C4-301 EXPERIMENTAL EVALUATION OF TRANSFERRED SURGES IN MV TRANSFORMERS FROM HV/LV

Size: px
Start display at page:

Download "C4-301 EXPERIMENTAL EVALUATION OF TRANSFERRED SURGES IN MV TRANSFORMERS FROM HV/LV"

Transcription

1 21, rue d'artois, F Paris C4-301 Session 2004 CIGRÉ EXPERIMENTAL EVALUATION OF TRANSFERRED SURGES IN MV TRANSFORMERS FROM HV/LV HERMOSO B.*, AGUADO M., SENOSIAIN V., MARTÍNEZ CID P.M. UNIVERSIDAD PÚBLICA DE NAVARRA IBERDROLA (Spain) In MV lines lightning produces overvoltages by direct action on line conductors or by induced overvoltages. In both cases, if the surge voltage resultant is lower than the line BIL, a surge wave is produced travels by the line arriving, in many cases, to the MV/LV transformers. These transformers allow the path of the waves from the HV to the LV side by different coupling mechanisms (capacitive, oscillatory, electromagnetic), finally the LV installations are the victims for this kind of overvoltages. According with the stard EN , Annexe E is easier to obtain the value of the transferred overvoltage in transformers, using a recurrent surge generator. From the results obtained in the tests describe above considering the CIGRE model for coupling mechanism transformer simulation it has been formulated a simple transformer model that it allows knowing the transferred surge at low side. Keywords: Lightning - Insulation Coordination-Overvoltages-Transformers 1. HV-LV TRANSFERRED OVERVOLTAGES The overvoltages transmission in a distribution transformer from the HV to LV side, due to the lightning, is a main point for the transformer design, for the customer protection. The value of the result transmitted overvoltages is given for the shape of the incident wave (fast front or low front) by the transformer structure (winding shapes, connections...) whose is resumed in capacitive inductive values. The different transmission modalities are indicated in the EN , Annex E [1]: - Electrostatic or capacitive transmission. This component appears the first his frequency is into the range of MHz - Oscillatory transmission. This component is due to the naturals oscillations generated by the capacitance to ground the inductance of transformers - Electromagnetic transmission. This component, also called "normal transmission" is related with the transformation ratio, the inductance the burden of transformer * hermoso@unavarra.es

2 The capacitive component appears the first; his frequency is in the range of MHz. its value is related with the windings capacities the capacity between the windings ground. After the capacitive component, appears the component transmitted by inductive way, whose value depend of voltage distribution in the winding. The transformers work as in normal condition. The oscillatory component is dimmed overlapped to the electromagnetic component. Normally is weak is not very important except when it appears resonance phenomena. Although Stard EN Appendix E gives the expressions to evaluate the different transmission components, this one recognizes the difficulty to applied them, due to the several factors that may appear must been take into account. It recommends, as a more practical method to measure the response with a recurrent generator. 2. TESTS WITH REGURRENT GENERATOR The tests have been achieved with a recurrent surge generator, output 100 volts wave 1,2/50µs (Fig. 2), 35 Hz, applied on different distribution transformers (power, ratio, group connection, insulation). See data in table 1. Table 1 Transformers characteristics KVA HV/LV (kv) Group Insulation 25 0,945/0,4-0,230 Yy0 oil 25 13,8/0,38 Dyn11 oil 25 13,2/0,38 Dyn11 oil 25 13,8/0,4/0,132 Dz0-Dyn11 oil 50 13,6/0,4 Yzn11 oil 50 13,2/0,23 Dyn11 oil ,2-21/0,42-0,24 Yzn11 oil ,8/0,42-0,24 Dyn11 silicone ,86/0,42-0,24 Dyn11 oil ,2/0,42 Dyn11 dry ,86/0,42-0,24 Dyn11 oil ,86/0,42-0,24 Dyn11 silicone /0,4 Ynd11 oil ,86/0,42 Dyn11 silicone /3,19 Dyn11 oil The voltage has been applied in the HV side between two phases, the oscillatory responses obtained in the LV side has been registered as seen in figure 1 figure 2 (100 kva-630 kva) The values (frequency amplitude as p.u. of voltage applied) are showed in table 2. 2

3 Table 2 Test result KVA input/ouput MHz p.u. KVA input/ouput MHz p.u. 25 AB-ca 0,164 0, AB-ca 0,476 0,106 BC-ca 0,172 0,0696 BC-ca 0,49 0,186 CA-ca 0,175 0,0777 CA-ca 0,463 0, AB-ca 0,108 0, AB-ca 0,678 0,0367 BC-ca 0,103 0,0411 BC-ca 0,69 0,025 CA-ca 0,164 0,0345 CA-ca 0,667 0, AB-ca 0,125 0, AB-ca 0,54 0,0847 BC-ca 0,109 0,0411 BC-ca 0,521 0,0851 CA-ca 0,189 0,0345 CA-ca 0,563 0, AB-ca 0,179 0, AB-ca 0,548 0,0596 BC-ca 0,172 0,0505 BC-ca 0,667 0,0176 CA-ca 0,179 0,0777 CA-ca 0,536 0, AB-ca 0,152 0, AB-ca 0,58 0,0827 BC-ca 0,144 0,0077 BC-ca 0,556 0,0303 CA-ca 0,135 0,03 CA-ca 0,606 0, AB-ca 0,458 0, AB-ca 0,667 0,0784 BC-ca 0,465 0,181 BC-ca 0,6 0,157 CA-ca 0,444 0,184 CA-ca 0,595 0, AB-ca 0,5 0,045 BC-ca 0,5 0,035 CA-ca 0,5 0,045 Input Wave 1,2/50 µs V c = 100 V Oscillatory wave f=0,179 MHz V c =783mV=0,783V 0,783/10=0,0783 f=0,172mhz V c =505mV=0,505V 0,505/10=0,0505 f=0,179 MHz V c =777mV=0,777V 0,777/10=0,0777 Fig. 1. Oscillatory response 100kVA; 14,2-21/0,42-0,242 kv; Yzn11; Oil 3

4 f=0,667 MHz V c =784mV=0,784V 0,784/10=0,0784 f=0,6 MHz V c =157mV=0,157V 0,157/10=0,157 f=0,595 MHz V c =849mV=0,849V 0,849/10=0,0849 Fig. 2. Oscillatory response 630 kva; 13,86/0,42 kv; Dyn11; Silicone 3. CORRELATIONS In figure 3 is plotted the transmission coefficient in figure 4 the frequency of the reference transformers sample versus the rated transformers power. correlations. As it is observed in figure 3 it does not exist correlations for all the sample, but it is possible to define a transmission coefficient (average value) around 0,1 p.u., except for one small transformer (25 kva). In figure 4 it may observe two main response frequencies, one around the 0,6 MHz for a wide range of transformers, other one around 0,2 MHz for a small group of transformers with rated power between kva p.u. 0,8 0,7 0,6 0,5 0,4 0,3 0,2 0,1 0 transmission coefficient y = 0,0992x -0,0199 R 2 = 0, kva Fig. 3. Transmission coefficient- kva MHz frecuencia y = 0,0762x 0,3122 R 2 = 0,5523 0,8 0,6 0,4 0, kva Fig. 4. Frequency response 4

5 4. SIMPLE TRANSFORMER MODEL The model developed is based on Group III of CIGRE (figure 5) but with some modifications [2]. Fig. 5. CIGRE model, Group III The reason of these modifications is connected with the objective of getting a very simple model, understing simple as feasible, that is without taking so many measures. According above indicated the model proposed is: kr1 R1 L1 C MB k L1 k 2 L2 R2 C W1 W2 MT C BT L Rt Lt Fig. 6. Transformer model proposed being R1 L1 resistance inductance of primary winding R2 L2 resistance inductance of secondary winding C MT, CBT CMB primary secondary capacitance to ground capacitance between primary secondary winding Rt Lt resistance inductance of transformer grounding k R1, L1 k, 2 k L coefficients of primary secondary windings The model in ATP is showing in the figure 7: 5

6 Fig.7. Model in ATP 5. CONCLUSIONS This paper shows that the use of a recurrent surge generator to analyse the transferred overvoltages in distribution transformers is a very useful tool. The transferred voltage coefficient for different distribution transformers is in the range of the 10 % of applied voltage the oscillatory frequency is in the range of 200 khz for transformers with rated power between kva around 600 khz. for a wide range of transformers. This paper presents too a simplified model to analyse the transferred voltages in three-phase distribution transformers. The simplicity lies on the fact that we need only the constructive data (given by manufacturer) the capacitance to ground of each winding between them (feasible measurements). 6. ACKNOWLEDGEMENTS The authors gracefully extent their thanks to IBERDROLA for provide us the necessary technical economical support. 7. REFERENCES [1] EN Insulation Coordination. Part 2: Application guide [2] CIGRE WG.33.02, Guidelines for representation of network elements when calculating transients, October

Fast Front Transients in Transformer Connected to Gas Insulated Substations: (White+Black) Box Models and TDSF Monitoring

Fast Front Transients in Transformer Connected to Gas Insulated Substations: (White+Black) Box Models and TDSF Monitoring Fast Front Transients in Transformer Connected to Gas Insulated Substations: (White+Black) Box Models and TDSF Monitoring Luis ROUCO 1, Xose M. LÓPEZ-FERNÁNDEZ 2, 3, Casimiro ALVAREZ-MARIÑO 3 and Hugo

More information

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation W. Buesch 1) G. Palmieri M.Miesch J. Marmonier O. Chuniaud ALSTOM LTD 1) ALSTOM LTD High Voltage Equipment

More information

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS TRANSFORMER IN GRID When surge arres t ers are installed close to a power transformer, they provide protection against lightning overvoltage ABSTRACT The aim of this research article is to determine the

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

Modeling insulation in high-voltage substations

Modeling insulation in high-voltage substations 38 ABB REVIEW DESIGNED FOR SAFETY DESIGNED FOR SAFETY Modeling insulation in high-voltage substations The goal of insulation coordination is to determine the dielectric strength of transformers and other

More information

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 4, OCTOBER 2002 969 Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies Taku Noda, Member, IEEE, Hiroshi Nakamoto,

More information

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES 21, rue d'artois, F-75008 Paris http://www.cigre.org A3-308 Session 2004 CIGRÉ HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES G.E. Agafonov, I.V. Babkin, B.E. Berlin Y. F. Kaminsky, S. V. Tretiakov,

More information

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning M. PSALIDAS, D. AGORIS, E. PYRGIOTI, C. KARAGIAΝNOPOULOS High Voltage Laboratory,

More information

(2) New Standard IEEE P (3) Core : (4) Windings :

(2) New Standard IEEE P (3) Core : (4) Windings : (d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.

More information

GIS Disconnector Switching Operation VFTO Study

GIS Disconnector Switching Operation VFTO Study GIS Disconnector Switching Operation VFTO Study Mariusz Stosur, Marcin Szewczyk, Wojciech Piasecki, Marek Florkowski, Marek Fulczyk ABB Corporate Research Center in Krakow Starowislna 13A, 31-038 Krakow,

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

Recent Improvements in K-Factor Models dl

Recent Improvements in K-Factor Models dl 1 Recent Improvements in K-Factor Models dl Yixin Zhang NEETRAC, Georgia Institute of Technology 2014 IEEE PES Panel Session Discussions on IEEE Std.4 2013: High Voltage Testing Techniques 2 Related Standards

More information

Electromagnetic Interference in the Substation Jose up 400/115 kv

Electromagnetic Interference in the Substation Jose up 400/115 kv Electromagnetic Interference in the Substation Jose up 400/115 kv 1 Gustavo Carrasco Abstract- In the Jose substation the presence of transient electromagnetic interference was dete cted in control and

More information

Propagation of Lightning Overvoltages Across MV/LV Substation Measurements and Modelling.

Propagation of Lightning Overvoltages Across MV/LV Substation Measurements and Modelling. Bogotá D.C., Colombia. Noviembre 16-18 de 005 Propagation of Lightning Overvoltages Across MV/LV Substation Measurements and Modelling. Jarosław M. Wiater Abstract - This paper presents measurement results

More information

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 23 CHAPTER 2 v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 2.1 INTRODUCTION For reliable design of power system, proper insulation coordination among the power system equipment is necessary. Insulation

More information

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering

More information

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2 ACTA UNIVERSITATIS APULENSIS Special Issue SIMULATION OF LIGHTNING OVERVOLTAGES WITH ATP-EMTP AND PSCAD/EMTDC Violeta Chiş, Cristina Băla and Mihaela-Daciana Crăciun Abstract. Currently, several offline

More information

How To Ground Electronic Equipment In Southern Company? Imagination at work

How To Ground Electronic Equipment In Southern Company? Imagination at work How To Ground Electronic Equipment In Southern Company? Imagination at work Surge Protection of Capacitor Feeder Controllers Robert Cheney Alabama Power John Skliutas GE Digital Energy Don Guinn Progress

More information

INFLUENCE FACTORS ON THE TRANSMITTED OVERVOLTAGES FROM HIGH VOLTAGE TO LOW VOLTAGE NETWORKS

INFLUENCE FACTORS ON THE TRANSMITTED OVERVOLTAGES FROM HIGH VOLTAGE TO LOW VOLTAGE NETWORKS U.P.B. Sci. Bull., Series C, Vol. 72, Iss. 1, 21 ISSN 1454-234x INFLUENCE FACTORS ON THE TRANSMITTED OVERVOLTAGES FROM HIGH VOLTAGE TO LOW VOLTAGE NETWORKS Marian COSTEA 1, Bogdan NICOARĂ 2 În reţelele

More information

ABSTRACTS of SESSION 6

ABSTRACTS of SESSION 6 ABSTRACTS of SESSION 6 Paper n 1 Lightning protection of overhead 35 kv lines by antenna-module long flashover arresters Abstract: A long-flashover arrester (LFA) of a new antenna-module type is suggested

More information

Transformers handling and transport

Transformers handling and transport Special tests (Credit: http://www.breakbulk.com/wp-content/uploads/2015/02/20141117160247x.jpg) Transformers handling and transport Damages that may arise and how to find them Table of contents summary

More information

Vallabh Vidyanagar, Anand, INDIA

Vallabh Vidyanagar, Anand, INDIA IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 1 Ver. V (Feb. 2014), PP 01-06 Interpretation of Sweep Frequency Response Analysis

More information

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems) Transmission Line Transient Overvoltages (Travelling Waves on Power Systems) The establishment of a potential difference between the conductors of an overhead transmission line is accompanied by the production

More information

Simulation Study of Voltage Surge Distribution in a Transformer Winding

Simulation Study of Voltage Surge Distribution in a Transformer Winding Simulation Study of Voltage Surge Distribution in a Transformer Winding R.V Srinivasamurthy [1] Pradipkumar Dixit [2] Research Scholar, Jain university Professor, EEE Dept Prof and Head, EEE Dept M.S.

More information

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP IJSTE - International Journal of Science Technology & Engineering Volume 3 Issue 2 August 216 ISSN (online): 2349-784X Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

More information

Error vs. Uncertainty Historical Perspective

Error vs. Uncertainty Historical Perspective 1 Error vs. Uncertainty Historical Perspective Jim McBride Chairman PSIM Committee Vice-Chairman HVTT Subcommittee IEEE PES SPDC Fall 2017 Clearwater, FL Discussions on Uncertainty PSIM - HVTT Subcommittee

More information

High-Voltage Test Techniques

High-Voltage Test Techniques High-Voltage Test Techniques Dieter Kind Kurt Feser 2nd Revised and Enlarged Edition With 211 Figures and 12 Laboratory Experiments Translated from the German by Y. Narayana Rao Professor of Electrical

More information

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY Dr. Karthik Reddy VENNA Hong URBANEK Nils ANGER Siemens AG Germany Siemens AG Germany Siemens AG Germany karthikreddy.venna@siemens.com

More information

HIGH VOLTAGE TESTING GENERATION AND MEASUREMENTS

HIGH VOLTAGE TESTING GENERATION AND MEASUREMENTS HIGH VOLTAGE TESTING GENERATION AND MEASUREMENTS 1. INTRODUCTION why high voltage test? 2. HIGH VOLTAGE GENERATION a) Generation of direct high voltages b) Generation of alternating high voltages c) Generation

More information

Shunt Reactor Switching

Shunt Reactor Switching Shunt Reactor Switching Dielectric stresses produced by circuit-breakers to shunt reactors. Presentation made during the IEEE Transformers Committee meeting, Amsterdam, Netherlands, April 2001 Presented

More information

Power Quality and Reliablity Centre

Power Quality and Reliablity Centre Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview

More information

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 1), Cairo University, Egypt, December 19-1, 1, Paper ID 1. Simplified Approach to Calculate the Back Flashover Voltage

More information

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy W. Piasecki, M. Stosur, T. Kuczek, M. Kuniewski, R. Javora Abstract-- Evaluation

More information

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces 1 Prediction of Transient Transfer Functions at Cable-Transformer Interfaces Joe Y. Zhou, Member, IEEE and Steven A. Boggs, Fellow, IEEE Joe Zhou participated in this work while completing his Ph.D. at

More information

Resonances in Collection Grids of Offshore Wind Farms

Resonances in Collection Grids of Offshore Wind Farms Downloaded from orbit.dtu.dk on: Dec 20, 2017 Resonances in Collection Grids of Offshore Wind Farms Holdyk, Andrzej Publication date: 2013 Link back to DTU Orbit Citation (APA): Holdyk, A. (2013). Resonances

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

FAULT IDENTIFICATION IN TRANSFORMER WINDING

FAULT IDENTIFICATION IN TRANSFORMER WINDING FAULT IDENTIFICATION IN TRANSFORMER WINDING S.Joshibha Ponmalar 1, S.Kavitha 2 1, 2 Department of Electrical and Electronics Engineering, Saveetha Engineering College, (Anna University), Chennai Abstract

More information

Insulation Level and Test Technology of. 1000kV Power Transformer

Insulation Level and Test Technology of. 1000kV Power Transformer Insulation Level and Test Technology of 1000kV Power Transformer Li Guangfan, Wang Xiaoning, Li Peng et al HIMALAYAL - SHANGHAI - CHINA Abstract: The insulation coordination for the first 1000kV UHVAC

More information

Experimental Study and Circuit Analysis Model of Lightning Isolation Transformer for Railway Signal System

Experimental Study and Circuit Analysis Model of Lightning Isolation Transformer for Railway Signal System 214 International Conference on Lightning Protection (ICLP), Shanghai, China Experimental Study and Circuit Analysis Model of Lightning Isolation Transformer for Railway Signal System Shunichi Yanagawa

More information

High frequency transformer model for calculations of transferred overvoltages. I. UGLESIC University of Zagreb, Croatia

High frequency transformer model for calculations of transferred overvoltages. I. UGLESIC University of Zagreb, Croatia 21, rue d Artois, F-75008 PARIS International Colloquium INSA LYON http : //www.cigre.org on Lightning and Power systems France High frequency transformer model for calculations of transferred overvoltages

More information

High Voltage Generation

High Voltage Generation High Voltage Generation Purposes (Manfaat) Company Logo High DC High AC Impulse Electron microscopes and x-ray units (high d.c. voltages 100 kv) Electrostatic precipitators, particle accelerators (few

More information

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Voltage (kv) Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Li-Ming Zhou, Senior Member, IEEE and Steven Boggs, Fellow, IEEE Abstract: The high frequency attenuation

More information

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations A. Xemard, M. Mesic, T. Sadovic, D. Marin, S. Sadovic Abstract- A lightning experiment

More information

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24 LECTURER-24 GENERATION OF HIGH ALTERNATING VOLTAGES When test voltage requirements are less than about 300kV, a single transformer can be used for test purposes. The impedance of the transformer should

More information

X International Symposium on Lightning Protection

X International Symposium on Lightning Protection X International Symposium on Lightning Protection 9 th -13 th November, 2009 Curitiba, Brazil LIGHTNING SURGES TRANSFERRED TO THE SECONDARY OF DISTRIBUTION TRANSFORMERS DUE TO DIRECT STRIKES ON MV LINES,

More information

LIGHTNING IMPULSE MODELING AND SIMULATION OF DRY-TYPE AND OIL-IMMERSED POWER- AND DISTRIBUTION TRANSFORMERS

LIGHTNING IMPULSE MODELING AND SIMULATION OF DRY-TYPE AND OIL-IMMERSED POWER- AND DISTRIBUTION TRANSFORMERS Journal of Energy VOLUME 63 2014 journal homepage: http://journalofenergy.com/ Jasmin Smajic, Roman Obrist, Martin Rüegg University of Applied Sciences of Eastern Switzerland (HSR) jasmin.smajic@hsr.ch

More information

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM Anna Tjäder Chalmers University of Technology anna.tjader@chalmers.se Math Bollen Luleå University of Technology math.bollen@stri.se ABSTRACT Power

More information

148 Electric Machines

148 Electric Machines 148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional

More information

The Influence of a Cable on the Voltage Distribution in Transformer Windings G. Hoogendorp, M. Popov, L. van der Sluis

The Influence of a Cable on the Voltage Distribution in Transformer Windings G. Hoogendorp, M. Popov, L. van der Sluis The Influence of a Cable on the Voltage Distribution in Transformer Windings G. Hoogendorp, M. Popov, L. van der Sluis Abstract Voltage distribution in transformer windings is influenced by the presence

More information

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel International Journal of Power and Energy Research, Vol. 1, No. 1, April 2017 https://dx.doi.org/10.22606/ijper.2017.11001 1 Lightning Protection of Distribution Substations by Using Metal Oxide Gapless

More information

Electrical Transient Interaction between Transformers and Power System. Brazilian Experience

Electrical Transient Interaction between Transformers and Power System. Brazilian Experience Electrical Transient Interaction between Transformers and Power System Brazilian Experience Ulisses R. R. Massaro, Ricardo Antunes On behalf of Cigré-Brazil Joint Working Group JWG A2/C4-03 Electrical

More information

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids Tarik Abdulahović #, Torbjörn Thiringer # # Division of Electric Power Engineering, Department of Energy

More information

ANALYSIS, SIMULATION AND TESTING OF TRANSFORMER INSULATION FAILURES RELATED TO SWITCHING TRANSIENTS OVERVOLTAGES.

ANALYSIS, SIMULATION AND TESTING OF TRANSFORMER INSULATION FAILURES RELATED TO SWITCHING TRANSIENTS OVERVOLTAGES. 1, rue d'artois, F-75008 Paris http://www.cigre.org 1-116 Session 00 CIGRÉ ANALYSIS, SIMULATION AND TESTING OF TRANSFORMER INSULATION FAILURES RELATED TO SWITCHING TRANSIENTS OVERVOLTAGES. J.LOPEZ-ROLDAN,

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

Prevention of transformers damage in HPP with double generating units connected to GIS via HV cables

Prevention of transformers damage in HPP with double generating units connected to GIS via HV cables nd This paper is part of the Proceedings of the 2 International Conference on Energy Production and Management (EQ 2016) www.witconferences.com Prevention of transformers damage in HPP with double generating

More information

Chapter 1. Overvoltage Surges and their Effects

Chapter 1. Overvoltage Surges and their Effects Chapter 1 Overvoltage Surges and their Effects 1.1 Introduction Power equipment are often exposed to short duration impulse voltages of high amplitude produced by lightning or switching transients. These

More information

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation P.S.Diwakar High voltage Engineering National Engineering College Kovilpatti, Tamilnadu, India S.Sankarakumar Department

More information

USING DAMPED AC VOLTAGES

USING DAMPED AC VOLTAGES MODERN & TESTING DIAGNOSIS OF POWER CABLES USING DAMPED AC VOLTAGES BY EDWARD GULSKI AND ROGIER JONGEN, Onsite HV Solutions ag, Switzerland AND RALPH PATTERSON, Power Products & Solutions LLC, United States

More information

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages Session Four: ractical Insulation Co-ordination Session Four: ractical Insulation Co-ordination for Lightning Induced Overvoltages Jason Mayer Technical Director, Energy Services, Aurecon Introduction

More information

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS AS 60044.1 2007 AS 60044.1 2007 Australian Standard Instrument transformers Part 1: Current transformers (IEC 60044-1 Ed.1.2 (2003) MOD) This Australian Standard was prepared by Committee EL-013, Measurement

More information

Capacitive voltage transformers

Capacitive voltage transformers Capacitive voltage transformers Outdoor operation Oil-paper insulated ECF (72 550) kv General description Capacitive voltage transformers of type ECF are used in high-voltage switchgears from 72 to 550

More information

G. KOEPPL Koeppl Power Experts Switzerland

G. KOEPPL Koeppl Power Experts Switzerland PS3: Substation Design: New Solutions and Experiences Bus-Node Substation A Big Improvement in Short-Circuit and Switching Properties at Reduced Substation Costs G. KOEPPL Koeppl Power Experts Switzerland

More information

Computation of Inter-turn Voltages in Transformer Windings with Interconnected Distribution Cable

Computation of Inter-turn Voltages in Transformer Windings with Interconnected Distribution Cable Computation of Inter-turn Voltages in Transformer Windings with Interconnected Distribution Cable G. Hoogendorp, M. Popov, L. van der Sluis Abstract The paper deals with the use of the hybrid model to

More information

Computation of Very Fast Transient Overvoltages in Transformer Windings

Computation of Very Fast Transient Overvoltages in Transformer Windings Computation of Very Fast Transient Overvoltages in Transformer Windings M. Popov, Senior Member, IEEE, L. van der Sluis, Senior Member, IEEE, G. C. Paap, Senior Member, IEEE, and H. de Herdt Abstract--

More information

500 kva Dry-type Isolation Transformer V-Delta to 208Y/120V 3PH - NEMA 1/Indoor

500 kva Dry-type Isolation Transformer V-Delta to 208Y/120V 3PH - NEMA 1/Indoor 500 kva Dry-type Isolation Transformer - 13200V-Delta to 208Y/120V 3PH - NEMA 1/Indoor Part #: MT-DOE16-3P-13200D-500KVA-208Y.120-N1 Page: 1 The MT-DOE16-3P-13200D-500KVA-208Y.120-N1 Dry-type Isolation

More information

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP Kresimir Fekete 1, Srete Nikolovski 2, Goran Knezević 3, Marinko Stojkov 4, Zoran Kovač 5 # Power System Department,

More information

Accr. 002-Test EN-ISO (2005)

Accr. 002-Test EN-ISO (2005) Electromagnetic compatibility LAB > Examination of compliance with EMC standards > Measurement of radio-disturbances > Immunity tests > 2004/108/EC EMC Directive > CE Marking > Measurement of electromagnetic

More information

Roadmap For Power Quality Standards Development

Roadmap For Power Quality Standards Development Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel

More information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING YEAR / SEM : IV / VII UNIT I OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What

More information

Transient Recovery Voltage at Transformer Limited Fault Clearing

Transient Recovery Voltage at Transformer Limited Fault Clearing Transient Recovery Voltage at Transformer Limited Fault Clearing H. Kagawa (Tokyo Electric power Company, Japan) A. Janssen (Liander N.V., the Netherlands) D. Dufounet (Consultant, France) H. Kajino, H.

More information

Tab 8 Surge Arresters

Tab 8 Surge Arresters s en em Tab 8 Surge Arresters Si Distribution System Engineering Course Unit 10 2017 Industry Inc., All Rights Reserved Surge Arresters The main protective devices against system transient overvoltages.

More information

Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL

Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL ENGLISH SC_Trafo-TI-en-66 Version 6.6 Table of Contents SMA Solar Technology AG Table of

More information

Electric Stresses on Surge Arrester Insulation under Standard and

Electric Stresses on Surge Arrester Insulation under Standard and Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems

More information

A1-101 INFLUENCE OF SPECIAL SHORT CIRCUIT ON ELECTRICAL GENERATOR DESIGN. Ding Zhong MENG (HONG KONG, CHINA)

A1-101 INFLUENCE OF SPECIAL SHORT CIRCUIT ON ELECTRICAL GENERATOR DESIGN. Ding Zhong MENG (HONG KONG, CHINA) 1, rue d'artois, F-758 Paris http://www.cigre.org A1-11 Session 4 CIGRÉ INFLUENCE OF SPECIAL SHORT CIRCUIT ON ELECTRICAL GENERATOR DESIGN Ding Zhong MENG (HONG KONG, CHINA) SUMMARY Refer to the IEC Standard

More information

A Study on Ferroresonance Mitigation Techniques for Power Transformer

A Study on Ferroresonance Mitigation Techniques for Power Transformer A Study on Ferroresonance Mitigation Techniques for Power Transformer S. I. Kim, B. C. Sung, S. N. Kim, Y. C. Choi, H. J. Kim Abstract--This paper presents a comprehensive study on the ferroresonance mitigation

More information

Measurements for validation of high voltage underground cable modelling

Measurements for validation of high voltage underground cable modelling Measurements for validation of high voltage underground cable modelling Unnur Stella Gudmundsdottir, Claus Leth Bak, Wojciech T. Wiechowski, Kim Søgaard, Martin Randrup Knardrupgård Abstract-- This paper

More information

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

Maximum Lightning Overvoltage along a Cable due to Shielding Failure Maximum Lightning Overvoltage along a Cable due to Shielding Failure Thor Henriksen Abstract--This paper analyzes the maximum lightning overvoltage due to shielding failure along a cable inserted in an

More information

Chapter 7 Conclusion 7.1 General

Chapter 7 Conclusion 7.1 General Chapter 7 7.1 General The mechanical integrity of a transformer winding is challenged by several mechanisms. Many dielectric failures in transformers are direct results of reduced mechanical strength due

More information

Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL

Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL ENGLISH SC_Trafo-TI-en-65 Version 6.5 Table of Contents SMA Solar Technology AG Table of

More information

Identification of network models parameters for simulating transients

Identification of network models parameters for simulating transients Identification of network models parameters for simulating transients D. Cavallera, J-L. Coulomb, O. Chadebec, B. Caillault, F-X. Zgainski and A.Ayroulet Abstract In case of electrical black-out, one of

More information

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of

More information

Switching Induced Transients:

Switching Induced Transients: Switching Induced Transients: Transformer switching is the most commonly performed operation in any power delivery system and most of the times this operation can be performed without any undesirable consequences.

More information

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements EMEL ONAL Electrical Engineering Department Istanbul Technical University 34469 Maslak-Istanbul TURKEY onal@elk.itu.edu.tr http://www.elk.itu.edu.tr/~onal

More information

High Frequency Conducted Disturbances

High Frequency Conducted Disturbances THESIS FOR THE DEGREE OF LICENTIATE OF ENGINEERING High Frequency Conducted Disturbances Anna Tjäder Department of Electric Power Engineering CHALMERS UNIVERSITY OF TECHNOLOGY Göteborg, Sweden, 2004 High

More information

Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines

Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines F. Faria da Silva, Claus L. Bak, Per B. Holst Abstract--The disconnection of HV underground cables may, if unsuccessful, originate

More information

Immunity Testing for the CE Mark

Immunity Testing for the CE Mark Immunity Testing for the CE Mark Summary The European Union (EU) currently has 25 member countries with 2 additional countries to be added in 2007. The total population at that time will be nearly a half

More information

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope Date: Page: 1 / 10 Personal Data Name: Company / institution: Phone: E-mail: Fax: Application Quotation number: (will be filled in by HIGHVOLT) Test field, stationary research institute mobile on-site

More information

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding Research Journal of Applied Sciences, Engineering and Technology 10(10): 1102-1107, 2015 DOI: 10.19026/rjaset.10.1879 ISSN: 2040-7459; e-issn: 2040-7467 2015 Maxwell Scientific Publication Corp. Submitted:

More information

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Calculation of Isc by the impedance method In a 3-phase installation Isc at any point is

More information

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES Shohreh Monshizadeh Islamic Azad University South Tehran Branch (IAU), Tehran,

More information

Statistical analysis of overvoltages due to the energisation of a 132 kv underground cable

Statistical analysis of overvoltages due to the energisation of a 132 kv underground cable University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part A Faculty of Engineering and Information Sciences 2009 Statistical analysis of overvoltages due to

More information

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS 29 th International Conference on Lightning Protection 23 rd 26 th June 2008 Uppsala, Sweden PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS Ivo Uglešić Viktor Milardić Božidar

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

OVERVOLTAGE PROTECTION OF POLE MOUNTED DISTRIBUTION TRANSFORMERS

OVERVOLTAGE PROTECTION OF POLE MOUNTED DISTRIBUTION TRANSFORMERS PERODCA POLYTECHNCA SER. EL. ENG. VOL. 41, NO. 1, PP. 27-40 (1997) OVERVOLTAGE PROTECTON OF POLE MOUNTED DSTRBUTON TRANSFORMERS Attila SOMOGY and Lasz16 VZ Department of Electric Power Systems Technical

More information

A C. Wallner Siemens AG Berlin, (Germany)

A C. Wallner Siemens AG Berlin, (Germany) 21, rue d'artois, F-75008 Paris http://www.cigre.org A3-115 Session 2004 CIGRÉ A Algorithm for the Three-Pole Controlled Auto-Reclosing of Shunt Compensated Transmission Lines with a Optimization for the

More information

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN Eugenio PEREA*, Eduardo ZABALA*, J. Emilio RODRÍGUEZ*, Asier GIL DE MURO*, Hugo GAGO * * * Fundación LABEIN,

More information

EN Assignment No.1 - TRANSFORMERS

EN Assignment No.1 - TRANSFORMERS EN-06 - Assignment No.1 - TRANSFORMERS Date : 13 th Jan 01 Q1) A 0kVA 00/0 Volts, 60Hz, single phase transformer is found to have the following equivalent circuit parameter referred to the high potential

More information

COMMISSION REGULATION (EU) No /.. of XXX

COMMISSION REGULATION (EU) No /.. of XXX EUROPEAN COMMISSION Brussels, XXX [ ](2013) XXX draft COMMISSION REGULATION (EU) No /.. of XXX on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small,

More information

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH Giuseppe Cappai, Bernhard Heinrich, Giuseppe Simioli, Leonardo Trevisan Weidmann Electrical Technology AG, Switzerland Abstract: A large solar

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi

More information