Three Phase Induction Motor Performance under Unbalanced Voltage Conditions

Size: px
Start display at page:

Download "Three Phase Induction Motor Performance under Unbalanced Voltage Conditions"

Transcription

1 Three Phase Induction Motor Performance under Unbalanced Voltage Conditions A Jalilian, IUST 1. Introduction Three phase induction motors are normally designed to operate under balanced supply voltage conditions. Australian Standards [AS86] specifies that a polyphase voltage system is virtually balanced if the negative sequence does not exceed 1% of positive sequence component of the system voltage over a long period. IEEE Std 112 [IEEE91] allows 0.5% voltage unbalance when performing standard tests on polyphase induction motors. Some manufacturers suggest an allowable deviation (mostly ±5%) from the nameplate voltage, however, little or no information is available on the manufacturer's data on the level of allowable unbalance. Voltage unbalance, in turn, affects the performance of induction motors as well as other power system loads and equipment. This report deals with a review of three phase induction motor performance under unbalanced voltage conditions. Two common definitions of the voltage unbalance are given and their method of calculations are presented. Experimental tests are conducted on a 7.5 kw high efficiency induction motor supplied by nominal balanced and unbalanced supply voltages under different loading conditions. Experimental results are utilised to investigate the effect of unbalanced supply on motor losses as well as on motor output power. 2. Voltage Unbalance in Power System There are two commonly used definitions for voltage unbalance. The simple approach is the NEMA definition [Lin72] which gives a numerical description for voltage unbalance, VU, as: V VU = max V av (1) where Vav is the average value of three phase voltages and Vmax is the maximum voltage deviation from Vav. Most standards organisations such as IEEE [IEEE93], IEC [IEC90] and Australian Standards [AS86] also recognise the given definition as a way to express the voltage unbalance in a system of

2 Induction Motor Performance under Unbalanced Voltage Conditions 1 voltages. However, the given simple definition is only an approximation of the negative sequence component present in a system of unbalanced voltages. Example 1: If the line to neutral voltages of a system are: Van = 240 V Vbn = 230 V and Vcn = 250 V, then Vav = 240 V and VU = 10/240 = (4.2%). The second definition is based on the theory of symmetrical components in three phase systems where a set of 3-phase unbalanced voltages can be specified as three balanced symmetrical components namely; positive, negative and zero sequence components. The positive sequence components have the same sequence as the main system having a 120 degree phase shift. The negative sequence components, however, have a sequence opposite to the sequence of the main system. The zero sequence components have no phase shift and are ineffective in 3-wire 3-phase systems. As a standard definition, the voltage unbalance, known as the Voltage Unbalance Factor (VUF), is defined as the ratio of the negative sequence component to the positive sequence component [IEEE93] [IEC90] as: VUF V V = 2 1 (2) where V1 and V2 are the positive and negative sequence components respectively. Both V1 and V2 can be calculated using the magnitude and phase shift of the 3-phase voltages. This definition is more complicated than that defined by NEMA definition, Equation (1). Assuming 120 degree phase shift for the unbalanced voltages given in example 1, the positive and negative sequence values and the VUF are: V1= V V2 = 11.6 V VUF = V2/V1 = (4.8%)

3 Induction Motor Performance under Unbalanced Voltage Conditions 2 It can be seen that the positive sequence voltage is almost the same as the average value of the three phase voltages (ie V1=Vav) but the VU and the VUF defined by Equations (1) and (2) differ by more than 10%. Example 2: Van=245 V, Vbn=237 V and Vcn=238 V According to NEMA definition: Vav=240 V and VU=5/240=0.021 (2.1%). Using symmetrical components: V1=240.0 V, V2=5.1 V and VUF=V2/V1=0.021 (2.1%). It can be seen that the two figures (VU and VUF) are almost the same for the given unbalanced supply. According to a graphical presentation given in [Cum85] the two definitions are almost equivalent for unbalanced voltages of less than 4% defined according to NEMA definition. Increased losses and relatively large unbalanced currents are two of the main effects of voltage unbalance in relation to induction motors [And54] [Wil54] [Gaf59] [AS86] [IEC90]. Depending on the level of voltage unbalance the machine temperature tends to exceed the specified limits causing motor overheating. The severity of the voltage unbalance has been emphasised in early issues of NEMA publications where it has been reported that a 3.5% voltage unbalance can cause about 25% increase in machine temperature rise [Lin72]. The current imbalance may introduce difficulties in motor overcurrent protection and results in nonuniform distribution of heating in the stator windings. Reduced torque and full load speed and increased noise and vibration are also other unwanted effects of voltage unbalance present in the supply of induction motors [Wol75] [[AS86]. 3. Equivalent Circuits In order to analyse the induction motor performance under unbalanced voltage supply conditions two equivalent circuits corresponding to positive and negative sequence components can be developed [Wil54]. The positive sequence equivalent circuit is the same as the conventional equivalent circuit as shown in Figure 1 (a). The negative sequence component of the supply voltage produces

4 Induction Motor Performance under Unbalanced Voltage Conditions 3 an air gap flux which rotates at the synchronous speed but opposite to the direction of the rotor motion. Therefore, under normal operating conditions (ie low slip where s 0), the frequency of the rotor current due to the induced emf produced by the negative sequence component is almost twice that of the supply frequency, ie (2-s) f1. As a result of skin effect, both rotor resistance and leakage reactance will be different from the low slip values, X2 and R2. The new parameters X' 2 and R' 2 illustrated in a modified equivalent circuit of Figure 1 (b) represent the corresponding rotor parameters at frequency (2-s)f1. In general, R1, X1 and Xm remain the same in both circuits. For motors with double cage rotors and/or deep bar rotors, R' 2 >> R2 and X' 2 < X2 mainly due to rotor skin effect. As an example, in a 10 hp induction motor having a double cage rotor, R' 2 3R2 and X' X2 as reported in [Wil54]. For the same motor a single cage rotor has been designed where R' 2 R2 and X' 2 X2 [Wil54]. R X X R X X' V 1 X m R s 2 V 2 X m R' 2 2-s (a) (b) Figure 1: Equivalent circuits to determine positive (a) and negative (b) sequence impedances of an induction motor Nowadays, most induction motors are designed with double cage and/or deep bar rotors in order to utilise the high starting torque characteristics. Therefore, it is most likely that the rotor parameters under frequencies higher than the low slip value (nominally a small fraction of the supply frequency) are significantly higher than the nominal rotor parameters. A comparison of the equivalent circuits of Figure 1 (a) and (b) indicates that the rotor circuit corresponding to the negative sequence component has a relatively smaller impedance compared to the positive sequence equivalent circuit. The reason is obviously the term R' 2 / (2-s) in the rotor circuit of Figure 1 (b) as compared with the term R2 /s in Figure 1 (a). The overall negative sequence impedance, Z2, is about 10% to 20% of the positive sequence impedance, Z1 [And54] [Wil54] [Lin72] [Ber63]. Therefore, a small negative sequence voltage in the supply can cause rather a large negative sequence current in the motor and hence a relatively large unbalanced current. For instance, for 5% negative sequence voltage (VUF = 5%) present in the supply of a motor having

5 Induction Motor Performance under Unbalanced Voltage Conditions 4 Z2 = 15% Z1, the Unbalanced Current Factor (UCF=I2/I1) is calculated to be 33% as: I2 = V2/Z2 = 0.05 V1/0.15 Z1 = 0.33 I1. In addition to increased losses and reduced torque, such unbalance in the current might activate thermal relays used to protect the motor [And54]. 4. Unbalanced Voltage Tests on an Induction Motor In order to experimentally investigate the effects of unbalanced voltages on the performance of induction motors, a 3-phase high efficiency cage induction motor with specifications shown in Table 1 was selected for testing purposes. Power rating Nominal voltage/frequency Connection Full load current Full load speed 7.5 kw 415 V, 50 Hz 14.5 A 1440 rpm Full load efficiency 0.88 Full load power factor 0.82 Table 1: Specifications of the test induction motor 4.1 Experimental setup and test procedure A three phase variac was employed to supply the test motor under balanced and unbalanced voltage conditions. The unbalanced voltage was produced by connecting the mains supply to different taps available on the variac windings. The line-to-line voltages, three line currents and motor input power level were measured continuously using a 3-phase digital AC meter and calibrated voltmeters/ammeters. Since one of the objectives of the tests was to estimate the motor losses under different supply/load conditions, the double chamber calorimeter (DCC) [JalI97] was employed for the direct measurement of motor losses. The loaded machine tests were conducted using previously developed experimental setup as shown in Figure 2 [JalII97]. A DC generator supplying a

6 Induction Motor Performance under Unbalanced Voltage Conditions 5 load bank was coupled to the test motor via a flexible universal coupling. The motor loading level was adjusted to desired values by changing the field current of the DC generator. The power supplied to the load bank was calculated by measuring its DC voltage and current. The shaft speed was also measured during each test using a digital tachometer. Test induction motor Flexible coupling Insulation material (EPS) Stuffing box Plummer block Variable DC supply + - A V Load bank A Field + - V DC Generator Universal coupling Wooden base Bakelised canvas plates Metal test bed Figure 2: Experimental setup developed to conduct loaded machine tests under different supply conditions and loss measurement using the Double Chamber Calorimeter (DCC) 4.2 Experimental results and analysis Balanced supply conditions The first series of tests was conducted on the test motor supplied by balanced supply with the average line-to-line voltages adjusted to the nominal value of 415 V using the variac. The motor loading level was adjusted to cover the light load to full load conditions in seven steps. Each step was continued long enough to achieve the thermally steady state conditions for the motor operating inside the calorimeter. The motor line-to-line voltages, line currents, total motor input power, Pin, and motor shaft speed, N, were measured continuously during each test. The corresponding averaged values along with the motor total losses, Pm estimated using the DCC approach, the calculated motor shaft power, Pshaft (=Pin-Pm) and the calculated motor slip, s, are given in Table 2. The accuracy of the current and voltage measurement is ±0.5% while the input power, Pin are measured with a maximum uncertainty of ±1%. Motor losses, Pm are subject to a maximum error of ±4%.

7 Induction Motor Performance under Unbalanced Voltage Conditions 6 Averaged line Motor input input current: power: I in (A) P in (W) Motor Losses: P m (W) Motor shaft power: P shaft = P in -P m Shaft speed: N (rpm) Calculated slip: s=(n s -N)/N s Table 2: Measured quantities corresponding to test motor supplied by balanced supply voltages at different loading levels According to the motor ratings given in Table 1 the calculated input power under rated conditions ( 3*V*I*cosφ) and the measured input power (8860 W) differ by less than 4%. The calculated motor shaft power under rated conditions (7800 W) is also different compared to the motor rated power (7500 W) by 4%. The given discrepancies can be justified by consideration of the accuracy corresponding to the measured quantities (ie motor voltage, current and input power). Using the rated motor power (7500 W) and the full load efficiency (0.88) the motor losses is calculated to be 1023 W having a discrepancy of < 4% compared with the measured value (1060 W) which is again within the accuracy limits of the loss measurements. In order to find a relationship between the motor losses and the average input current a curve of the form A+B*Iin 2 was fitted to the measured data as illustrated in Figure 3 where A=207 and B=4.0. The maximum discrepancy between the measured losses and losses estimated using the fitted curve is less than 30 W which is within the accuracy limits of the motor loss measurement using the DCC.

8 Induction Motor Performance under Unbalanced Voltage Conditions measured Motor Losses: Pm (W) fitted: *Iin^ Input current: Iin (A) Figure 3: Measured motor losses vs motor input current along with the fitted curve The variation of motor shaft power, Pshaft,with motor input current, Iin, is illustrated in Figure 4. It can be seen that at smaller values of motor current the motor shaft power increases at a higher rate as compared with that at larger currents. Also for motor input currents greater than 10 A, motor shaft power increases almost linearly as: Pshaft = (591 Iin)-698. This linear relationship can be utilised to approximate the motor loading level as a function of averaged motor input current varying between 10 A and 15 A Motor shaft power: Pshaft (W) for 10A > Iin > 15A Pshaft=(591*Iin) Input current: Iin (A) Figure 4: Variation of motor shaft power vs motor input current under balanced rated supply voltage conditions

9 Induction Motor Performance under Unbalanced Voltage Conditions Unbalanced supply conditions The second and the third series of tests were conducted under two different unbalanced voltage conditions where the average line-to-line voltages was kept constant at nominal value of 415 V. The motor loading level was adjusted to four different conditions as: 1. light load, 2. half load, 3. full load 1 where the largest line current, Imax, equals to the rated current, and, 4. full load 2 where the averaged value of the three phase currents, Iav, equals to the rated current, Irated. The measured line-to-line voltages, Vab, Vbc and Vca along with the calculated average voltage, Vav, are given in Table 3. The positive and negative sequence components of the given voltages were also calculated, including for the first series of tests (Section 4.2.1), according to the principle of symmetrical components and the sine rule. These quantities along with the voltage unbalance factor, VUF, corresponding to each case are averaged and shown in Table 3. It can be seen that in all three cases, the average voltage, Vav, and the positive sequence voltage, V1, are of the same order of magnitude. The nominally balanced supply voltage (A) contains a small amount of negative sequence component giving a VUF of less than 0.4%. The slight unbalance in the variac output voltage (under balanced mode) is mainly due to the random fluctuations in the mains voltages as well as the physical asymmetry of the variac. Supply condition V ab (V) V bc (V) V ca (V) V av (V) V 1 (V) V 2 (V) VUF Balanced voltage (A) Unbalanced voltage I (B) Unbalanced voltage II (C) % % % Table 3: Measured line-to-line voltages and the calculated average, positive/negative sequence voltages and the VUF under different supply conditions

10 Induction Motor Performance under Unbalanced Voltage Conditions 9 For each series of tests the measured line currents, Ia, Ib and Ic, motor input power, Pin, and motor losses, Pm, are given in Table 4. The calculated average, positive/negative sequence currents, CUF (=I2/I1) and motor shaft output power, Pshaft (=Pin-Pm) are also given in Table 4. For the balanced voltage test (case A) only the rated load condition is considered where the line currents are unbalanced due to the slight imbalance in the voltage (ie VUF=0.39%). The average current, Iav, and the positive sequence current, I1, are almost the same and equal to the rated current of 14.5 A. The negative sequence current, I2, is about 0.5 A giving CUF=3.6%. With unbalanced voltages applied to the test motor (ie cases B and C), the averaged motor line currents and the positive sequence current increase with load while the negative sequence current remains almost unchanged. The CUF is much larger than the corresponding VUF indicating a small negative sequence impedance of the test motor compared with its positive sequence impedance. The CUF decreases as the motor loading level increases mainly due to the increase of the positive sequence current with load. It can be seen that the negative sequence current, I2, increases only with the VUF leading to average values of 0.5 A, 0.9 A and 3.3 A for cases A, B and C respectively. Measured Calculated Supply Case I a I b I c P in P m I av I 1 I 2 CUF P shaft = P 1 * P 2 * = condition (A) (A) (A) (W) (W) (A) (A) (A) P in -P m (W) P m -P 1 Balanced voltage (A) VUF=0.39% A % Unbalanced voltage I (B) B1 B % 12.4% VUF=1.35% B3 B % 6.5% Unbalanced voltage II (C) C1 C % 44.3% VUF=3.71% C3 C % 21.7% * P 1 and P 2 are the motor losses due to the positive and negative sequence components of the motor input currents respectively. P 1 is calculated according to the fitted curve given in Figure 3 as: P 1 = 207+4*I 1 2. Table 4: Measured and calculated quantities corresponding to test motor operating under different supply/load conditions

11 Induction Motor Performance under Unbalanced Voltage Conditions 10 A comparison between cases B3 and C3, where the largest line current is equal to the rated current (14.5 A), shows that the average current in the case C3 (VUF=3.71%) is smaller than that in case B3 (VUF=1.35%). In other words, with a larger VUF, the average motor current and hence the motor loading level should be reduced so that the largest current does not exceed the rated value. For cases A, B4 and C4 where Iav = 14.5 A, the variation of motor line currents, Ia, Ib and Ic, positive and negative sequence currents, I1 and I2, with VUF is shown in Figure 5. It can be seen that, as VUF increases, one of the line currents exceeds the rated current while the other two decrease below the rated value. While I1 decreases slightly with VUF, increase of the negative sequence current, I2, with VUF is evident from the graph. Current (A) Ic I1 Ia Ib VUF% I2 Figure 5: Measured motor line currents, and the calculated positive and negative sequence currents as a function of VUF under loaded conditions where Iav=14.5 A 4.3 Limits for the motor losses In cases B and C if the effect of motor extra heating (due to the presence of voltage unbalance) on stator and rotor resistances, R1 and R2 in Figure 1 (a), is neglected then motor losses due to the positive sequence current can be calculated. In other words, it can be assumed that the motor is only supplied by a rated balanced system of voltages drawing a balanced current with an average value equal to the positive sequence current, I1. Accordingly, motor losses due to the positive sequence current is calculated based on the fitted curve presented in Figure 3 and shown in Table 4 as P1. For each case, the difference Pm-P1 (called P2 in Table 4) can be accounted for the losses due to the negative sequence current I2. It can be seen that P2 increases significantly with VUF but,

12 Induction Motor Performance under Unbalanced Voltage Conditions 11 for a given VUF, it is almost unchanged with load as in most cases shown in Table 4. On average, P2 is about 1%, 5% and 13% of the total machine losses for cases A, B and C respectively. Motor Losses: P1 and Pm (W) measured (VUF=3.71%) measured (VUF=1.35%) estimated (VUF=0.39%) Rated loss level Positive sequence current, I1 (A) Figure 6: Estimated and measured motor losses at different supply/load conditions The variation of motor losses with I1 corresponding to balanced and unbalanced voltages is also illustrated in Figure 6 (the solid line is P1). In order to find limits for the losses in the test motor due to the given unbalanced voltages, a line representing the rated motor losses (in case A where P1=1048 W due to I1=14.5 A) is specified in Figure 6. The intersection of this line with the two curves gives two new values for the line current (14.1 A when UVF=1.35% and 13.1 A when UVF=3.71%). The motor losses due to these currents are likely to be equal to the rated losses. Using the curve given in Figure 4, the motor shaft power, Pshaft, (which represents the motor loading level) corresponding to the given currents is estimated and utilised to calculate the deviation of the motor loading level from the rated value as shown in the last column of Table 5. When VUF=1.35%, the machine should supply 98% of its rated load in order to achieve the rated motor losses. This figure reduces to 90% when a higher VUF, ie 3.71%, is present in the motor supply voltage. The average value of the line currents in both cases remain under the rated value, however, the CUF is still high. The calculated pu values of the motor loading level under different conditions are summarised in Table 5. It can be seen that the motor loading level should be reduced to 97% (in case B3) and 78% (in case C3) of its rated power in order to

13 Induction Motor Performance under Unbalanced Voltage Conditions 12 keep the maximum line current equal to the rated current (Imax=Irated). According to the data given in Table 4, motor losses has reduced the rated value by a factor of 3% in case B3 and 20% in case C3. Considering cases B4 and C4, where Iav = Irated, the motor operates above the rated loading condition as shown in Table 5. According to data given in Table 4, motor losses exceed the rated value by about 3% and 12% in cases B4 and C4 respectively. Also the maximum difference in the line currents is relatively high (1.6 A with CUF=6.5% in case B4 and 4.8 A with CUF=21.7% in case C4). Such a large unbalanced current can activate the motor protection overcurrent relays. Motor loading level (pu) VUF for for for I max = I rated I av = I rated Motor losses = Rated losses 0.39% 1.00 (case A) 1.00 (case A) 1.00 (case A) 1.35% 0.97 (case B3) 1.04 (case B4) % 0.78 (case C3) 1.02 (case C4) % % Table 5: Motor loading level under different supply conditions Considering cases A, B4 and C4 where Iav=Irated, the variation of motor losses with VUF along with a straight line fitted to the experimental data is illustrated in Figure 7. It is shown that with VUF=5% and 10% the motor total losses can increase to 1210 W and 1375 W respectively. These values are about 16% and 31% more than motor rated losses (1048 W).

14 Induction Motor Performance under Unbalanced Voltage Conditions W Motor losses (W) W Measured Fitted: *VUF% VUF% Figure 7: Motor loading level as a function of VUF at different conditions 1.4 Motor loading level (pu) Iav=Irated Losses=Rated Imax=Irated VUF% Figure 8: Motor loading level as a function of VUF for different conditions Using the fitted curves of Figures 3 and 4 the motor loading level is estimated to increase by more than 11% and 21% respectively. In order to reduce the losses to the rated level, the motor load should be reduced to 84% and 69% of the rated value respectively. These figures are approximated according to the estimated motor losses due to the given VUFs. The motor loading level should be further reduced if the condition Imax=Irated is considered. The approximate figures must be less than 70% (for VUF=5%) and 40% (for VUF=10%). In order to specify the motor loading levels under different conditions the corresponding

15 Induction Motor Performance under Unbalanced Voltage Conditions 14 figures are shown in Table 5. For comparison and clarity a graphical presentation of data given in Table 5 is also illustrated in Figure 8. It can be seen that in the worst case of VUF=10% the motor should be significantly derated in order to allow Imax=Irated. A similar graph is given in [IEEE93] and [AS86] where a the motor should operate at 75% of its rated loading level if a voltage unbalance of 5% is present in its supply. 5. Summary and Conclusions The effect of unbalanced supply voltage on induction motor operation has been reviewed in this report. The conventional definitions for the voltage unbalance have been given. The induction motor equivalent circuit corresponding to the positive and negative sequence components of the supply voltage have been presented and the basic differences have been highlighted. It has been reported that the motor negative sequence impedance is about 10-20% of the positive sequence impedance and hence a small unbalance in voltage could cause a relatively large unbalanced current which might cause problems in motor overcurrent protection. Additional losses, extra heating, unbalanced current and reduced torque are some of the unwanted effects of the unbalanced voltages applied to induction motors. The performance of a 7.5 kw induction motor operating under different supply/load conditions has been investigated in this report. Experimental tests have been conducted on the test motor under balanced and two unbalanced voltage conditions and at different loading levels. It has been shown that the additional losses due to the unbalanced voltages are almost independent of the motor loading level. However, additional motor losses are significantly increased with the level of voltage unbalance factor. It has been shown that the motor loading level should be reduced to 97%, 78%, 70% and <40% with VUF=1.35%, 3.71%, 5% and 10% respectively in order to keep the maximum line current at the rated value. In this case the current in the other two lines are smaller than the rated value and the total machine losses are less than the rated value. The current unbalance factor, however, significantly increases with VUF. Experimental tests have also been conducted to change the motor loading level so that the motor losses meet the rated value. To achieve this condition, it has been shown that the motor loading level should be reduced to 98%, 90%, 84% and 69% corresponding to VUF=1.35%, 3.71%, 5% and 10% respectively. These figures can be considered as the derating factors for the given test motor. In the case that the motor has a 1.15 service factor, it can tolerate unbalanced voltages

16 Induction Motor Performance under Unbalanced Voltage Conditions 15 with VUF up to about 4.5% without being derated. This figure is comparable with the maximum allowable VUF of 5% presented in the literature. Note: the effect of unbalanced voltage on hot spot temperature has not been studied in this report. 6. References [And54] Anderson, A., S., Ruete, R., C., "Voltage Unbalance in Delta Secondaries Serving Single-Phase and 3-Phase Loads" AIEE Transactions, Part III-B (Power Apparatus and Systems), Vol. 73, pp , August [AS86] [Ber63] Australian Standard AS , "Rotating Electrical Machines - General Requirements, Part 31: Service and Operating Conditions", Berndt, M., M., Schmitz, N., L., "Derating of Polyphase Induction Motors Operated with Unbalanced Line Voltages" AIEE Transactions, Part III-A (Power Apparatus and Systems), pp , Feb [Cum85] Cummings, P., G., Dunki-Jacobs, J., R. and Kerr, R., H., "Protection of Induction Motors Against Unbalanced Voltage Operation" IEEE Transactions on Industry Applications, Vol. IA- 21, No. 4, pp , May/June [Gaf59] [IEC90] Gafford, B., N., Duestrhoeft, W. C., Mosher, C., C., "Heating of Induction Motors on Unbalanced Voltages" AIEE Transactions, Part III-A (Power Apparatus and Systems), Vol. 78, pp , June IEC Publication , "Electromagnetic Compatibility (EMC), Part 2: Environment, Section 1: Description of the Environment - Electromagnetic Environment for Low Frequency Conducted Disturbances and Signalling in Public Power Supply Systems" [IEEE91] IEEE Standards 112: Test Procedure for Polyphase Induction Motors and Generators, [IEEE93] IEEE Standards 141, "IEEE Recommended Practice for Electric Power Distribution for Industrial Plants (Red Book), [JalI97] [JalII97] [Lin72] [Wil54] [Wol75] Jalilian, A., Gosbell, V.J., Cooper, P., Perera, B.S.P., "Double Chamber Calorimeter: a New Approach to Measure Induction Motor Harmonic Losses" Proceedings of the IEEE International Electric Machine and Drives Conference (IEMDC'97), pp. MB1/ , Milwukee, WI, May Jalilian, A., Perera, B.S.P., Gosbell, V.J., "Loading Effects in the Estimation of Induction Motor Harmonic Losses" Accepted for presentation in the Australian Universities Power Engineering Conference (AUPEC'97), University of NSW, Sept.-Oct Linders, J., R., "Effects of Power Supply Variations on AC Motor Characteristics" IEEE Transactions on Industry Applications, Vol. IA-8, No. 4, pp , July/August Williams, J., E., "Operation of 3-Phase Induction Motors on Unbalanced Voltages" AIEE Transactions, Part III-A (Power Apparatus and Systems), Vol. 73, pp , April Woll, R., F., "Effect of Unbalanced Voltage on the Operation of Polyphase Induction Motors" IEEE Transactions on Industry Applications, Vol. IA-11, No. 1, pp , Jan./Feb

SOURCES OF ERROR IN UNBALANCE MEASUREMENTS. V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson

SOURCES OF ERROR IN UNBALANCE MEASUREMENTS. V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson SOURCES OF ERROR IN UNBALANCE MEASUREMENTS V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson Integral Energy Power Quality Centre School of Electrical, Computer and Telecommunications Engineering

More information

Voltage Unbalance Effects on Induction Motor Performance

Voltage Unbalance Effects on Induction Motor Performance Proceedings of the 6th WSEAS International Conference on Simulation, Modelling and Optimization, Lisbon, Portugal, September -4, 006 11 Voltage Unbalance Effects on Induction Motor Performance L. REFOUFI,

More information

SYNCHRONOUS MACHINES

SYNCHRONOUS MACHINES SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical

More information

Code No: R Set No. 1

Code No: R Set No. 1 Code No: R05220204 Set No. 1 II B.Tech II Semester Supplimentary Examinations, Aug/Sep 2007 ELECTRICAL MACHINES-II (Electrical & Electronic Engineering) Time: 3 hours Max Marks: 80 Answer any FIVE Questions

More information

Behavior of Induction Motor at Voltage Unbalanced

Behavior of Induction Motor at Voltage Unbalanced Behavior of Induction Motor at Voltage Unbalanced Rajashree U Patil Electrical Engineering MTech Power Student, VJTI Matunga, Mumbai, India Abstract A three phase induction motors are very commonly employed

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

THE UNIVERSITY OF BRITISH COLUMBIA. Department of Electrical and Computer Engineering. EECE 365: Applied Electronics and Electromechanics

THE UNIVERSITY OF BRITISH COLUMBIA. Department of Electrical and Computer Engineering. EECE 365: Applied Electronics and Electromechanics THE UNIVERSITY OF BRITISH COLUMBIA Department of Electrical and Computer Engineering EECE 365: Applied Electronics and Electromechanics Final Exam / Sample-Practice Exam Spring 2008 April 23 Topics Covered:

More information

PESIT Bangalore South Campus Hosur road, 1km before Electronic City, Bengaluru -100 Department of Electronics & Communication Engineering

PESIT Bangalore South Campus Hosur road, 1km before Electronic City, Bengaluru -100 Department of Electronics & Communication Engineering INTERNAL ASSESSMENT TEST 3 Date : 15/11/16 Marks: 0 Subject & Code: BASIC ELECTRICAL ENGINEERING -15ELE15 Sec : F,G,H,I,J,K Name of faculty : Mrs.Hema, Mrs.Dhanashree, Mr Nagendra, Mr.Prashanth Time :

More information

Frequency Converter Influence on Induction Motor Rotor Faults Detection Using Motor Current Signature Analysis Experimental Research

Frequency Converter Influence on Induction Motor Rotor Faults Detection Using Motor Current Signature Analysis Experimental Research SDEMPED 03 Symposium on Diagnostics for Electric Machines, Power Electronics and Drives Atlanta, GA, USA, 24-26 August 03 Frequency Converter Influence on Induction Motor Rotor Faults Detection Using Motor

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

Journal of World s Electrical Engineering and Technology J. World. Elect. Eng. Tech. 3(1): 18-25, 2014

Journal of World s Electrical Engineering and Technology J. World. Elect. Eng. Tech. 3(1): 18-25, 2014 ORIGINAL ARTICLE Received 25 Dec. 2013 Accepted 07 March. 2014 2014, Scienceline Publication www.science-line.com 2322-5114 Journal of World s Electrical Engineering and Technology J. World. Elect. Eng.

More information

Voltage and Current Waveforms Enhancement using Harmonic Filters

Voltage and Current Waveforms Enhancement using Harmonic Filters Voltage and Current Waveforms Enhancement using Harmonic Filters Rajeb Ibsaim rabsaim@yahoo.com, Azzawia University, Libya Amer Daeri ibnjubair1@yahoo.co.uk Azzawia University, Libya Abstract The demand

More information

Assessment of Energy Efficient and Standard Induction Motor in MATLAB Environment

Assessment of Energy Efficient and Standard Induction Motor in MATLAB Environment Volume 4 Issue 4 December 2016 ISSN: 2320-9984 (Online) International Journal of Modern Engineering & Management Research Website: www.ijmemr.org Assessment of Energy Efficient and Standard Induction Motor

More information

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at   Modeling and Analysis of Transformer ISSN: 2454-132X Impact factor: 4.295 (Volume 3, Issue 6) Available online at www.ijariit.com Modeling and Analysis of Transformer Divyapradeepa.T Department of Electrical and Electronics, Rajalakshmi Engineering

More information

ROTOR FAULTS DETECTION IN SQUIRREL-CAGE INDUCTION MOTORS BY CURRENT SIGNATURE ANALYSIS

ROTOR FAULTS DETECTION IN SQUIRREL-CAGE INDUCTION MOTORS BY CURRENT SIGNATURE ANALYSIS ROTOR FAULTS DETECTION IN SQUIRREL-CAGE INDUCTION MOTORS BY CURRENT SIGNATURE ANALYSIS SZABÓ Loránd DOBAI Jenő Barna BIRÓ Károly Ágoston Technical University of Cluj (Romania) 400750 Cluj, P.O. Box 358,

More information

Three-Phase Induction Motors. By Sintayehu Challa ECEg332:-Electrical Machine I

Three-Phase Induction Motors. By Sintayehu Challa ECEg332:-Electrical Machine I Three-Phase Induction Motors 1 2 3 Classification of AC Machines 1. According to the type of current Single Phase and Three phase 2. According to Speed Constant Speed, Variable Speed and Adjustable Speed

More information

An Improved Method for Protection of Three Phase Induction Motor using Microcontroller

An Improved Method for Protection of Three Phase Induction Motor using Microcontroller An Improved Method for Protection of Three Phase Induction Motor using Microcontroller Gagan Garg M.E. Student, EIED Thapar University, Patiala, India gagan_garg1989@yahoo.co.in Abstract A low cost and

More information

Generator Advanced Concepts

Generator Advanced Concepts Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves

More information

Pump ED 101. Two Steps To Increased Pump Life (Part Two) Voltage Unbalance

Pump ED 101. Two Steps To Increased Pump Life (Part Two) Voltage Unbalance Pump ED 101 Two Steps To Increased Pump Life (Part Two) Voltage Unbalance Joe Evans, Ph.D http://www.pumped101.com Last month we investigated the importance of identifying the actual operating point of

More information

Unbalance Detection in Flexible Rotor Using Bridge Configured Winding Based Induction Motor

Unbalance Detection in Flexible Rotor Using Bridge Configured Winding Based Induction Motor Unbalance Detection in Flexible Rotor Using Bridge Configured Winding Based Induction Motor Natesan Sivaramakrishnan, Kumar Gaurav, Kalita Karuna, Rahman Mafidur Department of Mechanical Engineering, Indian

More information

Electrical Machines (EE-343) For TE (ELECTRICAL)

Electrical Machines (EE-343) For TE (ELECTRICAL) PRACTICALWORKBOOK Electrical Machines (EE-343) For TE (ELECTRICAL) Name: Roll Number: Year: Batch: Section: Semester: Department: N.E.D University of Engineering &Technology, Karachi Electrical Machines

More information

Sizing Generators for Leading Power Factor

Sizing Generators for Leading Power Factor Sizing Generators for Leading Power Factor Allen Windhorn Kato Engineering 24 February, 2014 Generator Operation with a Leading Power Factor Generators operating with a leading power factor may experience

More information

Energy Analysis of a Three-Phase Induction Motor Under Unbalanced Voltage Using Simulation and Symmetrical Component

Energy Analysis of a Three-Phase Induction Motor Under Unbalanced Voltage Using Simulation and Symmetrical Component Energy Analysis of a Three-Phase Induction Motor Under Unbalanced Voltage Using Simulation and Symmetrical Component Abstract Three phase induction motors are widely used in industrial, commercial and

More information

AN ANN BASED FAULT DETECTION ON ALTERNATOR

AN ANN BASED FAULT DETECTION ON ALTERNATOR AN ANN BASED FAULT DETECTION ON ALTERNATOR Suraj J. Dhon 1, Sarang V. Bhonde 2 1 (Electrical engineering, Amravati University, India) 2 (Electrical engineering, Amravati University, India) ABSTRACT: Synchronous

More information

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 00 0 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK Course Name Course Code Class Branch : ELECRICAL MACHINES - II : A0 :

More information

UNBALANCED CURRENT BASED TARRIF

UNBALANCED CURRENT BASED TARRIF UNBALANCED CURRENT BASED TARRIF Hossein ARGHAVANI Tehran Electricity Distribution (TBTB) Co.-Iran hosein.argavani@gmail.com ABSTRACT The voltage &current unbalance are serious power quality problems with

More information

NERC Protection Coordination Webinar Series July 15, Jon Gardell

NERC Protection Coordination Webinar Series July 15, Jon Gardell Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

VALLIAMMAI ENGINEERING COLLEGE

VALLIAMMAI ENGINEERING COLLEGE VALLIAMMAI ENGINEERING COLLEGE SRM Nagar, Kattankulathur 603 203 DEPARTMENT OF ELECTRONICS AND INSTRUMENTATION ENGINEERING QUESTION BANK IV SEMESTER EI6402 ELECTRICAL MACHINES Regulation 2013 Academic

More information

CHAPTER 2 D-Q AXES FLUX MEASUREMENT IN SYNCHRONOUS MACHINES

CHAPTER 2 D-Q AXES FLUX MEASUREMENT IN SYNCHRONOUS MACHINES 22 CHAPTER 2 D-Q AXES FLUX MEASUREMENT IN SYNCHRONOUS MACHINES 2.1 INTRODUCTION For the accurate analysis of synchronous machines using the two axis frame models, the d-axis and q-axis magnetic characteristics

More information

Placement Paper For Electrical

Placement Paper For Electrical Placement Paper For Electrical Q.1 The two windings of a transformer is (A) conductively linked. (B) inductively linked. (C) not linked at all. (D) electrically linked. Ans : B Q.2 A salient pole synchronous

More information

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad ELECTRICAL AND ELECTRONICS ENGINEERING

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad ELECTRICAL AND ELECTRONICS ENGINEERING Course Name Course Code Class Branch INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 500 043 ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK : ELECRICAL MACHINES I : A40212

More information

INVESTIGATION OF THE IMPACT OF SPEED-RIPPLE AND INERTIA ON THE STEADY-STATE CURRENT SPECTRUM OF A DFIG WITH UNBALANCED ROTOR

INVESTIGATION OF THE IMPACT OF SPEED-RIPPLE AND INERTIA ON THE STEADY-STATE CURRENT SPECTRUM OF A DFIG WITH UNBALANCED ROTOR INVESTIGATION OF THE IMPACT OF SPEED-RIPPLE AND INERTIA ON THE STEADY-STATE CURRENT SPECTRUM OF A DFIG WITH UNBALANCED ROTOR S. Djurović*, S. Williamson *School of Electrical and Electronic Engineering,

More information

Dhanalakshmi Srinivasan Institute of Technology, Samayapuram, Trichy. Cycle 2 EE6512 Electrical Machines II Lab Manual

Dhanalakshmi Srinivasan Institute of Technology, Samayapuram, Trichy. Cycle 2 EE6512 Electrical Machines II Lab Manual Cycle 2 EE652 Electrical Machines II Lab Manual CIRCUIT DIAGRAM FOR SLIP TEST 80V DC SUPPLY 350Ω, 2 A 3 Point Starter L F A NAME PLATE DETAILS: 3Ф alternator DC shunt motor FUSE RATING: Volts: Volts: 25%

More information

The power transformer

The power transformer ELEC0014 - Introduction to power and energy systems The power transformer Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 35 Power transformers are used: to transmit

More information

Chapter Objectives: Payam zarbakhsh EElE301 Circuit Theory II Department of Electrical and Electronic Engineering Cyprus International university

Chapter Objectives: Payam zarbakhsh EElE301 Circuit Theory II Department of Electrical and Electronic Engineering Cyprus International university Chapter 12 Three Phase Circuits Chapter Objectives: Be familiar with different three-phase configurations and how to analyze them. Know the difference between balanced and unbalanced circuits Learn about

More information

Alternators Reactance for Nonlinear Loads

Alternators Reactance for Nonlinear Loads Alternators Reactance for Nonlinear Loads Allen Windhorn. P.E. 26 July, 2013 Introduction Widespread invocation of IEEE Std 519 on systems powered by generators, together with increased use of equipment

More information

Investigating the effects of Unbalanced Voltages and Voltage Harmonics on a Three-Phase Induction Motors Performance

Investigating the effects of Unbalanced Voltages and Voltage Harmonics on a Three-Phase Induction Motors Performance Investigating the effects of Unbalanced Voltages and Voltage Harmonics on a Three-Phase Induction Motors Performance School of Engineering and Energy This report is submitted to the School of Engineering

More information

CHAPTER 3 EQUIVALENT CIRCUIT AND TWO AXIS MODEL OF DOUBLE WINDING INDUCTION MOTOR

CHAPTER 3 EQUIVALENT CIRCUIT AND TWO AXIS MODEL OF DOUBLE WINDING INDUCTION MOTOR 35 CHAPTER 3 EQUIVALENT CIRCUIT AND TWO AXIS MODEL OF DOUBLE WINDING INDUCTION MOTOR 3.1 INTRODUCTION DWIM consists of two windings on the same stator core and a squirrel cage rotor. One set of winding

More information

Study on effects of supply voltage asymmetry and distortion on induction machine

Study on effects of supply voltage asymmetry and distortion on induction machine Louisiana State University LSU Digital Commons LSU Master's Theses Graduate School 2013 Study on effects of supply voltage asymmetry and distortion on induction machine Prashanna Dev Bhattarai Louisiana

More information

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 00 03 ELECTRICAL AND ELECTRONICS ENGINEERING ASSIGNMENT Course Name : ELECRICAL MACHINES - II Course Code : A0 Class : II B.TECH-II

More information

Application Note. GE Grid Solutions. Multilin 8 Series 869 Broken Rotor Bar Detection. Introduction

Application Note. GE Grid Solutions. Multilin 8 Series 869 Broken Rotor Bar Detection. Introduction GE Grid Solutions Multilin 8 Series 869 Broken Rotor Bar Detection Application Note GE Publication Number: GET-20061 Copyright 2018 GE Multilin Inc. Introduction The Multilin 869 motor protection relay

More information

CHAPTER-III MODELING AND IMPLEMENTATION OF PMBLDC MOTOR DRIVE

CHAPTER-III MODELING AND IMPLEMENTATION OF PMBLDC MOTOR DRIVE CHAPTER-III MODELING AND IMPLEMENTATION OF PMBLDC MOTOR DRIVE 3.1 GENERAL The PMBLDC motors used in low power applications (up to 5kW) are fed from a single-phase AC source through a diode bridge rectifier

More information

Experiment 3. Performance of an induction motor drive under V/f and rotor flux oriented controllers.

Experiment 3. Performance of an induction motor drive under V/f and rotor flux oriented controllers. University of New South Wales School of Electrical Engineering & Telecommunications ELEC4613 - ELECTRIC DRIVE SYSTEMS Experiment 3. Performance of an induction motor drive under V/f and rotor flux oriented

More information

UNIT-III STATOR SIDE CONTROLLED INDUCTION MOTOR DRIVE

UNIT-III STATOR SIDE CONTROLLED INDUCTION MOTOR DRIVE UNIT-III STATOR SIDE CONTROLLED INDUCTION MOTOR DRIVE 3.1 STATOR VOLTAGE CONTROL The induction motor 'speed can be controlled by varying the stator voltage. This method of speed control is known as stator

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES

More information

ELG2336 Introduction to Electric Machines

ELG2336 Introduction to Electric Machines ELG2336 Introduction to Electric Machines Magnetic Circuits DC Machine Shunt: Speed control Series: High torque Permanent magnet: Efficient AC Machine Synchronous: Constant speed Induction machine: Cheap

More information

CHAPTER 3 FAULT DETECTION SCHEMES FOR THREE PHASE INDUCTION MOTOR

CHAPTER 3 FAULT DETECTION SCHEMES FOR THREE PHASE INDUCTION MOTOR 62 CHAPTER 3 FAULT DETECTION SCHEMES FOR THREE PHASE INDUCTION MOTOR 3.1 INTRODUCTION Induction motors play a vital role in industries. Reliability of drive systems with these motors has a serious economical

More information

IOCL Electrical Engineering Technical Paper

IOCL Electrical Engineering Technical Paper IOCL Electrical Engineering Technical Paper 1. Which one of the following statements is NOT TRUE for a continuous time causal and stable LTI system? (A) All the poles of the system must lie on the left

More information

[71 Baran M.E and WU, F. "Network rcconfiguration in distribution system for. References:

[71 Baran M.E and WU, F. Network rcconfiguration in distribution system for. References: References: (I) William H. Kersting, "Distribution system modeling and Analysis", CRC Press, Boca-Raton, langdon. September I 994. (2) M.H.J. Bollen, Understanding power quality problems- voltage sags

More information

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit CHAPTER 2 Basic Concepts, Three-Phase Review, and Per Unit 1 AC power versus DC power DC system: - Power delivered to the load does not fluctuate. - If the transmission line is long power is lost in the

More information

Comparison and Detection of Abnormal Conditions in Induction Motors

Comparison and Detection of Abnormal Conditions in Induction Motors Comparison and Detection of Abnormal Conditions in Induction Motors Mehrdad Heidari 1, Ghodratollah Seifossadat 2, Davar Mirabbasi 1 mehrdad266@yahoo.com, seifossadat@yahoo.com, dmirabbasi@yahoo.com 1

More information

1. Explain in detail the constructional details and working of DC motor.

1. Explain in detail the constructional details and working of DC motor. DHANALAKSHMI SRINIVASAN INSTITUTE OF RESEARCH AND TECHNOLOGY, PERAMBALUR DEPT OF ECE EC6352-ELECTRICAL ENGINEERING AND INSTRUMENTATION UNIT 1 PART B 1. Explain in detail the constructional details and

More information

1 INTRODUCTION 2 MODELLING AND EXPERIMENTAL TOOLS

1 INTRODUCTION 2 MODELLING AND EXPERIMENTAL TOOLS Investigation of Harmonic Emissions in Wound Rotor Induction Machines K. Tshiloz, D.S. Vilchis-Rodriguez, S. Djurović The University of Manchester, School of Electrical and Electronic Engineering, Power

More information

1. SQUIRREL CAGE AC MOTOR. NO LOAD TEST

1. SQUIRREL CAGE AC MOTOR. NO LOAD TEST 1. SQUIRREL CAGE AC MOTOR. NO LOAD TEST 1.1 INTRODUCTION. DESCRIPTION OF THE EXPERIMENT The three-phase induction motor carries a three-phase winding on its stator. The rotor is either a wound type or

More information

3.1.Introduction. Synchronous Machines

3.1.Introduction. Synchronous Machines 3.1.Introduction Synchronous Machines A synchronous machine is an ac rotating machine whose speed under steady state condition is proportional to the frequency of the current in its armature. The magnetic

More information

SIGNATURE ANALYSIS FOR ON-LINE MOTOR DIAGNOSTICS

SIGNATURE ANALYSIS FOR ON-LINE MOTOR DIAGNOSTICS Page 1 of 10 2015-PPIC-0187 SIGNATURE ANALYSIS FOR ON-LINE MOTOR DIAGNOSTICS Ian Culbert Senior Member, IEEE Qualitrol-Iris Power 3110 American Drive Mississauga, ON Canada Abstract - Stator current signature

More information

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS 2-1. General but less than locked-rotor amperes and flows only Electrical power systems must be designed to serve in the normal circuit path. a variety of

More information

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE 58 CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE 4.1 INTRODUCTION Conventional voltage source inverter requires high switching frequency PWM technique to obtain a quality output

More information

IN MANY industrial applications, ac machines are preferable

IN MANY industrial applications, ac machines are preferable IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 46, NO. 1, FEBRUARY 1999 111 Automatic IM Parameter Measurement Under Sensorless Field-Oriented Control Yih-Neng Lin and Chern-Lin Chen, Member, IEEE Abstract

More information

Unit FE-5 Foundation Electricity: Electrical Machines

Unit FE-5 Foundation Electricity: Electrical Machines Unit FE-5 Foundation Electricity: Electrical Machines What this unit is about Power networks consist of large number of interconnected hardware. This unit deals specifically with two types of hardware:

More information

Alternative Approaches and Dynamic Analysis Considerations for Detecting Open Phase Conductors in Three Phase Power Systems

Alternative Approaches and Dynamic Analysis Considerations for Detecting Open Phase Conductors in Three Phase Power Systems Alternative Approaches and Dynamic Analysis Considerations for Detecting Open Phase Conductors in Three Phase Power Systems Robert M. Carritte, Kawa Cheung, Mohit Malik Abstract-- Open phase conductors

More information

V. Ramakrishnan 1, and S.K. Srivatsa 2 1

V. Ramakrishnan 1, and S.K. Srivatsa 2 1 International Journal of Power Unbalance Elecronics and and Induction Technology Machines January-June 2011, Volume 1, Number 1, pp. 61 81 V. Ramakrishnan 1, and S.K. Srivatsa 2 1 Department of EEE, Bharath

More information

Analysis Of Induction Motor With Broken Rotor Bars Using Discrete Wavelet Transform Princy P 1 and Gayathri Vijayachandran 2

Analysis Of Induction Motor With Broken Rotor Bars Using Discrete Wavelet Transform Princy P 1 and Gayathri Vijayachandran 2 Analysis Of Induction Motor With Broken Rotor Bars Using Discrete Wavelet Transform Princy P 1 and Gayathri Vijayachandran 2 1 Dept. Of Electrical and Electronics, Sree Buddha College of Engineering 2

More information

Contents. About the Authors. Abbreviations and Symbols

Contents. About the Authors. Abbreviations and Symbols About the Authors Preface Abbreviations and Symbols xi xiii xv 1 Principal Laws and Methods in Electrical Machine Design 1 1.1 Electromagnetic Principles 1 1.2 Numerical Solution 9 1.3 The Most Common

More information

STEADY STATE REACTANCE

STEADY STATE REACTANCE INDEX NO. : M-53 TECHNICAL MANUAL FOR STEADY STATE REACTANCE Manufactured by : PREMIER TRADING CORPORATION (An ISO 9001:2008 Certified Company) 212/1, Mansarover Civil Lines, MEERUT. Phone : 0121-2645457,

More information

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY LIST OF TOPICS 1 Electric Circuit Principles 2 Electronic Circuit Principles 3 Generation 4 Distribution 5 Utilisation The expected learning outcome is

More information

REV NO EXPERIMENT NO 1 AIM: To perform open and short circuit tests on 1-phase transformer and to calculate efficiency. Apparatus required:

REV NO EXPERIMENT NO 1 AIM: To perform open and short circuit tests on 1-phase transformer and to calculate efficiency. Apparatus required: KARNAL INSTITUTE OF TECHNOLOGY & MANAGEMENT KUNJPURA, KARNAL LAB MANUAL OF ------- SUBJECT CODE DATE OF ISSUE: SEMESTER: BRANCH: REV NO EXPERIMENT NO 1 AIM: To perform open and short circuit tests on 1-phase

More information

EE 410/510: Electromechanical Systems Chapter 5

EE 410/510: Electromechanical Systems Chapter 5 EE 410/510: Electromechanical Systems Chapter 5 Chapter 5. Induction Machines Fundamental Analysis ayssand dcontrol o of Induction Motors Two phase induction motors Lagrange Eqns. (optional) Torque speed

More information

Reg. No. : BASIC ELECTRICAL TECHNOLOGY (ELE 101)

Reg. No. : BASIC ELECTRICAL TECHNOLOGY (ELE 101) Department of Electrical and Electronics Engineering Reg. No. : MNIPL INSTITUTE OF TECHNOLOGY, MNIPL ( Constituent Institute of Manipal University, Manipal) FIRST SEMESTER B.E. DEGREE MKEUP EXMINTION (REVISED

More information

Generalized Theory Of Electrical Machines

Generalized Theory Of Electrical Machines Essentials of Rotating Electrical Machines Generalized Theory Of Electrical Machines All electrical machines are variations on a common set of fundamental principles, which apply alike to dc and ac types,

More information

Assessing network compliance for power quality performance

Assessing network compliance for power quality performance University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part A Faculty of Engineering and Information Sciences 214 Assessing network compliance for power quality

More information

VIDYARTHIPLUS - ANNA UNIVERSITY ONLINE STUDENTS COMMUNITY UNIT 1 DC MACHINES PART A 1. State Faraday s law of Electro magnetic induction and Lenz law. 2. Mention the following functions in DC Machine (i)

More information

Simulation of Sensorless Digital Control of BLDC Motor Based on Zero Cross Detection

Simulation of Sensorless Digital Control of BLDC Motor Based on Zero Cross Detection Simulation of Sensorless Digital Control of BLDC Motor Based on Zero Cross Detection S.P. Ajitha 1, S. Bagavathy 2, Dr. P. Maruthu Pandi 3 1 PG Scholar, Department of Power Electronics and Drives, Sri

More information

3. What is hysteresis loss? Also mention a method to minimize the loss. (N-11, N-12)

3. What is hysteresis loss? Also mention a method to minimize the loss. (N-11, N-12) DHANALAKSHMI COLLEGE OF ENGINEERING, CHENNAI DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE 6401 ELECTRICAL MACHINES I UNIT I : MAGNETIC CIRCUITS AND MAGNETIC MATERIALS Part A (2 Marks) 1. List

More information

PRECISE ASSESSMENT OF PERFORMANCE OF INDUCTION MOTOR UNDER SUPPLY IMBALANCE THROUGH IMPEDANCE UNBALANCE FACTOR

PRECISE ASSESSMENT OF PERFORMANCE OF INDUCTION MOTOR UNDER SUPPLY IMBALANCE THROUGH IMPEDANCE UNBALANCE FACTOR Journal of ELECTRICAL ENGINEERING, VOL. 64, NO. 1, 201, 1 7 PRECISE ASSESSMENT OF PERFORMANCE OF INDUCTION MOTOR UNDER SUPPLY IMBALANCE THROUGH IMPEDANCE UNBALANCE FACTOR Shashi Bhushan Singh Asheesh Kumar

More information

Flicker Attenuation Part I: Response of Three- Phase Induction Motors to Regular Voltage Fluctuations

Flicker Attenuation Part I: Response of Three- Phase Induction Motors to Regular Voltage Fluctuations University of Wollongong Research Online Faculty of Informatics - Papers (Archive) Faculty of Engineering and Information Sciences 2008 Flicker Attenuation Part I: Response of Three- Phase Induction Motors

More information

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Short-Circuit Analysis IEC Standard 1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Purpose of Short-Circuit Studies A Short-Circuit Study can be used to determine any or all of

More information

Power Plant and Transmission System Protection Coordination Fundamentals

Power Plant and Transmission System Protection Coordination Fundamentals Power Plant and Transmission System Protection Coordination Fundamentals NERC Protection Coordination Webinar Series June 2, 2010 Jon Gardell Agenda 2 Objective Introduction to Protection Generator and

More information

CHAPTER 8: ELECTROMAGNETISM

CHAPTER 8: ELECTROMAGNETISM CHAPTER 8: ELECTROMAGNETISM 8.1: MAGNETIC EFFECT OF A CURRENT-CARRYING CONDUCTOR Electromagnets 1. Conductor is a material that can flow.. 2. Electromagnetism is the study of the relationship between.and..

More information

Keywords: unbalanced voltage, unbalanced current, Load balancing transformer

Keywords: unbalanced voltage, unbalanced current, Load balancing transformer Effects of Distorted Source on Operating a Load-Balancing Transformer in a Distribution Network Danial Ahmadi Mohammad Tavakoli Bina Masoud Aliakbar Golkar Faculty of Electrical Engineering, K. N. Toosi

More information

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945

More information

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage 1 New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage B. B. Pimple, V. Y. Vekhande and B. G. Fernandes Department of Electrical Engineering, Indian Institute of Technology Bombay,

More information

Analysis of Wound Rotor Induction Machine Low Frequency Vibroacoustic Emissions under Stator Winding Fault Conditions

Analysis of Wound Rotor Induction Machine Low Frequency Vibroacoustic Emissions under Stator Winding Fault Conditions Analysis of Wound Rotor Induction Machine Low Frequency Vibroacoustic Emissions under Stator Winding Fault Conditions N Sarma, Q Li, S. Djurović, A C Smith, S M Rowland University of Manchester, School

More information

External Drive Hardware

External Drive Hardware US1086e_External Drive Hardware, 08/2010 External Drive Hardware Selection and Application Answers Answers to external hardware questions A soup to nuts list of questions with installation / application

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

Analysis of Indirect Temperature-Rise Tests of Induction Machines Using Time Stepping Finite Element Method

Analysis of Indirect Temperature-Rise Tests of Induction Machines Using Time Stepping Finite Element Method IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 16, NO. 1, MARCH 2001 55 Analysis of Indirect Temperature-Rise Tests of Induction Machines Using Time Stepping Finite Element Method S. L. Ho and W. N. Fu Abstract

More information

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY WN U-60 Attachment C to Schedule 152, Page 1 SCHEDULE 152 APPLICATION FOR INTERCONNECTING A GENERATING FACILITY TIER 2 OR TIER 3 This Application is considered complete when it provides all applicable

More information

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number:  Address: NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information

More information

INDUCTION MOTOR FAULT DIAGNOSTICS USING FUZZY SYSTEM

INDUCTION MOTOR FAULT DIAGNOSTICS USING FUZZY SYSTEM INDUCTION MOTOR FAULT DIAGNOSTICS USING FUZZY SYSTEM L.Kanimozhi 1, Manimaran.R 2, T.Rajeshwaran 3, Surijith Bharathi.S 4 1,2,3,4 Department of Mechatronics Engineering, SNS College Technology, Coimbatore,

More information

O V E R V I E W O F T H E

O V E R V I E W O F T H E A CABLE Technicians TESTING Approach to Generator STANDARDS: Protection O V E R V I E W O F T H E 1 Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments

More information

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21 Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive

More information

Short-Circuit Current Calculations

Short-Circuit Current Calculations Basic Point-to-Point Calculation Procedure Step. Determine the transformer full load amps (F.L.A.) from either the nameplate, the following formulas or Table : Multiplier = 00 *% Z transformer Step 2.

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information

POWER SYSTEM II LAB MANUAL

POWER SYSTEM II LAB MANUAL POWER SYSTEM II LAB MANUAL (CODE : EE 692) JIS COLLEGE OF ENGINEERING (An Autonomous Institution) Electrical Engineering Department Kalyani, Nadia POWER SYSTEM II CODE : EE 692 Contacts :3P Credits : 2

More information

Preface...x Chapter 1 Electrical Fundamentals

Preface...x Chapter 1 Electrical Fundamentals Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5

More information

Stator Fault Detector for AC Motors Based on the TMS320F243 DSP Controller

Stator Fault Detector for AC Motors Based on the TMS320F243 DSP Controller Stator Fault Detector for AC Motors Based on the TMS320F243 DSP Controller Bin Huo and Andrzej M. Trzynadlowski University of Nevada, Electrical Engineering Department/260, Reno, NV 89557-0153 Ph. (775)

More information

DISCUSSION OF FUNDAMENTALS

DISCUSSION OF FUNDAMENTALS Unit 4 AC s UNIT OBJECTIVE After completing this unit, you will be able to demonstrate and explain the operation of ac induction motors using the Squirrel-Cage module and the Capacitor-Start Motor module.

More information

Lecture 4 - Three-phase circuits, transformer and transient analysis of RLC circuits. Figure 4.1

Lecture 4 - Three-phase circuits, transformer and transient analysis of RLC circuits. Figure 4.1 Lecture 4 - Three-phase circuits, transformer and transient analysis of RLC circuits Power supply to sizeable power converters are often from three-phase AC source. A balanced three-phase source consists

More information

CHAPTER - 3. Induction Motor External Faults and its Simulation

CHAPTER - 3. Induction Motor External Faults and its Simulation Induction Motor CHAPTER - 3 Induction Motor External Faults and its Simulation 3.1 Induction Motor Induction motors are complex electromechanical devices widely used for conversion of power from electrical

More information