power cable systems, offering a very powerful diagnostic technique. Partial discharge testing can identify problem spots in cables long before they cause an in-service outage or, if used during commissioning testing, can detect problems before the cable is even placed into service. Ideally, the cable should be tested as if it were in service, at 50 or 60 Hz. However, the power requirements to charge a cable at this frequency make this kind of field testing equipment large, expensive, and impractical. Because of this, cable testing is usually done at very low frequency (VLF). VLF tests are most commonly performed at 0.1 Hz but this 0.1 Hz voltage source is not in the same frequency range as 50 or 60 Hz, so will the results of PD testing be the same, or what kind of differences can be expected? ONLINE PARTIAL DISCHARGE Online PD can be an effective tool as well. If used properly, it can give advance warning prior to a cable failing in service. However, it has the limitation 58 SUMMER 2017

2 that it can only be used at operating voltage. Many times an outage is still required to install the highfrequency current transformer (HFCT) sensors before the system can be monitored online. To get accurate location information on where the PD is occurring, additional sensors will need to be installed and their measurements synched so that recorded pulses can be accurately compared from multiple locations. This contributes to the cost and complexity of an online PD measurement system. Online PD can either be continuously monitored or intermittently scanned. In the case of an installation that is intermittently scanned, think of scan results as a photograph: The results capture an instant in time and, in this instant, the cable can be either PD free or show signs of PD. No further analysis is possible. In the case of an installation that is continuously monitored with online PD measurements, the amount of useful information also increases, but so does the cost and complexity. This method retains the photograph quality of intermittent scans in other words, the results can indicate if the cable has PD or if it is currently PD free but it also gains the ability to provide an alert if the cable develops PD at any time at operating voltage. As an example, think of online PD as an alarm. Imagine a house, built near a river. When heavy rains come, the house could flood, so the occupants must leave for their own safety. The continuously monitoring PD method is like installing a flood alarm. This alarm goes off once the water reaches a certain height and, if the occupants were unaware of the approaching rains, they would have enough time after that alarm goes off to safely evacuate the house. The intermittent scan method of PD would be like polling this alarm only once a day. If the water is already at a dangerous level, it will provide an alert, but it has no way of indicating how fast the water would rise if it wasn t already a problem. This flood alarm for both the intermittent scan and continuous scan examples provides no advanced warning the occupants or the cable owners must react immediately. OFFLINE PARTIAL DISCHARGE Offline PD solves many of online PD s shortcomings, but requires the cable to be removed from service during a planned outage. With offline PD testing, a separate power source is connected to the cable. This allows the PD test to be performed at any desired voltage, allowing for diagnostic test results that indicate the quality of the cable before it fails. By varying the voltage from about 0.5 times rated voltage to 1.7 times rated voltage for aged cables or up to 2 times rated voltage for new cables, it is possible to find out at what voltage PD begins. If PD events don t occur until well above operating voltage (say 1.5 or 1.7 times operating voltage), the cable should be monitored, but it is not necessarily an immediate concern. However, if PD events begin much closer to operating voltage (say 1.1 or 1.2 times operating voltage), then that cable is of greater concern and should be monitored more frequently. Cables with a partial discharge inception voltage (PDIV) below operating voltage would be of immediate concern and repaired or replaced as necessary. Conversely, cables that do not exhibit PD up to maximum voltage can have a much longer testing interval. In the case of partial discharge starting at 1.1 or 1.2 times rated voltage, which is not uncommon, none of the online PD measurements would give an alert to the critical state of this cable. The cable would remain in service without any indication of the PD occurring in it until the PD became severe enough to occur at operating voltage. Once PD begins, it is a continuously degrading process; if the PD is occurring at operating voltage, that cable may only have a short time until failure. Imagine that same house on the same river. It may still have the flood alarm installed, but now the occupants watch the weather report. The report says that a hurricane is going to reach the area in three days. The occupants know that amount of rain will force them to evacuate, so they can be prepared when it becomes necessary to leave. In this case, the weather report is like an offline PD diagnostic test. The occupants (cable owners) received notice of incoming danger before it was critical and took planned action instead of taking unplanned emergency action. NETAWORLD 59

3 OFFLINE PD POWER REQUIREMENTS Ideally, cables would be tested at 50/60 Hz to simulate what occurs in service. However, to do this as an offline test would require very large power sources. For example, a 1,000-foot 15 kv class cable tested per IEEE Table 3 specified maintenance test value of 16 kv would require 9,650 VA, nearly 10 kw capacitive charging power. And a 10,000-foot 15 kv class cable tested at the acceptance test value of 21 kv would require 166,250 VA, over 166 kw capacitive charging power: Power = 2 * π * Frequency * Cable Capacitance * Voltage 2, assuming nominal value of 100 pf/ft for capacitance. Since the power requirements are too large for practical field portable test equipment, what are the other options? DC testing used to be the go-to standard for cable testing. However, it has long since fallen out of favor for extruded cables. Based on the EPRI report V2, published in December 1995, and many others, it was found that dc testing can induce faults onto cables that they would not have otherwise seen due to trapped space charges. Additionally, studies have shown that dc is blind to gross defects in the cable insulation. As a result, Figure 1: Scale Diagram of Voltage Waveforms: One Cycle of VLF Sine, One Cycle of VLF CR, One Shot of DAC, and 600 Cycles of Power Frequency no IEEE standard exists for dc testing extruded power cables. So, if dc isn t a good choice and power frequency testing takes too much power, what other options are available? The problem with power frequency is that it takes too much power. If it was possible to lower the power requirements, then ac would be the best choice. The formula for calculating the power requirements is shown in the equation. In the equation, the numeral 2 and π are constants and cannot be changed. The cable capacitance is a function of the cable construction and length and cannot be changed at will. The voltage is dictated by the specific testing standard. This leaves only frequency available to be changed. If the frequency is lowered from 60 Hz to 0.1 Hz, there is a huge power savings. In fact, 0.1 Hz testing uses 600 times less power than the equivalent power frequency test. Those same cables that used 10 kw and 166 kw at power frequency would only need 16 W and 277 W, respectively, when tested at 0.1 Hz (very low frequency or VLF). A field test set using 300 W is a reasonable amount of power and is state of the art in cable testing today. OFFLINE PD WAVE SHAPES The term VLF covers several waveforms. In cable testing, these are most often one or more of the following: VLF sinusoidal, VLF cosine rectangular (CR), or damped ac (DAC). VLF sinusoidal and VLF cosine rectangular are continuous waves, while damped ac consists of discreet pulses that may have significant time between pulses. Figure 1 shows a visual comparison of these wave shapes. VLF Sinusoidal VLF sinusoidal is the easiest to understand. It is simply the same wave shape as power frequency, but it is slowed down to 0.1z. This wave is recognized by IEEE for VLF withstand testing, and test values are conveniently given in RMS voltage and peak voltage in standard Table 3. VLF sine is a very slow-changing wave, having a polarity crossover (from positive to negative, or vice versa) of 5,000 ms or 5 seconds. When zoomed in close to the zero crossing, as shown in Figure 2, the VLF sine wave looks almost flat with a very slow rate of voltage change. 60 SUMMER 2017

4 VLF Cosine Rectangular VLF cosine rectangular is more difficult to describe. It looks similar to a square wave, but when zoomed in close (Figure 2), it clearly is not a simple square wave. It has a 5-second dc hold period, followed by a sinusoidal transition, followed by a 5-second dc hold in the opposite polarity, and a sinusoidal transition back to the original polarity. These very short dc hold periods do not damage the cable as continuous dc testing does, since the duration in each polarity is kept short. The transition period is what makes this wave special regarding PD testing. Using the capacitance in the cable and a fixed inductor in the equipment, a resonance circuit is set up. When it is time to switch polarities, the circuit resonates one-half cycle, stopped by a diode. This results in a polarity reversal in the range of 16 ms to 1.6 ms (corresponding to a frequency range or 30 to 300 Hz, respectively). This is very similar to the polarity crossover of 60 Hz at 8.3 ms, or 50 Hz at 10 ms, and much closer to power frequency than VLF sine at 5,000 ms, which is approximately 1,000 times slower. DAC Similar to cosine rectangular, DAC sets up a resonance circuit between the capacitance of the cable and a fixed inductor in the test equipment (see circuit diagram, Figure 3). However, instead of limiting the resonance to a single half cycle, DAC allows the voltage to exponentially decay through the resistive losses in the circuit. This means that DAC has a frequency in the power frequency range of 30 to 300 Hz, and voltage is only on the cable for a very short period of time, oscillating for only a few hundred milliseconds. This makes DAC an ideal voltage for PD diagnostics. Because voltage is on the cable for such a short period, this waveform is very gentle on the cable and is very unlikely (although not impossible) to cause a weak spot in the cable to fail during testing. IEEE has recognized this waveform as viable for PD testing in standard 400.3, specifically clause Damped ac is also recognized by IEEE as appropriate for withstand testing, and commericaly available options up to 300 kv exist. Figure 2: Zoomed-in View of Figure 1 Showing Three Cycles of Power Frequency and the Different Polarity Reversal Times of Various VLF Waveforms (Note: DAC and CR have approximately the same polarity crossover speed as power frequency.) Figure 3: Diagram of Circuit Used to Create DAC Waveform (Note: Cosine rectangular circuit is similar, but includes a blocking diode to allow only a half cycle of resonance.) Why is all this important? The initiation and the amount of PD measured in a cable are related to the dv/dt or the rate of change in voltage over time. The faster the voltage changes (the higher the frequency), the more PD will be measured and the lower the PD inception voltage will be. Power frequency changes from one peak of voltage to the other peak of voltage in 8.3 ms or 10 ms (60 or 50 Hz), so the testing should be done to mimic this rate of voltage change. Both cosine rectangular and damped ac change polarity in this same few millisecond range, from 5 times faster to 2 times slower than power frequency, on the extreme ends of the scale, for very short or very long cables. However, VLF sinusoidal changes polarity 600 NETAWORLD 61

5 times slower than 60 Hz power frequency does. Due to this much slower polarity change, PD test results collected with a VLF sinusoidal wave may not represent what is occurring in the cable under operating conditions. As seen in the following case study, VLF sinusoidal did not detect the presence of PD on the splice at 750 meters at all, but DAC and cosine rectangular were both able to easily identify it. PD TESTNG RESULTS According to IEEE 400.3, clause 7.4: In summary, it is not possible to standardize a specific test protocol at the current time for either online or off-line tests. This may become possible as more data are collected. This standard is unable to provide limits to what would be considered good or bad cables, due to the wide variety of cables and defects encountered in PD testing. However, through experience, certain parameters are clear indicators of problems on the cable system. These parameters include intensity, position, and PD inception voltage. It is obvious that when numerous events occur at a specific location, that location is weaker than the surrounding material. The intensity is a measure of the strength of the discharge. Again, it is obvious that a stronger discharge indicates a more severe condition. Finally, the PD inception voltage (PDIV) is the minimum voltage needed to trigger partial discharge events. This is a critical measurement, as a cable that exhibits PD at or below operating voltage is much more critical than one that only exhibits PD at 1.5 or 1.7 times operating voltage. In the first case, the cable will experience PD continuously until finally failing in service or during a testing period. In the second case, the cable will operate without PD during day-to-day operation and only experience PD events when exposed to a high voltage, such as a switching transient or a lightning strike. This all may sound intimidating, but cables in very good condition are easy to identify, as are cables in very bad condition. It is the cables in between that require additional analysis, and experience quickly makes this simple as well. Some PD threshold levels exist from research and field use to help guide users of PD equipment, even though no standard has been adopted. CASE STUDY In the following example, a single section of cable was tested with each of the three voltage waveforms discussed previously. The tests were performed in this order: DAC, VLF sine, and VLF CR. All three tests were performed within about an hour. The cable sample as shown in Figure 4 was a service-aged mix of XLPE and oil impregnated paper insulation rated at 12/20 kv, and had a total length of 1,335 meters. It had 10 splices, including four transition splices between XLPE and PILC cable. The results are presented in the order the tests were performed. For simplicity, only the results from phase L1 are shown, but the tests were performed on all three phases with similar results across all phases. A summary of all three phases is in Figure 8. DAC Results The DAC results show two clear weak points in the cable. The splices at 750 m and at 1,000 m both display large amounts of PD activity. These also correspond to transition splices in the cable system, from XLPE to PILC cable. The DAC results show up to 1,500 picocoulombs (pc) of PD activity on the splice at 750 m and up to 2,000 pc of PD activity on the splice at 1,000 m. The PD activity shown in Figure 5 is up to Figure 4: Overview of Test Cable (Note: Cable is a total of 1,335 meters and contains 10 splices in 11 sections. Green sections are XLPE cable, and blue sections are PILC cable. Splices are represented by small black segments.) 62 SUMMER 2017

6 Figure 5: Case Study DAC Results Showing PD Measurements Up to 1.7 Times Rated Voltage Figure 6: Case Study Sinusoidal Results Showing PD Measurements Up to 1.7 Times Rated Voltage a voltage of 1.7 times operating voltage, but the PD activity started at a much lower voltage. In this case (Figure 5), the PDIV was 0.4 times operating voltage for the weak spot at 750 m and 0.6 times operating voltage for the weak spot at 1,000 m. Both are well below operating voltage and are cause for significant concern. VLF Sinusoidal VLF sinusoidal results as shown in Figure 6 indicated only one of the weak points detected by DAC. The splice at 1,000 m is identified again as a site of potential weakness, but it was unable to detect the weak spot at 750 m. Additionally, the weak spot identified at 1,000 m shows a PD activity of only 250 pc at 1.7 times rated voltage. This is a significantly different result from the DAC test. Although 250 pc in a splice may not be critical, it should be monitored, while the 2,000 pc detected during the DAC test is a critical level. Furthermore, the PDIV in this sample was 1.3 times operating voltage, meaning that this result is far less critical than the 0.6 times operating voltage result observed in the DAC test. NETAWORLD 63

7 Figure 7: Case Study VLF CR Results Showing PD Measurements Up to 1.7 Times Rated Voltage Cosine Rectangular The cosine rectangular results were very similar to the DAC results. This test (Figure 7) located the weak spots at 750 m and at 1,000 m, and identified a PD activity of about 2,000 pc at the 750 m point and about 4,000 pc at the 1,000 m point. While these are higher than the PD activity recorded by the DAC wave typically due to the continuing voltage application during the voltage hold phase the ultimate course of action for both tests would be the same. This cable shows a critical amount of PD in both these points for the CR and the DAC tests. The PDIV values for the CR test were approximately 0.5 times operating voltage for both weak spots detected. This test also revealed an additional weak spot. At approximately 1,050 meters, another PD weak spot emerges. This is different from the other points observed, as it is in the cable insulation itself and not in a splice. This is not unusual to see in an oil-impregnated insulation system and could indicate that the oil has leaked out at that point creating a dry spot, or possibly that a small rise in cable elevation resulted in a similar dry spot. At about 500 pc, this would not be an immediate concern for laminated insulation, but should be monitored closely. The results from this case study demonstrate the frequency-dependent nature of PD testing. In this example, the cable tested with VLF sine would be considered acceptable since the PDIV was above operating voltage, and the level of PD recorded was low. This cable would be placed back into service and would likely soon suffer an unplanned outage. However, by using waveforms that more closely simulate power frequency, the true health of the cable could be assessed. Both damped ac and cosine rectangular identified a weak spot at 750 m that VLF sine was not able to detect, and they detected higher levels of PD activity. The result for both VLF CR and DAC would mean that the cable would not be placed back into service until the splices were repaired or replaced. VLF CR was also able to identify a weak spot in the laminated insulation. At the time of the test, this weak spot did not exhibit enough PD to be of immediate concern, but it should be monitored closely. The summary in Figure 8 shows a side-by side comparison of the voltage waveforms. The results for DAC and CR are similar, easily locating the weak spots at 750 m and at 1,000 m at both operating voltage and at 1.7 times operating voltage. Both the DAC and CR waveforms had a resonant frequency of 280 Hz, similar in dv/ 64 SUMMER 2017

8 dt to 50/60 Hz and much faster than the 0.1 Hz from the VLF sine wave. The VLF sinusoidal waveform was just able to detect the weak spot at 750 m, with an intensity of less than 80 pc, compared to greater than 1,000 pc for DAC and 1,500 pc for CR. It is entirely possible that in an electromagnetically noisy environment, this amount of partial discharge may not be detectable because it is obscured by background noise. But the 1,000 pc level from DAC would be enough to detect above the background noise. Typical field background noise levels fall in the 20 to 150 pc range. Looking at Figure 8, it is obvious that DAC and CR have similar results, including a much more detectable PD compared to sinusoidal voltage. Even though DAC and CR detected more PD, it does not mean they were any more stressful to the cable. These tests were performed in the order DAC, VLF sinusoidal, and cosine rectangular. The sine wave was in between the other two wave forms, but did not produce the same results. CONCLUSION It is difficult to overstate the potential power of offline partial discharge diagnostic testing. From IEEE 400.3, clause 1.3: The PD measurement can, at times, predict with a high level of confidence that a given cable is in very poor condition and is likely to fail in the near future. This knowledge can then be used to improve system reliability, reduce unplanned outages, reduce emergency call-outs, and help target the most vulnerable cables for replacement while allowing good cables to remain in service. However, for accurate results, it is necessary to use a voltage source with characteristics similar to those experienced by the cable in operation, particularly the voltage rate of change from one polarity to the other. Practical, field-portable test sets are available that achieve results comparable to in-service conditions, allowing for the best and most accurate cable maintenance strategy. Figure 8: Summary of Test Results DAC (Top), VLF Sine (Middle), and CR (Bottom) Waveforms at Operating Voltage (Left Column) and 1.7 Times Operating Voltage (Right Column) Jason Souchak is an Application Engineer for Megger, specializing in cable testing and diagnostic and fault location techniques. He trains end users on the theory and proper use of various pieces of high-voltage testing equipment. Jason is an active member of the IEEE Insulated Conductors Committee (ICC), helping to develop the latest cable testing standards. He graduated from Drexel University in Philadelphia with a B.S. in Electrical Engineering (BSEE), specializing in the power track. He has worked with protective relay manufacturers, utilities, and development and certification testing labs in the United States and in Europe. REFERENCES R. Bach, P. Craatz, W.Kalkner, K. Hrefter, H. Oldenhoff, G. Ritter. Voltage tests to assess medium voltage cable systems, Elektrizitaetswirtschaft 92.17/18 (1993): NETAWORLD 65

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES HEIN PUTTER Productmanager cable testing and -diagnosis Megger Site Germany 1 13 th Insucon conference 16-18 th Mai 2017, Birmingham, UK Agenda Introduction

More information

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank

More information

USING DAMPED AC VOLTAGES

USING DAMPED AC VOLTAGES MODERN & TESTING DIAGNOSIS OF POWER CABLES USING DAMPED AC VOLTAGES BY EDWARD GULSKI AND ROGIER JONGEN, Onsite HV Solutions ag, Switzerland AND RALPH PATTERSON, Power Products & Solutions LLC, United States

More information

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES Hein PUTTER Frank PETZOLD Philipp LEGLER Megger Germany Megger Germany Megger - Germany hein.putter@megger.com frank.petzold@megger.com philipp.legler@megger.com

More information

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages F. Petzold, H.T. Putter, D. Götz, H. Schlapp, S. Markalous SebaKMT GmbH Baunach/Radeburg,

More information

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM,

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM, ONLINE OFFLINE VERSUS FEATURE PARTIAL DISCHARGE TESTING FOR CABLE ASSESSMENT B Y WIL L IAM H IG INBOT H AM, EA Technology, LLC Medium voltage cables have three distinct phases to their lifecycle: (1) new

More information

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing Cable Testing & Diagnostics Solutions for Medium Voltage Networks (1 kv - 36 kv) VLF Partial Discharge DC DAC tandelta Cable Testing Cable Diagnostics? There are two main applications for cable testing:

More information

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics Dominique Bolliger, Ph.D. HV TECHNOLOGIES, Inc. Manassas, VA, USA d.bolliger@hvtechnologies.com Abstract In

More information

Partial Discharge, Survey or Monitor?

Partial Discharge, Survey or Monitor? July 2014 Partial Discharge, Survey or Monitor? 24-7 Partial Discharge monitoring is the ultimate tool for finding insulation weaknesses before they fail. Introduction It s well established that Partial

More information

PARTIAL DISCHARGE LOCATION Selected Topics

PARTIAL DISCHARGE LOCATION Selected Topics PARTIAL DISCHARGE LOCATION Selected Topics M.S. Mashikian IMCORP ICC Meeting - Fall 2000 TOPICS TESTING PHILOSOPHY Excitation Voltage Test Voltage Level METHOD OF REFLECTOMETRY METHOD OF ARRIVAL TIME TESTING

More information

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen Aspects of PD interpretation in HV power cables by Edward Gulski, Piotr Cichecki, Rogier Jongen General There are several aspects having influence on the diagnostic information and the condition judgment

More information

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015 Basics of Partial Discharge Prepared for 2015 Phenix RSM Meeting January 2015 Definitions and History Standard Definitions Fundamentally, what is a Partial Discharge An electric discharge which only partially

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime

More information

Partial discharge diagnostics on very long and branched cable circuits

Partial discharge diagnostics on very long and branched cable circuits 11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA

More information

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables William Higinbotham, Neil Davies and Victor Chan EA Technology LLC, New Jersey; USA, EA Technology Pty Ltd, Brisbane Australia; EA

More information

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland Company HV Diagnostics Sarl is a Swiss based company in the field of high voltage test equipment for cable testing and diagnosis.

More information

PD Testing Considerations for MV Plant Cables

PD Testing Considerations for MV Plant Cables PD Testing Considerations for MV Plant Cables Cable Testing Philosophy Damage Mistake Aging Repair Manufacturing Transportation Installation Operation Power frequency 50/60 Hz Power frequency 50/60 Hz

More information

Investigation of PD Detection on XLPE Cables

Investigation of PD Detection on XLPE Cables Investigation of PD Detection on XLPE Cables Hio Nam O, T.R. Blackburn and B.T. Phung School of Electrical Engineering and Telecommunications The University New South Wales, Australia Abstract- The insulation

More information

Cable testing and diagnostics

Cable testing and diagnostics Cable testing and diagnostics To ensure the flow Cost-optimised maintenance through cable diagnostics The sheath and cable testing supports you in assessing whether a cable system is safe and ready to

More information

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage Journal of Energy and Power Engineering 9 () 3-3 doi:.7/93-897/.3. D DAVID PUBLISHIG Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

More information

ICC PES Spring 2011 Meeting, Educational Session Luigi Testa, Alfred Mendelsohn

ICC PES Spring 2011 Meeting, Educational Session Luigi Testa, Alfred Mendelsohn The use of pulse shape in PD testing of cable systems using VLF ICC PES Spring 2011 Meeting, Educational Session Luigi Testa, Alfred Mendelsohn 1 Introduction Hipot VLF testing of power cable systems is

More information

Experiment 2: Transients and Oscillations in RLC Circuits

Experiment 2: Transients and Oscillations in RLC Circuits Experiment 2: Transients and Oscillations in RLC Circuits Will Chemelewski Partner: Brian Enders TA: Nielsen See laboratory book #1 pages 5-7, data taken September 1, 2009 September 7, 2009 Abstract Transient

More information

MONTRANO. Continuous monitoring system for power transformers

MONTRANO. Continuous monitoring system for power transformers MONTRANO Continuous monitoring system for power transformers Condition monitoring to extend transformer life Knowing the dielectric condition of insulation is vital Dielectric flashover of insulation in

More information

Field Experiences. Partial Discharge Diagnosis on MV Cables. Philipp Legler. XVI. Szigetelésdiagnosztikai Konferencia (

Field Experiences. Partial Discharge Diagnosis on MV Cables. Philipp Legler. XVI. Szigetelésdiagnosztikai Konferencia ( Field Experiences Partial Discharge Diagnosis on MV Cables Philipp Legler Technical Support Applications Engineer (Megger Site Germany) XVI. Szigetelésdiagnosztikai Konferencia (19. - 20.10.2016, Sümeg)

More information

Estimating the Impact of VLF Frequency on Effectiveness of VLF Withstand Diagnostics

Estimating the Impact of VLF Frequency on Effectiveness of VLF Withstand Diagnostics Estimating the Impact of VLF on Effectiveness of VLF Withstand Diagnostics Nigel Hampton (1), Jean Carlos Hernandez-Mejia (2), Marina Kuntsevich (3), Joshua Perkel (1), Vivek Tomer (3) 1 - NEETRAC, Atlanta,

More information

CITY SERIES. Compact, fully equipped cable fault location, test and diagnostic systems

CITY SERIES. Compact, fully equipped cable fault location, test and diagnostic systems CITY SERIES Compact, fully equipped cable fault location, test and diagnostic systems Tailored to fit to small vehicles Easy operation in restricted spaces Centrally controlled, fully automatic system

More information

Diagnostic testing of cast resin transformers

Diagnostic testing of cast resin transformers Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com

More information

Test systems made by SebaKMT. Don t stress over tests! SebaKMT has the right answers: reliability, speed, economy.

Test systems made by SebaKMT. Don t stress over tests! SebaKMT has the right answers: reliability, speed, economy. Test systems made by SebaKMT Don t stress over tests! SebaKMT has the right answers: reliability, speed, economy. Know how to do it. And what happens next. Test first and save later Connected to the future

More information

Voltage Probe Manual and Data North Star High Voltage, Inc. Rev January 2016

Voltage Probe Manual and Data North Star High Voltage, Inc. Rev January 2016 561 Rose Loop NE Bainbridge Island, WA, USA 9811 (52)78-93; (26)219-425 FAX http://www.highvoltageprobes.com probes@highvoltageprobes.com Voltage Probe Manual and Data North Star High Voltage, Inc. Rev

More information

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB MV Power Cable Diagnostics by Frequency Domain Spectroscopy Peter Werelius Programma Electric AB Frequency Domain Spectroscopy Measurements of insulation capacitance and losses in a frequency interval

More information

APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS

APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS David Larochelle NDB Technologies Reasons leading to acoustic testing are different weather it is a manufacturing or field environment

More information

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM D. Clark¹ R. Mackinlay² M. Seltzer-Grant² S. Goodfellow² Lee Renforth² Jamie McWilliam³ and Roger

More information

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences

More information

Module 3. DC to DC Converters. Version 2 EE IIT, Kharagpur 1

Module 3. DC to DC Converters. Version 2 EE IIT, Kharagpur 1 Module 3 DC to DC Converters Version 2 EE IIT, Kharagpur 1 Lesson 2 Commutation of Thyristor-Based Circuits Part-II Version 2 EE IIT, Kharagpur 2 This lesson provides the reader the following: (i) (ii)

More information

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES Gonzalo MAIZ, Iberdrola Distribución, (Spain), gmaiz@iberdrola.es Armando RODRIGO, Instituto

More information

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to

More information

Underground System Design TADP 547

Underground System Design TADP 547 Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards

More information

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C S O L U T I O N S Y O U R S O U R C E F O R T O P Q U A L I T Y T E S T E Q U I P M E N T w w w. h v t e c h n o l o g i e s. c o m Company

More information

EI HIGH VOLTAGE INSULATION TESTING POLICY

EI HIGH VOLTAGE INSULATION TESTING POLICY Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and

More information

A Guide to the DC Decay of Fault Current and X/R Ratios

A Guide to the DC Decay of Fault Current and X/R Ratios A Guide to the DC Decay of Fault Current and X/R Ratios Introduction This guide presents a guide to the theory of DC decay of fault currents and X/R ratios and the calculation of these values in Ipsa.

More information

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV Paul P. SEITZ, Seitz Instruments AG, (Switzerland), pps@seitz-instruments.ch Ben QUAK, Seitz Instruments AG, (Switzerland),

More information

HVA SERIES VLF TEST SETS. Hipot Testers HVA Series for VLF (0.1 Hz) testing of MV and HV cables.

HVA SERIES VLF TEST SETS. Hipot Testers HVA Series for VLF (0.1 Hz) testing of MV and HV cables. HVA SERIES VLF TEST SETS Hipot Testers HVA Series for VLF (0.1 Hz) testing of MV and HV cables. INNOVATIVE, RELIABLE, ECONOMICAL HIGH VOLTAGE TESTING FROM b2 HIGH VOLTAGE VLF, DC, cable sheath testing

More information

Why partial discharge testing makes good sense

Why partial discharge testing makes good sense Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown

More information

Assuring the Reliability of Critical Power Cable Systems

Assuring the Reliability of Critical Power Cable Systems Assuring the Reliability of Critical Power Cable Systems Presented by: Benjamin Lanz Manager of Application Engineering IMCORP Power Cable Reliability Consulting & Diagnostics Some of the technologies

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE EPN, LPN, SPN ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing

More information

Cable diagnostic in MV underground cable networks

Cable diagnostic in MV underground cable networks Cable diagnostic in MV underground cable networks Theoretical background and practical application VLF testing tan delta loss factor measurement Partial discharge localization and measurement Author: Tobias

More information

IMPORTANCE OF INSULATION RESISTANCE

IMPORTANCE OF INSULATION RESISTANCE IMPORTANCE OF INSULATION RESISTANCE What is Good Insulation? Every electric wire in your plant whether it s in a motor, generator, cable, switch, transformer, etc., is carefully covered with some form

More information

Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor under Surge Voltage Application

Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor under Surge Voltage Application IEEE Transactions on Dielectrics and Electrical Insulation Vol. 14, No. 1; February 27 39 Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor under Surge Voltage

More information

Introduction. AC or DC? Insulation Current Flow (AC) 1. TECHNICAL BULLETIN 012a Principles of Insulation Testing. Page 1 of 10 January 9, 2002

Introduction. AC or DC? Insulation Current Flow (AC) 1. TECHNICAL BULLETIN 012a Principles of Insulation Testing. Page 1 of 10 January 9, 2002 Page 1 of 10 January 9, 2002 TECHNICAL BULLETIN 012a Principles of Insulation Testing Introduction Probably 80% of all testing performed in electrical power systems is related to the verification of insulation

More information

Troubleshooting accelerometer installations

Troubleshooting accelerometer installations Troubleshooting accelerometer installations Accelerometer based monitoring systems can be tested to verify proper installation and operation. Testing ensures data integrity and can identify most commonly

More information

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of

More information

ECP HV INSULATION TESTING

ECP HV INSULATION TESTING Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and

More information

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of

More information

VSD cables in. Working with. industrial & automation applications

VSD cables in. Working with. industrial & automation applications Cable Efficiency in Automation Connectivity Cabinet Control Working with VSD cables in industrial & automation applications Description of a VSD System A functional VSD system consists of at least three

More information

Electrical Equipment Condition Assessment

Electrical Equipment Condition Assessment Feature Electrical Equipment Condition Assessment Using On-Line Solid Insulation Sampling Importance of Electrical Insulation Electrical insulation plays a vital role in the design and operation of all

More information

An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley

An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley ArborLec Solutions Inc. CIGRE WG 21:04 in 1994 Purpose of diagnostic test is: To evaluate and locate degradation phenomena

More information

Low Pass Filtering for Checker with Input Noise from Mechanical Relays

Low Pass Filtering for Checker with Input Noise from Mechanical Relays Low Pass Filtering for Checker with Input Noise from Mechanical Relays Cognex Vision Products Business Unit 4/1/2014 Version 1.0 1 Preconditions - Checker is connected to a PLC via discrete I/O to perform

More information

Electric Stresses on Surge Arrester Insulation under Standard and

Electric Stresses on Surge Arrester Insulation under Standard and Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems

More information

HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL. Huazheng Electric Manufacturing(Baoding) Co.,Ltd

HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL. Huazheng Electric Manufacturing(Baoding) Co.,Ltd HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL Huazheng Electric Manufacturing(Baoding) Co.,Ltd Safety Terms and Symbols This manual may contain the terms: Warning! Indicate the conditions

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

PD Diagnostic Applications and TechImp solutions

PD Diagnostic Applications and TechImp solutions PD Diagnostic Applications and TechImp solutions Condition Assessment Solutions for Electrical Systems. PD based innovative tools for the Condition Based Maintenance. MD-04.05.004 - rev. 00-29/08/2006

More information

The Basics of Insulation Testing

The Basics of Insulation Testing The Basics of Insulation Testing Feature by Jim Gregorec IDEAL Industries, Inc. What Is Insulation Testing? In a perfect world, all the electrical current sent along a conductive wire would reach its intended

More information

Specialists in HV and MV test and diagnostics. Testing in Substations

Specialists in HV and MV test and diagnostics. Testing in Substations Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies

More information

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages Paul P. SEITZ, Ben QUAK, Seitz Instruments AG, Niederrohrdorf, Switzerland, pps@seitz-instruments.ch Edward GULSKI,

More information

Designers Series XIII

Designers Series XIII Designers Series XIII 1 We have had many requests over the last few years to cover magnetics design in our magazine. It is a topic that we focus on for two full days in our design workshops, and it has

More information

Testing 320 kv HVDC XLPE Cable System

Testing 320 kv HVDC XLPE Cable System Testing 320 kv HVDC XLPE Cable System H. He, W. Sloot DNV GL, KEMA Laboratories Arnhem, The Netherlands Abstract Two unique test requirements in testing of a high- voltage direct- current (HVDC) cable

More information

A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints

A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints WETS D 15 2.4 Drapeau A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints Jean-François DRAPEAU Researcher Expertise Équipement électriques IREQ Jacques CÔTÉ, HQD Simon

More information

Is Fault Location Killing Our Cable Systems?

Is Fault Location Killing Our Cable Systems? Is Fault Location Killing Our Cable Systems? Benjamin Lanz, Member, IEEE; Eugene Sanchez, Member, IEEE Abstract Power outages caused by faults in underground cable systems can be difficult to locate, however

More information

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES Frank WESTER, Edward GULSKI, Johan SMIT, Edwin GROOT*, Mark VAN VLIET* Delft University of Technology The Netherlands * NUON The Netherlands

More information

Practical aspects of PD localization for long length Power Cables

Practical aspects of PD localization for long length Power Cables Practical aspects of PD localization for long length Power Cables M. Wild, S. Tenbohlen University of Stuttgart Stuttgart, Germany manuel.wild@ieh.uni-stuttgart.de E. Gulski, R. Jongen onsite hv technology

More information

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE Fred STEENNIS, KEMA, (the Netherlands), fred.steennis@kema.com Peter VAN DER WIELEN, KEMA,

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

Exploring the Necessity of the Hot Hipot Test

Exploring the Necessity of the Hot Hipot Test Exploring the Necessity of the Hot Hipot Test Introduction In an industry comprised of workers with varying electronics knowledge, a Hipot test can seem a daunting task for some. Indeed, many test operators

More information

change (PABX) systems. There must, however, be isolation between and the higher voltage, transientprone

change (PABX) systems. There must, however, be isolation between and the higher voltage, transientprone Ring Detection with the HCPL-00 Optocoupler Application Note 0 Introduction The field of telecommunications has reached the point where the efficient control of voice channels is essential. People in business

More information

NEW. The new Centrix 2.0 sets the standard for testing, diagnosis and fault location of power cables.

NEW. The new Centrix 2.0 sets the standard for testing, diagnosis and fault location of power cables. The new Centrix 2.0 sets the standard for testing, diagnosis and fault location of power cables. NEW Intuitive easygo operation using a touch display Li-ion battery-power supply for the measurement system

More information

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES White Paper Tim Wylie, Ampcontrol s Chief Technology Officer discusses the impact of Variable Speed Drives (VSDs) on earth fault limited networks.

More information

ASTA TEST REPORT NO: HEATSHRINK TERMINATIONS 3 CORE 12kV PILC AND XLPE

ASTA TEST REPORT NO: HEATSHRINK TERMINATIONS 3 CORE 12kV PILC AND XLPE ASTA TEST REPORT NO: 2212 HEATSHRINK TERMINATIONS 3 CORE 12kV PILC AND XLPE UNIVERSAL 12kV HEATSHRINK JOINT TO SUIT 3 CORE XLPE / PILC CABLES INLINE OR TRANSITION RECORD OF PROVING TESTS Page 1 of 6 Laboratory

More information

Application Note 1024

Application Note 1024 HCPL-00 Ring Detection with the HCPL-00 Optocoupler Application Note 0 Introduction The field of telecommunications has reached the point where the efficient control of voice channels is essential. People

More information

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA 1 OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM A thesis submitted to the Faculty of Electrical Power Engineering

More information

Operations Manual. Model NT11 & NT11-E. June 18 th 2002

Operations Manual. Model NT11 & NT11-E. June 18 th 2002 Operations Manual Model NT11 & NT11-E June 18 th 2002 3609 North 44 th Street Phoenix, AZ 85018-6023 Internet: www.northstarcontrols.com Fax: (941) 426-0807 Tel: (941) 426-6396 Manual Contents Glossary

More information

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy IDAX 300 Insulation Diagnostic Analyzer Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy 1 Frequency Domain Spectroscopy Hi V A Lo Ground C HL Measure at several frequencies Use

More information

Alternative Testing Techniques for Current Transformers. Dinesh Chhajer, PE Technical Support Group MEGGER

Alternative Testing Techniques for Current Transformers. Dinesh Chhajer, PE Technical Support Group MEGGER Alternative Testing Techniques for Current Transformers Dinesh Chhajer, PE Technical Support Group MEGGER Agenda Current Transformer Definition and Fundamentals Current Transformer Applications o Metering

More information

Module 1. Power Semiconductor Devices. Version 2 EE IIT, Kharagpur 1

Module 1. Power Semiconductor Devices. Version 2 EE IIT, Kharagpur 1 Module 1 Power Semiconductor Devices Version EE IIT, Kharagpur 1 Lesson 8 Hard and Soft Switching of Power Semiconductors Version EE IIT, Kharagpur This lesson provides the reader the following (i) (ii)

More information

Partial Discharge Theory, Modeling and Applications To Electrical Machines

Partial Discharge Theory, Modeling and Applications To Electrical Machines Partial Discharge Theory, Modeling and Applications To Electrical Machines V. Vahidinasab, A. Mosallanejad, A. Gholami Department of Electrical Engineering Iran University of Science and Technology (IUST)

More information

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables 21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria

More information

EEE508 GÜÇ SİSTEMLERİNDE SİNYAL İŞLEME

EEE508 GÜÇ SİSTEMLERİNDE SİNYAL İŞLEME EEE508 GÜÇ SİSTEMLERİNDE SİNYAL İŞLEME Signal Processing for Power System Applications Triggering, Segmentation and Characterization of the Events (Week-12) Gazi Üniversitesi, Elektrik ve Elektronik Müh.

More information

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 23 CHAPTER 2 v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 2.1 INTRODUCTION For reliable design of power system, proper insulation coordination among the power system equipment is necessary. Insulation

More information

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

FGJTCFWPKPUVKVWVGQHVGEJPQNQI[ FGRCTVOGPVQHGNGEVTKECNGPIKPGGTKPI VGG246JKIJXQNVCIGGPIKPGGTKPI FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown

More information

Webinar: An Effective Arc Flash Safety Program

Webinar: An Effective Arc Flash Safety Program Webinar: An Effective Arc Flash Safety Program Daleep Mohla September 10 th, 2015: 2pm ET Agenda Arc Flash Defined and Quantified NFPA 70E / CSA Z 462 - Recent Updates What is the ANSI Z10 Hierarchy of

More information

Earthing of Electrical Devices and Safety

Earthing of Electrical Devices and Safety Earthing of Electrical Devices and Safety JOŽE PIHLER Faculty of Electrical Engineering and Computer Sciences University of Maribor Smetanova 17, 2000 Maribor SLOVENIA joze.pihler@um.si Abstract: - This

More information

portable affordable CDS Series Cable Fault Locators Thumpers - Surge Generators

portable affordable CDS Series Cable Fault Locators Thumpers - Surge Generators portable CDS Series Cable Fault Locators Thumpers - Surge Generators HVI offers the most complete fault locator packages available for primary cable. HVI offers the only VLF Thumper combination ideal for

More information

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH Giuseppe Cappai, Bernhard Heinrich, Giuseppe Simioli, Leonardo Trevisan Weidmann Electrical Technology AG, Switzerland Abstract: A large solar

More information

Partial Discharge Patterns in High Voltage Insulation

Partial Discharge Patterns in High Voltage Insulation 22 IEEE International Conference on Power and Energy (PECon), 2-5 December 22, Kota Kinabalu Sabah, Malaysia Partial Discharge Patterns in High Voltage Insulation Hazlee Illias, Teo Soon Yuan, Ab Halim

More information

SEL Phase Comparison Faulted Circuit Indicator (PC FCI) Communicates to line crews using the. Features and Benefits

SEL Phase Comparison Faulted Circuit Indicator (PC FCI) Communicates to line crews using the. Features and Benefits SEL-8 Phase Comparison ed Circuit Indicator (PC FCI) SEL-8 SEL-8 SEL-8 SEL-8 SEL-8 SEL-8 Communicates to line crews using the Features and Benefits Locates ed Cable Sections Quickly Locate cable failures

More information

DETECTING SHORTED TURNS

DETECTING SHORTED TURNS VOLTECH NOTES DETECTING SHORTED TURNS 104-029 issue 2 Page 1 of 8 1. Introduction Inductors are made up of a length of wire, usually wound around a core. The core is usually some type of magnetic material

More information

SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE

SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE Fred STEENNIS Paul WAGENAARS Denny HARMSEN DNV GL the Netherlands DNV GL the

More information

Electricity Basics

Electricity Basics Western Technical College 31660310 Electricity Basics Course Outcome Summary Course Information Description Career Cluster Instructional Level Total Credits 4.00 Total Hours 144.00 DC/AC electrical theory

More information

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24 LECTURER-24 GENERATION OF HIGH ALTERNATING VOLTAGES When test voltage requirements are less than about 300kV, a single transformer can be used for test purposes. The impedance of the transformer should

More information

Dr.Arkan A.Hussein Power Electronics Fourth Class. Commutation of Thyristor-Based Circuits Part-I

Dr.Arkan A.Hussein Power Electronics Fourth Class. Commutation of Thyristor-Based Circuits Part-I Commutation of Thyristor-Based Circuits Part-I ١ This lesson provides the reader the following: (i) (ii) (iii) (iv) Requirements to be satisfied for the successful turn-off of a SCR The turn-off groups

More information

CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS

CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS 136 CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS H. van Jaarsveldt* and R. Gouws** School of Electrical, Electronic and Computer Engineering, North-West

More information