1 LOW POWER FLOW COMPUTERS Greg Phillips Bristol Babcock Inc Governors Circle West, Suite F, Houston, TX INTRODUCTION Flow computers, themselves, are undergoing an evolution. One challenge for most vendors will be to offer a low power flow computer whose pricing approaches that of a three variable chart recorder. Many companies in the gas transmission, gas distribution and production industry; expect such a flow computer to be an evolution from today s smart transmitter technology, because of improved accuracy and innovation of multi-variable transmitters. That is to say, differential pressure, static pressure and temperature all in one transmitter. REQUIREMENTS The key operations, performed by low power flow computers include calculations, historical data storage, alarm/event logging, network communications for realtime or near-time data acquisition, trending of variables and flow rate to include data editing capability. Each of today s flow computers offers some subset of the following calculations: AGA3: Corrected flow for orifice meters. (Orifice) 1992 edition AGA5: Energy content (BTU) AGA7: Corrected flow for linear meters. (Turbine, PD) NX19: Compressibility AGA8: Super compressibility (Detailed and Gross) The low power flow computer (LPFC) of today requires that it be designed to provide high performance while minimizing the overall EGM installation cost. These electronic gas measurement locations vary from site to site; in most cases commercial power is not available, thus the need for LPFC s that can operate on direct current (DC) power sources. These power sources for remote locations can be battery power, for instance a lithium battery or alkaline battery. The lithium battery can provide longer life over a greater temperature range, while the alkaline battery is limited. The other most commonly used are the solar panel with lead acid or gel cell battery, this power source usually offered as an integral package with the LPFC includes panel, charger/regulator, battery, cabling and mounting hardware. The size and cost of the solar array will depend on the geographical location and power requirements of the LPFC. The energy from the sun creates a photovoltaic effect in solar panels that charges a storage battery powering the flow computer. The output voltage is 6vdc and should provide usually 30 days of autonomy. A typical LPFC offered by most vendors will include the following: Microprocessor capable of performing necessary equations and calculations. Capability to accept smart transmitter or analog transducer inputs. The ability to store historical data, hourly, daily, event and alarm logs. Capable of displaying real-time as well as historical data via a display or handheld. Able to be configured via a laptop computer or terminal interface by menu selection. Class 1, Div. 1, explosion proof, or intrinsically safe certified for hazardous areas. DC power source, internal lithium or alkaline battery, and solar array powered. Figure 1 shows an RTU-style single-run flow computer. This configuration includes a single-board RTU that is programmed to perform flow calculations and interfaces to differential pressure, pressure, and temperature transmitters. The transmitters are included in the package, but mount external to the flow computer. Optional items shown include the handheld terminal and internal modem. The hand-held terminal functions as both an operator interface/configurator and a data transfer medium. This same transfer medium might also be performed by a laptop computer. By adding a private line modem for telephone line communications or a switched network modem for dial-up phone communication wide-area networking to these remote sites can be achieved. FIGURE PROCEEDINGS PAGE 291
2 Since this type of flow computer is based on a singleboard RTU, it will, typically, include extra input/output points. For example, the unit shown in figure 1 includes eight analog inputs (4-20madc or 1-5vdc), three of which are interfaced to transmitters. The five remaining could be used to interface to additional transmitters for a multirun meter station. This RTU can also accommodate Digital I/O capability to perform run-switching valve status, valve control and gas sampling Instrumentation. While the additional I/O points imply that the flow computer can accommodate two or more meter-runs, if sufficient RAM (random access memory) is not available to store additional historical data, then the processing capability is limited. With today s technology and most vendors using 16 bit or 32 bit microprocessors data storage has not been a problem. FIGURE 2 Figure 2 shows an arrangement that is representative of the new trend in flow computers. DP and pressure transducers not transmitters, have been integrated into the LPFC package. That is to say that the secondary measuring device is mounted internally to the LPFC packaging not external. The amplifier electronics is included on the computer CPU (central processing unit) board. While figure 2 represents a single run application, some vendors can introduce dual-run capabilities by simply adding additional transmitters or one single multivariable transmitter. TOTAL MEASUREMENT ACCURACY A discussion of gas measurement accuracy must encompass all the stages of conversions and calculations there are in a LPFC system. Since each stage introduces error, the overall accuracy of the LPFC depends on the accumulated errors of all stages. The API has defined three stages in a flow computer system as primary, secondary, and tertiary. PRIMARY MEASUREMENT The orifice and the positive displacement meter or turbine has been the two primary methods of gas measurement in the United States. Some estimates put the number above half a million or more. These primary measuring elements impact the LPFC s performance greatly and must be inspected or verified as to their compliance to accuracy specifications. Remembering that the flow computer itself is considered a tertiary device that is responsible for correctly calculating flow based on information that it processes from secondary measuring devices such as transmitters or transducers. All together these three devices are critical to the overall accuracy of measurement we require. Positive displacement meters and turbines should normally be sized to operate between 60% to 90% of their maximum linear capacity. With proper maintenance with respect to mechanical drives, pitting, scratches, or deposits these inspections can normally be somewhat easily performed. On a scheduled basis these meters should be proven to insure accuracy and credibility not only to their mechanical but also electrical frequency output integrity. For instance two types of known provers are pipe and tank type. They provide a known volume against which the volume indicated by the flow meter can be compared. Both these provers are volumetric with respect to comparison results established. With proper maintenance and proving these P.D. and turbine meters should maintain accuracy to within plus or minus 1/4 %. Orifice meters are generally inspected to ensure compliance with ANSI/API 2530 established tolerances. These tolerances include orifice diameter, edge width, edge sharpness, surface finish, flatness, and concentricity. There are several defects that can cause adverse effects on the meter s accuracy such as a bent plate, a nicked bore or rough surface. Also, if it has residue build up or is dirty this needs to be cleaned. SECONDARY MEASUREMENT Most LPFC packages include secondary and tertiary devices: DP, pressure and temperature transmitters that which are interfaced to a digital flow computer. Transmitter specification provides the accuracy of conversion to a 1-5vdc or 4-20mA dc analog signal. To determine the accuracy (or really, uncertainty or probable error ) introduced by all three transmitters, the square root of the sum of the squares method is used. For example, if the accuracy of each transmitter is 0.25%, the total probable error of the secondary stage is approximately 0.43% (this method is accepted by the industry even though it weighs each input DP, pressure, and temperature the same). PAGE PROCEEDINGS
3 Further errors are introduced when the transmitter outputs are interfaced to A/D s (analog to digital converters). Typical accuracy for the input conversion is 0.025%. Again using the square root method, the total probable error for all three inputs is 0.043% The mathematically correct way to account for the combined uncertainty of the transmitters and analog inputs is to add them together: 0.43% to 0.043% = 0.473%. If you doubt this method, an alternative is to treat each of the three inputs separately. The 0.25% for the transmitter should be added to the 0.025% for the input, for a total error of 0.275% per input. The square root method for all three is still 0.473%. Advantages of figure 2 depend upon the strategy the particular vendor uses to process the data from the three variables DP, pressure and temperature. If the LPFC processing this data uses an A/D (Analog/Digital) converter the accuracy of that data may represent what is stated in the above paragraph using analog transmitter technology. If the vendor utilizes smart transmitter technology with digitized communication of the values presented, first, there is no secondary/tertiary conversion. There is no 1-5vdc or 4-20mA dc output and no A/D conversion, as performed by an analog input. Thus, the typical 0.025% uncertainty is eliminated. In addition, the smart transmitter accuracy is increased. For example, if the smart transmitter had an accuracy of 0.1%, then the square root summed for all three variables would equal 0.17%, compared with 0.473% for the aforementioned system. If this transmitter was to be a multi-variable three in one transmitter such as some vendors supply today, the DP sensor is fully static pressure compensated. TERTIARY MEASUREMENT The tertiary stage comprises the calculations within the LPFC. It is relatively easy to accurately perform an instantaneous AGA3 or AGA7 flow equation as most vendors do not consider this a problem. Compared with the input accuracy, the calculation accuracy is insignificant. However, how often are the calculations done? That is the main concern of manufactures of LPFC s. A further issue is averaging and totalizing over times such as an hour and a day. While some people think that calculations performed inside a flow computer are extremely accurate, the truth is precision can fall off in time-based averaging and totalizing. By using double precision (64 bit) floating-point math for all averaging and totalizing, these averages and totals are usually updated once per second. In general the LPFC of today will require it execute input sampling, alarming averaging, totalizing, PID control if required, and all calculations, except AGA8, once per second. Due to the intense calculation required by AGA8 for compressibility using detailed gas composition this could be performed once per minute. AUDIT TRAIL ALARM/EVENT LOG A requirement apparent to vendors that manufacture LPFC s is the audit trail. This is a log that will keep track of alarms and events that occur within the LPFC system. An example of alarms that may appear in the alarm log would be: System power down System power restore Low system power level DP, Pressure, Temp, and Turbine High alarm High high alarm Low alarm Low low alarm Out of range Rate of change Return to normal Power down Power restore Low RAM battery level Examples of events: Operator sign-on (laptop) Operator sign-off (laptop) Low flow cut-in Low flow cut-off Override mode on Override mode off Maintenance on (calibration) Maintenance off (calibration) Orifice plate change Value change of constant (Alarm and events should have the capability of being reported over the wide area network (WAN). SNAPSHOT LOG Upon certain alarms and events, some LPFC s will not only log an alarm message, but will store the entire list of input, flow, and configurable constant values. This allows the user to see the entire station status, rather than a single message, when an exception condition occurs. INSTANTANEOUS/HISTORICAL LOG In addition to storing alarm and event audit trail information a LPFC will have the capability to store current as well as historical information. A LPFC will typically store 35 days of information, the amount of information stored in an hourly or daily log varies and depends on what the vendor may offer. Information that may be available in the hourly, daily as well as quarter hour logs are: 2003 PROCEEDINGS PAGE 293
4 Date start Time start Flowing time Average Differential pressure Average Static pressure Average Temperature Average Specific gravity Average BTU Flow extension Flow Rate Energy Rate Alarms occurred Events occurred Compressibility (FPV) Average C-prime Average CO 2 (Carbon dioxide) Average N 2 (nitrogen) These items will also include station identification, station tag and meter identification. COMMUNICATIONS Requirements for LPFC s at a minimum, is to provide a RS-232 Port capable of interfacing with a laptop computer or a handheld device. This interface would enable the user to configure, monitor, and change parameters specific to the measurement requirements of the LPFC. It would also provide the capability to up dump or collect historical logs, such as daily, hourly and audit/event logs. RS-232C is a serial asynchronous communications standard used to connect modems, terminals and printers with serial interfaces. The Electronic Industries Association (EIA) developed the recommended Standard-232 to define a serial communication interface. This standard is referred to as RS-232/ RS232-C, and RS-232-D. The C and D refers to particular versions of the standard. Although RS232C is only specified for use in transmission lengths up to 50 feet, it is often used for greater distances at lower baud rates. An additional RS-232 port has to be made available for network communication for local area networks (LAN) and wide area networks (WAN). LPFC s in the digital communications world are defined as DTE (data terminal equipment) devices. Modems, radio modems and other communication media are considered DCE (data communication equipment). The main difference between DTE and a DCE device is definitions of their respective transmit and receive pins. Pins two and three have opposite meanings, the DTE device transmits to the DCE receive pin, and the DTE receives data from the DCE transmit pin. The other pins defined on a DB-9, DB-15 or a DB-25 pin connector refers to control or handshaking signals. These are used to control the timing between device s for transmitting and receiving data. To better define the operation of digital data exchange RS-232 link signaling is accomplished with voltages that range from +or 3vdc to +or- 25vdc. If the voltage on the transmit or receive lines is positive (between +3vdc and +25vdc) this represents a 0 bit; if the voltage is negative (between - 3vdc and -25vdc), this represents a 1 bit, both with reference to the signal ground pin. RS-232 communication is most used in implementing wide area networks where linking several LPFC s is required over many miles. This wide area link is accomplished via the DTE to DCE (modem/radio modem interface. RS-485 on the other hand is a EIA standard for serial communications that uses a balanced system for signaling and basically the same signaling voltages. The RS-485 link can be used over fairly long distances (1000 ft.) and at high baud rates such as 38.4 KB. This form of communication is normally used for local area networks, offshore platforms, gas plants, etc. The link is established by using a single twisted pair (both transmit and receive on the same set of wires) that is connected to each device and each device on the network having its own distinct hardware and/or software address, (this also applies to RS-232 as well). This forms a bus topology that can be made use of by network protocols. Since it is a very simple and inexpensive topology, RS-485 is used frequently in the field connecting LPFC s over a local area network. TELEMETRY Various types of communication media are available to us today. An example of the types range from the following: (PLM) Private line modem, communications a form of DCE that modulates over leased or private telephone lines. (SNM) Switched network modem, communication over the PSTN (public switched telephone network) modulate over PSTN for cellular or dial-up communication links. (FOM) Fiber optic modem, communication over fiber-optic cable usually 64 micron or 200 micron thickness cable. (Radio/Microwave, Spread Spectrum) These types of communication are capable of extending long distances, with wireless capability. INPUT/OUTPUT CAPABILITY Additional demands have been placed on LPFC s to provide I/O capable to perform various functions. This I/ O capability is performed by analog inputs and outputs (1-5 vdc or 4-20 ma dc) or discrete inputs and outputs (open collector or relay). INPUTS An example of signal inputs that may be interfaced with LPFC s are digital or discrete open/close contact closures. PAGE PROCEEDINGS
5 WELL TEST In the production industry for example a separator is used to separate condensate, water, and oil from the well. Normally measured in barrels or tenths of barrels, accumulators register the amount of liquid passing through a turbine and produce frequency and or contact closure outputs proportional to the amount of product produced. The LPFC can register these outputs from these accumulators and present hourly, daily and monthly totals. Some LPFC s based on a demand requested either locally through a laptop computer or globally over the network communication media may invoke a well test. While normal EGM calculations are occurring, a well test can be initiated where over a predetermined amount of time usually hours, a totalization of average DP, P, T, flow rate, total volume, condensate total, and water total can be determined. Contact closures from various alarms may be monitored by the LPFC as well. Valve status Security hatch Gas level detection Intrusion alarms High levels Low levels These are just a few examples of inputs that may be monitored by the LPFC. OUTPUTS An example of signal outputs that may be produced by LPFC s are analog and digital. VALVE CONTROL Some LPFC s provide analog outputs in the form of voltage or current, and digital output in the form of contact open collector or pulses. The output selected will depend on the actuator controlling the valve, usually a electronic to pneumatic converter is used. SAMPLERS Almost all LPFC manufactures offer the digital output configured as a standard to pulse a gas sampler. Using a predetermined volume of natural gas the user can configure a rate where which a digital output will activate a sampler. The rate or sampler activation interval is based on the cylinder size and the amount of time it will take to fill the sample cylinder. SUMMARY In recent years, it has become apparent that the gas production, distribution and transmission companies require greater accuracy and low power consumption. A rather extensive amount of gas research and standards committee activity is pointing to higher raw input sampling rates, higher calculation frequencies, more intensive calculations, more data storage, and, in general, considerably more work for the processors used in flow computers. With deregulation, gas marketing and contract agreements are placing their own demands on the LPFC s. They are now used for custody transfer. Specific data must be available for billing and auditing. Flow computers must reside on communication networks to provide data now, not two weeks from now. The contracts also dictate accuracy, which, in turn, dictates sampling rates of DP, pressure, temperature to include AGA calculations. To make matters worse for LPFC vendors, there is no uniformity in gas industry requirements. Every company seems to have a unique need, be it the data that is stored, on what interval, how to do averaging and integration, what information is required over a communication network, the communication protocol, and so forth. In addition, the field measurement personnel have their requirements. The flow computer should be easily installed, calibrated, and started up. Ideally, it should install like a smart DP transmitter, not three transmitters plus a computer. The unit must also be low enough in power consumption to make solar power or batteries viable. Analog output PID (Proportional, Integral, Derivative) control is a continuous signal to the valve, either 1-5vdc or 4-20madc. This output is usually determined manually by the user or automatic by the LPFC in that the valve may be controlled based on a pressure variable or flow rate. This term is based on which variable is chosen to be primary. The selection would be either pressure control with flow override or flow control with pressure override. Digital control uses a pulsed or intermittent voltage output to control the valve. Both outputs analog or digital are based on a variable chosen, pressure or flow and a set point at which the valve will be positioned. Greg Phillips 2003 PROCEEDINGS PAGE 295
The SFC 1000PA P2DAAA can be mounted on a prover trailer, which can be moved from field to field to provide proving services.
The SFC 1000 P2DAAA is a dual meter run bidirectional flow computer with a built in Rosemount 205 Multivariable Transmitter (DP, P, and TEMP) for the measurement of liquid & Gas products. Using orifice
More information905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use
Wireless New Products... New Solutions The range of telemetry modules provide remote monitoring and control by radio or twisted-pair wire, over short or long distances. Transducer signals connected at
More informationThe wireless alternative to expensive cabling...
The wireless alternative to expensive cabling... ELPRO 905U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 905U range of wireless I/O provides a low cost alternative
More informationThe wireless alternative to expensive cabling...
The wireless alternative to expensive cabling... ELPRO 905U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 905U range of telemetry modules provide remote monitoring
More informationROM/UDF CPU I/O I/O I/O RAM
DATA BUSSES INTRODUCTION The avionics systems on aircraft frequently contain general purpose computer components which perform certain processing functions, then relay this information to other systems.
More informationModel Sono-Trak Transit Time
Model Sono-Trak Transit Time Ultrasonic Flow Meter Engineered for performance excellence, the Sono-Trak Transit Time ultrasonic meter combines non-invasive, bi-directional measurement with advanced ultrasonic
More informationTS16 - Pre-Instructional Survey
TS16 - Pre-Instructional Survey Name: Date 1. What do you understand by the term Digital Transmitter? a. A transmitter that auto-configures and auto-calibrates itself. b. A transmitter that can be configured
More informationBASIC ELECTRONICS FOR FIELD MEASUREMENT John Culp Emerson Process Management Remote Automation Solutions Houston, Texas
BASIC ELECTRONICS FOR FIELD MEASUREMENT John Culp Emerson Process Management Remote Automation Solutions Houston, Texas Introduction If you are able to install your own TV dish satellite system and a wireless
More informationMicroprocessor Gas and Steam Flow Computer Energy Flow Computer (Consumption and Enthalpy for Steam) Series: DigiFlow Type: 515
Microprocessor Gas and Steam Flow Computer Energy Flow Computer (Consumption and Enthalpy for Steam) Series: DigiFlow Type: 515 Technical Information 03/2012 FLOW THE EXPERT IN LEVEL AND FLOW DigiFlow
More informationMicro MV P2DAAA. Custody transfer accuracy Built-in multivariable 3-in-1 transmitter. Daily. Zigbee wireless radio. Extended length battery backup
The Micro MV P2DAAA is a four meter bi-directional field mounted flow computer with a built in Rosemount 205 Multivariable Transmitter (DP, P, and TEMP) which can be used for all liquid and gas applications,
More informationE-Chart Image Release History
E-Chart Image Release History Version Release Date Changes 6.09.13 2/7/2014 Correction - Reset Reynolds Number Flag if Not Used (Cone Meter) 6.09.12 10/24/2013 Added Reynolds Number Linear Factor for SmartCone
More informationICARUS ELECTRONIC GAS VOLUME CONVERTER
ICARUS ELECTRONIC GAS VOLUME CONVERTER 1. INTRODUCTION 2. TECHNICAL DETAILS ICARUS is an electronic volume converter which, combined with a gas meter, provides the gas measurement in Sm3, calculated at
More informationSarasota CM200 Sarasota HME900 Density Converter Electronics
Sarasota CM00 Sarasota HME00 Density Converter Electronics Users of Sarasota density meters or specific gravity analyzers are offered the choice of a HART compatible, field mounted density converter, or
More informationThe wireless alternative to expensive cabling...
The wireless alternative to expensive cabling... ELPRO 105U ISO 9001 Certified New Products... New Solutions The ELPRO 105 range of telemetry modules provide remote monitoring and control by radio or twisted-pair
More informationThe wireless alternative to expensive cabling...
The wireless alternative to expensive cabling... ELPRO 105U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 105U range of wireless I/O provides a low cost alternative
More informationAnalog Inputs and Outputs
Analog Inputs and Outputs PLCs must also work with continuous or analog signals. Typical analog signals are 0-10 VDC or 4-20 ma. Analog signals are used to represent changing values such as speed, temperature,
More informationTI25 - Pre-Instructional Survey
TI25 - Pre-Instructional Survey Name: Date: 1. Scheduled maintenance that is planned, with materials on hand, personnel on site, and production planning advised is called maintenance. a. predictive b.
More informationSpirit IT Flow-X High accuracy flow computers
ABB MEASUREMENT & ANALYTICS CONFIGURATION MANUAL Spirit IT Flow-X High accuracy flow computers Operation and configuration Gas USC Measurement made easy Flow-X/P with Flow-X/M module Introduction Welcome
More informationEC 21 EC RMG Meßtechnik GmbH. Gas Volume Corrector. via Temperature. Volume Correction. via Pressure and Temperature
Gas olume Corrector EC21/EC24 24 EC 21 olume Correction via emperature 04.12 olume Correction via ressure and emperature 0.5 RMG Meßtechnik GmbH ublication No..62 Otto-Hahn-Str. 5 (Germany).O.Box 280 5502
More informationAPPLICATION BULLETIN. SERIAL BACKGROUNDER (Serial 101) AB23-1. ICS ICS ELECTRONICS division of Systems West Inc. INTRODUCTION CHAPTER 2 - DATA FORMAT
ICS ICS ELECTRONICS division of Systems West Inc. AB- APPLICATION BULLETIN SERIAL BACKGROUNDER (Serial 0) INTRODUCTION Serial data communication is the most common means of transmitting data from one point
More informationLST100 Ultrasonic level transmitter for upstream oil and gas
Data sheet DS/LST100-EN LST100 Ultrasonic level transmitter for upstream oil and gas Accurately track and measure the most expensive consumable on your site chemicals. Measurement made easy Features Keep
More informationDynatel. 2273M Cable/Pipe and Fault Locators 2273M-iD Cable/Pipe/Fault and Marker Locators with id Read/Write
3 Dynatel 2273M Cable/Pipe and Fault Locators 2273M-iD Cable/Pipe/Fault and Marker Locators with id Read/Write Designed to be more accurate, faster and more integrated than any other locator on the market,
More informationThink About Control Fundamentals Training. Terminology Control. Eko Harsono Control Fundamental - Con't
Think About Control Fundamentals Training Terminology Control Eko Harsono eko.harsononus@gmail.com; 1 Contents Topics: Slide No: Advance Control Loop 3-10 Control Algorithm 11-25 Control System 26-32 Exercise
More informationMPU 200 Series B. Ultrasonic Gas Flowmeter. Specifications. Features. Principle of Operation
Ultrasonic Gas Flowmeter MPU 200 Series B Specifications Issue/Rev. 0.4 (10/11) Bulletin SSKS004 The MPU 200 Series B Ultrasonic Gas Flow Meter is a single path ultrasonic meter with non-intrusive and
More informationModulating control valve
Modulating control valve Automatic modulating valve Automatic modulating valve Diaphragm Pneumatic Actuator Positioner Pneumatic Actuator Positioner Air filter regulator gauge = AIRSET BALL VALVE GLOBE
More informationInstrumentation and Control Technician A Guide to Course Content Implementation Beginning with Level 1 April 2013
Instrumentation and Control Technician A Guide to Course Content Implementation Beginning with Level 1 April 2013 Instrumentation and Control Technicians maintain, diagnose, calibrate and repair measurement
More informationSPECIAL SPECIFICATION 6744 Spread Spectrum Radio
2004 Specifications CSJ 0924-06-244 SPECIAL SPECIFICATION 6744 Spread Spectrum Radio 1. Description. Furnish and install spread spectrum radio system. 2. Materials. Supply complete manufacturer specifications
More informationWATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL
MicroChem Water Analysis System The MicroChem is a versatile multi-parameter instrument capable of being configured as a transmitter or PID controller. Specifically designed for drinking and wastewater
More informationUSER S MANUAL PULSE INPUTS MODULE WITH PROVER SUPPORT
USER S MANUAL PULSE INPUTS MODULE WITH PROVER SUPPORT D F 7 7 M E www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is available on our website.
More informationSL300 Snow Depth Sensor USL300 SNOW DEPTH SENSOR. Revision User Manual
USL300 SNOW DEPTH SENSOR Revision 1.1.2 User Manual 1 Table of Contents 1. Introduction... 3 2. Operation... 3 2.1. Electrostatic Transducer... 4 2.2. SL300 Analog Board... 4 2.3. SL300 Digital Circuit
More informationFGM 160 Ultrasonic Flaregas meter. Flare Gas Measurement
Fluenta Overview FGM 160 Ultrasonic Flaregas meter Flare Gas Measurement Why Measure Flare Gas? Flare systems at offshore production platforms, refineries and chemical plants are primarily installed for
More informationSupercal 531 Multi function Integrator that lives up to Your highest expectations
n Thermal Energy n Flow Metering n Supercal 531 Multi function Integrator that lives up to Your highest expectations Supercal 531 Multi functional integrator with unlimited options The Supercal 531 convinces
More informationand ClearSCADA s custom EFM object the SOLARPack 410 becomes a complete electronic flow measurement system. Chart Recorder Replacement
CONTROL MICROSYSTEMS SOLARPack 41O Solar-Powered Single Run Flow Computer Features: n Accurate gas measurement n API 21.1, BLM#5,EUB#17 n Single Seal Compliance Certification under ANSI/ISA 12.27.01 *
More informationSonoMeter 31 Energy Meters
SonoMeter 31 Energy Meters Description MID examination certificate no.: LT-1621-MI004-023 The Danfoss SonoMeter 31 is a range of ultrasonic, compact energy meters intended for measuring energy consumption
More informationTop Design Considerations for Low-Power Metering Applications
Top Design Considerations for Low-Power Metering Applications Smart metering brings intelligence and connectivity to energy and resource management Silicon Laboratories Inc., Austin, TX As green energy
More informationPRODUCT INFORMATION B&B ELECTRONICS. Port-Powered RS-232 Fiber Optic Modem with Handshake Support. Model 9PFLST. Description. RS-232 Connections
-01-1/ 00 by B&B Electronics. All rights reserved. Model Port-Powered RS- Fiber Optic Modem with Handshake Support Description The allows any two pieces of RS- asynchronous serial equipment to communicate
More informationGEONICA, S.A. - Alejandro Rodríguez, nº Madrid - Spain Tel Fax
A U T O M A T I C W E A T H E R A N D H Y D R O L O G I C A L S T A T I O N S M E T E O D A T A / H Y D R O D A T A - 2 0 0 0 C S E R I E S The type Automatic Meteorological and Hydrological Stations are
More informationNon-Intrusive Ultrasonic Corrosion-Rate Measurements in Lieu of Manual and Intrusive Methods
Non-Intrusive Ultrasonic Corrosion-Rate Measurements in Lieu of Manual and Intrusive Methods Mark Feydo, Steve Strachan, Bruce Pellegrino Sensor Networks, Inc. 176-500 Technology Drive Boalsburg, PA, 16827,
More informationRod Montrose Director of Device Development Numerex
Rod Montrose Director of Device Development Numerex rmontrose@numerex.com Rod Montrose 10+ Years at Motorola with Radio and Data Device Development 14 Years Founder and CEO of AVIDwireless Director of
More informationUNICOM 2500 UNICOM Installation Operation Programming. Universal Communication Converter
User Manual UNICOM 2500 Installation Operation Programming Universal Communication Converter UNICOM 2500 Electro Industries/GaugeTech 1800 Shames Drive Westbury, New York 11590 Tel 516.334.0870 Fax 516.338.4741
More informationConcept of Serial Communication
Concept of Serial Communication Agenda Serial v.s. Parallel Simplex, Half Duplex, Full Duplex Communication RS-485 Advantage over RS-232 Serial v.s. Parallel Application: How to Measure the temperature
More informationF-SERIES FOR. Indicators Totalizers Transmitters Flow computers Batch controllers Monitors. Flow Level Pressure Temperature
F-SERIES Indicators Totalizers Transmitters Flow computers Batch controllers Monitors Flow Level Pressure Temperature FOR F - SERIES F - SERIES F - SERIES F - SERIES F - SERIES F - SERIES F - SERIES F
More informationRHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits
RHE12 Hazardous Area Coriolis Mass Flow Transmitter Features Field mounting Compact, pressure safe housing ATEX and CSA approvals for installation in hazardous areas 24 VDC power supply Configurable analog
More informationSpecifications for 3M Dynatel 2273M/M-iD Cable/Pipe and Fault Locators
Specifications for 3M Dynatel 2273M/M-iD Cable/Pipe and Fault Locators PHYSICAL SPECIFICATIONS SIZE WEIGHT (H X W X D) IN. (CM) (INCLUDING BATTERIES) Transmitter 6.75 x 11.25 x 7.75 (17.2 x 28.6 x 19.7)
More informationXYR 5000 Wireless Transmitters SIMPLE. SAFE. SECURE. Honeywell Solutions for Wireless Data Acquisiton and Monitoring
XYR 5000 Wireless Transmitters SIMPLE. SAFE. SECURE. Honeywell Solutions for Wireless Data Acquisiton and Monitoring No Wire. No Problem. We ve cut the cord that s tethered transmitters to control or data
More informationField Devices and Wiring
Field Devices and Wiring Slide 2-1 Field Device and Wiring Overview The control system interfaces to the process through field devices. Our ability to control a process is limited to the accuracy of measurement
More informationDOCUMENT OBSOLETE. Dynatel. 2273M Cable/Pipe and Fault Locators 2273M-iD Cable/Pipe/Fault and Marker Locators with id Read/Write
3 Dynatel 2273M Cable/Pipe and Fault Locators 2273M-iD Cable/Pipe/Fault and Marker Locators with id Read/Write New-to-the-world technology for locating underground utilities without any doubt. The 3M Dynatel
More informationUSING RS-232 to RS-485 CONVERTERS (With RS-232, RS-422 and RS-485 devices)
ICS DataCom Application Note USING RS- to RS- CONVERTERS (With RS-, RS- and RS- devices) INTRODUCTION Table RS-/RS- Logic Levels This application note provides information about using ICSDataCom's RS-
More informationINSTRUMENTATION AND CONTROL TUTORIAL 3 SIGNAL PROCESSORS AND RECEIVERS
INSTRUMENTATION AND CONTROL TUTORIAL 3 SIGNAL PROCESSORS AND RECEIVERS This tutorial provides an overview of signal processing and conditioning for use in instrumentation and automatic control systems.
More informationAccuSolar SOLAR POWERED SYSTEM
AccuSolar SOLAR POWERED SYSTEM FLO-CORP s AccuSolar Solar Powered Level Monitoring System monitors process conditions through wireless WiFi that communicate up to 1,500 feet to a base station PC. The Solar
More informationChapter 7 Introduction to Instrumentation
Chapter 7 Introduction to Instrumentation Control Automático 3º Curso. Ing. Industrial Escuela Técnica Superior de Ingenieros Universidad de Sevilla Summary Introduction Basic concepts Properties of measurement
More informationImprove asset protection and utilization
QUALITROL 509 ITM Intelligent transformer monitor Improve asset protection and utilization Immediately know your transformer health with TransLife Optimize loading and equipment life Simplify root cause
More informationWireless Gas Detection System
Wireless Gas Detection System Sensidyne SensCast Brochure Rev.A Wireless Gas Detection System The Sensidyne SensCast Wireless Monitoring System consists of 1-32 battery-powered SensCast Transmitters and
More informationSpirit IT Flow-X High accuracy flow computers
ABB MEASUREMENT & ANALYTICS CONFIGURATION MANUAL Spirit IT Flow-X High accuracy flow computers Operation and configuration Gas Metric Measurement made easy Flow-X/P with Flow-X/M module Introduction Welcome
More informationMulti-Channel High Performance Data Acquisition System and Digital Servo Controller Module
VDSP-31 VXI MODULE Multi-Channel High Performance Data Acquisition System and Digital Servo Controller Module OVERVIEW The VDSP31 is a VXI based, multi-channel data acquisition system and digital servo
More informationInstruction Manual RCI-100-XXX. Remote Control Signal Interface
Manufacturers of Process Controls and Instrumentation Instruction Manual Model: Function: Communication: Input: Output: Power: RCI-100-XXX Remote Control Signal Interface XXX=SER: RS-232/485 XXX=MDM Modem
More informationMICROPROCESSOR BASED CONTROLLERS
MICROPROCESSOR BASED CONTROLLERS INPUTS Digital Analog TTL Pulse Keyboard Serial Microprocessor Based Controller OUTPUTS On/Off Analog PWM Serial Graphical Text RS232 Abstract: A controller is a system
More informationAUTOMATIC WEATHER AND HYDROLOGICAL STATIONS
AUTOMATIC WEATHER AND HYDROLOGICAL STATIONS METEODATA/HYDRODATA-3000C SERIES Brochure nº 9722.0044 GEONICA, S.A. - Alejandro Rodríguez, nº 22-28039 Madrid - Spain Tel. +34 91 450 51 18 Fax +34 91 459 46
More informationPreliminary. 4-Channel RTD/4-20 ma Wireless Sensor Node SN24R420-4
Preliminary - 4 Analog Channel, Battery Powered Wireless Sensor Node - 2 RTD Inputs and 2 4-20 ma Inputs Plus 2 Switch Inputs - Supports 2- and 3-Wire 100 ohm Platinum RTDs - Switch State and Change-of-State
More informationInstruction Manual ABM HART Gateway Software. Instruction Manual Revision A.1
Instruction Manual ABM HART Gateway Software Instruction Manual Revision A.1 Table of Contents Section 1: Getting Started... 3 1.1 Setup Procedure... 3 1.2 Quick Setup Guide for Ultrasonic Sensors... 11
More informationSensor Datasheet Collection
ISO 9001 REGISTERED Specials are Our Standard Sensor Datasheet Collection CONTENTS HR-DRO: HIGH RESOLUTION DIGITAL READOUT 3 THE RELS FAMILY: ROD-END LOAD SENSORS 4-15 S-RELS SERIES: STANDARD ROD-END LOAD
More informationBrunata Optuna H Ultrasonic energy meter Type 775 Installation Guide Edition 1.2
Ultrasonic energy meter Type 775 Installation Guide Edition 1.2 UK-QB101575 / 29.05.2012 Brunata a/s is a Danish owned company. We have more than 90 years of experience within developing and producing
More informationObsolete Document. Dynatel
3 Dynatel 2273ME Cable/Pipe and Fault Locators 2273ME-iD Cable/Pipe/Fault and Marker Locators with id Read/Write 2250ME Cable/Pipe Locators 2250ME-iD Cable/Pipe and Marker Locators with id Read/Write New-to-the-world
More informationIT6810/IT6811/IT6812 IMPACT TRANSMITTER Installation Manual
IT6810/IT6811/IT6812 IMPACT TRANSMITTER Installation Manual OVERVIEW IT6810 IT6811 The Model IT6810/IT6811/IT6812 Impact Transmitter uses new technology to measure impact severity on reciprocating machinery.
More informationUNIFORM NETWORK CODE OFFTAKE ARRANGEMENTS DOCUMENT SECTION E TELEMETRY, ETC
1 General 1.1 Introduction Joint Office of Gas Transporters UNIFORM NETWORK CODE OFFTAKE ARRANGEMENTS DOCUMENT 1.1.1 This Section E sets out: SECTION E TELEMETRY, ETC National Grid NTS' requirements for
More informationTRMC-19 GSM/GPRS DATALOGGER. Applications. Product description. Measure and remote monitoring
TRMC-19 GSM/GPRS DATALOGGER The TRMC-19 is a datalogger/dataconcentrator of measures GSM/GPRS radio or wire. This device fulfills the most demanding requirements and will help you to create an effective,
More informationAccutech FL10. Wireless float level field unit
Accutech FL10 Wireless float level field unit 1 The Accutech FL10 wireless float level field unit interfaces with the Siemens TM Model 2100 and 1000 digital level sensors, providing single or dual fluid
More informationSPECIAL SPECIFICATION 6734 RS-232 Optical Modem
2004 Specifications CSJ 0924-06-244 SPECIAL SPECIFICATION 6734 RS-232 Optical Modem 1. Description. This Item shall govern for the furnishing and installation of Fiber Optic RS- 232 Data Modem (OTR) in
More information- Continuous real-time measurement and PD trend analysis; not multiplexed data collection.
QTMS The transformer monitor shall provide data integration platform, cooling supervision & monitoring. User configurable without need of a technician, a 100% configurable to specific customer requirement.
More informationElectronics / Water analogy. Resistor. Inductance. Capacitor. Water Electronics Energy - Energy Pressure - Voltage Flow - Current Volume - Charge
Electronics / Water analogy Water Electronics Energy - Energy Pressure - Voltage Flow - Current Volume - Charge Resistor U = R * I 1 Capacitor U 1 i dt C U L di dt Inductance Turbine Flywheel Diode Transistor
More informationGasSense NDIR INFRARED TRANSMITTER
GasSense is an innovative high specification dual channel infrared gas sensor with integrated transmitter for the measurement of CO2, CO, CH4, N2O or hydrocarbons. Featuring automatic temperature compensation,
More informationSHARKY 775 ULTRASONIC COMPACT METER. 4 Approved according EN 1434 and MID in class 2 with dynamic range of 1:250 (qi:qp) in class 2
APPLICATION ultrasonic compact energy meter can be used for measuring the energy consumption in heating / cooling application for billing purposes. The measurement principle is static and based on the
More informationSTARTRAK PIGGING TECHNOLOGIES, INC. PIPELINE PIG MONITORING
STARTRAK PIGGING TECHNOLOGIES, INC. Pathfinder magnetic pigs can now be monitored for all types of operations, world wide. Station Magnetometers - Statics for land service operations. Buoy systems - Offshore
More informationBATAILG TAIL GAS ANALYZER. Rev. 1.1
BATAILG TAIL GAS ANALYZER Rev. 1.1 The Tail Gas Analyzer is part of the BAGGI BASE Instruments Series. They are the result of combining the latest state-of-the-art-technology with over 60 years of industry
More informationAccutech AM20. Wireless acoustic monitor field unit
Accutech AM20 Wireless acoustic monitor field unit 1 The Accutech AM20 wireless acoustic monitor field unit monitors pressure relief valves, steam traps, automatic tank cleaning (CIP) systems, and other
More informationAbstract. 1. Introduction
IBP1572_09 REMOTE EROSION AND CORROSION MONITORING OF SUBSEA PIPELINES USING ACOUSTIC TELEMETRY AND WET-MATE CONNECTOR TECHNOLOGY Howard Painter 1, Stewart Barlow 2, Daniel Clarke 3, Dale Green 4 Copyright
More informationCDG. Carbon Dioxide - User Manual Gas Detector. 1 Intended Use. 2 Functional Description. 3 Installation. 4 Electrical Connection.
Carbon Dioxide - User Manual 1 Intended Use 2 Functional Description 2.1 Control Mode 2.2 Sensor 3 Installation 3.1 Mounting instructions 3.2 Installation 4 Electrical Connection 4.1 Instruction 5 Commissioning
More informationAdvanced instrumentation solutions crafted with highest precision
www.adeptfluidyne.com Advanced instrumentation solutions crafted with highest precision Working Principle The Transit Time Flowmeter utilises two transducers that function as both ultrasonic transmitters
More informationSMART LASER SENSORS SIMPLIFY TIRE AND RUBBER INSPECTION
PRESENTED AT ITEC 2004 SMART LASER SENSORS SIMPLIFY TIRE AND RUBBER INSPECTION Dr. Walt Pastorius LMI Technologies 2835 Kew Dr. Windsor, ON N8T 3B7 Tel (519) 945 6373 x 110 Cell (519) 981 0238 Fax (519)
More informationSMART METERS ADVANCES IN WATER METER TECHNOLOGY BILL KASPER NORTH PENN WATER AUTHORITY
SMART METERS ADVANCES IN WATER METER TECHNOLOGY BILL KASPER NORTH PENN WATER AUTHORITY COMMON CURRENT METER TYPES MECHANICAL Positive displacement Nutating disk Oscillating piston Multijet Singlejet Compound
More informationSmart Mobile Metering Solutions WALK-BY OR DRIVE-BY READING HYDRUS SMART METERS AND IZAR SYSTEM COMPONENTS
Smart Mobile Metering Solutions WALK-BY OR DRIVE-BY READING HYDRUS SMART METERS AND IZAR SYSTEM COMPONENTS Faster accurate information with Enware Smart Mobile Metering Providing the ability to collect
More informationCable Testing TELECOMMUNICATIONS AND NETWORKING
Cable Testing TELECOMMUNICATIONS AND NETWORKING Analog Signals 2 Digital Signals Square waves, like sine waves, are periodic. However, square wave graphs do not continuously vary with time. The wave holds
More informationCALCULATING AND OPTIMIZING ACCURACY & REPEATABILITY of NATURAL GAS CUSTODY TRANSFER FLOW MEASUREMENTS UNDER INSTALLED CONDITIONS
CALCULATING AND OPTIMIZING ACCURACY & REPEATABILITY of NATURAL GAS CUSTODY TRANSFER FLOW MEASUREMENTS UNDER INSTALLED CONDITIONS Mark Menezes, Manager, Pressure Applications (Americas) Eric Wickberg, Senior
More informationModel FLSC-C1-LIQ. Microprocessor Based Loop Powered Transmitter
Model FLSC-C1-LIQ Microprocessor Based Loop Powered Transmitter CONTENTS 1. Introduction ------------------------------------------------------------ 2 2. Specifications-----------------------------------------------------------
More informationA NOVEL METHOD OF RATIO CONTROL WITHOUT USING FLOWMETERS
A NOVEL METHOD OF RATIO CONTROL WITHOUT USING FLOWMETERS R.Prabhu Jude, L.Sridevi, Dr.P.Kanagasabapathy Madras Institute Of Technology, Anna University, Chennai - 600 044. ABSTRACT This paper describes
More informationIdentifying Gas Ultrasonic Meter Problems Using Advanced Techniques
Identifying Gas Ultrasonic Meter Problems Using Advanced Techniques Randy McDaniel, Sr. Project Specialist, Atmos Energy John Lansing, VP Global Operations, CEESI Abstract During the past several years
More information1. Instrument diagnostics Interpreting the Optical Image and Diagnostic Values Prism washing... 8
1 (14) TROUBLESHOOTING GUIDE Contents 1. Instrument diagnostics... 2 2. Interpreting the Optical Image and Diagnostic Values... 3 3. Prism washing... 8 4. Typical Faults and Causes... 11 5. Preventive
More informationCellular Network Interface (CNI) Models GSM18, GSM20 and CDMA18
Cellular Network Interface (CNI) Models GSM18, GSM20 and CDMA18 AC- and DC- Powered Unit Assemblies with Cathodic Protection Monitor (CPM-1 or CPM-2) Option User s Guide Document: 900355 Revision: B September,
More informationFLOW SWITCH 600 Series Velocity Flow Sensor. Instruction Manual
SWITCH 600 Series Velocity Flow Sensor Instruction Manual Ultrasonic Velocity Sensor using Doppler Technology Model: FS-600 Manual Release Date: November, 2009 ECHO Process Instrumentation, Inc. CONTENTS
More informationORCA. Sonar System. Data Sheet. A Higher Level of Performance. Sludge and Settling Level Interface Monitoring.
A Higher Level of Performance Data Sheet ORCA Sonar System Sludge and Settling Level Interface Monitoring For more information, please visit > www.hawkmeasure.com Overview Principle of Operation The ORCA
More informationRadiocrafts Embedded Wireless Solutions
Implementing with RC1180-MBUS Wireless M-Bus module by Ø. Nottveit Introduction Wireless M-Bus (EN 13757-4:2005) is the only wireless standard specifically targeting the reading of electricity, gas-, water-,
More informationSpecialists in Remote Monitoring
ABRIOX www.abriox.com MERLIN CATHODIC PROTECTION MONITORING Specialists in Remote Monitoring REDUCING THE COST OF DATA COLLECTION - IMPROVING THE QUALITY OF DATA - INCREASING THE EFFICIENCY OF INTEGRITY
More informationUltrasonic transducers being installed in the 2.4m (96 ) aqueduct at Watchgate WTW, Cumbria, UK.
Ultrasonic transducers being installed in the 2.4m (96 ) aqueduct at Watchgate WTW, Cumbria, UK. A Sarasota 2000 Ultrasonic flowmeter, installed at Watchgate water treatment works in Cumbria on the 2.4m
More informationECB-103 BACnet B-ASC 10-Point Programmable Controllers
D a t a s h e e t BACnet B-ASC 10-Point Programmable Controllers Overview The is a microprocessor-based programmable controller designed to control terminal units such as fan coil unit, heat pump unit,
More information8450 Series CellGuard TM Power / VSWR Monitors
8450 Series TM Power / VSWR Monitors Precision Power and VSWR Measurements via Integral High Directivity Coupler (35 db typical) and Imbedded Microprocessor. True RMS Power Measurement over a 30 db Dynamic
More informationISO INTERNATIONAL STANDARD. Non-destructive testing Ultrasonic thickness measurement
INTERNATIONAL STANDARD ISO 16809 First edition 2012-11-15 Non-destructive testing Ultrasonic thickness measurement Essais non destructifs Mesurage de l'épaisseur par ultrasons Reference number ISO 2012
More informationSHARKY 775 ULTRASONIC COMPACT METER. 4 Approved according EN 1434 and MID in class 2 with dynamic range of 1:250 (qi:qp) in class 2
APPLICATION ultrasonic compact energy meter can be used for measuring the energy consumption in heating / cooling application for billing purposes. The measurement principle is static and based on the
More informationSubsea Control Systems
Subsea Control Systems Simplifying Subsea Production INGENIOUS SIMPLICITY Proserv s direct hydraulic and multiplexed production subsea control systems provide control and shutdown of subsea wells together
More informationRS 485/422 to Fibre Optic Modems ELO E243, ELO E244, ELO E245. Operation manual
RS 485/422 to Fibre Optic Modems ELO E243, ELO E244, ELO E245 Operation manual 1.0 Introduction 3 2.0 Operation principles 3 3.0 Installation 3 3.1 RS422 Interface Connection 4 3.2 RS485 Interface Connection
More informationSenseair S8 Commercial
Product Specification Senseair S8 Commercial Miniature infrared CO 2 sensor module 1 (8) Item Senseair S8 Commercial Article No. 004-0-0010, 004-0-0075 Target gas CO 2 Operating Principle Non-dispersive
More information