OVERVOLTAGE MEASUREMENTS RELATED TO LIGHTNING- DETECTION SYSTEMS IN NORWAY

Size: px
Start display at page:

Download "OVERVOLTAGE MEASUREMENTS RELATED TO LIGHTNING- DETECTION SYSTEMS IN NORWAY"

Transcription

1 3p.3 OVERVOTAGE MEASUREMENTS REATED TO IGHTNING- DETECTION SYSTEMS IN NORWAY H. K. Høidalen F. Dahlslett Norwegian University of Science and Technology Norway SINTEF Energy Research Norway Abstract: The paper presents measurement of lightning induced voltages in a real low-voltage system (isolated neutral) in Norway. The measurements are compared with calculations based on lightning location system data (position and signal strength) showing reasonable agreement for ground conductivity.1 S/m. However, the unknown grounding conditions in the system plays a very important role. 182 lightning strokes were registered within 1 km from the measurement site during the summer of 21. For 12 of these, induced voltages above 5 V were measured. Keywords: Induced voltages, lightning location, measurements, calculations, ground conductivity. 1. INTRODUCTION Power quality has become a key quantity for Norwegian electric power utilities. The demand of stable and reliable energy supply is continuously growing. In addition, the regulator fines power outages above 3 minutes with up to 5 NKr/kWh. ightning is a major cause of power quality disturbances (voltage dips, surges, interruptions etc.). In Norway a larger project at SINTEF Energy Research has used PQNode instruments to compare power quality measurements with lightning data [1,2]. However, the sampling frequency and the clock precision were found insufficient. As a result a new PCbased instrumentation was developed and tested in the summer of 21, following the ideas in [3]. Modern ightning ocation Systems (S) [4] may provide extensive data on the lightning exposure of power systems. By combining such data with efficient system computation models and tools it should be possible to estimate the impacts of lightning on the power quality of a local power system, also taking the actual power system configuration into account. The possibility to reach this rather ambitious goal is mainly limited by: The detection efficiency and location accuracy of the lightning location system and peak current estimate. The availability of an efficient computation model for induced lightning surges The complexity of the power system, including the loads (and their representation) in the low-voltage system. The transformer modelling and the handling of attenuation effects in the system are particularly important and critical. As a second step towards the ambitious goal, calculations based on S-data from the year 21 are compared with measurements. The same system as in [2] is used. 2. INSTRUMENTATION The lightning-induced voltages are measured with passive high-voltage probes (1:1) with a 15 MHz bandwidth. The common grounding point is taken from a wall-mounted isolated conductor connected to a small grounding rod. The voltage probes are further connected to buffer circuits with bandwidth 7 MHz and located in an outdoor metal cabinet. The buffer circuits supply the coaxial cables (RG58) to an indoor PC. Figure 1 shows the setup of the instrumentation. A plate antenna for measurements of the vertical electrical field is also mounted on the wall, unfortunately too close to the power line. The signal from the antenna is also connected to a buffer and integrated so that the output signal is proportional to 1 kv/m with 1 volt positive offset error.

2 ICP 22 Cracow, Poland September 2-6, The instrumentation is based on a data acquisition card in a PC. This card samples 4 channels continuously with sampling time of 1 MS/s and a 12 bit vertical resolution. The card uses the analogue trigger on channel 1 with a fixed trigger level of.5 volts. The pretrigger time is set to the maximum value 3.2 ms. A computer program based on abwindows is developed to control the cards and store the data after each triggering. The total length of the recorded event is microseconds (this gives a 512 kb binary disk file). The data card is ready to record a new event almost immediately, but the dead time between the second and the third event is about 1.5 seconds. Plate antenna overhead line Fig. 1. Measurement setup. Connection of voltage probes, vertical antenna and buffer. Node 1 in figure 2. The PC is also equipped and clock synchronised with an accurate GPS card. Due to problems with the digital trigger circuit it was not possible to find the exact time for the lightning event. Instead the GPS time was read just after the signal was recorded but before saving it to disk. This made is possible to identify and correlate the measured event to the lightning location data. 3. CACUATIONS 1:1 probes Cabinet for buffer circuits The calculations are based on the analytical approach from Rusck [5], modified to handle linear rising and falling lightning currents and finite line lengths. Besides, the lossy ground effect on the radial electrical field propagation is modelled with the Cooray-Rubinstein approximation [6,7]. The coupling between the electrical field and the overhead line(s) is modelled with the Agrawal model [8]. The induced voltages are calculated as outlined in [2, 9]. The main assumptions in this method are: The lightning channel is straight and vertical. The return stroke current propagates unattenuated upward with a constant velocity, v (T model). The shape of the lightning current is linear in time. Only the field from the return stroke is considered. The earth is homogenous with constant conductivity and permittivity. The overhead line is considered to be lossless. The lossy ground effect on the horizontal field is handled. Symmetry in connected electrical terminations (loads) is assumed and only the common mode system is studied. An analytical formulation of a two-phase overhead line from (x A, y A ) to (x B, y AB ) exposed by a lightning stroke in (x, y ) is implemented in the MODES language in ATP [1, 11]. The low-voltage network where the measurements and calculations are performed is shown in fig. 2. It consists of about 2.5 km of overhead line that mostly is performed as compact 2 or 3 phase XPE covered conductors. There is no neutral or ground wire in the system, which is typical for the Norwegian countryside. There are also no protective devices in the system (-14,36) 2 5 T 6 2 (-4,2) (, ) 4 (75,-7) -2 Cu High voltage lines -4 N Ex -6 1 (-255,-72) E , Fig. 2. System configuration. Some simplifications are made on the northern part where 3 subscribers are connected. : subscribers installation (load), T: transformer. Units in meters. Solid line: low-voltage system (23V-IT), dotted line: high voltage overhead line (24 kv). Ex: 3-phase XPE covered compact line (one phase is open) from the HV line. Cu: 2-phase cu-line. The squares in fig. 2 marked with are loads connected to the system. The loads are modelled as shown in fig. 3 with a capacitor of 1 nf in series with a

3 222 26th International Conference on ightning Protection

4 ICP 22 Cracow, Poland September 2-6, , 5-5 lossless.1 S/m.1 S/m measured , -2 lossless.1 S/m.1 S/m measured -1, Fig. 6. Measured and calculated return-stroke induced voltages for lightning 467_1 (21-7, 12:4:57.52). Distance 97 m, peak current estimate: -47 ka lossless.1 S/m.1 S/m measured Fig. 7. Measured and calculated return-stroke induced voltages for lightning 467_2 (21-7, 12:4:57.54). Distance 936 m, peak current estimate: -12 ka Fig. 8. Measured and calculated return-stroke induced voltages for lightning 468_1 (21-7, 12:42:45.15). Distance 464 m, peak current estimate: -4 ka lossless.1 S/m.1 S/m measured Fig. 9. Measured and calculated return-stroke induced voltages for lightning 468_2 (21-7, 12:42:45.2). Distance 334 m, peak current estimate: -3 ka.

5 224 26th International Conference on ightning Protection lossless.1 S/m.1 S/m measured Fig. 1. Measured and calculated return-stroke induced voltages for lightning 469 (21-7, 12:5:19.31). Distance 386 m, peak current estimate: -1 ka. Both the strokes 467_1 and 469 result in a strange measured signal both in front of and after the return stroke as shown in fig. 11 for lightning 469. The same phenomenon was measured in the electrical field, except for the AC component and the increasing DC-component. Induced voltage [kv], phase R time [ms] Figure 11. Measured induced voltage on a millisecond scale. The voltage consists of the normal 5 Hz component with amplitude 23/ 3 volts, an initial high frequency signal 1, the induced voltage from the return stroke 2 (shown in fig. 1), a positive part after the return stroke 3, an increasing DC component 4. Around 21 ms a subsequent event is registered, but this is not reported by the lightning detection system. 5. DISCUSSION Figure 6-1 all show that reasonable agreement between measurements and calculations is obtained for a 4 ground conductivity s=.1 S/m. The correct sign of the induced voltage is predicted and in the correct order of magnitude. These comparisons must be regarded as a very good match when all the uncertainties (current amplitude/velocity/shape, low-voltage loads, grounding etc.) are kept in mind. A calculation assuming a lossless ground would have given completely wrong results. The grounding condition plays a very important role, however, and has a strong influence both on the steepness and the amplitude of the induced voltage. It is not obvious how to handle the down-conductor and the connection to ground in order the measure the real stresses on a low-voltage installation. All the five events are at a rather long distance (3-9 km) and the resulting overvoltages are moderate. It is likely that no flashover occurred in the system, even if fig. 6 and 1 indicate a strange behaviour at the front. In these two cases a maximum calculated voltages of 1.79 kv and 1.18 kv (+ AC component) respectively will occur at node 4 (far end, ref. fig. 2). The oscillatory behaviour did not occur in fig. 7 where the difference from fig. 6 is the current amplitude only. A similar but not so dominant oscillation is shown in fig. 12. Induced voltage [kv] Phase R Fig. 12. Measured induced voltage, lightning 43 (12-7, 16:1:9.21) km right east, peak current amplitude 59 ka. The measurements for lightning 467_1 and 469 both include a signal with a very high frequency content in front of the return stroke. The source of this could be a preliminary cloud discharge or an inter-cloud lightning. ightning stroke 469 resulted in a high increasing "DC-component" as shown in fig. 11. This could be due to a continuous lightning current. Stroke 467_1 and 467_2 showed a more moderate DC-component, while stroke 468 had no such component at all. The system in

6 ICP 22 Cracow, Poland September 2-6, fig. 2 is not grounded so even a leader or cloud charge could introduce such a DC component. The positive part after the return stroke, indicated with symbol 3 in fig. 11 is difficult to explain by the authors. The induced voltage shown in fig. 12 shows also a positive second peak, but with a shorter duration than for lightning 467_1 and 469. The 3 rd open conductor in the compact XPE insulate overhead line obtains approximately the same induced voltages as the other two energised phases, which means that the coupling between the conductors is large. The vertical electrical field measured by the plate antenna was proportional to the induced voltage. This indicates that the antenna was located too close to the phase conductors and was influence strongly by them. The sample frequency of 1 MS/s is a bit low to get reliable results for the high frequency part in fig. 11 and for the oscillatory front event in fig. 6 and 1. However, it is sufficient to get an overview of the event and is a good compromise between return stroke effects and the total lightning flash effects. In several occasions the record length is sufficient to include subsequent events, like 467_1 and 467_2, reported as two individual strokes by the S. The exact timing of the measurements needs to be improved. Now the time is read from the GPS card after recording the data. The normal time delay is 55 ms, but is for a subsequent event some seconds due to the disk writing process. This time deviation is no problem for identifying the actual lightning stroke, but the time stamp has no value in verifying the lightning location system. The timing can be improved to 1 ms precision by introducing a common digital trigger for the DAQ and the GPS cards. Besides 12 recorded lightning-induced voltages coinciding with S-data, over 1 other events of voltages above 5 V (in the 23 V system) where recorded. These are a mixture of distant- and cloudlightning, and switching overvoltages. 6. CONCUSIONS In order to relate damages/fires and power quality to S-data, advanced models for calculating lightninginduced voltages must be developed and verified by measurements. The paper presents measurement of lightning induced voltages in a real low-voltage system (isolated neutral) in Norway. The measurements are compared with calculations based on lightning location system data (position and signal strength) showing reasonable agreement for ground conductivity.1 S/m. However, the unknown grounding conditions in the system plays a very important role. 182 lightning strokes were registered within 1 km from the measurement site during the summer of 21. For 12 of these, induced voltages above 5 V were measured. 7. REFERENCES [1] H. Seljeseth, O. Rokseth, J. Huse, F. Dahlslett: ightning impact on power quality preliminary investigations in Norway. Proc. Int. conf. on Electric Power Quality and Supply Reliability, june 9-12, 1999 Estonia. [2] H.K. Høidalen, J. Huse, F. Dahlslett, T. Aalborg: "Impacts of lightning-induced overvoltages on power quality in low-voltage distribution systems", Proc. ICP, pp , Rhodes-Greece, Sept. 2. [3] H. Torres, et.al.: "ightning induced voltages measured in a high lightning activity zone and its comparison with theoretical values", Proc. ICP, pp , Rhodes-Greece, Sept. 2. [4] F. Dahlslett, A. Pleym, O. Rokseth, K. Solberg: "Analysis of the collected data ( ) from the Norwegian lightning location system", Proc. ICP'22. [5] S. Rusck, Induced lightning over-voltages on power-transmission lines with special reference to the over-voltage protection of low-voltage networks, Royal Institute of Technology, PhD Thesis, Stockholm, Sweden, [6] M. Rubinstein, An approximate formula for the calculation of horizontal electric field from lightning at close, intermediate, and long range, IEEE Trans. on EMC, vol. 38, No. 3, pp , Aug [7] C.A. Nucci, Cigré 33.1: "ightning-induced voltages on overhead power lines", Part I: Electra, No. 161, pp , Aug Part II: Electra, No. 162, pp , Oct [8] A.K. Agrawal, H.J. Price, S. Gurbaxani, "Transient respons of multiconductor transmission lines excited by a nonuniform electromagnetic field". IEEE trans. on EMC, Vol. 22, No. 2, May 198, pp [9] H.K. Høidalen: ightning-induced overvoltages in low-voltage systems, PhD Thesis, The Norwegian University of Science and Technology, ISBN [1]. Dubè, I. Bonfanti, "MODES: A new simulation tool in the EMTP". European Trans. on Electric Power, vol. 2, no. 1, pp.45-5, Jan./Feb [11] Alternative Transient Program (ATP) RuleBook, Canadian/American EMTP User Group, [12] H.K. Høidalen, ightning-induced voltages in lowvoltage systems and its dependency on overhead line termination, ICP 98, paper 3a.8, Sept., 1998, Birmingham-UK.

An Approximate Formula for Estimating the Peak Value of Lightning-Induced Overvoltage Considering the Stratified Conducting Ground

An Approximate Formula for Estimating the Peak Value of Lightning-Induced Overvoltage Considering the Stratified Conducting Ground IEEE TRANSACTIONS ON POWER DELIVERY 1 An Approximate Formula for Estimating the Peak Value of Lightning-Induced Overvoltage Considering the Stratified Conducting Ground Qilin Zhang, Member, IEEE, Liang

More information

Comparison of Two Computational Programs for the Calculation of Lightning-Induced Voltages on Distribution Systems

Comparison of Two Computational Programs for the Calculation of Lightning-Induced Voltages on Distribution Systems Comparison of Two Computational Programs for the Calculation of Lightning-Induced Voltages on Distribution Systems M. Paolone, E. Perez, A. Borghetti, C.A. Nucci, F. Rachidi and H. Torres Abstract Lightning-induced

More information

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning M. PSALIDAS, D. AGORIS, E. PYRGIOTI, C. KARAGIAΝNOPOULOS High Voltage Laboratory,

More information

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 1), Cairo University, Egypt, December 19-1, 1, Paper ID 1. Simplified Approach to Calculate the Back Flashover Voltage

More information

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002 569 Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System Li-Ming Zhou, Senior Member, IEEE,

More information

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line NATIONAL POWER SYSTEMS CONFERENCE NPSC22 563 Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line P. Durai Kannu and M. Joy Thomas Abstract This paper analyses the voltages

More information

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

Maximum Lightning Overvoltage along a Cable due to Shielding Failure Maximum Lightning Overvoltage along a Cable due to Shielding Failure Thor Henriksen Abstract--This paper analyzes the maximum lightning overvoltage due to shielding failure along a cable inserted in an

More information

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION Andreas SUMPER sumper@citcea.upc.es Antoni SUDRIÀ sudria@citcea.upc.es Samuel GALCERAN galceran@citcea.upc.es Joan RULL rull@citcea.upc.es

More information

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise S. Sekioka, K. Aiba, S. Okabe Abstract-- The lightning overvoltages incoming from an overhead line such as a power distribution

More information

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 10), Cairo University, Egypt, December 19-21, 2010, Paper ID 111. Parameters Affecting the Back Flashover across the

More information

Paper presented at the Int. Lightning Detection Conference, Tucson, Nov. 1996

Paper presented at the Int. Lightning Detection Conference, Tucson, Nov. 1996 Paper presented at the Int. Lightning Detection Conference, Tucson, Nov. 1996 Detection Efficiency and Site Errors of Lightning Location Systems Schulz W. Diendorfer G. Austrian Lightning Detection and

More information

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT Akihiro AMETANI, Tomomi OKUMURA, Naoto NAGAOKA, Nobutaka, MORI Doshisha University - Japan

More information

Power Quality and Reliablity Centre

Power Quality and Reliablity Centre Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview

More information

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2 ACTA UNIVERSITATIS APULENSIS Special Issue SIMULATION OF LIGHTNING OVERVOLTAGES WITH ATP-EMTP AND PSCAD/EMTDC Violeta Chiş, Cristina Băla and Mihaela-Daciana Crăciun Abstract. Currently, several offline

More information

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP IJSTE - International Journal of Science Technology & Engineering Volume 3 Issue 2 August 216 ISSN (online): 2349-784X Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

More information

High voltage engineering

High voltage engineering High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency

More information

The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line.

The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line. The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line. J.O. Adepitan, Ph.D. 1 and Prof. E.O. Oladiran 2 1 Department of Physics and

More information

X International Symposium on Lightning Protection

X International Symposium on Lightning Protection X International Symposium on Lightning Protection 9 th -13 th November, 2009 Curitiba, Brazil LIGHTNING SURGES TRANSFERRED TO THE SECONDARY OF DISTRIBUTION TRANSFORMERS DUE TO DIRECT STRIKES ON MV LINES,

More information

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS 29 th International Conference on Lightning Protection 23 rd 26 th June 2008 Uppsala, Sweden PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS Ivo Uglešić Viktor Milardić Božidar

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Voltage (kv) Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Li-Ming Zhou, Senior Member, IEEE and Steven Boggs, Fellow, IEEE Abstract: The high frequency attenuation

More information

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems) Transmission Line Transient Overvoltages (Travelling Waves on Power Systems) The establishment of a potential difference between the conductors of an overhead transmission line is accompanied by the production

More information

Close and Distant Electric Fields due to Lightning Attaching to the Gaisberg Tower

Close and Distant Electric Fields due to Lightning Attaching to the Gaisberg Tower 4 th International Symposium on Winter Lightning (ISWL2017) Close and Distant Electric Fields due to Lightning Attaching to the Gaisberg Tower Naomi Watanabe 1, Amitabh Nag 1, Gerhard Diendorfer 2, Hannes

More information

ABSTRACTS of SESSION 6

ABSTRACTS of SESSION 6 ABSTRACTS of SESSION 6 Paper n 1 Lightning protection of overhead 35 kv lines by antenna-module long flashover arresters Abstract: A long-flashover arrester (LFA) of a new antenna-module type is suggested

More information

Chapter 1. Overvoltage Surges and their Effects

Chapter 1. Overvoltage Surges and their Effects Chapter 1 Overvoltage Surges and their Effects 1.1 Introduction Power equipment are often exposed to short duration impulse voltages of high amplitude produced by lightning or switching transients. These

More information

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Analysis of lightning performance of 132KV transmission line by application of surge arresters Analysis of lightning performance of 132KV transmission line by application of surge arresters S. Mohajer yami *, A. Shayegani akmal, A.Mohseni, A.Majzoobi High Voltage Institute,Tehran University,Iran

More information

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS TRANSFORMER IN GRID When surge arres t ers are installed close to a power transformer, they provide protection against lightning overvoltage ABSTRACT The aim of this research article is to determine the

More information

GIS Disconnector Switching Operation VFTO Study

GIS Disconnector Switching Operation VFTO Study GIS Disconnector Switching Operation VFTO Study Mariusz Stosur, Marcin Szewczyk, Wojciech Piasecki, Marek Florkowski, Marek Fulczyk ABB Corporate Research Center in Krakow Starowislna 13A, 31-038 Krakow,

More information

EVALUATION OF LIGHTNING-INDUCED VOLTAGES ON LOW-VOLTAGE DISTRIBUTION NETWORKS

EVALUATION OF LIGHTNING-INDUCED VOLTAGES ON LOW-VOLTAGE DISTRIBUTION NETWORKS IX International Symposium on Lightning Protection 6 th - th November 7 Foz do Iguaçu, Brazil EVALUATION OF LIGHTNING-INDUCED VOLTAGES ON LOW-VOLTAGE DISTRIBUTION NETWORKS Fernando H. Silveira Silvério

More information

Measurements for validation of high voltage underground cable modelling

Measurements for validation of high voltage underground cable modelling Measurements for validation of high voltage underground cable modelling Unnur Stella Gudmundsdottir, Claus Leth Bak, Wojciech T. Wiechowski, Kim Søgaard, Martin Randrup Knardrupgård Abstract-- This paper

More information

Investigation on the Performance of Different Lightning Protection System Designs

Investigation on the Performance of Different Lightning Protection System Designs IX- Investigation on the Performance of Different Lightning Protection System Designs Nicholaos Kokkinos, ELEMKO SA, Ian Cotton, University of Manchester Abstract-- In this paper different lightning protection

More information

Transient calibration of electric field sensors

Transient calibration of electric field sensors Transient calibration of electric field sensors M D Judd University of Strathclyde Glasgow, UK Abstract An electric field sensor calibration system that operates in the time-domain is described and its

More information

ARTICLE IN PRESS. Lightning effects in the vicinity of elevated structures. F.H. Silveira, S. Visacro

ARTICLE IN PRESS. Lightning effects in the vicinity of elevated structures. F.H. Silveira, S. Visacro 8:0f=WðJul62004Þ þ model ELSTAT : 20 Prod:Type:FTP pp:28ðcol:fig::nilþ ED:SumalathaP:N: PAGN:TNN SCAN: Journal of Electrostatics ] (]]]]) ]]] ]]] www.elsevier.com/locate/elstat Lightning effects in the

More information

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables J Electr Eng Technol Vol. 9, No. 2: 628-634, 2014 http://dx.doi.org/10.5370/jeet.2014.9.2.628 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 A Study on Lightning Overvoltage Characteristics of Grounding

More information

Accuracy of Lightning Surge Analysis of Tower Surge Response

Accuracy of Lightning Surge Analysis of Tower Surge Response Accuracy of ightning Surge Analysis of Tower Surge esponse Naoki Itamoto, Hironao Kawamura, Kazuo Shinjo, Hideki Motoyama, Masaru Ishii Abstract--This paper presents a comparison between the measured and

More information

FDTD Analysis of Distribution Line Voltages Induced by Inclined Lightning Channel

FDTD Analysis of Distribution Line Voltages Induced by Inclined Lightning Channel FDTD Analysis of Distribution Line Voltages Induced by Inclined Lightning Channel Masashi Natsui, Akihiro Ametani, Jean Mahseredjian, Shozo Sekioka, Kazuo Yamamoto Abstract--This paper investigates lightning

More information

Earthing of Electrical Devices and Safety

Earthing of Electrical Devices and Safety Earthing of Electrical Devices and Safety JOŽE PIHLER Faculty of Electrical Engineering and Computer Sciences University of Maribor Smetanova 17, 2000 Maribor SLOVENIA joze.pihler@um.si Abstract: - This

More information

Modeling insulation in high-voltage substations

Modeling insulation in high-voltage substations 38 ABB REVIEW DESIGNED FOR SAFETY DESIGNED FOR SAFETY Modeling insulation in high-voltage substations The goal of insulation coordination is to determine the dielectric strength of transformers and other

More information

Exercises. 6 Exercises

Exercises. 6 Exercises 6 Exercises The following five computer exercises accompany the course. Alternative Transients Program (ATP-EMTP) will be used to compute electrical transients. First electrical network should be created

More information

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces 1 Prediction of Transient Transfer Functions at Cable-Transformer Interfaces Joe Y. Zhou, Member, IEEE and Steven A. Boggs, Fellow, IEEE Joe Zhou participated in this work while completing his Ph.D. at

More information

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System A. Phayomhom and S. Sirisumrannukul Abstract This paper presents the guidelines for preparing

More information

Fig.1. Railway signal system

Fig.1. Railway signal system 2 2016 International Conference on Lightning Protection (ICLP), Estoril, Portugal Induced Surges in Railway Signaling Systems during an Indirect Lightning Strike Ruihan Qi*, Binghao Li and Y. Du Dept.

More information

In order to minimise distribution (11 and 22 kv) feeder breaker

In order to minimise distribution (11 and 22 kv) feeder breaker Lightning protection for equipment on MV feeders By WJD van Schalkwyk and M du Preez, Eskom This article presents the influence of lightning on MV feeders supplying small power users (400/230 V) with focus

More information

Power Quality Measurements the Importance of Traceable Calibration

Power Quality Measurements the Importance of Traceable Calibration Power Quality Measurements the Importance of Traceable Calibration H.E. van den Brom and D. Hoogenboom VSL Dutch Metrology Institute, Delft, the Netherlands, hvdbrom@vsl.nl Summary: Standardization has

More information

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection ECHNICAL NOE 2.0 Overvoltages origin and magnitudes Overvoltage protection he ECHNICAL NOES (N) are intended to be used in conjunction with the APPLICAION GIDELINES Overvoltage protection Metaloxide surge

More information

Overvoltage Protection of Light Railway Transportation Systems

Overvoltage Protection of Light Railway Transportation Systems Overvoltage Protection of Light Railway Transportation Systems F. Delfino, R. Procopio, Student Member, IEEE, and M. Rossi, Student Member, IEEE Abstract In this paper the behavior of the power supply

More information

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:15 No:03 39 Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models Shen-Wen Hsiao, Shen-Jen

More information

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland Application of Line Surge Arresters in Power Distribution and Transmission Systems COLLOQUIUM Cavtat 2008 Modeling of overhead transmission lines with line surge arresters for lightning overvoltages M.

More information

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP Kresimir Fekete 1, Srete Nikolovski 2, Goran Knezević 3, Marinko Stojkov 4, Zoran Kovač 5 # Power System Department,

More information

Sensitivity Analysis of Maximum Overvoltage on Cables with Considering Forward and Backward Waves

Sensitivity Analysis of Maximum Overvoltage on Cables with Considering Forward and Backward Waves Sensitivity Analysis of Maximum Overvoltage on Cables with Considering Forward and Backward Waves Hamed Touhidi 1,Mehdi Shafiee 2, Behrooz Vahidi 3, Seyed Hossein Hosseinian 4 1 Islamic Azad University,

More information

HIGH VOLTAGE Insulation Coordination

HIGH VOLTAGE Insulation Coordination HIGH VOLTAGE Insulation Coordination Assistant Professor Suna BOLAT KRÖGER Eastern Mediterranean University Department of Electric & Electronic Engineering Insulation coordination The term Insulation Co-ordination

More information

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES G. V. Podporkin, V. E. Pilshikov, A. D. Sivaev Streamer Electric

More information

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations A. Xemard, M. Mesic, T. Sadovic, D. Marin, S. Sadovic Abstract- A lightning experiment

More information

SURGES TRANSFERRED TO THE LOW-VOLTAGE NETWORK VIA TRANSFORMER THE INFLUENCE OF THE LOAD CONNECTED TO THE SECONDARY

SURGES TRANSFERRED TO THE LOW-VOLTAGE NETWORK VIA TRANSFORMER THE INFLUENCE OF THE LOAD CONNECTED TO THE SECONDARY GROUND and 3 rd WAE International Conference on Grounding and Earthing & 3 rd Brazilian Workshop on Atmospheric Electricity Rio de Janeiro - Brazil November -7, SURGES TRANSFERRED TO THE LOW-VOLTAGE NETWORK

More information

Lightning performance of a HV/MV substation

Lightning performance of a HV/MV substation Lightning performance of a HV/MV substation MAHMUD TAINBA, LAMBOS EKONOMOU Department of Electrical and Electronic Engineering City University London Northampton Square, London EC1V HB United Kingdom emails:

More information

Pre location: Impulse-Current-Method (ICE)

Pre location: Impulse-Current-Method (ICE) 1 ICE (Impulse current method three phased 2 1.1 Ionisation delay time 2 1.2 DIRECT MODE 2 1.3 Output impedance of the generator 2 Surge generator as impulse source 3 High voltage test set as impulse source

More information

High Voltage Induced By Transmission Lines Due To Lightning Case Study

High Voltage Induced By Transmission Lines Due To Lightning Case Study High Voltage Induced By Transmission Lines Due To Lightning Case Study K. Jayavelu 1 & F. Max Savio 2 1&2 Department of Electrical and Electronics Engineering, Jeppiaar Institute of Technology, India Abstract

More information

G. KOEPPL Koeppl Power Experts Switzerland

G. KOEPPL Koeppl Power Experts Switzerland PS3: Substation Design: New Solutions and Experiences Bus-Node Substation A Big Improvement in Short-Circuit and Switching Properties at Reduced Substation Costs G. KOEPPL Koeppl Power Experts Switzerland

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

Protection against unacceptable voltages in railway systems

Protection against unacceptable voltages in railway systems Bernhard Richter*, Alexander Bernhard*, Nick Milutinovic** SUMMERY Based on the system voltages for AC and DC railway systems the required voltage ratings for modern gapless MO surge arresters are given.

More information

INFLUENCE FACTORS ON THE TRANSMITTED OVERVOLTAGES FROM HIGH VOLTAGE TO LOW VOLTAGE NETWORKS

INFLUENCE FACTORS ON THE TRANSMITTED OVERVOLTAGES FROM HIGH VOLTAGE TO LOW VOLTAGE NETWORKS U.P.B. Sci. Bull., Series C, Vol. 72, Iss. 1, 21 ISSN 1454-234x INFLUENCE FACTORS ON THE TRANSMITTED OVERVOLTAGES FROM HIGH VOLTAGE TO LOW VOLTAGE NETWORKS Marian COSTEA 1, Bogdan NICOARĂ 2 În reţelele

More information

Analyzing and Modeling the Lightning Transient Effects of 400 KV Single Circuit Transmission Lines

Analyzing and Modeling the Lightning Transient Effects of 400 KV Single Circuit Transmission Lines International Journal of Science and Engineering Investigations vol. 2, issue 19, August 2013 ISSN: 2251-8843 Analyzing and Modeling the Lightning Transient Effects of 400 KV Single Circuit Transmission

More information

IMPROVEMENTS OF THE FACILITIES FOR LIGHTNING RESEARCH AT MORRO DO CACHIMBO STATION

IMPROVEMENTS OF THE FACILITIES FOR LIGHTNING RESEARCH AT MORRO DO CACHIMBO STATION 29 th International Conference on Lightning Protection 23 rd 26 th June 2008 Uppsala, Sweden IMPROVEMENTS OF THE FACILITIES FOR LIGHTNING RESEARCH AT MORRO DO CACHIMBO STATION Guilherme M. Corrêa 1, André

More information

Transient Data Acquisition System, TAS 4-40 Potential-free measurement of fast rise pulses:

Transient Data Acquisition System, TAS 4-40 Potential-free measurement of fast rise pulses: Transient Data Acquisition System, TAS 4-40 Potential-free measurement of fast rise pulses: High precision measurement of fast rising voltages and currents causes considerable problems in many spheres

More information

Insulation Co-ordination For HVDC Station

Insulation Co-ordination For HVDC Station Insulation Co-ordination For HVDC Station Insulation Co-ordination Definitions As per IEC 60071 Insulation Coordination is defined as selection of dielectric strength of equipment in relation to the operating

More information

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering

More information

(i) Determine the admittance parameters of the network of Fig 1 (f) and draw its - equivalent circuit.

(i) Determine the admittance parameters of the network of Fig 1 (f) and draw its - equivalent circuit. I.E.S-(Conv.)-1995 ELECTRONICS AND TELECOMMUNICATION ENGINEERING PAPER - I Some useful data: Electron charge: 1.6 10 19 Coulomb Free space permeability: 4 10 7 H/m Free space permittivity: 8.85 pf/m Velocity

More information

A Reflectometer for Cable Fault Location with Multiple Pulse Reflection Method

A Reflectometer for Cable Fault Location with Multiple Pulse Reflection Method 2014 by IFSA Publishing, S. L. http://www.sensorsportal.com A Reflectometer for Cable Fault Location with Multiple Pulse Reflection Method Zheng Gongming Electronics & Information School, Yangtze University,

More information

Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines

Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines 7th Asia-Pacific International Conference on Lightning, November 1-4, 2011, Chengdu, China Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines Zihui Zhao, Dong Dang,

More information

Immunity Testing for the CE Mark

Immunity Testing for the CE Mark Immunity Testing for the CE Mark Summary The European Union (EU) currently has 25 member countries with 2 additional countries to be added in 2007. The total population at that time will be nearly a half

More information

The impact of recent advances on lightning measurement and detection on the protection of transmission and distribution lines

The impact of recent advances on lightning measurement and detection on the protection of transmission and distribution lines Current [ka] Current [ka] 1 The impact of recent advances on lightning measurement and detection on the protection of transmission and distribution lines Silverio Visacro, IEEE Member Abstract Recent technological

More information

Lightning current waves measured at short instrumented towers: The influence of sensor position

Lightning current waves measured at short instrumented towers: The influence of sensor position GEOPHYSICAL RESEARCH LETTERS, VOL. 32, L18804, doi:10.1029/2005gl023255, 2005 Lightning current waves measured at short instrumented towers: The influence of sensor position Silvério Visacro and Fernando

More information

Estimating the Lightning Performance of a Multi- Circuit Transmission Tower

Estimating the Lightning Performance of a Multi- Circuit Transmission Tower Estimating the Lightning Performance of a Multi Circuit Transmission Tower Pawel Malicki, Andrzej Mackow and Mustafa Kizilcay University of Siegen Chair of Electrical Power Systems Siegen, Germany pawel.malicki@unisiegen.de

More information

Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin

Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin 4th International Conference on Machinery, Materials and Computing Technology (ICMMCT 2016) Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin

More information

Electromagnetic Interference in the Substation Jose up 400/115 kv

Electromagnetic Interference in the Substation Jose up 400/115 kv Electromagnetic Interference in the Substation Jose up 400/115 kv 1 Gustavo Carrasco Abstract- In the Jose substation the presence of transient electromagnetic interference was dete cted in control and

More information

The line-lightning performance and mitigation studies of shielded steelstructure

The line-lightning performance and mitigation studies of shielded steelstructure The line-lightning performance and mitigation studies of shielded steelstructure distribution lines ASNAWI MOHD BUSRAH, MALIK MOHAMAD Energy System Group TNB Research Sdn Bhd No 1, Lorong Ayer Hitam, 43000

More information

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM SYSTEM OVERVIEW Pollution monitoring of high voltage insulators in electrical power transmission and distribution systems, switchyards and substations is essential in order to minimise the risk of power

More information

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM Anna Tjäder Chalmers University of Technology anna.tjader@chalmers.se Math Bollen Luleå University of Technology math.bollen@stri.se ABSTRACT Power

More information

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of

More information

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 23 CHAPTER 2 v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 2.1 INTRODUCTION For reliable design of power system, proper insulation coordination among the power system equipment is necessary. Insulation

More information

ELECTRIC FIELD WAVEFORMS OF UPWARD LIGHTNING FORMING HOT SPOT IN WINTER IN JAPAN

ELECTRIC FIELD WAVEFORMS OF UPWARD LIGHTNING FORMING HOT SPOT IN WINTER IN JAPAN ELECTRIC FIELD WAVEFORMS OF UPWARD LIGHTNING FORMING HOT SPOT IN WINTER IN JAPAN Mikihisa SAITO Masaru ISHII Fumiyuki FUJII The University of Tokyo, Tokyo, Japan Akiko. SUGITA Franklin Japan, Co, Sagamihara,

More information

Technical Description. General System Information Appendix DCF77

Technical Description. General System Information Appendix DCF77 Technical Description General System Information Appendix DCF77 version 01.04 04.01.2001 CONTENTS Page 1 DCF77 - General Information 3 2 Antennas General 4 2.1 Antenna Structure 4 2.2 Types of Antennas

More information

ABSTRACT 1 INTRODUCTION

ABSTRACT 1 INTRODUCTION ELECTROMAGNETIC ANALYSIS OF WIND TURBINE GROUNDING SYSTEMS Maria Lorentzou*, Ian Cotton**, Nikos Hatziargyriou*, Nick Jenkins** * National Technical University of Athens, 42 Patission Street, 1682 Athens,

More information

Electromagnetic Shielding Analysis of Buildings Under Power Lines Hit by Lightning

Electromagnetic Shielding Analysis of Buildings Under Power Lines Hit by Lightning Electromagnetic Shielding Analysis of Buildings Under Power Lines Hit by Lightning S. Ladan, A. Aghabarati, R. Moini, S. Fortin and F.P. Dawalibi Safe Engineering Services and Technologies ltd. Montreal,

More information

Coordination of surge arresters in DC 3 kv railway traction system field tests

Coordination of surge arresters in DC 3 kv railway traction system field tests Coordination of surge arresters in DC 3 kv railway traction system field tests Miroslaw Zielenkiewicz Tomasz Maksimowicz Center of Protection against Overvoltages and Electromagnetic Interferences RST

More information

Monitoring power quality beyond EN and IEC

Monitoring power quality beyond EN and IEC Monitoring power quality beyond EN 50160 and IEC 61000-4-30 by A Broshi and E Kadec, Elspec, Israel The standards currently in place provide minimum requirements, since they want to create a level playing

More information

Electric Stresses on Surge Arrester Insulation under Standard and

Electric Stresses on Surge Arrester Insulation under Standard and Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems

More information

Computation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission Lines

Computation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission Lines www.ijape.org International Journal of Automation and Power Engineering (IJAPE) Volume Issue, January DOI:./ijape... omputation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission

More information

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations Ricard Petranovic and Amir M. Miri Universität Karlsruhe, Institut für Elektroenergiesysteme und Hochspannungstechnik,

More information

Utility System Lightning Protection

Utility System Lightning Protection Utility System Lightning Protection Many power quality problems stem from lightning. Not only can the high-voltage impulses damage load equipment, but the temporary fault that follows a lightning strike

More information

Partial discharge diagnostics on very long and branched cable circuits

Partial discharge diagnostics on very long and branched cable circuits 11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA

More information

Digital Fault Recorder Deployment at HVDC Converter Stations

Digital Fault Recorder Deployment at HVDC Converter Stations Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic

More information

Effect of Shielded Distribution Cable on Very Fast Transients

Effect of Shielded Distribution Cable on Very Fast Transients IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000 857 Effect of Shielded Distribution Cable on Very Fast Transients Li-Ming Zhou and Steven Boggs, Fellow, IEEE Abstract Fast transients in

More information

Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines

Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines F. Faria da Silva, Claus L. Bak, Per B. Holst Abstract--The disconnection of HV underground cables may, if unsuccessful, originate

More information

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE Willem DIRKSE VAN SCHALKWYK ESKOM - South Africa vschalwj@eskom.co.za ABSTRACT A high BIL (300 kv) on a MV feeder ensures that no

More information

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation P.S.Diwakar High voltage Engineering National Engineering College Kovilpatti, Tamilnadu, India S.Sankarakumar Department

More information

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables 21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria

More information

The Lightning Event. White Paper

The Lightning Event. White Paper The Lightning Event White Paper The Lightning Event Surge Protection Solutions for PTC 1 The Lightning Event There are volumes of information available on what we believe lightning is and how we think

More information