Wiring and Measuring 4-20mA Instruments

Size: px
Start display at page:

Download "Wiring and Measuring 4-20mA Instruments"

Transcription

1 5 Gould Road, PO Box 2155 New London, NH USA Voice: (603) Wiring and Measuring 4-20mA Instruments Sensor Application Note #33 - Revision 1/24/2019 Overview Sensors with 4-20mA current outputs commonly include flowmeters, pressure transducers, displacement transducers and load cells. The primary advantages of a 4-20mA output are that the signal can be transmitted over long cable lengths with minimal degradation, the voltage conversion using a shunt resistor is easily read by most data acquisition systems and the output is usually standardized for the range which simplifies programming, e.g. 20mA corresponds to a rated full-scale output of the transducer, say 100 psi. This Sensor Application Note offers guidance to connect these instruments to several Campbell Scientific dataloggers, including the CR1000, CR6, CR300 and CR200. There are 4 considerations when connecting 4-20mA instruments to a data acquisition system: First, if the instrument requires power, whether it is loop-powered or powered through the same connections as the 4-20mA output, or requires a separate power supply. Related, if the sensor requires a separate power supply, whether it requires 24VDC (typically) or can be powered using the datalogger 12VDC power system. Second, the value of the shunt resistor. A value of 125ohms is recommended as the 2.5VDC maximum output is supported by all the dataloggers. Alternate values include 100ohms or 250ohms. Third, whether the shunt resistor is connected for single-ended or differential measurements. Single-ended measurements are more universally supported (for example the CR200 does not support differential measurements) however differential measurements provide higher measurement resolution. Differential wiring and measurements should be used where supported. Last, how the measurements are converted from a voltage measurement to engineering units. This requires knowing the value of the shunt resistor and the full-scale range of the instrument. Additionally, this generally requires configuration of a proper Zero Reading to provide offsets from the zero output of the instrument. Note - This Sensor Application Note does NOT consider connections using a multiplexer, however all the same principles apply when it comes to making the instrument connections. Multiplexers are configured for either 2-wire switching, typically used for loop-powered instruments, or 4-wire switching, typically used for instruments with separate power supplies. Wiring and Measuring 4-20mA Instruments 1

2 Instrument Wiring In this section several wiring examples are illustrated, note configurations for different dataloggers. Consult the technical documentation for the 4-20mA instrument to determine which wiring example applies. Note - The examples shown utilize the recommended 125Ω resistor. Loop powered 4-20mA instrument with 12VDC supply from the datalogger: Loop powered 4-20mA instrument with separate 24VDC supply: 2 Wiring and Measuring 4-20mA Instruments

3 Separate power 4-20mA instrument: The following table describes minimum and maximum voltages for different resistors: Resistor Ω (R) 4mA (I) (E = I * R) 20mA (I) (E = I * R) VDC VDC 2.0 VDC VDC 2.5 VDC VDC 5.0 VDC 4.0 Prior to configuring the datalogger the voltage must be checked at the shunt resistor. Use a Digital Voltmeter (DVM) to read the shunt resistor voltage. Voltage measurements should fall in the range shown in the table above. Note - Do not proceed with system configuration if the shunt resistor voltage is not within the range per the shunt resistor being used. Wiring and Measuring 4-20mA Instruments 3

4 MultiLogger Configuration Within MultiLogger, the Gage Type selections for each datalogger vary, however all the gage types output volts as the standard output type. This section illustrates the configuration for each datalogger type. The shunt resistor as assumed to be 125Ω, the full-scale output of the instrument is assumed to be 250 GPM. Calculations of the Zero Reading and Gage Factor for alternate configurations are explained in the following section. CR1000 (MLDAQ): CR6 (MLDAQ): 4 Wiring and Measuring 4-20mA Instruments

5 CR300 (MCLOG): CR200 (MCLOG): Zero Reading and Gage Factor Configuration Conversion to engineering units is dependent on the value of the shunt resistor and the full-scale output of the instrument. The Zero Reading corresponds to 4mA output voltage (although an in-situ measurement should be used) and the Gage Factor is calculated by dividing the full-scale range of the instrument output by the voltage delta. For example, if the full-scale output is 500gpm and the shunt resistor is 250Ω the Gage Factor is (500/4). MultiLogger is a Registered Trademarks of Canary Systems, Inc. Campbell Scientific is a Registered Trademark of Campbell Scientific, Inc. Wiring and Measuring 4-20mA Instruments 5

HI 2204LT Loop Powered Level Weight Transmitter OPERATION AND INSTALLATION MANUAL

HI 2204LT Loop Powered Level Weight Transmitter OPERATION AND INSTALLATION MANUAL Loop Powered Level Weight Transmitter OPERATION AND INSTALLATION MANUAL Corporate Headquarters 9440 Carroll Park Drive San Diego, CA 92121 Phone: (858) 278-2900 FAX: (858) 278-6700 Web-Site: http://www.hardysolutions.com

More information

MECE 3320 Measurements & Instrumentation. Data Acquisition

MECE 3320 Measurements & Instrumentation. Data Acquisition MECE 3320 Measurements & Instrumentation Data Acquisition Dr. Isaac Choutapalli Department of Mechanical Engineering University of Texas Pan American Sampling Concepts 1 f s t Sampling Rate f s 2 f m or

More information

CURS OHM CURRENT SHUNT TERMINAL INPUT MODULE INSTRUCTION MANUAL

CURS OHM CURRENT SHUNT TERMINAL INPUT MODULE INSTRUCTION MANUAL CURS100 100 OM CURRENT SUNT TERMNA NPUT MODUE NSTRUCTON MANUA REVSON: 4/00 COPYRGT (c) 1996 CAMPBE SCENTFC, NC. This is a blank page. Warranty and Assistance The CURS100 100 OM CURRENT SUNT TERMNA NPUT

More information

Balanced Constant Current Excitation for RTD Sensor Measurements

Balanced Constant Current Excitation for RTD Sensor Measurements Balanced Constant Current Excitation for RTD Sensor Measurements Douglas R. Firth Alan R. Szary Precision Filters, Inc. Ithaca, New York (607) 277-3550 1 Balanced Constant Current Excitation for RTD Sensor

More information

Making Basic Strain Measurements

Making Basic Strain Measurements IOtech Product Marketing Specialist steve.radecky@iotech.com Making Basic Strain Measurements using 24-Bit IOtech Hardware INTRODUCTION Strain gages are sensing devices used in a variety of physical test

More information

Unit 8 Combination Circuits

Unit 8 Combination Circuits Unit 8 Combination Circuits Objectives: Define a combination circuit. List the rules for parallel circuits. List the rules for series circuits. Solve for combination circuit values. Characteristics There

More information

CEC VIBRATION TRANSMITTER

CEC VIBRATION TRANSMITTER CEC 1-808 VIBRATION TRANSMITTER Operation & Maintenance Manual 746 Arrow Grand Circle Covina, CA 91722 United States of America Tel: (626) 938-0200 Fax: (626) 938-0202 Internet: http://www.cecvp.com E-mail:

More information

Source Transformations

Source Transformations Source Transformations Introduction The circuits in this set of problems consist of independent sources, resistors and a meter. In particular, these circuits do not contain dependent sources. Each of these

More information

Signal Conditioning Devices

Signal Conditioning Devices Lecture 4. Signal Conditioning Devices Signal Conditioning Operations In previous lectures we have studied various sensors and transducers used in a mechatronics system. Transducers sense physical phenomenon

More information

TRANSMITTER CALIBRATION

TRANSMITTER CALIBRATION TRANSMITTER CALIBRATION In this laboratory study, you will be asked to calibrate two of four different devices. To do so, you will need to write the equation defining the performance of the unit. Use this

More information

Emant Pte Ltd BRIDGE SENSOR APPLICATION ADAPTOR FOR EMANT300, EMANT380

Emant Pte Ltd BRIDGE SENSOR APPLICATION ADAPTOR FOR EMANT300, EMANT380 Emant Pte Ltd Application Adaptor BRIDGE SENSOR APPLICATION ADAPTOR FOR EMANT300, EMANT380 The Bridge Sensor Application Adaptor is used to connect bridge sensors like strain gauge, force sensor, pressure

More information

Series GLET Accessory for dataloggers series GL in modular enclosure

Series GLET Accessory for dataloggers series GL in modular enclosure PRESSURE LOAD TORQUE POSITION ROTARY ANGLE TILT ACCELERATION VIBRATION RATE SIGNAL CONDITIONER DATALOGGER Series GLET Accessory for dataloggers series GL in modular enclosure Models: GLET-IU-BNC-BA4 passive,

More information

TECHNICAL MANUAL. SERIES AP5103 DIN-Rail DC Strain Gage Conditioner ISO 9001/AS9100

TECHNICAL MANUAL. SERIES AP5103 DIN-Rail DC Strain Gage Conditioner ISO 9001/AS9100 TECHNICAL MANUAL SERIES AP5103 DIN-Rail DC Strain Gage Conditioner ISO 9001/AS9100 Due to the nature of technology, changes are inevitable. For latest technical specifications, see our website. Copyright

More information

Model 140 Inline Amplifier

Model 140 Inline Amplifier Model 140 Inline Amplifier Low Noise Inline Amplifier Small Rugged Package Includes Auto-Zero Function The Model 140 is a remote in-line DC amplifier designed to be used with bridgetype mv output transducers.

More information

Page 1 of 6 A Historical Perspective From Aristotle to Hawking Force & Its Effects Measurement Limitations The Strain Gage Sensor Designs Measuring Circuits Application & Installation Process Pressure

More information

Isolated STs Series, 4-20 ma Dissolved Oxygen and Temperature transmitter for in-line or submersible applications Insertion (in-line)

Isolated STs Series, 4-20 ma Dissolved Oxygen and Temperature transmitter for in-line or submersible applications Insertion (in-line) phiconntm, phikliptm, and sensorloggertm are trademarks of phionics Inc.. The phiconntm connector system and the phikliptm array system are covered by U.S. Patent Nos. 6,331,117, 6,612,848, 6,824,394,

More information

DRG-SC Series Signal Conditioners

DRG-SC Series Signal Conditioners DRG-SC Series Signal Conditioners DRG-SC Series 245 Basic unit Models Available for Thermocouples, RTDs, DC Voltage and Current, Frequency, Strain Gage Bridge, AC Voltage and Current Field Configurable

More information

Mems Tiltmeter (IPI Sensor Based) User Manual. Man /08/2014 Final Chris Rasmussen Phil Day

Mems Tiltmeter (IPI Sensor Based) User Manual. Man /08/2014 Final Chris Rasmussen Phil Day Mems Tiltmeter (IPI Sensor Based) Man193 2.0.2 07/08/2014 Final Chris Rasmussen Phil Day Manual No. Revision Date Originator Checked Authorised for Issue 1 Contents Section 1 : Section 2 : Introduction...

More information

Q2. Figure 1 shows the oscilloscope trace an alternating current (a.c.) electricity supply produces.

Q2. Figure 1 shows the oscilloscope trace an alternating current (a.c.) electricity supply produces. SERIES AND PARALEL CIRCUITS Q1. A student set up the electrical circuit shown in the figure below. (a) The ammeter displays a reading of 0.10 A. Calculate the potential difference across the 45 Ω resistor.

More information

Model A. DIN Rail Strain Gage Conditioner. Installation and Operating Manual

Model A. DIN Rail Strain Gage Conditioner. Installation and Operating Manual Model 8161-011A DIN Rail Strain Gage Conditioner Installation and Operating Manual For assistance with the operation of this product, contact PCB Piezotronics, Inc. Toll-free: 800-828-8840 24-hour SensorLine:

More information

EKT 314/4 LABORATORIES SHEET

EKT 314/4 LABORATORIES SHEET EKT 314/4 LABORATORIES SHEET WEEK DAY HOUR 4 1 2 PREPARED BY: EN. MUHAMAD ASMI BIN ROMLI EN. MOHD FISOL BIN OSMAN JULY 2009 Creating a Typical Measurement Application 5 This chapter introduces you to common

More information

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005. EL AL STANDARDS LABORATORY EL AL Head Office Ben-Gurion Airport Motty Shai Phone:

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005. EL AL STANDARDS LABORATORY EL AL Head Office Ben-Gurion Airport Motty Shai Phone: SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 EL AL STANDARDS LABORATORY EL AL Head Office Ben-Gurion Airport Motty Shai Phone: 972 3 9716596 CALIBRATION Valid To: July 31, 2019 Certificate Number: 4282.01

More information

Signal Conditioning Amplifier

Signal Conditioning Amplifier 2300 System Micro-Measurements FEATURES Accepts all strain gage inputs (foil and piezoresistive), potentiometers, DCDT s, etc Selectable bridge excitation, 0.7 to 15 VDC (11 steps), plus 0.2 to 7 VDC continuously

More information

Series T. General Eastern Differential Pressure Transmitters. GE Sensing. Description

Series T. General Eastern Differential Pressure Transmitters. GE Sensing. Description Description The Series T family of differential pressure transmitters measure low pressures and feature low power consumption and a variety of analog signal outputs. A wide selection of standard pressure

More information

MEP 382: Design of Applied Measurement Systems Lecture 5: Signal Conditioning

MEP 382: Design of Applied Measurement Systems Lecture 5: Signal Conditioning Faculty of Engineering MEP 382: Design of Applied Measurement Systems Lecture 5: Signal Conditioning Transducer Last Week - Sensors Bridge Completion Excitation Amplification Signal Conditioner Low Pass

More information

Model 176 and 178 DC Amplifiers

Model 176 and 178 DC Amplifiers Model 176 and 178 DC mplifiers Features*! Drifts to 100 MΩ! CMR: 120 db @! Gain Linearity of ±.005% *The key features of this amplifier series, listed above, do not necessarily apply

More information

P2 Quick Revision Questions. P2 for AQA GCSE examination 2018 onwards

P2 Quick Revision Questions. P2 for AQA GCSE examination 2018 onwards P2 Quick Revision Questions Question 1... of 50 How can an insulator become charged? Answer 1... of 50 Electrons being transferred from one material to another by friction. Question 2... of 50 Fill the

More information

8248AU. 4-Ch Isolated Amplifier with Optional Bridge Conditioning FEATURES TYPICAL APPLICATIONS

8248AU.   4-Ch Isolated Amplifier with Optional Bridge Conditioning FEATURES TYPICAL APPLICATIONS 8248AU The 8248AU is a single-width, 4-Ch Isolated Amplifier with Optional Bridge Conditioning 6U, CompactPCI/PXI module with 4 channels of Isolated Signal Conditioning feeding two buffered outputs. This

More information

An input resistor suppresses noise and stray pickup developed across the high input impedance of the op amp.

An input resistor suppresses noise and stray pickup developed across the high input impedance of the op amp. When you have completed this exercise, you will be able to operate a voltage follower using dc voltages. You will verify your results with a multimeter. O I The polarity of V O is identical to the polarity

More information

Chapter 3 Electronic Circuit for MWCNT Ethylene Sensor

Chapter 3 Electronic Circuit for MWCNT Ethylene Sensor Chapter Electronic Circuit for MWCNT Ethylene Sensor This chapter deals with design and prototype development of electronic circuits required for MWCNT ethylene sensor application. The customized potentiostat

More information

DP2000 ORDERING GUIDE To Order MODEL NO.

DP2000 ORDERING GUIDE To Order MODEL NO. 1 8 DIN VERSATILE PROCESS MONITORS CONFIGURABLE DP2000-S, 1 8 DIN meter, shown smaller than actual size. DP2000 Series Complete with Input Board RoHS 2 Compliant DP2000-J1, with TJ36-ICSS-116G-12, transition

More information

Electronic Simulation Software for Teaching and Learning

Electronic Simulation Software for Teaching and Learning Electronic Simulation Software for Teaching and Learning Electronic Simulation Software: 1. Ohms Law (a) Example 1 Zoom 200% (i) Run the simulation to verify the calculations provided. (ii) Stop the simulation

More information

Differential Amplifier : input. resistance. Differential amplifiers are widely used in engineering instrumentation

Differential Amplifier : input. resistance. Differential amplifiers are widely used in engineering instrumentation Differential Amplifier : input resistance Differential amplifiers are widely used in engineering instrumentation Differential Amplifier : input resistance v 2 v 1 ir 1 ir 1 2iR 1 R in v 2 i v 1 2R 1 Differential

More information

Series APD4059. For Load Cells/Pressure Transducer Transmitters. Field Rangeable, with Calibration Resistor. Standard Features.

Series APD4059. For Load Cells/Pressure Transducer Transmitters. Field Rangeable, with Calibration Resistor. Standard Features. TECHNICAL MANUAL Series APD4059 For Load Cells/Pressure Transducer Transmitters. Field Rangeable, with Calibration Resistor Standard Features Use Internal or External Calibration Resistor Sense Lead Compensation

More information

MPXM2051G, 0 to 50 kpa, Gauge Compensated Pressure Sensors

MPXM2051G, 0 to 50 kpa, Gauge Compensated Pressure Sensors Freescale Semiconductor Document Number: Data Sheet: Technical Data Rev. 3.0, 11/2015, 0 to 50 kpa, Gauge Compensated Pressure The device is a silicon piezoresistive pressure sensor providing a highly

More information

SOIL INSTRUMENTS BEAM ELECTROLEVEL, ELECTROLEVEL TILTMETER & HELM INSTALLATION MANUAL (Including Cable-Free sensor zeroing)

SOIL INSTRUMENTS BEAM ELECTROLEVEL, ELECTROLEVEL TILTMETER & HELM INSTALLATION MANUAL (Including Cable-Free sensor zeroing) SOIL INSTRUMENTS BEAM ELECTROLEVEL, ELECTROLEVEL TILTMETER & HELM INSTALLATION MANUAL (Including Cable-Free sensor zeroing) Man 173 6(A5) 04/4/2006 C. Rasmussen Phil Day Chris Rasmussen Manual No. Revision

More information

DT9838 Strain Measurement Module

DT9838 Strain Measurement Module Strain- and Bridge-Based Measurement Module Strain Measurement Module The module is a strain gage measurement device intended for full-, half, and quarter-bridge strain gage elements and bridge-based sensor

More information

Model TS. Transducer Simulator User s Guide. Sensotec Sensors

Model TS. Transducer Simulator User s Guide. Sensotec Sensors Model TS Transducer Simulator User s Guide Sensotec Sensors Honeywell Sensotec Sensors 2080 Arlingate Lane Columbus, OH 43228, USA Telephone: (614)850-5000 Fax: (614) 850-1111 Toll Free: 1-800-848-6564

More information

Draw, in the space below, a circuit diagram of this circuit. Use the correct symbols for each part of the circuit.

Draw, in the space below, a circuit diagram of this circuit. Use the correct symbols for each part of the circuit. Q1. The drawing shows the circuit used to investigate how the current through a 5 ohm (Ω) resistor changes as the potential difference (voltage) across the resistor changes. (a) Draw, in the space below,

More information

Electronic Measurements & Instrumentation. 1. Draw the Maxwell s Bridge Circuit and derives the expression for the unknown element at balance?

Electronic Measurements & Instrumentation. 1. Draw the Maxwell s Bridge Circuit and derives the expression for the unknown element at balance? UNIT -6 1. Draw the Maxwell s Bridge Circuit and derives the expression for the unknown element at balance? Ans: Maxwell's bridge, shown in Fig. 1.1, measures an unknown inductance in of standard arm offers

More information

RS-232 to Current Loop Converters

RS-232 to Current Loop Converters CL1060/1090xxx 703 5856 RS-232 to Current Loop Converters DB25F to DB25M Product Code CL1060A-M DB25M to DB25F Product Code CL1060A-F DB25M to Terminal Block Product Code CL1090A-M DB25F to Terminal Block

More information

Calibration Instruction Manual Emerson 475 Field Communicator. Manual Revision FC.2

Calibration Instruction Manual Emerson 475 Field Communicator. Manual Revision FC.2 Calibration Instruction Manual Emerson 475 Field Communicator Manual Revision FC.2 ABM 2 Wire Radar with HART ABM Sensor Technologies Inc 2013, all rights reserved. Emerson is a registered trademark of

More information

CUSTOM RANGE MODULE FOR THE SMART II

CUSTOM RANGE MODULE FOR THE SMART II CUSTOM RANGE MODULE FOR THE SMART II FEATURES 100% Staefa Smart II compatible Factory can customize for most applications Over a hundred different temperature and ranges are available Provides pull-up

More information

Single- or Multi-Channel Digital Process Indicators

Single- or Multi-Channel Digital Process Indicators Single- or Multi-Channel Digital Process Indicators For Panel or Benchtop Use DP81 Series Starts at $ 599 DP81T, $599, shown smaller than actual size. High Accuracy 14 Thermocouple Input Types 6 RTD Inputs:

More information

Remote Sensor Manual. User Guide. Revision A.0

Remote Sensor Manual. User Guide. Revision A.0 Remote Sensor Manual User Guide Revision A.0 Contents Remote Sensor User Manual... 3 Connecting Power... 3 Basic Sensor Operation... 4 Basic Sensor Operation with Data Logging... 5 Sensor Calibration Button...

More information

12/4/ X3 Bridge Amplifier. Resistive bridge amplifier with integrated excitation and power conditioning. Logos Electromechanical

12/4/ X3 Bridge Amplifier. Resistive bridge amplifier with integrated excitation and power conditioning. Logos Electromechanical 12/4/2010 1X3 Bridge Amplifier Resistive bridge amplifier with integrated excitation and power conditioning. Logos Electromechanical 1X3 Bridge Amplifier Resistive bridge amplifier with integrated excitation

More information

using dc inputs. You will verify circuit operation with a multimeter.

using dc inputs. You will verify circuit operation with a multimeter. Op Amp Fundamentals using dc inputs. You will verify circuit operation with a multimeter. FACET by Lab-Volt 77 Op Amp Fundamentals O circuit common. a. inverts the input voltage polarity. b. does not invert

More information

Signal Conditioning Amplifier

Signal Conditioning Amplifier FEATURES Accepts full, half, or quarter bridges; all bridgecompletion gages built in, including 120/1000- and 350-ohm dummies Fully adjustable and regulated bridge excitation on each channel; up to 12

More information

Model 50 Ground Loop ph Sensor Model 55 Solution Ground ph Sensor

Model 50 Ground Loop ph Sensor Model 55 Solution Ground ph Sensor Model 50 Ground Loop ph Sensor Model 55 Solution Ground ph Sensor Features Patented Plunger 1 ph Electrode Design Patented Porous 2 Teflon Liquid Junctions Double Junction Reference Cell Integral Differential

More information

Transducer for Measurement Bridges SCM90, SIGS15

Transducer for Measurement Bridges SCM90, SIGS15 Transducer for Measurement Bridges SCM90, SIGS15 General Description Transducer for measurement bridges for DINrails and for printed circuit boards. Programmable ranges and bridge supply, voltage or current

More information

EBRG. Data Sheet. edaq Bridge Layer. Special Features. Block Diagram. B en

EBRG. Data Sheet. edaq Bridge Layer. Special Features. Block Diagram. B en EBRG edaq Bridge Layer Data Sheet Special Features - 16 simultaneously-sampled, low-level differential analog inputs from ±0.000625 to ±10 V - 96 automatic gain states ensuring use of the fullest possible

More information

Antenna ANTA ANTA PCB Printed

Antenna ANTA ANTA PCB Printed Enclosure ACM ACMi ACMm Wireless range / m 800 m (2,600 ft) 500 m (1,600 ft) Power supply 3-18 Vdc or 2xD cell 3 Vdc (2xAA) 3 Vdc (2xAAA with BB1) Battery life at 1 transmission per second* 1 year 5 months

More information

Why Use Isolated Signal Conditioners?

Why Use Isolated Signal Conditioners? AN116 Dataforth Corporation Page 1 of 5 DID YOU KNOW? Samuel B. Morse (1791-1872) was born in Charlestown, Massachusetts. He studied art at Yale and the Royal Academy of Arts in London and was by 1815

More information

inc Channel 1 ph, ORP (Redox) Conductivity or Dissolved Oxygen Transmitter Channel 2 Temperature Transmitter Black (V-) Green (V-)

inc Channel 1 ph, ORP (Redox) Conductivity or Dissolved Oxygen Transmitter Channel 2 Temperature Transmitter Black (V-) Green (V-) phiconntm, phikliptm, and sensorloggertm are trademarks of phionics Inc.. The phiconntm connector system and the phikliptm array system are covered by U.S. Patent Nos. 6,331,117, 6,612,848, 6,824,394,

More information

User s Guide EWS-BP-A. Barometric Pressure Transmitter. Shop online at omega.com

User s Guide EWS-BP-A. Barometric Pressure Transmitter. Shop online at omega.com User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: www.omegamanual.info EWS-BP-A Barometric Pressure Transmitter omega.com info@omega.com Servicing North America:

More information

Question Bank SENSORS AND INSTRUMENTATION [EE-305/405]

Question Bank SENSORS AND INSTRUMENTATION [EE-305/405] UNIT-1 1. Discuss liquid in glass thermometers? 2. Write a short note on strain gauges. 3. Mention the various temperature scales and relation between them. 4. An experiment is conducted to calibrate a

More information

Signal Conditioning Amplifier

Signal Conditioning Amplifier FEATURES Plug-in amplifier design; amplifiers are removable from the front panel without rear access Constant-voltage or constant-current excitation; 0.5 to 15 V or 0.5 to 30 ma; selectable by single internal

More information

Where Do I Find Everything I Need for Process Measurement and Control? OMEGA Of Course! Shop online at omega.com SM

Where Do I Find Everything I Need for Process Measurement and Control? OMEGA Of Course! Shop online at omega.com SM Where Do I Find Everything I Need for Process Measurement and Control? OMEGA Of Course! Shop online at omega.com SM TEMPERATURE MU Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies

More information

TECHNICAL MANUAL. SERIES AP5202 DC Strain Gage In-Line Amplifier ISO 9001/AS9100

TECHNICAL MANUAL. SERIES AP5202 DC Strain Gage In-Line Amplifier ISO 9001/AS9100 TECHNICAL MANUAL SERIES AP5202 DC Strain Gage In-Line Amplifier ISO 9001/AS9100 Due to the nature of technology, changes are inevitable. For latest technical specifications, see our website. Copyright

More information

AEI800L Avid extreme Liquid Cooled Inverter Module Data Sheet REV 00, March AEI800L Liquid Cooled Inverter Module Data Sheet

AEI800L Avid extreme Liquid Cooled Inverter Module Data Sheet REV 00, March AEI800L Liquid Cooled Inverter Module Data Sheet AEI800L Avid extreme Liquid Cooled Inverter Module REV 00, March 2016 Avid Controls Inc. 41261 Park 290 Drive, Waller, TX 77484, USA info@avidcontrolsinc.com (+1) (281) 640-8600 Page 1 of 16 Copyright

More information

DC Current Transducers 4XCT-100-C-HP User s Manual All Rights Reserved CAEN ELS s.r.l. Rev. 1.0 February 2017

DC Current Transducers 4XCT-100-C-HP User s Manual All Rights Reserved CAEN ELS s.r.l. Rev. 1.0 February 2017 PRECISION CURRENT TRANSDUCERS < DC Current Transducers 4XCT-100-C-HP User s Manual All Rights Reserved CAEN ELS s.r.l. Rev. 1.0 February 2017 CAEN ELS s.r.l. Via Vetraia, 11 55049 Viareggio (LU) Italy

More information

LI190SB QUANTUM SENSOR

LI190SB QUANTUM SENSOR LI190SB QUANTUM SENSOR REVISION: 6/97 COPYRIGHT (c) 1982-1997 CAMPBELL SCIENTIFIC, INC. WARRANTY AND ASSISTANCE The LI190SB QUANTUM SENSOR is warranted by CAMPBELL SCIENTIFIC, INC. to be free from defects

More information

MM1/MM2 CONTROL VALVES CLOSED LOOP PROPORTIONAL PRESSURE CONTROLS THE FUTURE OF CONTROL TM

MM1/MM2 CONTROL VALVES CLOSED LOOP PROPORTIONAL PRESSURE CONTROLS THE FUTURE OF CONTROL TM THE FUTURE OF CONTROL TM MM1/MM CONTROL VALVES CLOSED LOOP PROPORTIONAL PRESSURE CONTROLS 317-335-60 P.O. Box 18 McCordsville, Indiana 46055 www.proportionair.com FEATURES Universal Mounting Din Rail,

More information

Exercise 3: Voltage in a Series Resistive Circuit

Exercise 3: Voltage in a Series Resistive Circuit DC Fundamentals Series Resistive Circuits Exercise 3: Voltage in a Series Resistive Circuit EXERCISE OBJECTIVE When you have completed this exercise, you will be able to determine the voltage in a series

More information

Isolated Inputs Offer New Application Advantages Protection from noise and ground loops due to ISO-Channel architecture

Isolated Inputs Offer New Application Advantages Protection from noise and ground loops due to ISO-Channel architecture Isolated Inputs Offer New Application Advantages Protection from noise and ground loops due to ISO-Channel architecture Precision measurement systems are often limited in that all inputs are connected

More information

PRECISION CURRENT TRANSDUCERS. DC Current Transducers CT-100 CT-150. User s Manual. All Rights Reserved CAEN ELS d.o.o. Rev. 1.

PRECISION CURRENT TRANSDUCERS. DC Current Transducers CT-100 CT-150. User s Manual. All Rights Reserved CAEN ELS d.o.o. Rev. 1. < DC Current Transducers CT-100 CT-150 User s Manual PRECISION CURRENT TRANSDUCERS All Rights Reserved CAEN ELS d.o.o. Rev. 1.1 November 2014 CAEN ELS d.o.o. Kraška ulica, 2 6210 Sežana Slovenija Mail:

More information

THE FUTURE OF CONTROLTM MM1/MM2 CONTROL VALVES CLOSED LOOP PROPORTIONAL PRESSURE CONTROLS

THE FUTURE OF CONTROLTM MM1/MM2 CONTROL VALVES CLOSED LOOP PROPORTIONAL PRESSURE CONTROLS THE FUTURE OF CONTROLTM MM1/MM CONTROL VALVES CLOSED LOOP PROPORTIONAL PRESSURE CONTROLS 317-335-60 P.O. Box 18 McCordsville, Indiana 46055 www.proportionair.com FEATURES Universal Mounting Din Rail, Panel

More information

Chapter 26: Direct current circuit

Chapter 26: Direct current circuit Chapter 26: Direct current circuit Resistors in circuits Equivalent resistance The nature of the electric potential and current in circuit Kirchhoff s rules (for complicated circuit analysis) Resistors

More information

CSG110 Strain Gauge Universal Amplifier

CSG110 Strain Gauge Universal Amplifier Quick Start Guide CSG110 Strain Gauge Universal Amplifier Sensor Solutions Source Load Torque Pressure Multi-Axis Calibration Instruments Software www.futek.com Getting Help TECHNICAL SUPPORT For more

More information

DT9838. Strain- and Bridge-Based Measurement Module. Key Features: Bridge Configurations. Analog Input Features

DT9838. Strain- and Bridge-Based Measurement Module. Key Features: Bridge Configurations. Analog Input Features Strain- and Bridge-Based Measurement Module The module is a strain gage measurement device intended for full-, half, and quarter-bridge strain gage elements and bridge-based sensor assemblies such as load

More information

Product Description. SIGnal Workbench. Programmable Signal Conditioning System

Product Description. SIGnal Workbench. Programmable Signal Conditioning System Product Description SIGnal Workbench Programmable Signal Conditioning System The Programmable Signal Conditioning System is comprised of a 4U chassis that can be table-top or rack-mounted (requires 5U

More information

Industrial Systems Design & Implementation

Industrial Systems Design & Implementation Industrial Systems Design & Implementation * Is no larger than a packet of cigarettes, and does not need batteries. Comes with two test cables, and extensive documentation with instructions and examples

More information

NEW! AOIP FD5 Advanced Digital Data Logger

NEW! AOIP FD5 Advanced Digital Data Logger NEW! AOIP FD5 Advanced Digital Data Logger Versatile data logger, each output channel can be custom configured for current, voltage, resistance, frequency, and temperature. The NEW! FD5 Digital Datalogger

More information

Freescale Semiconductor Data Sheet: Technical Data

Freescale Semiconductor Data Sheet: Technical Data Freescale Semiconductor Data Sheet: Technical Data Media Resistant and High Temperature Accuracy Integrated Silicon Sensor for Measuring Absolute, On-Chip Signal Conditioned, Temperature Compensated and

More information

DC Current Transducers CT-200 CT-300 CT-400 User s Manual All Rights Reserved CAEN ELS d.o.o. Rev. 1.0 November 2014

DC Current Transducers CT-200 CT-300 CT-400 User s Manual All Rights Reserved CAEN ELS d.o.o. Rev. 1.0 November 2014 < DC Current Transducers CT-200 CT-300 CT-400 User s Manual PRECISION CURRENT TRANSDUCERS All Rights Reserved CAEN ELS d.o.o. Rev. 1.0 November 2014 CAEN ELS d.o.o. Kraška ulica, 2 6210 Sežana Slovenija

More information

CS105 BAROMETRIC PRESSURE SENSOR

CS105 BAROMETRIC PRESSURE SENSOR REVISION: 3/97 COPYRIGHT (c) 1995-1997 CAMPBELL SCIENTIFIC, INC. WARRANTY AND ASSISTANCE The CS105 BAROMETRIC PRESSURE SENSOR is warranted by CAMPBELL SCIENTIFIC, INC. to be free from defects in materials

More information

Making Sense of Wireless Sensor Power Consumption. Steven Lee Application Engineer

Making Sense of Wireless Sensor Power Consumption. Steven Lee Application Engineer Making Sense of Wireless Sensor Power Consumption Steven Lee Application Engineer Agenda The importance of optimizing power consumption on sensors Test Case: Tire Pressure Monitor Sensor Traditional approach

More information

AN-177 HI-8190/HI-8191/HI-8192 Analog Switch Application Note

AN-177 HI-8190/HI-8191/HI-8192 Analog Switch Application Note January 3, 22 AN-77 HI-/HI-/HI-2 Analog Switch Application Note Introduction This application note provides examples using Holt s analog switches in ARINC 2 and general purpose applications. Occasionally,

More information

Experiment P-24 Circuits and Series Resistance

Experiment P-24 Circuits and Series Resistance 1 Experiment P-24 Circuits and Series Resistance Objectives To study the relationship between the voltage applied to a given resistor and the intensity of the current running through it. Modules and Sensors

More information

KING-GAGE. D/P Transmitter 4-20 ma Pressure Transmitter ma Pressure Transmitter. Operation/Calibration Manual

KING-GAGE. D/P Transmitter 4-20 ma Pressure Transmitter ma Pressure Transmitter. Operation/Calibration Manual Effective: August, 2009 (January, 2007) KING-GAGE 4-20 ma Pressure Transmitter D/P Transmitter 4-20 ma Pressure Transmitter Operation/Calibration Manual User Guide to Range Calculation, Calibration Procedures,

More information

Kirchhoff s laws. Objectives. Assessment. Assessment. Assessment. Assessment 5/27/14. Apply Kirchhoff s first and second laws.

Kirchhoff s laws. Objectives. Assessment. Assessment. Assessment. Assessment 5/27/14. Apply Kirchhoff s first and second laws. Kirchhoff s laws Objectives Apply Kirchhoff s first and second laws. Calculate the current and voltage for resistor circuits connected in parallel. Calculate the current and voltage for resistor circuits

More information

STRAIN, FORCE, PRESSURE, AND FLOW MEASUREMENTS

STRAIN, FORCE, PRESSURE, AND FLOW MEASUREMENTS SECTION 4 STRAIN,, PRESSURE, AND FLOW MEASUREMENTS Walt Kester STRAIN GAGES The most popular electrical elements used in force measurements include the resistance strain gage, the semiconductor strain

More information

Tel: (949) Fax: (949) IAA100 Product Manual

Tel: (949) Fax: (949) IAA100 Product Manual IAA100 Product Manual Table of Contents Default Settings... 3 Connections... 3 Standard Span & Zero Adjustment... 4 Shunt Readings... 5 Digitally Controlled Remote Shunt... 5 Switch Configurations... 6

More information

Fundamentals of Electric Circuits Chapter 2. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.

Fundamentals of Electric Circuits Chapter 2. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Fundamentals of Electric Circuits Chapter 2 Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display. Overview This chapter will introduce Ohm s law: a central concept

More information

Modus M Series. General Eastern Differential Pressure Transmitters. GE Sensing

Modus M Series. General Eastern Differential Pressure Transmitters. GE Sensing The Modus M Series family of differential pressure transmitters measure low pressures, and feature a variety of analog signal outputs with low power consumption. A wide selection of standard pressure ranges

More information

Laboratory 6. Lab 6. Operational Amplifier Circuits. Required Components: op amp 2 1k resistor 4 10k resistors 1 100k resistor 1 0.

Laboratory 6. Lab 6. Operational Amplifier Circuits. Required Components: op amp 2 1k resistor 4 10k resistors 1 100k resistor 1 0. Laboratory 6 Operational Amplifier Circuits Required Components: 1 741 op amp 2 1k resistor 4 10k resistors 1 100k resistor 1 0.1 F capacitor 6.1 Objectives The operational amplifier is one of the most

More information

12. ELECTRONICS & INSTRUMENTATION FOR TEMPERATURE

12. ELECTRONICS & INSTRUMENTATION FOR TEMPERATURE 12. ELECTRONICS & INSTRUMENTATION FOR TEMPERATURE 12.1 INTRODUCTION The range requirement in instrumentation ranges from a simple display of a single temperature value to multi sensor data acquisition

More information

INSTRUCTION MANUAL. CURS Ohm Current Shunt Terminal Input Module Revision: 4/17. Copyright Campbell Scientific, Inc.

INSTRUCTION MANUAL. CURS Ohm Current Shunt Terminal Input Module Revision: 4/17. Copyright Campbell Scientific, Inc. INSTRUCTION MANUAL CURS100 100 Ohm Current Shunt Terminal Input Module Revision: 4/17 Copyright 1996-2017 Campbell Scientific, Inc. Assistance Products may not be returned without prior authorization.

More information

Investigation of Sensing for DTE Power Via MDI. Jennifer Rasimas, Stephen Jackson January 20, 2000

Investigation of Sensing for DTE Power Via MDI. Jennifer Rasimas, Stephen Jackson January 20, 2000 Investigation of Sensing for DTE Power Via MDI Jennifer Rasimas, Stephen Jackson January 20, 2000 Overview A study of load detection through direct sensing by the LAN powering source. Scope of Study Experimental

More information

P a g e 1. Introduction

P a g e 1. Introduction P a g e 1 Introduction 1. Signals in digital form are more convenient than analog form for processing and control operation. 2. Real world signals originated from temperature, pressure, flow rate, force

More information

TRANSDUCER INTERFACE APPLICATIONS

TRANSDUCER INTERFACE APPLICATIONS TRANSDUCER INTERFACE APPLICATIONS Instrumentation amplifiers have long been used as preamplifiers in transducer applications. High quality transducers typically provide a highly linear output, but at a

More information

CVD20 20:1 Voltage Divider Revision: 5/12

CVD20 20:1 Voltage Divider Revision: 5/12 CVD20 20:1 Voltage Divider Revision: 5/12 Copyright 1990-2012 Campbell Scientific, Inc. PLEASE READ FIRST About this manual Please note that this manual was originally produced by Campbell Scientific

More information

Sensors. CS Embedded Systems p. 1/1

Sensors. CS Embedded Systems p. 1/1 CS 445 - Embedded Systems p. 1/1 Sensors A device that provides measurements of a physical process. Many sensors are transducers, devices that convert energy from one form to another. Examples: Pressure

More information

Series T. Amphenol Advanced Sensors. Differential Pressure Transmitters

Series T. Amphenol Advanced Sensors. Differential Pressure Transmitters Series T Differential Pressure Transmitters The Series T family of differential pressure transmitters measure low pressures and feature low power consumption and a variety of analog signal outputs. A wide

More information

user leaflet ABSOLUTE TTL MODULE

user leaflet ABSOLUTE TTL MODULE user leaflet ABSOLUTE TTL MODULE Product Description Introduction The Solartron ATM transducer comprises a sensor and conditioning electronics which provides an RS422 level square wave output. Each output

More information

EET 438a Automatic Control Systems Technology Laboratory 1 Analog Sensor Signal Conditioning

EET 438a Automatic Control Systems Technology Laboratory 1 Analog Sensor Signal Conditioning EET 438a Automatic Control Systems Technology Laboratory 1 Analog Sensor Signal Conditioning Objectives: Use analog OP AMP circuits to scale the output of a sensor to signal levels commonly found in practical

More information

AMP-13 OPERATOR S MANUAL

AMP-13 OPERATOR S MANUAL AMP-13 OPERATOR S MANUAL Version 2.0 Copyright 2008 by Vatell Corporation Vatell Corporation P.O. Box 66 Christiansburg, VA 24068 Phone: (540) 961-3576 Fax: (540) 953-3010 WARNING: Read instructions carefully

More information

Experiment P-10 Ohm's Law

Experiment P-10 Ohm's Law 1 Experiment P-10 Ohm's Law Objectives To study the relationship between the voltage applied to a given resistor and the intensity of the current running through it. Modules and Sensors PC + NeuLog application

More information

Experiment A3 Electronics I Procedure

Experiment A3 Electronics I Procedure Experiment A3 Electronics I Procedure Deliverables: Checked lab notebook, Brief technical memo Overview Most of the transducers used in modern engineering applications are electronic, meaning they convert

More information

Technical Information

Technical Information Technical Information Introduction to force sensors Driving long cable lengths Conversions, article reprints, glossary INTRODUCTION TO QUARTZ FORCE SENSORS Quartz Force Sensors are well suited for dynamic

More information