BASIC ELECTRONICS FOR FIELD MEASUREMENT John Culp Emerson Process Management Remote Automation Solutions Houston, Texas

Size: px
Start display at page:

Download "BASIC ELECTRONICS FOR FIELD MEASUREMENT John Culp Emerson Process Management Remote Automation Solutions Houston, Texas"

Transcription

1 BASIC ELECTRONICS FOR FIELD MEASUREMENT John Culp Emerson Process Management Remote Automation Solutions Houston, Texas Introduction If you are able to install your own TV dish satellite system and a wireless home network for pes, you have a head starl 011 installing and maintaining electronic field measurement equipment. Today's measurement technicians and engineers are required to operate and maintain a variety of Hi-Tech field measurement equipment. Most of the field instrumentation is tightly integrated in a complete system functional environment. The larger the metering station, the more complex the system. The goal of this paper is to provide an introduction to electronics based on current field measurement technology. Basic field duties related to electronic instrumentation would include: installation calibration data collection, configuration, orifice plate changes, communication checks and maintenance. Some of the basic types of connections and measurements include power, analog signals and digital signals going into and out of the device. Each of these play unique circuitry roles and require different knowledge of their intended operation. The Basic Circuit Electricity has three components, Voltage (equivalent to pressure in a fluid piping system) measured in volts, Resistance (equivalent to pipe roughness) to the flow. measured in Ohms and current (equivalent to the fluid (gallons of water), measured in amps. If the pressure is one volt and the resistance one ohm the current will be one amp. V = I x R, In many tests voltage is referred to as the Electromotive Force and referred to as E but till measured in volts. So the text book fonnula is usually E = I x R The units of measure include V or E for Voltage (Volts), I for ClIrrent (Amps), R for Resistance (Ohms Q), P is for power measured in watts where: P=PxR p~ E x I The best way to understand this relationship is to look at a basic circuit. A simple circuit requires a power source to generate an electromotive (electrical power) source. In the circuit there is a load that provides the majority of the resistance to a flow in current and a switch to control the flow. As shown below the symbol for a battery or power source is on the left, the load is at the

2 top and the switch that controls the flow is one the bottom. Closing the switch completes the circuit and allows the current to flow. In this case the voltage applied is 12 volts and the resistance or load is two amps so the current is (12 16 = 6) 6 amps. Current flows from one tenninal to another only when there is a completed circuit. The device being powered must have enough current and voltage to insure proper operation (Inrush). Most Field electronics operate off of 6, 12 or 24 volts DC. A way to remember the relationship between voltage, resistance and current is shown in the diagram to the right. 20(ohm,), Battery (Powel Souce) Vois (E)' 12 Vois DC load (R) Ohms V =I R I= y R=y R 1 I=V IR Basic Electric Circuit P = J. 1,1 P :: 12. R P = y2 I :: Current (A) P :: Power ('0'01) R:: Resistance (Q) V :: Voltage (V) Relationship Diagram R In most text books the current is shown flowing from + to - on the voltage source but the actual electrons are negatively charged and flow from negative to positive. This is one of those "do we really care" facts. Current to vouage basics Most RTUs, PlCs and flow computers create outputs in the form of a transm itted signal that generates a current that is proportional to some level of measurement. The signal usually ranges from 4 mi ll iamps to 20 mi lliamps. 4 milliamps represents the minimum (sometimes zero) and 20 milliamps the maximum. So if I am measuring temperature I can calibrate my transmitter to send 4 milliamps when the temperature is O' Centigrade and 20 milliamps when the temperature is loo Centigrade. Thus a 12 milliamp signal would represent the halfway point and would indicate 50' Centigrade. Some people like to read their signals in voltage. By installing a 250 ohm resistor (shown below) 1 can convert a signal that will range from I to 5 volts. - ==1"P=;- Typical Resistor So a 4 milliamp signal would be measured as I volt and the 20 milliamp signal would be measured as 5 Volts. 4rnA x 2500 ~ I V 20rnA x 2500 ~ 5 V Current output devices are still common. When the transm itter is designed to deliver a current for a given signal it has several advantages. First it can be sent to more than one measuring device and can be sent to displays with thousands of feet between devices. In some cases the circuits become more complicated and more devices are connected. A more complicated circuit is shown below.

3 i 1 = 6 6= 2 +4 "- + 30(OhmS)~ i2=2a L i3 = 4 a I 6Vofts \: ~ T-1= VIR 30 (OhmS)~ 6 Vofts Complex Electric Circuit I I When the circuits get connected to equipment they can look like the diagram below. POl/-fER i 5.4 TO 36VDC) COMMON SIGNAL INPUT (O PEN CO LLE CTORi r "o------r.lax 1000 FEET 0 05 METERS) -----;.011 PULLUP RESISTOR END DEVICE " ~ Preamplifier OC Output Diagram Tl"Oubleshooling & Checkups 3-co N D U CTORS HIELDED CABLE. 2.AWG OR LARGER OC OUT MAX SOmA CONNECT SHIELD ONL Y AT END DEVICE PV-:R GND 0-5 OU T OC OUT COIL COIL- 24AWG OR ~ PICKUP LARGER PREAMPLIfiER TWISTED PAIR COIL I MAX 100 FEET I ~ i 30 METERS) ~ As-built drawings, Make & Model of equipment lists and the manuals usually are available from the manufacturer to describe the equipment. Most manuals can be found on the vendor's website. Other useful information as to support contacts, software upgrades/patches and FAQs ( Frequently Asked Questions) is also online. f'ield Checks I. Are there Lights, LCD, or other health indications'? 2. How's the Power'? 3. Check the Fuses. 4. How's the system grounding? (Another lengthy discussion)

4 The ~I way to verify comet operation is to interrogate the device by us ing its diagnostic modes. A laptop PC or PDA is needed. Some new technology even has predictive diagnostics, integrated documentation, calibration management and device configuration. Analog Signals 4 to 20 milliamp or I to 5 volts are generated so their level is in proportion to or analogous to the level of signal being sensed. As a result they are called analog signals. When more than one device is driven by an analog signal it is often useful to look at a Voltage Burden Chart. Loop loading can be seen on the Input Burden Chan below. This chart shows the maximum number of 2500 loads a device can power, based on loop voltage levels. This applies to both analog inputs and analog outputs. 30V., -., 20V '" ~ -:::l Q. c:..,., -:::l 10 V 1 Input Voltage Burden Chart V./ / ~20mA././ V"././'.J 10'" ~12mA././"././ I' 'f"./' 4mA / / o Output Load (0) Digital Signals Digital Signals is one that is ether on or off and are normally used as status type inputs that sense a voltage level transition. This could be from a valve limit switch. The signal is a low to high voltage level transition.

5 Freguency/Pulse Signals Some signals are in the form of a senes of pulses where the number of pulses in one second, represent the value of the signal. For instance ten pulses in one second could indicate ten volts or ten barrels of oil. Turbine meters, conolis meters and ultrasonic meters have a pulse or frequency type outputs. They are best measured by using an oscilloscope. This allows you to view the amplitude and frequency of the signal. Un-amplified signals are usually small amplitude sine waves. Amplified device outputs are more than likely a square wave. The chart below gives an example of the millivolt input lo frequency ratio on the input of a preamp. This shows that a high frequency (Noise) small amplitude signal would be filtered out... E :> - ~ 1 'g, E " E., E j l-=dd::ttI Frequency (Hz) Relays Preamp Frequency Input Graph Relay type circuits are magnetically operated switches. A wetting voltage usually DC is applied to the coil windings which produce a magnetic field used to open or close the relay switch. Relay terminals are referred to as "Normally Open", or "Normally Closed". Relays can be used to tum on or off different actuations such as: Solenoid valves, gas samplers, and radios. Open Collector Some signal inputs and outputs may require a "pull-up" resistor to source thc voltagc. These nrc mostly referred to as "Open Collector". Check the specifications to insure proper resistor sizing. The resistor has to be sized to allow only enough current to flow through it. Digital Signals Digital signals are normally low level, low voltage input types. They are typically looking for a voltage transition between 0 and 5 volts DC. Some digital signal types are as follows:

6 Digital Outputs are normally used to trigger an event like a smart gas sampler. This output could also be "OC" type. The signal is a low to high voltage level transition. Communications are digital in nature because they carry the binary code (Computer Talk) information needed for data transfer. While there are many different hardware formats for carrying data, RS232 is still the most common device interface today. The table shows the connector pin out for two types of common cables. Ethernet Ethernet connectivity is being used for most plant type operations involving line power flo w computers. This is a very common network medium that is spreading to more complex field measurement scenarios. Most RTUs, Gas Chromatographs and Gas Ultrasonic meters have Ethernet ports. Simply follow the instructions needed for setting up your laptop's Ethernet port. Fieldbus Connecting a set of measurement transducers to a flow computer has been traditionally an analog world. There is the low power 1 to 5vdc method and the 4 to 20 rna method for line powered applications. Fieldbus changes this in two ways. A standard set of wires and connectors are used between devices and a common communication protocol is used. Less fie ld wiring is needed and device interchangeability is added. Device interrogation is done digitally now instead of analog. Process variables along with performance diagnostics are now available at the device level. Protocols A protocol is a set of pulse codes that are designed to transmit information. Morse code used in telegraph messages is an example of a protocol. The de facto standard for flow computer protocol is ModSus, (developed by Modicon) or ASCII (developed by EIA). All major vendors otter some variation of this. This was the first step toward vendor interchangeability. The next step is the use of higher level protocols based from the internet standards. As communications become more complex more than one wire may be required to send information from one location to another. Multi-pin connections became the standard for the industry until the Ethernet moved in. Examples of multi-pin connectors are shown below. RS= D~~) OB9 D~~) 0826

7 Some Field Technician Tools Portable Laptop Computer with device software Cables Digital Voltmeter Transducer Calibration Test equipment Some Common Field Instruments Gas flow meter with solar panel for power. Area Classifications If the equipment is installed in a hazardous area for measuring natural gas or liquid hydrocarbons. it must meet certain safety requirements. In the Americas. U.L or CSA type ratings are required. Sanity Checks and Procedures Remember to shut down and start up electronic measurement & control equipment properly. Some valves and regulators will need to be placed in manual operation until the electronics are brought back online. Failure to operate and maintain the equipment in the manner it was designed for, might have undesired consequences. Results of this could be inaccurate measurement accounting and deliveries or worse. Before you attempt to work on any equipment, make sure that the area is safe. Sare from a hazardous area perspective and by general electrical safety precautions. Cautions such as, but not limited to: Working on (Hot) powered equipment while standing in water. Turning process control equipment off without setting proper manual, override or bypass conditions.

8 Conclusion As measurement devices and techniques change, so must the skill level of the Technician or Engineer. Training is a necessity and not a luxury. OJT (On the Job Training) in the measurement of natural gas does not lend itself to good results. Make sure there is a sound knowledge of the device's operation, especially when it relates to custody and gas control operations. Many times if an RTU or flow computer has to be configured, repaired or replaced, a software cold start or program memory re-flash will be required. Simply removing power will not work anymore! Learn the essentials.

LINCO MEASUREMENT MODEL CP-2B MASTER METER PROVER COUNTER INSTRUCTION MANUAL

LINCO MEASUREMENT MODEL CP-2B MASTER METER PROVER COUNTER INSTRUCTION MANUAL LINCO MEASUREMENT MODEL CP-2B MASTER METER PROVER COUNTER INSTRUCTION MANUAL ENGINEERED AUTOMATED SYSTEMS DESIGNERS ENGINEERS MANUFACTURERS SALES REPRESENTATIVES 4580 W. HWY 80 P.O. BOX 4096 MIDLAND, TEXAS

More information

INSTALATION, OPERATION & MAINTENANCE MANUAL. PA-1001A Series SIGNAL CONDITIONER & CONVERTORS

INSTALATION, OPERATION & MAINTENANCE MANUAL. PA-1001A Series SIGNAL CONDITIONER & CONVERTORS INSTALATION, OPERATION & MAINTENANCE MANUAL FOR PA-1001A Series SIGNAL CONDITIONER & CONVERTORS PA1001A 7/02 Page 1 of 11 SIGNAL CONDITIONER & CONVERTERS PA1001A Series INTRODUCTION: The PA1001A series

More information

Model Sono-Trak Transit Time

Model Sono-Trak Transit Time Model Sono-Trak Transit Time Ultrasonic Flow Meter Engineered for performance excellence, the Sono-Trak Transit Time ultrasonic meter combines non-invasive, bi-directional measurement with advanced ultrasonic

More information

TROUBLESHOOTING A TECHNICIAN S GUIDE 2ND EDITION. William L. Mostia, Jr., P. E. ISA TECHNICIAN SERIES

TROUBLESHOOTING A TECHNICIAN S GUIDE 2ND EDITION. William L. Mostia, Jr., P. E. ISA TECHNICIAN SERIES TROUBLESHOOTING A TECHNICIAN S GUIDE 2ND EDITION William L. Mostia, Jr., P. E. ISA TECHNICIAN SERIES TABLE OF CONTENTS Chapter 1 Learning to Troubleshoot........................ 1 1.1 Experience..............................

More information

Continental Hydraulics Installation Manual CEM-RA-A

Continental Hydraulics Installation Manual CEM-RA-A CEM-RA-A Description: This ramp amplifier drives either single or dual solenoid proportional valve coils up to 2.6A. It is suitable to control current to either proportional directional, flow, or pressure

More information

LOW POWER FLOW COMPUTERS Greg Phillips Bristol Babcock Inc Governors Circle West, Suite F, Houston, TX 77092

LOW POWER FLOW COMPUTERS Greg Phillips Bristol Babcock Inc Governors Circle West, Suite F, Houston, TX 77092 LOW POWER FLOW COMPUTERS Greg Phillips Bristol Babcock Inc. 2000 Governors Circle West, Suite F, Houston, TX 77092 INTRODUCTION Flow computers, themselves, are undergoing an evolution. One challenge for

More information

Sarasota CM200 Sarasota HME900 Density Converter Electronics

Sarasota CM200 Sarasota HME900 Density Converter Electronics Sarasota CM00 Sarasota HME00 Density Converter Electronics Users of Sarasota density meters or specific gravity analyzers are offered the choice of a HART compatible, field mounted density converter, or

More information

A Super trainer with advanced hardware and software features only found in very expensive equipment.

A Super trainer with advanced hardware and software features only found in very expensive equipment. PLC Trainer PTS T100 LAB EXPERIMENTS A Super trainer with advanced hardware and software features only found in very expensive equipment. You won t find any similar equipment among our competitors at such

More information

MPU 200 Series B. Ultrasonic Gas Flowmeter. Specifications. Features. Principle of Operation

MPU 200 Series B. Ultrasonic Gas Flowmeter. Specifications. Features. Principle of Operation Ultrasonic Gas Flowmeter MPU 200 Series B Specifications Issue/Rev. 0.4 (10/11) Bulletin SSKS004 The MPU 200 Series B Ultrasonic Gas Flow Meter is a single path ultrasonic meter with non-intrusive and

More information

Contents. Warranty and Disclaimer 2

Contents. Warranty and Disclaimer 2 Contents Warranty and Disclaimer 2 Physical Dimensions Board Layout 3 Usage Using the PWM board 4 Setting the start address 4 Dimming LED s 5,6 Typical hookup 7 Terminator 8 Troubleshooting Ground, termination,

More information

Field Devices and Wiring

Field Devices and Wiring Field Devices and Wiring Slide 2-1 Field Device and Wiring Overview The control system interfaces to the process through field devices. Our ability to control a process is limited to the accuracy of measurement

More information

The SFC 1000PA P2DAAA can be mounted on a prover trailer, which can be moved from field to field to provide proving services.

The SFC 1000PA P2DAAA can be mounted on a prover trailer, which can be moved from field to field to provide proving services. The SFC 1000 P2DAAA is a dual meter run bidirectional flow computer with a built in Rosemount 205 Multivariable Transmitter (DP, P, and TEMP) for the measurement of liquid & Gas products. Using orifice

More information

SL300 Snow Depth Sensor USL300 SNOW DEPTH SENSOR. Revision User Manual

SL300 Snow Depth Sensor USL300 SNOW DEPTH SENSOR. Revision User Manual USL300 SNOW DEPTH SENSOR Revision 1.1.2 User Manual 1 Table of Contents 1. Introduction... 3 2. Operation... 3 2.1. Electrostatic Transducer... 4 2.2. SL300 Analog Board... 4 2.3. SL300 Digital Circuit

More information

Programmable K-Factor Scaler B and Programming Software Kit B

Programmable K-Factor Scaler B and Programming Software Kit B Programmable K-Factor Scaler B220-885 and Programming Software Kit B220-900 INSTALLATION & INSTRUCTION MANUAL 8635 Washington Avenue Racine, Wisconsin 53406 Toll Free: 800.235.1638 Phone: 262.639.6770

More information

Harris IRT Enterprises Multi-Channel Digital Resistance Tester Model XR

Harris IRT Enterprises Multi-Channel Digital Resistance Tester Model XR Harris IRT Enterprises Multi-Channel Digital Resistance Tester Model 6012-06XR Specifications & Dimensions 2 Theory of Operation 3 System Block Diagram 4 Operator Controls & Connectors 5 Test Connections

More information

AccuSolar SOLAR POWERED SYSTEM

AccuSolar SOLAR POWERED SYSTEM AccuSolar SOLAR POWERED SYSTEM FLO-CORP s AccuSolar Solar Powered Level Monitoring System monitors process conditions through wireless WiFi that communicate up to 1,500 feet to a base station PC. The Solar

More information

Model FLSC-C3-XX. DC Powered Microprocessor Controlled Transmitter

Model FLSC-C3-XX. DC Powered Microprocessor Controlled Transmitter Model FLSC-C3-XX DC Powered Microprocessor Controlled Transmitter CONTENTS. Introduction----------------------------------------------------------------- 2 2. Specifications ---------------------------------------------------------------

More information

TS16 - Pre-Instructional Survey

TS16 - Pre-Instructional Survey TS16 - Pre-Instructional Survey Name: Date 1. What do you understand by the term Digital Transmitter? a. A transmitter that auto-configures and auto-calibrates itself. b. A transmitter that can be configured

More information

RS-422/RS-485 Line Tester Model 485T

RS-422/RS-485 Line Tester Model 485T Not Recommended for New Installations. Please contact Technical Support for more information. RS-422/RS-485 Line Tester Model 485T Documentation Number 485T1995 This product Designed and Manufactured In

More information

Mass and Volume Flow Transmitter

Mass and Volume Flow Transmitter IFT9701 Product Data Sheet PS-00218-EU December1999 Mass and Volume Flow Transmitter IFT9701 transmitter The IFT9701 microprocessor-based transmitter works with Micro Motion sensors to provide affordable,

More information

Continental Hydraulics Installation Manual CEM-PA-A

Continental Hydraulics Installation Manual CEM-PA-A CEMPAA Description: This closed loop PID amplifier drives a single solenoid proportional pressure or flow control valve coil up to 2.6A. It is suitable to provide precise closed loop control in pressure,

More information

Magnetic Flowmeter Simulator

Magnetic Flowmeter Simulator Quick Installation Guide Rosemount 8714D Magnetic Flowmeter Simulator Start Step 1: Change Transmitter Parameters Step 2: Connect the Rosemount 8714D Step 3: Perform Electronics Trim Step 4: Verify 8714D

More information

Improve asset protection and utilization

Improve asset protection and utilization QUALITROL 509 ITM Intelligent transformer monitor Improve asset protection and utilization Immediately know your transformer health with TransLife Optimize loading and equipment life Simplify root cause

More information

Modulating control valve

Modulating control valve Modulating control valve Automatic modulating valve Automatic modulating valve Diaphragm Pneumatic Actuator Positioner Pneumatic Actuator Positioner Air filter regulator gauge = AIRSET BALL VALVE GLOBE

More information

DR3535 DR3535-O. Hardware Reference Manual. Document Revision A7 May 16, 2018 MICROKINETICS CORPORATION

DR3535 DR3535-O. Hardware Reference Manual. Document Revision A7 May 16, 2018 MICROKINETICS CORPORATION -O Hardware Reference Manual Document Revision A7 May 16, 2018 MICROKINETICS CORPORATION 3380 Town Point Drive Suite 330 Kennesaw, GA 30144 Tel: (770) 422-7845 Fax: (770) 422-7854 www.microkinetics.com

More information

K-Factor Scaler F5140 and Programming Kit F5141 Installation & Operating Instructions

K-Factor Scaler F5140 and Programming Kit F5141 Installation & Operating Instructions F5140 and Programming Kit F5141 8635 Washington Avenue Racine, WI 53406 USA Tel: 800-433-5263 or 262-639-6770 Fax: 800-245-3569 or 262-639-2267 E-Mail: flo-techsales@racinefed.com www.flo-tech.com TABLE

More information

UltraFlo UFDD ULTRASONIC CLAMP-ON FLOW METER

UltraFlo UFDD ULTRASONIC CLAMP-ON FLOW METER UltraFlo UFDD ULTRASONIC CLAMP-ON FLOW METER DESCRIPTION The UltraFlo UFDD Clamp-On Ultrasonic Flow Meter is the ideal flow meter with accurate, easy-to-use, easy-to-install digital doppler technology.

More information

Instruction MI December Magnetic Flow System

Instruction MI December Magnetic Flow System Instruction MI 021-138 December 2015 Magnetic Flow System 2800 Series Flowtubes with an 896 or an E96 Transmitter Fault Location Guide Contents Contents...3 Figures...5 Tables...6 Introduction...7 Reference

More information

Product Range Electronic Units

Product Range Electronic Units Pyramid Technical Consultants, Inc. 1050 Waltham Street Suite 200 Lexington, MA 02421 TEL: +1 781 402-1700 TEL (UK): +44 1273 492001 FAX: (781) 402-1750 EMAIL: SUPPORT@PTCUSA.COM Product Range Electronic

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual NIAGARA M513 Rev. B Model 1005 Pulse to DC Converter Installation, Operation and Maintenance Manual Table of Contents General... 1 Specifications... 1 Installation... 1 Theory of Operation... 2 Setup...

More information

LINCO MEASUREMENT MODEL CP-2BD MASTER METER PROVER COUNTER INSTRUCTION MANUAL

LINCO MEASUREMENT MODEL CP-2BD MASTER METER PROVER COUNTER INSTRUCTION MANUAL LINCO MEASUREMENT MODEL CP-2BD MASTER METER PROVER COUNTER INSTRUCTION MANUAL ENGINEERED AUTOMATED SYSTEMS DESIGNERS ENGINEERS MANUFACTURERS SALES REPRESENTATIVES 4580 W. HWY 80 P.O. BOX 4096 MIDLAND,

More information

The wireless alternative to expensive cabling...

The wireless alternative to expensive cabling... The wireless alternative to expensive cabling... ELPRO 905U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 905U range of telemetry modules provide remote monitoring

More information

PEOPLE IN CONTROL OF MOTION

PEOPLE IN CONTROL OF MOTION MODEL 796500 RESOLVER TO ENCODER CONVERTER FOR MACHINE TOOL, POSITIONING, AND TRANSFER LINE APPLICATIONS *** APPLICATIONS *** Ideal For Closed Loop Positioning Systems Machine Tools Nuclear Applications

More information

RHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits

RHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits RHE12 Hazardous Area Coriolis Mass Flow Transmitter Features Field mounting Compact, pressure safe housing ATEX and CSA approvals for installation in hazardous areas 24 VDC power supply Configurable analog

More information

GTS High Frequency Pulser. Technical Bulletin

GTS High Frequency Pulser. Technical Bulletin GTS High Frequency Pulser Technical Bulletin 02 Elster American Meter High Frequency Pulser System control and data acquisition in gas distribution networks begins with process sensors: sensors to detect

More information

Process Control Calibration Made Easy with Agilent U1401A

Process Control Calibration Made Easy with Agilent U1401A Process Control Calibration Made Easy with Agilent U1401A Application Note This application note explains how the Agilent U1401A with simultaneous source and measure functions eases technicians calibration

More information

905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use

905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use Wireless New Products... New Solutions The range of telemetry modules provide remote monitoring and control by radio or twisted-pair wire, over short or long distances. Transducer signals connected at

More information

2 Thermistor + Op-Amp + Relay = Sensor + Actuator

2 Thermistor + Op-Amp + Relay = Sensor + Actuator Physics 221 - Electronics Temple University, Fall 2005-6 C. J. Martoff, Instructor On/Off Temperature Control; Controlling Wall Current with an Op-Amp 1 Objectives Introduce the method of closed loop control

More information

IS-3000 SERIES INFRARED SCANNER

IS-3000 SERIES INFRARED SCANNER IS-3000 SERIES INFRARED SCANNER NON-CONTACT, RELIABLE, PRECISE, LONG RANGE POSITIONING FOR HOT OR COLD PRODUCTS FEATURES ANALOG AND DIGITAL OUTPUTS INDICATIVE OF TARGET POSITION, WIDTH AND TEMPERATURE

More information

SPECIAL SPECIFICATION 6744 Spread Spectrum Radio

SPECIAL SPECIFICATION 6744 Spread Spectrum Radio 2004 Specifications CSJ 0924-06-244 SPECIAL SPECIFICATION 6744 Spread Spectrum Radio 1. Description. Furnish and install spread spectrum radio system. 2. Materials. Supply complete manufacturer specifications

More information

PRELIMINARY. Preliminary TECHNICAL DATASHEET #TDAX DC MOTOR CONTROLLER P/N: AX100650

PRELIMINARY. Preliminary TECHNICAL DATASHEET #TDAX DC MOTOR CONTROLLER P/N: AX100650 Preliminary TECHNICAL DATASHEET #TDAX100650 DC MOTOR CONTROLLER P/N: AX100650 Variable Speed Control, Onboard Inputs 6A DC Motor Output, 2.5A Proportional Output, 2 Signal Outputs CAN SAE J1939, Rugged

More information

ECE3204 D2015 Lab 1. See suggested breadboard configuration on following page!

ECE3204 D2015 Lab 1. See suggested breadboard configuration on following page! ECE3204 D2015 Lab 1 The Operational Amplifier: Inverting and Non-inverting Gain Configurations Gain-Bandwidth Product Relationship Frequency Response Limitation Transfer Function Measurement DC Errors

More information

TI25 - Pre-Instructional Survey

TI25 - Pre-Instructional Survey TI25 - Pre-Instructional Survey Name: Date: 1. Scheduled maintenance that is planned, with materials on hand, personnel on site, and production planning advised is called maintenance. a. predictive b.

More information

Effective: June, 2000 EX-1821 Satellite Display Unit Receiver Installation Manual Models: 4643-*-* 4644-*-9 Since 1937

Effective: June, 2000 EX-1821 Satellite Display Unit Receiver Installation Manual Models: 4643-*-* 4644-*-9 Since 1937 Effective: June, 2000 LevelPRO Satellite Display Unit Receiver Installation Manual Models: 4643-*-* 4644-*-9 Since 1937 The information contained in this manual was accurate at the time of release. Specifications

More information

Box chopper amplifier BOE

Box chopper amplifier BOE Box chopper amplifier BOE Description The box chopper amplifier is an always energised Pulse-Wide-Modulated (PWM) H-Bridge for to drive inductive loads with bipolar current in according to an analogue

More information

User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters

User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters Table of Contents Page Introduction 1 Description 1 Specifications 2 Installation 3 Calibration 4 General Maintenance

More information

M2 Antenna Systems, Inc. Model No: S3 Sequencer. Operating Instructions

M2 Antenna Systems, Inc. Model No: S3 Sequencer. Operating Instructions WARRANTY ADDENDUM TROUBLESHOOTING INSTALLATION OVERVIEW M2 Antenna Systems, Inc. Model No: S3 Sequencer Operating Instructions PLEASE READ BEFORE USE AND SAVE M2 Antenna Systems, Inc. 4402 N. Selland Ave.

More information

TITANIUM SERIES R 51 PART NUMBER SELECTION. High Performance Multiport Switches. Our Most Important Connection is with You.

TITANIUM SERIES R 51 PART NUMBER SELECTION. High Performance Multiport Switches. Our Most Important Connection is with You. PART NUMBER SELECTION Models: 2: Without 50 Ω terminations 4: With 50 Ω terminations RF Connectors: 3: SMA up to 6 GHz 4: SMA up to 20 GHz F: SMA up to 26.5 GHz 8: SMA 2.9 up to 40 GHz (1) Radiall s TITANIUM

More information

Ultrasonic transducers being installed in the 2.4m (96 ) aqueduct at Watchgate WTW, Cumbria, UK.

Ultrasonic transducers being installed in the 2.4m (96 ) aqueduct at Watchgate WTW, Cumbria, UK. Ultrasonic transducers being installed in the 2.4m (96 ) aqueduct at Watchgate WTW, Cumbria, UK. A Sarasota 2000 Ultrasonic flowmeter, installed at Watchgate water treatment works in Cumbria on the 2.4m

More information

Sealed Interface Control: EC20300

Sealed Interface Control: EC20300 ISO 9001:2000 WITH DESIGN Certificate #02.002.1 Sealed Interface Control: EC20300 FEATURES: Weather tight control package Pulse Width Modulated output Waterproof altitude pressure and vapor release vent

More information

TECHNICAL DATASHEET #TDAX A DC MOTOR CONTROLLER P/N: AX Variable Speed Control, Onboard I/O CAN SAE J1939, Rugged Packaging

TECHNICAL DATASHEET #TDAX A DC MOTOR CONTROLLER P/N: AX Variable Speed Control, Onboard I/O CAN SAE J1939, Rugged Packaging TECHNICAL DATASHEET #TDAX102000 35A DC MOTOR CONTROLLER P/N: AX102000 Variable Speed Control, Onboard I/O CAN SAE J1939, Rugged Packaging with Electronic Assistant Features: Unidirectional or bi-directional

More information

INSTALLATION & OPERATION MANUAL

INSTALLATION & OPERATION MANUAL INSTALLATION & OPERATION MANUAL AN25 Totalizer/ Rate Indicator DOC#: MN-AN25.doc Sponsler Co., Inc. AN25 Totalizer/Rate Indicator pg. 2 DOC#: MN-AN25 SPECIFICATIONS Temperature: Operating 0 to 70 C Storage

More information

HI 2204LT Loop Powered Level Weight Transmitter OPERATION AND INSTALLATION MANUAL

HI 2204LT Loop Powered Level Weight Transmitter OPERATION AND INSTALLATION MANUAL Loop Powered Level Weight Transmitter OPERATION AND INSTALLATION MANUAL Corporate Headquarters 9440 Carroll Park Drive San Diego, CA 92121 Phone: (858) 278-2900 FAX: (858) 278-6700 Web-Site: http://www.hardysolutions.com

More information

Installation Tech Note Dallas, Texas

Installation Tech Note Dallas, Texas AMC B40A40AC Installation Tech Note Dallas, Texas May, 2010 ! CAUTION! Do NOT apply air pressure to release the collet while the servo motor is rotating. The servo motor spindle must be FULLY STOPPED before

More information

Applications: Power generation, Cogeneration, Stationary power Large engines

Applications: Power generation, Cogeneration, Stationary power Large engines Features: 8 inputs are user selectable from the following. 0-5V, 0-10V, 4-20 ma or 0-20 ma Digital inputs for interface to switches, etc. PWM signal, pulse or 16-bit counter inputs from sensors or diesel

More information

SECTION BUILDING METERING (Indianapolis Campus Only)

SECTION BUILDING METERING (Indianapolis Campus Only) A. PURPOSE 1. The general purpose of this standard is to provide minimal criteria for utility metering equipment for new IUPUI facilities. 2. The purpose of this metering system is twofold: B. GENERAL

More information

The wireless alternative to expensive cabling...

The wireless alternative to expensive cabling... The wireless alternative to expensive cabling... ELPRO 105U ISO 9001 Certified New Products... New Solutions The ELPRO 105 range of telemetry modules provide remote monitoring and control by radio or twisted-pair

More information

DLVP A OPERATOR S MANUAL

DLVP A OPERATOR S MANUAL DLVP-50-300-3000A OPERATOR S MANUAL DYNALOAD DIVISION 36 NEWBURGH RD. HACKETTSTOWN, NJ 07840 PHONE (908) 850-5088 FAX (908) 908-0679 TABLE OF CONTENTS INTRODUCTION...3 SPECIFICATIONS...5 MODE SELECTOR

More information

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents KENCO ENGINEERING COMPANY P.O. BOX 470426, TULSA, OK 74147-0426 PHONE: (918) 663-4406 FAX: (918) 663-4480 http://www.kenco-eng.com e-mail: info@kenco-eng.com KENCO Loop Powered Magnetostrictive Transmitter

More information

TRANSMITTER CALIBRATION

TRANSMITTER CALIBRATION TRANSMITTER CALIBRATION In this laboratory study, you will be asked to calibrate two of four different devices. To do so, you will need to write the equation defining the performance of the unit. Use this

More information

Perry DEHC Test Platform

Perry DEHC Test Platform Perry DEHC Test Platform 2017 Power Plant Simulation Conference San Diego, Ca January 16-19, 2017 Perry DEHC Test Platform John Stone Senior Engineer - CORYS Yves Lacombe Principal Engineer - CORYS This

More information

User s Manual for Integrator Short Pulse ISP16 10JUN2016

User s Manual for Integrator Short Pulse ISP16 10JUN2016 User s Manual for Integrator Short Pulse ISP16 10JUN2016 Specifications Exceeding any of the Maximum Ratings and/or failing to follow any of the Warnings and/or Operating Instructions may result in damage

More information

The wireless alternative to expensive cabling...

The wireless alternative to expensive cabling... The wireless alternative to expensive cabling... ELPRO 105U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 105U range of wireless I/O provides a low cost alternative

More information

PHASE CUT SIGNAL DRIVERS

PHASE CUT SIGNAL DRIVERS FEATURES Input to output isolation 27, 40 or 80 watts output power Fused 24VAC power supply Input and power LED indication DESCRIPTION & OPERATION The Digital Controller Interface Module Phase Cut Driver

More information

Model FLSC-C1-LIQ. Microprocessor Based Loop Powered Transmitter

Model FLSC-C1-LIQ. Microprocessor Based Loop Powered Transmitter Model FLSC-C1-LIQ Microprocessor Based Loop Powered Transmitter CONTENTS 1. Introduction ------------------------------------------------------------ 2 2. Specifications-----------------------------------------------------------

More information

The wireless alternative to expensive cabling...

The wireless alternative to expensive cabling... The wireless alternative to expensive cabling... ELPRO 905U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 905U range of wireless I/O provides a low cost alternative

More information

Introduction. Specifications LF620,LF622. Field Intelligent Device Series Electromagnetic Flowmeter Converter

Introduction. Specifications LF620,LF622. Field Intelligent Device Series Electromagnetic Flowmeter Converter Field Intelligent Device Series Electromagnetic Flowmeter Converter LF620,LF622 Introduction Combined with a multi-functional converter LF620 (combined type) or LF622 (separate type) equipped with its

More information

SPECIFICATION EP 1000/1500/2000 Series

SPECIFICATION EP 1000/1500/2000 Series UNINTERRUPTIBLE POWER SYSTEM SPECIFICATION EP 1000/1500/2000 Series Page 1 of 28 1.0 Revision Summary REVISION SECTION DESCRIPTION Formal Release Page 2 of 28 Table of Contents 1. Introduction. 4 2. Block

More information

B850 Boiler House Energy Monitor

B850 Boiler House Energy Monitor Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

Contents. Warranty and Disclaimer 2 Introduction 3

Contents. Warranty and Disclaimer 2 Introduction 3 Contents Warranty and Disclaimer 2 Introduction 3 Physical Dimensions Board Layout 4 Usage Using the Relay board 5 Setting the start address 5 Configuration Jumper 6 Using the Relays 7 Using the DMX connectors

More information

TECHNICAL DATASHEET #TDAX Universal Input, Single Output Valve Controller CAN (SAE J1939)

TECHNICAL DATASHEET #TDAX Universal Input, Single Output Valve Controller CAN (SAE J1939) Features: TECHNICAL DATASHEET #TDAX021610 Universal Input, Single Output Valve Controller CAN (SAE J1939) 1 universal signal input (voltage, current, resistive, PWM, frequency or digital) 1 output: proportional

More information

Model RFT9709 Transmitter Instruction Manual

Model RFT9709 Transmitter Instruction Manual Model RFT9709 Transmitter Instruction Manual March 1999 Model RFT9709 Transmitter Instruction Manual For technical assistance, phone the Micro Motion Customer Service Department: In the U.S.A., phone

More information

Coils & Electronic Controls

Coils & Electronic Controls HYDRAFORCE Coils & Electronic Controls COILS FOR SOLENOID OPERATED VALVES Standard Coils and Proportional Valve Coils... 3.200.1 Series E Water/Weather Resistant Coils... 3.400.1 ELECTRONIC CONTROLS FOR

More information

K-FACTOR SCALER B & B

K-FACTOR SCALER B & B K-FACTOR SCALER B220-880 & B220-881 INSTALLATION & INSTRUCTION MANUAL 8635 Washington Ave. Racine, Wisconsin 53406 Technical Toll-Free: 877.722.4631 Sales Toll-Free: 800.235.1638 Phone: 262.639.6770 Fax:

More information

Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control

Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control Gain Electronic Co. Ltd. Table Of Contents Safety Considerations ------------------------------------------------------------2

More information

USING RS-232 to RS-485 CONVERTERS (With RS-232, RS-422 and RS-485 devices)

USING RS-232 to RS-485 CONVERTERS (With RS-232, RS-422 and RS-485 devices) ICS DataCom Application Note USING RS- to RS- CONVERTERS (With RS-, RS- and RS- devices) INTRODUCTION Table RS-/RS- Logic Levels This application note provides information about using ICSDataCom's RS-

More information

SECTION GPS WIRELESS CLOCK SYSTEMS

SECTION GPS WIRELESS CLOCK SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. G.P.S. Receiver B. Primary Transmitter C. Satellite Transmitter D. Analog Clocks E. Digital Clocks 1.2 REGULATORY REQUIREMENTS SECTION 27 53 13 GPS WIRELESS CLOCK

More information

MS8268 HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL

MS8268 HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL MS8268 HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL Table of Contents TITLE PAGE 1. GENERAL INSTRUCTIONS 1 1.1 Precaution safety measures 1 1.1.1 Preliminary 1 1.1.2 During use 2 1.1.3 Symbols

More information

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters Table of Contents Page Introduction 1 Description 1 Specifications 2 Installation 3 Calibration 4 General Maintenance

More information

with Electronic Assistant

with Electronic Assistant TECHNICAL DATASHEET #TDAX021300 Valve Controller 6 On/Off P/N: AX021300 2 Analog and 3 Frequency Command Inputs 6 On/Off Outputs (Option: PWM) CAN (SAE J1939) with Electronic Assistant Features: 2 user

More information

What is the Kicker F.I.T. input circuit and why is it better?

What is the Kicker F.I.T. input circuit and why is it better? What is the Kicker F.I.T. input circuit and why is it better? F.I.T. input: Kicker uses a special circuit for the audio input to our amplifiers called Failsafe Integration Technology or (F.I.T.) for short.

More information

P o w e r. C O N T R O L S A N D a t h e n a c o n t r o l s. c o m. ATHENA CONTROLS, INC Campus Drive Plymouth Meeting, PA U.S.A.

P o w e r. C O N T R O L S A N D a t h e n a c o n t r o l s. c o m. ATHENA CONTROLS, INC Campus Drive Plymouth Meeting, PA U.S.A. P o w e r C O N T R O L S A N D a t h e n a c o n t r o l s. c o m ATHENA CONTROLS, INC. 5145 Campus Drive Plymouth Meeting, PA 19462-1129 U.S.A. TABLE OF CONTENTS Model Page Series 19/39 1 and Zero-Switched

More information

1 Second Time Base From Crystal Oscillator

1 Second Time Base From Crystal Oscillator 1 Second Time Base From Crystal Oscillator The schematic below illustrates dividing a crystal oscillator signal by the crystal frequency to obtain an accurate (0.01%) 1 second time base. Two cascaded 12

More information

THE PROBE, 5 METER, 2WIRE, LOOP POWERED SINGLE POINT LEVEL MEASUREMENT SYSTEM (ULTRASONIC)

THE PROBE, 5 METER, 2WIRE, LOOP POWERED SINGLE POINT LEVEL MEASUREMENT SYSTEM (ULTRASONIC) THE PROBE, 5 METER, 2WIRE, LOOP POWERED SINGLE POINT LEVEL MEASUREMENT SYSTEM (ULTRASONIC) Part 1. General 1.1 Scope A. This section describes the requirements for an ultrasonic, single-point level controller

More information

201AP Charge Amplifier User Manual

201AP Charge Amplifier User Manual Trig-Tek 201AP Charge Amplifier User Manual Publication No. 980996 Rev. A Astronics Test Systems Inc. 4 Goodyear, Irvine, CA 92618 Tel: (800) 722-2528, (949) 859-8999; Fax: (949) 859-7139 atsinfo@astronics.com

More information

Micro MV P2DAAA. Custody transfer accuracy Built-in multivariable 3-in-1 transmitter. Daily. Zigbee wireless radio. Extended length battery backup

Micro MV P2DAAA. Custody transfer accuracy Built-in multivariable 3-in-1 transmitter. Daily. Zigbee wireless radio. Extended length battery backup The Micro MV P2DAAA is a four meter bi-directional field mounted flow computer with a built in Rosemount 205 Multivariable Transmitter (DP, P, and TEMP) which can be used for all liquid and gas applications,

More information

Microprocessor Control Board Set Up Procedures (OR PLC)

Microprocessor Control Board Set Up Procedures (OR PLC) Microprocessor Control Board Set Up Procedures (OR-00 PLC) SWITCHES/PUSHBUTTONS Push Buttons at display SW Enter button SW Back button SW Down SW UP Back light on/off switch Rotary switches on main board

More information

2/2 way Proportional Valve (motordriven)

2/2 way Proportional Valve (motordriven) 2/2 way Proportional (motordriven) Actuator isolated from fl ow path Excellent range and fast response times Low power consumption Orifi ce sizes 8 to 25 mm Versions: Standard, positioner, process controller

More information

Connecting Mains Electrical Power

Connecting Mains Electrical Power Tide Level Monitoring Instrumentation The following documentation details the electrical installation for the tide level monitoring instrumentation and also a summary of the logger configurations required

More information

Analog Module D1-15P User Manual

Analog Module D1-15P User Manual D1-15P Manual Analog Module D1-15P User Manual Sielco Elettronica Srl Edison Street 209 20019 Settimo Milanese (MI) - Italy http://www.sielcoelettronica.com info @ sielcoelettronica.com Tel 02 48916252

More information

UTM10 Series Ultrasonic Transit-time Flowmeters

UTM10 Series Ultrasonic Transit-time Flowmeters Ultrasonic Transit-time meters Description UTM10 ultrasonic flow and energy meters clamp onto the outside of pipes and do not make contact with the internal liquid. The technology has inherent advantages

More information

Sensors. CS Embedded Systems p. 1/1

Sensors. CS Embedded Systems p. 1/1 CS 445 - Embedded Systems p. 1/1 Sensors A device that provides measurements of a physical process. Many sensors are transducers, devices that convert energy from one form to another. Examples: Pressure

More information

DM8010 tm. Hardware Reference Manual. Document Revision B3 May 16, 2018

DM8010 tm. Hardware Reference Manual. Document Revision B3 May 16, 2018 tm Hardware Reference Manual Document Revision B3 May 16, 2018 MICROKINETICS CORPORATION 3380 Town Point Drive Suite 330 Kennesaw, Georgia 30144 Tel: (770) 422-7845 Fax: (770) 422-7854 Table Of Contents

More information

MICROPROCESSOR BASED CONTROLLERS

MICROPROCESSOR BASED CONTROLLERS MICROPROCESSOR BASED CONTROLLERS INPUTS Digital Analog TTL Pulse Keyboard Serial Microprocessor Based Controller OUTPUTS On/Off Analog PWM Serial Graphical Text RS232 Abstract: A controller is a system

More information

Coriolis Mass Flow Meters. Advanced flow measurement made easy.

Coriolis Mass Flow Meters. Advanced flow measurement made easy. Coriolis Mass Advanced flow measurement made easy. Introducing Coriolis Mass The Badger Meter RCT1000 Coriolis mass flow meter identifies flow rate by directly measuring fluid mass over a wide range of

More information

TOA PROFESSIONAL POWER AMP

TOA PROFESSIONAL POWER AMP Operating Instruction Manual TOA PROFESSIONAL POWER AMP Model P-150M, P-300M TOA ELECTRIC CO, LTD. KOBE, JAPAN Contents Precautions... 2 General Description... 2 Features... 3 Specifications... 4~5 Performance

More information

Electrical Fundamentals and Basic Components Chapters T2, T3, G4

Electrical Fundamentals and Basic Components Chapters T2, T3, G4 Electrical Fundamentals and Basic Components Chapters T2, T3, G4 Some Basic Math, Electrical Fundamentals, AC Power, The Basics of Basic Components, A Little More Component Detail, Reactance and Impedance

More information

Signal Paths from Analog to Digital

Signal Paths from Analog to Digital CHAPTER 1 Signal Paths from Analog to Digital Introduction Designers of analog electronic control systems have continually faced following obstacles in arriving at a satisfactory design: 1. Instability

More information

Generator Speed Controller Model GSC 1

Generator Speed Controller Model GSC 1 enerator Speed Controller odel SC 1 RA 29 977/09.95 Replaces: 4.92 Self contained controller for driving electrical power generators with a hydrostatic transmission 16 Bit microprocessor based controller

More information

Owner s Manual S5 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL

Owner s Manual S5 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL Owner s Manual S5 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL This manual covers installation, setup, operation and troubleshooting. Read carefully before attempting to install, operate or service

More information