UNDERGROUND UTILITY TRENCHES AND VAULTS Page 1 of 6 ADDENDUM #1

Size: px
Start display at page:

Download "UNDERGROUND UTILITY TRENCHES AND VAULTS Page 1 of 6 ADDENDUM #1"

Transcription

1 Page 1 of 6 ADDENDUM #1 PART 1 GENERAL 1.01 PRINCIPAL WORK IN THIS SECTION A. The requirements of the Owner's General Conditions, Supplementary Conditions, Special Conditions, and Division 1 - General Requirements apply to the work of this Section. B. Coordinate the work of this Section with related trades. C. Verify applicable extents of work and dimensions at the jobsite. D. Furnish materials and perform labor required to execute this work as indicated on the drawings, as specified herein and as necessary to complete the work required by project conditions, including but not limited to: 1. Precast Concrete Trench Utility Trench Sections - Owner furnished, Contractor installed (OFCI) 2. Precast Concrete Steam Vaults - Owner furnished, Contractor installed (OFCI) 3. Precast Concrete Splice Vaults - Owner furnished, Contractor installed (OFCI) 4. Precast Accessories - Contractor furnished, Contractor installed (CFCI) E. Bids shall be based upon the specified product(s). The specified product(s) have been used in preparing the Drawings and Specifications and thus establish minimum qualities that substitutions must meet to qualify as acceptable. Proof of equality rests with the Bidder and adequate supporting information must accompany the Bid REFERENCE STANDARDS A California Building Code. B. Title 24 California Code of Regulations C. ATBCB ADAAG - Americans with Disabilities Act Accessibility Guidelines, current version. D. CBC Energy Code E. American Society For Testing and Materials (ASTM) 1. ASTM C 39 Test Method for Compressive Strength of Cylindrical Concrete Specimens 2. ASTM A 184 Standard Specification for Welded Deformed Steel Bar Mats for Concrete Reinforcement 3. ASTM A 185 Standard Specification for Steel Welded Wire Reinforcement, Plain, for Concrete 4. ASTM A 615 Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement 5. ASTM A 706 Standard Specification for Low-Alloy Steel Deformed and Plain Bars for Concrete Reinforcement 6. ASTM A 497 Standard Specification for Steel Welded Wire Reinforcement, Deformed, for Concrete 7. ASTM C 33 Standard Specification for Concrete Aggregates 8. ASTM C143 Standard Test Method for Slump of Hydraulic-Cement 9. ASTM C 150 Standard Specification for Portland Cement 10. ASTM C173 Standard Test Method for Air Content of Freshly Mixed Concrete by Volumetric Method 11. ASTM C 231 Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method 12. ASTM C 260 Standard Specification for Air-Entraining Admixtures for Concrete 13. ASTM C 443 Standard Specification for Joints for Concrete Pipe and Manholes, Using Rubber Gaskets 14. ASTM C 494 Standard Specification for Chemical Admixtures for Concrete 15. ASTM C 618 Standard Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in Concrete 16. ASTM C 990 Standard Specification for Joints for Concrete Pipe, Manholes, and Precast Box Sections Using Preformed Flexible Joint Sealants 17. ASTM A 48/A 48M - Standard Specification for Gray Iron Castings; 2003 (Reapproved 2008). 18. ASTM C Standard Practice for Minimum Structural Design Loading for Underground Precast Concrete Utility Structures; ASTM C Standard Specification for Underground Precast Concrete Utility Structures; 2010.

2 Page 2 of 6 ADDENDUM #1 20. ASTM C Standard Practice for Installation of Underground Precast Concrete Utility Structures; ASTM C Standard Practice for Inspection of Underground Precast Concrete Utility Structures; F. National Precast Concrete Association (NPCA) 1. NPCA Quality Control Manual. G. "Standard Specifications". 1. Is understood to refer to the Standard Specifications of the State of California, Business and Transportation Agency, Department of Transportation (CALTRANS), latest adopted edition. 2. In case of conflict between the Standard Specifications and these Specifications, whichever is greater and more stringent shall govern. H. Agency having jurisdiction: (AHJ) 1. California State University, Chico 2. When reference is made to the Standards it shall be understood that reference is to the Standard Specifications and Standard Detail Drawings of the jurisdiction herein indicated 1.03 PERFORMANCE, TESTING AND INSPECTION A. General: 1. Comply with manufacturer's standards. 2. Comply with Building Code. 3. Job site inspections shall be done as herein specified and as listed in drawings. 4. Testing shall be done as herein specified and as listed in drawings SUBMITTALS B. Submit O&M (Operation and Maintenance) manuals in accordance with Exhibit "C" Contract. C. General Conditions and as herein specified. D. Submit Manufacturers data and shop drawings. 1. Manufacturer's data: Submit complete data on materials including accessories and fittings. 2. Layout Drawings: Submit layouts of all utility trenches and vaults including all required openings. 3. Concrete mix design certificates and testing reports QUALITY ASSURANCE A. Contractor/Installer/Fabricator shall have been in business for five (5) years providing/installing/finishing projects of similar size and complexity. B. Manufacturer shall have been in business for five (5) years providing/installing/finishing projects of similar size and complexity. C. Pre-Installation Conference: A pre-installation conference shall be held prior to commencement of field operations to establish procedures to maintain optimum working conditions and to coordinate this work with related and adjacent work PRODUCT DELIVERY, STORAGE AND HANDLING 1.07 GUARANTEE / WARRANTY B. Furnish one (1) year written warranty signed by manufacturer and installer agreeing to repair and/or replace work which has failed as a result of defects in materials or workmanship. 1. Upon notification of Owner within the warranty period, such defects shall be repaired and replaced at no cost to the Owner.

3 Page 3 of 6 ADDENDUM # RELATED WORK / SECTIONS B. The requirements of the Owner's General Conditions, Supplementary Conditions, and Division 1 - General Requirements apply to the work of this Section. C. Related work includes, but is not limited to the following: 1. Sitework. 2. Underground electrical 3. Existing street utilities 1.09 OPERATION AND MAINTENANCE DATA A. Submit as part of project closeout: 1. Complete instructions regarding maintenance of the materials, etc SEQUENCING AND SCHEDULING A. Schedule work and sequence with General Contractor. B. Schedule required testing, prior to the installation of materials, components, etc. PART 2 PRODUCTS 2.01 ACCEPTABLE MANUFACTURERS A. Single source responsibility, specified items shall be from one manufacturer for each product type. B. All products and materials indicated shall be installed according to current listed specification requirements and manufacturers specifications/recommendations. C. Refer to drawings, details, and other related specification section whether listed or not. D. Details shall set basic requirements for size and configuration of systems. E. Basis of Design: Provide all precast concrete components shown on the plans and as needed for a complete and proper installation. Precast manhole components shall be manufactured and furnished by Jensen Precast, Sacramento, CA, info@jensenprecast.com <mailto:info@jensenprecast.com>, < 1. Provide basis of design product, or equal product approved by Engineer prior to bid in accordance with project bidding requirements PRECAST CONCRETE STEAM VAULTS - Owner furnished, Contractor installed (OFCI) A. Description: Precast steam vaults designed in accordance with ASTM C 858, comprising modular, interlocking sections complete with accessories. Jensen Precast Steam Vault or equivalent. B. Loading: ASTM C 857, Class A-16. C. Shape: As indicated on plans. D. Nominal Inside Dimensions: 10 feet x 8 feet. E. Inside Depth: 9 feet 6 inches. F. Base Section: Include 18 inch x 18 inch sump blockout. G. Top Section: Include 39 inch diameter grooved opening for frame and cover. H. Riser Casting: 6 inch, with step cast into frame. I. Frames and Covers: ASTM A 48; Class 30B gray cast iron, 27 inch size, machine finished with flat bearing surfaces. Provide cover marked STEAM to indicate utility. J. Ladder: Aluminum, with top hook to engage manhole step in riser casting. Provide one ladder for each vault. K. Sump Covers: ASTM A 48; Class 30B gray cast iron. L. Source Quality Control: Inspect manholes in accordance with ASTM C PRECAST CONCRETE JUNCTION BOX (TURN VAULT) - Owner furnished, Contractor installed (OFCI) A. General: Jensen Precast Junction Box or Pre-Approved Equal Model, meeting the following requirements:

4 Page 4 of 6 ADDENDUM #1 1. Shape/Size: As indicated on plans. 2. Loading: ASTM C 857, Class A Depth of Bury: As indicated on plans. 4. Lateral Soil Pressure: 60 lbs/cft 5. Earth Dead Load: 120 lbs/cft plus 1.15 Soil Interaction Factor 6. AASHTO M 198 and ASTM C 990, bitumen or butyl rubber PRECAST CONCRETE UTILITY TRENCH - Owner furnished, Contractor installed (OFCI) A. General: Jensen Precast Utility Trench Sections or Pre-Approved Equal Model, with provision for sealant at joints, meeting the following requirements: 1. Shape/Size: As indicated on plans. 2. Loading: ASTM C 857, Class A Depth of Bury: As indicated on plans. 4. Lateral Soil Pressure: 60 lbs/cft. 5. Earth Dead Load: 120 lbs/cft plus 1.15 Soil Interaction Factor. 6. AASHTO M 198 and ASTM C 990, bitumen or butyl rubber 2.05 PRECAST CONCRETE MATERIALS AND MIX DESIGN A. General: Precast concrete according to NPCA Quality Control Manual. B. Reinforcing Materials: 1. Reinforcing Bars: ASTM A 615/A 615M, Grade 60 (Grade 420), deformed. 2. Low-Alloy-Steel Reinforcing Bars: ASTM A 706/A 706M, deformed. 3. Steel Bar Mats:ASTM A 184/A 184M, fabricated from ASTM A 615/A 615M, Grade 60 (Grade 420), deformed bars, assembled with clips. 4. Plain-Steel Welded Wire Reinforcement: ASTM A 185, fabricated from as-drawn steel wire into flat sheets. 5. Deformed-Steel Welded Wire Reinforcement: ASTM A 497/A 497M, flat sheet. C. Concrete Materials: 1. Portland Cement: ASTM C 150, Type I, II or V. 2. Blended Cements: ASTM C Supplementary Cementitious Materials: 4. Fly Ash: ASTM C 618, Class C or F. 5. Aggregates: ASTM C 33 free from deleterious or reactive substances. 6. Water: ASTM C 1602, free from deleterious material. Use of reclaimed/recycled process water is acceptable. 7. Air-Entraining Admixture: ASTM C Chemical Admixtures: ASTM C 494/C 494M, water reducing; high-range water reducing; water reducing and accelerating; and water reducing and retarding. Do not use admixtures containing chlorides CONCRETE DESIGN MIXTURES A. Prepare design mixtures for each type of precast concrete required, by qualified independent laboratory or by manufacturer's qualified personnel at plant serving project. B. Proportion normal-weight concrete mixes to provide the following properties: 1. Minimum Compressive Strength: 5000 psi (34.5 MPa) at 28 days. 2. Maximum Water-Cementitious Materials Ratio: 0.40 maximum. 3. Air Content: 5.5 to 7.5 percent for concrete exposed to freezing and thawing, 2.5 to 4.5 percent elsewhere. C. Concrete Mixing: Comply with NPCA Quality Control Manual D. Finishes: Standard for formed surfaces. Trowel unformed surfaces. E. Replace precast concrete units deficient in strength, manufacturing tolerances, and finishes FABRICATION A. Fabricate precast concrete units according to NPCA Manual. B. Reinforcement: Comply with NPCA Quality Control Manual for fabricating, placing, and

5 Page 5 of 6 ADDENDUM #1 supporting reinforcement. 1. Fabricated cages of reinforcement either by tying bars, wires or welded wire reinforcement into rigid assemblies 2. Position reinforcing as specified by design, meeting minimum concrete cover requirements. Concrete cover minimum tolerance shall be one-third of that specified but not more than 1/2 inch (12 mm) but not less than 1/2 inch (12 mm). C. Comply with NPCA Quality Control Manual for measuring, mixing, transporting, and placing concrete. D. Print Manufactures Name, Job, Trench, Vault, and Casting Date on each precast structural concrete unit on a surface that will not show in finished structure. E. Discard and replace precast concrete box culvert units that do not comply with requirements unless repairs meet requirements and engineer's approval SOURCE QUALITY CONTROL A. Testing Agency: Owner will engage a qualified testing agency to evaluate precast structural concrete fabricator's quality-control and testing methods. B. Testing: Test and inspect precast structural concrete according to referenced design standards. C. Defective Units: Discard and replace precast structural concrete units that do not comply with requirements 2.09 OTHER MATERIALS (ACCESSORIES) - Contractor furnished, Contractor installed (CFCI) A. Provide other materials, not specifically described but required for a complete and proper installation, as selected by the General Contractor subject to the approval of the Architect. B. Joint Baker Material: Closed cell baker-rod and soft backer rod, closed cell polyethelene foam. ASTM C 1330, Type c. C. Sealant: One part polyurethene elastomeric sealant/adhesive. ASTM C-920, Type S, Grade NS, Class 25. PART 3 EXECUTION 3.01 EXAMINATION A. Verify that field measurements are as indicated. B. Verify routing and termination locations of utility trenches and vaults prior to excavation for rough-in. C. Verify locations of existing vaults prior to excavating for installation. D. Identify conditions detrimental to proper or timely completion of work and coordinate with General Contractor to rectify. E. Examine and verify that receiving conditions of substrate have no defects or errors, which would result in poor or potentially defective application or cause latent defects in workmanship. F. Utility trench routing is shown in approximate locations unless dimensions are indicated. Route as required to complete system. G. Vault locations are shown in approximate locations unless dimensions are indicated. Locate as required to complete utility trench system routing INSTALLATION OF PRECAST CONCRETE TRENCH SECTIONS A. Install precast concrete structure sections with sealants per ASTM C 990. B. Install precast concrete units to lines and grades indicated. Lift units by suitable lifting devices at points provided. Install units in accordance with manufacturer's recommendations. C. For multi-cell installations, install multiple units in parallel utilizing compacted earth fill, granular fill, flowable fill, or grouting to establish positive lateral bearing. D. Commence setting units at downstream end of line, with grooved ends of box bottom segments facing upstream. Place bottom of each segment in full contact with prepared bedding. After joining units, check for alignment and grade. E. Keep interior of units free of dirt and other foreign material as setting of units progresses. Leave installation clean at completion of work. F. Reset units not in true alignment, which show settlement, or are damaged.

6 Page 6 of 6 ADDENDUM #1 G. Joint units in such a manner that ends are fully entered and inner surfaces are flush and even, with maximum allowable gap between joints of 0.5 inch. Check joint and gap immediately after laying each unit. H. Install trench sections at slope and elevation as indicated on plans. Coordinate installation with steam condensate piping requirements. I. Provide suitable fittings to accommodate expansion and deflection where required. J. Seal joint between trenches and vaults with backing material and joint filler to form water tight connection INSTALLATION OF PRECAST CONCRETE VAULTS A. Install precast concrete units in compliance with manufacturer's instructions. B. Install precast concrete units to lines, grades, and inverts indicated. Lift units by suitable lifting devices at points provided. Install units in accordance with manufacturer's recommendations. C. Place bottom of each precast concrete unit in full contact with prepared bedding. Check for alignment and grade. D. Tests and Inspections: Verify bearing substrate preparation and compaction. Verify unit placement and joints meet requirements of referenced design and quality control standards FIELD QUALITY CONTROL A. Perform tests and inspections and prepare test reports. B. Tests and Inspections: Verify unit placement and joints meet requirements of referenced design and quality control standards. C. Remove and replace components of the precast concrete sections that do not pass tests and inspections and retest as specified above. D. Repairing Minor Defects: 1. Boxes which are cracked, checked or damaged shall not be placed and will be removed from the work unless appropriate repair procedures are submitted and approved. 2. Fine cracks and checks on the surface of the member which do not extend to the plane of the nearest reinforcement will not be cause for rejection unless they are numerous and extensive. Cracks which extend into the plane of the reinforcing shell shall be repaired in an approved manner. 3. Small damaged or honeycombed areas, which are purely surface in nature, shall be repaired in an approved manner. Excessive damage, honeycomb, or cracking will be subject to structural review. All repairs shall be made sound, properly finished, and cured according to the pertinent repair procedure. When fine cracks or hair checks on the surface indicate poor curing practices, the production of precast boxes shall be discontinued until corrections are made and proper curing is provided PROTECTION AND CLEAN UP A. Subcontractor will keep the work areas in a clean and safe condition so his rubbish, waste, and debris do not interfere with the work of others. B. Protect work and materials of this Section prior to and during installation, and protect the installed work and materials of other trades. C. Perform work in accordance with manufacturer's recommendations, as herein specified and in accordance with drawings. D. In the event of damage, immediately make all repairs and replacements necessary to the approval of the Architect and at no cost to the Owner. E. After completion of work in this section, remove all erection equipment and implements of service, and debris. 1. Leave entire area in a neat, clean, acceptable condition. END OF SECTION

Standard Specifications

Standard Specifications Standard Specifications PART 1.00 GENERAL 1.01 DECRIPTION SECTION 02620 PRECAST REINFORCED CONCRETE SANITARY MANHOLES A. Work included: The Contractor shall furnish all labor, materials, equipment, and

More information

A. Extent of structural precast concrete work is shown on drawings and in schedules.

A. Extent of structural precast concrete work is shown on drawings and in schedules. SECTION 03 41 00 - STRUCTURAL PRECAST CONCRETE PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 specification

More information

SPECIFICATIONS FOR THE MANUFACTURE AND DESIGN OF PRECAST THREE SIDED ARCH STRUCTURES, WINGWALLS AND HEADWALLS

SPECIFICATIONS FOR THE MANUFACTURE AND DESIGN OF PRECAST THREE SIDED ARCH STRUCTURES, WINGWALLS AND HEADWALLS SPECIFICATIONS FOR THE MANUFACTURE AND DESIGN OF PRECAST THREE SIDED ARCH STRUCTURES, WINGWALLS AND HEADWALLS 1. DESCRIPTION THESE SPECIFICATIONS ARE FOR A PRECAST THREE SIDED ARCH STRUCTURE, HEADWALLS

More information

14 March 2016 City Hall Station Renovations Bid Documents 15 th Street Station Phase Station Improvements SECTION PRECAST CONCRETE

14 March 2016 City Hall Station Renovations Bid Documents 15 th Street Station Phase Station Improvements SECTION PRECAST CONCRETE SECTION 03400 PRECAST CONCRETE PART 1 GENERAL 1.01 DESCRIPTION A. The work specified in this Section consists of designing, furnishing and installing precast concrete components. 1.02 RELATED SECTIONS

More information

StormTrap Guide Specification. StormTrap 2 SingleTrap on Aggregate Foundation Groundwater BELOW Invert Revised 11/30/17

StormTrap Guide Specification. StormTrap 2 SingleTrap on Aggregate Foundation Groundwater BELOW Invert Revised 11/30/17 StormTrap Guide Specification StormTrap 2 SingleTrap on Aggregate Foundation Groundwater BELOW Invert Revised 11/30/17 This product guide specification is written according to the Construction Specifications

More information

StormTrap Guide Specification. StormTrap SingleTrap on Pad Foundation Groundwater BELOW Invert Revised 11/21/18

StormTrap Guide Specification. StormTrap SingleTrap on Pad Foundation Groundwater BELOW Invert Revised 11/21/18 StormTrap Guide Specification StormTrap SingleTrap on Pad Foundation Groundwater BELOW Invert Revised 11/21/18 This product guide specification is written according to the Construction Specifications Institute

More information

SECTION PRECAST CONCRETE SECTIONAL MANHOLES

SECTION PRECAST CONCRETE SECTIONAL MANHOLES SECTION 02545 PRECAST CONCRETE SECTIONAL MANHOLES PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Precast reinforced concrete cylindrical sectional manholes, complete with openings, inserts, hardware,

More information

1. Architectural precast concrete cladding units.

1. Architectural precast concrete cladding units. SECTION 034500 - PRECAST ARCHITECTURAL CONCRETE PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Architectural precast concrete cladding units. 1.2 DEFINITION A. Design Reference

More information

SECTION PRECAST HOLLOW CORE PLANKS

SECTION PRECAST HOLLOW CORE PLANKS PART 1 GENERAL 1.1 SECTION INCLUDES A. Roof planks. B. Floor planks. C. Accessories. 1.2 RELATED REQUIREMENTS A. Division 01 General Requirements. SECTION 03 4113 PRECAST HOLLOW CORE PLANKS B. Section

More information

SECTION MANHOLES

SECTION MANHOLES SECTION 02601 MANHOLES PART 1 GENERAL 1.01 SCOPE OF WORK A. WORK required under this section consists of all materials, accessories, equipment, tools, and labor required to install precast concrete standard

More information

SECTION MANHOLES

SECTION MANHOLES SECTION 33 05 13 MANHOLES PART 1 GENERAL 1.01 SECTION INCLUDES A. CONTRACTOR shall furnish and install precast concrete manhole base, sections, adjusting rings, steps, and manhole ring and cover, complete.

More information

Large Scale CalArc Pavers for Sand-Set Pedestrian Use Installations

Large Scale CalArc Pavers for Sand-Set Pedestrian Use Installations The following specification refers to the Stepstone, Inc. product known as: Large Scale CalArc Pavers for Sand-Set Pedestrian Use Installations Large Scale CalArc Pavers are part of the California Architectural

More information

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION Sheet 1 of 5 KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION NOTE: This special provision is generally written in the imperative mood. The subject, "the

More information

SECTION 58 PRECAST CONCRETE BOX CULVERT. This work consists of furnishing and installing Pre-cast Concrete Box Culverts.

SECTION 58 PRECAST CONCRETE BOX CULVERT. This work consists of furnishing and installing Pre-cast Concrete Box Culverts. SECTION 58 PRECAST CONCRETE BOX CULVERT 58.1 DESCRIPTION A. General This work consists of furnishing and installing Pre-cast Concrete Box Culverts. B. Related Work Section 51 Section 52 Section 53 Section

More information

BPDL Architectural precast concrete specifications USA TESTING AND INSPECTION A. Testing by Independent Agency : Materials and workmanship furn

BPDL Architectural precast concrete specifications USA TESTING AND INSPECTION A. Testing by Independent Agency : Materials and workmanship furn BPDL Architectural precast concrete specifications USA 01 PART 1 General 1.1 DESCRIPTION OF WORK The work includes, but is not limited to : 1. Architectural precast concrete 2. Structural design, fabrication,

More information

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS. Notification of Completed Conduit Sections

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS. Notification of Completed Conduit Sections SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS Section 1 Definitions 2 Scope of Work 3 Extent of Work 4 Inspection and Performance of Work 5 Trenching 6 Duct Installation

More information

B. Installation Instructions. Provide installation instructions, including any special equipment, to address the following.

B. Installation Instructions. Provide installation instructions, including any special equipment, to address the following. SAMPLING AND TESTING. The Sampling and Testing requirements contained in -03 shall apply. MARKING. The Marking requirements contained in -03 shall apply. FINAL PRODUCTION INSPECTION. The Final Production

More information

2016 Specification Treads, Base, Stringers and other Amenities Wausau Tile Precast Epoxy Terrazzo

2016 Specification Treads, Base, Stringers and other Amenities Wausau Tile Precast Epoxy Terrazzo 2016 Specification Treads, Base, Stringers and other Amenities 09400 Wausau Tile Precast Epoxy Terrazzo PART 1 - GENERAL 1.1 SUMMARY A. Perform all work required to complete, as indicated by the Contract

More information

SECTION CONCRETE REINFORCEMENT FOR STEAM UTILITY DISTRIBUTION

SECTION CONCRETE REINFORCEMENT FOR STEAM UTILITY DISTRIBUTION PAGE 032015-1 SECTION 032015 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification sections,

More information

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENT 1073 PRECAST CONCRETE CERTIFICATION PROGRAM JULY 20, 2018

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENT 1073 PRECAST CONCRETE CERTIFICATION PROGRAM JULY 20, 2018 STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENT 1073 PRECAST CONCRETE CERTIFICATION PROGRAM JULY 20, 2018 1073.01 Program Overview 1073.02 Qualification 1073.03 Documentation Phase 1073.04 Documentation

More information

3400 Tectura Designs Precast Concrete

3400 Tectura Designs Precast Concrete 3400 Tectura Designs Precast Concrete PART 1 - GENERAL 1.1 SUMMARY A. Perform all work required to furnish and complete the proper installation of precast concrete. B. Types of Precast Concrete work include:

More information

SECTION COUNTERTOPS ecox PART 1 GENERAL

SECTION COUNTERTOPS ecox PART 1 GENERAL SECTION 11456 COUNTERTOPS ecox PART 1 GENERAL 1.1 SECTION INCLUDES A. Countertops B. Bar tops C. Vanity tops D. Table tops E. Reception counters F. Cash/back wraps G. Transaction counters H. Service counters

More information

SECTION PRECAST CONCRETE STRUCTURES

SECTION PRECAST CONCRETE STRUCTURES SECTION 02605 PRECAST CONCRETE STRUCTURES PART 1 GENERAL 1.01 DESCRIPTION A. CONTRACTOR shall provide all professional services, labor, materials, equipment and incidentals as shown, specified and required

More information

Section 914. JOINT AND WATERPROOFING MATERIALS

Section 914. JOINT AND WATERPROOFING MATERIALS 914.01 Section 914. JOINT AND WATERPROOFING MATERIALS 914.01. General Requirements. Joint and waterproofing material for use in concrete construction must meet the requirements of this section. 914.02.

More information

SECTION 39 - MANHOLES TABLE OF CONTENTS

SECTION 39 - MANHOLES TABLE OF CONTENTS SECTION 39 - MANHOLES TABLE OF CONTENTS Section Page 39-1 GENERAL... 39.1 39-2 PRECAST CONCRETE MANHOLES... 39.1 39-2.01 Precast Concrete Sewer Manholes... 39.1 39-2.02 Precast Concrete Storm Drain Manholes...

More information

SECTION ARCHITECTURAL PRECAST CONCRETE PART 1 - GENERAL

SECTION ARCHITECTURAL PRECAST CONCRETE PART 1 - GENERAL SECTION 03450 - ARCHITECTURAL PRECAST CONCRETE PART 1 - GENERAL 1.01 DESCRIPTION A. Work of this section is subject to requirements of the Contract Documents including the General Conditions and Supplementary

More information

CONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION

CONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 407 NOVEMBER 2013 CONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION TABLE OF CONTENTS 407.01

More information

SECTION PUBLIC UTILITY MANHOLES AND STRUCTURES. 2. Modular precast concrete pump wetwell. 5. Manhole bedding and cover materials.

SECTION PUBLIC UTILITY MANHOLES AND STRUCTURES. 2. Modular precast concrete pump wetwell. 5. Manhole bedding and cover materials. SECTION 02082 PUBLIC UTILITY MANHOLES AND STRUCTURES PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Modular precast concrete manholes with tongue-and-groove joints, transition to cover frame, covers,

More information

MANHOLES PART I: GENERAL. A. Precast Concrete Manholes

MANHOLES PART I: GENERAL. A. Precast Concrete Manholes MANHOLES PART I: GENERAL A. Precast Concrete Manholes 1) Manholes shall be made of precast concrete sections of which the top section shall be eccentric or flat slab top. The bottom section shall be a

More information

B. Terracotta Precast Facade Assembly consisting of single-leaf, through body color terracotta clay tiles.

B. Terracotta Precast Facade Assembly consisting of single-leaf, through body color terracotta clay tiles. SECTION 07 4229 TERRACOTTA CLAY TILE IN PRECAST SPECIFICTION FOR TERRART SOLID PART 1 GENERAL 1.1 SECTION INCLUDES A. Drawings and general provisions of the Contract, including General and Supplementary

More information

4.1. Foremen 4.2. Concrete plant manager 4.3. Concrete plant operator 4.4. Personnel performing saw cutting and joint sealing

4.1. Foremen 4.2. Concrete plant manager 4.3. Concrete plant operator 4.4. Personnel performing saw cutting and joint sealing 10-1. JOINTED PLAIN CONCRETE PAVEMENT GENERAL Summary This work includes constructing jointed plain concrete pavement. Comply with Section 40, "Concrete Pavement," of the Standard Specifications. Submittals

More information

East Central College

East Central College SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

A. Action Submittals: Written and graphic information that requires Engineer's responsive action.

A. Action Submittals: Written and graphic information that requires Engineer's responsive action. SECTION 01330 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification

More information

SECTION STRUCTURAL STEEL. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION STRUCTURAL STEEL. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 051200 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS

DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS PART 1 GENERAL 1.01 Scope of Work A. Provide material, accessories, tools, equipment and labor as required for the complete fabrication

More information

A. Action Submittals: Written and graphic information that requires Architect's responsive action.

A. Action Submittals: Written and graphic information that requires Architect's responsive action. SECTION 01330 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification

More information

STRUCTURES FOR SANITARY AND STORM SEWERS

STRUCTURES FOR SANITARY AND STORM SEWERS SUDAS Standard Specifications Division 6 - Structures for Sanitary and Storm Sewers Section 600 - Structures for Sanitary and Storm Sewers STRUCTURES FOR SANITARY AND STORM SEWERS PART - GENERAL.0 SECTION

More information

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence MILWAUKIE OR #3144-00 ADDENDUM #5 NARRATIVE: 11-08-12 WAL-MART SUPERCENTER #3144-00; Milwaukie, OR: SPECIFICATIONS SPECIFICATIONS Revisions to Specification 02822 Fence Spec division 02822 has been revised

More information

SECTION MANUFACTURED CASEWORK

SECTION MANUFACTURED CASEWORK 1 GENERAL 1.1 SECTION INCLUDES SECTION 12300 MANUFACTURED CASEWORK A. Work required to complete the manufactured casework indicated by the Contract Documents, and the items necessary for its proper installation.

More information

IGGA Guide Specification: Dowel Bar Retrofit (DBR) Introduction

IGGA Guide Specification: Dowel Bar Retrofit (DBR) Introduction IGGA Guide Specification: Dowel Bar Retrofit (DBR) Introduction This standard developed by the International Grooving and Grinding Association (IGGA) specifies the procedures for construction of dowel

More information

SECTION SAND CUSHION TERRAZZO FLOORING

SECTION SAND CUSHION TERRAZZO FLOORING SECTION 09 66 13.13 SAND CUSHION TERRAZZO FLOORING THIS GUIDE SPECIFICATION HAS BEEN PREPARED BY THE NATIONAL TERRAZZO AND MOSAIC ASSOCIATION, INC., AND IS DISTRIBUTED FOR USE BY ITS MEMBERS AND DESIGN

More information

To: New York State Department of Transportation ENGINEERING INSTRUCTION. Approved:

To: New York State Department of Transportation ENGINEERING INSTRUCTION. Approved: To: New York State Department of Transportation ENGINEERING INSTRUCTION Title: PRECAST CONCRETE PAVEMENT SLAB SYSTEMS STANDARD SPECIFICATION Distribution: Manufacturers (18) Local Govt. (31) Agencies (32)

More information

CVO/169897A OCTOBER 29, GROUT

CVO/169897A OCTOBER 29, GROUT SECTION 03600 GROUT PART 1 GENERAL 1.1 REFERENCES A. The following is a list of standards which may be referenced in this section: 1.2 SUBMITTALS 1. ASTM International (ASTM): a. C230, Standard Specification

More information

STANDARD SPECIFICATIONS SECTION PRECAST CONCRETE 1.2 REQUIREMENTS FOR MANUFACTURERS AND SUPPLIERS BEFORE DELIVERY

STANDARD SPECIFICATIONS SECTION PRECAST CONCRETE 1.2 REQUIREMENTS FOR MANUFACTURERS AND SUPPLIERS BEFORE DELIVERY STANDARD SPECIFICATIONS SECTION 03400 PRECAST CONCRETE PART 1 GENERAL 1.1 DESCRIPTION A. Section includes requirements for providing precast concrete structures, manholes, valve vaults, and other specified

More information

SECTION THERAPEUTIC POOL ACCESSORIES

SECTION THERAPEUTIC POOL ACCESSORIES PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 13 17 23.11 THERAPEUTIC POOL ACCESSORIES SPEC WRITER NOTES: Delete between // // if not applicable to project. Also, delete any other item or paragraph not applicable

More information

CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS

CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 422 MAY 1993 CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS 422.01 SCOPE 422.02 REFERENCES 422.03 DEFINITIONS

More information

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 2007 EDITION

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 2007 EDITION Sheet 1 of 7 KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 2007 EDITION SECTION 502 PORTLAND CEMENT CONCRETE PAVEMENT (NON-QC/QA) Page 500-20, subsection 502.2.

More information

SECTION TRACER WIRE FOR NONMETALLIC PIPE

SECTION TRACER WIRE FOR NONMETALLIC PIPE PART 1 GENERAL 1.1 DESCRIPTION A. The CONTRACTOR shall furnish and install a conductive tracer wire with all buried plastic water mains, services and appurtenances in accordance with the Water Utilities

More information

UNION COUNTY VOCATIONAL-TECHNICAL SCHOOLS West Hall Addition Project Raritan Road, Scotch Plains, NJ

UNION COUNTY VOCATIONAL-TECHNICAL SCHOOLS West Hall Addition Project Raritan Road, Scotch Plains, NJ SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 General

More information

1. Land survey Work. 2. Civil and Structural engineering services.

1. Land survey Work. 2. Civil and Structural engineering services. SECTION 01050 FIELD ENGINEERING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division-1 Specification

More information

JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia

JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia BULLETIN NO. 6 TO THE PLANS AND SPECIFICATIONS FOR JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia EwingCole Architects.Engineers.Interior Designers.Planners

More information

B. Bidders shall acknowledge receipt of this Addendum in writing on his Proposal Form.

B. Bidders shall acknowledge receipt of this Addendum in writing on his Proposal Form. McKee and Associates Architecture and Interior Design Addendum No. THREE Date: 12.11.17 Project: A NEW BUILDING FOR THE GREATER LIMESTONE COUNTY CHAMBER OF COMMERCE ATHENS, ALABAMA A3.1 GENERAL PROJECT

More information

SECTION ARCHITECTURAL PRECAST CONCRETE

SECTION ARCHITECTURAL PRECAST CONCRETE PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Column covers. 1.2 SUBMITTALS A. Design Mixtures: For each precast concrete mixture. Include compressive strength and waterabsorption

More information

SECTION PRECAST CULVERT STEAM TUNNEL

SECTION PRECAST CULVERT STEAM TUNNEL SECTION 334100 PRECAST CULVERT STEAM TUNNEL -, PART I - GENERAL LI STIPULATIONS - A. The Specification Sections "General Conditions of Contract", "Special Conditions" and "Division 01 - General Requirements"

More information

For crossing under a railroad, contact the specific railroad company's engineering department.

For crossing under a railroad, contact the specific railroad company's engineering department. PAGE 330524-1 SECTION 330524 SPECIFIER: This section is for the underground installation of piping by directional drilling. When specifying this method of piping installation, care must be taken to ensure

More information

A. Deviation from this standard must be approved by the Project Architect.

A. Deviation from this standard must be approved by the Project Architect. September 2012, rev. 00 26 5600 Exterior Lighting PART 1. GENERAL 1.01 Related Documents A. Deviation from this standard must be approved by the Project Architect. B. Drawings and general provisions of

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 01 3300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

SECTION DEWATERING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION DEWATERING PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 312319 - DEWATERING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

1.04 QUALITY ASSURANCE

1.04 QUALITY ASSURANCE SECTION 07312 ARCHITECTURAL ASPHALT SHINGLES PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Project No.: VTRC 06-R22 March Period Covered: Contract No.

Project No.: VTRC 06-R22 March Period Covered: Contract No. Standard Title Page - Report on State Project Report No. Report Date No. Pages Type Report: Final Project No.: 78783 VTRC 06-R22 March 2006 17 Period Covered: Contract No. Title: Evaluation of Precast

More information

SECTION SUBMITTAL PROCEDURES

SECTION SUBMITTAL PROCEDURES SECTION 013300 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections, apply

More information

SECTION SUBMITTAL PROCEDURES

SECTION SUBMITTAL PROCEDURES SECTION 01330 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification

More information

Design and Construction Standards SECTION ATHLETIC LOCKERS

Design and Construction Standards SECTION ATHLETIC LOCKERS SECTION 10505 ATHLETIC LOCKERS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The provisions of the General Conditions, Supplementary Conditions, and the Sections included under Division 1, General Requirements,

More information

.2 Accompany all submissions with a transmittal letter, in duplicate, containing:.4 Specification Section number for each submittal

.2 Accompany all submissions with a transmittal letter, in duplicate, containing:.4 Specification Section number for each submittal City of Winnipeg Brady Road Landfill Site Section 01300 New Entrance and Scale Facility Page 1 of 4 SUBMITTALS 1. SHOP DRAWINGS 1.1 General.1 Arrange for the preparation of clearly identified Shop Drawings

More information

THE ONTARIO CONCRETE PIPE ASSOCIATION

THE ONTARIO CONCRETE PIPE ASSOCIATION THE ONTARIO CONCRETE PIPE ASSOCIATION PRECAST BOX & CULVERT GUIDELINE Table of Contents 1 INTRODUCTION... 6 1.1 Background... 6 1.2 Existing Handbook and Drawings... 6 1.3 Distribution... 6 1.4 Revisions...

More information

Jointed Precast Concrete Pavement

Jointed Precast Concrete Pavement NATIONAL PRECAST CONCRETE ASSOCIATION Manual for Jointed Precast Concrete Pavement 3rd Edition Authors Peter Smith, P.E. Mark B. Snyder, Ph.D., P.E. Graphic Designer Deborah Templeton NPCA Precast Concrete

More information

MISSISSIPPI STATE UNIVERSITY Office of Planning Design and Construction Administration

MISSISSIPPI STATE UNIVERSITY Office of Planning Design and Construction Administration SECTION 01 340 - SHOP DRAWINGS, PRODUCT DATA AND SAMPLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other

More information

INDEX OF SPECIFICATIONS SECTION F SPECIAL CONDITIONS DIVISION 1 - GENERAL REQUIREMENTS:

INDEX OF SPECIFICATIONS SECTION F SPECIAL CONDITIONS DIVISION 1 - GENERAL REQUIREMENTS: INDEX OF SPECIFICATIONS SECTION F SPECIAL CONDITIONS DIVISION 1 - GENERAL REQUIREMENTS: 013300 SUBMITTAL PROCEDURES 018116 CONSTRUCTION WASTE MANAGEMENT DIVISION 2 EXISTING CONDITIONS: 023000 EARTHWORK

More information

SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING SECTION 230516 - EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION 1085 PRECAST REINFORCED CONCRETE BOX CULVERT

SECTION 1085 PRECAST REINFORCED CONCRETE BOX CULVERT 1085.1 1085.2(k) SECTION 1085 PRECAST REINFORCED CONCRETE BOX CULVERT 1085.1 DESCRIPTION This work is the manufacture, storage, delivery, installation, and assembly of precast reinforced concrete box culvert

More information

1. ANSI/ASME Standard B , Square and Hex Bolts and Screws, Inch Series

1. ANSI/ASME Standard B , Square and Hex Bolts and Screws, Inch Series SECTION 31 66 13 HELICAL PILES AND HELICAL ANCHORS PART 1 - GENERAL 1.1 DESCRIPTION A. This work pertains to furnishing and installing Helical Piles and Bracket Assemblies shown in the Contract in accordance

More information

ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030 ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO. 2018-008-COM.00030 To: Prospective Bidders of Record Date: January 8, 2019 The following changes, additions, revisions, and/or deletions

More information

B422 - PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS - OPSS 422

B422 - PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS - OPSS 422 B422 - PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS - OPSS 422 422.1 GENERAL The work under these tender items consists of the fabrication and installation in open cut of precast reinforced

More information

Solid Surface Countertops

Solid Surface Countertops USE THIS SECTION FOR COUNTERTOPS. USE SECTION 06 61 16 FOR OTHER SOLID SURFACING APPLICATIONS INCLUDING WALL CLADDING AND MISCELLANEOUS FABRICATIONS. GENERAL NOTES TO SPECIFIER: THIS SPECIFICATION SECTION

More information

PART MATERIALS. Section Fencing Materials. Description

PART MATERIALS. Section Fencing Materials. Description PART 03000 - MATERIALS Section 03010 - Fencing Materials Description 03010.00 Scope - This section consists of the test requirements, specifications and tolerances for barbed wire, woven wire and chain

More information

UCCS University Hall Fire Sprinkler System Upgrade March 1, 2011 RTA SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL

UCCS University Hall Fire Sprinkler System Upgrade March 1, 2011 RTA SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

A. Dewatering observation wells are part of dewatering allowance.

A. Dewatering observation wells are part of dewatering allowance. SECTION 312319 - DEWATERING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

NITTERHOUSE CONCRETE PRODUCTS, INC Molly Pitcher Highway South Chambersburg, PA

NITTERHOUSE CONCRETE PRODUCTS, INC Molly Pitcher Highway South Chambersburg, PA NITTERHOUSE CONCRETE PRODUCTS, INC. 2655 Molly Pitcher Highway South Chambersburg, PA 17201 717-267-4505 GUIDE SPECIFICATION FOR ARCHITECTURAL PRECAST CONCRETE INDEX Page PART I - GENERAL...1 A. DESCRIPTION...1

More information

SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 01 33 00 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II SECTION 013300 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

W DESIGN ASSOCIATES. Consulting Engineers & Architects McCook, Nebraska Hastings, Nebraska 68901

W DESIGN ASSOCIATES. Consulting Engineers & Architects McCook, Nebraska Hastings, Nebraska 68901 Consulting Engineers & Architects McCook, Nebraska 69001 Hastings, Nebraska 68901 ACME BUILDING DEVELOPMENT ADDENDUM NO. 1 SOUTHERN BELL HEARTLAND LLC HASTINGS, NEBRASKA WDA PROJECT #614-18 I. INSTRUCTIONS

More information

SECTION METAL FABRICATIONS

SECTION METAL FABRICATIONS SECTION 05100 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for metal fabrications, including minimum requirements for fabricator, and galvanizing. 1.02 REFERENCE STANDARDS A. ASTM

More information

2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations.

2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations. General Conditions: 1. Deliver all food service equipment as specified herein, including that which is reasonably inferred, with all related items necessary to complete work shown on contract drawings

More information

TABLE OF CONTENTS. 1.0 Scope. 2.0 References. 3.0 Definitions. 4.0 Submission and Design Requirements. 5.0 Materials 5.1 General 5.

TABLE OF CONTENTS. 1.0 Scope. 2.0 References. 3.0 Definitions. 4.0 Submission and Design Requirements. 5.0 Materials 5.1 General 5. 1.0 Scope 2.0 References 3.0 Definitions 4.0 Submission and Design Requirements 5.0 Materials 5.1 General 5.2 Marking 6.0 Equipment 7.0 Production 7.1 Steel Octagonal Poles 7.2 Base Plate 7.3 Top Cap 7.4

More information

Anti-Trust Statement

Anti-Trust Statement Anti-Trust Statement http://www.concrete-pipe.org/ A joint effort of the Texas Concrete Pipe Association and the Texas Department of Transportation What brought this about? The TxDOT organization consists

More information

Proposal PROJECT MANUAL P R O P E R T Y M A N A G E M E N T F A L L O N C O U N T Y. Baker, MT P.O. Box 846

Proposal PROJECT MANUAL P R O P E R T Y M A N A G E M E N T F A L L O N C O U N T Y. Baker, MT P.O. Box 846 PROJECT MANUAL P R O P E R T Y M A N A G E M E N T F A L L O N C O U N T Y Proposal P.O. Box 846 Baker, MT 59313 P R E C A S T R E I N F O R C E D C O N C R E T E B O X C U L V E R T F O R W E S T M O

More information

SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section

SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section 02760-1 of 5 SECTION 02760 STEEL LIGHTING STANDARDS 02760.01 GENERAL A. Description Steel lighting standards shall include, but not necessarily be limited to, furnishing and installing steel lighting poles,

More information

SECTION BULLET- RESISTANT DOORS

SECTION BULLET- RESISTANT DOORS 1 SECTION 08 3950 BULLET- RESISTANT DOORS PART 1- GENERAL 1.01 SUMMARY A. This Section Includes: 1. Bullet- resistant steel door and frame systems. 2. Door hardware for bullet- resistant steel door and

More information

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING SECTION 230516 - EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING PART I - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

1. INTRODUCTION 2. REFERENCE SPECIFICATIONS. Page -1- Bonding and Grouting

1. INTRODUCTION 2. REFERENCE SPECIFICATIONS. Page -1- Bonding and Grouting Page -1-1. INTRODUCTION 1.1 Scope This specification covers non-shrink and epoxy grouting of structural column base plates and equipment bases, Portland cement grout for minor elements and bonding agents

More information

SECTION SHEET METAL FLASHING AND TRIM

SECTION SHEET METAL FLASHING AND TRIM SECTION 07620 PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Formed roof drainage sheet metal fabrications. 2. Formed low-slope roof sheet metal fabrications. 1.2 SUBMITTALS A. Shop Drawings: Show

More information

Series Sloped glazed Curtain wall. Installation Instructions

Series Sloped glazed Curtain wall. Installation Instructions Series 5600 Sloped glazed Curtain wall Installation Instructions Part NO. Y308 February 2013 SECTION TABLE OF CONTENTS PAGE I. General Notes & Guidelines. 3-4 II. Gutter and Mullion Assembly.. 5 III. End

More information

GUIDELINE SPECIFICATIONS

GUIDELINE SPECIFICATIONS GUIDELINE SPECIFICATIONS GORDON MILLENNIUM DECORATIVE METAL COLUMN COVERS DIVISION 05 7500 or DIVISION 09 2000 Note To Specifier: Column Covers are a finished, decorative product and should be installed

More information

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II SECTION 101400 - SIGNAGE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and supplementary Conditions and Division-1 Specification Sections,

More information

SECTION DEWATERING TANKAGE PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION DEWATERING TANKAGE PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 31 23 19 - DEWATERING TANKAGE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

St. Monica Food Pantry

St. Monica Food Pantry St. Monica Food Pantry 26 5113-1 ELECTRICAL WORK DIVISION 26 SECTION 265113 INTERIOR LIGHTING FIXTURES PART 1. GENERAL 1.1 WORK INCLUDES A. Extent, location, and details of interior lighting fixture work

More information

SECTION CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP

SECTION CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP 1 1 1 0 1 0 1 0 1 SECTION 1 1 CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP BASED ON DFD MASTER SPECIFICATION DATED /01/ P A R T 1 - G E N E R A L SCOPE The work under this section shall consist of

More information

REVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty

REVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty HOT AISLE CONTAINMENT SYSTEM (HACS) REVISION #1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. B. C. Drawings and general provisions of the Contract, including General and Supplementary. Conditions apply to

More information

C. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available.

C. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available. SECTION 105113 - METAL LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Zip Block MODEL ZB INSTALLATION INSTRUCTIONS

Zip Block MODEL ZB INSTALLATION INSTRUCTIONS Zip Block MODEL ZB 100-400 INSTALLATION INSTRUCTIONS 12BT EXPOSED SURFACE SEAL WIDTH Zip Block SEAL 3/4" ± 1/8" [19.05mm ± 3.18mm] BLOCKOUT EDGE 3 1/2" [88.90mm] MAXIMUM BLOCKOUT NOMINAL JOINT WIDTH EPOXY

More information