SPPA-E3000 Brushless Excitation System (BES, Type RG3)

Size: px
Start display at page:

Download "SPPA-E3000 Brushless Excitation System (BES, Type RG3)"

Transcription

1 / Technical Description / Juni 2014 SPPA-E3000 Brushless Excitation System (BES, Type RG3) Maximum-availability excitation system for synchronous generators with brushless exciters Answers for energy.

2 Table of Contents 1. Introduction Basic circuit Method of operation Automatic voltage regulator (automatic control system) Manual control system (excitation current regulator) Other operating modes Follow-up control Limiters Overmodulation and field-forcing limiter Power system stabilizer (PSS) Open-loop control Power circuit De-excitation Basic modules Basic modules Data exchange with DCS Local operator and monitoring Software Areas of Applicaltion Technical Data Abbreviations Unrestricted Siemens AG All rights reserved

3 1. Introduction The automatic voltage regulator SPPA-E3000 BES Type RG3 (SPPA Siemens Power Plant Automation) for brushless excitation system is suitable for any type of synchronous generator. It is equally suited to hydroelectric, steam, or nuclear power plants. Thanks to its high degree of flexibility, it can be adapted to the conditions of any plant and is an optimal solution both for new plants and for the modernization of existing plants. Depending on the technical aspects of the modernization of existing plants, a number of flexible, project-specific adaptations are possible. The main performance characteristics of the BES excitation system are: High reliability High availability Good adaptability Low maintenance requirements High speed of response Good regulating properties Robust construction Digital open- and closed-loop control Extreme flexibility Compact design Low space requirements Figure 1: SPPA-E3000 BES Type RG3-S (Example) The voltage converter is implemented with a powerful microprocessor which, besides performing voltage control, also assumes all the important limitation and monitoring functions of the excitation system. A high availability factor is achieved by the use of field-proven industrial components. It s completely modular design makes the operation and maintenance extremely user friendly. A brief description of the main components of the excitation system is given below followed by a detailed description of the device and component scope and their functions. 3 Unrestricted Siemens AG All rights reserved

4 2. Basic circuit The voltage regulator RG3 is suitable for brushless excitation system for synchronous generators with an exciter. It can also be connected directly to the slip rings of the generator. Its high flexibility and modular design make it suitable for use in all power plant types, and especially for the modernization of existing plants. Versions of BES available: RG3 DUR is designed especially for small generators with excitation current up to 30 A RG3 S is suitable for all power ratings. This version also offers the full flexibility of the logic as well as in the communication to the control system The power section comprises a transistorized chopper regulator which is connected to the field winding of the exciter or the generator slip rings. The BES excitation system can obtain its excitation power from any of the following: from the permanent-magnet pilot exciter (PMG) from an auxiliary winding in the generator stator (e.g. clamping bolt voltage of laminated core) from the auxiliary power supply of the power plant via a separate excitation transformer This excitation transformer can either be connected to the terminals of the synchronous generator or supplied by the auxiliary power supply. Other redundant power supplies are possible, e.g. battery power supply or UPS system. A redundant power supply from two or more of the sources named above is also possible in order to increase the availability. The modular design, the flexible software of the digital open- and closed-loop control, and the low space requirements make the RG3 especially suited for new plants and for the modernization of existing excitation systems. 4 Unrestricted Siemens AG All rights reserved

5 3. Method of operation 3.1 Automatic voltage regulator (automatic control system) In this operating mode the generator voltage actual value is compared with an adjustable generator voltage setpoint in the automatic voltage regulator. The resulting signal is compared with the outputs of the excitation limit controllers and applied to the input of the PI voltage regulator. The PI voltage regulator, whose gain and time response can be adjusted, supplies an output signal which is used as the current setpoint input (I setpoint) for the lower-level excitation current regulator. The degree of modulation of the pulse-width modulated trigger signals for the power transistors varies depending on the output of the current regulator. The structure of the AVR is represented by the model AC7B in IEEE Manual control system (excitation current regulator) A smoothed setpoint signal is input to the associated P-action control amplifier in the excitation current regulator and compared with the excitation current actual value. The output signal controls the power transistors of the associated output stage by means of pulse-width modulation. This operating mode is especially used during commissioning and testing of the generator and protection system. It is also the emergency operating mode as a backup mode for the AVR. 3.3 Other operating modes Automatic power factor regulation or reactive power regulation on generator leads or net coupling point The power factor regulator compares the actual value with an adjustable power factor setpoint. In the event of a deviation, the setpoint value of the voltage regulator is adjusted until the power factor deviation is reduced to zero. In isolated or no-load operation of the generator, automatic switchover from the power factor regulator to the automatic voltage regulator is performed. The reactive power regulator is working analog to the power factor regulator. Optionally also regulation at the net coupling point is available. Of the three operating modes (chapter 3.1, 3.2 and 3.3), the automatic voltage regulator is normally the one in operation, even during startup and shutdown of the turbine generator. The automatic voltage regulator comprises measured value acquisition, setpoint inputs and the control and monitoring circuits for the following functions: Generator voltage regulation Lower-level control and limitation of the excitation current (excitation current regulation) and/or field-forcing limiter Limit controller for the under-excited range (under-excitation limiter) Delayed limit controller for the overexcited range (overexcitation limiter) Delayed generator current limit controller (stator current limiter) 3.4 Follow-up control The setpoint value of the excitation current controller is continuously updated during operation with the automatic control system, thus ensuring rapid and virtually bumpless changeover to the excitation current regulator (manual control system or the other channel) in the event of a fault. Automatic changeover takes place, for example, when internal monitoring functions for the excitation current respond and in the event of error messages relating to generator voltage actual value acquisition. 5 Unrestricted Siemens AG All rights reserved

6 3.5 Limiters When operating a synchronous generator, it is necessary to observe the permissible combinations of active and reactive power, as shown in the capability diagram. L-M-O O-P P-Q Limit characteristic of the underexcited range Limit characteristic set by the stator temperature rise Limit characteristic set by the rotor temperature rise The underexcitation limiter corrects the reactive power by raising the generator voltage such that, in the case of an excursion beyond limit characteristic L-M-O, the operating point is returned to that characteristic before the generator is tripped by the underexcitation protection. This limiter can be represented by UEL2 model in IEEE Figure 2: Limit characteristics of synchronous generator in The overexcitation limiter ensures that the operating point is always kept within section P-Q of the generator capability diagram in the overexcited range. In response to system voltage drops caused by high reactive power requirements, switching operations or faults, the voltage regulator raises the excitation level so as to keep the generator voltage constant. The overexcitation limiter acts as a safeguard against thermal overloading of the rotor. The overexcitation limiter permits excitation values between the maximum continuous current and the maximum excitation current (field-forcing) for a limited period of time to enable the generator to provide voltage support in response to short-time voltage dips on the power system. The excitation current limiter (field-forcing limiter), in contrast, has the task of limiting the excitation current to the maximum permissible value as quickly as possible. The stator current limiter ensures delayed limiting to the continuously permitted stator current. The task of the stator current limiter is to prevent the thermal overload of the generator stator which can be caused by high reactive power at increased active power. The stator current limiter also permits increased excitation values for a limited period to enable the generator to provide voltage support for the power system. Figure 3: Underexcitation limiter Ceiling current limiter Overexitation limiter Ceiling current limiter Figure 4: Overexcitation limiter and ceiling current limiter 6 Unrestricted Siemens AG All rights reserved

7 3.6 Overmodulation and field-forcing limiter At full modulation, the chopper regulator outputs a higher voltage than is required for excitation to ceiling current. This voltage overmodulation of the field winding shortens the time required for the ceiling current to be reached, thus also shortening the compensation of setpoint deviations of the voltage on the generator terminals. The output voltage of the chopper regulator for the manual control system is limited by the upper value of the setpoint. The output voltage of the chopper regulator for the automatic control system is affected by the modulation limiter of the PI voltage regulator. This reference variable corresponds to the voltage value of the required excitation current. Figure 5: Overexcitation limiter and lower-level excitation current limiter 3.7 Power system stabilizer (PSS) A "Dual Input PSS" according to IEEE type PSS2B is implemented. This feature acquires the frequency or active power changes in the natural frequency range of the generator and the network, and exerts a damping influence through the voltage regulator and the generator excitation. This is achieved by calculation of the integral of the accelerating power from the electrical active power and compensated frequency as input variables into the PSS. Implemented is also the model Hinfinite (PSS3B). A PSS is recommended for networks where steady-state stability is endangered by the presence of long transmission lines and the natural damping properties of the generator are inadequate. 7 Unrestricted Siemens AG All rights reserved

8 3.8 Open-loop control Every operating condition of the excitation system is monitored and displayed. In addition to internal fault indication, the internal monitoring routine makes the following alarms available at the cabinet terminals: Fault with TRIP command Fault in automatic voltage regulator and switchover to manual mode Group alarm triggered by various internal fault signals Status signals are also made available for external indication: Excitation is on Excitation is off Automatic is on Manual is on Power factor / reactive power regulation is on Limiters are active Other detailed alarms status signals are possible as options on customer-specific design for modernization projects. 3.9 Power circuit In the power circuit, SINAMCS S120 or DIGUREG transistorized chopper regulators are used to make the necessary excitation power available via a DC link, i.e. the output stages of the transistorized chopper regulator derive their power from the DC link. The excitation voltage is influenced by the pulse/pause ratio and the excitation current is changed via the field resistor. The excitation current is measured in the output stage and converted for the field current regulator De-excitation When the synchronous generator is shut down or when the protection systems of the generator or unit transformer respond, the generator must be de-excited. The chopper regulator is disabled directly by the de-excitation command for this purpose. The magnetic energy of the field is fed back into the DC link via the integrated diodes in the chopper regulator. The de-excitation process can therefore be performed very quickly. The excitation switch also isolates the power circuit from the power supplies. U DC positive voltage Zero voltage negative voltage 0 t 1 -U DC T Figure 6: Block diagram of transistorized DC link converter Figure 7: Principle of operation of pulse-width modulation 8 Unrestricted Siemens AG All rights reserved

9 4. Basic modules The transistorized chopper (1), and in the case of redundant systems a second transistorized chopper (2), supplies the necessary excitation current for the exciter (5-7) or the generator field (8). Whereas the automatic voltage regulator (3) controls the generator terminal voltage (automatic channel), the excitation current regulator (4) controls the field current of the exciter (manual channel). Thanks to their compact design, these two modules have been integrated in a single device. The excitation power (E) can be supplied by the auxiliary power supply, a power plant battery, an auxiliary winding, a separate excitation transformer or via a pilot exciter. The optional redundant supplies of exciter power, e.g. from the power plant battery, ensure high availability of the excitation system. RG3 can be used for a wide variety of generator types, e.g. for brushless turbine generators with a three-phase exciter and rotating-rectifier diodes (5) and (7), for turbine generators with a direct-current exciter (6) and also for directly excited generators (8). The transistorized chopper regulator is supplied by means of a DC link. The integrated de-excitation resistor, which is connected in parallel to the DC link of the chopper regulator, is used for de-excitation of the generator. In the event of de-excitation, the field power of the exciter is fed back into the DC link of the chopper regulator. Figure 8: RG3 basic modules 4.1 Basic modules Both versions of the BES excitation system are installed in a standard cabinet specially designed for systems combining electronic closed- and open-loop control systems, and power electronics. Modular design and easy access to all components make for simple handling of all the important functions and optimization equipment. The dimensions of the standard cabinet are 800 mm wide, 2200 mm high and 600 mm deep. However, adaptations to a wide range of plant requirements, especially in the case of modernization projects, may necessitate deviations from these dimensions. 9 Unrestricted Siemens AG All rights reserved

10 SIMOTION D435-2 Open / closed loop control incl. communication to DCS Basic Line Module (BLM) Power supply module with DC-Link SINAMICS S120 Single Line Module (SLM) Power module De-excitation resistor Output choke to compensate the cable length NTG-3000 Actual value acquisition Power supply, output to field Figure 9: Main components in RG3-S cabinet - example 10 Unrestricted Siemens AG All rights reserved

11 4.2 Data exchange with DCS Data exchange to/from the excitation system is implemented via a PROFIBUS DP interface and at a standard baud rate of 12Mbit/s. On redundant excitation systems, the PROFIBUS DP interface is also redundantly implemented. The main control commands, feedback signals for operator control and monitoring of the excitation system, as well as fault messages and measured values of the generator and excitation variables are transmitted. Optionally, the signal interface can also be implemented with conventional hardwiring with coupling relays and optocouplers. 4.3 Local operator and monitoring (Option) An operator control and monitoring device SIMATIC TouchPanel can be installed in the door of the regulating and control cubicle for local operation, monitoring of operating states, measured values from the excitation system and for signaling faults and alarms. The main functions and features of this visualization unit are: Simultaneous display of operating and display values of both channels Simultaneous display of 6 analog values per channel Password protection Local operation of the excitation system Figure 10: Local operator panel (example) 11 Unrestricted Siemens AG All rights reserved

12 5. Software User-friendly software tools (SCOUT or Webserver for RG3-S and DIGUREG-Tool for RG3-DUR) are used for easy commissioning and maintenance of the excitation system. The converter and the power section can be parameterized fully with this software. For this, the voltage converter is connected to a PC via the ethernet, from where it is configured. Actual parameters can be monitored directly in the parameter list. A parameter can be changed simply by selecting it and entering a new value. Several predefined parameter lists for various applications (e.g. inputs/outputs) and an entire parameter list are available. It is also possible to compile user-defined parameter lists by entering parameter numbers. The current parameterization can also be stored on data media. This provides a simple method of documenting the actual state of the voltage regulator. The RG3-DUR DIGUREG-Tool can also be used as a local HMI (Human Machine Interface) installed either in the cabinet door or directly in the control room. RG3 features a TRACE memory. The TRACE is an important commissioning, diagnostic and trouble-shooting tool. Up to 8 analog values (measuring channels) of any type can be recorded with the TRACE function as with a storage oscilloscope. Alternatively, each measuring channel can be used to record 16 binary values. An easy-to-use trigger can be used to start recording. A pretrigger can be set to record events before and after the main trigger event. The recording level can be configured. The sampling time between two measuring points is 250µs. Figure11: Trace function for RG3-S Figure12: Trace function for RG3-DUR 12 Unrestricted Siemens AG All rights reserved

13 6. Areas of Application Figure 13: Applications of SPPA-E3000 SES excitation systems Example of a version in the lower power range Dual-channel open- and closed-loop control DIGUREG dual-channel voltage regulator Example for newly built power plant Figure 14: BES-DUR dual-channel excitation system with integrated redundant closed-loop controller Example of a version in the upper power range Dual-channel open- and closed-loop control with local control AC and DC power supply Example for modernization project Figure 15: RG3-S dual-channel excitation system with integrated redundant closed-loop controller 13 Unrestricted Siemens AG All rights reserved

14 7. Technical Data Auxiliary power supply from power plant battery: For signal and controller power supply (24 V DC power supply) Power consumption: < 0.2 kw continuous Accuracy of AVR: Transformers: 0,5% continuously Voltage converters: 3-phase connection to generator voltage Power consumption < 5 VA per phase Rated secondary voltage 100 V to 120 V Current transformer: 1 to 3-phase for measurement of generator current Rated secondary current 1 A or 5 A Power consumption < 3 VA (not including losses on incoming cables) The transformers are not included in the scope of supply of the voltage regulator. Standards: The BES excitation system complies with the applicable IEC, EN, DIN, VDE standards and IEEE-421. Models: according to IEEE AC7B (available in PSS/E version 31 or higher) 14 Unrestricted Siemens AG All rights reserved

15 8. Abbreviations BES DIN EN I E IEC IEEE I EN I EO IGBT I max I setpoint PMG PSS RG3 DUR RG3 S SES SPPA SPPA-E3000 U E VDE Brushless Excitation System (= Rotating Excitation System) Deutsches Institut für Normung e. V. (German Standards Institute) European standard Output current of chopper regulator corresponds to excitation current International Electrotechnical Commission Institute of Electrical and Electronics Engineers Output current for rated load Output current for no-load operation Insulated-Gate Bipolar Transistor Ceiling current Exciter setpoint Permanent magnet synchronous generator Power System Stabilizer BES with DIGUREG as power stage and as closed-loop control BES with SINAMICS S120 as power stage and SIMOTION D4x5-2 as open-loop control Static excitation systems Siemens Power Plant Automation Siemens Power Plant Automation Electrical Solutions Output voltage of chopper regulator corresponds to excitation voltage Verband der Elektrotechnik Elektronik Informationstechnik e.v. 15 Unrestricted Siemens AG All rights reserved

16 Published by and copyright 2014 Siemens AG Power and Gas Freyeslebenstrasse Erlangen, Germany For more information, please contact Siemens AG Fossil Power Generation Division Siemensallee Karlsruhe, Germany Siemens Energy, Inc Ridgeland Parkway, Suite 116 Alpharetta, GA 30004, USA sppa-e3000.energy@siemens.com E3071_DT31_BES_TechnDescription_e_V2-4 AL: N ECCN: N Unrestricted All rights reserved. Trademarks mentioned in this document are the property of Siemens AG, its affiliates, or their respective owners. Printed on elementary chlorine-free bleached paper. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract. 16 Unrestricted Siemens AG All rights reserved

Excitation Systems RG3 - T4. Transistorized Excitation Systems for Synchronous Generators. Power Generation

Excitation Systems RG3 - T4. Transistorized Excitation Systems for Synchronous Generators. Power Generation Excitation Systems RG3 - T4 Transistorized Excitation Systems for Synchronous Generators Power Generation Operating Characteristics Reliability High availability Digital control facilities Very good control

More information

Excitation Systems. Service Generators SIPOL. Transistorized Excitation Systems for Synchronous Generators. Power Generation

Excitation Systems. Service Generators SIPOL. Transistorized Excitation Systems for Synchronous Generators. Power Generation Excitation Systems Service Generators Transistorized Excitation Systems for Synchronous Generators Power Generation Operating Characteristics High availability Reliability Digital control facilities Very

More information

Instrumentation, Controls & Electrical / Technical Description / February 2016

Instrumentation, Controls & Electrical / Technical Description / February 2016 / Technical Description / February 2016 SPPA-E3000 Static Excitation Systems (SES) Static excitation systems for excitation and voltage regulation of synchronous machines Answers for energy. Table of contents

More information

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability

More information

Thyricon Excitation System

Thyricon Excitation System Thyricon Excitation System 1 1 2 3 2 Excitation System The Thyricon Excitation Family represents the extensive experience and knowledge of Voith Hydro as one of the major hydropower generator manufacturers.

More information

Excitation systems and automatic voltage regulators

Excitation systems and automatic voltage regulators ELEC0047 - Power system dynamics, control and stability Excitation systems and automatic voltage regulators Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 16 Overview

More information

EXCITATION SYSTEM MODELS OF GENERATORS OF BALTI AND EESTI POWER PLANTS

EXCITATION SYSTEM MODELS OF GENERATORS OF BALTI AND EESTI POWER PLANTS Oil Shale, 2007, Vol. 24, No. 2 Special ISSN 0208-189X pp. 285 295 2007 Estonian Academy Publishers EXCITATION SYSTEM MODELS OF GENERATORS OF BALTI AND EESTI POWER PLANTS R. ATTIKAS *, H.TAMMOJA Department

More information

New Redundant Automatic Voltage Regulator (AVR) Solution

New Redundant Automatic Voltage Regulator (AVR) Solution White Paper New Redundant Automatic Voltage Regulator (AVR) Solution Author: David R. Brown, Turbomachinery Control Solutions Senior Consultant, Invensys Operations Management What s Inside: 1. Introduction

More information

SPPA-E3000 Electrical Solutions Excitation and Startup Frequency Converter Systems

SPPA-E3000 Electrical Solutions Excitation and Startup Frequency Converter Systems SPPA-E3000 Electrical Solutions Excitation and Startup Frequency Converter Systems Plant Survey & Characteristics 2018 Instrumentation, Controls & Digitalization PERSONAL SAFETY PRECAUTIONS: NOTE: we follow

More information

Development of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine

Development of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine Development of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine T. Neumann, C. Feltes, I. Erlich University Duisburg-Essen Institute of Electrical Power Systems Bismarckstr. 81,

More information

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX SSE-N NEGATIVE FIELD FORCING SHUNT STATIC EXCITER/REGULATOR SYSTEM Control Chassis 6 SCR Power Chassis APPLICATION The SSE-N Negative Field Forcing Exciter/Regulator is used for both new and old installations

More information

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase

More information

Magnetization System of Magnetically Controlled Shunt Reactors

Magnetization System of Magnetically Controlled Shunt Reactors Magnetization System of Magnetically Controlled Shunt Reactors Leonid Kontorovych, Technical Director of ZTR PJSC, PH.D. in Engineering Sciences; Igor Shyrokov, head of the department of reactors control

More information

Three Phase Automatic Voltage Regulator Using Microcontroller

Three Phase Automatic Voltage Regulator Using Microcontroller Journal of Scientific Research and Advances 5 Three Phase Automatic Voltage Regulator Using Microcontroller Osman Billah Cite this article: J. Sci. Res. Adv. Vol., No., 5, 95-00. The AVR (automatic voltage

More information

Increasing security. Saving space. Gaining flexibility. Signal Conditioners for Industrial Automation

Increasing security. Saving space. Gaining flexibility. Signal Conditioners for Industrial Automation Increasing security. Saving space. Gaining flexibility. Signal Conditioners for Industrial Automation The SC-System: Interference-Free Signals, Maximum Performance The SC-System from Pepperl+Fuchs offers

More information

Type Ordering Code Package TDA Q67000-A5066 P-DIP-8-1

Type Ordering Code Package TDA Q67000-A5066 P-DIP-8-1 Control IC for Switched-Mode Power Supplies using MOS-Transistor TDA 4605-3 Bipolar IC Features Fold-back characteristics provides overload protection for external components Burst operation under secondary

More information

IRT Mini Evo. Technical Manual. quality IN MOTION. quality IN MOTION

IRT Mini Evo. Technical Manual. quality IN MOTION.   quality IN MOTION IRT quality IN MOTION www.irtsa.com 2000 Mini Evo Technical Manual IRT quality IN MOTION Contents 1. INTRODUCTION 3 2. DESCRIPTION 5 3. TECHNICAL DATA 7 3.1 GENERAL DATA FOR ALL TYPES 7 3.2 SPECIFIC DATA

More information

These drawings and single line diagrams provide an outlook of Basler Electric solutions for Excitation System installations and retrofit

These drawings and single line diagrams provide an outlook of Basler Electric solutions for Excitation System installations and retrofit BSLER ELECTRIC DECS EXCITTION SYSTEMS For Retrofitting solutions and New installations These drawings and single line diagrams provide an outlook of Basler Electric solutions for Excitation System installations

More information

Design, Implementation, and Dynamic Behavior of a Power Plant Model

Design, Implementation, and Dynamic Behavior of a Power Plant Model Design, Implementation, and Dynamic Behavior of a Power Plant Model M.M. A. Rahman, Member ASEE Grand Valley State University Grand Rapids, MI rahmana@gvsu.edu Daniel Mutuku Consumers Energy West Olive,

More information

SPECIFICATION, CONTROLS AND ACCESSORIES

SPECIFICATION, CONTROLS AND ACCESSORIES AS440 Automatic Voltage Regulator (AVR) SPECIFICATION, CONTROLS AND ACCESSORIES English Original Instructions A043Y697 (Issue 2) Table of Contents 1. DESCRIPTION... 1 2. SPECIFICATION... 3 3. CONTROLS...

More information

3TK28 Safety Relays. General data. 7/70 Siemens LV

3TK28 Safety Relays. General data. 7/70 Siemens LV 3TK28 Safety Relays General data Overview SIRIUS safety relays are the key elements of a consistent and cost-effective safety chain. Be it EMERGENCY-STOP disconnection, protective door monitoring or the

More information

Dynamic Performance of an Excitation System Built in a Digital Way

Dynamic Performance of an Excitation System Built in a Digital Way Dynamic Performance of an Excitation System Built in a Digital Way M.L. Orozco, H. Vásquez 1 Universidad del Valle, Escuela de Ingeniería Eléctrica y Electrónica, Cali, Colombia, email : maloroz@hotmail.com

More information

VF-nC1 Adjustable Speed Drive Engineering Specification

VF-nC1 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba VF-nC1 AC Variable Frequency Drives, 6 pulse for 100V single-phase 0.1 to 0.75kW, 200V single-phase 0.2 to 2.2kW and 200V threephase 0.1

More information

2.4 Modeling on reactive power or voltage control. Saadat s Chapters Kundur s Chapters 5.4, 8 and 11.2 EPRI Tutorial s Chapter 5

2.4 Modeling on reactive power or voltage control. Saadat s Chapters Kundur s Chapters 5.4, 8 and 11.2 EPRI Tutorial s Chapter 5 2.4 Modeling on reactive power or voltage control Saadat s Chapters 12.6 12.7 Kundur s Chapters 5.4, 8 and 11.2 EPRI Tutorial s Chapter 5 1 Objectives of Reactive Power and Voltage Control Equipment security:

More information

FEATURES. Custom-designed DIGITAL EXCITATION CONTROL SYSTEMS For synchronous generators. Digital Excitation Control Systems

FEATURES. Custom-designed DIGITAL EXCITATION CONTROL SYSTEMS For synchronous generators. Digital Excitation Control Systems Custom-designed DIGITAL EXCITATION CONTROL SYSTEMS For synchronous generators Basler Electric engineers excitation systems to meet the specific needs of your power plant! More than 60 years of experience

More information

ELECTRONIC CONTROL OF A.C. MOTORS

ELECTRONIC CONTROL OF A.C. MOTORS CONTENTS C H A P T E R46 Learning Objectives es Classes of Electronic AC Drives Variable Frequency Speed Control of a SCIM Variable Voltage Speed Control of a SCIM Chopper Speed Control of a WRIM Electronic

More information

Scope of functions 32R

Scope of functions 32R Scope of functions 21 32 32R 46 64 78 Fig. 1 7UM516 generator protection Application The 7UM516 is a numerical generator protection relay and is mainly used with larger generation units. In most cases

More information

Overcurrent Protection / 7SJ45

Overcurrent Protection / 7SJ45 Overcurrent Protection / SJ SIPROTEC easy SJ numerical overcurrent protection relay powered by CTs Fig. / Description SIPROTEC easy SJ numerical overcurrent protection relay powered by current transformers

More information

Page ENSC387 - Introduction to Electro-Mechanical Sensors and Actuators: Simon Fraser University Engineering Science

Page ENSC387 - Introduction to Electro-Mechanical Sensors and Actuators: Simon Fraser University Engineering Science Motor Driver and Feedback Control: The feedback control system of a dc motor typically consists of a microcontroller, which provides drive commands (rotation and direction) to the driver. The driver is

More information

TOSHIBA International Corp

TOSHIBA International Corp TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification

More information

Static Frequency Converter TMP-TS250. Series

Static Frequency Converter TMP-TS250. Series Static Frequency Converter TMP-TS250 Series Preface SFC is a load commutated inverter LCI, which drives a gas turbine generator like a synchronous motor, and accelerates up to the gas turbine s self-sustaining

More information

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD)

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD) Drives 101 Lesson 3 Parts of a Variable Frequency Drive (VFD) This lesson covers the parts that make up the Variable Frequency Drive (VFD) and describes the basic operation of each part. Here is the basics

More information

Totally Integrated Power SIVACON 8PS LDM busbar trunking system siemens.com/ldm-system

Totally Integrated Power SIVACON 8PS LDM busbar trunking system siemens.com/ldm-system Safe and efficient power transmission in wind turbines Totally Integrated Power SIVACON 8PS LDM busbar trunking system siemens.com/ldm-system Contents Totally Integrated Power 2 SIVACON 8PS busbar trunking

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

Static Frequency Converter TMP-TS370. Series

Static Frequency Converter TMP-TS370. Series Static Frequency Converter TMP-TS370 Series Preface SFC is a load commutated inverter (LCI), which drives a gas turbine generator like a synchronous motor, and accelerates up to the gas turbine s self-sustaining

More information

SIPROTEC. Multi-Functional Generator Protection Relay 7UM61. Preface. Contents. Introduction 1. Functions 2. Mounting and Commissioning 3

SIPROTEC. Multi-Functional Generator Protection Relay 7UM61. Preface. Contents. Introduction 1. Functions 2. Mounting and Commissioning 3 Preface SIPROTEC Multi-Functional Generator Protection Relay 7UM61 V4.1 Manual Contents Introduction 1 Functions 2 Mounting and Commissioning 3 Technical Data 4 Appendix Literature Glossary A Index C53000-G1176-C127-4

More information

Speed and Key Monitor Specifications

Speed and Key Monitor Specifications Speed and Key Monitor Specifications The Speed and Key Monitor is designed for high reliability for the plant s most critical rotating machinery monitoring speed, phase, zero speed and direction of rotation.

More information

TDE MACNO Spa. AC&DC Drives, Servos and Drive System. AFE converters for Renewable Energies Regenerative (active) power supply (Active Front End)

TDE MACNO Spa. AC&DC Drives, Servos and Drive System. AFE converters for Renewable Energies Regenerative (active) power supply (Active Front End) TDE MACNO Spa AC&DC Drives, Servos and Drive System AFE converters for Renewable Energies Regenerative (active) power supply (Active Front End) Automation and Control Systems OPENDRIVE EXP MINI OPENDRIVE

More information

IRT AT-Small. Technical Manual. quality IN MOTION. quality IN MOTION

IRT AT-Small. Technical Manual. quality IN MOTION.   quality IN MOTION IRT quality IN MOTION www.irtsa.com 2000 AT-Small Technical Manual IRT quality IN MOTION E2 0 8 4 1 5 September 2013-Rev. 4 UL Requirements Drives Series 2000 / 4000 AT 1. Field wiring terminal to use

More information

WDG 13 - Technical Data Sheet

WDG 13 - Technical Data Sheet LV 804 T WDG 13 - Technical Data Sheet FRAME LV 804 T SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

Modern Hardware Technology in Inverters and Servo Systems

Modern Hardware Technology in Inverters and Servo Systems Modern Hardware Technology in Inverters and Servo Systems Yoshihiro Matsumoto Seiji Shinoda 1. Introduction With the popularization of variable speed drive systems for electric motors, including general-purpose

More information

100 h; (min. 70 h at 40 C); 200 days (typ.) with optional battery module Memory Number of memory modules (optional)

100 h; (min. 70 h at 40 C); 200 days (typ.) with optional battery module Memory Number of memory modules (optional) CPUs CPU 226 6ES7 216-2AD23-0XB0 Supply voltages Rated value 24 V DC Yes Permitted range, lower limit 20.4 V permissible range, upper limit 28.8 V 120 V AC Yes 230 V AC Yes permissible range, lower limit

More information

Universal Controller

Universal Controller 7 863 Universal Controller POLYGYR RWF32... ISO 9001 RWF32... with casing ARG61.01 The RWF32... is a universal digital boiler temperature / pressure controller designed for use in oil- and / or gas-fired

More information

12/2 Product overview. 12/3 7KT1 14, 7KT1 53 E-counters. 12/9 7KT1 11, 7KT1 12 digital measuring devices. 12/11 7KT1 0 analog measuring devices

12/2 Product overview. 12/3 7KT1 14, 7KT1 53 E-counters. 12/9 7KT1 11, 7KT1 12 digital measuring devices. 12/11 7KT1 0 analog measuring devices BETA Measuring /2 Product overview /3 7KT1 14, 7KT1 53 E-counters /9 7KT1 11, 7KT1 digital measuring devices /11 7KT1 0 analog measuring devices / 7KT5 8 time and pulse counters /14 7KT5 5, 7KT5 6 time

More information

S11 Adjustable Speed Drive Engineering Specification

S11 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba S11 AC Variable Frequency Drives, 6 pulse for 3- phase 200-240VAC, 380-500VAC and single phase 200V to 240VAC. 1.1 References A. National

More information

LV Compensation & Filtering Products

LV Compensation & Filtering Products GE Grid Solutions LV Compensation & Filtering Products Providing Power Quality and Energy Efficiency Low (LV) reactive power compensation and harmonic filtering solutions help customers to improve the

More information

WDG 83 - Technical Data Sheet

WDG 83 - Technical Data Sheet HV 804 R WDG 83 - Technical Data Sheet FRAME HV 804 R SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international

More information

ECS2100 Excitation Control Systems

ECS2100 Excitation Control Systems ECS2100 Excitation Control Systems APPLICATION Basler Electric has expanded its excitation product offering with the addition of the ECS2100 excitation control system. The ECS2100 is a multi-microprocessor

More information

Arbitrary power supplies. 160 W to 5200 W

Arbitrary power supplies. 160 W to 5200 W Arbitrary power supplies 160 W to 5200 W TOE 8815 Arbitrary power supplies for generation of any voltage and current characteristics with an output power from 160 W to 5200 W. With exceptionally versatile

More information

Inverter MICROMASTER 410

Inverter MICROMASTER 410 Inverter MICROMASTER 40 /2 Description /4 Circuit diagrams /6 Technical data /7 Selection and ordering data /8 Options /0 Dimension drawings Siemens DA 5.2 2005/2006 / MICROMASTER 40 Description Inverter

More information

DeltaV SIS Logic Solver

DeltaV SIS Logic Solver DeltaV SIS Process Safety System Product Data Sheet September 2017 DeltaV SIS Logic Solver World s first smart SIS Logic Solver Integrated, yet separate from the control system Easy compliance with IEC

More information

Simulation of Advanced ELC with Synchronous Generator for Micro Hydropower

Simulation of Advanced ELC with Synchronous Generator for Micro Hydropower Simulation of Advanced ELC with Synchronous Generator for Micro Hydropower Station ANKITA GUPTA 1 Alternate Hydro Energy Centre Indian Institute of Technology, Roorkee, India Email: ankita.iitr.6@gmail.com

More information

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections

More information

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 5th October 2010 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT

More information

VARIABLE FREQUENCY RESONANT TEST SYSTEM

VARIABLE FREQUENCY RESONANT TEST SYSTEM VARIABLE FREQUENCY RESONANT TEST SYSTEM 400kV,1200kVA Tank Type Reactor for Outdoor Cable Test Field 650kV, 5850kVA, Cylinder Type Reactors for Onsite Testing of GIS and Cable PHENIX Variable Frequency

More information

A Subsidiary of Regal-Beloit Corporation. AC Inverter Terminology

A Subsidiary of Regal-Beloit Corporation. AC Inverter Terminology AP200-9/01 Acceleration The rate of change in velocity as a function of time. Acceleration usually refers to increasing velocity and deceleration to decreasing velocity. Acceleration Boost During acceleration,

More information

Electronic Air / Fuel Ratio Control System

Electronic Air / Fuel Ratio Control System 7 871 ISO 9001 Electronic Air / Fuel Ratio Control System RVW20... Electronic control unit - for use with modulating single- and dual-fuel burners - with extended functionality for mechanical air / fuel

More information

T 1000 PLUS Secondary Injection Relay Test Set

T 1000 PLUS Secondary Injection Relay Test Set Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator Test results and settings are saved into local memory

More information

ESR. The Dynamic Solution. Applications. Products, Consultation, and Service. ESR Pollmeier GmbH

ESR. The Dynamic Solution. Applications. Products, Consultation, and Service. ESR Pollmeier GmbH Analog AC servo drive systems with sinusoidal commutation Servo drives in compact design, 230 V AC mains connection Servo motors with high power density up to 5.0 Nm / 1.1 kw Components of the TrioDrive

More information

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator High power outputs Large graphical display Compact

More information

Solid-State Upgrade for the COBRA JUDY S-Band Phased Array Radar

Solid-State Upgrade for the COBRA JUDY S-Band Phased Array Radar Solid-State Upgrade for the COBRA JUDY S-Band Phased Array Radar M. Gaudreau, J. Casey, P. Brown, T. Hawkey, J. Mulvaney, M. Kempkes Diversified Technologies, Inc. 35 Wiggins Avenue, Bedford, MA USA Abstract

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements Section 502.8 SCADA Technical and Operating Applicability 1 Section 502.8 applies to: (a) the legal owner of a generating unit: (i) connected to the transmission facilities in the balancing authority area

More information

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New) XR1 Rotor Earth Fault Relay (May 2007) Manual XR1 (Revision New) Woodward Manual XR1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

SPECIFICATION, CONTROLS AND ACCESSORIES

SPECIFICATION, CONTROLS AND ACCESSORIES MX341 Automatic Voltage Regulator (AVR) SPECIFICATION, CONTROLS AND ACCESSORIES English Original Instructions A043Y699 (Issue 2) Table of Contents 1. DESCRIPTION... 1 2. SPECIFICATION... 3 3. CONTROLS...

More information

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Overcurrent Protection / 7SJ46 SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Function overview Fig. /11 Description The SIPROTEC easy 7SJ46 is a numerical overcurrent protection relay which

More information

QUINT-PS/ 3AC/24DC/10

QUINT-PS/ 3AC/24DC/10 Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system

More information

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet LV 804 T WDG 12 - Technical Data Sheet FRAME LV 804 T SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

Job Sheet 2 Servo Control

Job Sheet 2 Servo Control Job Sheet 2 Servo Control Electrical actuators are replacing hydraulic actuators in many industrial applications. Electric servomotors and linear actuators can perform many of the same physical displacement

More information

Safe and efficient power transmission in wind turbines

Safe and efficient power transmission in wind turbines Totally Integrated Power SIVACON 8PS Safe and efficient power transmission in wind turbines LDM busbar trunking system www.siemens.com/busbar Contents Totally Integrated Power 2 SIVACON 8PS busbar trunking

More information

Extraction of Extreme Power and Standardize of Voltage and Frequency under Varying Wind Conditions

Extraction of Extreme Power and Standardize of Voltage and Frequency under Varying Wind Conditions Extraction of Extreme Power and Standardize of Voltage and Frequency under Varying Wind Conditions V. Karthikeyan 1 1 Department of ECE, SVSCE, Coimbatore, Tamilnadu, India, Karthick77keyan@gmail.com `

More information

WDG 71 - Technical Data Sheet

WDG 71 - Technical Data Sheet HV 804 R WDG 71 - Technical Data Sheet FRAME HV 804 R SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

WDG 61 - Technical Data Sheet

WDG 61 - Technical Data Sheet HV 804 W WDG 61 - Technical Data Sheet FRAME HV 804 W SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international

More information

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet LV 804 S WDG 12 - Technical Data Sheet FRAME LV 804 S SPECIFICATIONS & OPTIONS STANDARDS Cummins Generator Technologies industrial generators meet the requirements of BS EN 60034 and the relevant sections

More information

CPU 221, CPU 222, CPU 224, CPU 224 XP, CPU 224 XPsi, CPU 226

CPU 221, CPU 222, CPU 224, CPU 224 XP, CPU 224 XPsi, CPU 226 Siemens AG 2008 SIMATIC S7-200 Overview CPU 226 The high-performance package for complex technical tasks With additional PPI port for added flexibility and communication options With 40 inputs/outputs

More information

Generator Speed Controller Model GSC 1

Generator Speed Controller Model GSC 1 enerator Speed Controller odel SC 1 RA 29 977/09.95 Replaces: 4.92 Self contained controller for driving electrical power generators with a hydrostatic transmission 16 Bit microprocessor based controller

More information

Wind Power Facility Technical Requirements CHANGE HISTORY

Wind Power Facility Technical Requirements CHANGE HISTORY CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical

More information

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13 Index A A Group functions 3 9 AC reactors 5 3 Acceleration 1 15, 3 8 characteristic curves 3 26 second function 3 24 two-stage 4 19 Acceleration stop function 3 21 Access levels 3 5, 3 36, 4 25 Access

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Courseware Sample F0

Courseware Sample F0 Electric Power / Controls Courseware Sample 85822-F0 A ELECTRIC POWER / CONTROLS COURSEWARE SAMPLE by the Staff of Lab-Volt Ltd. Copyright 2009 Lab-Volt Ltd. All rights reserved. No part of this publication

More information

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY LIST OF TOPICS 1 Electric Circuit Principles 2 Electronic Circuit Principles 3 Generation 4 Distribution 5 Utilisation The expected learning outcome is

More information

FUJI Inverter. Standard Specifications

FUJI Inverter. Standard Specifications FUJI Inverter o Standard Specifications Norminal applied motor The rated output of a general-purpose motor, stated in kw. That is used as a standard motor. Rated capacity The rating of an output capacity,

More information

Training Fees 4,000 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch.

Training Fees 4,000 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch. Training Title POWER SYSTEM GENERATION & DISTRIBUTION Training Duration 5 days Training Venue and Dates Power System Generation & Distribution 5 08-12 December, 2019 $4,000 Dubai, UAE Trainings will be

More information

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet LV 804 R WDG 12 - Technical Data Sheet FRAME LV 804 R SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international

More information

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet LV 804 W WDG 12 - Technical Data Sheet FRAME LV 804 W SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international

More information

Product Overview. Rotary Encoders for the Elevator Industry

Product Overview. Rotary Encoders for the Elevator Industry Product Overview Rotary Encoders for the Elevator Industry 05/2018 Rotary encoders for the elevator industry The demands on elevator technology have been growing steadily over these last several years:

More information

Data sheet VIPA CPU 314SC DPM (314-6CG23)

Data sheet VIPA CPU 314SC DPM (314-6CG23) Data sheet VIPA CPU 314SC DPM (314-6CG23) Technical data Order no. Type 314-6CG23 VIPA CPU 314SC DPM General information Note - Features Powered by SPEED7 Work memory [KB]: 512...2.048 Onboard 24x DI /

More information

Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis

Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis By ALL-TEST Pro, LLC & EMA Inc. Industry s use of Motor Drives for AC motors continues to grow and the Pulse-Width

More information

POLYMOBIL III. Function description X038I. Wiring index E from Serial no. 3000

POLYMOBIL III. Function description X038I. Wiring index E from Serial no. 3000 POLYMOBIL III SP Function description X038I Wiring index E from Serial no. 3000 English Print No.: RXB8-115.041.02.03.02 Doc. Gen. Date: 10.97 Replaces: RXB8-115.041.02.02.02 Siemens AG 1995 The reproduction,

More information

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator Test results and settings are saved into local memory

More information

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications: SGMF(T) series Onsite Mobile AC High Voltage Test System On-site AC high voltage test systems are used for voltage withstanding test, partial discharge measurement, tan delta measurement on those instrument

More information

Low Voltage Alternators

Low Voltage Alternators Low Voltage Alternators Excitation and regulation systems SHUNT - PMG - AREP Low Volta SHUNT excitation for basic applications - The AVR power supply voltage is shunted on the alternator output terminals.

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES

More information

r 450 Installation and maintenance This manual is to be given to the end user R 450 VOLT. STAB. I EXC STAT. AREP PMG FUSIBLES / FUSES

r 450 Installation and maintenance This manual is to be given to the end user R 450 VOLT. STAB. I EXC STAT. AREP PMG FUSIBLES / FUSES 8 7 9 6 5 4 C 45 en -. / a R 45 DETECT. PH PH. SENSING 5 Hz EXT FREQ 6 Hz SETTING This manual is to be given to the end user VOLT. STAB. I EXC FUSIBLES / FUSES EXT.FREQ. SET. ON ONLY FOR SPECIAL CONFIG.

More information

RAPID CONTROL PROTOTYPING FOR ELECTRIC DRIVES

RAPID CONTROL PROTOTYPING FOR ELECTRIC DRIVES RAPID CONTROL PROTOTYPING FOR ELECTRIC DRIVES Lukáš Pohl Doctoral Degree Programme (2), FEEC BUT E-mail: xpohll01@stud.feec.vutbr.cz Supervised by: Petr Blaha E-mail: blahap@feec.vutbr.cz Abstract: This

More information

ESR. The Dynamic Solution. Main Characteristics. Applications. ESR Pollmeier GmbH

ESR. The Dynamic Solution. Main Characteristics. Applications. ESR Pollmeier GmbH Modular Multi-Axis Servo System for Any Type of Servo Motors Servo Power Modules for Direct Mains Connection Motion Control Modules for Coordinated Axis Motion MidiDrive C (3 400/480 V AC) Servo Power

More information

Product Information ECN 424 S EQN 436 S. Absolute Rotary Encoders with DRIVE-CLiQ Interface for Safety-Related Applications.

Product Information ECN 424 S EQN 436 S. Absolute Rotary Encoders with DRIVE-CLiQ Interface for Safety-Related Applications. Product Information ECN 424 S EQN 436 S Absolute Rotary Encoders with DRIVE-CLiQ Interface for Safety-Related Applications Firmware 53 12/2017 ECN 424 S, EQN 436 S Rotary encoders for absolute position

More information

CHAPTER 2 CURRENT SOURCE INVERTER FOR IM CONTROL

CHAPTER 2 CURRENT SOURCE INVERTER FOR IM CONTROL 9 CHAPTER 2 CURRENT SOURCE INVERTER FOR IM CONTROL 2.1 INTRODUCTION AC drives are mainly classified into direct and indirect converter drives. In direct converters (cycloconverters), the AC power is fed

More information

INTER PLANT STANDARD STEEL INDUSTRY VARIABLE VOLTAGE VARIABLE FREQUENCY SYSTEM (V.V.V.F.) V/F, VECTOR CONTROL / TORQUE CONTROL

INTER PLANT STANDARD STEEL INDUSTRY VARIABLE VOLTAGE VARIABLE FREQUENCY SYSTEM (V.V.V.F.) V/F, VECTOR CONTROL / TORQUE CONTROL INTER PLANT STANDARD STEEL INDUSTRY VARIABLE VOLTAGE VARIABLE FREQUENCY SYSTEM (V.V.V.F.) V/F, VECTOR CONTROL / TORQUE CONTROL IPSS: 1-10-035-06 IPSS Corresponding IS does not exist 0. FOREWORD 0.1 This

More information