1 TAC 2112 Manual T1 P (GB),

2

3 Contents TAC 2112 Manual Subject to modification TAC AB Contents 1 About this manual... 1:1 1.1 Overview... 1:1 1.2 How to use this manual... 1:1 1.3 Associated documentation... 1:2 2 TAC 2112 heating controller... 2:1 3 Using the operator s panel... 3:1 3.1 Introduction... 3:1 3.2 What is shown in the display window?... 3: Parameter numbers and parameter values... 3: Operating modes... 3: Weekly program... 3: Outputs from the controller... 3: Alarm... 3:5 3.3 How are the buttons used?... 3:6 4 Day-to-day usage... 4:1 4.1 Introduction... 4:1 4.2 Reading temperatures... 4:1 4.3 Setting temperatures... 4:2 4.4 Adjusting the reset curve... 4:2 4.5 Setting the time schedule for daytime/night operation... 4: Weekly program for night setback of heat... 4: Reduction in heating during a holiday period... 4: Weekly program for external units... 4:4 4.6 Reading alarms... 4:5 4.7 Setting the operating mode... 4:5 4.8 Setting the clock... 4:6 5 Installation... 5:1 5.1 Assembly... 5:1 5.2 Connection... 5:6 5.3 Starting up... 5:10 6 Troubleshooting... 6:1 TAC AB, (GB), i

4 Contents 7 Functional description... 7:1 7.1 Introduction... 7:1 7.2 Controller operating modes... 7:1 7.3 Heat control... 7: Functional diagram... 7: Damped outdoor temperature... 7: Reset curve for outdoor compensation... 7: Automatic adjustment of the reset curve... 7: Supply controller... 7: Room controller...7: Return temperature limitation... 7: Remote heating control (SPC)... 7: Pump control... 7: Variable night setback... 7: Morning heating... 7: Reduced daytime operation (optimised stop)... 7: Extended daytime operation... 7: Forced night setback... 7: Clock... 7: Time schedules... 7: Alarm... 7: Memory backup... 7: Adjustment of sensor inputs... 7: Manual control... 7: Test functions... 7:21 8 Technical data... 8:1 Appendix A, Commissioning protocol/list of parameters... A:1 Index... Index:1 ii, (GB) TAC AB,

5 About this manual 1 About this manual 1.1 Overview Chapter 2, TAC 2112 heating controller Chapter 3, Using the operator s panel Chapter 4, Day-to-day usage Chapter 5, Installation Chapter 6, Troubleshooting Chapter 7, Functional description Chapter 8, Technical data This gives a brief introduction to the controller. This provides a more detailed explanation of how to read off and set the values using the buttons and the display window. This chapter provides you with sufficient information to be able to use the controller during normal operation. This chapter shows you how to assemble, connect and commission the controller. This chapter contains actions that you yourself can implement in order to locate and rectify any faults in the control system. Here you will find a detailed description of all the functions and parameters of the controller. All the technical data for the TAC 2112 can be found here. Appendix A, Commissioning protocol/list of parameters Index Here you will find a commissioning protocol, which also provides support for adjustment of the controller. All the parameters in the controller are also defined. At the end of this manual is an index with page references. TAC AB, (GB) 1:1(2)

6 About this manual 1.2 How to use this manual During normal operation During installation and commissioning During troubleshooting The TAC 2112 Manual describes all the functions and procedures necessary to install, adjust and use the controller. The TAC controller, as well as other products from the 2000-range, should not be used for purposes other than intended for. Before reading off or setting temperatures and other parameters during normal operation, it is sufficient to read Chapter 3, Using the operator s panel and Chapter 4, Day-to-day usage. You can also use the Quick Reference on the front of the controller. Before installing and commissioning the controller, you should read Chapter 5, Installation. The enclosed document entitled Installation instructions may also be used. A commissioning protocol is supplied with the controller, but this can also be found in Appendix A. In the event of a fault with the controller you should read Chapter 3, Using the operator s panel, Chapter 4, Day-to-day usage, and Chapter 6, Troubleshooting. 1.3 Associated documentation Enclosed documentation The documentation listed below is supplied with the controller. It contains all the information you need to install and commission the controller. Installation instructions for the TAC 2112 (part number 0FL-3678) Commissioning protocol for the TAC 2112 (part number 0FL-3679) TAC 2112 Quick Reference (part number 0FL-3672) 1:2(2), (GB) , TAC AB

7 TAC 2112 Heating Controller 2 TAC 2112 Heating Controller The TAC 2112 is a digital heating controller for controlling waterborne heat in buildings. The radiator circuit is controlled according to an outdoor temperaturecompensated reset curve, with or without a reference sensor. The controller contains a real time clock and can be set for weekly and yearly time schedules, along with powerful functions for optimum energy saving. It is very simple to read and set temperatures and other parameters. The display window provides clear information with digits and symbols. The controller can be mounted on a norm rail, in a panel or on a wall. TAC AB, (GB), 2:1(2)

8 TAC 2112 Heating Controller The TAC 2112 is designed to control heat in apartment buildings, offices, schools and other large buildings. Installation with district heating The controller operates both with and without reference sensors. However, some optimisation functions require a reference sensor to be installed. Installation with heating boiler 2:2(2), (GB) , TAC AB

9 Using the Operator s Panel 3 Using the Operator s Panel 3.1 Introduction This chapter shows you how to use the buttons on the operator s panel and the display window to read off and set parameters such as temperatures. 3.2 What is shown in the display window? The display window provides you with information from the heating installation in the form of digits and symbols. 24-hour time bar Parameter number Parameter value Alarm Pump MO TU WE TH FR SA P 00 12:00! K1 K2 SU AM C F K3 K Heating valve opens Heating valve closes Morning heating Heating off Fixed night setback Timed operation Fixed daytime operation Buzzer alarm Manual control Weekly program 2 Information in the display window TAC AB, (GB), 3:1(6)

10 Using the Operator s Panel Parameter numbers and parameter values The controller has a list of 100 parameters numbered from 0 to 99. Some of these parameters can be set (such as the setpoint for supply temperature), while others can just be read (such as the outdoor temperature). Some parameters cannot be displayed if the corresponding function is blocked. For example, the room temperature will not be displayed if there is no reference sensor. The parameter numbers and parameter values in the display window constitute a window to the list of parameters. List of parameters P 18 Reset curve (x1) P 19 Reset curve (y0) Display window 6 P 20 Reset curve (y1) Window up Parameter number Parameter value K1 MO P C P 24 P band, supply c. P 25 Run time, actuator P 26 Max. increase rate Window down The display window constitutes a window to the list of parameters The buttons and are used to move the window up and down over the list of parameters. 3:2(6), (GB) , TAC AB

11 Using the Operator s Panel Operating modes The different operating modes of the controller are shown in the display window using the symbols below MO TU WE TH FR SA P 00 12:00! K1 K2 SU AM C F K3 K Operating mode The symbols for the operating mode of the controller The symbols have the following meanings: Heating off Fixed night setback Timed operation Fixed daytime operation Manual control Heat reduction during holiday period Forced night setback from external connection (flashing moon) Extended daytime operation from external connection (flashing sun) How to set the operating mode is described in chapter 4. See chapter 7 for a more detailed description of the operating modes. TAC AB, (GB), 3:3(6)

12 Using the Operator s Panel Weekly program The weekly program for daytime and night operation is displayed in the form of a 24-hour time bar from 00:00 to 24:00. Filled segments show the time of day when daytime operation is to be effected. 24-hour time bar Weekdays MO TU WE TH FR SA P 00 12:00! K1 K2 SU AM C F K3 K The symbols for weekly programs Each segment on the 24-hour bar equals 30 minutes. A filled-in segment signifies daytime operation. Segments which are not filled in signify night setback. The days of the week are included beneath the clock. They show the day of the week to which the 24-hour bar refers. MO = Monday TU = Tuesday WE = Wednesday TH = Thursday FR = Friday SA = Saturday SU = Sunday How to set the weekly program is described on in chapter 4. See chapter 7 for a more detailed description of time schedules. 3:4(6), (GB) , TAC AB

13 Using the Operator s Panel Outputs from the controller The controller has a number of outputs for the control of external units (such as the actuator for the heating valve). When an output is activated, its symbol is displayed in the display window Pump MO TU WE TH FR SA P 00 12:00! K1 K2 Morning heating Heating valve opens Buzzer alarm SU AM C F K3 K Weekly program 2 Heating valve closes The symbols for outputs from the controller Alarm In the event of an alarm, a flashing alarm symbol is displayed in the display window MO TU WE TH FR SA P 00 12:00! K1 K2 SU AM C F K3 K Alarm The alarm symbol How to read off alarms is described in chapter 4. See chapter 7 for a more detailed description of the alarm function in the controller. TAC AB, (GB), 3:5(6)

14 Using the Operator s Panel 3.3 How are the buttons used? The controller has five buttons beneath the display window. Daytime/night operation weekly program Select parameter Increase/decrease parameter value The buttons on the operator s panel The and buttons are used to select a parameter. The and buttons are used to change a parameter value. The button is used to toggle between a filled and a blank segment in the 24-hour clock. To save a changed parameter value, press again. 3:6(6), (GB) , TAC AB

15 Day-to-day Usage 4 Day-to-day Usage 4.1 Introduction 4.2 Reading temperatures This chapter provides sufficient information for you to read off and set temperatures and other parameters during normal operation. All parameters and functions are described in detail in Chapter 7, Functional description. Procedure for reading a temperature: P C Select parameter number (P No.) by pressing or as shown in the list below. Increase or decrease the number by pressing or K Hold down the button for fast increase/decrease. 3 Press and at the same time to get to P 15 P Read the value. Temperature P No. Outdoor temperature P 01 Damped outdoor temperature P 02 Supply temperature P 03 Supply temperature, calculated setpoint P 04 Room temperature P 07 Room temperature, calculated setpoint P 08 Return temperature, heating circuit P 13 TAC AB, , 4:1(6)

16 Day-to-day Usage 4.3 Setting temperatures Procedure for setting a temperature: K1 P C Select parameter number (P No.) by pressing or as shown in the list below. The parameter number is increased and decreased by pressing or. Hold down the button for fast increase/decrease. 2 Press and at the same time to get to P 15 P Change the temperature by pressing or. 4 Exit by pressing. Temperature P No. Night setback of supply temperature P 06 Room temperature, setpoint day P 09 Room temperature, setpoint night P Adjusting the reset curve Procedure for adjusting the reset curve: K1 P C Select parameter number (P No.) by pressing or as shown in the figure below. Increase and decrease by pressing or. Hold down the button for fast increase/decrease. 2 Press and at the same time to get to P 15 P Adjust the curve point by pressing or. 4 Exit by pressing. P 23 P P 19 P 20 P 18 Parallel shift ± C P 21 P Damped Reset curve parameters See chapter 7 for a more detailed description of the function of the reset curve. 4:2(6), (GB) , TAC AB

17 Day-to-day Usage 4.5 Setting the time schedule for daytime/night operation Weekly program for night setback of heat When the controller is supplied, it is set for night setback of heat between 22:00 and 06:00 for all days of the week. See chapter 7 for a more detailed description of the time schedule. Procedure for changing the weekly program: MO P 14 K Select parameter number P 14 by pressing or. The parameter number is increased and decreased by pressing. 2 When the parameter number has been selected, the 24-hour time bar will be displayed showing MO for Monday. or 3 Scroll in the 24-hour time bar by pressing or until you get to the segment to be changed. The segment will flash. 4 Change the half-hour segments by pressing. A filled-in segment will result in daytime operation. When a segment has been changed, the next segment will start to flash. 5 Scroll on to TU for Tuesday by pressing. 6 Change the half-hour segments for Tuesday by pressing. 7 Repeat steps 5 and 6 for each day of the week. 8 Exit by pressing or Reduction in heating during a holiday period It is possible to program up to six holiday periods. During a holiday period, the heating is controlled at the setpoint for the night. No holiday periods are programmed prior to delivery. See chapter 7 for a more detailed description of time schedules. Procedure for setting a holiday period: K1 P Select parameter number P 63 by pressing or. The parameter number is increased and decreased by pressing. Press and at the same time to get to P 15 P Select a holiday period (1 6) by pressing or. or K1 P Go to P 64 by pressing. 4 Set the start date (month.day) by pressing or. Hold the button down for fast increase/decrease. TAC AB, , 4:3(6)

18 Day-to-day Usage K1 P Go to P 65 by pressing. 6 Set the end date (month.day) by pressing or. 7 Exit by pressing. Procedure for deleting a holiday period: K1 P Select parameter number P 63 by pressing or. The parameter number is increased and decreased by pressing or. Press and at the same time to get to P 15 P Select a holiday period (1 6) by pressing or K1 P Go to P 64 by pressing. 4 Change the start date to day 0 in the month (month.00) by pressing or. Hold the button down for fast increase/decrease. 5 Exit by pressing. It is also possible to change the end date to day 0 to delete a holiday period Weekly program for external units This weekly program can be used to control an external unit (such as lighting). The controller is set for night operation on all days of the week when it is delivered. See chapter 7 for a more detailed description of time schedules. Procedure for changing the weekly program: MO P 61 K Select parameter number P 61 by pressing or. The parameter number is increased and decreased by pressing. Press and at the same time to get to P 15 P When the parameter number has been selected, the 24-hour clock will be displayed showing MO for Monday. or 3 Scroll in the 24-hour time bar by pressing or until you get to the segment to be changed. The segment will flash. 4 Change the half-hour segments by pressing. A filled-in segment will result in daytime operation. When a segment has been changed, the next segment will start to flash. 5 Scroll on to TU for Tuesday by pressing. 6 Change the half-hour segments for Tuesday by pressing. 7 Repeat steps 5 and 6 for each day of the week. 8 Exit by pressing or. 4:4(6), (GB) , TAC AB

19 Day-to-day Usage 4.6 Reading alarms When an alarm has been triggered, the! symbol in the display window will flash. The display window will also specify what has triggered the alarm. Procedure for reading off alarms: P 82 1! K Select parameter number (P No.) by pressing or as shown in the list below. The parameter number is increased and decreased by pressing or. 2 Press and at the same time to get to P 15 P Hold down the button for fast increase/decrease. 4 Read the value. 1=ALARM, 0=NO ALARM The alarm is reset automatically when the reason for it no longer exists. Temperature P No. Circulation pump P 82 Supply temperature P Setting the operating mode The controller usually operates in a timed manner; that is to say, a weekly program and yearly program determine whether the supply temperature or room temperature should be controlled to a daytime or night setpoint. The controller can also be set to other operating modes. See chapter 7 for a more detailed description of the operating modes. Procedure for setting an operating mode: TU P 00 12:35 K Select parameter number P 00 by pressing or. The parameter number is increased and decreased by pressing. 2 Change the operating mode by pressing or. 3 Confirm by pressing. or Operating mode Symbol Heating off Fixed night setback Timed operation Fixed daytime operation Manual control TAC AB, , 4:5(6)

20 Day-to-day Usage 4.8 Setting the clock To display the current time on the clock, select parameter P 00 (usually displayed). The clock must be set after a power cut lasting more than 48 hours. See chapter 7 for a more detailed description of the clock. Procedure for setting the time: K1 P 15 0: Select parameter number P 15 by pressing or. The parameter number is increased and decreased by pressing or. Press and at the same time to get to P 15 P Change the clock by pressing or. Hold down the button for fast increase/decrease. 3 Exit by pressing. Procedure for setting the date: K1 P Select parameter number P 16 by pressing or. The parameter number is increased and decreased by pressing or. Press and at the same time to get to P 15 P Change the date (month.day) by pressing or. Hold down the button for fast increase/decrease. 3 Exit by pressing K1 P Procedure for setting the year: 1 Select parameter number P 17 by pressing or. The parameter number is increased and decreased by pressing. Press and at the same time to get to P 15 P Change the year by pressing or. 3 Exit by pressing. Days of the week are calculated automatically by the controller and do not, therefore, need to be set. or 4:6(6), (GB) , TAC AB

21 Installation 5 Installation 5.1 Assembly Controller Position the controller so that it is easy to read off and set values and so that the cover can be opened. The permissible ambient temperature range and humidity range must not be exceeded (see Technical data, chapter 8). The controller is enclosed in a plastic box comprising four parts: Transparent cover Electronic part Backplate with terminal block Metal Brace The backplate must be removed from the electronic part in order to gain access to the terminal blocks. There is a modular jack on the electronic part for connecting the information tool Inta2000.! WARNING! Check that the terminal blocks are not connected to the mains before removing the backplate. TAC AB, (GB), 5:1(10)

22 Installation Procedure for removing the backplate: 1. Remove the metal brace by unscrewing the fastening device. 2. Press in the two round buttons on the sides of the controller. 3. Hold the buttons in while carefully pulling the electronic part out of the back. Fastening device The controller can be mounted in three different ways: On a norm rail EN (TS 35 mm) In a panel, with or without a backplate Directly on a wall Procedure for mounting controller on a norm rail: 1. Place the backplate of the controller with the metal brace on the upper side of the rail (arrow 1). 2. Turn it downwards until it snaps onto the rail (arrow 2). 3. Press on the electronic part. Secure the controller into the metal brace with the fastening device for panel mounting. 4. To remove, place a screwdriver in the lock on the bottom of the controller and pull down. It is then possible to lift the controller diagonally upwards and off the rail. 5:2(10), (GB) , TAC AB

23 Installation Procedure for mounting controller in a panel: 1. Make an opening in the panel as shown in the adjacent scale drawing. The max. panel thickness is 5 mm , Remove the backplate from the electronic part (see above). Remove the terminal blocks from the backplate. 3. Place the controller in the panel and lock it in position by tightening the two locking screws. Seal the holes using the two gaskets. It is not necessary to install the metal brace when mounting panel. 4. Attach the terminal blocks to the pin on the back of the controller. Note that the terminal blocks are coded, so they cannot be interchanged. It is also possible to use the backplate when fitting the controller in a panel. TAC AB, (GB), 5:3(10)

24 Installation Procedure for mounting controller on a wall: 1. Drill holes for the three screws as shown in the scale drawing below Remove the backplate from the electronic part (see above). 3. Mount the backplate and the metal brace. 4. Connect the wires. 5. Push the electronic part onto the backplate and secure the controller in the metal brace with the fastening device max. 5 Dimensions in mm. 5:4(10), (GB) , TAC AB

25 Installation Outdoor temperature sensor, EGU Supply temperature sensor, EGWS, EGA Room temperature sensor, EGRL Return temperature sensor, EGWS, EGA Actuators M5, M15, M42, M44, M500, M750 Mount the sensor to an exterior wall facing north or north-west. Place it approximately 3 m above ground with the cable entry facing down. If several TAC 2000 are to be used in the same building, it may be sufficient to mount only one outdoor temperature sensor. A controller which has no outdoor temperature sensor of its own can then receive outdoor sensor signals from the controller which has one. The immersion sensor EGWS should be mounted in the supply pipe m after the heat exchanger or the shunt valve. If a strapped-on sensor EGA is used, this should be mounted onto an uninsulated part of the supply pipe. Clean the pipe thoroughly so that the copper sensor plate makes good contact. EGA should not be used on pipes where Ø > 50 mm (2"). The sections of a building which are most affected by changes in climate should be those in which there is most possibility to influence the supply temperature. It is also important to ensure that the sensor is not affected by irrelevant factors. The following should therefore be considered when fitting: Place the sensor in a north-facing apartment which has more than one exterior wall (a corner apartment). Install the sensor in the most representative room. Place the sensor on an interior wall made of a light building material. Avoid stone or concrete. The wall must not be heated by an underlying heater pipe. The room should be of sufficient size for the temperature not to be affected by heat from people or machines. The radiators in the room should not have thermostat valves. If they do, set them to their maximum values. Position the sensor so that air can flow freely around it. Place the reference sensor no more than 10 m from the nearest radiator, but not directly above it. This is particularly important in rooms which do not have mechanical ventilation. The immersion sensor EGWS should be mounted in the return pipe. If a strapped-on sensor EGA is used, this should be mounted to an uninsulated part of the pipe. Clean the pipe thoroughly so that the copper sensor plate makes good contact. Assembly instructions are supplied with the actuators and assembly kits. TAC AB, (GB), 5:5(10)

26 Installation 5.2 Connection All equipment which is connected to the controller must comply with the following standards: EN (or other applicable safety standard) for air handlers which provide ELV-type power supply (normally 24 V AC) to the controller and other connected equipment. EN or IEC 950 (or other applicable safety standard) for computers, modems and other equipment supplied by 230 V mains. If equipment using 230 V mains is connected to a relay output terminal of the controller, low-voltage equipment connected to other relay terminals of the controller must then have at least basic insulation to all touchable parts. There should be a switch in order to break the power to the controller. It does not have to be a separate switch for the controller, instead it can also cut the supply voltage to the installation. The function of the switch should be marked clearly.! WARNING! All power supply cables should be installed by authorised electricians. Connect the wires to the controller as shown in the circuit diagrams. 5:6(10), (GB) , TAC AB

27 Installation The outdoor temperature signal (Y2) is connected to the input of the outdoor temperature sensor (B2) in the controllers (TAC 2000) which have no outdoor sensor of their own. If the SPC signal is connected from equipment which has a different transformer, the G0s from each transformer must be connected to one another. The controller has 25 cable entries in the back. Ensure that signal cables and mains cables are pulled through separate cable entries in the back and are kept well apart. Tie up the cables together in a bundle quite close to the terminal blocks in order to limit movability. The rail with three screws in the middle of the back is insulated. It can be used as measurement neutral. A connection must then be made between the rail and measurement neutral (M) in the terminal block. TAC AB, (GB), 5:7(10)

28 Installation Cable lengths The following applies when the 24 V transformer is placed by the TAC 2112: The cables to G, G0 and other terminal blocks on TAC 24 V actuators must not exceed 50 m in length, and shall have a minimum crosssectional area of 0,8 mm 2. If the cables exceed 50 m in length, the minimum cross-sectional area is 1,5 mm 2. The same requirements apply for cables connected to KC3, K5 and K6. Cables connected to the terminal blocks KC1, K1, K2, KC2, K3, and K4, must not exceed 100 m in length, and shall have a minimum cross-sectional area of 1,5 mm 2. Cables leading to the controller should be fixed by stapling or as such. Cables connected to terminal block types B, U, and X must not exceed 200 m, and shall have a minimum cross-sectional area of 0,5 mm 2. Terminal blocks The location of the terminal blocks in the back of the controller can be seen in the figure below. L 16 Y1 15 Y KC3 12 K5 11 K G 8 G0 7 6 KC1 5 K1 4 K2 3 KC2 2 K3 1 K4 Output, outdoor temp. signal Common to K5 and K6 Output, open heating valve Output, close heating valve 24 V AC, phase 24 V AC, zero Safety ground Common to K1 and K2 Output, pump control Output, morning heating Common to K3 and K4 Output, buzzer alarm Output, weekly program 2 Measurement neutral Measurement neutral Input, SPC signal Input, pump alarm Measurement neutral Supply temperature Measurement neutral Outdoor temperature Reference temperature Return temperature, heating Measurement neutral Input, extended daytime op. Input, forced night setback Measurement neutral M M U1 U2 U3 M B1 M B2 B3 B4 M U4 X1 X2 M R Terminal blocks in the back of the controller 5:8(10), (GB) , TAC AB

29 Installation 5.3 Starting up Before the power is switched on The following should be carried out before switching on the power: 1. Check that sensors and actuators are connected correctly. 2. Set the changeover switch to configuration. It is possible to gain access to the changeover switch by pulling out the quick reference and removing the plastic disk in front of it. 3 Switch on the power to the controller. 4 Set the clock (see chapter 4). The controller should now control using pre-set parameters. off on off on 1 Outdoor sensor connected Outdoor sensor from another TAC No reference sensor Reference sensor connected Normal operation Resetting controller Testing inputs and outputs To test inputs and outputs, you need to read off and set parameters using the operator panel. Skip any tests which are not relevant to your installation. Procedure for testing inputs and outputs: 1. Check that all the temperatures are reasonable. Follow the instructions in chapter Ensure that the controller is in the timed operation operating mode. There is a description of how to set the operating mode in chapter 4. 3 Close input X2 (extended daytime operation) to measurement neutral (M) and check that the clock and the flashing sun appear in the display window. TAC AB, (GB), 5:9(10)

30 Installation 4. Close input X1 (forced night setback) to measurement neutral (M) and check that the clock and the flashing moon appear in the display window. 5. Close input U3 (pump alarm) to measurement neutral (M) and check that the alarm symbol! appears in the display window. 6. Set P 81 (SPC effect at +10 V) to 10. Vary the SPC signal at input U2 and check that P 80 (Current SPC effect) changes. 7. Set the operating mode of the controller to manual control. There is a description of how to set the operating mode in chapter Check that all outputs are operational. Follow the instructions in chapter 7. Commissioning If the above tests have given approved results, the controller is ready to be commissioned. A commissioning protocol is enclosed to assist you. You can also use the commissioning protocol in Appendix A. If the controller is not working as it should, read Chapter 6, Troubleshooting for advice on how to remedy this. 5:10(10), (GB) , TAC AB

31 Troubleshooting 6 Troubleshooting The TAC 2112 is usually a very reliable controller. If problems occur in spite of this, you can use the troubleshooting advice given below. If you require further assistance, please contact your nearest TAC service point. Problem Check that... The display window is blank the controller has power Room temperature too low the heat supply (district heating or boiler) is at the correct temperature the shunt valve is not stuck or seizes the actuator is moving as it should the circulation pump is running the operating mode is set to timed operation or fixed daytime operation (see chapter 7) night setback is not switched on the holiday program is not switched on the temperatures are reasonable the room temperature or supply temperature are set correctly Room temperature too high the shunt valve is not stuck or seizes the actuator moves as it should the temperatures are reasonable TAC AB, (GB), 6:1(2)

32 Troubleshooting Problem Check (that)... The calculated setpoint does not seem to be correct the effect from the remote heating control (SPC, P 80) is reasonable The pump is not running if the pump has stopped due to a high outdoor temperature or a low supply temperature (see chapter 7) The heating is not affected by the remote control signal (SPC) the parameter SPC effect at +10 V (P 81) is set correctly (see chapter 7) No night setback occurs the controller is in timed operation or fixed night setback mode (see chapter 7) the weekly program is set correctly (see chapter 7) the parameters for night setback are set correctly (see chapter 4). If the outdoor temperature is less than the limit for 0% night setback, night setback will not occur. 6:2(2), (GB) , TAC AB

33 Functional Description 7 Functional Description 7.1 Introduction This chapter contains a description of all the functions in the controller. At the end of each section is a list of parameters. How to read off and set these parameters is described in Chapter 3, Using the operator s panel. 7.2 Controller operating modes The controller usually operates in a timed manner, i.e. a weekly program and yearly program determine whether the supply temperature or room temperature should be controlled to a daytime or night setpoint. The controller can also be set to other operating modes by changing the parameter P 00. Timed operation When the controller is set to the timed operation operating mode, the following takes place: The symbol on the left is displayed in the display window. The supply temperature or the room temperature is controlled to the setpoint for daytime or night operation as a function of the weekly program. Holiday period When the controller is in the timed operation operating mode and a holiday period occurs, the following takes place: The symbols on the left are displayed in the display window. The supply temperature or the room temperature is reduced to the setpoint for night setback, independent of the outdoor temperature; that is to say, not the setpoint for variable night setback. TAC AB, (GB), 7:1(22)

34 Functional Description Forced night setback When the controller is in the timed operation operating mode and the input X2 is connected to M (measurement neutral), the following takes place: The symbols on the left are displayed in the display window (the moon flashes). The supply temperature or the room temperature is reduced to the setpoint for night setback. Extended daytime operation When the controller is in the timed operation operating mode and input X1 is connected to M (measurement neutral), the following takes place: The symbols on the left are displayed in the display window (the sun flashes). The supply temperature or room temperature is controlled to the setpoint for daytime operation. Fixed night setback When the controller is in the fixed night setback operating mode, the following takes place: The symbol on the left is displayed in the display window. The supply temperature or room temperature is reduced to the setpoint for night setback. Fixed daytime operation When the controller is in the fixed daytime operation operating mode, the following takes place: The symbol on the left is displayed in the display window. The supply temperature or room temperature is controlled to the setpoint for daytime operation. Heating off (standby) When the controller is in the heating off operating mode, the following takes place: The symbol on the left is displayed in the display window. The setpoint of the supply controller is set to the lowest permissible supply temperature (P 22). The circulation pump stops irrespective of whether pump stop has been selected or not. However, frost protection and pump exercise remain operational. 7:2 (22), (GB) , TAC AB

35 Functional Description Manual control Changing the operating mode Priorities When the controller is in the manual control operating mode, the following takes place: The symbol on the left is displayed in the display window. All relay outputs except for Open heating valve and Close heating valve are activated (the contacts are closed). The analogue outputs remain at the same levels. The outputs can be controlled manually from the operator s panel. The operating mode of the controller can be changed by means of the following functions: The operator s panel, by changing parameter P 00. The input for forced night setback (X2). The input for extended daytime operation (X1). The holiday periods in the yearly program. The operating mode can be changed only by a function which has the same or a higher priority than the function which is the reason for the current operating mode. The priorities of the functions are as follows (1 is the highest priority): 1 Operating modes chosen by use of the operator s panel 2 Input for extended daytime operation 3 Yearly program under timed operation 4 Input for forced night setback 5 Weekly program under timed operation For example: The yearly program cannot affect control if the input for extended daytime operation is on. TAC AB, (GB), 7:3(22)

36 Functional Description 7.3 Heat control Functional diagram The TAC 2112 can control heat with or without a reference sensor. The control function both with and without a reference sensor is described in the illustrations below. SPC Time program Outdoor temperature Parallel shift Damping Reset curve Limit. SP MV Supply regulator Actuator, heating Reset curve SP MV Return temp. limit. Pump control Pump Return temperature Minimum supply temperature Supply temperature Control function with no reference sensor installed SPC Setpoint for room temperature Reference temperature SP MV Room regulator Time program SP MV Automatic curve adjustment Outdoor temperature Damping Reset curve Limit. SP MV Supply regulator Actuator, heating Reset curve SP MV Return temp. limit. Pump control Pump Return temperature Minimum supply temperature Supply temperature Control function with reference sensor installed 7:4 (22), (GB) , TAC AB

37 Functional Description Damped outdoor temperature The object of controlling the supply temperature is to maintain the correct room temperature irrespective of the outdoor temperature. The heat storage capacity of the building shell means that a change in the outdoor temperature affects the room temperature only after a certain time. Control takes place according to a damped outdoor temperature in order to utilise effectively the heat storage in the building shell. The controller calculates the value of the damped outdoor temperature every 10 minutes. Temperature Actual Damping level= 6 hours C outdoor 16 temperature Damped 14 outdoor 12 temperature :00 12:00 00:00 12:00 00:00 Parameters Damped outdoor temperature This function minimises the utilisation of energy by preventing unnecessary heat demands during the usually cool evening hours before a night setback. The damping level is adjustable so that the controller is able to suit all types of building. P No. Parameter Min. Max. Step Default Comments P 01 Outdoor temperature 30 C 40 C 0,3 C - Step=0,1 at 2 40 C P 02 Damped outdoor temperature 30 C 40 C 0,1 C - P 79 Damping level, outdoor temp. 0 h 20 h 1 h 4 h 0=no damping. h=hours TAC AB, (GB), 7:5(22)

38 Functional Description Reset curve for outdoor compensation The correct amount of heating is supplied to the building throughout the year by allowing the supply temperature to be changed as a function of the damped outdoor temperature. This function is described by the reset curve. The reset curve is made of three adjustable curve points. The outer points are firmly defined by the outdoor temperature, while the break point in the middle of the curve is adjustable. P 23 P y y y2 10 P 19 P 20 P 18 Parallel shift ± C P 21 P x0 x1 x2 Damped Parameters Reset curve for outdoor compensation of the supply temperature The curve has a maximum and a minimum limit. The curve can also be parallel-shifted up and down (does not apply if a reference sensor is used). P No. Parameter Min. Max. Step Default Comments P 05 Curve shift 40 C 40 C 0,5 C 0 C Without reference sensor only P 06 Night setback 40 C 40 C 0,5 C 10 C Without reference sensor only P 18 Curve point x1 9 C 19 C 1 C 5 C P 19 Curve point y0 P C 1 C 60 C P 20 Curve point y1 P 21 P 19 1 C 45 C P 21 Curve point y2 5 C P 20 1 C 18 C P 22 Min. supply temp. 0 C P 23 0,5 C 10 C P 23 Max. supply temp. P C 0,5 C 80 C 7:6 (22), (GB) , TAC AB

39 Functional Description Automatic adjustment of the reset curve Curve adjustment controller Maximum curve adjustment In systems with reference sensors, the controller can adjust the reset curve automatically. The temperature at the reference sensor is used to continually carry out small corrections (±1 C) to the three points (y0, y1 and y2) of the reset curves. After about a week, the reset curve will have been adapted to suit the appropriate building. The automatic curve adjustment is carried out by an I controller (integrated controller), actual values and setpoints for the room being used as input parameters. The following data apply for the controller: I time: minutes Dead zone: 0,5 C The I time corresponds to the time taken, in minutes, for the controller to adjust the reset curve, at a constant control deviation of around 1 C in the room. Example: If the deviation is 2 C, the I time becomes 2 1 min., and so forth. Adjustment of the reset curve has an adjustable limitation known as Maximum curve adjustment. When the equipment is supplied, this is set to ±5 C from the nominal curve. The nominal curve is the curve from which the limitation is calculated. Adjusted curve Nominal curve Maximum curve adjustment = permissible range for automatic curve adjustment Automatic adjustment of the reset curve The nominal curve is determined by the fact that it takes on the values of the adjusted curve. This takes place in the following cases: When the controller is reset (all parameters resume their defaults). Any curve point is adjusted manually. The Maximum curve adjustment parameter is changed. TAC AB, (GB), 7:7(22)

40 Functional Description Criteria for automatic curve adjustment Parameters The following criteria must be met for the automatic curve adjustment to work: A reference sensor is installed. Automatic curve adjustment is on (P 27). The controller is working under timed operation. Daytime operation is on. The pump is working, i.e. there is a heating requirement. The return temperature limitation is not active. P No. Parameter Min. Max. Step Default Comments P 27 Automatic curve adjustment 0 (off) 1 (on) 1 1 (on) With reference sensor only P 28 I time for curve adj. controller 1 min. 720 min. 1 min. 180 min. With reference sensor only P 29 Max curve adjustment 0 C 40 C 1 C 5 C With reference sensor only Supply controller Controller The supply temperature is controlled by a PI controller (proportional and integrating controller) of the increase/decrease type. The setpoint for this controller is calculated on the basis of the following parameters: Operating mode The reset curve for outdoor temperature compensation Room temperature effect, if a reference sensor is fitted Parallel shifting of the reset curve, if no reference sensor is fitted Return temperature limitation Remote setpoint control, SPC adjustment Pump control Night setback Supplement during morning boost 7:8 (22), (GB) , TAC AB

41 Functional Description The following data apply for the supply controller: P band: C I time: 2 minutes Dead zone: 1,0 C The supply setpoint is set to Min. supply temperature (P 22) when the pump is stopped in order to ensure that the valve moves into the closed position. Ramp limitation Parameters To prevent increases in the supply temperature which are much too rapid, the supply temperature can be ramp-limited. This means that the setpoint is not allowed to increase as rapidly as possible, but instead it is limited to an adjustable increase rate. This limitation applies only when the setpoint increases. The setpoint can be reduced without limitation. P No. Parameter Min. Max. Step Default Comments P 03 Supply temperature 0 C 120 C 0,3 C - Step=0,1 at 2 55 C P 04 Calc. setpoint, supply temp. 0 C 120 C 0,1 C - P 24 P band, supply controller 10 C 200 C 0,5 C 100 C P 25 Run time for actuator 0 s 300 s 5 s 300 s P 26 Max. increase rate, supply SP 1 C/min 50 C/m. 0,1 C/m. 2 C/min Ramp limitation Room controller Controller A reference sensor can be connected in order to control the room temperature more precisely. The reference sensor should measure the room temperature in the most representative room in the building (see also chapter 5). The signal from the reference sensor represents the actual value to the room controller. The output signal from the controller affects the setpoint for the supply temperature. The controller may have various setpoints and control effects for day and night. The room controller has no effect if no reference sensor is fitted. The room temperature is controlled by a P controller (proportional controller). The setpoint for the controller is calculated on the basis of the following parameters: Commissioned setpoint for day or night Remote setpoint control, SPC adjustment The following data apply to the room controller: Control effect: Dead zone: 0 5 C TAC AB, (GB), 7:9(22)

42 Functional Description Parameters P No. Parameter Min. Max. Step Default Comments P 07 Room temperature 0 C 45 C 0,1 C - With reference sensor only P 08 Calculated SP, room temp. 35 C 70 C 0,1 C - With reference sensor only P 09 Setpoint room, day 5 C 30 C 0,5 C 21 C With reference sensor only P 10 Setpoint room, night 5 C 30 C 0,5 C 18 C With reference sensor only P 30 Control effect room, day 0,5 20 0,5 2 With reference sensor only P 31 Control effect room, night 0,5 50 0,5 10 With reference sensor only P 32 Dead zone, room 0 C 5 C 0,1 C 0,3 C With reference sensor only Return temperature limitation The return water temperature can be limited by the controller. The magnitude of this limitation is determined by a separate reset curve with the max. return temperature as a function of the damped outdoor temperature. The reset curve is based on two curve points as depicted below. y0 y P 46 P 45 P 48 P x0 x1 Damped Reset curve for return temperature limitation Limitation controller The limitation of the return temperature is controlled by a controller using the following data: P band: C I time: 3 minutes Dead zone: 1 C The output signal from the controller has an effect on the setpoint for the supply temperature. The limitation controller has no effect in the operating modes heating off and manual control. 7:10 (22), (GB) , TAC AB

43 Functional Description Parameters P No. Parameter Min. Max. Step Default Comments P 13 Return temperature, heating 0 C 120 C 0,3 C - Step=0,1 at 2 55 C P 43 Return limitation on/off (off) 1=heating, 2=heat.+dom.h.w. P 44 Return limit., heating, P band 10 C 200 C 0,5 C 20 C Not if P 43=0 P 45 Curve point x0-30 C P 48 1 C -10 C Not if P 43=0 P 46 Curve point y0 P C 1 C 70 C Not if P 43=0 P 47 Curve point x1 P C 1 C 10 C Not if P 43=0 P 48 Curve point y1 10 C P 47 1 C 40 C Not if P 43= Remote heating control (SPC) The heating can be remote-controlled by connecting an external 2 10 V DC control voltage to the SPC input. In systems with a reference sensor, the setpoint for the room temperature is affected, and in systems without a reference sensor, the setpoint for the supply temperature is affected. The effect of the control voltage on the setpoint is shown in the illustration below. Effect on setpoint ( C) +40 P SPC signal (V) Parameters The effect of the SPC signal on the setpoint The effect of the control voltage on the setpoint can be adjusted by means of the SPC effect at +10 V parameter (P 81). When the equipment is delivered, the SPC signal has no effect due to the fact that the SPC effect at +10 V parameter is set to zero. P No. Parameter Min. Max. Step Default Comments P 80 Current SPC effect (-1) P 81 P 81 0,1 C - P 81 SPC effect at +10 V 0 C 40 C 1 C 0 C TAC AB, (GB), 7:11(22)

44 Functional Description Pump control The pump control acts to utilise the heat accumulated in the building as efficiently as possible by allowing the circulation pump to operate only when there is a specific heating requirement. Pump stop The circulation pump is stopped and the setpoint for the supply temperature is set to Min. supply temperature in the following cases: The outdoor temperature exceeds the Outdoor temperature for pump stop limit. The calculated setpoint for the supply temperature is less than the Supply temperature for pump stop limit. The pump stop has a fixed switch-off delay of 5 minutes, i.e. the pump runs for at least 5 minutes every time (does not apply for pump exercise see below). Restarting the pump The circulation pump is restarted with a fixed hysteresis of 1.5 C. The pump can be restarted only after a set time, the Min. pump off time. However, the pump can be started immediately in the event of frost protection if so required (see below) or in operating modes other than timed operation. Pump exercise The pump starts at 12:00 and runs for one minute every Monday in order to prevent pump seizure, for example during the summer months. Frost protection Parameters The pump always starts and the valve is controlled whenever the outdoor temperature is less than +3 C in order to prevent freezing in the heating installation. P No. Parameter Min. Max. Step Default Comments P 72 Pump stop on/off 0 (off) 1 (on) 1 1 (on) 0=off, 1=on P 73 Outdoor temp. for pump stop 3 C 50 C 1 C 20 C P 74 Supply temp., pump stop 0 C 120 C 1 C 20 C P 75 Exercise on/off 0 (off) 1 (on) 1 1 (on) 0=off, 1=on P 76 Min. pump off time 0 h 12 h 0,5 h 2 h h=hours 7:12 (22), (GB) , TAC AB

User Instructions For TopTronic RS-10

User Instructions For TopTronic RS-10 User Instructions For TopTronic RS-0 409ENG-Dec0 Hoval Ltd Northgate Newark Nottinghamshire NG4 JN Phone 066 677 Fax 066 675 Index 409ENG-Dec0 Introduction Introduction... Controls... Display... User instructions

More information

LK Wireless Room Control Cq

LK Wireless Room Control Cq LK Wireless Room Control Cq Description LK Wireless Room Control Cq consists of a LK Room Thermostat Cq-n (transmitter) and a LK Receiver Unit Cq 8 (8 channel receiver unit). The range also includes a

More information

Titan Products RDU-4/TS & RDU-4/5B Time Scheduling Room Display Units

Titan Products RDU-4/TS & RDU-4/5B Time Scheduling Room Display Units Titan Products RDU-4/TS & RDU-4/5B Time Scheduling Room Display Units 1 Time Scheduling RDU-4/TS - Description of Control Operation The temperature control and time scheduling for the building space is

More information

Self-learning Room Temperature Controller Receiver

Self-learning Room Temperature Controller Receiver 2 265 REV23RF REV-R.02/1 REV23RF/SE Self-learning Room emperature Controller Receiver Consisting of controller (with integrated radio transmitter) and receiver (switching unit with relay outputs) REV23RF

More information

AURATON 2020 AURATON 2020 TX RX Plus

AURATON 2020 AURATON 2020 TX RX Plus 0 I 31 EN AURATON 2020, AURATON 2020 TX RX Plus AURATON 2020 AURATON 2020 AURATON 2020 TX RX Plus Preliminary notes The manual includes the information on AURATON 2020 and AURATON 2020 TX RX Plus controllers.

More information

Installation Guide. ECL Comfort 310, application A Table of Contents

Installation Guide. ECL Comfort 310, application A Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 6 2.1 Before you start.....................................................

More information

PRODUCT CATALOGUE TEMPERATURE CONTROL Grässlin products for individual control of temperature

PRODUCT CATALOGUE TEMPERATURE CONTROL Grässlin products for individual control of temperature PRODUCT CATALOGUE TEMPERATURE CONTROL Grässlin products for individual control of temperature Temperature control: Feel good at any time of year Room thermostats Heating time switches Excellent products

More information

TC 204 Heating Controller

TC 204 Heating Controller TC 204 Heating Controller ver. 1.32-01 The TC204 is a multi-purpose heating controller with built-in programs for different types of heating systems. General Data Power requirement 24 volts ac, 2 va Inputs

More information

4.3 Touchscreen User Manual

4.3 Touchscreen User Manual 4.3 Touchscreen User Manual Contents 1. Temperature 1. How do I adjust the temperature at console 2. How do I use the buttons on the sensor (Digital Sensor Only) 3. Sensor Symbols Explained (Digital Sensor

More information

Use of the application program. Contents. instabus EIB Application program description. September S2 Room temperature controller

Use of the application program. Contents. instabus EIB Application program description. September S2 Room temperature controller Use of the application program Product family: Product type: Manufacturer: Heating, Air conditioning, Ventilation Thermostat Siemens Name: Room temperature controller IKE 250 DELTA millennium Order no.:

More information

SERVICE-MANUAL ROOM TEMPERATURE CONTROLLER NEA 230V / 24V. Construction Automotive Industry

SERVICE-MANUAL ROOM TEMPERATURE CONTROLLER NEA 230V / 24V. Construction Automotive Industry ROOM TEMPERATURE CONTROLLER NEA 230V / 24V Construction Automotive Industry ROOM TEMPERATURE CONTROLLER NEA 230V / 24V TABLE OF CONTENTS 1....... Information and safety guidelines......................................................

More information

Wireless Room Thermostat Installation and Operation Y6630D1007

Wireless Room Thermostat Installation and Operation Y6630D1007 Wireless Room Thermostat Installation and Operation Y6630D1007 General safety instructions Contents 1. General safety instructions... 3 1.1. Commissioning the relay module HC60NG... 3 2. Overview... 4

More information

Communicative heating controller

Communicative heating controller UC100 Communicative heating controller Summary UC100 is a communicative room heating controller with one PWM output for control of a radiator or electrical heater. It can work autonomously, or in connection

More information

Please enter the identity code of your device here!

Please enter the identity code of your device here! Operating Instructions DULCOMETER D1C Part 2: Adjustment and Operation, Measured Variable Conductive Conductivity ProMinent D1C2-Leit.-001-GB Conductivity 100 µs/cm DULCOMETER STOP START Conductivity 100

More information

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application STR-LCF Electronic Fan Coil Thermostat (Flush mounting) Datasheet Subject to technical alteration Issue date: 28.2.217 Application The fan coil room thermostat has been designed for individual control

More information

Fan Coil Actuator FCA 2

Fan Coil Actuator FCA 2 Fan Coil Actuator FCA 2 FCA 2 4920210 Updated: Feb-16 (subject to changes) Page 1 of 89 Contents 1 Function description... 4 1.1 Operation and display... 5 1.2 Advantages of the FCA 2... 6 1.2.1 Special

More information

theben Fan Coil Actuator FCA 1 Fan Coil Actuator FCA 1 FCA Version: Jan-08 (Subject to change) Page 1 of 77

theben Fan Coil Actuator FCA 1 Fan Coil Actuator FCA 1 FCA Version: Jan-08 (Subject to change) Page 1 of 77 Fan Coil Actuator FCA 1 FCA 1 492 0 200 Version: Jan-08 (Subject to change) Page 1 of 77 Contents 1 Functional characteristics...4 1.1 Operation and display...5 1.2 Advantages of the FCA 1...5 1.2.1 Special

More information

Model: 5301P INSTALLATION AND OPERATION INSTRUCTIONS

Model: 5301P INSTALLATION AND OPERATION INSTRUCTIONS Model: 5301P INSTALLATION AND OPERATION INSTRUCTIONS INTRODUCTION IF YOU CANNOT READ OR UNDERSTAND THESE INSTALLATION INSTRUCTIONS DO NOT ATTEMPT TO INSTALL OR OPERATE This SKYTECH remote control system

More information

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description. Use of the application program Product family: Product type: Manufacturer: Heating, air conditioning, ventilation Thermostat Siemens Name: Temperature controller UP 237 DELTA i-system Order no.: 5WG1 237-2AB_1

More information

Thermostat P. Thermostats Electronic room thermostat with clock for thermal actuators

Thermostat P. Thermostats Electronic room thermostat with clock for thermal actuators Thermostat P Thermostats Electronic room thermostat with clock for thermal actuators IMI HEIMEIER / Thermostats & Actuators / Thermostat P Thermostat P The Thermostat P room temperature controller is used

More information

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description. Use of the application program Product family: Product type: Manufacturer: Heating, air conditioning, ventilation Thermostat Siemens Name: Temperature controller UP 237 DELTA i-system Order no.: 5WG1 237-2AB_1

More information

SA-027HQ 365-Day Annual Timer

SA-027HQ 365-Day Annual Timer SA-027HQ 365-Day Annual Timer Manual Two N.O. or N.C. Form C relays, 10A@14VDC Each relay can be programmed for 50 events, for a total of 100 individual programmable events 10 Programmable holidays The

More information

E N SHT-1 SHT-1/2 SHT-3 SHT-3/2

E N SHT-1 SHT-1/2 SHT-3 SHT-3/2 Digital time switch E N SHT-1 SHT-1/2 SHT-3 SHT-3/2 Content Symbol, Connection... 3 Warning... Characteristics... 5 Technical parameters... 6 Versions of time switches, Load... 7 Description... 8-9 Control...

More information

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems 3 041 RCU10 RCU10.1 Room Temperature Controllers for heating and cooling systems RCU10... Choice of two-position or modulating PI control ON / OFF or PWM outputs for heating and cooling Operating modes:

More information

Control solutions Biofloor

Control solutions Biofloor MR24 Central radio controller 24V Connect COMAP offers the Connect control system as part of its underfloor heating and cooling solution. Composed of a central radio control module (MR24), wireless digital

More information

RAM 712 KNX room thermostat for surface-mounted and flush-mounted installation

RAM 712 KNX room thermostat for surface-mounted and flush-mounted installation RAM 712 KNX room thermostat for surface-mounted and flush-mounted installation RAM 712 712 9 200 Version: Dec-10 (subject to change) Page 1 of 65 Contents 1 Functional characteristics... 4 1.1 Operation...

More information

Multi-Channel In-Out Thermometer with Cable Free Sensor and RF Clock

Multi-Channel In-Out Thermometer with Cable Free Sensor and RF Clock Multi-Channel In-Out Thermometer with Cable Free Sensor and RF Clock MAIN FEATURES: MAIN UNIT GB MODEL: RMR182 USER'S MANUAL INTRODUCTION Congratulations on your purchase of the RMR182 Multi- Channel In-Out

More information

Application Programs Descriptions

Application Programs Descriptions Devices Employing the Program Product family: Product type: Manufacturer: Heating Regulator Siemens Name: Temperature Controller UP 250 DELTA studio, titanium white Order-no.: 5WG1 250-2AB12 Name: Temperature

More information

TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller. Mounting and Operating Instructions EB 5578 EN

TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller. Mounting and Operating Instructions EB 5578 EN TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller Mounting and Operating Instructions EB 5578 EN Firmware version 2.30 Edition November 2017 Definition of signal words DANGER!

More information

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems 3 048 RCU15 Room Temperature Controllers for heating and cooling systems RCU15 Choice of two-position or modulating PI control ON / OFF or PWM outputs for heating and cooling Control depending on room-

More information

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems 3 041 RCU10 RCU10.1 Room Temperature Controllers for heating and cooling systems RCU10... Choice of two-position or modulating PI control ON / OFF or PWM outputs for heating and cooling Operating modes:

More information

Sentido KNX Manual. Sentido KNX. Manual. basalte bvba hundelgemsesteenweg 1a 9820 merelbeke belgium

Sentido KNX Manual. Sentido KNX. Manual. basalte bvba hundelgemsesteenweg 1a 9820 merelbeke belgium basalte bvba hundelgemsesteenweg a 980 merelbeke belgium / 68 06 basalte Table of contents:. Introduction... 3. Installation... 4. 3. Identifying the parts... 5 General... 6 3. General functions... 7 3.

More information

TLC3-BCR-U Series Thermostat

TLC3-BCR-U Series Thermostat OVERVIEW TLC3-BCR-U Series Thermostat Features Low power energy consumption: < 1W per unit Relays switching for outputs each up to 300W Temperature control for 2 or 4-pipe heating or cooling systems. Optional

More information

INSTAT 868 Radio Frequency Single-Room Controls

INSTAT 868 Radio Frequency Single-Room Controls INSTAT 868 Radio Frequency Single-Room Controls Easy to operate wireless application HEATING People Performance Products Climate Controls Europe An Invensys company Radio Frequency Controls Single-room

More information

WIRELESS Energy Monitor - Smart Meter

WIRELESS Energy Monitor - Smart Meter Energy saving made simple MONITOR CONTROL SAVE WIRELESS Energy Monitor - Smart Meter Monitors your electricity use and cost in real time Instruction Manual EW4500 IMPORTANT Please retain your Instruction

More information

V22 Thermostat N515/R00( )

V22 Thermostat N515/R00( ) V22 Thermostat N515/R00(02.10.12) 2 USER GUIDE GB RF Digital programmable Thermostat 3-59 3 IMPORTANT! Before starting work the installer should carefully read this Installation & Operation Manual, and

More information

Installation Guide. ECL Comfort 310, application A Table of Contents

Installation Guide. ECL Comfort 310, application A Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 5 2.1 Before you start.....................................................

More information

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems 3 048 RCU15 Room Temperature Controllers for heating and cooling systems RCU15 Choice of two-position or modulating PI control ON / OFF or PWM outputs for heating and cooling Control depending on room-

More information

TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller. Mounting and Operating Instructions EB 5578 EN

TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller. Mounting and Operating Instructions EB 5578 EN TROVIS 5500 Automation System TROVIS 5578 Heating and District Heating Controller Mounting and Operating Instructions EB 5578 EN Firmware version 2.2x Edition May 2015 Definition of signal words DANGER!

More information

Please enter the identity code of your device here!

Please enter the identity code of your device here! Operating Instructions DULCOMETER D2C Part 2: Adjustment and Operation, Measured Variables chlorine/chlorine ProMinent D2C2-001-chlorine/chlorine-GB CI 2 /Cl 2 0.50 ppm CLE 0.20 ppm CI DULCOMETER STOP

More information

Sauter Components

Sauter Components R 44.488/ QRK 0: Heating controller Used in conjunction with temperature detectors (Ni000) and appropriate control valves for heating and domestic-hot-water control (with various configurations), mainly

More information

OPERATING INSTRUCTIONS ARE ON PAGE 5. SECTION 2 Technical Data Transmitter Unit. RVHT 2 MULTI-FIT Programmable R/F Thermostat-Pair SECTION 1

OPERATING INSTRUCTIONS ARE ON PAGE 5. SECTION 2 Technical Data Transmitter Unit. RVHT 2 MULTI-FIT Programmable R/F Thermostat-Pair SECTION 1 OPERATING INSTRUCTIONS ARE ON PAGE 5 RVHT 2 MULTI-FIT Programmable R/F Thermostat-Pair SECTION 1 This Programmable Ravenheat R/F controlled room Thermostat RVHT 2, consists of 2 items: a Mobile Transmitter

More information

Please enter the identity code of your device here!

Please enter the identity code of your device here! Operating Instructions DULCOMETER D2C Part 2: Adjustment and Operation, Measured Variables ph/chlorine dioxide ProMinent D2C2-001-pH/CIO2-GB ph/clo 2 7.20 ph 0.45 ppm DULCOMETER STOP STAR T ph/clo 2 7.20

More information

RWD44U Controller. Installation and Commissioning Guide Document No October 5, Function. Application

RWD44U Controller. Installation and Commissioning Guide Document No October 5, Function. Application RWD44U Controller Installation and Commissioning Guide Document No. 129-408 Function RWD44U controllers are intended for HVAC and Refrigeration systems including Heat Pumps. They are suitable for 1-, 2-,

More information

1 Digital input (24Vac or dry contact) Inputs

1 Digital input (24Vac or dry contact) Inputs Fan oil Thermostat Fan oil Thermostat Features: Attractive modern look with large LD and backlight Icons driven information and 1 line of text information 2 Pipes Analog, ON/OFF or Floating 4 Pipes Analog,

More information

WIRELESS 868 MHz TEMPERATURE STATION Instruction Manual

WIRELESS 868 MHz TEMPERATURE STATION Instruction Manual WIRELESS 868 MHz TEMPERATURE STATION Instruction Manual INTRODUCTION: Congratulations on purchasing this temperature station with wireless 868MHz transmission. It not only displays the indoor temperature

More information

INSTRUCTION MANUAL DT10RF OPTIMISING PROGRAMMER UK/IE OPERATING AND INSTALLATION

INSTRUCTION MANUAL DT10RF OPTIMISING PROGRAMMER UK/IE OPERATING AND INSTALLATION Hol Man Auto Day OPERATING AND INSTALLATION DIGISTAT OPTIMISER - Radio frequency controlled programmable room thermostat with domestic hot water programmer FOR GREENSTAR CDi AND GREENSTAR Si MODELS ALSO

More information

Please completely read through operating instructions! Do not discard! The warranty shall be invalidated by damage caused by operating errors!

Please completely read through operating instructions! Do not discard! The warranty shall be invalidated by damage caused by operating errors! Operating Instructions DULCOMETER D1C Part 2: Adjustment and Operation, Measured Variable Conductivity ProMinent D1C2-Leit.-001-GB Conductivity 100 µs/cm DULCOMETER STOP START Please completely read through

More information

RWD68U Controller. Installation and Commissioning Guide Document No October 1, Function. Application

RWD68U Controller. Installation and Commissioning Guide Document No October 1, Function. Application RWD68U Controller Installation and Commissioning Guide Document No. 129-411 Function Application The RWD68U is a three-input, two-output device used to control temperature, humidity, air pressure, fluid

More information

CD-Pxx-00-0 Series Duct Mount CO 2 Transmitter

CD-Pxx-00-0 Series Duct Mount CO 2 Transmitter Installation Instructions CD-Pxx-00-0 Issue Date February 4, 006 CD-Pxx-00-0 Series Duct Mount CO Transmitter Application Requirements FCC Compliance Statement This equipment has been tested and found

More information

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems 3 041 RCU10 RCU101 Room Temperature Controllers for heating and cooling systems RCU10 Choice of two-position or modulating PI control ON / OFF or PWM outputs for heating and cooling Operating modes: normal

More information

Wireless multizone receiver RDE-MZ6

Wireless multizone receiver RDE-MZ6 s 1 428 Wireless multizone receiver RDE-MZ6 for floor heating / zone heating systems Mains-powered RDE-MZ6 multizone wireless receiver (AC 230 V) DIN rail mounting 2-position control with On/Off output

More information

Mx-D15 Intelligent Valve Actuator

Mx-D15 Intelligent Valve Actuator Application Small radio controlled, battery-powered actuator for room temperature control. For thermostat valve bodies for direct mounting on commercially available radiator valves for room-specific temperature

More information

Table of Contents. Introduction...3 Specifications...6 Installation Instructions...6

Table of Contents. Introduction...3 Specifications...6 Installation Instructions...6 2 Table of Contents Introduction.............................3 Specifications...........................6 Installation Instructions......................6 Basic Programming To Set Date.............................10

More information

EQJW145. Content: 1 General. 2. Indicators and operating controls 3. Putting into service (by a technician) 4. How to operate (user)

EQJW145. Content: 1 General. 2. Indicators and operating controls 3. Putting into service (by a technician) 4. How to operate (user) SAUER equitherm Electronic heating controller 1) Valid from soft version 09 Content: General 2. Indicators and operating controls 3. Putting into service (by a technician) 4. How to operate (user) en Quick

More information

Please enter the identity code of your device here!

Please enter the identity code of your device here! Operating Instructions DULCOMETER D1C Part 2: Adjustment and Operation, Measured Variable Ozone ProMinent D1C2-03-001-GB O 3 DULCOMETER STOP START O 3 DULCOMETER STOP START Type D Type W D1C A Please enter

More information

Please enter the identity code of your device here!

Please enter the identity code of your device here! Operating Instructions DULCOMETER D1C Part 2: Adjustment and Operation, Measured Variable ph ProMinent D1C2-001 D ph 7.20 ph Temp.: 33.2 C DULCOMETER STOP START ph 7.20 ph Temp.: 33.2 C DULCOMETER STOP

More information

Wireless valve actuator for bidirectional EnOcean communication. The SAB05 combines with message server and enocean transmitter.

Wireless valve actuator for bidirectional EnOcean communication. The SAB05 combines with message server and enocean transmitter. SAB05 EasySens wireless radiator valve actuator for room temperature control Data Sheet Subject to technical alteration Issue date: 26.11.2015 Application Wireless valve actuator for bidirectional EnOcean

More information

LIGHTING CONTROL PANEL

LIGHTING CONTROL PANEL LIGHTING CONTROL PANEL Installation Guide & User Manual 925 A.E.C. D R IVE, W O O D D A LE, IL 60191 (630) 238-1516 / FA X (630) 860-2934 THIS PAGE INTENTIONALLY LEFT BLANK 2 WARRANTY STATEMENT Automated

More information

beginning with version 1.01

beginning with version 1.01 DeltaTherm HC mini beginning with version 1.01 Heating controller Manual for the specialised craftsman Mounting Connection Operation Troubleshooting Application examples *11205773* 11205773 Adjust your

More information

Aqua-Gen 3BR INSTRUCTIONS

Aqua-Gen 3BR INSTRUCTIONS Aqua-Gen 3BR INSTRUCTIONS INSTALLATION INSTRUCTIONS CONTROLLER: Find a suitable location to mount the control box* radio note. The controller must be installed out of direct weather and no closer than

More information

ELECTRONIC THERMOSTAT: T920

ELECTRONIC THERMOSTAT: T920 μnistδt ELECTRONIC THERMOSTAT: T One analog output DESCRIPTION The T series thermostats are microcomputer-based, proportional and integral (PI) devices with one analog 0 to 0 output. They can be used with

More information

Honeywell. W7620 Zone Controller Water Source Heat Pump A. GENERAL RESIDENTIAL AND BUILDING CONTROL GUIDE SPECIFICATION FOR THE ENGINEER

Honeywell. W7620 Zone Controller Water Source Heat Pump A. GENERAL RESIDENTIAL AND BUILDING CONTROL GUIDE SPECIFICATION FOR THE ENGINEER Honeywell RESIDENTIAL AND BUILDING CONTROL GUIDE SPECIFICATION FOR THE ENGINEER W7620 Zone Controller Water Source Heat Pump - -.> The W7620 Zone Controller provides customized control of HVAC zone equipment.

More information

Analogue temperature controllers

Analogue temperature controllers Analogue temperature controllers CT8A Input by J-K thermo-couple or by thermo-resistance Pt 00 (-wire) regulation modes : ON/OFF or proportional derivative selected by wiring Relay output Specifications

More information

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion

More information

Smartzone LCD TOUCHPAD USER GUIDE.

Smartzone LCD TOUCHPAD USER GUIDE. Smartzone LCD TOUCHPAD USER GUIDE www.ias.net.au TOUCHPAD USER GUIDE Touchpad and Display Layout PAGE 2 TOUCHPAD USER GUIDE Dual Line Back lit LCD Display With scrolling zone summary Change variable values

More information

Long-Range Multi-Channel In-Out Thermometer with Cable Free Sensor and RF Clock Model: RMR183 & RMR183U User Manual

Long-Range Multi-Channel In-Out Thermometer with Cable Free Sensor and RF Clock Model: RMR183 & RMR183U User Manual Long-Range Multi-Channel In-Out Thermometer with Cable Free Sensor and RF Clock Model: RMR183 & RMR183U User Manual RMR183-e Cover R2 OP 1 Long-Range Multi-Channel In-Out Thermometer with Cable Free Sensor

More information

OWNERS MANUAL FOR STERLING SERIES CONTROLLERS

OWNERS MANUAL FOR STERLING SERIES CONTROLLERS OWNERS MANUAL FOR STERLING SERIES CONTROLLERS 24950 AVENUE KEARNY, VALENCIA, CALIFORNIA 91355-2142 PHONE (661) 257-3533 FAX (661) 257-9472 TABLE OF CONTENTS Selecting the Location for the Controller...3

More information

Intelligent Compact Controller

Intelligent Compact Controller TCY-T0121 Intelligent Compact Controller Features Temperature control for 2-pipe, 4-pipe HVAC systems. Temperature range from 40 to 140 C. 1 independent PI and On/Off control loop to control temperature.

More information

NRT 105: Electronic fan-coil controller, equiflex

NRT 105: Electronic fan-coil controller, equiflex Product data sheet 4.04 R 105: Electronic fan-coil controller, equiflex How energy efficiency is improved ECO Meter for displaying the current energy consumption and digital input for the change-over between

More information

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W ADC5000 SERIES AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications 60W, 125W and 250 W Input voltage 230/115 VAC voltages 12, 24, 36 or 48 VDC Statistical MTBF >3 000

More information

KNX TH65-AP. Thermo-Hygrometer. Installation and Adjustment. Item number 70184

KNX TH65-AP. Thermo-Hygrometer. Installation and Adjustment. Item number 70184 EN KNX TH65-AP Thermo-Hygrometer Item number 70184 Installation and Adjustment 1 Content 1. Description... 3 1.1. Technical specifications... 3 2. Installation and commissioning... 4 2.1. Installation

More information

RAMSES 784 HF Set 1. Bedienungsanleitung Uhrenthermostat 1. Operating Instructions Clockthermostat 14. Mode d emploi Thermostat à horloge 26

RAMSES 784 HF Set 1. Bedienungsanleitung Uhrenthermostat 1. Operating Instructions Clockthermostat 14. Mode d emploi Thermostat à horloge 26 309 484 01 RAMSES 784 HF Set 1 784 9 407 784 9 417 Bedienungsanleitung Uhrenthermostat 1 Operating Instructions Clockthermostat 14 Mode d emploi Thermostat à horloge 26 Gebruiksaanwijzing Klokthermostaat

More information

EUROSTER 2026/2026TX

EUROSTER 2026/2026TX EUROSTER 2026/2026TX - User Manual 1 EUROSTER 2026/2026TX 1. CHARACTERISTICS 4 different programs for each day of the week (28 different ranges and temperatures altogether). Time programming with 10 minutes

More information

User Manual OFF ON IN OUT ALARM RESET AURATON RTH software ver. F0F

User Manual OFF ON IN OUT ALARM RESET AURATON RTH software ver. F0F www.auraton.pl User Manual software ver. F0F OFF ON IN OUT ALARM RESET AURATON RTH Thank you for purchasing this modern, advanced, microprocessor-based temperature regulator AURATON 2025 / AURATON 2025

More information

WIRELESS CONTROL UNIT FOR CONTROL OF ELECTRIC HEATING DEVICES (WITHIN ONE ROOM)

WIRELESS CONTROL UNIT FOR CONTROL OF ELECTRIC HEATING DEVICES (WITHIN ONE ROOM) PH-BSP WIRELESS CONTROL UNIT FOR CONTROL OF ELECTRIC HEATING DEVICES (WITHIN ONE ROOM) Wireless control unit Two-way radio communication on 433.92 MHz Comfortable solution of room heating Predictive system

More information

ELECTRONIC THERMOSTAT: T951

ELECTRONIC THERMOSTAT: T951 μnistδt ELECTRONIC THERMOSTAT: T9 One floating output One contact output DESCRIPTION The T9 series thermostats are microcomputer-based, proportional and integral (PI) devices with one floating (incremental)

More information

Operating & Maintenance Instructions 25 Injection Moulding Machine

Operating & Maintenance Instructions 25 Injection Moulding Machine Operating & Maintenance Instructions 25 Injection Moulding Machine Table of Contents 1. Health and Safety Information... 2 2. Upon Receipt... 2 3a. Temperature Controller Settings (Brainchild Controller)...

More information

CM927 WIRELESS PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET

CM927 WIRELESS PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET CM927 WIRELESS PROGRAMMABLE THERMOSTAT FEATURES CM927 can be installed without disrupting your room décor as no wiring connection is required between the room unit and the boiler Attractive, slim, ultra-modern

More information

Aqua-Gen 3PV INSTRUCTIONS

Aqua-Gen 3PV INSTRUCTIONS Aqua-Gen 3PV INSTRUCTIONS INSTALLATION INSTRUCTIONS CONTROLLER: Find a suitable location to mount the control box* radio note. The controller must be installed out of direct weather and no closer than

More information

vacon 100 flow ac drives application manual

vacon 100 flow ac drives application manual vacon 100 flow ac drives application manual PREFACE VACON 3 PREFACE Document ID: DPD01083D Date: 15.10.2014 Software version: FW0159V010 ABOUT THIS MANUAL This manual is copyright of Vacon Plc. All Rights

More information

Digital amplifier for proportional valves PEM XD

Digital amplifier for proportional valves PEM XD Digital amplifier for proportional valves PEM XD FEATURES - Amplifier for cap rail mounting according to DIN EN 50022 - Control of 2 coils in open loop, or 2 proportional valves with 1 coil in open loop

More information

Model: 3003P INSTALLATION AND OPERATING INSTRUCTIONS

Model: 3003P INSTALLATION AND OPERATING INSTRUCTIONS Model: 3003P INSTALLATION AND OPERATING INSTRUCTIONS IF YOU CANNOT READ OR UNDERSTAND THESE INSTALLATION INSTRUCTIONS DO NOT ATTEMPT TO INSTALL OR OPERATE INTRODUCTION This remote control system was developed

More information

3000W multi Pir light controller

3000W multi Pir light controller 3000W multi Pir light controller Cat No. MLB3000 - Black Cat No. MLW3000 - White Installation & Operating Instructions INSTALLATION & operating instructions SECTION ONE GENERAL INFORMATION The unit utilises

More information

Documentation. Content. Measurement and Control. Type: ELT-GP1. 1. Installation instructions 2. Data sheets 3. Declarations of conformity

Documentation. Content. Measurement and Control. Type: ELT-GP1. 1. Installation instructions 2. Data sheets 3. Declarations of conformity Documentation Measurement and Control Type: ELT-GP1 Content 1. Installation instructions 2. Data sheets 3. Declarations of conformity (Part No. 008Q520) eltherm GmbH Ernst-Heinkel-Str. 6-10 57299 Burbach

More information

Wireless temperature controller E N RFTC-50/G

Wireless temperature controller E N RFTC-50/G Wireless temperature controller E N RFTC-50/G Contents Warning... 3 Characteristics... 4 Technical parameters... 5 Battery replacement... 6 Description of device... 7 Description of display... 8 Description

More information

RN-16TM LIGHT-SENSITIVE MULTIFUNCTIONAL DAILY-WEEKLY TIMER SERVICE MANUAL. NOVATEK-ELECTRO LTD Research-and-Manufacture Company

RN-16TM LIGHT-SENSITIVE MULTIFUNCTIONAL DAILY-WEEKLY TIMER SERVICE MANUAL. NOVATEK-ELECTRO LTD Research-and-Manufacture Company LTD Research-and-Manufacture Company RN-16TM LIGHT-SENSITIVE MULTIFUNCTIONAL DAILY-WEEKLY TIMER SERVICE MANUAL www.novatek-electro.com - 2-1 APPLICATION Multifunctional relay RN-16TM (hereinafter RN-16TM)

More information

Universal Controller

Universal Controller 7 863 Universal Controller POLYGYR RWF32... ISO 9001 RWF32... with casing ARG61.01 The RWF32... is a universal digital boiler temperature / pressure controller designed for use in oil- and / or gas-fired

More information

Room Temperature Controller with Built-in Room Sensor 1 Feb 2002

Room Temperature Controller with Built-in Room Sensor 1 Feb 2002 R, RL C-32-10 Room Temperature Controller with Built-in Room Sensor 1 Feb 2002 R, RL controls room temperature in air handling systems with heating or cooling coils and in VAV systems. The controller has

More information

SmartZone-2 & SmartZone-4

SmartZone-2 & SmartZone-4 SmartZone-2 & SmartZone-4 Quick-Start Guide UPDATED 2011-7-26 This guide is intended to give the installer a brief set of instructions about how to set up the XCI Zoning SmartZone System. For more detailed

More information

Overview per day of the programmed switching times 5 = Friday. Channel statuses / OFF

Overview per day of the programmed switching times 5 = Friday. Channel statuses / OFF 310 785 01 TR 611 top TERMINA 1-channel 7 day timer According to version Preprogrammed with the current time and summer/ winter norm time Safety Information The connection and installation of electrical

More information

TM Analogic. Serie TM. Cod. rev

TM Analogic. Serie TM. Cod. rev TM Digital TM Digital-B TM Analogic Serie TM. Cod. rev. 1.0 1 CONTENTS 1 First of all Page 2 2 Installation Page 4 3 Setting and Operation Page 7 4 Maintenance Page 10 1 FIRST OF ALL - WARNINGS Check the

More information

Hardware Installation. Do this first:

Hardware Installation. Do this first: 1 Do this first: Hardware Installation Need some help? Here s what you ll need: 4 AA Batteries Phillips screwdriver Visit us online. support.remotelock.com We re here to help. 1 (877) 254 5625 support@remotelock.com

More information

CONTROL MANUAL. Dry-Pic 09PE - 09VE

CONTROL MANUAL. Dry-Pic 09PE - 09VE CONTROL MANUAL Dry-Pic 09PE - 09VE Translation of the original document 003, 04.01 EN CONTENTS PAGE 1 - IMPORTANT RECOMMENDATIONS 1.1 Power supply 1. Electronic board specifications 1.3 Caution 1.4 Earth

More information

Operating instructions Electronic level sensor LK / / 2008

Operating instructions Electronic level sensor LK / / 2008 Operating instructions Electronic level sensor LK31 UK 704046 / 00 01 / 2008 Contents Safety instructions...2 Menu structure...3 Controls and indicating elements...4 Function and features...5 Functional

More information

User s Manual. F2 Calculator. A metering component for thermal energy applications

User s Manual. F2 Calculator. A metering component for thermal energy applications User s Manual F2 Calculator A metering component for thermal energy applications Rev 08.24.2007 1 Installation 1.1 At delivery F2 calculators are delivered in the Transport Mode. Only the clock is active

More information

USER MANUAL ENGLISH 1450 COIN COUNTER & SORTER

USER MANUAL ENGLISH 1450 COIN COUNTER & SORTER USER MANUAL ENGLISH 1450 COIN COUNTER & SORTER INTRODUCTION ENGLISH Thank you for purchasing the Safescan 1450 coin counter and sorter. For proper use and maintenance, we advise to read this user manual

More information

RCMS460 and RCMS490 Series

RCMS460 and RCMS490 Series 4 T M RCMS460 and RCMS490 Series Digital Multi-Channel Ground Fault Monitor / Ground Fault Relay Grounded and High-Resistance Grounded AC/DC Systems Technical Bulletin NAE1042060 / 04.2013 BENDER Inc.

More information

Operating Manual MU2000K

Operating Manual MU2000K ZIEHL industrie elektronik GmbH + Co KG Daimlerstr.13, 74523 Schwäbisch Hall, Germany + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN

More information

Control module 2 circuits AD290. Installation and Service Manual

Control module 2 circuits AD290. Installation and Service Manual EN Control module 2 circuits AD290 Installation and Service Manual 129443-02 Contents 1 Introduction...4 1.1 Symbols used...4 1.2 Abbreviations...4 2 Safety instructions and recommendations...5 2.1 Recommendations...5

More information