AC Magnetic Field Survey Report

Size: px
Start display at page:

Download "AC Magnetic Field Survey Report"

Transcription

1 AC Magnetic Field Survey Report of Literature Building - 3 University of California San Diego for University of California San Diego La Jolla, California Report Date: February 15, 21 FMS Ref: FIELD MANAGEMENT SERVICES CORP. 123 North Laurel Los Angeles, California 948 Telephone (323) Fax (323)

2 NOTICE All materials contained in this report are protected by copyright and may not be used by others. All content herein, including but not limited to text, graphics, and other intellectual property, cannot be reproduced except by permission of Field Management Services Corp. and provided that copyright notice appear in all copies and that both the copyright notice and permission notice appear in supporting documentation. Documentation contained in this report may not be reproduced, distributed, published, entered into a database, displayed, modified, used to create derivative works, transmitted, or exploited for distribution to others without the expressed written consent of Field Management Services Corp. Field Management Services Corp. has expressly prepared this report for the party noted as Client. Field Management Services Corp. shall be indemnified and held harmless from any losses, damages and costs with respect to the unauthorized use of any information contained in this report. Field Management Services Corp. is only responsible for the content of this report and reference to any other service or information source does not imply an endorsement by Field Management Services Corp.

3 Table of Contents BACKGROUND:...2 ELF OR AC MAGNETIC FIELD CHARACTERISTICS:...2 UNITS OF MEASURE:...4 SURVEY MEASUREMENT EQUIPMENT:...4 MEASUREMENT PROCEDURES:...5 TEMPORAL VARIATIONS:...6 MEASUREMENT OBSERVATIONS:...7 Attachments I. Measurement Floor Plans 21 Field Management Services Corp. - Los Angeles New York

4 FIELD MANAGEMENT SERVICES CORP 123 North Laurel Los Angeles, California 948 Telephone (323) Fax (323) DATE: February 15, 21 FMS REF: CLIENT: University of California San Diego 95 Gilman Drive La Jolla, California 9293 ATTN: Grant Silva Health Physicist PROPERTY: Literature Building - 3 University of California San Diego La Jolla, California PROJECT: AC Magnetic Field Survey SCOPE: The scope of this project involved measurement of the magnitude and vector direction of power frequency magnetic fields. Submitted by: FIELD MANAGEMENT SERVICES

5 UCSD Literature Building - EMF Survey Pg. 2 February 15, 21 BACKGROUND: This report documents results of an AC 6 Hz magnetic field survey authorized by the University of California San Diego (UCSD) and conducted by Field Management Services (FMS) of the Literature Building 3 located on the UCSD Campus in La Jolla, California. This survey which involved spot measurements of AC magnetic fields at random locations on all four floors of the building was authorized pursuant to terms of UCSD Purchase Order dated January 7, 21. On January 13 and February 1, 21, an FMS technical representative visited the UCSD site and conducted detailed measurements of AC magnetic fields present in the areas of interest. To inform the reader, the following general information is provided regarding AC magnetic fields. ELF OR AC MAGNETIC FIELD CHARACTERISTICS: ELF or AC magnetic fields are naturally emitted by current-carrying electrical conductors and devices. The AC magnetic field strength emitted by electrical circuits is directly proportional to the magnitude of electrical current. However, multiple conductor cables carrying balanced currents have a low net emission, a consequence of the natural cancellation of magnetic fields created by currents traveling in opposite directions (or with different phase angles) in adjacent conductors. Rigid metallic conduit generally provides good magnetic field reduction, provided that the feed and return currents are equal, in single-phase circuits, and if all of the currents (both feed and return) are present, in multiphase circuits. If electrical current from a circuit returns via an alternate path, then magnetic field levels emitted from such a circuit can increase significantly. This condition usually occurs if neutral circuits are cross connected or illicit connections are made between a neutral and ground in a building s electrical distribution system. This is often referred to as stray, ground or net-current conditions. Field Management Services

6 UCSD Literature Building - EMF Survey Pg. 3 February 15, 21 AC magnetic fields decrease naturally in intensity as function of distance (d) from the source. The rate of decrease however, can vary dramatically depending on the source. For example, magnetic fields from motors, transformers, etc. decrease very quickly (1/d 3 ) while circuits in a typical multi-conductor circuit decay slower (1/d 2 ). Magnetic fields from stray current on water pipes, building steel, etc. tend to decay much slower (1/d). Simply increasing the distance from the source(s) of an area with elevated magnetic field strengths can often reduce magnetic fields to an acceptable level. Unlike electric fields that are relatively easily shielded by common materials used in commercial construction, magnetic fields are capable of penetrating all but a very few, specially manufactured and installed materials. AC magnetic fields will pass undiminished through earth, concrete and most metals, including lead. The actual AC magnetic field strengths encountered within a given commercial building typically range from under.2 mg in open areas to several hundred near electrical equipment. As previously mentioned AC magnetic fields at relatively low levels are capable of producing interference patterns on computer monitors and have been shown to otherwise interfere with electronic equipment. Available technical literature on the subject indicates that computer monitor interference patterns will occur at background AC magnetic field strengths of approximately 5-1 mg and in certain circumstances in environments as low as 3 mg. State of the art flat screen LCD computer monitors and processors utilized in today s applications are generally immune to interference threats from AC magnetic fields. The possible effects of AC magnetic fields on human health have been extensively studied. FMS, by virtue of this report, makes no attempt to attribute value to either side of the question regarding risk to human health nor, for the purposes of health or safety, does the company assign value to any particular magnetic field level. The US Department of Energy RAPID Program WEB site ( and the World Health Organization ( are excellent sources for comprehensive information on the EMF health issue. Field Management Services

7 UCSD Literature Building - EMF Survey Pg. 4 February 15, 21 UNITS OF MEASURE: Magnetic flux densities (B) are reported using units of gauss (G). However, it is usually more convenient to report magnetic field levels using milligauss (mg) which is equal to one-thousandth of a gauss (i.e., 1 mg =.1 G). Some technical reports also use the unit Tesla (T) or microtesla (.µt); (1.µT =.1 T) for magnetic flux densities. The conversion between these two units is 1 mg =.1µT and 1 µt = 1 mg. SURVEY MEASUREMENT EQUIPMENT: To record AC magnetic field values, the following equipment was utilized: Instrument Manufacturer Model Serial No. Gauss Meter Dexsil Fieldstar 1 Magnum AC magnetic field measurements were taken using a Dexsil Fieldstar 1 Gauss meter and a Dexsil Magnum 31 Gauss meter. The meters take readings in three orthogonal planes and calculate the resultant field (square root of the sum of the squares) for the measurement point in space. The Field Star 1 and Magnum 31 are computer-controlled, three-axis, AC magnetic field exposure meters. Each of the three-axis sensors measures the magnetic field and the on-board computer calculates a resultant field value. The resultant is comparable to a maximum field value and is calculated as the square root of the sum of the squares for all three orthogonal axes Br = Bx² + By² + Bz². All magnetic field measurements in this report are the RMS (root mean square) values. The Dexsil Magnum 31 and Fieldstar 1 meters were used to take spot measurements at selected locations on all four floors of the Literature Building. Field Management Services

8 UCSD Literature Building - EMF Survey Pg. 5 February 15, 21 The Field Star 1 meter also contains an internal sampling mode wherein measurement values can be stored at intervals of 1 second or any number of minutes between For this study, the meter was set to record timed data at the rate of 1 sample per second in a First Floor Conference Room study site. At the conclusion of the measurement session, a file name was created, which describes the conditions of the test location, and the data uploaded to a laptop computer that is equipped with interface software. MEASUREMENT PROCEDURES: For this survey, measurement procedures consistent with test protocols and techniques described in ANSI/IEEE Standard & C , IEEE Recommended Practices for Measurement of Electric and Magnetic Fields from AC Power Lines were utilized. As shown on attached figures, magnetic field spot measurements were first taken throughout each floor of the Literature Building including hallways and areas adjacent to the Literature Building s electrical & elevator equipment rooms at a constant height of one meter above floor level. At the request of UCSD representatives, spot magnetic field measurements were also taken on a random basis, in occupied offices on each floor Detailed spot measurements were taken in areas immediately adjacent to the First Floor electrical and elevator equipment rooms and in areas adjacent to the electrical rooms on Floors 2, 3 & 4. Attached enlarged floor plans of these areas provide a more detailed view of magnetic field conditions adjacent to the electrical facilities. Note that two sets of AC magnetic field spot measurements were taken in areas immediately adjacent to each floor s electrical room; one set with the two hydraulic elevators not in use and a second set of measurements with the elevators in operation. Field Management Services

9 UCSD Literature Building - EMF Survey Pg. 6 February 15, 21 A supplemental set of detailed AC magnetic field measurements were taken in a First Floor Conference Room No. utilizing an x & y grid of equal four foot spacing. Spot measurement values were recorded at each grid intersection point at one meter from the floor surface. To determine to what extent if any, AC magnetic field conditions in the First Floor Conference Room No. may momentarily increase when the nearby elevators are operating, timed magnetic field measurements were taken at a study location as shown on an attached diagram. Timed measurements utilizing a 1 second sample rate were taken for a twenty minute period without the elevators operating and then for an additional ten minute period with each of the two elevators operating in varying lifting and descending sequences to emulate a busy elevator operation conditions. TEMPORAL VARIATIONS: AC magnetic field spot readings taken during magnetic field surveys are accurate only for the specific point in time that they were taken. Magnetic field strengths emanating from electrical equipment such as is adjacent to the measured areas of the Literature Building, will vary with the electric (current) load. It was noted during the January 13 and February 1, 21 survey visits, that the Literature Building appeared to be at a reasonable level of occupancy and typical of normal day-to-day operations. It is the observation of FMS based on prior experience and observation that it is possible that magnetic field conditions at other times of the year in the Literature Building may be somewhat higher or lower and will vary in relation with the amount activity in the building and ambient external conditions. Field Management Services

10 UCSD Literature Building - EMF Survey Pg. 7 February 15, 21 MEASUREMENT OBSERVATIONS: The following observations are offered after a review by FMS of the data from the January 13 and February 1, 21 AC magnetic field survey visits to the UCSD Literature Building in areas of interest: AC magnetic field levels throughout all occupied areas of the Literature Building, generally were well below 1 mg with many areas near mg. As can readily be seen from the attached measurement floor plans for each level of the Literature Building, the only areas with modestly elevated AC magnetic field levels present were areas adjacent to the central core of the building on each level, which is the location of elevators and electrical rooms. The measurement data demonstrates that magnetic fields from the central core electrical equipment on each floor generally decay at the anticipated 1/d 2 rate associated with typical electrical circuits. This suggests that net-current circuit conditions, if present, are negligible. The measurement data confirms that relatively short duration increases in electrical loading in the MS-3 main distribution panel caused by cycling of the elevator hydraulic pumps, causes a like short duration but very minimal increase in the AC magnetic field environment in areas immediately adjacent to the Ground Floor electrical room. Similarly on Floors 2,3 & 4, increases in AC magnetic field levels in areas immediately adjacent to the elevator core and electrical rooms with the elevators operating, were negligible. Detailed grid measurements taken in Conference Room No. were generally <.1 mg with the exception of a small area in the northwest corner which is adjacent to a small telecom equipment room. An examination of the telecom room revealed the presence of a small electrical breaker panel which explains the source of very modestly elevated AC magnetic field levels in the corner of the conference room. Field Management Services

11 UCSD Literature Building - EMF Survey Pg. 8 February 15, 21 Data from the 3 minute time study of AC magnetic field levels in a selected location of Conference Room No. are presented in the attached plot of field values vs time. While it is interesting to note that field levels during the study period, momentarily (several seconds) increased periodically every 5 minutes or so, likely due to cycling of some device such as a refrigerator, etc, it appears as anticipated, that operation of the nearby elevators had no noticeable effect on field levels when compared to the period of time when the elevators were not in operation. The detailed grid spot measurements recorded in Conference Room No. failed to confirm the presence of a buried electrical feed circuit which was suspected to transverse an area of the Conference Room. Further investigation by University s facility maintenance confirmed that the feed circuit did not run beneath the Conference Room, but rather, beneath the main building entrance. In sum, the measurement data indicates that AC magnetic field levels in very limited areas of the Literature Building ground floor immediately adjacent to the ground floor electrical room and in the immediate region of a buried, under slab feed conduit in the building s entrance hallway, are modestly higher than the background magnetic field; a consequence of close adjacency to electrical circuits. AC magnetic field levels measured outside these areas were generally consistent with ambient AC magnetic field levels typically present in office buildings. Field Management Services

12 (J)157 FIRST FLOOR University of California, San Diego Literature Building - 3 AC (6 Hz) Magnetic Field Survey January 13, 21-2:15 PM (C) DN PATIO (CU) ELEVATOR (C) ELEVATOR ROOM (M) (M) ELEVATOR (C)16 (M) (C) (TW) (C) (J) (C)182 (TM) (G) Confirmed path of V Buired feed from MS-2 (C) AC (6 Hz) Magnetic Field Levels Spot +1 Meter from Floor, Resultant Value in mg Field Management Services Corp. New York - Los Angeles

13 University of California, San Diego Literature Building - 3 FIRST FLOOR (Electrical & Elevator Room) AC (6 Hz) Magnetic Field Survey January 13, 21-3:55 PM Elevator Pump EL-3 MS-3 8 Amp Panel Elevator Pump EL AC (6 Hz) Magnetic Field Levels Spot +1 Meter from Floor, Resultant Value in mg Values in Blue - Elevators Being Exercised Field Management Services Corp. New York - Los Angeles

14 University of California, San Diego Literature Building - 3 FIRST FLOOR (Conference & Restroom) AC (6 Hz) Magnetic Field Survey January 1, 21-3:15 PM Refrigerator Breaker Panel in Closet Location of Time Study Confirmed path of V Buired feed from MS AC (6 Hz) Magnetic Field Levels Spot +1 Meter from Floor, Resultant Value in mg Field Management Services Corp. New York - Los Angeles

15 University of California, San Diego Literature Building - 3 FIRST FLOOR (Conference Room) AC (6 Hz) Magnetic Field Survey - Timed Measurements February 1, 21-3:4 PM AC (6 Hz) Magnetic Field - One Second Sample Rate At +1 Meter from Floor, Resultant Value in mg Elevators Not Running Elevators Running 2 MG Seconds :4 pm 4:1 pm Conference Room Time Study Point (See First Floor Conference Room Diagram for Study Location) Field Management Services Corp. New York - Los Angeles

16 SECOND FLOOR University of California, San Diego Literature Building - 3 AC (6 Hz) Magnetic Field Survey January 13, 21-4:5 PM (C)283P P DN 229P 227P P P 231P 225P P 224P P 223P P P 2 215P P P 322 (M)221P5 213P P BP68 21CP9 21DP84 21AP 3 21P 854 (C)25P41.7 (C)29P25 (C)26P45 (M)22P (C)28P 1368 (TW)235P P P P 24P P 244P P P 18 DN (M)259P24 (J)257P22 (J)256P21 (M)258P14 254P P 252P 251P 25P 249P 248P 247P DN (C)281P P 42 (TM)236P AP 147 (G)29P 1177 (C)282P158 AC (6 Hz) Magnetic Field Levels Spot +1 Meter from Floor, Resultant Value in mg Field Management Services Corp. New York - Los Angeles

17 University of California, San Diego Literature Building - 3 SECOND FLOOR (Electrical & Elevator Room) AC (6 Hz) Magnetic Field Survey January 13, 21-4:15 PM AC (6 Hz) Magnetic Field Levels Spot +1 Meter from Floor, Resultant Value in mg Values in Blue - Elevators Being Exercised Field Management Services Corp. New York - Los Angeles

18 THIRD FLOOR University of California, San Diego Literature Building - 3 AC (6 Hz) Magnetic Field Survey January 13, 21-2:21PM (C)383P P DN 329P 327P P P 331P 325P P 324P P P P P P 2 315P P P (M)321P P 198 (C)35P41 (C)36P45 (M)32P19 (TW)335P P P 338P P 34P 341P P 343P P P 346P (C)38P25.1 (C)37P P P 297 (M)358P24 (J)356P21.2 DN (J)357P22 (M)359P14 355P P P 352P 351P 35P 349P 348P 347P DN (C)381P 156 (TM)336P158 (C)382P158 (G)39P 1177 AC (6 Hz) Magnetic Field Levels Spot +1 Meter from Floor, Resultant Value in mg Field Management Services Corp. New York - Los Angeles

19 University of California, San Diego Literature Building - 3 THIRD FLOOR (Electrical & Elevator Room) AC (6 Hz) Magnetic Field Survey January 13, 21-2:4 PM AC (6 Hz) Magnetic Field Levels Spot +1 Meter from Floor, Resultant Value in mg Values in Blue - Elevators Being Exercised Field Management Services Corp. New York - Los Angeles

20 FOURTH FLOOR University of California, San Diego Literature Building - 3 AC (6 Hz) Magnetic Field Survey January 13, 21-3:1 PM (C)483P P DN 429P 427P P P 431P 425P P P 433P.1 415P P P 418P P P 154 (M)422P P 149 (TW)435P P DP65 41CP65 419P 54 ELEVATOR ELEVATOR (C)45P41 (C)46P45 (M)42P19 41AP62 41BP 13 CONFERENCE ROOM 437P P P 44P 441P P 443P P P 446P 413P 84 (C)49P25 (C)48P P P P 262 DN (M)458P24 (J)457P22 (J)456P21 (M)459P14 453P 452P 451P 45P 449P 448P 447P DN (C)481P P P 237 (TM)458P158 (C)482P158 (G)49P 1177 AC (6 Hz) Magnetic Field Levels Spot +1 Meter from Floor, Resultant Value in mg Field Management Services Corp. New York - Los Angeles

21 University of California, San Diego Literature Building - 3 FOURTH FLOOR (Electrical & Elevator Room) AC (6 Hz) Magnetic Field Survey January 13, 21-3: PM AC (6 Hz) Magnetic Field Levels Spot +1 Meter from Floor, Resultant Value in mg Values in Blue - Elevators Being Exercised Field Management Services Corp. New York - Los Angeles

ELF Magnetic Field Survey & Assessment Report

ELF Magnetic Field Survey & Assessment Report ELF Magnetic Field Survey & Assessment Report of Literature Building - 3000 University of California San Diego for University of California San Diego La Jolla, California Report Date: FMS Ref: 2008-1020

More information

Research Activities Plan. Appendix K Magnetic Fields from Submarine Cables

Research Activities Plan. Appendix K Magnetic Fields from Submarine Cables VOWTAP Research Activities Plan Appendix K Magnetic Fields from Submarine Cables December 2013 Electrical Engineering and Computer Science Practice Virginia Offshore Wind Technology Advancement Project

More information

Subject: AC ELF EMF EMC Magnetic Field Testing for a Sauna Heater

Subject: AC ELF EMF EMC Magnetic Field Testing for a Sauna Heater EMF Measurements, Surveys & Risk Assessment EMF Mitigation Shielding & Cancellation E-Mail: dvitale@vitatech.net www.vitatech.net VitaTech Electromagnetics, LLC 115 Juliad Ct., Suite 105 Fredericksburg,

More information

Electric and magnetic field levels around Christchurch

Electric and magnetic field levels around Christchurch Electric and magnetic field levels around Christchurch M D Gledhill 1992/1 NRL Report Report NRL 1992/1 ISSN O111-753x ELECTRIC AND MAGNETIC FIELD LEVELS AROUND CHRISTCHURCH M D Gledhill National Radiation

More information

Intermediate Frequency Electric and Magnetic Emissions Testing

Intermediate Frequency Electric and Magnetic Emissions Testing Intermediate Frequency Electric and Magnetic Emissions Testing 22 December 2018 Prepared by: Charles Keen EMF SERVICES LLC www.emfservices.com 845-276-9500 Intermediate Frequency Electric and Magnetic

More information

The Nature of Electric and Magnetic Fields 2017

The Nature of Electric and Magnetic Fields 2017 The Nature of Electric and Magnetic Fields 2017 FACT SHEET 1 3 4 5 What are Electric and Magnetic Fields (EMF)? How are electricity and EMF related? Many people will have seen the attraction or repulsion

More information

v1.0.1 March AlphaLab, Inc. All rights reserved. TriField EMF Meter Owner s Manual

v1.0.1 March AlphaLab, Inc. All rights reserved. TriField EMF Meter Owner s Manual v1.0.1 March 2018 2018 AlphaLab, Inc. All rights reserved. TriField EMF Meter Owner s Manual TABLE OF CONTENTS Overview... 1 Introduction... 1 Features... 1 Applications... 1 Using the TriField EMF Meter...

More information

Mr. Aaron Zack Tel: Subject: AC ELF EMF EMC Magnetic Field Testing for a Sauna Heater

Mr. Aaron Zack Tel: Subject: AC ELF EMF EMC Magnetic Field Testing for a Sauna Heater 115 Juliad Court, Suite 105 Fredericksburg VA, 22406 Phone 540 286 1984 Fax 540 268 1865 www.vitatech.net November 14th, 2012 Mr. Aaron Zack Tel: 877.292.0020 President/CEO Email: azack@sunlighten.com

More information

Instructions for Use: DSP-523 True-RMS 3 Axis DSP Gaussmeter Magnii Technologies

Instructions for Use: DSP-523 True-RMS 3 Axis DSP Gaussmeter Magnii Technologies Instructions for Use: DSP-523 True-RMS 3 Axis DSP Gaussmeter Magnii Technologies www.magnii.com FEATURES 3 Axis AC Gaussmeter: Accurately measure AC magnetic fields regardless of meter orientation. Advanced

More information

MAGNETIC FIELD METER Operator s Manual

MAGNETIC FIELD METER Operator s Manual Edition 4.4 September 2011 MAGNETIC FIELD METER 3000 Operator s Manual The MFM 3000 is a professional magnetic field instrument To make the best use of the instrument we recommend that you read this manual

More information

ELF ELECTRIC AND MAGNETIC FIELDS MEASUREMENTS IN GREECE

ELF ELECTRIC AND MAGNETIC FIELDS MEASUREMENTS IN GREECE ELF ELECTRIC AND MAGNETIC FIELDS MEASUREMENTS IN GREECE E. Karabetsos, G. Filippopoulos, D. Koutounidis CH. Govari, N. Skamnakis Non ionizing radiation office, Greek atomic energy commission, P. O. BOX

More information

F3A Magnetic Field Transducers

F3A Magnetic Field Transducers DESCRIPTION: The F3A denotes a range of SENIS Magnetic Fieldto-Voltage Transducers with fully integrated 3-axis Hall Probe. The Hall Probe contains a CMOS integrated circuit, which incorporates three groups

More information

Magnetic Field Meter EM-191

Magnetic Field Meter EM-191 Magnetic Field Meter EM-191 1 Introduction Safety precautions should be taken against electric appliances in places including medical institutions, schools and residential districts, where people usually

More information

Interpreting RF Radiation Patterns

Interpreting RF Radiation Patterns Interpreting RF Radiation Patterns Application Note D00001625 Rev 1.0 Page 2 of 9 Interpreting RF Radiation Patterns, Rev 1.0 Copyright Information and Usage Notice This information disclosed herein is

More information

Grounding Complications

Grounding Complications Grounding Complications Sensitive Equipment Isolated grounding Supplemental grounds Sensitive Electronic Equipment NEC 647 [2002-2005] Originally intended for audio studios -- now Industrial/commercial

More information

LOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS

LOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS LOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS Peter Leipold, Klaus-Peter Panzlaff Bewag Aktiengesellschaft, Puschkinallee 52, D-12435 Berlin Tel.: +49 30 267 10 350 - Fax: +49 30 267 10 352 -

More information

PS 1000 X-Scan Tips & Tricks. Quick Guide

PS 1000 X-Scan Tips & Tricks. Quick Guide PS 1000 X-Scan Tips & Tricks Quick Guide en en QUICK GUIDE Tips & tricks 1. PS 1000 X-Scan Scanning on rough surfaces When the scanner is moved over a rough surface, the distance between the scanner and

More information

B perpendicular to plane of loop

B perpendicular to plane of loop SYNOPSS #3 EMF ENGNEERNG REVEW SYMPOSUM Version 04/22/98 NSTRUMENTATON AND MEASUREMENT TECHNOLOGY GARY B. JOHNSON POWER ENGNEERNG RESEARCH EMF MEASUREMENT: NSTRUMENTATON The measurement of any quantity

More information

Zoning Amendment Carlson Z AP 8234 Carlson under separate cover Development Permit/Specific Use PSCo DP AP 8237 PSCo

Zoning Amendment Carlson Z AP 8234 Carlson under separate cover Development Permit/Specific Use PSCo DP AP 8237 PSCo FILED ELECTRONICALLY May 3, 2017 Ms. Lori Hight, AICP Senior Planner City Development 9500 Civic Center Drive Thornton, CO 80229 Re: Response to Comments on the Second Review of the Land Development Approvals

More information

F1A Magnetic Field Transducers

F1A Magnetic Field Transducers DESCRIPTION: The F1A denotes a range of SENIS Magnetic Fieldto- Voltage Transducers with fully integrated 1-axis Hall Probe. It measures magnetic fields perpendicular to the probe plane (By). The Hall

More information

GEOMETRICS technical report

GEOMETRICS technical report GEOMETRICS technical report MA-TR 15 A GUIDE TO PASSIVE MAGNETIC COMPENSATION OF AIRCRAFT A fixed installation of a total field magnetometer sensor on an aircraft is much more desirable than the towed

More information

I1A Magnetic Field Transducers

I1A Magnetic Field Transducers DESCRIPTION: The I1A denotes a range of SENIS Magnetic Fieldto-Voltage Transducers with integrated 1-axis Hall Probe. It measures magnetic fields perpendicular to the probe plane (By). The Hall Probe contains

More information

DISCUSSION OF FUNDAMENTALS

DISCUSSION OF FUNDAMENTALS Unit 4 AC s UNIT OBJECTIVE After completing this unit, you will be able to demonstrate and explain the operation of ac induction motors using the Squirrel-Cage module and the Capacitor-Start Motor module.

More information

CHAPTER ELECTRIC AND MAGNETIC FIELDS

CHAPTER ELECTRIC AND MAGNETIC FIELDS CHAPTER 62-814 ELECTRIC AND MAGNETIC FIELDS 62-814.100 Intent, Findings, Basis of Standards, and Research Needs 62-814.200 Electric and Magnetic Fields; Definitions 62-814.300 General Technical Requirements

More information

Upgrading Your Electrical Distribution System To Resistance Grounding

Upgrading Your Electrical Distribution System To Resistance Grounding Upgrading Your Electrical Distribution System To Resistance Grounding The term grounding is commonly used in the electrical industry to mean both equipment grounding and system grounding. Equipment grounding

More information

Report Of. Shielding Effectiveness Test For. DefenderShield. Test Date(s): September 1 October 2, 2012

Report Of. Shielding Effectiveness Test For. DefenderShield. Test Date(s): September 1 October 2, 2012 Report Of Test For Test Date(s): September 1 October 2, 2012 UST Project No: Total Number of Pages Contained Within This Report: 15 3505 Francis Circle Alpharetta, GA 30004 PH: 770-740-0717 Fax: 770-740-1508

More information

STEREO IMPACT Solar Energetic Particles Package (SEP) Dynamic Test Plan

STEREO IMPACT Solar Energetic Particles Package (SEP) Dynamic Test Plan 1 2 Jet Propulsion Laboratory 352G-WBT-0507 Interoffice Memorandum January 13, 2005 To: From: Subject: References: Distribution W. B. Tsoi STEREO IMPACT Solar Energetic Particles Package (SEP) Dynamic

More information

Current transducer FHS 40-P/SP600

Current transducer FHS 40-P/SP600 Current transducer I PM = 0-100 A Minisens transducer The Minisens transducer is an ultra flat SMD open loop integrated circuit current transducer based on the Hall effect principle. It is suitable for

More information

H3A Magnetic Field Transducer

H3A Magnetic Field Transducer DESCRIPTION: The H3A denotes a range of Low Noise SENIS Magnetic Field-to-Voltage Transducers with hybrid 3- axis Hall Probe. The Hybrid Hall Probe integrates three highresolution with good angular accuracy

More information

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential

More information

DEP 2008 ELECTRIC AND MAGNETIC FIELDS CHAPTER ELECTRIC AND MAGNETIC FIELDS

DEP 2008 ELECTRIC AND MAGNETIC FIELDS CHAPTER ELECTRIC AND MAGNETIC FIELDS CHAPTER 62-814 ELECTRIC AND MAGNETIC FIELDS TABLE OF CONTENTS PAGE 62-814.100 Intent, Findings, Basis of Standards, and Research Needs. 2 62-814.200 Electric and Magnetic Fields; Definitions. 3 62-814.300

More information

3Ø Short-Circuit Calculations

3Ø Short-Circuit Calculations 3Ø Short-Circuit Calculations Why Short-Circuit Calculations Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

Report. Mearns Consulting LLC. Former Gas Station 237 E. Las Tunas Drive San Gabriel, California Project # E

Report. Mearns Consulting LLC. Former Gas Station 237 E. Las Tunas Drive San Gabriel, California Project # E Mearns Consulting LLC Report Former Gas Station 237 E. Las Tunas Drive San Gabriel, California Project #1705261E Charles Carter California Professional Geophysicist 20434 Corisco Street Chatsworth, CA

More information

Magnetic fields around transmission lines in northeast Arizona a field study by Andrew Eriksen with comments by Ragnar Forshufvud

Magnetic fields around transmission lines in northeast Arizona a field study by Andrew Eriksen with comments by Ragnar Forshufvud Magnetic fields around transmission lines in northeast Arizona a field study by Andrew Eriksen with comments by Ragnar Forshufvud The magnetic fields (EMF) around power lines can be measured up to several

More information

Niederfrequenz-Analyser für elektrische und magnetische NF-Wechselfelder

Niederfrequenz-Analyser für elektrische und magnetische NF-Wechselfelder ME3030B ME3830 ME3951A (16 Hz 2 khz) (16 Hz 100 khz) (5 Hz 100 khz) Deutsch Seite 1 English Page 6 Italiano Page 11 Français Page 16 Español Página 21 Niederfrequenz-Analyser für elektrische und magnetische

More information

Reducing personal EMF exposure

Reducing personal EMF exposure www.emfields-solutions.com www.powerwatch.org.uk EMFields Solutions Ltd in conjunction with Powerwatch This leaflet and information are written for the EMFields pocket PF5 meter which measures ELF and

More information

Royal Street Communications, LLC Proposed Base Station (Site No. LA0366A) 315 4th Avenue Venice, California

Royal Street Communications, LLC Proposed Base Station (Site No. LA0366A) 315 4th Avenue Venice, California Statement of Hammett & Edison, Inc., Consulting Engineers The firm of Hammett & Edison, Inc., Consulting Engineers, has been retained on behalf of Royal Street Communications, LLC, a personal wireless

More information

ELECTROMAGNETIC ENERGY (EME) EXPOSURE REPORT

ELECTROMAGNETIC ENERGY (EME) EXPOSURE REPORT ELECTROMAGNETIC ENERGY (EME) EXPOSURE REPORT Site Name: Site ID: USID: FA Location: Marin Avenue CCL04554 101927 10113497 Site Type: Location: Latitude (NAD83): NAD83): Longitude (NAD83): Report Completed:

More information

Voltage-Versus-Speed Characteristic of a Wind Turbine Generator

Voltage-Versus-Speed Characteristic of a Wind Turbine Generator Exercise 1 Voltage-Versus-Speed Characteristic of a Wind Turbine Generator EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the principle of electromagnetic induction.

More information

Measurements of MeV Photon Flashes in Petawatt Laser Experiments

Measurements of MeV Photon Flashes in Petawatt Laser Experiments UCRL-JC-131359 PREPRINT Measurements of MeV Photon Flashes in Petawatt Laser Experiments M. J. Moran, C. G. Brown, T. Cowan, S. Hatchett, A. Hunt, M. Key, D.M. Pennington, M. D. Perry, T. Phillips, C.

More information

Electromagnetic Harmonic Filters Technical Guide

Electromagnetic Harmonic Filters Technical Guide Eliminator Series Electromagnetic Harmonic Filters Technical Guide Neutral Eliminator TM (NCE TM ) Parallel connected, 3-phase, 4-wire passive electromagnetic device that diverts 3rd and other triplen

More information

Project: IEEE P Working Group for Wireless Personal Area Networks (WPANs)

Project: IEEE P Working Group for Wireless Personal Area Networks (WPANs) Project: IEEE P802.15 Working Group for Wireless Personal Area Networks (WPANs) Title: Panasonic Chanel Models for Image Sensor-based Communication Date Submitted: July, 2015 Source: Hideki Aoyama Panasonic

More information

FCC PART 95 MEASUREMENT AND TEST REPORT. Powerwerx, Inc.

FCC PART 95 MEASUREMENT AND TEST REPORT. Powerwerx, Inc. FCC PART 95 MEASUREMENT AND TEST REPORT For Powerwerx, Inc. 23695 Via Del Rio Yorba Linda California 92887, United States FCC ID: 2ACK8TR505D Report Type: Original Report Product Type: Two-way radio Test

More information

I. Introduction to Animal Sensitivity and Response

I. Introduction to Animal Sensitivity and Response I. Introduction to Animal Sensitivity and Response The term stray voltage has been used to describe a special case of voltage developed on the grounded neutral system of a farm. If this voltage reaches

More information

1.0 Job Description 1.1 Client Information This EUT has been tested at the request of: Company: Spectronic Denmark A/S Contact: John Herlev Telephone: 011 45 863-87-222 Fax: 011 45 863-87-704 Email: jhe@spectronic-denmark.com

More information

STATE UNIVERSITY CONSTRUCTION FUND

STATE UNIVERSITY CONSTRUCTION FUND DIRECTIVE 1C-12 Issue date: August 2012 1. General SURVEY, MAPPING AND UTILITY LOCATING This Directive has been developed as a general guide for the survey and mapping effort required for Fund projects.

More information

MAGNETIC FIELD METER Operator s Manual

MAGNETIC FIELD METER Operator s Manual Edition 3.1 2009-09-03 MAGNETIC FIELD METER 2000 Operator s Manual The MFM 2000 is a professional magnetic field instrument To make the best use of the instrument we recommend that you read this manual

More information

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...

More information

Short-Circuit Current Calculations

Short-Circuit Current Calculations Basic Point-to-Point Calculation Procedure Step. Determine the transformer full load amps (F.L.A.) from either the nameplate, the following formulas or Table : Multiplier = 00 *% Z transformer Step 2.

More information

INTEGRATED METHOD IN ELECTROMAGNETIC INTERFERENCE STUDIES

INTEGRATED METHOD IN ELECTROMAGNETIC INTERFERENCE STUDIES INTEGRATED METHOD IN ELECTROMAGNETIC INTERFERENCE STUDIES Jinxi Ma and Farid P. Dawalibi Safe Engineering Services & technologies ltd. 1544 Viel, Montreal, Quebec, Canada, H3M 1G4 Tel.: (514) 336-2511

More information

Gareth Evans STV. Peter Tabolt STV. Boston, MA. Philadelphia, PA. Simulation and Mitigation of Magnetic Field Created By Traction Power Systems

Gareth Evans STV. Peter Tabolt STV. Boston, MA. Philadelphia, PA. Simulation and Mitigation of Magnetic Field Created By Traction Power Systems Simulation and Mitigation of Magnetic Field Created By Traction Power Systems Peter Tabolt STV Vehicle Specialist Boston, MA Gareth Evans STV Senior Vehicle Specialist Philadelphia, PA 1 Presentation Purpose

More information

Verizon Wireless Proposed Base Station (Site No South Goleta ) 4500 Hollister Avenue Santa Barbara, California

Verizon Wireless Proposed Base Station (Site No South Goleta ) 4500 Hollister Avenue Santa Barbara, California Statement of Hammett & Edison, Inc., Consulting Engineers The firm of Hammett & Edison, Inc., Consulting Engineers, has been retained on behalf of Verizon Wireless, a personal wireless telecommunications

More information

X80 Activator. User's Manual. Version 1.1.

X80 Activator. User's Manual. Version 1.1. X80 Activator User's Manual Version 1.1 www.buckeyecam.com Table of Contents 1. Warnings... 3 2. Overview... 4 3. Getting Started... 5 4. Using the Activate Button... 7 5. Wiring... 8 6. Specifications...

More information

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Substation Auxiliary Transformer from Rectifier Transformer Secondary Reference Number PDS 01 (RIC Standard: EP 05 00 00 01 SP) Document Control

More information

Chrysalis E - AC Magnetic Field Assessment

Chrysalis E - AC Magnetic Field Assessment Safe Living Technologies Inc. 7 Clair Road West, P.O. Box 27051, Guelph, ON N1L0A0, Canada Tel: 519-240-8735 support@slt.co www.slt.co Chrysalis E - AC Magnetic Field Assessment Chrysalis Energies Corporation

More information

RADIOFREQUENCY ELECTROMAGNETIC FIELDS

RADIOFREQUENCY ELECTROMAGNETIC FIELDS CHAPTER 19. RADIOFREQUENCY ELECTROMAGNETIC FIELDS 19.1 INTRODUCTION 19.1.1 CONTEXT The proposed buildings of the World Trade Center Memorial and Redevelopment Plan (Proposed Action) are being designed

More information

AT&T Mobility Proposed Base Station (Site No. CN4779A) 1101 Keaveny Court Walnut Creek, California

AT&T Mobility Proposed Base Station (Site No. CN4779A) 1101 Keaveny Court Walnut Creek, California Statement of Hammett & Edison, Inc., Consulting Engineers The firm of Hammett & Edison, Inc., Consulting Engineers, has been retained on behalf of AT&T Mobility, a personal wireless telecommunications

More information

POWER TRACE TM TASCO, INC.

POWER TRACE TM TASCO, INC. POWER TRACE TM Instruction Manual PTL610 TASCO, INC. HOW YOUR POWER TRACE TM OPERATES The Power Trace TM is composed of two primary components: the Receiver and the Transmitter. When the Transmitter is

More information

RTCA Special Committee 186, Working Group 5 ADS-B UAT MOPS. Meeting #3. UAT Performance in the Presence of DME Interference

RTCA Special Committee 186, Working Group 5 ADS-B UAT MOPS. Meeting #3. UAT Performance in the Presence of DME Interference UAT-WP-3-2 2 April 21 RTCA Special Committee 186, Working Group 5 ADS-B UAT MOPS Meeting #3 UAT Performance in the Presence of DME Interference Prepared by Warren J. Wilson and Myron Leiter The MITRE Corp.

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 200-215.3 CHANGES FROM 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 200 Use and Identification of Grounded Conductors 200.2 General Grounded Conductors

More information

Utility Locating Terminology & Equipment Guide. Utility Survey Corp.

Utility Locating Terminology & Equipment Guide. Utility Survey Corp. Utility Locating Terminology & Equipment Guide Utility Survey Corp. Contents Utility Locating Terminology Utility Locating Toning or Scoping Scanning X Ray the Ground & Ground Penetrating Radar 3 4 5 6

More information

FGM-series Magnetic Field Sensors

FGM-series Magnetic Field Sensors Speake & Co. Limited Distributed in the United States by Fat Quarters Software 24774 Shoshonee Drive Murrieta, California 92562 USA Tel: 951-69-7950 Fax: 951-69-7913 FGM-series Magnetic Field Sensors +5

More information

Human Exposure Requirements for R&TTE and FCC Approval

Human Exposure Requirements for R&TTE and FCC Approval Human Exposure Requirements for R&TTE and FCC Approval Derek Y. W. LEUNG Founding and Committee Member of EMC Chapter- IEEE-HK Requirements of Non-Specific Short Range Device (SRD) for CE Marking Radio

More information

Analysis of static and time-variable magnetic fields

Analysis of static and time-variable magnetic fields Magnetometer HP-01 Analysis of static and time-variable magnetic fields Field exposure evaluation according to current standards and regulations such as Directive 2013/35/EU for workplaces Frequency-selective

More information

2-wire level transmitter

2-wire level transmitter Badger Meter Europa GmbH 2-wire level transmitter Model L2xx INSTALLATION AND OPERATION MANUAL July 2002 Version UF-L2xx-07/02-e Contents Contents Page 1. Installation 1 1.1 Mounting the instrument 1 1.2

More information

PalmGauss SC PGSC-5G. Instruction Manual

PalmGauss SC PGSC-5G. Instruction Manual PalmGauss SC PGSC-5G Instruction Manual PalmGauss SC PGSC 5G Instruction Manual Thank you very much for purchasing our products. Please, read this instruction manual in order to use our product in safety

More information

RF FIELD SURVEY REPORT

RF FIELD SURVEY REPORT RF FIELD SURVEY REPORT MANLY NATIONAL BUILDING 22 CENTRAL AVE, MANLY, NSW RFNSA #: 2095004 DATE OF SURVEY: 18TH NOVEMBER 2016 REPORT VERSION: R1 Accredited for compliance with ISO/IEC 17025 The results

More information

Experiment 12: Microwaves

Experiment 12: Microwaves MASSACHUSETTS INSTITUTE OF TECHNOLOGY Department of Physics 8.02 Spring 2005 OBJECTIVES Experiment 12: Microwaves To observe the polarization and angular dependence of radiation from a microwave generator

More information

Eddy current flaw detector «Eddycon C»

Eddy current flaw detector «Eddycon C» ULTRACON-SERVICE LLC Eddy current flaw detector «Eddycon C» Quick start guide CONTENTS P. 1 CONTROLLERS OF EDDYCON C FLAW DETECTOR... 3 2 SETTINGS OF «TEST» MENU... 5 3 INSTRUCTIONS FOR USE... 8 3.1 THRESHOLD

More information

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS Ljubomir KOJOVIC Cooper Power Systems - U.S.A. Lkojovic@cooperpower.com INTRODUCTION In steel facilities that use Electric Arc Furnaces (EAFs) to manufacture

More information

Wireless Facility Peer Engineering Review

Wireless Facility Peer Engineering Review Page 1 of 11 Wireless Facility Peer Engineering Review Regarding Verizon Wireless Application 2750 Dwight Way, Berkeley, CA August 10, 2015 Page 2 of 11 Introduction RCC Consultants, Inc. has been engaged

More information

HARMONIC MITIGATIONCASE STUDY

HARMONIC MITIGATIONCASE STUDY HARMONIC MITIGATIONCASE STUDY CNCE AND NCE INSTALLATION AT BROADCASTING STUDIO Concerned about video noise detected on some of its studio equipment, E! Entertainment Television (ETV), commissioned a study

More information

Lecture 3.10 ELECTRICITY Alternating current Electrical safety

Lecture 3.10 ELECTRICITY Alternating current Electrical safety Lecture 3.1 ELECTRCTY Alternating current Electrical safety Alternating Current (ac) Batteries are a source of steady or direct voltage. Current in a circuit powered by a battery is also steady and is

More information

AGN 008 Vibration DESCRIPTION. Cummins Generator Technologies manufacture ac generators (alternators) to ensure compliance with BS 5000, Part 3.

AGN 008 Vibration DESCRIPTION. Cummins Generator Technologies manufacture ac generators (alternators) to ensure compliance with BS 5000, Part 3. Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 008 Vibration DESCRIPTION Cummins Generator Technologies manufacture ac generators (alternators) to ensure compliance

More information

Signal and Noise Measurement Techniques Using Magnetic Field Probes

Signal and Noise Measurement Techniques Using Magnetic Field Probes Signal and Noise Measurement Techniques Using Magnetic Field Probes Abstract: Magnetic loops have long been used by EMC personnel to sniff out sources of emissions in circuits and equipment. Additional

More information

"Natural" Antennas. Mr. Robert Marcus, PE, NCE Dr. Bruce C. Gabrielson, NCE. Security Engineering Services, Inc. PO Box 550 Chesapeake Beach, MD 20732

Natural Antennas. Mr. Robert Marcus, PE, NCE Dr. Bruce C. Gabrielson, NCE. Security Engineering Services, Inc. PO Box 550 Chesapeake Beach, MD 20732 Published and presented: AFCEA TEMPEST Training Course, Burke, VA, 1992 Introduction "Natural" Antennas Mr. Robert Marcus, PE, NCE Dr. Bruce C. Gabrielson, NCE Security Engineering Services, Inc. PO Box

More information

VHF LAND MOBILE SERVICE

VHF LAND MOBILE SERVICE RFS21 December 1991 (Issue 1) SPECIFICATION FOR RADIO APPARATUS: VHF LAND MOBILE SERVICE USING AMPLITUDE MODULATION WITH 12.5 khz CARRIER FREQUENCY SEPARATION Communications Division Ministry of Commerce

More information

Regulatory Authority of Bermuda report on

Regulatory Authority of Bermuda report on Regulatory Authority of Bermuda report on Bermuda Electric Light Company Smart Meter Maximum Permissible Exposure 14 June 2018 This report reflects the electromagnetic radio frequency Maximum Permissible

More information

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING 1 PRACTICAL PROBLEMS WITH SUBSTATION EARTHING Dr Hendri Geldenhuys Craig Clark Eskom Distribution Technology This paper considers the issues around substation sites where the soil resistivity is of particularly

More information

ELECTROMAGNETIC INDUCTION AND ALTERNATING CURRENT (Assignment)

ELECTROMAGNETIC INDUCTION AND ALTERNATING CURRENT (Assignment) ELECTROMAGNETIC INDUCTION AND ALTERNATING CURRENT (Assignment) 1. In an A.C. circuit A ; the current leads the voltage by 30 0 and in circuit B, the current lags behind the voltage by 30 0. What is the

More information

Standardized Measurements for Elevated NEV and Energized Object Concerns Doug Dorr, Charles Perry, Mark McGranaghan Arindam Maitra, Wes Sunderman

Standardized Measurements for Elevated NEV and Energized Object Concerns Doug Dorr, Charles Perry, Mark McGranaghan Arindam Maitra, Wes Sunderman Standardized Measurements for Elevated NEV and Energized Object Concerns Doug Dorr, Charles Perry, Mark McGranaghan Arindam Maitra, Wes Sunderman Doug Dorr EPRI Solutions Inc. ddorr@eprisolutions.com 407-968-3010

More information

A Study of Magnetic Shielding Performance of a Fermilab International Linear Collider Superconducting RF Cavity Cryomodule

A Study of Magnetic Shielding Performance of a Fermilab International Linear Collider Superconducting RF Cavity Cryomodule A Study of Magnetic Shielding Performance of a Fermilab International Linear Collider Superconducting RF Cavity Cryomodule Anthony C. Crawford Fermilab Technical Div. / SRF Development Dept. acc52@fnal.gov

More information

Magnetic Field Meter BMM-5 user instructions

Magnetic Field Meter BMM-5 user instructions EnviroMentor has both the measuring instruments and the expertise English EnviroMentor AB is a young, skills-based company, yet is also one of the oldest in its field. All of our measuring instruments

More information

Radio Frequency Exposure Test Report

Radio Frequency Exposure Test Report Radio Frequency Exposure EN 62311 January 2008 Assessment of electronic and electrical equipment related to human exposure restrictions for electromagnetic fields (0Hz 300GHz) (IEC 62311:2007, modified)

More information

Telecommunication Wiring Questions

Telecommunication Wiring Questions Telecommunication Wiring Questions 1. is the process of modifying a carrier frequency in rhythm to the audio frequency. A, Modulation B. Amplitude C. Change of phase D. Interference 2. is the property

More information

Lecture 9: Spread Spectrum Modulation Techniques

Lecture 9: Spread Spectrum Modulation Techniques Lecture 9: Spread Spectrum Modulation Techniques Spread spectrum (SS) modulation techniques employ a transmission bandwidth which is several orders of magnitude greater than the minimum required bandwidth

More information

Road vehicles Component test methods for electrical disturbances from narrowband radiated electromagnetic energy. Part 3:

Road vehicles Component test methods for electrical disturbances from narrowband radiated electromagnetic energy. Part 3: INTERNATIONAL STANDARD ISO 11452-3 Third edition 2016-09-01 Road vehicles Component test methods for electrical disturbances from narrowband radiated electromagnetic energy Part 3: Transverse electromagnetic

More information

Grounding Recommendations for On Site Power Systems

Grounding Recommendations for On Site Power Systems Grounding Recommendations for On Site Power Systems Revised: February 23, 2017 2017 Cummins All Rights Reserved Course Objectives Participants will be able to: Explain grounding best practices and code

More information

Radio Frequency Electromagnetic Energy (RF-EME) Compliance Report

Radio Frequency Electromagnetic Energy (RF-EME) Compliance Report Page 1 of 36 Radio Frequency Electromagnetic Energy (RF-EME) Compliance Report Site No. FN03XC065 Huntmount Medical Center 2999 Regent Street Berkeley, California 94705 Alameda County 37.855900; -122.256000

More information

Improve asset protection and utilization

Improve asset protection and utilization QUALITROL 509 ITM Intelligent transformer monitor Improve asset protection and utilization Immediately know your transformer health with TransLife Optimize loading and equipment life Simplify root cause

More information

EN 62479:2010 ASSESSMENT REPORT WIN CHANNEL ELECTRONICS (HK) CO., LTD

EN 62479:2010 ASSESSMENT REPORT WIN CHANNEL ELECTRONICS (HK) CO., LTD EN 62479:2010 ASSESSMENT REPORT For WIN CHANNEL ELECTRONICS (HK) CO., LTD No.1, Shangxing Road, Shangjiao, Changan Town, Dongguan, Guangdong, China Tested Model: 318EU Multiple Models: 73500, 73506, FREECOMM

More information

AC Voltage- Pipeline Safety and Corrosion MEA 2015

AC Voltage- Pipeline Safety and Corrosion MEA 2015 AC Voltage- Pipeline Safety and Corrosion MEA 2015 WHAT ARE THE CONCERNS ASSOCIATED WITH AC VOLTAGES ON PIPELINES? AC concerns Induced AC Faults Lightning Capacitive coupling Safety Code Induced AC Corrosion

More information

EM-7530 Meter, Magnetic Field Strength

EM-7530 Meter, Magnetic Field Strength EM-7530 Meter, Magnetic Field Strength Specifications Electrical Special Features Full operation from either front-panel controls or from computer via GPIB for maximum versatility. Special compact highly-sensitive

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Verizon Wireless Proposed Base Station (Site No Lake Cachuma ) 2680 Highway 154 Santa Barbara County, California

Verizon Wireless Proposed Base Station (Site No Lake Cachuma ) 2680 Highway 154 Santa Barbara County, California Statement of Hammett & Edison, Inc., Consulting Engineers The firm of Hammett & Edison, Inc., Consulting Engineers, has been retained on behalf of Verizon Wireless, a personal wireless telecommunications

More information

Radiodetection Pipeline Products

Radiodetection Pipeline Products Radiodetection Pipeline Products For efficient troubleshooting of cathodic protection systems on buried pipelines The Pipeline Range Pipeline Products Radiodetection is the world leader in the field of

More information

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the

More information

Alternating Current Page 1 30

Alternating Current Page 1 30 Alternating Current 26201 11 Page 1 30 Calculate the peak and effective voltage of current values for AC Calculate the phase relationship between two AC waveforms Describe the voltage and current phase

More information

HAWK5000 Operators Manual

HAWK5000 Operators Manual HAWK5000 Operators Manual Keison Products P.O. Box 2124, Chelmsford CM1 3UP, England Tel: +44 (0) 1245 600560 Fax: +44 (0) 1245 600030 Email: sales@keison.co.uk www.keison.co.uk KANE INTERNATIONAL LIMITED

More information