B OPTIMISING COMPENSATOR. DTE 611 Eng. C2 COSTER C BUS C RING. B DTE 611 Eng. C

Size: px
Start display at page:

Download "B OPTIMISING COMPENSATOR. DTE 611 Eng. C2 COSTER C BUS C RING. B DTE 611 Eng. C"

Transcription

1 OPIMISING COMPENSAOR B C BUS C RING DE 611 Eng. C2 Digital controller for boiler plant with annual programming : control of temperature boilers at fixed point or variable compensated control of heating zone control of DHW temperature and of DHW pump Communication systems : C-Bus compatible C-Ring compatible Power supply 230 V ~ ; DIN rail mounting 1. APPLICAION DE 611 controller is designed for winter compensated control of heating plants in, for example : administrative and commercial buildings schools residential complexes 2. FUNCIONS he principal functions of DE 611 are : Control of temperature of boiler or boilers at fixed point or control at a variable value according to outside temperature, to the request for DHW, or to the request for heat from one of heating zones (if controllers are wired in C-Ring with DE 611). control of a 1- or 2-stage burner or two 1-stage burners in sequence. Compensated control of heating plant by 3-wire control of motorised valve : optimisation of start and stop times of plant control of plant pump by timed programme in use with delay in switching off ambient frost protection minimum and maximum flow temperature limits correction of heating curve origin ambient authority Eco Off Control of DHW storage tank temperature: control loading pump by detector or only with timed programmes DHW priority and antibacteria function 24-hour and 7-day programming with timed events Programming with dates : 25 holiday periods; winter season; special period Automatic switching GM-BS Summer plant exercise to prevent lockout of valve and pumps Metering of degree-days and of operating hours of burners elecontrol for changing programme in use Five On-Off inputs for signalling status or alarm. Alarms for detector short or open circuits and for irregular operation of plant and controller C-Ring connection for local exchange of data with other controllers; C-Bus connection for exchange data with local PCs or remote telemanagement PC. 3. DEECORS, ELECONROLS & ACCESSORIES No. Description ype Sensing Code Data element t sheet 1 Heating flow surface temperature detector 1) SCH 010 NC 10 kω B1 1 Outside temperature detector SAE 001 NC 1kΩ B2 1 Boiler immersion temperature detector 2) SIH 010 NC 10 kω B4 1 DHW immersion temperature detector 3) SIH 010 NC 10 kω B5 Accessories 1 Ambient temperature detector SAB 010 NC 10 kω B3 1or2 Flue gases temperature detector SF 001 P 1 kω B6-B7 1 Accessory for connection ma active detector ASA 420 B8 1 elecontrol for changing programme in use CDB 300 R Alternatives : 1 1) Immersion temperature detector SIH 010 NC 10 kω B1 1 2) Cable-type temperature detector SAF 010 NC 10 kω B4 1 3) Cable-type temperature detector SAF 010 NC 10 kω B5 1

2 4. ECHNICAL DAA Electrical Power supply 230 V~ ± 10% Frequency Hz Consumption 5 VA Protection IP40 Radio disturbances VDE0875/0871 Vibration test with 2g (DIN ) Voltage-free output contacts: maximum switched voltage 250 V ~ maximum switched current 5 (1) A Construction standards Italian Electrotech. Committee (CEI) Storage data in memory 5 years Software Class A Mechanical Case DIN 6E module Mounting DIN 35 rail Materials: base NYLON cover ABS Ambient temperature: operation 0 45 C storage C Ambient humidity Class F DIN Dimensions 105 x 115 x 71,5 Weight 1,0 kg Programmes & periods 24-hour programmes hour events day programmes : 0 2 Holiday period 0 25 Special period 1 Remote extension period h Measurement ranges Flow temperature 0 99 C Outside temperature C Ambient temperature 0 40 C Boiler temperature C DHW temperature C Flue gases temperature C Active detector ma Heating Flow temperature : radiators C fan coils C panels C minimum limit 1 99 C maximum limit 1 99 C Design outside temperature C Correction curve origin C Valve actuator run time ,600 s Delay switching off pump minuti Ambient authority C/ C Mode temperatures: ambient of the 5 Normal modes C ambient of the 2 Setback modes C water of Flow modes C ambient of Frost Protection mode C ambient of Remote Extension mode C Optimisation of operating times : start inertia h Normal optimisation limit h Holidays optimisation limit h boosting C reduction ambient temp.optimum stop C time constant h Control boiler emperature C Differential C Increase in heating and DHW C Maximum limit C Minimum limit C Minimum operation of burner 1 minute fixed Control DHW emperature C Differential C elemanagment (setting by PC) Attempts send alarms Interval between sending alarms min. Alarms (setting by PC): threshold diff. temp. flow (B1) C delay diff. temp. flow min. threshold diff. temp. boiler (B5) C delay diff. temp. boiler min. threshold diff. ambient temp.(b3) C delay diff. temp. ambiente min. overtemperature boiler C threshold diff. temp. DHW (B4) C delay diff. temp. DHW min. max. temp. flue gases 1 & C detector ma : min. or max ma In the presence of electrical disturbances the output controls of the controller may change status but these will recover automatically. 5. OVERALLDIMENSIONS 6. FACIA OPIMISING COMPENSAOR DE C! ESC HEAING BOILER ALARMS Protective cover for electronic components 2 Base with transformer, relay & terminal blocks 3 Screws for fixing cover- base 4 DIN rail securing elements 5 DIN rail release lever 1 - Backlighted two-line 7 - Burner 2 or 2 nd stage On LED alphanumeric display 8 - DHW or secondary circuit On LED and operating keys 9 - On-Off alarms LED 3 - and operating keys 10 - Measurement alarms LED 4 - Control valve LEDs 11 - Fault LED 5 - Control pump LED 6 - Burner 1 or 1 st stage On LED 2

3 7. WIRING DIAGRAM Y M1 230 V ~ M2 E1 E2 L N 2 Op 1 Co 3 Cl F1 F L L N N B1 M B2 B3 M B4 B5 M B6 B7 E1 E2 E3 E D U 0C C c1 B2 B1 Plant flow temp.detector B2 Outside temp. detector B3 Ambient temp. detector B4 Boiler temp. detector B5 DHW temp. detector B6 Flue gases 1 detector (alternative to remote control R) B7 Flue gases 2 detector (alternative to detector B8) B8 Active detector ma (alternative to B7 and k5) E1 Boiler 1 or 1st stage boiler E2 Boiler 2 or 2nd stage boiler 8. SIING CONROLLER & DEECORS 8.1 Controller B1 B3 B4 B5 R B7 k1 k2 k3 F1 and F2 Boiler thermostats k Alarm contacts k4 Alarm contact (alternative to remote control R) k5 Alarm contact (alternative to detector B8) c1 Remote Extension SPS switch L Line 230 V ~ N Neutral M1 Heating pump M2 DHW pump or second timed output R Remote control for modifying programmes Y Motorised heating valve C-Bus ransmission telemanagement data C-Ring ransmission data between controllers he controller must be sited in a dry space, which meets the permitted ambiental limits shown under 4. ECHNICAL DAA. If sited in spaces classified as Dangerous it must be installed in a cabinet for electrical appliances constructed according to the regulations in force for the danger class involved. he controller can be installed on a DIN rail or in a DIN modular enclosure. 8.2 Plant flow temperature detector B1 With plant pump on flow detector must be installed downstream of this ; with pump on return it must be installed at least 1.5 meters downstream of the regulating valve. 8.3 Outside temperature detector B2 his must be installed outside the building on the north or north-west side, at at least three meters from the ground protected from direct sunlight, and as far as possible from windows, doors, chimneys or other sources of thermal disturbance. 8.4 Ambient temperature detector B3 his must be installed at a point which represents the average temperature of a significant space (eg living room) at a height of meters from the floor, on an internal wall as far as possible from windows, doors and sources of heat ; corners, shelving and curtains should be avoided. 8.5 Boiler detector B4 his must be used with boilers provided with anticondensing pump and must be installed on the flow piping of the boiler between the boiler itself and the anticondensing pump connector. 8.6 DHW temperature detector B5 his must be installed on the DHW storage boiler, preferably on the lower part (1/3 height) using cable-type detectors for deep pockets. B8 k4 k5 C RING B6 C BUS WIRING Proceed as follows : Separate the base and cover Mount base on DIN rail and check that the securing elements (5.4) hold it firmly in place. Carry out the wiring according to the diagram and in observance of the regulations in force, using cables of : 1,5 mm 2 for power and relay control outputs 1 mm 2 for detectors and remote control 1 mm 2 for C-Bus and C-Ring. For limits of cable length please see technical data sheets 021 and 022 Switch on power (230 V ~) and check the voltage across terminals L and N Switch off power, replace cover on base and secure it with the four screws supplied (5.3). You are advised not to insert more than two cables in a single terminal of the controller and if necessary to use external junction boxes. 3

4 10. EXAMPLES OF BOILER PLAN CONROL 10.1 Control of a single-stage boiler with compensated heating zone and DHW at constant temperature 27.1 Configuration : ype of Boi l er 1BOI LER 1SAGE B2 B3 Y M1 230 V ~ M2 E1 L N 2 Op 1 Co 3 Cl DE611 B1 M1 B L L N N F1 B4 B6 F1 Y M2 B1 M B2 B3 M B4 B5 M B6 B7 E1 E2 E3 E D U 0C C c1 E1 B1 B2 B3 B4 B5 R k4 k5 k1 k2 k3 0 0 B6 B8 C RING C BUS B1 Plant flow temp.detector B2 Outside temp. detector B3 Ambient temp. detector B4 Boiler temp. detector B5 DHW temp. detector B6 Flue gases 1 detector (alternative to remote control R) B8 Active detector ma (alternative to B7 and k5) E1 Boiler F1 Boiler thermostats k Alarm contacts k4 Alarm contact (alternative to remote control R) k5 Alarm contact (alternative to detector B8) c1 Remote Extension SPS switch L Line 230 V ~ N Neutral M1 Heating pump M2 DHW pump or second timed output R Remote control for modifying programmes Y Motorised heating valve C-Bus ransmission telemanagement data C-Ring ransmission data between controllers 10.2 Control of a two-stage boiler with compensated heating zone and DHW at constant temperature 27.1 Configuration : ype of Bo i l er 1BOI LER 2SAGES B2 DE611 B1 M1 B3 B5 Y M1 230 V ~ M2 E1.1 E1.2 L N 2 Op 1 Co 3 Cl L L N N F1 B6 B4 Y M2 B1 M B2 B3 M B4 B5 M B6 B7 E1 E2 E3 E D U 0C C c1 F1 E1.1 E1.2 B1 B2 B3 B4 B5 R k4 k5 k1 k2 k3 0 0 B6 B8 C RING C BUS B1 Plant flow temp.detector B2 Outside temp. detector B3 Ambient temp. detector B4 Boiler temp. detector B5 DHW temp. detector B6 Flue gases 1 detector (alternative to remote control R) B8 Active detector ma (alternative to B7 and k5) E1.1 1 st stage boiler E1.2 2 nd stage boiler F1 Boiler thermostats k Alarm contacts k4 Alarm contact (alternative to remote control R) k5 Alarm contact (alternative to detector B8) c1 Remote Extension SPS switch L Line 230 V ~ N Neutral M1 Heating pump M2 DHW pump or second timed output R Remote control for modifying programmes Y Motorised heating valve C-Bus ransmission telemanagement data C-Ring ransmission data between controllers 4

5 10. EXAMPLES OF BOILER PLAN CONROL 10.3 Sequencing of two burners with compensated heating zone and DHW at constant temperature 27.1 Configuration : ype of Bo i l er 2BOI LERS IN SEQU B2 DE611 B1 M1 B3 B5 Y M1 230 V ~ M2 E1 E2 L N 2 Op 1 Co 3 Cl L L N N F1 F2 B6 B7 B4 F1 E1 F2 E2 Y M2 B1 M B2 B1 B2 c1 B3 M B4 B5 M B6 B3 B4 B5 R B7 E1 E2 E3 k4 k5 k1 k2 k3 E D U 0C C C RING B6 B7 B8 C BUS 0 0 B1 Plant flow temp.detector B2 Outside temp. detector B3 Ambient temp. detector B4 Boiler temp. detector B5 DHW temp. detector B6 Flue gases 1 detector (alternative to remote control R) B7 Flue gases 2 detector (alternative to detector B8) B8 Active detector ma (alternative to B7 and k5) E1 Boiler 1 E2 Boiler 2 F1 e F2 Boiler thermostats k Alarm contacts k4 Alarm contact (alternative to remote control R) k5 Alarm contact (alternative to detector B8) c1 Remote Extension SPS switch L Line 230 V ~ N Neutral M1 Heating pump M2 DHW pump or second timed output R Remote control for modifying programmes Y Motorised heating valve C-Bus ransmission telemanagement data C-Ring ransmission data between controllers 5

6 11. COMMUNICAION 11.1 C-Ring : communication between controllers (for detailed information please see technical data sheet 022) DC 611 controller is always Primary. In the C-Ring the following signals are transmitted : permission to operate as Slave controllers value of the outside temperature (use of a single detector for several controllers) 28.3 CRing Connect ion NO value of flow temperature requested by zone controllers; used by PRIMARY controller for regulation temperature boilers (if scheduled). DHW priority and/or anticondensing = closure valves heating zones with modulating control action C-Ring wiring diagram NO = connection to C-Ring not scheduled YES= connection to C-Ring scheduled outside detector Primary Secondary or Slave Secondary or Slave DHW detector E D U E D U E D U 11.3 C-Bus communication for telemanagement (for detailed information please see technical data sheet 021) By means of C-Bus output DE 611 can be telemanaged : two-way transmission of data using one or more local PCs and / or remote central PC via telephone network. From PC or PCs it is possible to display and/or change : the data and values entered on display pages of the controller and those of configuration dedicated exclusively to telemanagment (see 4.ECHNICAL DAA) operational status of plant components (pumps, auxiliaries in general) acquire alarms coming from boiler plant read the measurements of the detectors (temperatures : outside, flow, boiler, etc) 11.4 Address for telemanagment 28.2 Add r ess : 1 Group : With telemanagement setup, in order to be identified by the central PC and/or by the local PCs, the controllers must have a progressive address number. If required, it is also possible to subdivide the controllers in groups. When telemanagement is not to be used it is not necessary to enter the address in memory ( ) o cancel the values keep + and keys pressed at the same time Sending alarms 28.1 Send Al a rms :NO PassWe l eman:no 11.6 Recording data Sending alarms : NO = alarms not sent YES= alarms sent to central PC and indicated by blinking of LEDs on controller. PassWeleman : NO = keynumber disabled YES= keynumber enabled he controller can memorise 32 series of all the operational data of the heating zones controlled. he last recording brings about the cancellation of the oldest one. he recordings take place automatically at a change of mode brought about either by the timed programme or by the operator C-Bus wiring diagram Controller with Address No. 1 Controller with Address No. 2 Controller with Address No.... 0C C 0C C 0C C to modem and/or convertor for local PC 6

7 12. OPERAION DE 611 is a digital controller with microprocessor designed for : compensated control, or at a constant value, of a boiler with single-or two-stage burner or two single-stage burners in sequence (without shut-off valves). compensated control, with or without ambient authority, of the heating zone. hree-wire control of motorised valve and On-Off control of pump. control of temperature at a constant value (or according to a timed programme) of a secondary zone for DHW, fan coils etc. On-Off control of plant component. acquisition of status and / or alarms regarding plant components. o configure the controller please see 21. SEQUENCE OF DISPLAY PAGES. 13. BOILER 13.1 Configuration of type of plant boiler & burner 27.1 ype of Bo i l er 1BOI LER 1SAGE 1 BOILER 1SAGE = boiler with single-stage burner 1 BOILER 2SAGES = boiler with two-stage burner 2 BOILERS IN SEQU = 2 boilers with single-stage burner in sequence (without shut-off valves) or 1 boiler with 2 single-stage burners in sequence Operating mode Oper a t i on Bo i l e r AUOMAI C Choice of type of operation of boiler(s) : ALWAYS ON = control of burner(s) by boiler thermostats. Emergency or temporary operation for special needs. AUOMAIC = detector B4 is indispensable (see 7. WIRING DIAGRAM). Control by controller of burner(s) according to type of boiler plant. 1 boiler 1stage = start/stop of burner according to differential. 1 boiler 2 stage = start/stop in sequence of stages of burner according to differential value set. 2 boilers in sequence = start/stop in sequence of the two single-stage burners each according to differential value set. Possibility of setting operation of the two boilers in sequence : for fixed sequence 1-2. or fixed sequence 2-1. for automatic sequence = inversion sequence every 100 hours. Minimum operating time of burners = 1 minute (cannot be changed) 13.3 Differential boiler 27.4 Di f ferent ial Bo i l e r : 5. 0c E On b Off + t b E b b On E2 Off On E1 Off + t b E = boiler E1 = boiler 1 or 1 st stage E2 = boiler 2 or 2 nd stage b = differential in C b = desired temperature boiler t b = actual temperature boiler b b he differential is the difference in temperature required to bring about the start / stop of a singlestage burner or the sequencing of each of the two stages or of the two single-stage burners Control of the temperature he operation of the boiler can be configured for the control of temperature at : 27.2 Con t r o l Bo i l e r FIXED POIN 27.3 Des i r ed Bo i l e r emp : 80. 0c 27.2 Con t r o l Bo i l e r COMPENSA I ON FIXED POIN = Control with constant temperature at value set COMPENSAION = Control with variable temperature in relation to outside temperature. When DHW calls for heat (pump M2 On) the desired boiler temperature moves to the FIXED POIN value With C-Ring setup the desired operating temperature will correspond to the highest among the temperature of its own controller and those coming from the controllers connected Increase in the curve (only with COMPENSAION control of boiler) o ensure that with compensation the boiler is always able to meet the request from the heating 27.3 zones it is necessary to increase the value of the maximum temperature requested. Increase Boi l er on Ht g : 5. 0c 7

8 13.6 Maximum and minimum limits (only with COMPENSAION control of boiler) 27.5 Bo i l e r L imi t s M i n : 1 c Max: 9 9 c Both the limits enter into the calculation of the boiler operating temperature. When the boiler temperature reaches one of the limit values it is kept constant at that value (the controller no longer considers the maximum temperature requested). WARNING: the maximum limit does not substitute observance of the safety regulations in force Operation with heating Off he status of the boiler when the plants are turned off (including those in C-Ring) can be configured for : Bo i l e r w i t h ON = boiler always in operation, and in particular : Hea t i ng: OFF with compensation = at the minimum limit temperature set at fixed point = at the temperature set in 27.3 OFF = burners Off, but in relation to the normal operating temperature (fixed point or compensated) on request for heat : from DHW from heating zone of controller from controllers connected in C-Ring Eco Off Safety of operation: Boiler in operation controlled by own thermostats if : short or open circuit of detector B4 break in C-Ring (if connected) Eco Of f NO If configured PLAN + BOILER, this function brings about the switching off of the boiler. For further details please see Eco Off (14.8) Control for outside temperature (only with 1 boiler 2 stages or two boilers in sequence) 27.7 Of f Stage 2: NO Ou t s i de : 3. 0 c For operation with reduced thermal load in intermediate seasons. Off stage 2 : NO = function excluded YES =2 nd stage or 2 nd boiler excluded when outside temperature exceeds value set Metering of operating hours he controller memorises the lengths of time the stages or the two burners remain On Permits making a good approximation of fuel consumption thereby enabling rationalisation of fuel Boi l er1:xxxx hrs deliveries. Boi l er2:xxxx hrs o cancel the value keep pressed + and keys at the same time. 14. HEAING ZONE 14.1 ype of installation 26.1 Hea t Emi t t e r s RAD I AORS 14.2 Heating control f he controller must be configured according to the type of installation : ype installation : RADIAORS PANELS FAN COILS he flow temperature requested by the controller (detector B1) is adjusted in relation to the outside temperature (detector B2 or value transmitted via C-Ring) and to the heating control curve. he controller compares the actual value of the flow temperature with the corresponding one on the curve and, if there is a difference, regulates, with PI control action (proportional band Pb and integral time It set) the motorised valve to eliminate the difference f de C C A+ A A 20 C f max C f fde ode fmax fmin f min t o t o o de = correction curve origin = desired flow temperature = design winter flow temperature = design winter outside temperature = winter maximum flow limit = winter minimum flow limit = outside temperature 8

9 he heating control curve, referring to a desired ambient temperature of 20 C, is established by : 26.2 Des i gn Ou t s i de emp : 5. 0c 26.3 Des i gn F l ow emp : 70. 0c design outside temperature, used for calculation of winter heat loss from building ; depends on the climatic area in which the building is situated. design flow temperature, used for determining thermal requirements of heating zone (eg: radiators = 70 C, fan coils = 80 C, panels = 40 C). origin of heating curve = winter flow temperature with outside temperature of 20 C. he flow temperature requested by the controller depends also on the value of the ambient temperature requested by the operating mode Normal,Setback, Frost Protection (parallel ± shift of curve) Origin of heating curve 26.4 Cu r veor i g i n O20 Flow : 20.0c he conventional point of origin of the heating curve (+ 20 C flow at + 20 C outside) can be adjusted by an increase in the flow temperature (max C). he adjustment may be necessary to avoid possible imbalances in the output of the heat emitters with high outside temperatures (intermediate seasons) Operating temperatures Des i r ed emp NORMAL c Des i r ed emp SEBACK c 23.8 Des i r ed emp FROSPRO 6. 0c Des i r ed emp FLOW c DE 611 permits the configuration, even with different values of desired temperature, of the various operating modes available, namely is : 5 NORMAL = operation of compensated control at comfortable ambient temperatures (during the day or when building occupied) 2 SEBACK = operation of compensated control at reduced ambient temperatures (at night or when building not occupied) FROS PROECION = operation of control at safety temperature (holidays or building unoccupied) 2 FLOW = operation of control at constant flow temperature value (compensation curve not taken into account) OFF = valve closed and pump idle 14.5 Minimum and maximum limits of flow temperature When the requested flow temperature reaches one of its limit values it is kept constant at that value. Flow 26.5 Limi ts Examples : - minimum limit to avoid circulation of cold air in fan coils. - maximum limit to avoid dangerous overheating of the panels. Min: 1c Max:99c Warning : the maximum limit temperature does not substitute observance of the safety regulations in force Actuator run time 26.6 Con t r o l : VALVE ime : 630sec his is the time for a complete run (open/closed) of valve actuator, necessary for correct control operation Ambient authority 26.7 Ambi en t Au t ho r i t y on Flow : c When ambient detector B3 is connected, the controller is able to adjust the desired flow temperature according to the ambient authority set. When detector B3 is not connected the adustment takes place only in the Setback/Frost Protection modes using the value of the ambient temperature calculated in relation to the cooling time constant. Ambient authority on flow = value in C of change (increase/decrease) in flow temperature for each degree of difference in ambient temperature Eco Off Eco Of f NO Permits excluding heating when the weather conditions do not require it : NO = not enabled ECO PLAN = enabled only for heating (valve closed & pump idle) P + B = enabled for heating and boiler (the boiler starts at request of DHW or of C-Ring). 9

10 Functions only in Normal / Setback modes for : f aa 2 C f = flow temperature calculated by compensation control aa = actual or calculated ambient temperature Function ceases and returns to automatic operation when the difference is :: f aa 4 C 14.9 Operating programmes 22.2 Htg: HOUR 1 Choice of operating programme for heating zone according to requirements : 24 HOUR1...7; 7 DAY 1-2, NORMAL 1...5; SEBACK 1-2; FROSPRO; FLOW 1-2; OFF In place of the programme the following can appear : SUMMER = controller is in summer period; HOLIDAY = controller is in holiday period; SPECIAL =controller is in special period; REMOE EXENSION = the Remote Extension period has been activated. o cancel this function, on first page press at the same time and keys. REMOENORMAL 1 = remote control R is in Normal position; REMOESEBACK 1 = remote control R is in the Setback position; REMOEFROSPRO = remote control R is in the Frost Protection position; REMOE OFF = remote control R is in the Off position; REMOE+2c =remote control R is in the Automatic + 2 C position Operating mode & adjustment of temperature he mode in use depends on the programme set in of display NORMAL d c 22.3 SEBACK d c Mode : NORMAL FLOW d c d21. 0c Va r+0. 0c FROSPRO d c Htg: HOUR 1 and is shown on the page OFF In the NORMAL / SEBACK operating modes it is possible to make an adjustment to the desired temperature value : Var + = variation of ± 3 C Remote control for modifying programmes he remote control R (CDB 300) can be used as an alternative to flue gases detector B6 (see Complementary functions ). It allows modifying from a distance the operating programme in use: 28.4 OFF : plant excluded. FROSPRO : continuous operation at desired Frostprot ambient temperature I npu t B6 NORMAL : continuous operation at desired Normal 1 ambient temperature REMOE CONROL SEBACK : continuous operation at desired Setback 1 ambient temperature. Ad +2c : increase of 2 C in desired temperature of mode in use. AUOMAIC : operation with chosen programme on controller Control plant pump He a ting Pump : AU De l ay Of f : 30mi n he heating plant pump can be controlled in two ways : Pump : MAN = pump always in operation. AU = pump controlled by event times of programme in use. Delay Off : - - min = delay in switching off for dissipating heat accumulated in plant Metering degree-days 25.8 Degree-Days 20:xxxx Amb:xxxx 15. OPIMISAION DE 611 carries out a double metering of degree-days : 20 = metering of degree-days with reference to conventional ambient temperature of 20 C. Amb = metering of degree-days with reference to actual ambient temperature (with detector B3) or to that calculated (without B3). Start and stop at variable times so as to obtain the desired ambient temperature in coincidence with the times of start and end of occupancy. Useful for buildings with discontinuous occupancy such as : schools, business and public offices. he method for establishing the time of optimised start depends on the presence or not of the ambient detector Optimisation with ambient detector he start time is established by the meeting point of the descending curve of the actual ambient temperature (with plant OFF or in SEBACK/FROSPRO mode) and the ascending of ambient temperature curve defined by the parameter Start inertia. With Start inertia on AUOMAIC (15.4) : if the desired ambient temperature is obtained too soon or too late in respect of the required time, the controller corrects the start time for the following day by ± 15 minutes until the desired time is obtained. 10

11 15.2 Optimisation without ambient detector Start inertia must be set on MANUAL in he start time is established by the controller on the basis of the Cooling time constant (26.12) Enabling of the function Op t imumst a r t Op t imum S t op :NO :NO Optimum start = automatic change of start time of plant after night shutdown/seback or after the holidays. NO =function disabled YES = function enabled Optimum stop = stop before programmed end of NORMAL (day) mode. NO =function disabled YES = function enabled WARNING:he functions are not enabled in the FLOW 1-2 modes and are operative only for the first and last events of the programme Start inertia 26.8 Star t Iner t ia MANUAL h / c ime necessary (hours / C) for plant to increase ambient temperature by 1 C. MANUAL =the value can be adjusted only manually. AUOMAIC =only with ambient detector. he value is adjusted automatically by ± 15 minutes per day Duration of normal optimisation 26.9 Op t S t a r t No rma l Ma x Du r a t : h Maximum period before start occupancy for first startup of plant, when controller uses one of 7-day and/or 24-hour programmes available ; in practice, startup after being shut down at right Duration of optimisation holidays Op t S t a r t Ho l i da y Ma x Du r a t : h 15.7 Boosting Op t imum S t a r t Boos t i ng : 3. 0c Maximum period before start occupancy for first startup of plant after a holiday period. Increase in desired ambient temperature, with consequent increase in flow temperature, during period of optimum start, so as to reduce the time for heating zone to reach required temperature. With ambient detector, if desired ambient temperature is reached before desired time, the controller changes to compensation as per programme Cooling time constant ime taken by ambient temperature, with plant Off, to fall by 2/3 its initial value. Coo l i ng ime It is used by the controller to calculate the ambient temperature (in SEBACK / FROSPRO modes) Cons t an t : 48 h r s when the plant is without ambient detector Reduction of temperature for optimum stop Op t imum S t op DecreaseA: 0. 5c Maximum optimum stop Op t imum S t op Ma x Du r a t : h Maximum reduction of ambient temperature permitted at time of end of occupancy in respect of desired temp. on condition that ambient temperature is below value set in respect of that of mode in use at end of occupancy. his function is not enabled in the FLOW 1-2 modes and is performed only at the last event of the programme. Maximum period before programmed end of occupancy for shutdown of plant. he time is calculated in relation to the reduction in temperature set in with ambient detector and to the Cooling time constant without ambient detector. With ambient detector : if ambient temperature falls, in respect of value of the reduction set, before the time of end of occupancy, the controller returns to operate according to the programme. 11

12 16. CONROL DHW 28.7 De t ec t o r A l a rms 5 When detector B5 is connected and is enabled in Detector Alarms, the controller regulates DHW pump M2 according to operating programme selected and desired temperature set. If the presence of the detector is disabled in Detector Alarms, whether detector B5 is connected or not, the output can be used for timed control Desired temperature Des i r ed emp DHW c Value of temperature desired for DHW storage Differential & antibacteria DHW Differ = difference of temperature for control of DHW pump M Antibacteria = increase in DHW temperature to70 for 90 minutes every Wednesday at 12 noon DHW D i f f e r : 3. 0 c to prevent formation of bacteria inside the storage tank. An t i bac t e r i a :NO NO = function disabled YES = function enabled 16.3 Operating programmes DHW Summer : YES ALWAYS ON Operation of DHW during summer period : YES = DHW operating NO = DHW Off Choice of operating programme: 24HOUR 1...7; 7DAY 1-2, FOLLOWS HEAING; ALWAYS ON; ALWAYS OFF; NB: if FOLLOWS HEAING set and DHW summer : YES, DHW in summer is, however, switched off Operating modes DHW control uses one of the programmes available on the controller. It is important to note that when a 24-hour programme is prepared specifically for DHW, the operating modes available have the following significance : NORMAL 1...7; SEBACK 1-2 ; = ON (On) FLOW 1-2; FROSPRO; OFF =OFF (Off) = desired DHW = desired DHW Des i r ed emp BO I LER c 23.8 Des i r ed emp FROSPRO 6. 0c he same also applies when the operating programme of DHW is FOLLOWS HEAING Delay switching off pump DHW Pump De l ay Of f :NO Delay in switching off DHW pump when desired DHW temperature is reached : NO = no delay YES =delay in switching off 5 minutes fixed. 17. PROGRAMMES & PERIODS WIH DAES All the timed programmes are available both for compensated control and for the control of DHW. he periods with dates refer to compensated control and are followed for the control of DHW only if this is programmed as FOLLOWS HEAING hour programmes 24.1 How many 24hou r Programmes? P1 Event NORMAL c 24.7 P1 Event SEBACK c Set the number of 24-hour programmes you wish to use (1... 7). In each 24-hour programme (P1... P7) you can set a maximum of 6 event start times (Event 1... Event 6) assigning to each one of modes : NORMAL = compensated control with NORMAL ambient temperature SEBACK 1-2 = compensated control with SEBACK ambient temperature FLOW 1-2 = control with fixed FLOW temperature FROSPRO = compensated control with FROSPRO ambient temperature OFF = plant Off, valve closed & pump idle he event start times must be entered in increasing order. he events not used must be excluded by pressing + and keys at the same time ( ). You must not leave unused events ( ) between programmed events. 12

13 day programmes 24.8 How many 7day Programmes? day 1 MONDAY 2 4HOUR da y 1 SUNDAY 2 4HOUR Holiday periods How many Ho l i day Pe r i ods? Ho l i day P r og r am FROSPRO 6. 0c Ho l 01 s t a r t NO Fr --.--to Enter the number of programmes you wish to use (max. 2). In each 7-day programme you can assign to each day of the week one of following programmes : 24HOUR 1 7; NORMAL ; SEBACK 1-2 ; FLOW 1-2 ; FROSPRO; OFF. Set an operating programme, the same for all periods, which overrides the one in use. At the end of each holiday period the controller returns to normal operation. Enter the number of holiday periods or of bank holidays you wish to use (max. 25) so as to reduce the number of display pages dedicated to the entering of the dates. If left at 0 the programming pages do not appear. Choose the programme to be used during all the holiday periods : 7DAY 1-2; 24HOUR 1 7; NORMAL ; SEBACK 1-2; FLOW 1-2; FROSPRO ; OFF. Enter the dates of each single period : Hol 01 = selection of the periods available from How many Ho l i day Start : NO = holiday period not used Pe r i ods? = start period at hours 12 = start period at hours Fr to = day and month of start and end of holiday period For a single day of holiday enter the same date for start and end. o cancel a holiday period keep pressed the + and keys at the same time Special period 22.5 Spec i a l P r og r am 2 4HOUR Spec i a l Pe r i od Fr --.--to Extension period Remot e Ex t 21. 0c f or hour s 3 Period in which compensated control has to follow an operating programme, which overrides temporarily that in use, to meet special requirements : 7DAY 1-2; 24HOUR 1 7; NORMAL ; SEBACK 1-2; FLOW 1-2; FROSPRO ; OFF. It also applies to control of DHW if FOLLOWS HEAING has been configured (see 16. CONROL DHW). Enter the day and month of start and end of the special periods. he Extension period overrides all the programmes and modes in use, causing the heating to operate for the time and at the temperature entered. o activate the Extension period, close the switch c1 for at least five seconds and then open it. At the expiry of the hours set the controller will resume its automatic operation. Remote Ext 21.0c =entering desired ambient temperature during Remote Extension period. for hours : 3 =entering duration in hours of Remote Extension period. o stop the Remote Extension period before the time entered has expired press and keys at the same time Heating season Heat ing Season Fr --.--to Establishes the winter season heating period. Enter the day and month of start and end of heating season. Applies also to DHW if DHW summer : NO selected in DHW Summer : ALWAYS ON YES In summer period the boiler is excluded if OFF selected in Bo i l e r w i t h Hea t i ng :OFF o cancel the period keep pressed + and keys at the same time. 13

14 17.7 Summer time Summer ime Fr to he controller automatically changes the actual time in relation to the summer time period. Fr = the night of the last Saturday in March the clock is automatically put forward one hour to = the night of the last Saturday in October the clock is automatically put back one hour o cancel the period keep + and keys pressed at the same time Summer plant exercise Summer P l an t Exe rc i se NO his function prevents lockouts of valve and pumps during long periods of inactivity. NO: function excluded YES: Heating circuit : every Sunday at valve is opened for 15 minutes and at noon pump is switched on for 5 minutes. DHW circuit : If excluded in summmer, every Sunday at noon pump is switched on for 5 minutes. 18. COMPLEMENARY FUNCIONS 18.1 DHW priority & anticondensing he same function controls anticondensing and DHW priority : 27.6 NO = function excluded DHW P r i o r i t y & YES = When boiler temperature (measured by detector B4) falls by three times the differential An t i condens : NO set in respect of the desired value, the controller closes the heating valve with modulating control action. he DHW pump functions only when actual boiler temperature exceeds by 3 C actual DHW temperature Input B I npu t B6 : FLUGAS + ALARM Configuration of detector B6 input : FLUGAS + ALARM = if flue gases detector Pt 1000 and / or an alarm contact is connected REMOE CONROL = if remote control CDB 300 is connected 18.3 Input B I npu t B7 : FLUGAS + ALARM 18.4 Access keynumber 28.9 Cho i ce Keynumbe r ---- Access Keynumber Name site (plant) NameHea t i ngp l an t Display measurement 25.1 Des Amb : 21. 0c Ac t Amb : 21. 0c Des Ac t 25.3 Ou t s i de emp Actual : 2.0c 25.4 Des DHW : 50. 0c Ac t DHW : 58. 0c F l ow : 65. 0c F l ow : 64. 0c 25.5 DesBo i l e r : 70. 0c Ac tbo i l e r : 67. 0c 25.6 Flugas1Max: Flugas2Max: 185c 190c Configuration of detector B7 input : FLUGAS+ ALARM = if flue gases detector Pt 100 and / or an alarm contact is connected mA = if an active detector for various measurements (levels, etc) is connected Choice and enabling of access keynumber which prevents any modification of data by means of + and keys. Enter the number ( ) using + and keys. o cancel keynumber press + and at the same time until the dashes reappear. When keynumber is enabled, if + or keys pressed there will appear on the display a request to enter keynumber. Only after having entered the exact keynumber can + and keys be used. If for 15 minutes no key is pressed the keynumber is automatically re-enabled. Entering name of site (plant) which appears on first page of display. Each dash can be replaced, using + and keys, by a letter of the alphabet (A... Z) or by a digit (0... 9). he and key serve to position the cursor. he controller displays all the values measured by the detectors and the data which serves to monitor the operational status of the plant : ambient temperature requested by mode in use and actual measured by detector B3. If detector B3 is not connected, in place of Act Amb appears Cal Amb. flow temperature requested by mode in use and actual measured by detector B1. actual outside temperature. If detector B2 is not connected to controller, in place of actual will appear C-Ring and the value is that coming via C-Ring. DHW temperature requested by mode in use and actual measured by detector B5. If detector B5 not connected there will appear Act DHW : c temperature boiler requested by mode in use and actual measured by detector B4. If detector B4 not connected there will appear Act Boiler : c max temperature flue gases measured by detectors B6 and B7. if input B6 is configured as REMOE CONROL there will appear B6 : REMOE instead of Flugas 1 if input B7 is configured as mA there will appear B7 : 2.0mA instead of Flugas 2 o cancel the measurements press + and keys at the same time.

15 18.7 Recording data For each plant controlled, at each change of mode and every two hours, the controller records a series of data indicating the operational status of the plants controlled : Current time, current day, type of recording (change of mode or end of two-hour period); current mode, actual outside temp.,compensated flow temp., desired and actual flow temp, desired and actual ambient temp., anticondensing temperature. Status output relays. It is able to memorise 28 complete recordings. he last recording brings about the cancellation of the oldest one. If the first page is not displayed the controller makes the recording at the end of the two-hour period but not the recording at the change of mode because it presumes changes to the setting data are in progress. he recordings can be viewed only by the telemanagement computer. 19. ALARMS he alarms processed by the controller are of three types : alarms for abnormal functioning of the controller and of the heating zones controlled; alarms for short or open circuits of the detectors connected; alarms from external contacts. he alarm status is indicated by the LEDs on the controller facia and is identified, on the page Detector Alarms, by the letter A alternating with the number of the alarm concerned. With the C-Bus setup alarms can be sent to a local PC and / or to the telemanagement central PC Functional alarms 28.6 Func t i ona la l a rms 8 he functional alarms are triggered in the presence of prolonged differences between actual measured values and those desired. hese alarms, with the exception of the real time clock alarm (8), do not affect the operation of the controller Factory setting : all disabled except for real time clock alarm (8). With + and keys enable the alarms required by replacing the dashes with numbers. When the number blinks = alarm triggered he limit values and delay times for sending the alarms can be changed only by PC. ype and cause of alarm : 1 = difference temperature heating flow (B1) enabled when pump M1 in operation 2 = difference temperature boiler (B4) enabled when burner in operation triggered when actual temperature below that desired 3 = difference ambient temperature (B3) enabled with NORMAL modes and with outside temperature below desired ambient temperature. triggered when actual temperature below or above that desired. 4 = boiler overtemperature (B4) triggered when actual temperature above maximum limit temperature 5 = DHW temperature (B5) enabled when pump M2 in operation triggered when actual temperature below desired temperature 6 = flue gases 1 temperature (B6) enabled if input B6 is configured as FLUGAS + ALARM triggered when actual temperature above maximum limit temperature 7 = flue gases 2 temperature or active detector mA (B7) enabled according to configuration of input B7 triggered when actual temperature above maximum limit temperature or when actual measurement mA exceeds for at least one minute the minimum or maximum thresholds set 8 = internal real time clock (cannot be disabled ) triggered when clock assumes meaningless values Detector alarms he detector alarms are triggered in the event of short or open circuits De t ec t o r A l a rms Using + and keys, disable unrequired alarms replacing the numbers with dashes ype of alarm and effect : 15

16 19.3 Alarms or status by external contacts (K) 1 = flow detector (B1) with short or open circuit : valve stops where it happens to be and pump M1 maintains its status (idle or in operation) 2 = outside detector (B2) with short or open circuit : valve stops where it happens to be and pump M1 maintains its status (idle or in operation) In C-Ring last value continues to be transmitted 3 = ambient detector (B3) with short or open circuit : with pump M1 in operation, ambient temp. = desired ambient temp. With pump M1 Off, value of ambient temp. calculated by controller. 4 = boiler detector (B4) with short or open circuit : boilers operate with own thermostats ; anticondensing function disabled. 5 = DHW detector (B5) with short or open circuit : pump M2 idle 6 = flue gases 1 (B6) detector with open circuit alarm 7 = flue gases 2 (B7) detector with open circuit alarm 8 = C-Ring : open circuit or faulty controller, in ring. he effect of the alarm situation is delayed by a minute. Factory setting : or allarms enabled 28.8 K Al arms Alarms triggered by the closure of voltage-free contacts k1... k5 by the plant components (pumps, burners, etc). he presence of the alarm is indicated after about 60 seconds. Factory setting : all disabled. Enable alarms of interest by replacing dashes by numbers using + and keys. When the number blinks = alarm triggered. If not used as alarm they can be used as status indicators. 20. COMMISSIONING PLAN esting to be carried out on completion and testing of installation, wiring and configuration esting C-Ring he page of C-Ring testing appears only if configured YES in Ensure that all the other controllers wired in C-Ring are : 28.3 CRing Connection YES 29.1 CR i ng :?? correctly powered by mains voltage (230 V ~) Slave controllers or configured as SECONDARIES in selected on testing page 29.1 CR i ng :?? 28.3 CRing Connection: SECONDARY he PRIMARY controller (Cont. 1) sends via C-Ring a signal every five seconds ; on all the displays appears??. Each controller checks the incoming signal ; if the connection is positive the word YES replaces?? on all the displays. If on one or more displays YES does not appear, this indicates that there is an open connection between the last controller with YES and the first with?? ; or, in the event that YES does not appear on any display, this indicates that there is an open circuit between the first controller and the second. Examples of testing a C-Ring circuit with four controllers : Cont.1 "YES" Cont.2 "YES" Cont.3 "YES" Cont.4 "YES": C-Ring OK Cont.1 "??" Cont.2 "YES" Cont.3 "YES" Cont.4 "YES": Fault between 4 and 1 Cont.1 "??" Cont.2 "YES" Cont.3 "??" Cont.4 "??" : Fault between 2 and 3 Cont.1 "??" Cont.2 "??" Cont.3 "??" Cont.4 "??" : Fault between 1 and esting outputs 29.2 Ou t pu t : VALVE Status: IDLE Using + and keys, choose : output to be tested : VALVE ; PUMP ; DHW; BOILER 1; BOILER 2. status : with VALVE : IDLE ; CLOSES ; OPENS with PUMP, DHW, BOILER 1, BOILER 2 : ON or OFF Check the results. 16

17 21. SEQUENCE OF DISPLAY PAGES (the data and the functions are those in memory at time of delivery) 22. Htg: MONDAY Htg: HOUR 1 Mode : NORMAL d21.0c Var+0.0c MONDAY GM Spec i a l Pr og r am 24HOUR 1 Spec i a l Fr--.-- Pr og r am to--.-- DE 61 1 Eng. C2 Ve r s. xx ECHN I CAL PAGES PRESS + KEY Cho i ce Menu + / EMP & CONROLS + Des i r ed emp NORMAL c Des i r ed emp SEBACK c Des i r ed emp NORMAL c Des i r ed emp SEBACK c Des i r ed emp NORMAL c Des i r ed emp FROSPRO 6. 0 c Des i r ed emp NORMAL c Des i r ed emp FLOW c Des i r ed emp NORMAL c Des i r ed emp FLOW c Des i r ed DHW emp c DHW Summer ALWAYS ON : YES Remot e Ex t 21. 0c for hours 3 Ope r a t i on Bo i l e r AUOMAI C Bo i l e r w i t h Hea t i ng :OFF 24. Eco Of f NO Op t imumst a r t Op t imumst op : NO : NO Summer P l an t Exe r c i se : NO Cho i ce Menu + / EVENS & PER I ODS How many 24hou r P r og r ammes? 1 P1 Even t NORMAL c P1 Even t SEBACK c How many 7day P r og r ammes? 1 + 7day 1 MONDAY 2 4HOUR 1 7 da y 1 SUNDAY 2 4HOUR 1 How many Ho l i day Pe r i ods? 0 Ho l i day P r og r am FROSPRO 6. 0c 25. Ho l 01 s t a r t NO Fr to--.-- Hea t ing Season Fr to Summer ime Fr to Cho i ce Menu + / MEAS&COUN&CALC Cho i ce Menu + / SE HG & DHW Des Amb : 20. 0c Ac t Amb : 20. 0c Flugas1Max: 185c Flugas2Max: 190c ECHN I CAL PAGES PRESS + KEY + Des F l ow : 80. 0c Ac t F l ow : 80. 0c Bo i l er1 :xxxx hrs Bo i l er2 :xxxx hrs Hea t Emi t t e r s RAD I AORS Ou t s i de emp Ac t ua l : 2. 0c Degree-Days 20:xxxx Amb:xxxx Des i gn Ou t s i de emp : 5. 0c Des DHW : 60. 0c Des DHW : 58. 0c Design F l ow emp : 70. 0c DesBo i l e r : 70. 0c Ac tbo i l e r : 67. 0c Cu r veor i g i n O20 Flow : 20.0c + Flow Limi ts Min: 1c Max:99c Con t r o l : VALVE ime : 630 sec Ambi en tau thor i t y on Flow :---- Star t Iner t ia MANUAL h / h Op t S t a r t No rma l Ma x Du r a t : h Op t S t a r t Ho l i day Ma x Du r a t : h Op t imum S t a r t Coo l i ng ime Op t imum S t op + Boos t i ng: 3. 0c Cons t an t : 48 h r s DecreaseA :0. 5c Op t imum S t op Ma x Du r a t : h He a t i ng Pump : AU De l ay Of f : 30mi n DHW Pump De l ay Of f :NO DHW D i f f e r : 3. 0c An t i bac t e r i a :NO 27. Con t r o l Bo i l e r FIXED POIN Cho i ce Menu + / ECHN I CAL PAGES ype of Bo i l e r SE I NG BOI LER PRESS + KEY + 1BOI LER 1SAGE Con t r o l Bo i l e r COMPENSA ION + Des i r ed Bo i l e r emp : 80. 0c Increase Boi l er on Ht g+dhw:05. 0c Differential Bo i l e r : 5. 0c Cho i ce Menu + / CONF I G DE Bo i l e r L imi t s Min: 1c Max :99c ECHN I CAL PAGES Send A l a rms :NO Add r ess : 1 CRing Connect ion Input B6 PRESS + KEY + PassWe l eman :NO Group : NO FLUGAS + ALARM Input B7: FLUGAS + ALARM DHW P r i o r i t y & An t i condens : NO Func t i ona lal arms 8 Of f Stage 2: NO Ou t s i de : c De t ec t o r A l a rms K Al arms Cho i ce Ke ynumbe r 29. Cho i ce Menu + / ES I NG NameHea t i ngp l an t CR i ng :?? Ou t pu t : VALVE Status: IDLE Keys for scrolling the pages on display and positioning the cursor on the data which can be changed. he data which can be changed, in the following desriptive list of display pages, are highlighted thus Htg: By pressing at the same time, or at any rate after 15 minutes, the first page returns to the display MONDAY + Keys for : changing the values highlighteded by the cursor Hea t Emi t t e r s viewing the configuration options of a function, for example : FAN COI LS or passing directly from one menu (series of pages) to another. Hea t Emi t t e r s PANELS 17

B OPTIMISING COMPENSATOR FOR CONTROL TWO ZONES. DTE 602 Eng. C2 COSTER C BUS C RING. B DTE 602 Eng C

B OPTIMISING COMPENSATOR FOR CONTROL TWO ZONES. DTE 602 Eng. C2 COSTER C BUS C RING. B DTE 602 Eng C OPIMISING COMPENSAOR FOR CONROL WO ZONES C BUS C RING B 261 - DE 602 Eng C2 13.04.99 B 261 13.04.99 DE 602 Eng. C2 Optimising compensator compensated and optimised control of two heating zones Communication

More information

B 265 OPTIMISING COMPENSATOR SLAVE. DSE 600 Eng. C2 COSTER C BUS C RING. B DSE 600 Eng. C LB

B 265 OPTIMISING COMPENSATOR SLAVE. DSE 600 Eng. C2 COSTER C BUS C RING. B DSE 600 Eng. C LB OPTIMISING COMPENSATOR SLAVE B 265 - DSE 600 Eng. C2 28.12.05 LB B 265 28.12.05 LB C BUS C RING DSE 600 Eng. C2 Digital controller for boiler house with annual programming : compensated control of heating

More information

By means of C-Bus connection DTT 318 can be inserted in a telemanagement system.

By means of C-Bus connection DTT 318 can be inserted in a telemanagement system. B 282 - D 38 C Eng. 8..8 LB REV. FIXED POIN CROLLER FOR DISRIC HEAING B 282 8..8 LB REV. D 38 C Eng. Control of secondary circuit temperature at fixed point Control of minimum or maximum limits of primary

More information

B 520 ELECTRONIC AMBIENT TEMPERATURE CONTROLLERS. RTB C2 Eng. COSTER BUS. B RTB C2 Eng MC REV 01

B 520 ELECTRONIC AMBIENT TEMPERATURE CONTROLLERS. RTB C2 Eng. COSTER BUS. B RTB C2 Eng MC REV 01 ELECTRONIC AMBIENT TEMPERATURE CONTROLLERS C BUS C2 Eng. B 520 - C2 Eng. 25.09.07 MC REV 01 B 520 25.09.07 MC REV 01 1 On-Off output or 1 modulating & 1 On-Off 2 modulating outputs with Pl control action

More information

User Instructions For TopTronic RS-10

User Instructions For TopTronic RS-10 User Instructions For TopTronic RS-0 409ENG-Dec0 Hoval Ltd Northgate Newark Nottinghamshire NG4 JN Phone 066 677 Fax 066 675 Index 409ENG-Dec0 Introduction Introduction... Controls... Display... User instructions

More information

NRT 105: Electronic fan-coil controller, equiflex

NRT 105: Electronic fan-coil controller, equiflex Product data sheet 4.04 R 105: Electronic fan-coil controller, equiflex How energy efficiency is improved ECO Meter for displaying the current energy consumption and digital input for the change-over between

More information

COSTER. Adjustment of desired value by means of remote set point adjuster.

COSTER. Adjustment of desired value by means of remote set point adjuster. COSER EPERAURE CROER D 5 - RF 8 Eng. C.. D 5.. RF 8 Eng. C ntrol of temperature with cfigurable features : hree-point modulating with PI - in e or two stages Proportial - in e stage Power supply ; DI rail

More information

Sauter Components

Sauter Components R 44.488/ QRK 0: Heating controller Used in conjunction with temperature detectors (Ni000) and appropriate control valves for heating and domestic-hot-water control (with various configurations), mainly

More information

EQJW145. Content: 1 General. 2. Indicators and operating controls 3. Putting into service (by a technician) 4. How to operate (user)

EQJW145. Content: 1 General. 2. Indicators and operating controls 3. Putting into service (by a technician) 4. How to operate (user) SAUER equitherm Electronic heating controller 1) Valid from soft version 09 Content: General 2. Indicators and operating controls 3. Putting into service (by a technician) 4. How to operate (user) en Quick

More information

D 151 TEMPERATURE CONTROLLER. RTF 31.. C1 Eng. COSTER. D RTF 31.. C1 Eng DA REV. 01

D 151 TEMPERATURE CONTROLLER. RTF 31.. C1 Eng. COSTER. D RTF 31.. C1 Eng DA REV. 01 COSER EPERAURE COROER D 151 - RF 31.. C1 Eng. 18.1.7 DA REV. 1 D 151 18.1.7 DA REV. 1 RF 31.. C1 Eng. Cfigurable temperature ctrol: hree-wire modulating with PI ctrol acti - in e or two stages - proportial

More information

LK Wireless Room Control Cq

LK Wireless Room Control Cq LK Wireless Room Control Cq Description LK Wireless Room Control Cq consists of a LK Room Thermostat Cq-n (transmitter) and a LK Receiver Unit Cq 8 (8 channel receiver unit). The range also includes a

More information

TAC 2112 Manual (GB),

TAC 2112 Manual (GB), TAC 2112 Manual T1 P1 0-004-7459-3 (GB), 1999-08-01 Contents TAC 2112 Manual Subject to modification. 1999 TAC AB Contents 1 About this manual... 1:1 1.1 Overview... 1:1 1.2 How to use this manual...

More information

PRODUCT CATALOGUE TEMPERATURE CONTROL Grässlin products for individual control of temperature

PRODUCT CATALOGUE TEMPERATURE CONTROL Grässlin products for individual control of temperature PRODUCT CATALOGUE TEMPERATURE CONTROL Grässlin products for individual control of temperature Temperature control: Feel good at any time of year Room thermostats Heating time switches Excellent products

More information

Installation Guide. ECL Comfort 310, application A Table of Contents

Installation Guide. ECL Comfort 310, application A Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 6 2.1 Before you start.....................................................

More information

Universal Controller

Universal Controller 7 863 Universal Controller POLYGYR RWF32... ISO 9001 RWF32... with casing ARG61.01 The RWF32... is a universal digital boiler temperature / pressure controller designed for use in oil- and / or gas-fired

More information

Control module 2 circuits AD290. Installation and Service Manual

Control module 2 circuits AD290. Installation and Service Manual EN Control module 2 circuits AD290 Installation and Service Manual 129443-02 Contents 1 Introduction...4 1.1 Symbols used...4 1.2 Abbreviations...4 2 Safety instructions and recommendations...5 2.1 Recommendations...5

More information

theben Fan Coil Actuator FCA 1 Fan Coil Actuator FCA 1 FCA Version: Jan-08 (Subject to change) Page 1 of 77

theben Fan Coil Actuator FCA 1 Fan Coil Actuator FCA 1 FCA Version: Jan-08 (Subject to change) Page 1 of 77 Fan Coil Actuator FCA 1 FCA 1 492 0 200 Version: Jan-08 (Subject to change) Page 1 of 77 Contents 1 Functional characteristics...4 1.1 Operation and display...5 1.2 Advantages of the FCA 1...5 1.2.1 Special

More information

TLC3-BCR-U Series Thermostat

TLC3-BCR-U Series Thermostat OVERVIEW TLC3-BCR-U Series Thermostat Features Low power energy consumption: < 1W per unit Relays switching for outputs each up to 300W Temperature control for 2 or 4-pipe heating or cooling systems. Optional

More information

TC 204 Heating Controller

TC 204 Heating Controller TC 204 Heating Controller ver. 1.32-01 The TC204 is a multi-purpose heating controller with built-in programs for different types of heating systems. General Data Power requirement 24 volts ac, 2 va Inputs

More information

43.019/1. NRT 300: Electronic controller for air-conditioning (heating/cooling) Sauter Components

43.019/1. NRT 300: Electronic controller for air-conditioning (heating/cooling) Sauter Components 43.09/ NR 300: Electronic controller for air-conditioning (heating/cooling) For fixed-value control (I control, continuous) in air-conditioning systems, for residential and business premises. Used with

More information

COSTER E DTU 618 Eng. C

COSTER E DTU 618 Eng. C COSER E 111 - DU 618 Eng. C1 11.1. EMPERAURE & UMIDIY COROER FOR AIR ADIG UIS C BUS E 111 11.1. DU 618 Eng. C1 ranslator's note : hroughout this document the terms "discharge air" and "flow" have the same

More information

CM927 WIRELESS PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET

CM927 WIRELESS PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET CM927 WIRELESS PROGRAMMABLE THERMOSTAT FEATURES CM927 can be installed without disrupting your room décor as no wiring connection is required between the room unit and the boiler Attractive, slim, ultra-modern

More information

Fan Coil Actuator FCA 2

Fan Coil Actuator FCA 2 Fan Coil Actuator FCA 2 FCA 2 4920210 Updated: Feb-16 (subject to changes) Page 1 of 89 Contents 1 Function description... 4 1.1 Operation and display... 5 1.2 Advantages of the FCA 2... 6 1.2.1 Special

More information

Self-learning Room Temperature Controller Receiver

Self-learning Room Temperature Controller Receiver 2 265 REV23RF REV-R.02/1 REV23RF/SE Self-learning Room emperature Controller Receiver Consisting of controller (with integrated radio transmitter) and receiver (switching unit with relay outputs) REV23RF

More information

Electronic Air / Fuel Ratio Control System

Electronic Air / Fuel Ratio Control System 7 871 ISO 9001 Electronic Air / Fuel Ratio Control System RVW20... Electronic control unit - for use with modulating single- and dual-fuel burners - with extended functionality for mechanical air / fuel

More information

SERVICE-MANUAL ROOM TEMPERATURE CONTROLLER NEA 230V / 24V. Construction Automotive Industry

SERVICE-MANUAL ROOM TEMPERATURE CONTROLLER NEA 230V / 24V. Construction Automotive Industry ROOM TEMPERATURE CONTROLLER NEA 230V / 24V Construction Automotive Industry ROOM TEMPERATURE CONTROLLER NEA 230V / 24V TABLE OF CONTENTS 1....... Information and safety guidelines......................................................

More information

Device connection and commissioning can only be carried out by qualified professionals. Always make the connections while the power is switched off.

Device connection and commissioning can only be carried out by qualified professionals. Always make the connections while the power is switched off. V1.2.0 (03.03.2014) 1 (21) This user guide is for controllers with the software version 1.2.0 or newer. WIRING Device connection and commissioning can only be carried out by qualified professionals. Always

More information

Communicative heating controller

Communicative heating controller UC100 Communicative heating controller Summary UC100 is a communicative room heating controller with one PWM output for control of a radiator or electrical heater. It can work autonomously, or in connection

More information

43.030/1. NRT 101: Electronic room-temperature controller with time program. Sauter Components

43.030/1. NRT 101: Electronic room-temperature controller with time program. Sauter Components 43.030/ R 0: Electronic room-temperature controller with time program How energ efficienc is improved ECO meter for displa of instantaneous energ consumption and integrated time-switch for individual programming

More information

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W Page 2 / 16 INDEX: GENERAL TYPES ACESSORIES AND OPTIONS INSTALLATION WIRING DIAGRAMS CONNECTING TERMINALS DIAGRAMS WIRING DIAGRAM DESCRIPTION WORKING DESCRIPTION AND KEYBOARD WORKING DESCRIPTION AND PROGRAMMING

More information

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INSTRUCTIONS MANUAL IM831-U v0.92 HRI-R40W sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INDEX: GENERAL TYPES ACESSORIES AND OPTIONS

More information

WIRELESS CONTROL UNIT FOR CONTROL OF ELECTRIC HEATING DEVICES (WITHIN ONE ROOM)

WIRELESS CONTROL UNIT FOR CONTROL OF ELECTRIC HEATING DEVICES (WITHIN ONE ROOM) PH-BSP WIRELESS CONTROL UNIT FOR CONTROL OF ELECTRIC HEATING DEVICES (WITHIN ONE ROOM) Wireless control unit Two-way radio communication on 433.92 MHz Comfortable solution of room heating Predictive system

More information

Electronic AC Load ZSAC Series. 400 W up to 21,000 W 260 V up to 440 V 3 A up to 100 A. Rev. 3.03

Electronic AC Load ZSAC Series. 400 W up to 21,000 W 260 V up to 440 V 3 A up to 100 A. Rev. 3.03 Electronic AC Load Series 400 W up to 21,000 W 260 V up to 440 V 3 A up to 100 A Rev. 3.03 Electronic AC Loads, Series Interface overview RS-232 USB GPIB LAN System bus Analog / Analog isolated X X Standard

More information

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS INSTRUCTION MANUAL BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS 1/23 More information than that reported

More information

NRT 300: Electronic air-conditioning controller, heating/cooling, equiflex

NRT 300: Electronic air-conditioning controller, heating/cooling, equiflex roduct data sheet 43.019 NR 300: Electronic air-conditioning controller, heating/cooling, equiflex ow energy efficiency is improved ey directly on device for individual changeover between presence and

More information

VIESMANN. Installation and service instructions VITOTROL 300 RF. for contractors. Vitotrol 300 RF

VIESMANN. Installation and service instructions VITOTROL 300 RF. for contractors. Vitotrol 300 RF Installation and service instructions for contractors VIESMANN Vitotrol 3 RF Wireless remote control for one, two or three heating circuits For applicability, see the last page VITOTROL 3 RF 4/212 Please

More information

Microprocessor Based Multistage Temperature Controller & Two Channel 365 Day Time Switch. Made in Australia 100% Australian Owned Company

Microprocessor Based Multistage Temperature Controller & Two Channel 365 Day Time Switch. Made in Australia 100% Australian Owned Company Microprocessor Based Multistage Temperature Controller & Two Channel 365 Day Time Switch HTC DIGITAL-TC Features Use Australian Made and designed Combined Temperature & Time Switch Functions Power Supply

More information

FCU-503 FAN COIL CONTROLLER WITH RDU-TOUCH INTERFACE

FCU-503 FAN COIL CONTROLLER WITH RDU-TOUCH INTERFACE FCU-503 FAN COIL CONTROLLER WITH RDU-TOUCH INTERFACE BACnet Enabled Description The FCU-503 is designed to provide complete control of fan coil units and / or underfloor heating circuits. The FCU-5 incorporates

More information

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description. Use of the application program Product family: Product type: Manufacturer: Heating, air conditioning, ventilation Thermostat Siemens Name: Temperature controller UP 237 DELTA i-system Order no.: 5WG1 237-2AB_1

More information

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht Temperature Controller model MFC-301/T-Dry Version for Dry Transformers and Motors Technical Manual Licht Contents 1 Introduction 2 2 Operating principle 3 2.1 General principle 3 2.2 RTD operation 3 3

More information

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description. Use of the application program Product family: Product type: Manufacturer: Heating, air conditioning, ventilation Thermostat Siemens Name: Temperature controller UP 237 DELTA i-system Order no.: 5WG1 237-2AB_1

More information

Thermostat P. Thermostats Electronic room thermostat with clock for thermal actuators

Thermostat P. Thermostats Electronic room thermostat with clock for thermal actuators Thermostat P Thermostats Electronic room thermostat with clock for thermal actuators IMI HEIMEIER / Thermostats & Actuators / Thermostat P Thermostat P The Thermostat P room temperature controller is used

More information

Application Programs Descriptions

Application Programs Descriptions Devices Employing the Program Product family: Product type: Manufacturer: Heating Regulator Siemens Name: Temperature Controller UP 250 DELTA studio, titanium white Order-no.: 5WG1 250-2AB12 Name: Temperature

More information

Control solutions Biofloor

Control solutions Biofloor MR24 Central radio controller 24V Connect COMAP offers the Connect control system as part of its underfloor heating and cooling solution. Composed of a central radio control module (MR24), wireless digital

More information

CONTROL MANUAL. Dry-Pic 09PE - 09VE

CONTROL MANUAL. Dry-Pic 09PE - 09VE CONTROL MANUAL Dry-Pic 09PE - 09VE Translation of the original document 003, 04.01 EN CONTENTS PAGE 1 - IMPORTANT RECOMMENDATIONS 1.1 Power supply 1. Electronic board specifications 1.3 Caution 1.4 Earth

More information

Installation Guide. ECL Comfort 310, application A Table of Contents

Installation Guide. ECL Comfort 310, application A Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 5 2.1 Before you start.....................................................

More information

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems 3 048 RCU15 Room Temperature Controllers for heating and cooling systems RCU15 Choice of two-position or modulating PI control ON / OFF or PWM outputs for heating and cooling Control depending on room-

More information

16-Channel Yearly Time Switch TR 648 S DCF

16-Channel Yearly Time Switch TR 648 S DCF 16-Channel Yearly Time Switch TR 648 S DCF Illustration 1 : TR 648 S DCF TR 648 S DCF EIB 648 9 201 DCF 77 Antenna 907 0 271 Obelisk 2.0 Programming set 907 0 305 Obelisk 2.1 Software 931 0 961 Page 1

More information

WLDS-10 Mk3 MAJOR WATER LEAK DETECTION SYSTEM INSTALLATION & COMMISSIONING

WLDS-10 Mk3 MAJOR WATER LEAK DETECTION SYSTEM INSTALLATION & COMMISSIONING WLDS-10 Mk3 MAJOR WATER LEAK DETECTION SYSTEM INSTALLATION & COMMISSIONING DESCRIPTION: An electronic control panel used in conjunction with one pulse meter (a water meter with pulse output proportional

More information

Radiocontrol F. Floor Heating Controller Radio control system for floor heating

Radiocontrol F. Floor Heating Controller Radio control system for floor heating Radiocontrol F Floor Heating Controller Radio control system for floor heating IMI HEIMEIER / Floor Heating Control / Radiocontrol F Radiocontrol F The Radiocontrol F radio control system for controlling

More information

TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller. Mounting and Operating Instructions EB 5578 EN

TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller. Mounting and Operating Instructions EB 5578 EN TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller Mounting and Operating Instructions EB 5578 EN Firmware version 2.2x Edition May 2015 Definition of signal words DANGER!

More information

B 556. LOCAL BUILT-IN OR WALL-MOUNTED UNIT WITH Volt RELAY OUTPUT "MULTIZONE" SYSTEM. RTL 120 Eng. = built-in unit

B 556. LOCAL BUILT-IN OR WALL-MOUNTED UNIT WITH Volt RELAY OUTPUT MULTIZONE SYSTEM. RTL 120 Eng. = built-in unit LOCAL BUILT-IN OR WALL-MOUNTED UNIT WITH 0...10 Volt RELAY OUTPUT "MULTIZONE" SYSTEM P LOC RTL 120 Eng. = built-in unit B 556 - RTL 120/520 Eng. 24.05.10 AM REV. 03 B 556 24.05.10 AM REV. 03 RTL 520 Eng.

More information

Contents. English User Manual Regulators

Contents. English User Manual Regulators Contents Safety warnings Page 28 Technical specifications Page 28 Description of instrument Page 31 Electrical connections Page 31 Glossary Page 32 Operation Page 37 Setting the regulation parameters Page

More information

Titan Products RDU-4/TS & RDU-4/5B Time Scheduling Room Display Units

Titan Products RDU-4/TS & RDU-4/5B Time Scheduling Room Display Units Titan Products RDU-4/TS & RDU-4/5B Time Scheduling Room Display Units 1 Time Scheduling RDU-4/TS - Description of Control Operation The temperature control and time scheduling for the building space is

More information

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems 3 048 RCU15 Room Temperature Controllers for heating and cooling systems RCU15 Choice of two-position or modulating PI control ON / OFF or PWM outputs for heating and cooling Control depending on room-

More information

EY-EM 527: Remote I/O module, ecolink527

EY-EM 527: Remote I/O module, ecolink527 Product data sheet 94.078 EY-EM 527: Remote I/O module, ecolink527 How energy efficiency is improved Regulation, control, monitoring and optimisation of operational systems, e.g. room automation or HVAC

More information

TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller. Mounting and Operating Instructions EB 5578 EN

TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller. Mounting and Operating Instructions EB 5578 EN TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller Mounting and Operating Instructions EB 5578 EN Firmware version 2.30 Edition November 2017 Definition of signal words DANGER!

More information

INSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12

INSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12 INSTRUCTION MANUAL Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS Power Factor Controller A12 1. CONTENTS 1. CONTENTS 1 2. FEATURES 2 3. INSTALLATION, CONNECTION AND APPLYING POWER 2 4.

More information

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions ELECTRONIC SPEED CONTROLLER Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING

More information

Functional data Factory settings Variable Settings

Functional data Factory settings Variable Settings echnical data sheet Rotary actuator RF-MF(-O) Multifunctional rotary actuator with emergency control for and 3 way control ball valve orque Nm Nominal voltage AC/DC V Control: Modulating DC... V or variable

More information

EIB/KNX Switch Actuators. User manual

EIB/KNX Switch Actuators. User manual EIB/KNX Switch Actuators User manual IT KNT 004 IT KNT 012 Tel.: +34943627988 E-mail: knx@dinuy.com Web: www.dinuy.com Contents 1. Introduction --------------------------------------------------------------------------------------------------------------

More information

Intelligent Compact Controller

Intelligent Compact Controller TCY-T0121 Intelligent Compact Controller Features Temperature control for 2-pipe, 4-pipe HVAC systems. Temperature range from 40 to 140 C. 1 independent PI and On/Off control loop to control temperature.

More information

400 W up to 21,000 W 260 V up to 440 V 3 A up to 100 A. Electronic Load ZSAC

400 W up to 21,000 W 260 V up to 440 V 3 A up to 100 A. Electronic Load ZSAC 400 W up to 21,000 W 260 V up to 440 V 3 A up to 100 A Electronic Load Electronic AC Loads, Interface overview RS-232 USB GPIB LAN System bus Analog X Analog isolated X Standard ption / not available 4226

More information

CAN-I/O 45 CAN-I/O Module 45 Software Version 1.13 Programming Functions Manual Version 1.13

CAN-I/O 45 CAN-I/O Module 45 Software Version 1.13 Programming Functions Manual Version 1.13 www.ta.co.at CAN-I/O 45 CAN-I/O Module 45 Software Version 1.13 Programming Functions Manual Version 1.13 English Table of contents Programming with TAPPS2... 5 Schematic diagram of a function module...

More information

AEROCONNECT 1B NA C Control manual

AEROCONNECT 1B NA C Control manual AEROCONNECT 1B NA 11.3 C 03-01 Control manual EN CONTENTS PAGE 1 - IMPORTANT RECOMMENDATIONS 1.1 Power supply 1. Electronic board specifications 1.3 Caution 1.4 Earth 1. Sensor connections 1.6 Communication

More information

WIREFREE CHRONOTHERM FEATURES PRODUCT SPECIFICATION SHEET. CM67RF can be used with Automatic Time Setting module (Q6667B1007)

WIREFREE CHRONOTHERM FEATURES PRODUCT SPECIFICATION SHEET. CM67RF can be used with Automatic Time Setting module (Q6667B1007) CM67RF WIREFREE CHRONOTHERM PRODUCT SPECIFICATION SHEET The CM67RF Chronotherm is designed to provide automatic time and temperature control of heating or cooling systems in villas and apartments. It can

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet SVK24A--PC Communicative globe valve actuator with emergency control function for 2-way and 3-way globe valves Actuating force 1500 N Nominal voltage AC/DC 24 V Control modulating,

More information

AC/DC 24 V, 50/60 Hz. Functional data Variable Settings. DC V, max. 0.5 ma. End point DC V... 4 ma ma Non-variable

AC/DC 24 V, 50/60 Hz. Functional data Variable Settings. DC V, max. 0.5 ma. End point DC V... 4 ma ma Non-variable echnical data sheet S--MF- Multifunctional rotary actuator for butterfly valves orque 00 Nm Nominal volta e V Control: ontrol configurable confi urable Position feedback: configurable Auxiliary u iliary

More information

OPERATING INSTRUCTIONS ARE ON PAGE 5. SECTION 2 Technical Data Transmitter Unit. RVHT 2 MULTI-FIT Programmable R/F Thermostat-Pair SECTION 1

OPERATING INSTRUCTIONS ARE ON PAGE 5. SECTION 2 Technical Data Transmitter Unit. RVHT 2 MULTI-FIT Programmable R/F Thermostat-Pair SECTION 1 OPERATING INSTRUCTIONS ARE ON PAGE 5 RVHT 2 MULTI-FIT Programmable R/F Thermostat-Pair SECTION 1 This Programmable Ravenheat R/F controlled room Thermostat RVHT 2, consists of 2 items: a Mobile Transmitter

More information

K-BUS Switch Actuator

K-BUS Switch Actuator K-BUS Switch Actuator User manual-ver. 2 KA/R0416.1 KA/R0816.1 KA/R1216.1 Contents Contents... 2 1. Introduction... 3 1.1 Product and function overview... 3 2. Technical Properties... 3 3. Commissioning...

More information

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. REGULATION AUTOMATIC SYNCHRONIZER for GENERATOR NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

EUROSTER 2026/2026TX

EUROSTER 2026/2026TX EUROSTER 2026/2026TX - User Manual 1 EUROSTER 2026/2026TX 1. CHARACTERISTICS 4 different programs for each day of the week (28 different ranges and temperatures altogether). Time programming with 10 minutes

More information

ELECTRONIC THERMOSTAT: T920

ELECTRONIC THERMOSTAT: T920 μnistδt ELECTRONIC THERMOSTAT: T One analog output DESCRIPTION The T series thermostats are microcomputer-based, proportional and integral (PI) devices with one analog 0 to 0 output. They can be used with

More information

R7426A. MicroniK 200 TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK

R7426A. MicroniK 200 TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK MicroniK 200 R7426A TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK PRODUCT DATA Fig. 1. Temperature controller FEATURES Microcontroller design based on modern digital technology User interface

More information

AHC-XP. Dewpoint-guided Power Controller for Glass and Handrail Heaters. Front view. Characteristics

AHC-XP. Dewpoint-guided Power Controller for Glass and Handrail Heaters. Front view. Characteristics Dewpoint-guided Power Controller for Glass and Handrail Heaters Front view Characteristics Dew point-guided power controller for cost-optimized operation of glass and handrail heaters Digital display of

More information

RAM 712 KNX room thermostat for surface-mounted and flush-mounted installation

RAM 712 KNX room thermostat for surface-mounted and flush-mounted installation RAM 712 KNX room thermostat for surface-mounted and flush-mounted installation RAM 712 712 9 200 Version: Dec-10 (subject to change) Page 1 of 65 Contents 1 Functional characteristics... 4 1.1 Operation...

More information

Application Sheet Fan coil unit with staged fan, heating/cooling coil (2 pipe) on triac output and electric reheater

Application Sheet Fan coil unit with staged fan, heating/cooling coil (2 pipe) on triac output and electric reheater Heating with LHW and cooling with CHW changeover Modulating control of heating and cooling valve (2 pipe) on triac Automatic or manual 3-speed fan control Room temperature and fan speed operation via KNX

More information

RAMSES 784 HF Set 1. Bedienungsanleitung Uhrenthermostat 1. Operating Instructions Clockthermostat 14. Mode d emploi Thermostat à horloge 26

RAMSES 784 HF Set 1. Bedienungsanleitung Uhrenthermostat 1. Operating Instructions Clockthermostat 14. Mode d emploi Thermostat à horloge 26 309 484 01 RAMSES 784 HF Set 1 784 9 407 784 9 417 Bedienungsanleitung Uhrenthermostat 1 Operating Instructions Clockthermostat 14 Mode d emploi Thermostat à horloge 26 Gebruiksaanwijzing Klokthermostaat

More information

Series R48 Single Zone Load Sequenced Economizer System: Installation & Troubleshooting

Series R48 Single Zone Load Sequenced Economizer System: Installation & Troubleshooting FANs 216, 121 Technical Bulletin R48 Issue Date 0695 Series R48 Single Zone Load Sequenced Economizer System: Installation & Troubleshooting Table of Contents Mounting... 1 Output Control... 2 Wiring...

More information

NRT 107: Room- and supply-temperature controller, equiflex

NRT 107: Room- and supply-temperature controller, equiflex Product data sheet 43.036 NR 107: Room- and supply-temperature controller, equiflex Ho energy efficiency is improved Analogue input for shifting the setpoint depending on the outside temperature, and integrated

More information

UBZ-301 (63-630A) UNIVERSAL INDUCTION MOTOR PROTECTION UNIT

UBZ-301 (63-630A) UNIVERSAL INDUCTION MOTOR PROTECTION UNIT Ltd Intelligent industrial electronics UBZ-301 (63-630A) UNIVERSAL INDUCTION MOTOR PROTECTION UNIT OPERATING MANUAL Quality control system on the development and production complies with requirements ISO

More information

INSTRUCTION MANUAL DT10RF OPTIMISING PROGRAMMER UK/IE OPERATING AND INSTALLATION

INSTRUCTION MANUAL DT10RF OPTIMISING PROGRAMMER UK/IE OPERATING AND INSTALLATION Hol Man Auto Day OPERATING AND INSTALLATION DIGISTAT OPTIMISER - Radio frequency controlled programmable room thermostat with domestic hot water programmer FOR GREENSTAR CDi AND GREENSTAR Si MODELS ALSO

More information

[ 4 ] Using pulse train input (F01 = 12)

[ 4 ] Using pulse train input (F01 = 12) [ 4 ] Using pulse train input (F01 = 12) Selecting the pulse train input format (d59) A pulse train in the format selected by the function code d59 can give a frequency command to the inverter. Three types

More information

WLDS-10 Mk2 MAJOR WATER LEAK DETECTION SYSTEM INSTALLATION & COMMISSIONING

WLDS-10 Mk2 MAJOR WATER LEAK DETECTION SYSTEM INSTALLATION & COMMISSIONING WLDS-10 Mk2 MAJOR WATER LEAK DETECTION SYSTEM INSTALLATION & COMMISSIONING DESCRIPTION: An electronic control panel used in conjunction with one pulse meter (a water meter with pulse output proportional

More information

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION GUIDE SPECIFICATIONS 256920-UGS-A-0506 Simplicity Intelli-Comfort Optional Control in 3-25 Ton Packaged Units GENERAL DESCRIPTION CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP Equipment with Simplicity

More information

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator REGULATION Automatic Synchronizer for Generator NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

Technical manual GS 4x.00 knx application description air quality sensor

Technical manual GS 4x.00 knx application description air quality sensor Technical manual GS 4x.00 knx application description air quality sensor General Information The device fits for the particular use of the following tasks: monitoring of the air quality in building systems

More information

Overview of types. Technical data

Overview of types. Technical data echnical data sheet SHA-.. Multifunctional linear actuators for adjusting air dampers and slide valves in ventilation and air-conditioning systems for building services installations For air control dampers

More information

Instruction manual. art Installation manual

Instruction manual. art Installation manual Instruction manual art. 01521 Installation manual Contents GENERAL FEATURES AND FUNCTIONALITY from page 4 ETS PARAMETERS AND COMMUNICATION OBJECTS from page 6 COMMUNICATION OBJECTS GENERAL FEATURES AND

More information

SYNCHRONISM RELAY SYNCRO-96. (Code ) INSTRUCTION MANUAL ( M / 99A ) (c) CIRCUTOR S.A.

SYNCHRONISM RELAY SYNCRO-96. (Code ) INSTRUCTION MANUAL ( M / 99A ) (c) CIRCUTOR S.A. SYNCHRONISM RELAY SYNCRO-96 (Code 2 28 913-2 28 914-2 28 915) INSTRUCTION MANUAL ( M 981 196 / 99A ) (c) CIRCUTOR S.A. ----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 1 Synchronism relay

More information

FCU-501 FAN COIL CONTROLLER WITH RDU-4 INTERFACE

FCU-501 FAN COIL CONTROLLER WITH RDU-4 INTERFACE FCU-501 FAN COIL CONTROLLER WITH RDU-4 INTERFACE BACnet Enabled Description The FCU-501 is designed to provide complete control of fan coil units and / or underfloor heating circuits. The FCU-5 incorporates

More information

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application STR-LCF Electronic Fan Coil Thermostat (Flush mounting) Datasheet Subject to technical alteration Issue date: 28.2.217 Application The fan coil room thermostat has been designed for individual control

More information

RADIO DRIVER. * _Rev.1* Installation guide. Wireless programmer. RADIO DRIVER zone RADIO DRIVER zones

RADIO DRIVER. * _Rev.1* Installation guide. Wireless programmer. RADIO DRIVER zone RADIO DRIVER zones Installation guide RADIO DRIVER Wireless programmer 6051117 6051118 RADIO DRIVER 610-1 zone RADIO DRIVER 620-2 zones DELTA DORE - Bonnemain - 35270 COMBOURG - FRANCE E-mail: deltadore@deltadore.com 6051119

More information

Room Temperature Controller

Room Temperature Controller 2 214 REV200.03RF REV200S.03RF REV200RF/SE REV200SRF/SE Room emperature Controller REV-R.03/1 REV-R.03S/1 REV200../SE Backlit touch screen with integrated radio transmitter and receiver (switching unit

More information

Room sensors. In ventilating and air conditioning plants to acquire relative humidity and temperature in rooms. Humidity measuring range

Room sensors. In ventilating and air conditioning plants to acquire relative humidity and temperature in rooms. Humidity measuring range 1 857 1857P01 QFA20 Room sensors For relative humidity and temperature QFA20 Operating voltage AC 24 V or DC 13.5 35 V Signal output DC 0...10 V for relative humidity Signal output DC 0...10 V or LG-Ni

More information

Application Sheet Fan coil unit with variable fan, heating/cooling coil (2 pipe) on triac output and electric reheater

Application Sheet Fan coil unit with variable fan, heating/cooling coil (2 pipe) on triac output and electric reheater Heating with LHW and cooling with CHW changeover Modulating control of heating and cooling valve (2 pipe) on triac Automatic or manual variable fan speed control DC 0...10 V Room temperature and fan speed

More information

Computer-14d - xx - 144a

Computer-14d - xx - 144a POWER FACTOR REGULATOR Computer-14d - xx - 144a INSTRUCTION MANUAL ( M 981 602 / 98B ) (c) CIRCUTOR S.A. -------- POWER FACTOR REGULATOR COMPUTER- 14d --------- Page 2 1.- POWER FACTOR REGULATORS COMPUTER-14d-144a

More information

CAN-IO Custom IO remote module

CAN-IO Custom IO remote module CAN-IO Custom IO remote module Main characteristics High customization Integrate different types of inputs/ outputs Up to 40 total channels DIN rail mount or plate Main applications Climatic chambers Autoclaves

More information

* _Ver.1* GP8 Radio CPL Radio DRIVER Energy manager

* _Ver.1* GP8 Radio CPL Radio DRIVER Energy manager GP8 Radio CPL Radio DRIVER Energy manager Delta Dore hereby declares that the equipment complies with the essential requirements and other relevant provisions of the R&TTE Directive 1999/5/EC The EC declaration

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet GR24A--R Communicative Retrofit rotary actuator for rotary valves and butterfly valves Nominal torque 40 Nm Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Position

More information