Alternative Testing Techniques for Current Transformers. Dinesh Chhajer, PE Technical Support Group MEGGER

Size: px
Start display at page:

Download "Alternative Testing Techniques for Current Transformers. Dinesh Chhajer, PE Technical Support Group MEGGER"

Transcription

1 Alternative Testing Techniques for Current Transformers Dinesh Chhajer, PE Technical Support Group MEGGER

2 Agenda Current Transformer Definition and Fundamentals Current Transformer Applications o Metering / Revenue o Protection Accuracy Classification IEEE Field Testing Practices Alternative Testing Techniques Concurrent Testing Method DC Excitation Technique Summary 2

3 Applicable Standards IEEE C57.13 IEEE Standard Requirements for Instrument Transformers IEEE C Field Testing of Relaying Current Transformers IEC Instrument Transformers Part 1: Current Transformers IEC Requirements for protective current transformers for transient performance IEC Instrument transformers - Part 2: Additional requirements for current transformers 3

4 CURRENT TRANSFORMER DEFINITION & FUNDAMENTALS Application & Classification (IEEE) 4

5 Current Transformer - Definition IEEE C IEC :2012 (IEC :1986) An instrument transformer that is intended to have its primary winding connected in series with the conductor carrying the current to be measured or controlled. An instrument transformer in which the secondary current, under normal conditions of use, is substantially proportional to the primary current and differs in phase from it by an angle which is approximately zero for an appropriate direction of the connections. 5

6 Current Transformers Definition Ideally, CT is a transformer with the secondary short-circuited. The secondary terminal voltage is zero and the magnetizing current is negligible. 6

7 Current Transformer Ideal vs. Real Ideal CT Real CT I p N = Is 1 N 2 N N 1 2 Ip = Is + Ie 7

8 Current Transformer Ideal vs. Real Current transformers (CTs) exhibit two primary errors: Accuracy errors (related to gain or linearity) Phase angle errors The error in the current reproduction from primary to secondary will be reflected in both amplitude and phase. 8

9 Current Transformer - Applications 9

10 Metering CT - IEEE High degree of accuracy at the specified standard burden at 10% and 100% of the rated primary current. 10

11 Current Transformer - Protection Protective Relaying Protection class CTs provide input information for the protection of a power system. IEEE C specifies that protection CTs must maintain a ratio error of no more than ± 10% in a range from 1 to 20 times rated secondary current at the specified load. 14

12 Protection CTs Classification IEEE Class T Covers CTs in which the leakage flux in the core creates a 1% difference between the actual ratio correction and the calculated ratio correction within the current and burden limits. In this case the ratio must be Tested. 15 Class C Covers CTs in which the leakage flux in the core has a negligible effect on the ratio within the limits of current and burden, so that ratio can be Calculated.

13 Protection CTs - Standard Burden IEEE Burden R (Ω) L (mh) Z (Ω) VA (at 5A) PF B B B B

14 FIELD TESTING PRACTICES 17

15 Standard Field Electrical Tests for CTs Saturation/ Excitation Ratio and Phase Deviation Polarity Winding Resistance Insulation Resistance Burden CT Demagnetization 18

16 CT Insulation Resistance Test DC voltage applied across the insulation and IR is measured CT Primary (H1-H2) CT Secondary (X1-X2) CT Primary (H1-H2) Ground CT Secondary (X1-X2) Ground 19

17 Winding and Lead Resistance WR test Factors Affecting WR Static stress: weight of the connected conductor Dynamic stress: wind / seismic activity vibrations in CB operation Electrodynamic forces: under short-circuit conditions Forces in the system This test confirms that: the DC resistance of the CT is within specification there is no high resistance connection in the CT or the wiring connected to it Temperature correction shall be made to meet 75 C.

18 CT Demagnetization The demagnetization of transformer cores can be performed in several ways: Variable Voltage Constant Frequency (VVCF) source Constant Voltage Variable Frequency (CVVF) source Decreasing the amplitude of an alternating DC current 21

19 CT Demagnetization Demagnetization needs to be done to eliminate the effects of residual magnetism due to DC current injection. Achieved by slowly ramping the secondary RMS voltage and taking the CT to saturation region, then slowly decreasing the voltage back to zero. 22

20 Excitation / Saturation Curve This test confirms that: The CT is of the correct accuracy rating The CT has no shorted turns No wiring or physical short circuits have developed in the primary or secondary windings of the CT after installation. An AC voltage is applied to the secondary winding of the CT while the primary winding is left open circuited.

21 Excitation / Saturation Curve 24

22 Excitation / Saturation Curve 25

23 Ratio Tests Current Method Voltage Method This test is not intended to prove the accuracy of the ratio, but simply to prove that the ratio, as installed, is as specified, and if taps are available, that they also have the correct ratio and have been wired to the correct terminals. 26

24 Polarity Test Polarity tests prove that the predicted direction of secondary current flow is correct for a given direction of primary current flow. 27

25 Burden Test External burden is measured by injecting AC current into the circuit connected to the CT and measuring the voltage drop across it. Both resistive and reactive components are determined from the phase angle difference between V and I. 31

26 Verifies that the CT will maintain its accuracy under a specified set of loading conditions. Ensures that the CT is able to operate the devices linked within their operating characteristics. Burden 32

27 Protection CT Assessment 33

28 ALTERNATIVE TESTING TECHNIQUES Efficiency and Accuracy

29 Multi-tap CT Field Testing Traditional Non-Concurrent CT Test Set CT Test Set 35

30 Concurrent Method of Testing 36

31 Alternative: Concurrent Measurement Inject voltage on full secondary winding of a multi tap CT. Example X1 X5 Simultaneously measure voltage on all CT secondary taps Simultaneously measure voltage on the CT primary Measure current passing through CT secondary and phase angle between primary and secondary. 37

32 Alternative: Concurrent Measurement Various data points are measured as voltage applied to CT secondary is increased to saturate the CT Ratio is still calculated as X1-X5/H1-H2 This same calculation is used for all other ratios (i.e. X1-X3/H1-H2) Saturation curve is plotted as X1-X5 voltage vs current through secondary winding (I s ) 38

33 Alternative: Concurrent Measurement Simultaneously measuring all values allows the calculation of saturation curves, knee points, ratio, polarity and winding resistance on all taps The concurrent measurement on all other taps significantly reduces testing time 39

34 Concurrent Vs Non-Current Saturation Testing 40

35 Inter Winding Taps Inter-winding taps saturation and ratio s (i.e. X2-X3) can be calculated from other measurements obtained. 41

36 Multi-tap CT Test: Concurrent Method 42

37 INSULATION RESISTANCE TEST 43

38 WINDING RESISTANCE TEST 44

39 Winding Resistance Test Results Comparison Between Different Methods Four Concurrent Measurements X2-X3 X1-X4 X3-X5 X2-X Four Non-Concurrent Measurements Readings in mohms 45

40 Saturation Test Results 46

41 Saturation Test Results Comparison Between Different Methods X1-X3 (V/I) X2-X3 (V/I) X2-X4 (V/I) X2-X5 (V/I) / / / / Four Concurrent Measurements / / / / / / / / / / / / / / / / Four Non-Concurrent Measurements / / / / / / / / / / / /

42 Ratio & Polarity Test 48

43 Ratio Test Results Comparison Between Different Methods Four Concurrent Measurements X1-X2 (200:5) Error (%) X3-X4 (500:5) Error (%) X1-X4 (800:5) Error (%) X2-X5 (1000:5) Error (%) : : : : : : : : : : : : : : : : : : : : 5 0 Four Non-Concurrent Measurements : : : : : : : : : : : :

44 Concurrent Vs. Non-concurrent Ratio Method 50

45 DC Excitation Technique For Saturation Test 51

46 Issues during Saturation of Protection Class CTs An excitation test on protection class CTs requires to reach saturation of the core. A C800 CT will require a minimum of 400 V AC test voltage and under some instances can take around 1300V to achieve 1A of excitation current. For transient type CTs, the test voltage can easily reach 4,000V or more to achieve 1A saturation 52

47 The AC method - Core Saturation Effect of ffffffffffffffffff vvvvvvvvvvvvvvvvvv 12 Excitation Voltage, V [kv] B VV ff Excitation Current, Iexc [ma] 45 Hz 50 Hz 60 Hz 120 Hz 53

48 Alternative method for Saturation IEC : 2012 The most suitable procedure for the determination of the saturation flux ψ sat with the d.c. saturation method is given DC method: An alternative method to obtain saturation / excitation curves of a CT is to use a low DC voltage. This method eliminates the need for dangerous high AC voltages during testing.

49 DC Excitation Method The core saturation can be achieved by applying DC voltage. IEC Instrument Transformers Part 6: Requirements for Protective Current Transformers for Transient Performance in Annex B-3 explains this alternate way to perform CT excitation. φφ = dddd dddd The integral of voltage over a period of time would be a measure of the flux produced. It can be generated by using AC or DC excitation voltage. The area under the curve reflects the flux produced. 55

50 DC Excitation Method The flux can be increased by utilizing either of the two methods. Either the time can be kept constant as the voltage is increased, or the voltage can be kept constant as the time increases. The conventional method used over the years has been to keep the time constant (or fixed frequency at 50/60Hz) as the voltage is increased until it reaches saturation. Alternatively, the voltage can be kept the same; thus DC voltage, and the time can be prolonged until the core becomes saturated. By integrating the constant DC voltage over time the core saturation can be determined. This saturation can then be mathematically converted back to an equivalent 50 Hz / 60 Hz saturation. This will achieve the same result as conventional AC excitation test technique. 56

51 DC Excitation Method The advantage of DC Excitation method is: Eliminates the need of high voltage AC and achieve the same results by utilizing a DC voltage at or below the available line voltage. Safer operation! The technique allows to test CTs with higher knee point voltages utilizing the same concept although with a slightly longer test duration. 57

52 AC Vs DC Excitation Methods 58

53 Concurrent DC Excitation Curves Comparison of concurrent AC and DC excitation testing methods 59

54 Alternative DC Technique for Saturation/Excitation Testing AC Saturation up to 2kV DC Saturation up to 30 kv AC and DC Saturation 60

55 DC Saturation Testing 61

56 Recommended Testing Sequence 62

57 Summary and Conclusions New measurement techniques proposed utilize the concepts well described in electrical textbooks. DC excitation and concurrent method of testing offer an alternative approach for testing CTs that provide same measurements and results as conventional techniques recommended in various international standards. The comparative analysis between different methods indicate that DC excitation and concurrent method of testing can be utilized in place of AC excitation and individual tap by tap testing techniques without compromising the accuracy and reliability of the results. Demagnetization is highly recommended after DC excitation to minimize any residual magnetism in the core of the CT. 63

58 Questions? Power on At Megger, we understand that keeping the power on is essential for the success of your business. That is why we are dedicated to creating, designing and manufacturing safe, reliable, easy-to-use portable test equipment backed by world-leading support and expertise. We can assist your acceptance, commissioning and maintenance testing for predictive, diagnostic or routine purposes. By working closely with electrical utilities, standards bodies and technical institutions, we contribute to the dependability and advancement of the electrical supply industry. 64

Demagnetization of Power Transformers Following a DC Resistance Testing

Demagnetization of Power Transformers Following a DC Resistance Testing Demagnetization of Power Transformers Following a DC Resistance Testing Dr.ing. Raka Levi DV Power, Sweden Abstract This paper discusses several methods for removal of remanent magnetism from power transformers.

More information

Importance of Transformer Demagnetization

Importance of Transformer Demagnetization Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia 4th International Colloquium "Transformer Research and Asset Management Importance

More information

MVCT. Megger VT & CT Analyzer. MVCT Megger VT & CT Analyzer

MVCT. Megger VT & CT Analyzer. MVCT Megger VT & CT Analyzer MVCT Ability to test both VT and CT Easy to use one-button automated test plans Industry leading test duration using patented simultaneous tap measurements Smallest and lightest unit on the market CT Kneepoints

More information

Back to the Basics Current Transformer (CT) Testing

Back to the Basics Current Transformer (CT) Testing Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of

More information

A Revolution in. Transformer EQUIVALENT CIRCUIT DIAGRAM OF A REAL CURRENT TRANSFORMER 1. by Benton Vandiver, Omicron

A Revolution in. Transformer EQUIVALENT CIRCUIT DIAGRAM OF A REAL CURRENT TRANSFORMER 1. by Benton Vandiver, Omicron by Benton Vandiver, Omicron A Revolution in D ifferent test devices and methods are used in the market to verify the performance of current transformers during development, production, installation and

More information

CT Analyzer. Revolution in current transformer testing and calibration

CT Analyzer. Revolution in current transformer testing and calibration CT Analyzer Revolution in current transformer testing and calibration Revolutionary way of CT testing Current transformers are used for relaying and metering purposes in electrical power systems. They

More information

STS Fully automatic. Large graphic display. Primary injection testing capabilities: up to 3000 A, with the optional module BUX 3000

STS Fully automatic. Large graphic display. Primary injection testing capabilities: up to 3000 A, with the optional module BUX 3000 STS 4000 Multifunction substation maintenance & commissioning test system for current, voltage and power transformers. Capacitance / Tan Delta diagnostic system with the optional module TD 5000. w w w.

More information

The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms

The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms Why Measure Winding Resistance? The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms Partial or dead short-circuited

More information

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques Charles Sweetser, Services Manager, PRIM Engineering, Waltham, Mass. Topics of Discussion

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities

More information

Outdoor Instrument Transformers. Application Guide

Outdoor Instrument Transformers. Application Guide Outdoor Instrument Transformers Application Guide Introduction Edited by Knut Sjövall, knut.sjovall@se.abb.com ABB Power Technologies AB Department: PTHV/HV/MT SE-771 80 LUDVIKA, Sweden 2 1HSE 9543 40-00en

More information

TRAX Transformer and Substation Test System

TRAX Transformer and Substation Test System TRAX Replaces need for multiple test sets Saves time by eliminating need for multiple instruments learning User-friendly interface reduces training and testing time Portable and compact system components

More information

TRAX Transformer and Substation Test System

TRAX Transformer and Substation Test System Replaces need for multiple test sets Saves time by eliminating need for multiple instruments learning User-friendly interface reduces training and testing time Portable and compact system components for

More information

Specialists in HV and MV test and diagnostics. Testing in Substations

Specialists in HV and MV test and diagnostics. Testing in Substations Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies

More information

TRAX Transformer and Substation Test System

TRAX Transformer and Substation Test System TRAX Replaces need for multiple test sets Saves time by eliminating need for multiple instruments learning User-friendly interface reduces training and testing time Portable and compact system components

More information

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,

More information

Contribution for new C62.69 clause Saturated Core Secondary Winding Parameters

Contribution for new C62.69 clause Saturated Core Secondary Winding Parameters Mick Maytum 0-0 Contribution for PC.a Contribution for new C. clause -. Saturated Core Secondary Winding Parameters This contribution is set in IEEE Word template style to simplify its incorporation in

More information

Three-Phase Transformer Demagnetizer DEM60

Three-Phase Transformer Demagnetizer DEM60 Three-Phase Transformer Demagnetizer DEM60 Fully automatic demagnetization Demagnetization currents 5 ma 60 A DC Automatic discharging circuit Lightweight 13,1 kg High DC Current Source for Automatic Transformers

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

Power Factor Insulation Diagnosis: Demystifying Standard Practices

Power Factor Insulation Diagnosis: Demystifying Standard Practices Power Factor Insulation Diagnosis: Demystifying Standard Practices Dinesh Chhajer, PE 4271 Bronze Way, Dallas Tx Phone: (214) 330 3238 Email: dinesh.chhajer@megger.com ABSTRACT Power Factor (PF) testing

More information

Diagnostic measurements on instrument transformers

Diagnostic measurements on instrument transformers Diagnostic measurements on instrument transformers A classification and overview of diagnostic measurements ABSTRACT The article presents the most common diagnostic measurements on instrument transformers

More information

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV

More information

2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd

2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd 2C73 Setting Guide High Impedance Differential Relay relay monitoring systems pty ltd Advanced Protection Devices 1. INTRODUCTION This document provides guidelines for the performance calculations required

More information

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic

More information

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at   Modeling and Analysis of Transformer ISSN: 2454-132X Impact factor: 4.295 (Volume 3, Issue 6) Available online at www.ijariit.com Modeling and Analysis of Transformer Divyapradeepa.T Department of Electrical and Electronics, Rajalakshmi Engineering

More information

CT Analyzer. Current transformer testing, calibration and assessment

CT Analyzer. Current transformer testing, calibration and assessment CT Analyzer Current transformer testing, calibration and assessment Analyze your current transformer (CT) with the push of a button How CT Analyzer works > > Injects low test signals into secondary side

More information

Beyond the Knee Point: A Practical Guide to CT Saturation

Beyond the Knee Point: A Practical Guide to CT Saturation Beyond the Knee Point: A Practical Guide to CT Saturation Ariana Hargrave, Michael J. Thompson, and Brad Heilman, Schweitzer Engineering Laboratories, Inc. Abstract Current transformer (CT) saturation,

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

Method for Static and Dynamic Resistance Measurements of HV Circuit Breaker

Method for Static and Dynamic Resistance Measurements of HV Circuit Breaker Method for Static and Dynamic Resistance Measurements of HV Circuit Breaker Zoran Stanisic Megger Sweden AB Stockholm, Sweden Zoran.Stanisic@megger.com Abstract S/DRM testing methods usually use long,

More information

TWA Series Three-Phase Winding Ohmmeters & Tap Changer & Winding Analyzers

TWA Series Three-Phase Winding Ohmmeters & Tap Changer & Winding Analyzers TWA Series Three-Phase Winding Ohmmeters & Tap Changer & Winding Analyzers Resistance measurement of all tap positions in all six windings performed in a single test True three-phase on-load tap changer

More information

2C73 Setting Guide. High Impedance Differential Relay. relay monitoring systems pty ltd Advanced Protection Devices

2C73 Setting Guide. High Impedance Differential Relay. relay monitoring systems pty ltd Advanced Protection Devices 2C73 Setting Guide High Impedance Differential Relay relay monitoring systems pty ltd Advanced Protection Devices 1. INTRODUCTION This document provides guidelines for the performance calculations required

More information

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis 1 Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis BK Pandey, DGM(OS-Elect) Venkateswara Rao Bitra, Manager (EMD Simhadri) 1.0 Introduction: Current

More information

Tap Changer Analyzer & Winding Ohmmeter RMO60TD

Tap Changer Analyzer & Winding Ohmmeter RMO60TD Tap Changer Analyzer & Winding Ohmmeter RMO60TD Test current 5 ma 60 A DC Rapid automatic demagnetization AC Current monitoring channel Lightweight 13 kg Measuring range 0,1-2 k Two voltage sense channels

More information

Core Technology Group Application Note 1 AN-1

Core Technology Group Application Note 1 AN-1 Measuring the Impedance of Inductors and Transformers. John F. Iannuzzi Introduction In many cases it is necessary to characterize the impedance of inductors and transformers. For instance, power supply

More information

Power Measurements and Basic Electrical Diagnostic Tests

Power Measurements and Basic Electrical Diagnostic Tests Power Measurements and Basic Electrical Diagnostic Tests Instrument Basics Burden VA Sources V and I Meters V and I KVL and KCL Kelvin Connection KVL and KCL Kelvin Connection 4-Wire Technique Exclude

More information

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS AS 60044.1 2007 AS 60044.1 2007 Australian Standard Instrument transformers Part 1: Current transformers (IEC 60044-1 Ed.1.2 (2003) MOD) This Australian Standard was prepared by Committee EL-013, Measurement

More information

Transformer Factory Testing

Transformer Factory Testing Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification

More information

Substation Preventive Maintenance

Substation Preventive Maintenance Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS

More information

Tap Changer Analyzer & Winding Ohmmeter RMO-TT

Tap Changer Analyzer & Winding Ohmmeter RMO-TT Tap Changer Analyzer & Winding Ohmmeter RMO-TT On-load tap changer dynamic resistance measurement Three resistance measurement channels Four temperature measurement channels Vibration measurement Automatic

More information

Provisional Specifications

Provisional Specifications Provisional Specifications Category: ELECTRICITY Provisional Specification: PS-E-15 Page: 1 of 7 of Type of Electricity Meters, Instrument Transformers and Auxiliary Devices, Provisional Specifications

More information

HYVA404 CTPT Analyzer instruction manual (V1.3.19) CT/PT Analyzer. User Manual (V1.3.19)

HYVA404 CTPT Analyzer instruction manual (V1.3.19) CT/PT Analyzer. User Manual (V1.3.19) CT/PT Analyzer User Manual (V1.3.19) Content Warning...3 1 Application and Technical Index of CT/PT Analyzer... 4 1.1 Application... 4 1.2 CT Technical Index... 4 2 Hardware... 6 2.1 Introduction... 6

More information

ECG 741 Power Distribution Transformers. Y. Baghzouz Spring 2014

ECG 741 Power Distribution Transformers. Y. Baghzouz Spring 2014 ECG 741 Power Distribution Transformers Y. Baghzouz Spring 2014 Preliminary Considerations A transformer is a device that converts one AC voltage to another AC voltage at the same frequency. The windings

More information

Diagnostic testing of cast resin transformers

Diagnostic testing of cast resin transformers Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com

More information

ISSN: Page 298

ISSN: Page 298 Sizing Current Transformers Rating To Enhance Digital Relay Operations Using Advanced Saturation Voltage Model *J.O. Aibangbee 1 and S.O. Onohaebi 2 *Department of Electrical &Computer Engineering, Bells

More information

Tap Changer Analyzer & Winding Ohmmeter RMO60TD

Tap Changer Analyzer & Winding Ohmmeter RMO60TD Tap Changer Analyzer & Winding Ohmmeter RMO60TD Test current 5 ma 60 A DC Rapid automatic demagnetization AC Current monitoring channel Lightweight 13 kg Measuring range 0,1-2 k Two voltage sense channels

More information

KEVCY 24 RE1; KEVCY 24 RF1 Indoor combined sensor; Indoor voltage sensor

KEVCY 24 RE1; KEVCY 24 RF1 Indoor combined sensor; Indoor voltage sensor Medium Voltage Product KEVCY 24 RE1; KEVCY 24 RF1 Indoor combined sensor; Indoor voltage sensor Parameters for Application Unit Value Rated primary current of application A up to 630 Rated primary voltage

More information

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers International Conference on Power System Transients IPST 23 in New Orleans, USA Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

More information

Megger. Megger 4271 Bronze Way Dallas Tx , USA. User s Guide For MCT Megger Current Transformer Test Set

Megger. Megger 4271 Bronze Way Dallas Tx , USA. User s Guide For MCT Megger Current Transformer Test Set Megger User s Guide For MCT- 1600 Megger Current Transformer Test Set Megger 4271 Bronze Way Dallas Tx-75237-1017, USA. T+1 (800) 723 2861 (USA only) T+1 (214) 330 3203 (International) F +1 (214) 337 3038

More information

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES PURPOSE The following is PG&E's procedure for pre-energization inspections. For PG&E to provide the Load

More information

Winding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer

Winding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer Winding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer Lightweight 9,5 kg Test current 5 ma 40 A DC Measuring range 0,1-2 k Two voltage sense channels Extremely quick measurement Rapid automatic

More information

SYNCHRONOUS MACHINES

SYNCHRONOUS MACHINES SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical

More information

Tap Changer Analyzer & Winding Ohmmeter RMO25TD

Tap Changer Analyzer & Winding Ohmmeter RMO25TD Tap Changer Analyzer & Winding Ohmmeter RMO25TD Test current 5 ma 25 A DC Rapid automatic demagnetization AC Current monitoring channel Lightweight 9,5 kg Measuring range 0,1-2 k Two voltage sense channels

More information

Tap Changer Analyzer & Winding Ohmmeter RMO-TT

Tap Changer Analyzer & Winding Ohmmeter RMO-TT Tap Changer Analyzer & Winding Ohmmeter RMO-TT On-load tap changer dynamic resistance measurement Three resistance measurement channels Up to six temperature measurement channels Automatic resistance/temperature

More information

Maintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems

Maintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems Maintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems Brian Kingham, Utility Market Manager, Schneider Electric, PMC Division Abstract: Historical power quality measurement

More information

Generator Advanced Concepts

Generator Advanced Concepts Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves

More information

MEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly

MEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly MEDIUM VOLTAGE PRODUCT PARAMETERS GUIDE How to specify the indoor instrument transformers correctly The range of electric values in the power supply systems is very extensive. This is why it is necessary

More information

Končar TMS - Bushing monitoring

Končar TMS - Bushing monitoring Končar TMS - Bushing monitoring Many recent studies have shown that bushing failure is one of the most common causes of transformer failure. Thus need for bushing diagnostic and monitoring system has risen.

More information

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CP RC Resonance circuit for GIS testing A new approach to testing gas-insulated switchgear Testing gas-insulated switchgear

More information

TEST VOLTAGES INFLUENCE ON TURN RATIO TESTING ndb Technologies model ART-3D

TEST VOLTAGES INFLUENCE ON TURN RATIO TESTING ndb Technologies model ART-3D TEST VOLTAGES INFLUENCE ON TURN RATIO TESTING model ART-3D Application has been working with several transformer maintenance crews manufacturers over the years. One of the prevalent challenges was obtaining

More information

The power transformer

The power transformer ELEC0014 - Introduction to power and energy systems The power transformer Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 35 Power transformers are used: to transmit

More information

Transformer & Induction M/C

Transformer & Induction M/C UNIT- 2 SINGLE-PHASE TRANSFORMERS 1. Draw equivalent circuit of a single phase transformer referring the primary side quantities to secondary and explain? (July/Aug - 2012) (Dec 2012) (June/July 2014)

More information

Overcurrent Protection / 7SJ45

Overcurrent Protection / 7SJ45 Overcurrent Protection / SJ SIPROTEC easy SJ numerical overcurrent protection relay powered by CTs Fig. / Description SIPROTEC easy SJ numerical overcurrent protection relay powered by current transformers

More information

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software Govind Pandya 1, Rahul Umre 2, Aditya Pandey 3 Assistant professor, Dept. of Electrical & Electronics,

More information

MULTI FUNCTION OVER CURRENT AND EARTH FAULT RELAY[50/51X3,50/51N]

MULTI FUNCTION OVER CURRENT AND EARTH FAULT RELAY[50/51X3,50/51N] DOG-M51D Feature The multi-ocr is a microprocessor based digital type protective relay that has 3 phases overcurrent and ground overcurrent element which are provided with inverse, very inverse, extremely

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

Chapter 2-1 Transformers

Chapter 2-1 Transformers Principles of Electric Machines and Power Electronics Chapter 2-1 Transformers Third Edition P. C. Sen Transformer application 1: power transmission Ideal Transformer Assumptions: 1. Negligible winding

More information

CP CU1. Coupling unit for line and ground testing

CP CU1. Coupling unit for line and ground testing CP CU1 Coupling unit for line and ground testing Line and ground test system CPC 100 The CPC 100 is a multifunctional test set for primary assets. When combined with the CP CU1 it covers the following

More information

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis feature By brandon dupuis An Introduction to Electrical diagnostic TesTIng of Power Transformers 38 Transformers are the largest, most expensive, and highly critical components of most utility substations.

More information

MEDIUM VOLTAGE PRODUCT. KOKM Cable current instrument transformers Instruction for Installation, use and maintenance

MEDIUM VOLTAGE PRODUCT. KOKM Cable current instrument transformers Instruction for Installation, use and maintenance MEDIUM VOLTAGE PRODUCT KOKM Cable current instrument transformers Instruction for Installation, use and maintenance 2 KOKM CABLE CURRENT INSTRUMENT TRANSFORMERS INSTRUCTION FOR INSTALLATION, USE AND MAINTENANCE

More information

Automatic Transformer Winding Analyser

Automatic Transformer Winding Analyser 2293 Automatic Transformer Winding Analyser The 2293 is an automatic winding analyser, optimized for three phase power and distribution transformer measurements. It uniquely combines winding resistance

More information

Tap Changer Analyzer & Winding Ohmmeter RMO-TD Series

Tap Changer Analyzer & Winding Ohmmeter RMO-TD Series Tap Changer Analyzer & Winding Ohmmeter RMO-TD Series On-load tap changer dynamic resistance measurement Three resistance measurement channels One temperature measurement channel Automatic resistance measurement

More information

ACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH

ACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH ACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH Michael Freiburg Erik Sperling Michael Krueger OMICRON Austria

More information

FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC.

FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC. Regional Technical Seminar FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC. Field Electrical Testing Applications Key Purposes of Field Electrical Testing: Receiving inspection Acceptance testing/commissioning

More information

Innovative Science and Technology Publications

Innovative Science and Technology Publications Innovative Science and Technology Publications Manuscript Title SATURATION ANALYSIS ON CURRENT TRANSFORMER Thilepa R 1, Yogaraj J 2, Vinoth kumar C S 3, Santhosh P K 4, 1 Department of Electrical and Electronics

More information

Apprentice Electrical Technician Test (ETT) Preparation Guide

Apprentice Electrical Technician Test (ETT) Preparation Guide Apprentice Electrical Technician Test (ETT) Preparation Guide APPRENTICE ELECTRICAL TECHNICIAN TEST (ETT) About the Test There are 40 questions with a maximum time limit of three hours. This is a closed

More information

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd. Functional Range - Earth Fault Relay C&S Protection & Control Ltd. 2 Contents Page No. 1. Application 2. Operating Principle. Current Transformer Connections 5. Connections, Contact Arrangement and Setting

More information

Solutions to Consider in Current Transformer Selection for APR1400 Nuclear Power Plant Medium Voltage Switchgears

Solutions to Consider in Current Transformer Selection for APR1400 Nuclear Power Plant Medium Voltage Switchgears Journal of Energy and Power Engineering 11 (2017) 670-678 doi: 10.17265/1934-8975/2017.10.008 D DAVID PUBLISHING Solutions to Consider in Current Transformer Selection for APR1400 Nuclear Power Plant Medium

More information

7PG21 Solkor Rf Feeder Protection Energy Management

7PG21 Solkor Rf Feeder Protection Energy Management Reyrolle Protection Devices 7PG21 Solkor Rf Feeder Protection Energy Management 7PG21 Solkor Rf Contents Contents Technical Manual Chapters 1. Description of Operation 2. Performance Specification 3.

More information

High-Voltage Isolation Amplifiers / Shunt Isolators. VariTrans P TRMS

High-Voltage Isolation Amplifiers / Shunt Isolators. VariTrans P TRMS High-Voltage Isolation Amplifiers / Shunt Isolators AC/DC high-voltage isolators for true rms measurement Input voltages up to Vin = 3600 V AC The Task In electrical systems, alternating voltages from

More information

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Christian Suttner*, Stefan Tenbohlen Institute of Power Transmission and High Voltage Technology (IEH), University of

More information

USER'S GUIDE. Power Transducer WA / RA / WR. Review I

USER'S GUIDE. Power Transducer WA / RA / WR. Review I USER'S GUIDE WA / RA / WR Table of Contents Chapter Page Introduction 3 Term of Warranty 3 Technical Features 4 Wiring Diagrams 6 Single element, two-wire transducer WA or RA 6 Single element, two-wire

More information

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions 1 Transmission transformers are important links in the bulk power system. They allow transfer of power from generation centers, up to the high-voltage grid, and to bulk electric substations for distribution

More information

Tap Changer Analyzer & Winding Ohmmeter RMO60TT

Tap Changer Analyzer & Winding Ohmmeter RMO60TT Tap Changer Analyzer & Winding Ohmmeter RMO60TT On-load tap changer dynamic resistance measurement Three resistance measurement channels Three temperature measurement channels Automatic resistance/temperature

More information

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions ENOSERV 2014 Relay & Protection Training Conference Course Descriptions Day 1 Generation Protection/Motor Bus Transfer Generator Protection: 4 hours This session highlights MV generator protection and

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering) R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between

More information

CPC 100. Multi-functional primary test system for substation commissioning and maintenance

CPC 100. Multi-functional primary test system for substation commissioning and maintenance CPC 100 Multi-functional primary test system for substation commissioning and maintenance CPC 100 The revolutionary all-in-one test system The patented test system replaces numerous individual testing

More information

Ferrite Transformer Testing

Ferrite Transformer Testing AT Series Testers Application Note Ferrite Transformer Testing VPN: 104-128/2 Voltech Instruments, all rights reserved Page 1 of 16 Introduction: As electronic products utilise higher frequency techniques

More information

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Jules Esztergalyos, Senior Member, IEEE Abstract--The measuring technique described in this paper is based on Electro Magnetic

More information

AC Excitation. AC Excitation 1. Introduction

AC Excitation. AC Excitation 1. Introduction AC Excitation 1 AC Excitation Introduction Transformers are foundational elements in all power distribution systems. A transformer couples two (or more) coils to the same flux. As long as the flux is changing

More information

Laminate Transformer Testing

Laminate Transformer Testing 1. Introduction: Laminate transformers are mostly used as line frequency, low frequency and low/high voltage step-up, step-down transformers. Two coils are wound over a core such that they are magnetically

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

Conventional Paper-II-2013

Conventional Paper-II-2013 1. All parts carry equal marks Conventional Paper-II-013 (a) (d) A 0V DC shunt motor takes 0A at full load running at 500 rpm. The armature resistance is 0.4Ω and shunt field resistance of 176Ω. The machine

More information

ISSN: [IDSTM-18] Impact Factor: 5.164

ISSN: [IDSTM-18] Impact Factor: 5.164 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY A REVIEW OF ROUTINE TESTING ON DISTRIBUTION TRANSFORMER Sukhbir Singh 1, Parul Jangra 2, Anoop Bhagat 3, Vipin Saini 4 1 Assistant

More information

Current clamps for AC current

Current clamps for AC current Current clamps for AC current Y series The Y series clamps are designed to be both rugged and versatile whilst remaining easy to use. The jaws are designed so that the clamps can be hooked onto cables

More information

3. COMBINED TRANSFORMERS Oil-paper insulation

3. COMBINED TRANSFORMERS Oil-paper insulation 3. COMBINED TRANSFORMERS Oil-paper insulation 123 kv Combined transformers. 26 Instrument transformers High voltage INTRODUCTION Combined instrument transformers contain a current transformer and an inductive

More information

A Laboratory Investigation into the use of MV Current Transformers for Transient Based Protection.

A Laboratory Investigation into the use of MV Current Transformers for Transient Based Protection. International Conference on Power Systems Transients IPST 3 in New Orleans, USA A Laboratory Investigation into the use of MV Current Transformers for Transient Based Protection. M A Redfern, S C Terry,

More information

MFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work

MFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work GE Grid Solutions MFAC High Impedance Differential Relay MFAC relays provide high speed differential protection for various types of power systems plants including generators, reactors, busbars, motors

More information