Investigation of Transmission Line Overvoltages and their Deduction Approach
|
|
- Shauna Greer
- 6 years ago
- Views:
Transcription
1 Investigation of Transmission Line Overvoltages and their Deduction Approach A. Hayati Soloot, A. Gholami, E. Agheb, A. Ghorbandaeipour, and P. Mokhtari Abstract The two significant overvoltages in power system, switching overvoltage and lightning overvoltage, are investigated in this paper. Firstly, the effect of various power system parameters on Line Energization overvoltages is evaluated by simulation in ATP. The dominant parameters include line parameters; short-circuit impedance and circuit breaker parameters. Solutions to reduce switching overvoltages are reviewed and controlled closing using switchsync controllers is proposed as proper method. This paper also investigates lightning overvoltages in the overhead-cable transition. Simulations are performed in PSCAD/EMTDC. Surge arresters are applied in both ends of cable to fulfill the insulation coordination. The maximum amplitude of overvoltages inside the cable is surveyed which should be of great concerns in insulation coordination studies. Keywords Switching Overvoltage, Lightning Overvoltage, Insulation Coordination, ATP, PSCAD/EMTDC. I. INTRODUCTION HE level of transient overvoltage has a strong effect to T power system reliability. It has already been known that switching overvoltages are the most important criteria which the design of insulation of extra high voltage (EHV) systems is based on [1]. With the increment of the operating voltage of transmission systems, switching surge overvoltages determine the insulation design rather than lightning overvoltages. The insulation level required to withstand the switching surge overvoltages can have a significant influence on the cost of transmission systems. Therefore, an accurate estimation of the switching overvoltages under various conditions of operation is an important factor for the design of transmission systems. The main operations that can produce switching overvoltages are line energization and reenergization, capacitor and reactor switching, occurrences of faults and breaker openings [2]. Transmission line switching transient and its severity depend on the difference between the supply and the line voltages at the instant of energization. If energization occurs A. Hayati Soloot is with Electrical Engineering Department, Iran University of Science and Technology (corresponding author to provide phone: ; amir.hayati@ gmail.com). A. Gholami is with Electrical Engineering Department, Iran University of Science and Technology, ( gholami@iust.ac.ir). E. Agheb is with School of Electrical and Computer Department, University of Tehran ( e.agheb@gmail.com). A. Ghorbandaeipour is with School of Electrical and Computer Department, University of Tehran ( ali.ghr@gmail.com) P. Mokhtari is with North Industrial Electricity Company ( pozhhan@gmail.com). at an instant when the difference between supply voltage and the line voltage is high, a large traveling wave would be injected on the transmission line. At the time, this wave reaches the open far end of the line, it gets reflected and a high transient overvoltage is experienced [3]. Such switching transients are of concern for many EHV transmission networks, especially for long transmission lines. For transmission networks rated at voltages of 420 kv and above, switching impulse withstand voltage of the system and its equipments is about 2-3 p.u. and therefore, switching overvoltages have to be kept under control [3], [4]. Line parameters surveyed here are the length of transmission line, trapped charge and shunt compensation. Circuit breaker parameters are pole discordance, preinsertion resistors and their being in system duration. The limitation of the switching overvoltages especially when used in combination with surge arresters could be similar to what is achieved with preinsertion resistors [4]. ATP program is used to simulate the energization of a typical 400 kv transmission line. J.Marti Model applied for the transmission line is a frequency dependant model with constant transformation matrix [5]. Since switching phenomenon is simulated; the appropriate matrix frequency is 5 khz [6]. Lightning overvoltages must be taken into account when designing the insulation system of a cable. The required lightning impulse voltage withstand capability (BIL) is defined in norms (e.g., IEC ) as specified levels of a 1.2/50 µs impulse voltage. IEC specifies one, two, or three BIL levels for each system voltage, thus giving the customer some room for adapting the BIL to the actual lightning overvoltage conditions. The manufacturer is simply required to produce cables that satisfy the lightning test voltages [7]. To avoid cable failures due to Lightning Overvoltages, it is essential to keep the protective level provided by arresters within a safe margin. It is then desirable to calculate the maximum overvoltages experienced by cables with certain accuracy [8]. The models for overhead lines and underground cables in ATP/EMTP are generally based on the Method of Characteristics (MoC) with recursive convolution due to the high efficiency of the resulting model. For overhead lines, satisfactory results can usually be achieved by assuming a constant transformation matrix and frequency-dependent modes. For underground cables, however, the assumption of a constant can lead to erroneous results. This problem can, for most cable systems, be overcome by frequency dependent 18
2 transformation matrix [9], [10]. II. SWITCHING OVERVOLTAGES A. Simulation Specifications for Line Energization In order to investigate the effects of power system parameters on switching overvoltages, the following circuit in Fig. 1 is used for simulation. The parameters of the voltage source are determined in Table I. TABLE II RADII AND RESISTANCES OF PHASE CONDUCTOR AND SHIELD WIRE outer radius of shield wire 0.76 mm inner radius of shield wire 0 resistance per kilometer of shield wire 1.63 Ω outer radius of phase conductor 3.15 mm inner radius of phase conductor resistance per kilometer of phase conductor 0.85 mm Ω Fig. 1 Power network arrangement applied for simulation in ATP TABLE I PARAMETERS OF THE VOLTAGE SOURCE source voltage (line voltage) frequency positive sequence resistance zero sequence resistance positive sequence inductance zero sequence inductance 400 kv 50 Hz Ω 0.55 Ω mh 8.98 mh Fig. 2 depicts the dimensions of the transmission line towers and the conductor arrangements. J. Marti model is defined for transmission line modeling. Skin effect, segmented grounding and transposition are considered in the modeling. Table II provides the radii and resistances of phase conductors and shield wires. Considering these phase distances, the per-meter inductance and per-meter capacitance of transmission line is achievable by these formulas [11]: μ GMD L = 0 Ln( ) 2 π r (H/m) (1) 2πε C = 0 GMD Ln( ) r (F/m) (2) where: GMD = 3 D D (3) e 12 13D r = r (4) D 12, D 13 and D 23 in equation (3), are phase-to-phase distances and r is the radius of phase conductor. The time takes for switching surge to travel from the beginning to the end of the transmission line is represented by τ and is calculated using equation (5): τ = l LC In equation (5), l is the length of the transmission line and is assumed 220 kilometer in this paper. For the dimensions shown in Fig. 2 and the assumed length, τ is 0.74 millisecond. The period of switching overvoltages is 4τ and equals to 2.96 millisecond. (5) Fig. 2 Conductor arrangements for the 400 kv tower Fig. 3 Voltage at the beginning of the transmission line (red curve), voltage at the end of the transmission line (green curve) 19
3 The duplication of the switching surge at the end of transmission line is illustrated in Fig. 3 and Fig. 4. From Fig. 3, it can be obtained that damping of switching overvoltages takes around 100 milliseconds. Comparing the green curve (voltage at the end of transmission line) with the red one (voltage ate the beginning of transmission line) in Fig. 4, traveling time is 740 microseconds which exactly corresponds to the amount calculated from equation 5. U = Z i (8) f s f R and L in equation 7 and 8 are R + and L +. U f is the front traveling surge. Combining the two equations, equation (9) is resulted. ( R+ Zs ) t RU Z su L U RL = + e (9) R + Z s R + Z s URL is the voltage drop on equivalent short circuit impedance. As R is so smaller than Z s, equation 9 can be simplified to the following formula: Z st L (10) U RL = Ue Equation 10 describes the blue curve in Fig. 5. Increasing the inductance leads to higher time constant for the deduction of voltage on short circuit impedance and consequently slower increase in switching surge at the beginning and end of transmission line. Fig. 4 Voltage at the beginning of the transmission line (red curve), voltage at the end of the transmission line (green curve), voltage drop on the equivalent short circuit impedance (blue curve) and current surge by a factor of 500 (pink curve) It takes 2τ for switching surge to return to the beginning of the transmission line. In this time interval, voltage and current surges have the same form, just the current surge is 500 times smaller than voltage one. This multiplication factor is equal to surge impedance Z s which is defined as: L Z s = (6) C The diversion of current surge after 2τ causes a spike voltage on the equivalent short circuit impedance and affects the switching surge as well. According to what mentioned in this section, the effect of power system parameters is investigated in the following sections. B. Effect of Voltage Source Parameters Voltage source represents network voltage, frequency and short circuit impedance. Among these parameters, network voltage and frequency are consistent and short circuit impedance can be considered as a variable parameter. At first, the effect of positive sequence inductance is surveyed. If the positive sequence inductance is multiplied by four, the time constant of voltage rising at the end of the transmission line will be quadrupled. It results in smoother switching overvoltage but the peak of switching transient is some ten kilovolts higher. In order to describe this effect, the following equations just after switching can be applied: di U Ri + L + dt = (7) U f Fig. 5 Voltage at the beginning (red curve) and voltage at the end of the transmission line (green curve) for L + = mh, voltage at the beginning of the transmission line (blue curve) and voltage at the end of the transmission line (pink curve) for L + =47.4 mh C. Effect of Circuit Breaker Parameters Circuit breaker plays the main role in transient overvoltages of line energization. Voltage difference on circuit breaker before switching definitely determines the amplitude of overvoltages at the end of transmission line. In previous section, it was mentioned that energizing a transmission line at the moment of peak voltage results in 2 p.u. overvoltage surge at the end of transmission line. In order to reduce the amplitude of overvoltages, pre-insertion resistors can be used at the moment of switching. The simulation circuit suitable for investigating preinsertion resistor effect is brought in Fig. 6. The time interval which the resistor presents is in the order of milliseconds due to the mechanical delay time in breakers which is in the same order. The second breaker bypasses the resistor after some ten milliseconds of first breaker closure. This delay time is a margin to prevent from closure of bypassing breaker sooner 20
4 than main breaker. Bypassing Breaker Second Breaker First Breaker Fig. 8 The simulation circuit to model the trapped charge Main Breaker Fig. 6 The simulation circuit for investigating pre-insertion resistor effects Fig. 7 describes the effect of pre-insertion resistance value on the amplitude of overvoltages in the 400 kv network in Fig. 6. Increasing the resistance, the amplitude of overvoltages will be deducted. Besides, the more resistance is inserted, the more voltage drop is across the pre-insertion resistor in steady state which means that if the bypassing of the resistor is not done precisely at the moment of zero potential across it, higher switching transients will occur again. This effect was of main importance when the idea of synchronous switching was not prompt. Synchronous switching by switch-sync relays is definitely a proper substitution for pre-insertion resistors which will be discussed in next section. TABLE III DAMPING TIME OF OVERVOLTAGE TRANSIENTS APPLYING VARIOUS RESISTANCE VALUES Resistance Value Damping Time (Ohm) (ms) The worst case is when a trapped charge of -1 p.u and energizing the transmission line in +1 p.u. The transient overvoltage reaches to 3 p.u. illustrated in Fig. 9. The insulators at the end of transmission line encounter 4 p.u. voltage changes in 100 us when the first surge reaches to end of transmission line. Overvoltage(pu) Overvoltage at the end of trans. line(pu) Res. voltage(kv) Pre-insertion Resistance Fig. 7 The effect of pre-insertion resistance on overvoltage amplitude and voltage on pre-insertion resistor in steady state Res. Peak voltage(kv) Analyzing the curves in Fig. 7, the optimum pre-insertion resistor is 500 ohm which is equal to surge impedance of transmission line. In this case, pre-insertion resistor is called matching impedance. This matching impedance makes the switching surge to be half in the beginning of the transmission line and at the end it will be doubled. So, the amplitude will be the same as original switching surge and not more. As in Table III, the more resistance, the sooner the overvoltage transients damp which result in the decrement of insulation failure probability. It confirms that 500 ohm is the appropriate value for pre-insertion resistance. D. Effect of Transmission Line Parameters For a transmission line with definite length and definite tower geometry, the main and effective parameter which should be considered is the trapped charge on transmission line. To model the effect of trapped charge, the follow circuit is applied, Fig. 8. Fig. 9 Switching surge in the beginning (green curve) and at the end of transmission line (red curve), the transmission line has -1 p.u. trapped charge and line energized in 1 p.u. Energizing the line at the moment of zero voltage while line has -1 p.u. trapped charge has two forms, Fig. 10 and Fig. 11. First surge has more severe waveform in the case when voltage ascends after voltage zero, Fig. 10. The maximum overvoltage in both cases is 2.5 p.u. The last case which can be obtained by synchronous switching has the lowest overvoltages in the order of 1.5 p.u., Fig. 12. Thus, energizing the transmission line considering the equipotentiality of breaker terminals deduces the overvoltages to the acceptable margin. 21
5 III. LIGHTNING OVERVOLTAGES Fig. 10 The switching surge in the beginning (green curve) and at the end of transmission line (red curve), the transmission line has -1 p.u. trapped charge and line energized at the moment of zero potential and when the sinusoidal voltage curve goes up to 1 p.u. A. Lightning Modeling Sometimes, there is a necessity to connect over-head lines with cable systems. It mostly occurs in distribution networks. In special cases such as environmental requirements or limited space for overhead lines in densely populated areas, the usage of cable connection or GIL [12] is mandatory. As the overhead line and cable connection illustrated in Fig. 13, lightning may strike one phase of the overhead line and the overvoltage surge travels toward the cable. A surge arrester should be applied in the connection point to protect cable from overvoltages. By the way, simulations should be performed to notice about the possibility of the maximum overvoltage occurrence inside the cable and its amplitude. Fig. 13 Overhead line- Underground transition [7] A 100 kilometers transmission line, which has cable transition in the50 kilometer, is simulated in this paper, Fig 14. The transmission line has 132 kv rated line voltage and feeds a load of 50 MW, 50 MVAr at the end of the transmission line. The characteristics of the voltage source are brought in Table I. TABLE IV PARAMETERS OF THE VOLTAGE SOURCE Fig. 11 The switching surge in the beginning (green curve) and at the end of transmission line (red curve), the transmission line has -1 p.u. trapped charge and line energized at the moment of zero potential and when the sinusoidal voltage curve goes down to -1 p.u. source voltage (line voltage) frequency positive sequence resistance positive sequence inductance 132 kv 50 Hz Ω mh Fig. 15 depicts the dimensions of the transmission line towers and the conductor arrangements. C 1 is a side conductor and considered as phase A. As illustrated in simulation circuit, Fig. 14, the lightning surge strikes C 1. The specifications of the phase conductor and shield wire are given in Table II. TABLE V THE SPECIFICATIONS OF PHASE CONDUCTOR AND SHIELD WIRE phase conductor radius 0.02m phase conductor DC resistance ohms/km SAG for all conductors 10m ground wire radius m Fig. 12 The switching surge in the beginning (green curve) and at the end of transmission line (red curve), the transmission line has -1 p.u. trapped charge and line energized at -1 p.u. Ground wire DC resistance SAG for all ground wires Shunt conductance 2.865ohms/km 10m 1e-11 mhos/m 22
6 Fig. 14 The simulation circuit of the 100 kilometer transmission line with cable transition in middle. In order to obtain 1.2/50 µs lightning surge in PSCAD/EMTDC, parameter a in equation (9) is adjusted to 15500, in which the half time will be set to 50 µs. Parameter b is So, the rise time is 1.2 µs, the blue curve in Fig. 17. Fig. 15 Conductor arrangement of the transmission tower In PSCAD/EMTDC a frequency dependent phase model is applied for the transmission line and the underground cable. In this model, curve fitting start frequency is 0.5 Hz and curve fitting end frequency is 1 MHz. Maximum order of fitting for both Y shunt and propagation function is 20 with the maximum fitting error of 0.2%. The radius of different layers of underground cable is illustrated in Fig. 16. The underground cable is placed 1meter under the ground surface. In this model, lightning surge is modeled with a current source with the following equation: at bt I = I m ( e e ) (9) ) Fig. 16 Underground Cable Characteristics Fig. 17 Current waveform of lightning surge, I surge (blue curve), current of the point hit by lightning in phase A, I a (green curve) Analyzing the green curve and comparing it with the blue one, the addition of another surge to flowing lightning surge in phase A is obtainable. It emerges some ten microseconds after lightning surge injection. The time interval is around twice the time takes for surge to reach to cable connection. Therefore the time interval directly depends on the distance of stroke place to cable connection. After some 100 microseconds, another pulse can be observed in current waveform of stroke point. In fact, that s the reflection of lightning surge reached to the source. B. Simulation Results In the model delivered in Fig. 14, the overvoltage at the end of the second section of the transmission line and cable end is directly related to lightning current and distance of lightning strike from the cable. In Fig. 18, the overvoltage surges at different places along the transmission line are illustrated. It should be noted that the 23
7 waveforms of V cable and V load are multiplied by a scale factor of 10 in order to be in the same order of magnitude with V surge. Thus, the maximum surge amplitude on the load is limited to 2.5 p.u. For stroke place, a sharp deduction in voltage surge after some ten microseconds is observable. Simulating precisely the time interval which this phenomenon happened, the reflection of lightning surge from cable-transmission line connection can be comprehended as the cause for it. The moment which the reflected surge reaches the stroke point, the duplication in current surge and sharp decrease in voltage surge come about simultaneously, Fig. 19. Since the surge impedance of cable is one order of magnitude lower than that of transmission line and the overvoltage surge reflects again at the end of cable, the sharp decrease follows by a smooth increase in the voltage at the stroke point. For cables with longer length, the reflections inside cable are more obvious, Fig. 18 and Fig. 19. voltage surge on the load without or with applying surge arrester, respectively. Comparing these figures, one can obtain that the amplitude of overvoltages are deducted one order of magnitude and limited to 2 p.u. which is bearable for line insulators and load dielectrics. Although the application of surge arrester ensures insulation coordination for load and line insulators, the overvoltages inside cable and their severity should be seriously considered. Fig. 20 Maximum amplitude of voltage surge on the load without cable surge arresters in cable-line connection Fig. 18 V surge : Voltage surges in the stroke place (blue curve), V cable : Voltage surge at the beginning of cable (green curve) and V load : Voltage surge on the load (red curve) for Lightning strike with amplitude of 30 ka and 5 km distance from the cable. V cable and V load are multiplied by 10 Fig. 21 Maximum amplitude of voltage surge on the load with cable surge arresters in cable-line connection Fig. 19 I a : current of the point hit by lightning in phase A (blue curve). V surge : Voltage surges in the stroke place (green curve), V cable : Voltage surge at the beginning of cable (red curve) for Lightning strike with amplitude of 30 ka and 5 km distance from the cable. I a is multiplied by 450 and V cable is multiplied by 10 Fig. 22 and Fig. 23 depict the voltage surge at different points inside the cable while the lightning strike the line at 2km and 25 km to cable connection, respectively. The first voltage surge approaches 4 p.u. and even more instantaneously and have oscillatory waveform. The longer distance lightning strikes the transmission line, the closer are the first surge and the reflected surge from voltage source. Thus, overvoltage surge inside cable will be similar to square form with some oscillations, Fig. 23. Fig. 20 and Fig. 21 depict the maximum amplitude of 24
8 Fig. 22 V cable : Voltage surge at the beginning of cable (blue curve), V cableend : Voltage surge at the end of cable (red curve), V cablemid (green curve): Voltage surge inside cable at 50 m from cable beginning (a), 150 m from cable beginning (b), 250 m from cable beginning (c) and 350 m from cable beginning (d). The cable length is 420 meters. Lightning surge strikes the line at 2 kilometers to cable and its amplitude is 30 ka. Fig. 23 V cable : Voltage surge at the beginning of cable (blue curve), V cableend : Voltage surge at the end of cable (red curve), V cablemid (green curve): Voltage surge inside cable at 50 m from cable beginning (a), 150 m from cable beginning (b), 250 m from cable beginning (c) and 350 m from cable beginning (d). The cable length is 420 meters. Lightning surge strikes the line at 25 kilometers to cable and its amplitude is 30 ka. 25
9 IV. LIGHTNING OVERVOLTAGES Investigating switching overvoltages due to line energization, network short circuit impedance, pre-insertion resistors and the trapped charge of transmission line have the main effect on switching transients. The optimum preinsertion resistor obtained from simulation results, is called matching impedance which is equal to surge impedance of transmission line. The hazardous transients caused by energizing transmission line while line has opposite trapped charge presents the necessity of closing the breaker when its terminal is equipotential. The implementation of switch sync relays properly deduces the transient overvoltages. Investigating lightning overvoltages in overheadunderground transition, the effective application of surge arrester with V ref 120 kv is simulated in a 100 km 132 kv transmission line. The implementation of arresters in cableline transition points result in the one order of magnitude reduction of overvoltages comparing to having no arresters. The overvoltages restricted to 2 p.u. which is bearable for line insulators and load dielectrics. Although insulation coordination is fulfilled for transmission line and load by surge arresters, the overvoltages inside cable and their severity should be seriously considered which may approach 4. p.u. and even more instantaneously and have oscillatory waveform. REFERENCES [1] K. Ngamsanroaj and W. Tayati, An analysis of switching overvoltages in the EGAT 500 kv transmission system, in proc IEEE Conference on Power Engineering, pp [2] A. I. Ibrahim and H. W. Dommel, A Knowledge Base for Switching Surge Transients, in proc. Intr. Conf. on Power Systems Transients (IPST 05),Montreal, Canada, 2005, paper 50. [3] M. Sanaye-Pasand, M.R. Dadashzadeh and M. Khodayar, Limitation of transmission line switching overvoltages using switchsync relays, in proc. Intr. Conf. on Power Systems Transients (IPST 05), Montreal, Canada, 2005, paper 87. [4] "Controlled Switching Application Guide", Edition 1, ABB., [5] B. Gustavsen and A. Semlyen, Calculation Of Transmission Line Transients Using Polar Decomposition, IEEE Trans. on Power Delivery, vol. 13, pp , July [6] P.C. Magnusson, Traveling Waves on Multi-Conductor Open-Wire Lines-A Numerical Survey of the Effects of Frequency Dependence of Modal Composition, IEEE Trans. on Power Apparatus and systems, PAS-92, pp , May [7] T. Henriksen, B. Gustavsen, G. Balog, and U. Baur, Maximum Lightning Overvoltage along a Cable Protected by Surge Arresters, IEEE Trans. Power Delivery, vol. 20, pp , April [8] J. A. Martinez and F. Gonzalez-Molina, Surge protection of underground distribution cables, IEEE Trans. Power Delivery, vol. 15, pp , April [9] B. Gustavsen and J. Mahseredjian, Simulation of Internal Overvoltages on Transmission Lines by an Extended Method of Characteristics Approach, IEEE Trans. Power Delivery, vol. 22,pp , July [10] B. Gustavsen and A. Semlyen, Simulation of transmission line Transients using vector fitting and modal decomposition, IEEE Trans. Power Delivery, vol. 13, pp , April [11] H. Saadat, Power System Analysis, McGraw-Hill, 1999, pp [12] H,Koch and T.Hillers, Second generation gas-insulated line, IEEE Power Engineering Journal, vol.16, pp , Jun
Limitation of Transmission Line Switching Overvoltages using Switchsync Relays
Limitation of Transmission Line Switching Overvoltages using Switchsync Relays M. Sanaye-Pasand, M.R. Dadashzadeh, M. Khodayar Abstract-- When an overhead transmission line is energized by closing the
More informationMaximum Lightning Overvoltage along a Cable due to Shielding Failure
Maximum Lightning Overvoltage along a Cable due to Shielding Failure Thor Henriksen Abstract--This paper analyzes the maximum lightning overvoltage due to shielding failure along a cable inserted in an
More informationCapacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices
Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices M. Sanaye-Pasand, R. Aghazadeh Applied Electromagnetics Research Excellence Center, Electrical & Computer Engineering
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationAnalysis and Mitigation Techniques of Switching Overvoltages for A 500 kv Transmission Line
Vol. 7 (6) No.3, pp. 96-3 ISSN 78-365 Analysis and Mitigation Techniques of Switching Overvoltages for A 5 kv Transmission Line Ahmed S. Shafy *, Ahmed M.Emam**, Samy M. Ghania *, A. H. Hamza* *Electrical
More informationAnalysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP
IJSTE - International Journal of Science Technology & Engineering Volume 3 Issue 2 August 216 ISSN (online): 2349-784X Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP
More informationTransmission of Electrical Energy
Transmission of Electrical Energy Electrical energy is carries by conductors such as overhead transmission lines and underground cables. The conductors are usually aluminum cable steel reinforced (ACSR),
More informationSimulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models
International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:15 No:03 39 Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models Shen-Wen Hsiao, Shen-Jen
More informationEffect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers
Voltage (kv) Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Li-Ming Zhou, Senior Member, IEEE and Steven Boggs, Fellow, IEEE Abstract: The high frequency attenuation
More informationPower Quality and Reliablity Centre
Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview
More informationEffect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002 569 Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System Li-Ming Zhou, Senior Member, IEEE,
More informationPREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS
29 th International Conference on Lightning Protection 23 rd 26 th June 2008 Uppsala, Sweden PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS Ivo Uglešić Viktor Milardić Božidar
More informationSwitching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines
Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines F. Faria da Silva, Claus L. Bak, Per B. Holst Abstract--The disconnection of HV underground cables may, if unsuccessful, originate
More informationGIS Disconnector Switching Operation VFTO Study
GIS Disconnector Switching Operation VFTO Study Mariusz Stosur, Marcin Szewczyk, Wojciech Piasecki, Marek Florkowski, Marek Fulczyk ABB Corporate Research Center in Krakow Starowislna 13A, 31-038 Krakow,
More informationHigh voltage engineering
High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency
More informationModeling insulation in high-voltage substations
38 ABB REVIEW DESIGNED FOR SAFETY DESIGNED FOR SAFETY Modeling insulation in high-voltage substations The goal of insulation coordination is to determine the dielectric strength of transformers and other
More informationTab 2 Voltage Stresses Switching Transients
Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles
More informationSensitivity Analysis of Maximum Overvoltage on Cables with Considering Forward and Backward Waves
Sensitivity Analysis of Maximum Overvoltage on Cables with Considering Forward and Backward Waves Hamed Touhidi 1,Mehdi Shafiee 2, Behrooz Vahidi 3, Seyed Hossein Hosseinian 4 1 Islamic Azad University,
More informationIEEE Power Engineering Society 2001 Winter Meeting Columbus, OH. Panel Session. Data for Modeling System Transients
IEEE Power Engineering Society 2001 Winter Meeting Columbus, OH Panel Session Data for Modeling System Transients Parameters for Modeling Transmission Lines and Transformers in Transient Studies Bruce
More informationConventional Paper-II-2011 Part-1A
Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance
More informationSimulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP
Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP Kresimir Fekete 1, Srete Nikolovski 2, Goran Knezević 3, Marinko Stojkov 4, Zoran Kovač 5 # Power System Department,
More informationChapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two
Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead
More informationSWITCHING OVERVOLTAGES IN A 400-KV CABLE SYSTEM
SWITCHING OVERVOLTAGES IN A 4-KV CABLE SYSTEM Mustafa Kizilcay University of Siegen Siegen, Germany kizilcay@uni-siegen.de Abstract This paper deals with the computation of switching overvoltages in a
More informationTransmission Line Transient Overvoltages (Travelling Waves on Power Systems)
Transmission Line Transient Overvoltages (Travelling Waves on Power Systems) The establishment of a potential difference between the conductors of an overhead transmission line is accompanied by the production
More informationShunt Reactor Switching
Shunt Reactor Switching Dielectric stresses produced by circuit-breakers to shunt reactors. Presentation made during the IEEE Transformers Committee meeting, Amsterdam, Netherlands, April 2001 Presented
More informationMeasurements for validation of high voltage underground cable modelling
Measurements for validation of high voltage underground cable modelling Unnur Stella Gudmundsdottir, Claus Leth Bak, Wojciech T. Wiechowski, Kim Søgaard, Martin Randrup Knardrupgård Abstract-- This paper
More informationNeutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping
Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping P. Mestas, M. C. Tavares Abstract. The optimization of the grounding neutral reactor is a common practice
More informationTECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection
ECHNICAL NOE 2.0 Overvoltages origin and magnitudes Overvoltage protection he ECHNICAL NOES (N) are intended to be used in conjunction with the APPLICAION GIDELINES Overvoltage protection Metaloxide surge
More informationIdentification of network models parameters for simulating transients
Identification of network models parameters for simulating transients D. Cavallera, J-L. Coulomb, O. Chadebec, B. Caillault, F-X. Zgainski and A.Ayroulet Abstract In case of electrical black-out, one of
More informationElectric Stresses on Surge Arrester Insulation under Standard and
Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems
More information2. Current interruption transients
1 2. Current interruption transients For circuit breakers or other switching facilities, transient voltages just after the current interruptions are of great concern with successful current breakings,
More informationAnalysis of lightning performance of 132KV transmission line by application of surge arresters
Analysis of lightning performance of 132KV transmission line by application of surge arresters S. Mohajer yami *, A. Shayegani akmal, A.Mohseni, A.Majzoobi High Voltage Institute,Tehran University,Iran
More informationWhen surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS
TRANSFORMER IN GRID When surge arres t ers are installed close to a power transformer, they provide protection against lightning overvoltage ABSTRACT The aim of this research article is to determine the
More informationInsulation Co-ordination For HVDC Station
Insulation Co-ordination For HVDC Station Insulation Co-ordination Definitions As per IEC 60071 Insulation Coordination is defined as selection of dielectric strength of equipment in relation to the operating
More informationParameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning
Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 10), Cairo University, Egypt, December 19-21, 2010, Paper ID 111. Parameters Affecting the Back Flashover across the
More informationDIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY
DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY Dr. Karthik Reddy VENNA Hong URBANEK Nils ANGER Siemens AG Germany Siemens AG Germany Siemens AG Germany karthikreddy.venna@siemens.com
More informationRelevant Factors to a Statistical Analysis of Overvoltages - Application to Three-Phase Reclosing of Compensated Transmission Lines
Energy and Power Engineering, 2013, 5, 1165-1171 doi:10.4236/epe.2013.54b221 Published Online July 2013 (http://www.scirp.org/journal/epe) Relevant Factors to a Statistical Analysis of Overvoltages - Application
More informationLightning transient analysis in wind turbine blades
Downloaded from orbit.dtu.dk on: Aug 15, 2018 Lightning transient analysis in wind turbine blades Candela Garolera, Anna; Holbøll, Joachim; Madsen, Søren Find Published in: Proceedings of International
More informationEffects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages
Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Waruna Chandrasena, Bruno Bisewski, and Jeff Carrara Abstract-- This paper describes several system
More information2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2
ACTA UNIVERSITATIS APULENSIS Special Issue SIMULATION OF LIGHTNING OVERVOLTAGES WITH ATP-EMTP AND PSCAD/EMTDC Violeta Chiş, Cristina Băla and Mihaela-Daciana Crăciun Abstract. Currently, several offline
More informationANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM
ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM Anna Tjäder Chalmers University of Technology anna.tjader@chalmers.se Math Bollen Luleå University of Technology math.bollen@stri.se ABSTRACT Power
More informationABSTRACT 1 INTRODUCTION
ELECTROMAGNETIC ANALYSIS OF WIND TURBINE GROUNDING SYSTEMS Maria Lorentzou*, Ian Cotton**, Nikos Hatziargyriou*, Nick Jenkins** * National Technical University of Athens, 42 Patission Street, 1682 Athens,
More informationLightning performance of a HV/MV substation
Lightning performance of a HV/MV substation MAHMUD TAINBA, LAMBOS EKONOMOU Department of Electrical and Electronic Engineering City University London Northampton Square, London EC1V HB United Kingdom emails:
More informationDEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING YEAR / SEM : IV / VII UNIT I OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What
More informationCalculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation
Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation M. Kondalu1, Dr. P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. 1 Kondalu_m@yahoo.com
More informationA Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear
A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear Nguyen Nhat Nam Abstract The paper presents an simple model based on ATP-EMTP software to analyze very
More informationSimulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP
Simulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP Predrag Maric 1, Srete Nikolovski 1, Laszlo Prikler 2 Kneza Trpimira 2B 1 Faculty of
More informationIn power system, transients have bad impact on its
Analysis and Mitigation of Shunt Capacitor Bank Switching Transients on 132 kv Grid Station, Qasimabad Hyderabad SUNNY KATYARA*, ASHFAQUE AHMED HASHMANI**, AND BHAWANI SHANKAR CHOWDHRY*** RECEIVED ON 1811.2014
More informationA Study on Ferroresonance Mitigation Techniques for Power Transformer
A Study on Ferroresonance Mitigation Techniques for Power Transformer S. I. Kim, B. C. Sung, S. N. Kim, Y. C. Choi, H. J. Kim Abstract--This paper presents a comprehensive study on the ferroresonance mitigation
More informationSession Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages
Session Four: ractical Insulation Co-ordination Session Four: ractical Insulation Co-ordination for Lightning Induced Overvoltages Jason Mayer Technical Director, Energy Services, Aurecon Introduction
More informationExercises. 6 Exercises
6 Exercises The following five computer exercises accompany the course. Alternative Transients Program (ATP-EMTP) will be used to compute electrical transients. First electrical network should be created
More information5. Black box arc modelling
1 5. Black box arc modelling Circuit-breaker s performance in power system is analysed by representing the circuit-breaker characteristics by a function of electrical parameters such as current/voltage,
More informationDelayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines
Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,
More informationSwitching and Fault Transient Analysis of 765 kv Transmission Systems
Third International Conference on Power Systems, Kharagpur, INDIA December >Paper #< Switching and Transient Analysis of 6 kv Transmission Systems D Thukaram, SM IEEE, K Ravishankar, Rajendra Kumar A Department
More informationRelay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle
Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Jules Esztergalyos, Senior Member, IEEE Abstract--The measuring technique described in this paper is based on Electro Magnetic
More informationTransient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines
Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines Presenter Mark McVey C4/B5.41 INTERNATIONAL COUNCIL ON LARGE
More informationVFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES
VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES Shohreh Monshizadeh Islamic Azad University South Tehran Branch (IAU), Tehran,
More informationLumped Network Model of a Resistive Type High T c fault current limiter for transient investigations
Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations Ricard Petranovic and Amir M. Miri Universität Karlsruhe, Institut für Elektroenergiesysteme und Hochspannungstechnik,
More informationModeling and Analysis of a 3-Phase 132kv Gas Insulated Substation
Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation M. Kondalu1, Dr. P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering College,
More informationStudy of Tower Grounding Resistance Effected Back Flashover to 500 kv Transmission Line in Thailand by using ATP/EMTP
Study of Tower Grounding Resistance Effected Back Flashover to 500 kv Transmission Line in Thailand by using ATP/EMTP B. Marungsri, S. Boonpoke, A. Rawangpai, A. Oonsivilai, and C. Kritayakornupong Abstract
More informationInvestigation of Inter-turn Fault in Transformer Winding under Impulse Excitation
Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation P.S.Diwakar High voltage Engineering National Engineering College Kovilpatti, Tamilnadu, India S.Sankarakumar Department
More informationANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION
ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION R.Rahnavard 1, 2 M.Valizadeh 1 A.A.B.Sharifian 2 S.H.Hosseini 1 rerahnavard@gmail.com mj_valizad@yahoo.com hosseini@tabrizu.ac.ir
More informationLightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System
Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System A. Phayomhom and S. Sirisumrannukul Abstract This paper presents the guidelines for preparing
More informationSimulation of line fault locator on HVDC Light electrode line
August 10, 2010 Simulation of line fault locator on HVDC Light electrode line Andreas Hermansson BACHELOR S THESIS Electrical Engineering, Electric Power Technology Department of Engineering Science BACHELOR
More informationEE 740 Transmission Lines
EE 740 Transmission Lines 1 High Voltage Power Lines (overhead) Common voltages in north America: 138, 230, 345, 500, 765 kv Bundled conductors are used in extra-high voltage lines Stranded instead of
More informationA Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks
A Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks C. D. TSIREKIS Hellenic Transmission System Operator Kastoros 72, Piraeus GREECE
More informationSolving Customer Power Quality Problems Due to Voltage Magnification
PE-384-PWRD-0-11-1997 Solving Customer Power Quality Problems Due to Voltage Magnification R. A. Adams, Senior Member S. W. Middlekauff, Member Duke Power Company Charlotte, NC 28201 USA E. H. Camm, Member
More informationInvestigation into Transient SFO, FFO, VFTO Overvoltage Characteristics for Typical Gas Insulated Substations
nvestigation into Transient SFO, FFO, VFTO Overvoltage Characteristics for Typical Gas nsulated Substations L. Czumbil, J. Kim, H. Nouri Abstract--Overvoltage characteristics of typical single bus, double
More informationCHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS
84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial
More informationCalculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS
Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering
More informationTab 8 Surge Arresters
s en em Tab 8 Surge Arresters Si Distribution System Engineering Course Unit 10 2017 Industry Inc., All Rights Reserved Surge Arresters The main protective devices against system transient overvoltages.
More informationEE 340 Transmission Lines
EE 340 Transmission Lines Physical Characteristics Overhead lines An overhead transmission line usually consists of three conductors or bundles of conductors containing the three phases of the power system.
More informationLIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION
LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION Andreas SUMPER sumper@citcea.upc.es Antoni SUDRIÀ sudria@citcea.upc.es Samuel GALCERAN galceran@citcea.upc.es Joan RULL rull@citcea.upc.es
More informationResearch Article Survey of Induced Voltage and Current Phenomena in GIS Substation
Research Journal of pplied Sciences, Engineering and Technology 7(9): 179733, 14 DOI:1.196/rjaset.7.456 ISSN: 4-7459; e-issn: 4-7467 14 Maxwell Scientific Publication Corp. Submitted: February 7, 17 ccepted:
More informationChapter 1. Overvoltage Surges and their Effects
Chapter 1 Overvoltage Surges and their Effects 1.1 Introduction Power equipment are often exposed to short duration impulse voltages of high amplitude produced by lightning or switching transients. These
More informationTravelling Wave Based DC Line Fault Location in VSC HVDC Systems
M.Sc. Thesis Presentation Travelling Wave Based DC Line Fault Location in VSC HVDC Systems K.P.A.N. Pathirana Department of ECE University of Manitoba Canada. Outline Introduction Surge detection method
More informationG. KOEPPL Koeppl Power Experts Switzerland
PS3: Substation Design: New Solutions and Experiences Bus-Node Substation A Big Improvement in Short-Circuit and Switching Properties at Reduced Substation Costs G. KOEPPL Koeppl Power Experts Switzerland
More informationROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING
ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR 621 212 DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING EE1003 HIGH VOLTAGE ENGINEERING QUESTION BANK UNIT-I OVER VOLTAGES IN ELECTRICAL POWER SYSTEM
More informationModeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning
Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning M. PSALIDAS, D. AGORIS, E. PYRGIOTI, C. KARAGIAΝNOPOULOS High Voltage Laboratory,
More informationTransient Analysis and Mitigation of Capacitor Bank Switching on a Standalone Wind Farm
ol:1, No:4, 216 Transient Analysis and Mitigation of Capacitor Bank Switching on a Standalone Wind Farm Ajibola O. Akinrinde, Andrew Swanson, Remy Tiako Digital Open Science Index, Electrical and Computer
More informationElectromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching
International Conference on Power Systems Transients IPST 3 in New Orleans, USA Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching Ivo Uglesic
More informationPublished in: Proceedings of the International Conference on Power Systems Transients (IPST 2009)
Aalborg Universitet Measurements for validation of high voltage underground cable modelling Bak, Claus Leth; Gudmundsdottir, Unnur Stella; Wiechowski, Wojciech Tomasz; Søgaard, Kim; Knardrupgård, Martin
More informationSURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES
SURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES Jae-bong LEE, Korea Electric Power Research Institute(KEPRI), (Korea), jbonglee@kepco.co.kr Ju-yong KIM, Korea Electric Power Research
More informationSimplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers
Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 1), Cairo University, Egypt, December 19-1, 1, Paper ID 1. Simplified Approach to Calculate the Back Flashover Voltage
More informationA Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables
J Electr Eng Technol Vol. 9, No. 2: 628-634, 2014 http://dx.doi.org/10.5370/jeet.2014.9.2.628 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 A Study on Lightning Overvoltage Characteristics of Grounding
More informationLightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise
Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise S. Sekioka, K. Aiba, S. Okabe Abstract-- The lightning overvoltages incoming from an overhead line such as a power distribution
More informationEE 340 Transmission Lines. Spring 2012
EE 340 Transmission Lines Spring 2012 Physical Characteristics Overhead lines An overhead transmission line usually consists of three conductors or bundles of conductors containing the three phases of
More informationAbstract. 1 Introduction
Energy Production and Management in the 21st Century, Vol. 1 345 Investigation of the electrical strength of a contact gap of the high voltage live tank circuit breaker 126 kv class using an intelligent
More informationConsidering Characteristics of Arc on Travelling Wave Fault Location Algorithm for the Transmission Lines without Using Line Parameters
Considering Characteristics of Arc on Travelling Wave Fault Location Algorithm for the Transmission Lines without Using Line Parameters M. Bashir mohsenbashir@ieee.org I. Niazy ismail_niazy@ieee.org J.
More informationSYSTEM STUDIES for HVDC
INTRODUCTION The design of HVDC requires Careful study coordination, which must be achieved in compliance with the Owner s requirements. To achieve these objectives, number of highly interactive system
More informationAdi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN
Effectiveness of Surge Capacitors on Transformer Tertiary connected shunt reactors in preventing failures- Field measurements and comparison with Transient study results Pratap G. Mysore, P.E Pratap Consulting
More informationPower Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer
Power Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer C.GOPI*, M.KISHOR** *(Department. of Electrical and Electronics Engineering, SVPCET, Puttur)
More informationStatistical analysis of overvoltages due to the energisation of a 132 kv underground cable
University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part A Faculty of Engineering and Information Sciences 2009 Statistical analysis of overvoltages due to
More informationAccurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 4, OCTOBER 2002 969 Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies Taku Noda, Member, IEEE, Hiroshi Nakamoto,
More informationSimulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines
7th Asia-Pacific International Conference on Lightning, November 1-4, 2011, Chengdu, China Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines Zihui Zhao, Dong Dang,
More informationEffect of Shielded Distribution Cable on Very Fast Transients
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000 857 Effect of Shielded Distribution Cable on Very Fast Transients Li-Ming Zhou and Steven Boggs, Fellow, IEEE Abstract Fast transients in
More informationGreat Northern Transmission Line: Behind the (Electrical) Design
Great Northern Transmission Line: Behind the (Electrical) Design November 8, 2017 Christian Winter, P.E. Minnesota Power Sivasis Panigrahi, P.E. POWER Engineers, Inc. What is the Great Northern Transmission
More informationANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES
ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES Authors: Joe Perez, P.E.: SynchroGrid, College Station, Texas Hung Ming Chou, SynchroGrid, College Station, Texas Mike McMillan, Bryan
More informationEXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT
EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT Akihiro AMETANI, Tomomi OKUMURA, Naoto NAGAOKA, Nobutaka, MORI Doshisha University - Japan
More informationCAPACITORS are commonly found in distribution
1 Mitigation of Back-to-Back Capacitor Switching Transients on Distribution Circuits M.F. Iizarry-Silvestrini, PREPA T. E. Vélez-Sepúlveda, PREPA Abstract-- In this paper we evaluate three technologies
More information