VT guard Frequntly Asked Questions
|
|
- Madlyn Parrish
- 5 years ago
- Views:
Transcription
1 VT guard Frequntly Asked Questions I.Technical Informations a) Another possibility of connecting ( screws?) or suppling together with steel connector (would it be possible?) VT guard is connected via DIN TS 35 rail. Is a standart rail used for connecting of other equipment. We think that every other type of connection will be more complicated. b) No information in the catalog list and in instruction list about red lamp ( function) The Red LED diode indicate earth fault c) Do they have enough space in the cubicle (task for the customer) Please check on Your side d) Phase test - how long time it is tested e) 16 2/3Hz is possible No problem to use it by frequenz 16 2/3Hz f) Application for temperatures from - 25 C to - 50 C The test are at this moment not done. g) how does it change its characteristic under ferroresonance conditions? The ferroresonance phenomenon may take place in the case when the core of an inductive device becomes saturated, and its current-flux characteristic becomes non-linear. In practice the ferroresonant oscillations may be initiated by momentary saturation the core of the inductive element resulting from e.g. switching operation or other type of event resulting in a transient overvoltage in the system. The undamped ferroresonant osillations in power system are dangerous to the equipment installed due to large overcurrents and/or overvolatages which may ultimately lead to permanent equipment damage. For elimination of ferroresonance phenomenon is used normaly dumping resistor. Nominal value of dumping resistor is important for effective and quick dumping - see pictures. There is current versus time dependance. Dumping resistor 17ohm in first case - not effective long time. Dumping resistor 13ohm in the second case - effective dumping. 20KV 0V -20KV 0s 0.5s 1.0s 1.5s V(V2:-) Time - 1 -
2 20KV 0V -20KV 0s 0.5s 1.0s 1.5s V(V2:-) Time h) is there dissipated power during damping? VT guard combine low ohm dumping resistor for effective dumping and high ohm thermal protection (for earth fault). The thermal protection is activated in 1,5s for 100V(depends on voltage). There are used PTC thermistor for encreasing resistive value - generating heat. The temperature of VT guard cover is about 50C during earth fault. VT guard is insensitive to natural network asymetry - threshold voltage is between 20-24V. i) Typical earth fault clearing time for earth faults in XXX are about YY seconds, considering that saturation could occur during the overvoltage produced by the eath fault (sustained 3 seconds until protection operates), can effectiveness of the VT guard be assured?? VT guard funcionality: - During the first part (about 1,5s) the equipment has low resistance then after warming PTC thermistors, the equipment rise its resistive value to protect voltage transformer against overloading. After the earth fault is eliminated (if takes more than 1,5s), the VT guard needs about 2 minutes to cool down and lower its resistive value. - The voltage transformer is designed to withstand earth fault (normaly 1,9Un/8h) - voltage transformer is still in linear part of its charakteristick. - The ferroresonance phenomenon can occure only in ungrounded or not directly grounded networks. During earthfault the system is directly grounded and ferroresonance phenomenon can not occure. j) You have sent to me time - impedance characteristics for 100V, our customers asked if you have developed curves withing the device operating range (from 24 to 110 V) We have complete charateristic for 100V. Because PTC thermistor are used, the input's impedance is dependand on feed voltage (the input impedance is 450Ohm for 190V ) The input's impedance of VT Guard versus time for 100V - 2 -
3 k) The customer has recently normaliza a value of 150 ohm for the fixed damping resistor, is it possible to show using test results, simulations and comparisons that the VT Guard solution is more advantageous than the 150 ohm resistor? Simulations show that in many cases the resistance value needed for efficient damping of the ferroresonant oscillations is very small (<20Ohm). Using a damping resistor of such a low value results in a risk of thermal damage of the VTs during abnormal network asymmetry resulting from prolonged earthfaults. Simulation model for testing the effectiveness of ferroresonance damping with a resistor was done. See the case of phase disconnection at 0,2s time for different value of damping resistors. The effective damping was done by 15 Ohm resistor. But 15 Ohm resistor would cause overloading VT during earth fault, that is why VT Guard incraeases its Ohm value up to 200Ohm for 100V feed voltage
4 40A Secondary current at R=15Ohm 0A - 40A 0s 0. 2s 0. 4s 0. 6s 0. 8s 1. 0s -I(L1a) Ti me l) Is VT Guard apllicable to any VT regardless of its rated burden (VA), because if we take into account that during the first seconds the resistance has a value of about 15 ohms (this means a 600 VA burden for 100V), can this load cause thermal stress to the VT? Shoult it have a minimum rated VA? Time when VT guard has low input's impedance is short to could cause thermal stress to the VT. If the residual winding is 100/3V, there is 100V on VT guard during earth fault. The input impedance is 13 Ohm during first second - current is about 7,7A, after 3s the input's impedance of VT Guard is about 130Ohm - current is about 0,8A. Example: ABB VT use 1,6mm2 wire for secondary (residual winding). The secondary winding whitstand 206A for 3s. m) Can this very low initial resistance cause a voltage drop in the measured residual voltage? can it cause protective relays measuring residual voltage from the open delta winding to register smaller values during earth faults? The earth fault protection should be in paralel connection with VT guard - then there is the same voltage on VT guard and earth fault protection n) Are there minimum or special requierements for the VTs to be used with VT Guard? The VT guard is applicable to any type of voltage transformer equiped by auxiliary winding. VT guard should be used with cooperation with voltage transformers connected to open delta. o) Are available test procedures to check that VT guards are OK when doing periodic maintenance and testing of MV switchgear? The test can be done according to routine teststing (test of insensibility zone, threshold voltage, effctive dumping time - this three tests verify equipment funcionality) p) Are FerroTool and FerroSim software (depicted in the article) available? Ferro tool is under development and it isn't available in official application. q) Life time for VTGuard assuming frequent or not frequent ferroresonance corrections? No problem - no influence for operation and life time. r) Withstand time during earth fault? VT guard was tested for earth connection 110V ( voltage on residual winding when one phase is grounded - earth fault) for 8 hours and the temperatures according to temperature rise tests standard - 4 -
5 were below the required temperature given by this standard. It means that operation during earthfault is not a problem. II.Waranty a) Life time warranty 24 months warranty since the day of putting the apparatus into operation, but not longer than 36 months since the day of delivery. III. Delivery conditions a) Delivery time ( which delivery time we will set up as a standard) 14 days DDU Germany up to 100 pcs. Higher amounts has to be agreed
Ironing out resonance
Ironing out resonance Ferroresonance prevention in MV voltage transformers Wojciech Piasecki, Marek Florkowski, Marek Fulczyk, Pentti Mahonen, Mariusz Luto, Wieslaw Nowak, Otto Preiss Every engineer knows
More informationFerroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy
Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy W. Piasecki, M. Stosur, T. Kuczek, M. Kuniewski, R. Javora Abstract-- Evaluation
More informationFERRORESONANCE SIMULATION STUDIES USING EMTP
FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in
More informationTECHNICAL BULLETIN 004a Ferroresonance
May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques
More informationTRANSFORMERS FOR GIS APPLICATIONS VOLTAGE VOLTAGE TRANSFORMERS FOR GIS APPLICATIONS
VOLTAGE TRANSFORMERS FOR GIS APPLICATIONS VOLTAGE TRANSFORMERS FOR GIS APPLICATIONS INFORMATION ABOUT THE SAFE OPERATION OF VOLTAGE TRANSFORMERS OPERATION CONDITIONS FOR POTENTIAL TRANSFORMERS 1. When
More informationVoltage Transformers type UMZ User s Manual, Operation and Maintenance
Voltage Transformers type UMZ User s Manual, Operation and Maintenance ÿþþ Safety at first Safety instructions: Installation, connecting, operation and maintenance should be carried out by the authorised
More informationTypes CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay
Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Relay withdrawn from case Application The type CDG 11 relay
More informationType CP-S, CP-C & CP-A Switch mode
Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting
More informationSensor Technology. Applications for medium voltage
Sensor Technology Applications for medium voltage Contents Introduction to sensor technology... 3 Sensors versus instrument transformers... 6 Advantages for builders and users of switchgear... 7 The impact
More informationAddendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays
Dual-Source Power Supply Addendum to I.B. 17555 Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Table of Contents Page 1.0 Introduction...1 2.0 General
More informationTransformer Fault Categories
Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)
More informationCapacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices
Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices M. Sanaye-Pasand, R. Aghazadeh Applied Electromagnetics Research Excellence Center, Electrical & Computer Engineering
More informationTransformers, Power Supply Units and Socket Outlets
Transformers, Power Supply Units and Socket Outlets /2 Introduction /3 4AC3 bell transformers /4 4AC3 safety transformers /5 4AC2 power supply units /6 5TE6 REG socket outlets For further technical product
More informationModern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions
1 Transmission transformers are important links in the bulk power system. They allow transfer of power from generation centers, up to the high-voltage grid, and to bulk electric substations for distribution
More informationA Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage
A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of Hz zero sequence continuous voltage S. Nishiwaki, T. Nakamura, Y.Miyazaki Abstract When an one line grounding fault in a transmission
More information10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units
BETA Switching Transformers, Bells and Socket Outlets /2 Product overview /3 4AC3 0, 4AC3 1 bell transformers /5 4AC3 4... 4AC3 transformers for permanent loads /8 4AC2 4 power supply units / 7LQ2 2 bells
More informationLine to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems December 2010/AT301 by Reza Tajali, P.E. Square D Power Systems Engineering Make the most of your energy SM Revision
More informationCT Analyzer. Revolution in current transformer testing and calibration
CT Analyzer Revolution in current transformer testing and calibration Revolutionary way of CT testing Current transformers are used for relaying and metering purposes in electrical power systems. They
More informationModule 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor
Module 2 : Current and Voltage Transformers Lecture 8 : Introduction to VT Objectives In this lecture we will learn the following: Derive the equivalent circuit of a CCVT. Application of CCVT in power
More informationInstrument transformers for indoor applications. Product overview. Instrument transformers for indoor applications.
Instrument transformers for indoor applications Product overview Instrument transformers for indoor applications Product overview 2 I N S T R U M E N T T R A N S F O R M E R S F O R I N D O O R A P P L
More informationSpecifications. S&C BankGuard Plus Controls. For Substation Capacitor Banks and Shunt Reactors. Conditions of Sale
For Substation Capacitor Banks and Shunt Reactors Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified by the SPE CIAL
More informationDemagnetization of Power Transformers Following a DC Resistance Testing
Demagnetization of Power Transformers Following a DC Resistance Testing Dr.ing. Raka Levi DV Power, Sweden Abstract This paper discusses several methods for removal of remanent magnetism from power transformers.
More informationPower System Stability. Course Notes PART-1
PHILADELPHIA UNIVERSITY ELECTRICAL ENGINEERING DEPARTMENT Power System Stability Course Notes PART-1 Dr. A.Professor Mohammed Tawfeeq Al-Zuhairi September 2012 1 Power System Stability Introduction Dr.Mohammed
More informationSRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS
ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase
More informationT/3000 T/3000. Substation Maintenance and Commissioning Test Equipment
T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY
More informationELECTRICIAN S THEORY EXAMINATION 15 November 2014 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET51 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 15 November 2014 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three
More informationAlternative Testing Techniques for Current Transformers. Dinesh Chhajer, PE Technical Support Group MEGGER
Alternative Testing Techniques for Current Transformers Dinesh Chhajer, PE Technical Support Group MEGGER Agenda Current Transformer Definition and Fundamentals Current Transformer Applications o Metering
More informationPrimary Metering. What is Primary Metering?
NWEMS Primary Metering August 22, 2018 Bill Unbehaun, Tacoma Power Exchanging Expertise Since 1893 What is Primary Metering? Metering energy flow past a point at high voltage above 600v Both PTs and CTs
More informationQUINT-PS/ 3AC/24DC/10
Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system
More informationCapacitor protection relay
Capacitor Protection Relay FEATURES Capacitor unbalance protection Line current unbalance protection Overvoltage protection Overheating protection Ground fault protection Overcurrent protection Undercurrent
More informationCDV 22, 62. Voltage Controlled Overcurrent Relay GRID PROTECTION
PROTECTION CDV 22, 62 Voltage Controlled Overcurrent Relay CDV22 relay is used for overload and fault protection for ac generators when the sustained short circuit current is less than the full load current.
More informationSimulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid
5th International Conference on Computer Sciences and Automation Engineering (ICCSAE 2015) Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault
More informationMBS AG. KBR 18 Split-core current transformer. Further information about our new split-core current transformer KBR 18: Dimensions:
KBR 18 Split-core current transformer Dimensions: Round conductor: 18 mm Transformer width: 41.6 mm Transformer height: 64.5 mm Transformer depth incl. fixing clasps: 67.3 mm General technical specifications:
More informationA Study on Ferroresonance Mitigation Techniques for Power Transformer
A Study on Ferroresonance Mitigation Techniques for Power Transformer S. I. Kim, B. C. Sung, S. N. Kim, Y. C. Choi, H. J. Kim Abstract--This paper presents a comprehensive study on the ferroresonance mitigation
More informationGIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation
GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation W. Buesch 1) G. Palmieri M.Miesch J. Marmonier O. Chuniaud ALSTOM LTD 1) ALSTOM LTD High Voltage Equipment
More informationDesign, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter
1 Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter Nee, Staffan Norrga, Remus Teodorescu ISBN-10: 1118851560
More informationFerroresonance Experience in UK: Simulations and Measurements
Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey
More informationQUINT-PS-24DC/24DC/10
QUINT-PS-24/24/10 QUINT - converter, primary switched mode, input: 24 V, output: 24 V /10 A INTERFACE Data Sheet PHOENIX CONTACT - 02/2006 Description The QUINT - converter 24 V/10 A converts the voltage
More informationQUINT-PS/ 1AC/24DC/20
Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data sheet 103129_en_04 1 Description PHOENIX CONTACT - 02/2010 Features QUINT POWER power supply units Maximum system
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationHigh voltage engineering
High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency
More informationProtective Relays Digitrip 3000
New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer
More informationModeling Ferroresonance Phenomena on Voltage Transformer (VT)
Modeling Ferroresonance Phenomena on Voltage Transformer (VT) Mohammad Tolou Askari Department of Electrical Faculty of Engineering Universiti Putra Malaysia 43400 UPM Serdang, Selangor, Malaysia Abstract
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities
More informationVOLTAGE REGULATOR R 449. Installation and maintenance. This manual must be sent to the end user R 449 X2 Z1 X1 Z2 E+ E- (12V - 10A)
This manual must be sent to the end user X2 Z1 X1 Z2 E+ E- J1 t (12V - 10A) ~ 10 ohms Exciter field + - Isolated DC power supply Installation and maintenance WARNING TO AVOID HARM EITHER TO PEOPLE OR TO
More informationThe study of ferroresonance effects in electric power equipment
O.A. Ezechukwu, J.O. Ikelionwu / Journal of Engineering and Applied Sciences 6 () 7-77 Journal of Engineering and Applied Sciences 6 () 7-77 JOURNAL OF ENGINEERING AND APPLIED SCIENCES The study of ferroresonance
More informationSeries P. Applications
Ratings 25 800 VA Voltage Primary 230 / 400 / 460 V range Secondary 6 / 12 V 12 / 24 V 24 / 48 V 115 / 230 V Voltage selection by means of metal connection bridges, offering the full rated power at any
More informationACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH
ACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH Michael Freiburg Erik Sperling Michael Krueger OMICRON Austria
More informationDevice Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.
/9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala
More informationWebinar: An Effective Arc Flash Safety Program
Webinar: An Effective Arc Flash Safety Program Daleep Mohla September 10 th, 2015: 2pm ET Agenda Arc Flash Defined and Quantified NFPA 70E / CSA Z 462 - Recent Updates What is the ANSI Z10 Hierarchy of
More informationVariable Transformers Product Design & Engineering Data
Variable Transformers Product Design & Engineering Data Product Design & Engineering Data Type 1010B Cutaway General Information STACO ENERGY PRODUCTS CO. is a leading manufacturer of variable transformers,
More informationProtection components
General Application LT3-Si thermistor protection units continuously monitor the temperature of the machines to be protected (motors, generators, etc.) by means of PTC thermistor probes embedded in the
More informationSTS Fully automatic. Large graphic display. Primary injection testing capabilities: up to 3000 A, with the optional module BUX 3000
STS 4000 Multifunction substation maintenance & commissioning test system for current, voltage and power transformers. Capacitance / Tan Delta diagnostic system with the optional module TD 5000. w w w.
More informationPower Supplies 3. SDN-C Compact DIN Rail Series
SDN-C Compact DIN Rail Series The SDN-C DIN rail power supplies are the next generation of the popular SDN series. These models combine high efficiency and compact size with new visual diagnostic LEDs
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities
More informationTABLE OF CONTENT
Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES
More informationHYVA404 CTPT Analyzer instruction manual (V1.3.19) CT/PT Analyzer. User Manual (V1.3.19)
CT/PT Analyzer User Manual (V1.3.19) Content Warning...3 1 Application and Technical Index of CT/PT Analyzer... 4 1.1 Application... 4 1.2 CT Technical Index... 4 2 Hardware... 6 2.1 Introduction... 6
More information7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy
Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Additional Options Solkor
More informationSmart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INSTRUMENTRANSFORMER
Customer : REV. 0 Page 1/16 Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INRUMENTRANSFORMER CVS - 24 - G - Revision Prepared Description Checked by Rev. Date by 0 13/06/16 First issue E.
More informationMINI-PS AC/2X15DC/1
MII-PS-100-240AC/2X15DC/1 Power supply unit ITERFACE Data sheet 100299_en_04 1 Description PHOEIX COTACT - 2010-10-20 Features MII POWER is the extremely slim power supply unit with constructional widths
More informationNumbering System for Protective Devices, Control and Indication Devices for Power Systems
Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements
More informationOur Brands. Where we are?
CATALOG 2019 Our Brands Aktif trade mark for Measuring, Protection, Automatic Meter Reading, Billing and Energy Management Software. by Aktif Aktif trade mark for Measuring, Protection, Control and Power
More informationReyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy
Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Additional Options 15kV Isolation
More informationCatalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC
Catalogue 1SFC 266006-en, Edition 3 November 2003 Supersedes Catalogue 1SFC 266006-en, Edition 2 November 2000 Arc Guard System TVOC System units The two units of the are used as below: Approvals 1. with
More informationExcitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation
Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability
More informationCurrent and Voltage (potential) Instrument transformers Instruction for installation, use and maintenance
Current and Voltage (potential) Instrument transformers Instruction for installation, use and maintenance ABB Content: 1. Service conditions 3 2. Technical details. 3 3. Instruction for Installation..
More informationHigh-Efficiency Forward Transformer Reset Scheme Utilizes Integrated DC-DC Switcher IC Function
High-Efficiency Forward Transformer Reset Scheme Utilizes Integrated DC-DC Switcher IC Function Author: Tiziano Pastore Power Integrations GmbH Germany Abstract: This paper discusses a simple high-efficiency
More informationDEIF A/S. Insulation monitor. Type SIM-Q
Insulation monitor 4921232C Monitoring of insulation resistance on ungrounded AC networks (IT network) Working voltage up to 69V AC, withstands up to V DC Measuring range 1...Mohm or 1...Mohm Alarm on
More informationOperating Instruction
Level and Pressure Operating Instruction VEGASEL 643 6 5 + + 3 5 + + max. min. on VEGASEL 643 5 6 7 8 9 10 11 12 13 14 in out Contents Contents Safety information... 2 1 Product description 1.1 Function
More informationAPPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges.
APPLICATION: Basler Electric offers a New Line of digitally controlled brush (static) or brushless excitation systems designed for use with existing Hydro, Gas as well as Diesel driven generators requiring
More informationPower supply CP-D 24/4.2 Primary switch mode power supply
Data sheet Power supply CP-D 24/4.2 Primary switch mode power supply The CP-D range of modular power supply units in MDRC design (modular DIN rail components) is ideally suited for installation in distribution
More informationProtection of Electrical Networks. Christophe Prévé
Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé
More informationW DATA SHEET Current Transformer 40 x 10, A
W DATA SHEET Current Transformer 40 x 10, 250 600A W SCHRACK-INFO Current transformers for low-voltage network accuracy Single-phase current transformer Passing cable/ bus bar primary Primary current 250
More informationInstallation and Operating Instructions. Power IT Power Factor Controller RVC
Installation and Operating Instructions Power IT Power Factor Controller RVC Table of contents Page 1. Read this first... 3 About this Instruction Manual... 3 Safety... 3 Electromagnetic compatibility...
More informationHigh Performance Current Transducer ITL 900-T = A
High Performance Current Transducer ITL 900-T For the electronic measurement of currents: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. I PM = 0... 900 A Electrical
More informationGeneration Interconnection Requirements at Voltages 34.5 kv and Below
Generation Interconnection Requirements at Voltages 34.5 kv and Below 2005 March GENERATION INTERCONNECTION REQUIREMENTS AT 34.5 KV AND BELOW PAGE 1 OF 36 TABLE OF CONTENTS 1. INTRODUCTION 5 1.1. Intent
More informationFor the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer IN 1000-S N = 1000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Closed loop (compensated)
More informationTransformer Protection
Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing
More informationSimulations of open phase conditions on the high voltage side of YNd05-power plant transformers
Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Disclaimer: All information presented in the report, the results and the related computer program, data,
More informationQUINT-PS/ 3AC/24DC/40
Primary-switched power supply unit with SFB technology, 3 AC, output current 40 A INTERFACE Data sheet 103133_en_00 1 Description PHOENIX CONTACT - 07/2009 Features QUINT POWER power supply units Maximum
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationMedium voltage products. Field Application Support Analysis and calculations in Medium-Voltage electrical networks
Medium voltage products Field Application Support Analysis and calculations in Medium-Voltage electrical networks Concept The electrical installation of an industrial site is a complex structure. Analyzing
More informationPower supply CP-D 12/2.1
2CDC 271 025 F0t07 a OUTPUT ++/ : terminals output Features Rated output voltage 12 V DC Output voltage adjustable via front face potentiometer OUTPUT Adjust Rated output current 2.1 A Rated output power
More informationSpecialists in HV and MV test and diagnostics. Testing in Substations
Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies
More informationTVA 080 / 100 / 120 / 180 / 200 / 220 Isolation amplifier active
Technical manual BA 0318 Signal converter Isolation amplifier active for galvanic isolation, conversion and adjustment of electrical standard signals Evaluable input signals Direct voltage 0...10V / 0...1V
More informationRAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements
RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying
More informationThe new Yaskawa Varispeed G7 Inverter
The new Yaskawa Varispeed G7 Inverter Unique new 3-level PWM flux vector Constant or variable torque applications control method 0.4 kw to 300 kw power range Exceptional low speed/high torque control Quick
More informationPower factor correction and harmonic filtering. Automatic power factor regulators R.1
Power factor correction and harmonic filtering Automatic power factor regulators R.1 R.1 Automatic power factor regulators R.1 - Automatic power factor regulators Selection table R1-4 computer Plus-T Intelligent
More informationMedium-voltage transfomers
Medium-voltage transfomers We make energy measurable and take care of your future www.mbs-ag.com Page 2 E-Mail: info@mbs-ag.com Web: www.mbs-ag.com Contents Technical characteristics From page 4 Current
More informationQUINT-PS AC/24DC/40
Power supply unit INTERFACE Data sheet 102315_en_02 1 Description PHOENIX CONTACT 2010-04-23 Features QUINT POWER power supply units for plant and special engineering reliably start heavy loads with high
More informationSPAE 010, 011 High Impedance Protection Relay
SPAE 010, 011 High Impedance Protection Relay User s manual and Technical description f n = 50/60 Hz U n = 50 / 100 / 200 V 2 5 U REF > SPAE 010 0.8 U aux 0.6 1.0 RESET OK x 80... 265 V ~ _ 0.4 U > U n
More informationProtection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin
Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad
More informationImpact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis
1 Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis BK Pandey, DGM(OS-Elect) Venkateswara Rao Bitra, Manager (EMD Simhadri) 1.0 Introduction: Current
More informationIntegration between the MV protection and control unit REF542 and the LV protection trip unit PR123: selectivity and earth fault 1SDC007402G0201
1SDC007402G0201 Index 1. Introduction... 2 2. Theoretical outline 2.1 Restricted earth fault... 3 2.2 Selectivity between medium and low voltage... 4 3. Application examples and wiring logic 3.1 Restricted
More information1/23/2003. Sensor presentation
1/23/2003 Sensor presentation Product Scope A Sensor is a device intended to transmit a signal corresponding to the primary current or voltage to the secondary equipment. Power IT Sensors are typically
More informationProtection and control. Sepam range Sepam 100 LA Self-powering protection. Merlin Gerin Square D Telemecanique
Protection and control Sepam range Sepam 0 LA Self-powering protection Merlin Gerin Square D Telemecanique presentation contents page presentation protection functional and connection schemes other connection
More information02/11/2015
Smart range with Removable Terminal blocks XD26RBT Smart Part number 88974561 Designed for industrial, commercial, medical and paramedical machines Faster maintenance process which improves the machine
More informationOriginal operating instructions Fail-safe inductive sensor GM504S / / 2010
Original operating instructions Fail-safe inductive sensor GM504S 704070 / 01 06 / 2010 Contents 1 Preliminary note 3 1.1 Explanation of symbols 3 2 Safety instructions 4 2.1 Safety-related requirements
More informationTap Changer Analyzer & Winding Ohmmeter RMO60TD
Tap Changer Analyzer & Winding Ohmmeter RMO60TD Test current 5 ma 60 A DC Rapid automatic demagnetization AC Current monitoring channel Lightweight 13 kg Measuring range 0,1-2 k Two voltage sense channels
More informationPHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.
Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103129_en_01 PHOENIX CONTACT - 05/2008 1 Description QUINT POWER power supply units highest system availability
More information