1 Scope of functions R Fig. 1 7UM516 generator protection Application The 7UM516 is a numerical generator protection relay and is mainly used with larger generation units. In most cases it is combined with other devices of the 7UM51 and 7UT51 series, where several functions can be implemented as redundant protection. Construction The unit incorporates in its compact construction all components for Acquisition and evaluation of measured values Operator panel with display Event/alarm and command outputs inputs Serial interfaces Auxiliary DC/DC converters. Three housing variants are available. The model for panel flush mounting or cubicle mounting has rear connection terminals. The model for panel surface mounting has 100 screw terminals accessible from the front. A third variant for flush or cubicle mounting without glass cover is available. Functions The following protection functions are integrated: ANSI No.: Impedance protection 21 Out of step protection 78 Reverse power protection 32R Forward power monitor 32 Unbalanced load protection 46 Earth fault protection V 0 > 64 Direct coupling (for separate protection units). Measurement method The influence of harmonics, higher frequency transients, DC transient components and current transformer saturation effects are extensively suppressed. This is achieved using a high performance microprocessor and continuous digital signal processing (measured value acquisition, measured value conditioning and measured value processing). High measurement accuracy is achieved by the use of physical models for process imaging. The correct measurement is ensured by filter adaptation even with deviations from rated frequency (f N 10 Hz). Serial interfaces The unit is equipped with 2 serial interfaces. The front serial interface is suitable for connecting an AT compatible PC. The PC based program DIGSI can be used for convenient and transparent setting, disturbance recording and evaluation as well as commissioning (optional). The rear system interface is available alternatively as an isolated V.24(RS232) interface or as a fibre optic interface for connecting to the SINAUT LSA station control or to a protection data master unit (protocol to DIN ). Setting All setting parameters can be input either via the integrated operator and display panel or a personal computer. The parameters are written into non volatile memory so that the setting values remain secure even during interruption of the supply voltage. Self monitoring All important hardware and software components are continuously monitored, irregularities in hardware and program sequence are detected and alarmed. This significantly improves the security and availability of the protection system. Siemens LSA April 1995 Siemens AG

2 Im Z X t 2 X 1B Z TRIP Characteristic 2 t 1b t 1 X 1 Z Make Z pos t T WARN Unbalanced load Warning stage 2 > Z TRIP R 1 R 1B R P Z Make Re Z T>> TRIP Thermal instigation stage Unbalanced load Instigation stage 2 >> Thermal warning stage 2adm. 2 >> 2 Characteristic 1 Fig. 2 Characteristic of the impedance protection (R 1 0,4 X Tr, X 1 0,7 X Tr ; characteristics X 1B and R 1B are activated via binary input) Impedance protection This protection function operates as short circuit protection and simultaneously takes over reserve protection functions for the main protection or upstream series connected protection equipment (e.g. generator protection, transformer differential protection and network protection). Fault detection is implemented with an overcurrent pick up (with undervoltage seal in) and initiates computation of the loop impedance. Depending on the vector position in the rectangular tripping characteristic, the time to operate is allocated (Fig. 2). The first zone time t 1 should be set undelayed and the grading time t 2 in accordance with the higher order protection. The first zone trip is blocked automatically if tripping of the voltage transformer mcb is detected via binary input, or a power swing is detected by a further integrated algorithm. As a function of the particular switching state of the system, it is desirable to extend the first zone reach or to re route trip signals. An additional impedance stage R 1B, X 1B or an additional logic tripping function can be activated via the binary inputs. Fig. 3 Characteristic of the out of step tripping Out of step protection Depending on the network configuration state and the infeed generators, power swings can occur after disconnection of short circuits. If the centre of the power swing falls within the unit this may lead to inadmissible loading of the generator and requires disconnection from the network. On the other hand network side power swings are less critical. The generator related protection is based on the proven impedance measurement principle and evaluation of the progress of the complex impedance vector. Fig. 3 shows the power swing characteristics. Depending on characteristics, a number of swings are permitted. Exceeding thereof causes a trip signal. Using the tilt of the characteristics it is possible to achieve optimum adaptation to the particular system conditions. For purposes of external evaluation each swing through the power swing characteristic is signalled. Activation of the protection function is performed using the positive sequence components of the current. At the same time no negative sequence components must exist. Fig. 4 Instigation range of unbalanced load protection Unbalanced load protection This protection function detects unsymmetrical loading of three phase machines. It operates on the principle of component splitting and evaluates only the negative phase sequence component of the current. In the evaluation circuit a sensitive alarm stage 2 > and a course stage 2 are provided. In addition the negative sequence component of the current is fed into a thermal replica where the corresponding heating of the rotor surface of a generator is simulated (Fig. 4). For indication (alarm) purposes an indication (alarm) relay can also be parameterized to operate before the tripping limit of the thermal replica is reached. 2 Siemens LSA April 1995

3 Reverse power protection If the driving energy of a generator fails, the generator continues on the network as a motor and covers its friction losses in the form of power withdrawal from the network. This is undesirable from the network and turbine viewpoint, and should be terminated after a short period by opening the generator circuit breaker. Calculation of the effective power is performed using the positive sequence component vectors of current and voltage, so that asymmetric network conditions do not lead to measurement errors. In addition it is possible to compensate angle errors of the current and voltage instrument transformer by using a correction angle. Optimized algorithms ensure high sensitivity. The state of the emergency trip valve can be fed to the relay to control switching between two delay times (long time short time). Earth fault protection The main application is for the acquisition of earth faults in the stator and on the generator terminals. With a high ohmic or ungrounded generator in unit connection the displacement voltage is evaluated. By digital filtering of the input value, only the fundamental component is evaluated. Any harmonics (e.g. third harmonic) are effectively suppressed. Appropriate dimensioning of the load resistor protects 90% of the stator winding (Fig. 5). External signals This enables the processing of signals and commands from the Buchholz and other relays, which are fed to binary inputs. External signals (up to 4) can be separately time delayed and marshalled like a protection function. The advantages are in the trip signal processing and the precise timed event logging. On load measurement The on load measured values generated in the unit such as current, voltage, frequency, active and reactive power, power factor, phase angle, resistance and reactance as well as negative sequence current can be displayed at the LC display or by means of a PC. Fault event data In a protection unit, depending on the parameterization, either the instantaneous values (input values) or rms values (calculated values every 10 ms) are used. The maximum period of a disturbance recording depends on the memory and system frequency. Within the buffer several disturbance records (up to 8) can be stored consecutively. The number is dependent on the parameterization and nature of the fault event data record. The possibility to set a pre and post trigger time and the triggering event (disturbance recording start with activation or trip) permits flexible adaptation to the differing requirements. The disturbance record data can either be transferred to the SINAUT LSA station control or to a PC, and evaluated there depending on the user preference. Trip matrix/trip circuits The unit is equipped with five trip/command relays. The described protection functions can be arbitrarily allocated to these relays. In addition, each protection function can be set to OFF or ON via the operator panel. A third BLOCKED position permits commissioning of the unit with the local indications and the indication (alarm) relay circuits, but without tripping of the circuit breakers. With the many parameterizing possibilities provided, testing of and alternations to the circuit breaker operation can be performed during commissioning, as well as during normal operation without the need for rewiring. Non volatile storage of operational records The unit supplies detailed data for the analysis of disturbances as well as for checking of states during operation. All subsequently listed indication memories are safeguarded against supply voltage failure. Real time clock A standardized, battery buffered clock is provided, it is synchronized via binary input or the system interface. All events are recorded with a date and time tag. Disturbance event indications The indications of the last 3 disturbances are always accessible. Operation indications All indications which do not directly belong to a disturbance, are stored in the operation indication buffer. Assignable indication (alarm) relays, LEDs and binary inputs For user specific output and display of indications, indication (alarm) relays and LEDs can be freely assigned. The storable LED displays are secured against supply voltage failure. All binary inputs are similarly freely assignable. It is thus possible to assign a binary input to several logical inputs. Siemens LSA April

4 Technical data Input circuits Voltage supply via integrated DC/DC converter Setting ranges Impedance protection Out of step protection Rated current N Rated voltage V N, can be parameterized Rated frequency f N, can be parameterized Thermal overload capability in voltage path, continuous in current path, continuous 1s 10 s Power consumption in voltage path in current path Rated auxiliary voltage V aux at V N = 100 V at N = 1 A at N = 5 A Permissible tolerance at rated auxiliary voltage Power consumption Starting: Current > Reset ratio Undervoltage seal in V < Seal in time t Measurement: Resistance (R 1, R 1B ) Reactance (X 1, X 1B ) Times: Delay times t 1, t 1B Reset delay t r Minimum response time Starting: Positive sequence current 1 > Negative sequence current 2 > Power swing polygon Impedances Z a to Z d Angle of inclination P Number of admissible swings Characteristic 1 N1 Characteristic 2 N2 Times: Start holding time t H Holding time of out of step indication t M Reset delay t r 1 or 5 A 100 to 125 V AC 50/60 Hz 140 V AC 4 x N 100 x N 20 x N < 0.3 VA < 0.1 VA < 0.5 VA 24, 48 V DC or 60, 110, 125 V DC or 220, 250 V DC 20 to +15 % max. 16 W 0.2 to 4 x / N to 110 V 0.05 to 65 Ω 0.05 to 130 Ω approx. 80 ms 0.2 to 4 x / N 0.05 to 1 x / N 0.05 to 130 Ω 60 to 90 1 to 4 1 to to 32 s 0.02 to 0.15 s 0.05 to 32 s Unbalance load protection Warning stage 2 > Max. continuous admissible unbalanced load t 1 Tripping stage 2 Tripping time t 2, reset delay time t r Reset ratio Minimum response time Thermal replica Time constant Warning stage Reverse power protection Reverse power P > Delay times t 1, t 2 (without/with emergency tripping) Reset delay t r Reset ratio Minimum response time Earth fault protection Displacement voltage V E > Delay time t, reset delay time t r Reset ratio V E or E Minimum response time 3 to 30 % of 2 / N 10 to 80 % of 2 / N ms 100 to 2500 s max. 70 to 99 % of tripping stage 0.5 to 30 % of S N approx ms 5 to 120 V AC 0.7 or ms Pick up tolerances under rated conditions Current values Voltage values Impedance values Active power values Time values 3 % of setting value 3 % of setting value 3 % of setting value 5 % of setting value or 0.2 % off S N 10 ms 4 Siemens LSA April 1995

5 Technical data (continued) On load measurement Fault recording Contacts Displays, inputs Construction Display of values for current for voltage for frequency for active power for reactive power for load angle for load angle for resistance for reactance for inverse current Instantaneous values (approx. every 1.67 ms at 50 Hz) RMS values (approx. every 10 ms at 50 Hz) Potential free trip/command contacts Switching capacity make break Permissible current continuous 0.5 s Switching voltage Indication contacts Switching capacity make/break Permissible current Switching voltage LED displays on unit front inputs for 24 to 250 V DC operating voltage Current consumption independent of voltage range For panel surface mounting Weight approx. For panel flush mounting/cubicle mounting Weight approx. Protection class to EN L1, L2, L3, pos V L1, V L2, V L3, 3V 0, V pos Freq. P/S N Q/S N p.f. PHI R X 2, 2th. L1, L2, L3, v L1, v L2, v L3, 3v 0 pos, V pos, PHI, 2, R, X, P/S N, Q/S N 3 x 2 NO, 2 x 1 NO (total 5 trip relays) 1000 W/VA 30 W/VA 5 A 30 A 250 A DC 13 (see Fig. 5) 20 W/VA 1 A 250 V DC 16 8 approx. 2.5 ma in housing 7XP kg in housing 7XP kg IP 51 Standards DIN VDE 0435, part 303 and IEC or IEC Insulation tests Disturbance tests Degree of radio interference High voltage test Impulse voltage test High frequency test (1 MHz test) IEC , class III Electrostatic discharges (ESD test) IEC , class III Electromagnetic fields (Radiated electr. magn. field test) IEC (report), class III High speed, transient disturbances (Fast transient test) IEC 41B (CO) 53 (draft), class III DIN VDE 0871, limit value class B 2 kv (rms), 50 Hz; 1 min or alternatively 2.8 kv DC; 1 min 5 kv (peak); 1.2/50 s; 0.5 J; 3 positive and 3 negative shots at intervals of 5s 2.5 kv (peak); 1 MHz; = 15 s; 400 shots per s; duration 2 s 8 kv (peak); 5/30 ns; 10 positive discharges Frequency 27 MHz to 500 MHz; 10 V/m 2 kv (peak); 5/50 ns; 5 khz; 4 mj per pulse; 1 min per polarity Climatic conditions Permissible ambient temperature during service during storage during transport Humidity class 5 to +55 C 25 to +55 C 25 to +70 C Annual average 75% relative humidity; on 30 days/year up to 95% relative humidity; condensation not permissible Mechanical stress DIN Permissible mechanical stress during service during transport 10 to 60 Hz: mm amplitude 60 to 500 Hz: 0.5 g acceleration 5 to 8 Hz: 7.5 mm amplitude 8 to 500 Hz: 2 acceleration Siemens LSA April

6 Selection and ordering data Order No. 7UM516 generator protection relay 7UM516 A A 0 Rated current at 50 to 60 Hz, 100 to 125 V AC 1 A 5 A Rated auxiliary voltage 24, 48 V DC 60, 110, 125 V DC 220, 250 V DC Mechanical design for panel flush mounting or cubicle mounting for surface mounting for panel flush mounting or cubicle mounting, without glass cover Serial interface decoupled, wire connected (V24) integrated fibre optic connection C D E B C 6 Siemens LSA April 1995

7 Excitation system Unit transformer L1 L2 L3 G n I N I L1 I L2 I L3 e R L V L1 V L2 V L3 V N 3 V 0 I L1 I L2 I L3 LED Reset I N Reset thermal image I 2 Block I Pr I > Emergency trip valve contact Voltage transformer mcb Activation overreach stage Z 1Ü External signal 1 L External signal 2 Power supply RxD MR Version for panel surface mounting 3B1 Version for flush mounting/cubicle mounting 2B1 3B2 Alarm relay 1 2B2 3B3 2B3 2C2 2C4 3A1 3A2 2A1 2A2 1A1 1A2 8A2 8A1 8A4 8A3 7A2 7A1 7A4 7A3 8D2 8D1 8D4 8D3 7D2 7D1 7D4 7D3 input 1 input 2 input 3 input 4 input 5 input 6 input 7 input 8 7UM516 Alarm relay 2 Alarm relay 3 Alarm relay 4 Alarm relay 5 Alarm relay 6 Alarm relay 7 Alarm relay 8 Alarm relay 9 Alarm relay 10 Alarm relay 11 Alarm relay 12 Alarm relay 13 (Unit malfunction alarm) Trip/command relay 1 Trip/command relay 2 Trip/command relay 3 4B1 4B2 4A1 4A2 L Trip/command relay 4 Trip/command relay 5 V.24 interface, 2 kv isolated Coupling to central unit Fibre optic interface Coupling to central unit 7B1 8B1 6B1 7B2 8B2 6B2 7B3 8B3 6B3 7B4 8B4 6B4 3D1 4D1 3D2 4D2 3D3 4D3 3D4 4D4 3C1 4C1 3C2 4C2 3C3 4C3 3C4 4C4 6A3 6A1 6A2 5B1 5B3 5B4 5B2 5A1 5A3 5A4 5A2 6D1 6D3 6D4 6D2 5D1 5D2 5D3 5D4 4A3 4A Ind. out of step cl. 1 Ind. out of step cl.2 Trip out of step (cl. 1, cl. 2) Trip impedance protection (Z1) Group alarm (activ. L1, L2, L3) Anti hunt device impedance protection Trip reverse power l Pr l with SS Trip reverse power l Trip unbalanced load ( I 2 I 2th. ) Warning stage unbalanced load ( I 2 I 2th. ) Trip stator earth falut ( V 0 ) Trip coupling (M2) (M1) Internal failure Trip command 1 L Trip command 2 L Trip command 3 L Trip command 4 Trip command 5 TxD MT Optional V.24 or FO connection Fig. 5 Connection diagram for the 7UM516 Siemens LSA April

8 Dimension drawings in mm Diam. 5 or M4 Fibre optic interface Diam Front view Side view Panel cutout Fig. 6 7UM516 with housing 7XP (for panel flush mounting or cubicle mounting) Cutout 20 x 60 (without paint) detail Z: fibre optic interface Z Front view Side view Fig. 7 7UM516 with housing 7XP (for panel surface mounting) 8 Siemens LSA April 1995

9 Conditions of Sale and Delivery Export Regulations Trademarks Dimensions Conditions of Sale and Delivery Subject to the General Conditions of Supply and Delivery for Products and Services of the Electrical and Electronic Industry and to any other conditions agreed upon with the recipients of catalogs. Export Regulations In accordance with present German and US export regulations export licences (dated 03.95) are not required for the products listed in this catalog. Export and re export are therefore The technical data, dimensions and weights are subject to change unless otherwise stated on the individual pages of this catalog. The illustrations are for reference only. permissible without the approval of the relevant authorities except where current German export regulations contain country specific restrictions. We reserve the right to adjust the prices and shall charge the price applying on the date of delivery. A 9.91 a Subject to change. Relevant are the criteria stated in the delivery note and in the invoice. An export licence may be required due to country specific application of the product. Trademarks All product designations used are trademarks or product names of Siemens AG or of suppliers. Dimensions All dimensions in this catalog are given in mm Responsible for Technical contents: Norbert Schuster, Siemens AG, EV S T11, Nürnberg General editing: Claudia Kühn Sutiono, Siemens AG, EV MK 2, Erlangen Siemens LSA April

10 Bereich Energieübertragung und -verteilung Geschäftsgebiet Zähler, Sekundär- und Netzleittechnik P. O. Box D Nürnberg 10 Siemens Aktiengesellschaft Power Transmission and Distribution Order No.: E50001-K5752 A151-A Siemens LSA April 1995 Printed in the Federal Republic of Germany KG K SC 10 En

Overcurrent Protection / 7SJ45

Overcurrent Protection / 7SJ45 Overcurrent Protection / SJ SIPROTEC easy SJ numerical overcurrent protection relay powered by CTs Fig. / Description SIPROTEC easy SJ numerical overcurrent protection relay powered by current transformers

More information

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Overcurrent Protection / 7SJ46 SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Function overview Fig. /11 Description The SIPROTEC easy 7SJ46 is a numerical overcurrent protection relay which

More information

Overcurrent and Distance Relays

Overcurrent and Distance Relays Fig. 7SA53 line protection relay Application The 7SA53 numerical line protection relay provides selective and fast clearance of faults on overhead lines and cables with single and multiple end infeed in

More information

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New) XR1 Rotor Earth Fault Relay (May 2007) Manual XR1 (Revision New) Woodward Manual XR1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided

More information

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C) XR1 Rotor Earth Fault Relay Manual XR1 (Revision C) Woodward Manual XR1 (EN) Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by

More information

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New) XUA1 AC Voltage and phase balance relay (August 1996) Manual XUA1 (Revision New) Woodward Manual XUA1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

XUA1 - AC Voltage and phase balance relay

XUA1 - AC Voltage and phase balance relay XUA1 - AC Voltage and phase balance relay Contents 1. Applications and features 2. Design 3. Function 3.1 Voltage supervision 3.2 Unbalanced voltage supervision 4. Operation and settings 4.1 Setting of

More information

SIPROTEC 7SD60 Numerical Current Differential Protection Relay for Two Pilot-Wire Link

SIPROTEC 7SD60 Numerical Current Differential Protection Relay for Two Pilot-Wire Link SIPROTEC 7SD60 Numerical Current Differential Protection Relay for Two Pilot-Wire Link Protection Systems Catalog SIPROTEC 5.2 1999 SIPROTEC 7SD60 Numerical Current Differential Protection Relay for Two

More information

SIPROTEC. Multi-Functional Generator Protection Relay 7UM61. Preface. Contents. Introduction 1. Functions 2. Mounting and Commissioning 3

SIPROTEC. Multi-Functional Generator Protection Relay 7UM61. Preface. Contents. Introduction 1. Functions 2. Mounting and Commissioning 3 Preface SIPROTEC Multi-Functional Generator Protection Relay 7UM61 V4.1 Manual Contents Introduction 1 Functions 2 Mounting and Commissioning 3 Technical Data 4 Appendix Literature Glossary A Index C53000-G1176-C127-4

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

SIPROTEC 7SJ600 Numerical Overcurrent, Motor and Overload Protection Relay

SIPROTEC 7SJ600 Numerical Overcurrent, Motor and Overload Protection Relay Overcurrent Protection / 7SJ600 SIPROTEC 7SJ600 Numerical Overcurrent, Motor and Overload Protection Relay Function overview Description The SIPROTEC 7SJ600 is a numerical overcurrent relay which, in addition

More information

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New)

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New) XP2-R Power and reverse power relay (January 2006) Manual XP2-R (Revision New) Woodward Manual XP2-R GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

Excitation Systems. Service Generators SIPOL. Transistorized Excitation Systems for Synchronous Generators. Power Generation

Excitation Systems. Service Generators SIPOL. Transistorized Excitation Systems for Synchronous Generators. Power Generation Excitation Systems Service Generators Transistorized Excitation Systems for Synchronous Generators Power Generation Operating Characteristics High availability Reliability Digital control facilities Very

More information

XP2-R Power and Reverse Power Relay

XP2-R Power and Reverse Power Relay XP2-R Power and Reverse Power Relay Manual XP2-R (Revision C) Woodward Manual XP2-RE Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward

More information

Excitation Systems RG3 - T4. Transistorized Excitation Systems for Synchronous Generators. Power Generation

Excitation Systems RG3 - T4. Transistorized Excitation Systems for Synchronous Generators. Power Generation Excitation Systems RG3 - T4 Transistorized Excitation Systems for Synchronous Generators Power Generation Operating Characteristics Reliability High availability Digital control facilities Very good control

More information

XU2-AC AC voltage relay. (Februar 1997) Manual XU2-AC (Revision New)

XU2-AC AC voltage relay. (Februar 1997) Manual XU2-AC (Revision New) XU2-AC AC voltage relay (Februar 1997) Manual XU2-AC (Revision New) Woodward Manual XU2-AC GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

Plug-in microprocessor controlled multifuncional relay with automatic shorting of c.t.

Plug-in microprocessor controlled multifuncional relay with automatic shorting of c.t. Multifunctional relay Page 1 Issued: July 1998 Changed: since April 1989 Data subject to change without notice Features Plug-in microprocessor controlled multifuncional relay with automatic shorting of

More information

XI1-I Time overcurrent relay. (Januar 2007) Manual XI1-I (Revision New)

XI1-I Time overcurrent relay. (Januar 2007) Manual XI1-I (Revision New) XI1-I Time overcurrent relay (Januar 2007) Manual XI1-I (Revision New) Woodward Manual XI1-I GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

SIPROTEC 7SS60 Centralized Numerical Busbar Protection

SIPROTEC 7SS60 Centralized Numerical Busbar Protection SIPROTEC 7SS60 Centralized Numerical Busbar Protection Fig. /1 Description The SIPROTEC 7SS60 system is an inexpensive numerical differential current protection for busbars in a centralized configuration.

More information

E550 Series 2. Electricity Meters IEC/MID Industrial and Commercial ZMG400AR/CR. Technical Data

E550 Series 2. Electricity Meters IEC/MID Industrial and Commercial ZMG400AR/CR. Technical Data Electricity Meters IEC/MID Industrial and Commercial ZMG400AR/CR E550 Series 2 Technical Data Building on its tradition of industrial meters, Landis+Gyr is now bringing out the E550 Series 2, the latest

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

XF2 Frequency Relay. Manual XF2 (Revision A)

XF2 Frequency Relay. Manual XF2 (Revision A) XF2 Frequency Relay Manual XF2 (Revision A) Woodward Manual XF2 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by Woodward Governor

More information

SWT 3000 Teleprotection technical data siemens.com

SWT 3000 Teleprotection technical data siemens.com Power network telecommunication SWT 3000 Teleprotection technical data siemens.com Sustainable success for high-voltage power networks The SWT 3000 Teleprotection system has been the first choice for reliable

More information

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions Operating Instructions SIMEAS-T s Operating Instructions Transducer without auxiliary power for alternating current for alternating voltage for alternating voltage with expanded end range 7KG6111 and 7KG6101

More information

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103383_en_00 1 Description PHOENIX CONTACT - 06/2008 Features QUINT POWER power supply units highest system

More information

SPAE 010, 011 High Impedance Protection Relay

SPAE 010, 011 High Impedance Protection Relay SPAE 010, 011 High Impedance Protection Relay User s manual and Technical description f n = 50/60 Hz U n = 50 / 100 / 200 V 2 5 U REF > SPAE 010 0.8 U aux 0.6 1.0 RESET OK x 80... 265 V ~ _ 0.4 U > U n

More information

QUINT-PS/ 3AC/24DC/10

QUINT-PS/ 3AC/24DC/10 Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system

More information

E550 Series 2. Electricity Meters IEC/MID Industrial and Commercial ZMG310AR/CR. Technical Data

E550 Series 2. Electricity Meters IEC/MID Industrial and Commercial ZMG310AR/CR. Technical Data Electricity Meters IEC/MID Industrial and Commercial ZMG310AR/CR E550 Series 2 Technical Data Building on its tradition of industrial meters, Landis+Gyr is now bringing out the E550 Series 2, the latest

More information

Type CP-S, CP-C & CP-A Switch mode

Type CP-S, CP-C & CP-A Switch mode Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting

More information

PD300. Transformer, generator and motor protection Data sheet

PD300. Transformer, generator and motor protection Data sheet PD300 Transformer, generator and motor protection Data sheet DSE_PD300_eng_AO No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam T&D. One of

More information

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area. Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103129_en_01 PHOENIX CONTACT - 05/2008 1 Description QUINT POWER power supply units highest system availability

More information

3 Pole high impedance differential relay 7VH83

3 Pole high impedance differential relay 7VH83 Fig 1. High impedance differential protection relay 7VH83 Features l Integral CT shorting relay. l Robust solid state design. l Inrush stabilisation through filtering. l Fast operating time. l LED indicator.

More information

QUINT-PS-24DC/24DC/10

QUINT-PS-24DC/24DC/10 QUINT-PS-24/24/10 QUINT - converter, primary switched mode, input: 24 V, output: 24 V /10 A INTERFACE Data Sheet PHOENIX CONTACT - 02/2006 Description The QUINT - converter 24 V/10 A converts the voltage

More information

Utility Communications Teleprotection Equipment TPT-200

Utility Communications Teleprotection Equipment TPT-200 Utility Communications Teleprotection Equipment TPT-200 5C Communications Inc. All rights reserved Teleprotection is designed to transfer protection commands coming, in most cases, from distance protection

More information

METRAClip87 and 88 Clamp Multimeters

METRAClip87 and 88 Clamp Multimeters 3-349-795-03 1/7.14 Current and frequency measurement via clamp meter: METRAClip87: 1500 A AC TRMS and 1500 A DC METRAClip88: 2000 A AC TRMS and 3000 A DC Multimeter functions via connector sockets: V

More information

Phase and neutral overcurrent protection

Phase and neutral overcurrent protection Phase and neutral overcurrent protection Page 1 ssued June 1999 Changed since July 1998 Data subject to change without notice (SE970165) Features Two-phase or three-phase time-overcurrent and earth fault

More information

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase

More information

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:

More information

IRI1-ER - Stabilized Earth Fault Current Relay. Manual IRI1-ER (Revision A)

IRI1-ER - Stabilized Earth Fault Current Relay. Manual IRI1-ER (Revision A) IRI1-ER - Stabilized Earth Fault Current Relay Manual IRI1-ER (Revision A) Woodward Manual IRI-ER GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters Technical Data Sheet Alpha 20 Alpha 20 is a compact multifunction instrument which Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel

More information

AMIK 200 / 201 Technical Data Sheet

AMIK 200 / 201 Technical Data Sheet AMIK 200 / 201 Technical Data Sheet AMIK Special Features MODBUS (RS-485) Communication available only on Amik 201 On site Programmable CT/PT Ratios User selectable CT Secondary 1A/5A User selectable PT

More information

XN2 - Mains decoupling relay. Manual XN2 (Revision C)

XN2 - Mains decoupling relay. Manual XN2 (Revision C) XN2 - Mains decoupling relay Manual XN2 (Revision C) Woodward Manual XN2 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by Woodward

More information

Technical Specification

Technical Specification LARGEST RANGE OF IMPULSE TESTERS UP TO 100KV/100KA Technical Specification No. E-MIG0603IN2.doc revised: 20.October 2004 1 MIG Tester Type MIG0603IN2 1 MIG Tester Type MIG0603IN2 1 1.1 Introduction 1 2

More information

QUINT-PS/ 3AC/24DC/40

QUINT-PS/ 3AC/24DC/40 Primary-switched power supply unit with SFB technology, 3 AC, output current 40 A INTERFACE Data sheet 103133_en_00 1 Description PHOENIX CONTACT - 07/2009 Features QUINT POWER power supply units Maximum

More information

SPAD 346 C Stabilized differential relay

SPAD 346 C Stabilized differential relay SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Environmental Influences. Display. Inputs and Outputs. Electromagnetic Compatibility. Communication Interfaces. Insulation Strenght.

Environmental Influences. Display. Inputs and Outputs. Electromagnetic Compatibility. Communication Interfaces. Insulation Strenght. Electricity Meters IEC INDUSTRIAL+COMMERCIAL Landis+Gyr Dialog ZMG310AR/CR TECHNICAL DATA Frequency Nominal Frequency fn 50 or 60 Hz tolerance ± 2 % Mesurement Accuracy Accuracy ZMG310xR active energy

More information

IRI1-ER - Stabilized Earth Fault Current Relay

IRI1-ER - Stabilized Earth Fault Current Relay IRI1-ER - Stabilized Earth Fault Current Relay TB IRI1-ER 02.97 E 1 Contents 1. Summary 2. Applications 3. Characteristics and features 4. Design 4.1 Connections 4.1.1 Analog inputs 4.1.2 Output relays

More information

SIPROTEC Compact 7SJ80 V4.6 Overcurrent Time Protection

SIPROTEC Compact 7SJ80 V4.6 Overcurrent Time Protection SIPROTEC Compact 7SJ80 V4.6 Overcurrent Time Protection Technical Data Extract from manual E50417-G1140-C343-A4, chapter 4 Energy Automation Note For safety purposes, please note instructions and warnings

More information

QUINT-PS/ 1AC/24DC/20

QUINT-PS/ 1AC/24DC/20 Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data sheet 103129_en_04 1 Description PHOENIX CONTACT - 02/2010 Features QUINT POWER power supply units Maximum system

More information

INDUSTRIAL+COMMERCIAL ZMG400AR/CR, ZFG400AR/CR TECHNICAL DATA. IEC-specific data. Current. Measurement Accuracy. Measurement Behaviour.

INDUSTRIAL+COMMERCIAL ZMG400AR/CR, ZFG400AR/CR TECHNICAL DATA. IEC-specific data. Current. Measurement Accuracy. Measurement Behaviour. Electricity Meters IEC/MID INDUSTRIAL+COMMERCIAL Landis+Gyr Dialog ZMG400AR/CR, ZFG400AR/CR TECHNICAL DATA IEC-specific data Current Nominal Current I n 1 A, 5 A, 5 1 A Maximal Current I max metrological

More information

SPPA-E3000 Brushless Excitation System (BES, Type RG3)

SPPA-E3000 Brushless Excitation System (BES, Type RG3) / Technical Description / Juni 2014 SPPA-E3000 Brushless Excitation System (BES, Type RG3) Maximum-availability excitation system for synchronous generators with brushless exciters Answers for energy.

More information

E650 Series 3. Electricity Meters IEC/MID Industrial and Commercial ZMD402AT/CT, ZFD402AT/CT. Technical Data

E650 Series 3. Electricity Meters IEC/MID Industrial and Commercial ZMD402AT/CT, ZFD402AT/CT. Technical Data Electricity Meters IEC/MID Industrial and Commercial ZMD402AT/CT, ZFD402AT/CT E650 Series 3 Technical Data Building on its tradition of industrial meters, Landis+Gyr has developed the E650 Series 3, the

More information

Installation / Monitoring Technique

Installation / Monitoring Technique Installation / Monitoring Technique VARIMETER RCM Residual Current Monitor, Type B for AC and DC Systems IP 5883 0249633 IP 5883 ND 5018/035 ND 5018/030 According to IEC/EN 62 020, VDE 0663 For AC and

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

XN2 - Mains decoupling relay

XN2 - Mains decoupling relay XN2 - Mains decoupling relay Contents 1. Applications and features 2. Design 3. Function 3.1 Voltage supervision 3.2 Frequency supervision 3.3 Vector surge and frequency gradient supervision 3.3.1 Measuring

More information

3EE2 Special-Purpose Surge Arresters for the Protection of Motors, Generators and Furnace Transformers

3EE2 Special-Purpose Surge Arresters for the Protection of Motors, Generators and Furnace Transformers 3EE2 Special-Purpose Surge Arresters for the Protection of Mors, Generars and Furnace Transformers Rated 5.6 52 for ZnO types Low protection level Very high energy absorption capacity Very high short-circuit

More information

Capacitor protection relay

Capacitor protection relay Capacitor Protection Relay FEATURES Capacitor unbalance protection Line current unbalance protection Overvoltage protection Overheating protection Ground fault protection Overcurrent protection Undercurrent

More information

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide Relion 605 series Relion 605 series Self-Powered Feeder Protection Product Guide Contents 1 Description...3 2 Protection functions...3 3 Application...4 4 Self-supervision...4 5 Inputs and outputs...4

More information

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria

More information

High-Tech Range. IRI1-ER- Stablized Earth Fault Current Relay. C&S Protection & Control Ltd.

High-Tech Range. IRI1-ER- Stablized Earth Fault Current Relay. C&S Protection & Control Ltd. High-Tech Range IRI1-ER- Stablized Earth Fault Current Relay C&S Protection & Control Ltd. Contents 1. Summary 7. Housing 2. Applications 3. Characteristics and features 4. Design 7.1 Individual housing

More information

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice Issued: April 1999 Status: Updated Version: B/08.11.200 Data subject to change without notice Features Versatile, multifunction line fault indicator for distribution networks Overcurrent, earth-fault and

More information

Power Meter Series PM3200 Functions and characteristics

Power Meter Series PM3200 Functions and characteristics Functions and characteristics PB108433 This PowerLogic Power meter offers basic to advanced measurement capabilities. With compact size and DIN rail mounting, the PM3200 allows mains and feeders monitoring

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

INDUSTRIAL+COMMERCIAL ZMD400AR/CR, ZFD400AR/CR TECHNICAL DATA. Frequency. IEC-specific data. Current. Measurement Accuracy.

INDUSTRIAL+COMMERCIAL ZMD400AR/CR, ZFD400AR/CR TECHNICAL DATA. Frequency. IEC-specific data. Current. Measurement Accuracy. Electricity Meters IEC INDUSTRIAL+COMMERCIAL Landis+Gyr Dialog ZMD400AR/CR, ZFD400AR/CR TECHNICAL DATA Frequency Nominal Frequency f n 50 or 0 Hz tolerance ± 2% IEC-specific data Current Nominal Current

More information

ISOMETER IRDH575. Approvals

ISOMETER IRDH575. Approvals Insulation monitoring device for unearthed AC, DC and AC/DC systems (IT systems) with control and display function for EDS insulation fault location systems IRDH575_D00089_02_D_XXEN/09.2018 Insulation

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

Protection components

Protection components Multifunction protection relays LT-P Environment Conforming to standards IEC 947-4-1, IEC 34-11, IEC 755, VDE 010, VDE 00. &Ãmarking Meets the essential requirements of the Low Voltage equipment (LV) &

More information

QUINT-PS AC/24DC/40

QUINT-PS AC/24DC/40 Power supply unit INTERFACE Data sheet 102315_en_02 1 Description PHOENIX CONTACT 2010-04-23 Features QUINT POWER power supply units for plant and special engineering reliably start heavy loads with high

More information

SPECIFICATION FOR OVERCURRENT RELAYS

SPECIFICATION FOR OVERCURRENT RELAYS SPECIFICATION FOR OVERCURRENT RELAYS 1/9 1. Procedure A manufacturer willing to classify an overcurrent relay according to this specification should provide: A complete file providing a clear, unambiguous

More information

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300 Monitoring Technique VARIMETER IMD Insulation monitor RN 5897/300 0274214 Your Advantages For mobile generator sets according to DIN VDE 0100-551 Preventive fire and system protection Detection of symmetric

More information

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection DATASHEET - ETR4-70-A Delivery program Timing relay, 2W, 0.05s-100h, multi-function, 24-240VAC/DC, potentiometer connection Part no. ETR4-70-A Catalog No. 031888 Eaton Catalog No. XTTR6A100H70B EL-Nummer

More information

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics Power Quality Monitor Individual Harmonics measurement upto 56th Harmonics True representation of Voltage & Current waveforms. Phasor Representation of All 3 phases for system analysis Real Time Clock

More information

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents Data sheet Current monitoring relays CM-SRS.2 for single-phase AC/DC currents For the monitoring of currents in single-phase AC/DC systems, ABB s CM range comprises a wide selection of powerful and compact

More information

MINI-PS AC/24DC/1.3

MINI-PS AC/24DC/1.3 Power supply unit INTERFACE Data sheet 102894_en_03 1 Description PHOENIX CONTACT 2015-11-17 Features MINI POWER power supplies for MCR technology In measurement and control technology (MCR), modular electronics

More information

Reactive Power Control Relay RM 2106 / 2112 Operating Instructions. FRAKO Kondensatoren- und Anlagenbau

Reactive Power Control Relay RM 2106 / 2112 Operating Instructions. FRAKO Kondensatoren- und Anlagenbau Reactive Power Control Relay RM 2106 / 2112 Operating Instructions FRAKO Kondensatoren- und Anlagenbau www.frako.com Figure 1 Front view a b c d e Display for active capacitor stages Display for inductive

More information

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC DATASHEET - ETR4-51-A Timing relay, star-delta, 50 ms, 1W, 3-60s, 24-240VAC/DC Part no. ETR4-51-A Catalog No. 031884 Eaton Catalog No. XTTR6A60S51B EL-Nummer 0004133308 (Norway) Delivery program Product

More information

Three-phase monitoring relay CM-PFS

Three-phase monitoring relay CM-PFS Data sheet Three-phase monitoring relay CM-PFS The CM-PFS is a three-phase monitoring relay that is used to monitor three phase mains for incorrect phase sequence and phase failure. All devices are available

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities

More information

ALPHA 20 MULTIFUNCTION METER (ALPHA SERIES)

ALPHA 20 MULTIFUNCTION METER (ALPHA SERIES) Alpha Series www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters Shunts ALPHA

More information

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. REGULATION AUTOMATIC SYNCHRONIZER for GENERATOR NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks. 2CDC 251 048 F0t08 CM-MPS.11 2CDC 251 049 F0t08 CM-MPS.21 2CDC 251 050 F0t08 CM-MPS.31 2CDC 251 051 F0t08 CM-MPS.41 R/T: yellow LED - relay status, timing F1: red LED - fault message F2: red LED - fault

More information

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator REGULATION Automatic Synchronizer for Generator NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

Modular multifunction generator protection

Modular multifunction generator protection Modular multifunction generator Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970186) Features is a modular generator that enables selection of the desired in

More information

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication: Application : RISH Master 3490 SS is a 96mm x 96mm panel mounted kilowatt hour meter it measures active energy with class 1.0 accuracy having auto-resetting 8 digit seven segment LED counter. The unit

More information

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual REK 50 protection of a synchronous machine User s Manual REK 50 X 0 9 8 7 6 5 4 0 V 00 V 0 V 5 6 7 Ordering No: REK 50-AA Uau = 00/0 Vac Un = 48 V Serial No: fn = 50/60 Hz Uec = ma 600 Vdc MRS 75587-MUM

More information

SINEAX I 503 / SINEAX U 504 Transducer for AC current or AC voltage

SINEAX I 503 / SINEAX U 504 Transducer for AC current or AC voltage Application The transducers SINEAX I 503/U 504 (Figs. 1 and 2) are designed to convert a sinusoidal AC current or voltage into a load independent DC signal proportional to the measured value. This output

More information

Transformer differential protection

Transformer differential protection Transformer differential protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970883) Features Three phase differential protection with two, three, five or

More information

Data Sheet. RISH Master Record %THD

Data Sheet. RISH Master Record %THD Data Sheet %THD Application : measures important electrical parameters & replaces the multiple analog panel meters. It measures electrical parameters like AC current, Voltage, frequency, active energy

More information

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks. 2CDC 251 054 F0t08 CM-MPN.52 2CDC 251 055 F0t08 CM-MPN.62 2CDC 251 056 F0t08 CM-MPN.72 Features Monitoring of three-phase mains for phase sequence (can be switched off), phase failure, over- and undervoltage

More information

Time over/underfrequency relay with protection assemblies

Time over/underfrequency relay with protection assemblies Time over/underfrequency relay with protection assemblies RXFK 2H and RAFK 509 009-BEN Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970104) (SE970108) Features

More information

SIPROTEC 5 V1.1 Distance Protection, Line Differential Protection and Breaker Management for 1-Pole and 3-Pole Tripping 7SA87, 7SD87, 7SL87, 7VK87

SIPROTEC 5 V1.1 Distance Protection, Line Differential Protection and Breaker Management for 1-Pole and 3-Pole Tripping 7SA87, 7SD87, 7SL87, 7VK87 SIPROTEC 5 V1.1 Distance Protection, Line Differential Protection and Breaker Management for 1-Pole and 3-Pole Tripping 7SA87, 7SD87, 7SL87, 7VK87 Technical Data Extract from manual C53000-G5040-C011-2,

More information

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC 2CDC 251 048 F0t08 CM-MPS.11 2CDC 251 049 F0t08 CM-MPS.21 Features Monitoring of three-phase mains for phase sequence (can be switched off), phase failure, over- and undervoltage as well as phase unbalance

More information

MINI MCR-SL-UI-f(-SP)

MINI MCR-SL-UI-f(-SP) Configurable Analog Frequency Transducer INTERFACE Data Sheet PHOENIX CONTACT - 02/2006 Description The configurable analog frequency transducer MINI MCR-SL-UI-f(-SP) is used to convert analog standard

More information

Introduction DIN rail mounted electricity meters

Introduction DIN rail mounted electricity meters Introduction DIN rail mounted electricity meters Modular DIN Rail Products offer a wide range of functions to be integrated in electrical installations with significant benefits for the user. DIN rail

More information

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay Generator Differential Relay The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3G relay offers the following

More information

Miniature circuit-breakers S 280 UC series. System pro M. Technical data

Miniature circuit-breakers S 280 UC series. System pro M. Technical data Technical data 11 Robbie Rd. / Avon, MA 02322 T:(508)513-1000 F:(508)513-1100 70 Ernest St. / Providence, RI 02905 T:(401)781-7100 www.controllerservice.com System pro M Prior to connection of aluminum

More information

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks. 2CDC 251 052 F0t08 CM-MPS.23 2CDC 251 053 F0t08 CM-MPS.43 - relay status, timing - fault message - fault message Adjustment of the tripping delay t V Adjustment of the threshold value for overvoltage 6

More information

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) 1MRS752324-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) Contents 1. Introduction... 2 1.1

More information