D64RPBH13 INSTRUCTION MANUAL G/F TRIP LEVEL + TRIP INHIBIT LEVEL 500:1 CT 10000:1 CT L RRR L RRL

Size: px
Start display at page:

Download "D64RPBH13 INSTRUCTION MANUAL G/F TRIP LEVEL + TRIP INHIBIT LEVEL 500:1 CT 10000:1 CT L RRR L RRL"

Transcription

1 D64PBH13 INSTUCTION MANUA ON ON SWITCH G/F TIP EVE + TIP INHIBIT EVE 500:1 CT 10000:1 CT A + 200A A + 200A A + 200A A + 200A A + 200A A + 20A + 20A + 20A + 20A + 20A + 400A + 400A + 400A + 400A + 400A + 400A A A + 50A A + 50A A + 50A A + 50A A + 50A A + 50A A + 100A A + 100A A + 100A A + 100A A + 100A A + 100A A + 100A A SWITCH G/F TIP DEAY 25 ms 65 ms 100 ms 130 ms 160 ms 190 ms 225 ms 255 ms 375 ms 500 ms 625 ms 750 ms 875 ms 1000 ms NOMA SW 11 TIP INHIBIT MODE DISABED ENABED SW 12 OPEATING MODE UN AST TIP FASHES: 1 = GOUND FAUT 2 = INHIBIT BACKUP 4 = CT OPEN CICUIT 5 = F/S CV O SS CON T = TIP FAIED ESET NON-FAISAFE FAISAFE DOU BE C ICK FO TEST T TIPPED F Cat. No. D64PBH13 CANADA USA Eaton Electrical Canadian Operation Eaton Electrical 5050 Mainway Drive 1000 Cherrington Parkway Burlington, Ontario, Moon Township, PA 7 5Z September, 2009 Page 1

2 TABE OF CONTENTS PAGE TABE OF CONTENTS... 2 IST OF FIGUES, TABES & FOMS GENEA DESCIPTION OPEATION GOSSAY OF TEMS DIPSWITCH SETTINGS GOUND FAUT TIP DEAY GOUND FAUT TIP EVE TIP INHIBIT MODE OUTPUT CICUIT BEAKE OPEATING MODE TAMPEPOOF DIPSWITCHES INDICATION G/F TEST - ESET G/F TEST INTENA G/F TEST EXTENA ESET MEMOY AFTE OSS OF CONTO VOTAGE INSTAATION INSTUCTIONS MOUNTING THOUGH-THE-DOO EA PANE EXTENA C311CT CUENT TANSFOME CONNECTIONS CATAOG NUMBES TECHNICA SPECIFICATION FIGUE NO. IST OF FIGUES, TABES, & FOMS PAGE 1. TYPICA FIED CONNECTIONS DIMENSIONS & WEIGHTS TABE NO. 1. GOUND FAUT TIP DEAY GOUND FAUT TIP EVE TIP INHIBIT MODE OUTPUT CICUIT BEAKE OPEATIN MODE CICUIT BEAKE TIP CONTACT STATES FOM NO. 1. TEST ECOD September, 2009 Page 2

3 1. GENEA DESCIPTION The D64PBH13 is a ground fault relay for use on solidly grounded or resistance grounded systems over a frequency range of Hz. This innovative digital electronic relay measures ground fault current using either, a special Eaton s Cutler-Hammer C311CT zero sequence current transformer with a turns ratio of 10000:1 or, the standard family of C311CT zero sequence current transformers with a turns ratio of 500:1. Either C311CT is connected to the CT input terminals CT1 & CT2 The D64PBH13 reacts to alternating current only and will reject direct current signals. It will maintain accuracy over a frequency range of 40 to 200 Hz., making it suitable for variable frequency drive applications. The ground fault current trip level is set on 5 DIPswitches in 25 discrete steps. The range is 50 Amps Amps when using the 10,000:1 CTs and 2.5 Amps 60 Amps when using the 500:1 CTs. The trip level can be set just above the charging current 1. Any deterioration in the circuit will trip the relay. This also permits scheduled field testing of the relay (by lowering the trip level). 1 The capacitance-to-ground charging current on a system will vary depending on: the overall length of the cables; the types of loads; the quality of insulation on the phase conductors; the surrounding equipment grounding, cable trays, junction boxes, etc.; and, the type of transformer. A "ule-of-thumb" for systems 600 Volts and lower: The charging current is 0.5 Amps per 1000 kva of transformer capacity. The response time on ground fault trip is set on 4 DIPswitches. The range is 25 ms second in 14 discrete steps. The D64PBH13 is suitable for use on Service Protection Equipment applications. The Trip INHIBIT function can be Enabled or Disabled by means of a front accessible DIPswitch. The inhibit level is related to the ground fault trip level setting over a range of 200 Amps to 2000 amps when using the 10,000:1 CTs and 10 Amps 100 Amps when using the 500:1 CTs. With Inhibit Enabled, if the ground fault current exceeds the inhibit level, the output circuit breaker trip will be inhibited until the ground fault current drops below the inhibit level. A voltage-operated circuit breaker with an external toggle handle is used as the output device. It provides a visual indication of the status of its output contacts. The contacts are Form "C" N.O. - N.C. voltage free. They may be used to operate the upstream protective device and indicate a failure of the system. The circuit breaker can be set to operate in the failsafe or the non-failsafe mode by means of a front accessible DIPswitch. The circuit breaker mechanism is trip free (cannot be closed if a ground fault is being sensed by the relay). Manual reset of the circuit breaker toggle will restore the output contacts to the normal state. The circuit breaker toggle in the Tripped position indicates that the D64PBH13 has sensed a ground fault current higher than the trip level for a period longer than the trip time and that the output contacts have operated, or, if in the Failsafe mode, it will also indicate that the control voltage has been removed from terminals + & N-. The D64PBH13 constantly supervises the connection to the external CT. Open circuits are detected and will cause a trip. Please note that the D64PBH13 does not employ any DC injection to implement this since even small DC current sent through the secondary windings of a CT can bias its core enough to shift the trip point outside specification on sensitive settings. For the CT supervision to work, either the special Eaton s Cutler- Hammer C311CT zero sequence current transformer with a turns ratio of 10000:1, or the standard family of Series A2 C311CT zero sequence current transformers with a turns ratio of 500:1 must be installed, as specified in section 3.2. A Cover mounted ESET button is standard. A green UN ED shows correct operation by slowly flashing (1 s on/ 1 s off) when control voltage is applied to terminals + & N-. A red ED shows short 0.25 s flashes as a code indicating the cause of trip: 1 flash every few seconds ground fault; 2 consecutive flashes Inhibit Backup; 4 consecutive flashes CT circuit open; 5 consecutive flashes Control Voltage lost in Failsafe mode (See Section 2.6 for explanation of memory feature); continuous consecutive flashes Trip Failed. September, 2009 Page 3

4 Pull-apart terminal blocks simplify connection of field wiring. They have two 12 AWG screw clamps per pole with 90 and 180 orientation. Captive screws secure the blocks to the relay, safe from the effects of shock and vibration. The D64PBH13 operates on a control voltage of Volts ac/dc. 2. OPEATION 2.1 GOSSAY OF TEMS Circuit Breaker Toggle - Normal: It is not necessary to apply control voltage to terminals + & N- before resetting the toggle of the circuit breaker to Normal. However, control voltage must be applied to terminals + & N- in order for the relay to sense a trip condition. With control voltage on terminals +& N- (green UN ED flashing), The Normal position indicates that the D64PBH13 is sensing a normal condition (no ground fault on the system being monitored). In the Normal position the output contacts are in the normal state: Terminals closed, Terminals open. Circuit Breaker Toggle - Tripped: With control voltage on terminals + & N- (green UN ED flashing), The Tripped position indicates that the D64PBH13 has sensed a ground fault current higher than the trip level for a period longer than the trip time and that the output contacts have operated. Also, if the D64PBH13 is in Failsafe mode, the Tripped position will indicate that the control voltage has been removed from terminals + & N-. In the Tripped position the output contacts are in the tripped state: Terminals open; Terminals closed. Manual eset: The toggle of the circuit breaker must be placed in the Normal position to reset the contacts to the normal state after a trip, providing the ground fault has been cleared or the measured values are within the preset limits. Non-Failsafe: The circuit breaker can be placed in the Normal position with or without control voltage being applied on terminals + & N-. Control voltage must be applied to terminals + & N- in order for the relay to sense a trip condition. With control voltage on terminals + & N- (green UN ED flashing), the circuit breaker will trip and the output contacts will change state when the measured values reach or exceed the DIPswitch settings for current and time. The Non-Failsafe mode is recommended for the circuit breaker Trip when being used with shunt trip devices. The circuit breaker should be equipped with a coil clearing contact in its shunt trip circuit. Failsafe: The circuit breaker can be placed in the Normal position with or without control voltage being applied on terminals + & N-. Control voltage must be applied to terminals + & N- in order for the relay to sense a trip condition. The circuit breaker will trip and the output contacts will change state when either or both of the following conditions occur: - The measured values reach or exceed the DIPswitch settings for current and time. - Control voltage is removed from terminals + & N-. The Failsafe mode is recommended for the circuit breaker Trip when being used with undervoltage devices. This includes: contactor coils; starter coils; and circuit breakers equipped with UV trip coils. September, 2009 Page 4

5 Trip Free: The output circuit breaker is 'trip free', meaning that its contact cannot be held closed against a fault by manually keeping the toggle in the NOMA position. Note however that this is only true when control voltage is present on terminals + and N-. Trip Inhibit: Contactors are not designed to interrupt high fault currents. Under these conditions the upstream short circuit protective devices, fuses or circuit breaker, should interrupt the fault. Trip INHIBIT function can be Enabled or Disabled by means of DIPswitch no. 11. The inhibit level is related to the ground fault trip level over a range of 200 Amps to 2000 amps when using the special Eaton s Cutler-Hammer C311CT zero sequence current transformer with a turns ratio of 10000:1. With Inhibit Enabled, if the ground fault current exceeds the inhibit level the output circuit breaker will be inhibited until the ground fault current drops below the inhibit level. However, should the current fail to drop within 1.2 s, then, as a last resort, the unit will trip showing the Inhibit Backup Trip code on its red ED (2 flashes). It is advisable to replace the contactor after this event since it was used to break a current possibly well outside its rating. The inhibit level is related to the ground fault trip level over a range of 10 Amps to 100 amps, when using the standard family of C311CT zero sequence current transformers with a turns ratio of 500:1. With Inhibit Disabled under the same conditions, the output circuit breaker will trip after the preset trip delay time. The INHIBIT function is useful when the D64PBH13 is being used to trip a contactor or motor starter on a solidly grounded system. In this application, there is no defined limit to the magnitude of ground fault current should a bolted ground fault occur. By inhibiting the trip it allows the upstream protective device to clear the fault. MEMOY AFTE OSS OF CONTO VOTAGE When control voltage is removed from the D64PBH13, the AST TIP registration will be memorized (for at least one week). Pressing the eset pushbutton before restoring control voltage will light either the green ED or the red ED, green indicating no trip was registered and red indicating the opposite. The green ED will light continuously, whereas the red ED will give a sequence of short flashes as described in section 2.4 indicating the cause of trip. 2.2 DIPSWITCH SETTINGS efer to the figure on the front page of this manual. There is one 12 - position array of DIPswitches on the front of the D64PBH13. The factory setting of all DIPswitches is EFT (). Position 1-4: These four DIPswitches (1, 2, 3, & 4) are assigned to Ground Fault TIP DEAY settings. Position 5-8: These five DIPswitches (5, 6, 7, 8, & 9) are assigned to Ground Fault TIP EVE and TIP INHIBIT EVE settings. Position 10: This DIPswitch is reserved for use in the D64PBH15 relay Position 11: This DIPswitch is assigned to TIP INHIBIT MODE. Position 12: This DIPswitch is assigned to Output Circuit Breaker OPEATING MODE. September, 2009 Page 5

6 2.2.1 GOUND FAUT TIP DEAY The ground fault TIP DEAY time range is 25 milliseconds second. Table 1 provides a listing of the TIP DEAY settings, which can be made with DIPswitches 1 through 4 on the 12 Position Array. The Trip Delay begins when the ground fault trip level setting is reached or is exceeded. Table 1: Ground Fault Trip Delay DIPSWITCH SETTINGS TIME DEAY IN MIISECONDS =EFT =IGHT * * Factory Setting Set the ground fault TIP DEAY to provide the desired delay before the output relay will trip when the ground fault TIP EVE setting is reached or exceeded. The setting should be selected to co-ordinate with other ground-fault devices connected on the same transformer secondary: set shorter than upstream devices; set longer than downstream devices. If no other ground-fault devices are connected, set for the shortest time GOUND FAUT TIP EVE The ground fault TIP EVE range is either Amps when using the special Eaton s Cutler- Hammer C311CT zero sequence current transformer with a turns ratio of 10000:1 or Amps when using the standard family of C311CT zero sequence current transformers with a turns ratio of 500:1. The following table provides a listing of the TIP EVE settings, which can be made with DIPswitches 5 through 9. The ground fault TIP EVE setting determines the inhibit level (when inhibit is enabled). September, 2009 Page 6

7 Table 2: Ground Fault Trip evel DIPSWITCH SETTINGS EVES WHEN USING C311CTs WITH 500:1 TUNS ATIO TIP EVE INHIBIT EVE =EFT IN AMPS IN AMPS =IGHT (When INHIBIT is Enabled) As indicated in the General Description, it is recommended that the ground fault TIP EVE setting be kept as close to the charging current as possible. This will provide maximum safety for operating personnel and equipment protection. On resistance grounded systems, the TIP EVE setting should be set lower than 20% of the Neutral Grounding esistor let-through current. If the measured ground fault current exceeds the TIP EVE setting, the output circuit breaker will trip after the pre-selected TIP DEAY TIP INHIBIT MODE TIP INHIBIT is described under the glossary of terms. The setting of DIPswitch 11 determines if TIP INHIBIT is disabled or enabled. This is shown in Table 3. Table 3: Trip Inhibit Mode DIPSWITCH SETTINGS 11 =EFT =IGHT TIP INHIBIT MODE * DISABED ENABED * Factory Setting September, 2009 Page 7 EVES WHEN USING C311CTs WITH 10,000:1 TUNS ATIO TIP EVE INHIBIT EVE IN AMPS IN AMPS (When INHIBIT is Enabled) * * * Factory Setting * Factory Setting

8 2.2.4 OUTPUT CICUIT BEAKE OPEATING MODE CONTACT STATE The two different OPEATING MODES are described under the glossary of terms. The setting of DIPswitch 12 determines the operating mode of the D64PBH13 output circuit breaker. This is shown in Table 4. Use this table when deciding on field connections. The state of the output circuit breaker contacts is shown in Table 5. Also, refer to the CONNECTIONS section. Table 4: Output Circuit Breaker Operating Mode DIPSWITCH SETTINGS 12 =EFT =IGHT OUTPUT CICUIT BEAKE OPEATING MODES * NON-FAISAFE FAISAFE * Factory Setting 2.3 TAMPE POOF DIPSWITCHES Eleven of the twelve DIPswitches are used to program the D64PBH13. However, to discourage unauthorized manipulation, the preselected settings can only be changed by going through the procedure outlined below. When an attempt is made to change the settings without going through this procedure, the green and red EDs start to blink alternately until the switches are returned to their original positions. Should the switches be left in other than the preselected settings, the preselected settings, being stored in nonvolatile memory, remain valid. The proper procedure to change settings is as follows: 1. The dipswitches are placed in the new positions (ignoring the blinking EDs). 2. Within 15 seconds after the last change was made (or control power was applied), the system is brought in test mode using the local pushbutton, causing the new settings to become active. Since the system will trip now, changing the settings cannot go by undetected. See section 2.5 for a description of how to invoke test mode. Note that any trips must be reset before this procedure can be completed. 2.4 INDICATION There are two ED s on the front of the D64PBH13. - A green UN ED shows correct operation by slowly flashing (1 s on/ 1 s off) when control voltage is applied to terminals + & N-. - A red AST TIP ED shows short 0.25 s flashes as a code indicating the cause of AST TIP: - One flash every few seconds means that the ground fault current exceeded the set G/F Trip evel during the G/F Trip Delay time.. In case the G/F Trip Inhibit function is enabled, the ground fault current may have exceeded the Trip Inhibit evel (overriding the G/F Trip Delay time), but in that case the upstream tripping device tripped correctly within 1.2 s and after the current dropped to zero as a result of that, the D64PBH13 activated its output circuit breaker to isolate the faulty circuit. This trip is labelled Ground Fault. September, 2009 Page 8

9 - Two.25 s flashes every few seconds means that the ground fault current exceeded the Trip Inhibit evel but the upstream device failed to trip during 1.2 s. The D64PBH13 then tripped as a last resort. The contactor should be replaced since its contacts may well be damaged. This trip is labelled Inhibit Backup. - Four 0.25 s flashes every few seconds means that the connection of the external CT is open circuited. Note that the trip is latched until reset; therefore intermittent failures will be captured, overcoming the impression that the D64PBH3 tripped without cause. This trip is labelled CT Open Circuit. - Five 0.25 s flashes every few seconds means that control voltage was lost while the D64PBH13 was in the Failsafe operating mode. The ESET pushbutton must be pressed before restoring control voltage to activate this indication. - Continuous 0.25 s flashes indicate an extra trip failed alarm state on top of one of the possible trips described above. Following the operation of the output circuit breaker, measured ground fault current remained at a high level. When the local reset button is first pressed, the trip is not reset, but the trip failed alarm state is. As a result the red ED will now show the original cause of trip. This alarm is labelled Trip Failed. Please note that the red ED is a convenient indicator only. It does not affect the operation of the output circuit breaker. After a fault is cleared, the user may or may not decide to reset the ED. A subsequent fault will cause the indication to be updated in either case. 2.5 G/F TEST - ESET G/F TEST INTENA Double-clicking the built-in ESET TEST pushbutton invokes a test which switches an AC voltage onto the processor s CT sensor input. The voltage is scaled to simulate a Ground fault current of 1.5 times the G/F trip level set point. The output circuit breaker will trip on G/F after the set delay (plus 0.4 s) and the AC test voltage will be switched off. The red ED will turn on solid. This proves that the internal electronics and output circuit breaker are functioning. Optionally, pressing the reset button again will reset the red ED enabling the green UN ED. eclose the circuit breaker (Normal position). No external power supply is required G/F TEST EXTENA Provision is made for external testing if required. efer to Figure 1. Select a momentary contact single pole normally closed pushbutton rated at least 3 Amps at 10 Volts ac. Connect as shown in Figure 1. When pressed the circuit to the external CT is opened. This results in a trip and the red ED will flash four 0.25 s flashes (CT Open Circuit). This proves that the current transformer is connected and the windings are okay, the CT monitor's detection circuit is operating, and the internal electronics and output circuit breaker are functioning. A Test ecord Form is included in this instruction manual. This form provides spaces to record the date the test was performed and the results. Those in charge of the building s electrical installation should retain the form in order to be available to the authority having jurisdiction ESET The built-in ESET TEST pushbutton is used to optionally reset the red AST TIP ED in the D64PBH13. The external pushbutton cannot be used to reset the red AST TIP ED. September, 2009 Page 9

10 2.6 MEMOY AFTE OSS OF CONTO VOTAGE When control voltage is removed from the D64PBH13, the AST TIP registration will be memorized (for at least one week). Pressing the eset pushbutton before restoring control voltage will light either the green ED or the red ED, green indicating no trip was registered and red indicating the opposite. The green ED will light continuously, whereas the red ED will give a sequence of short flashes as described in section 2.4 indicating the cause of trip. Please note that if the D64PBH13 is operated in the Failsafe mode (see section 2.2.4), and there was no trip when control voltage disappeared, the system will still activate the trip register and trip the output circuit breaker at the very moment of losing voltage. If this is what happened, the red ED will show five consecutive short flashes, meaning relay was merely activated because control voltage was lost while operating in Failsafe mode. The AST TIP registration is written to non volatile memory at the moment the D64PBH13 powers down. This way the trip code is accessible -by pressing the ESET button- even without control voltage present, which is particularly helpful when the tripping of the relay also causes control voltage to disappear. However, there is a very limited amount of backup power stored internally to support this, so the number of red flashes must be verified at the very moment when the button is being pressed. The backup power will hold for days as long as it is not exhausted by the pressing of the button. 3. INSTAATION INSTUCTIONS Place the D64PBH13 in a clean dry enclosure. Try to keep the exposure to mechanical shock and vibration to a minimum. The internal electronics have been encapsulated in epoxy to improve the performance in high vibration environments. ocate the relay close to the isolating device (circuit breaker or contactor) which is protecting the circuit being monitored. Provide maximum clearance between both the D64PBH13 and the C311CT and any strong magnetic flux producing devices such as power transformers, autotransformers, control transformers, reactors, and high power conductors and buswork. 3.1 MOUNTING efer to Figure 2 for mounting dimensions of the D64PBH13 relay. It is designed for through-the-door or rear panel mounting THOUGH-THE-DOO Four 4 mm (5/32") holes in the flanged cover of the relay permit bolting to the door using suitable hardware. A 102 mm high (4.0") x 72 mm wide (2.85") cut-out is required in the door. emove the pull-apart terminal block from the relay to permit the relay to be inserted through the cutout. From the front of the door, insert the relay through the cut-out. Mount the relay cover to the front of the door using the customer supplied mounting hardware (four bolts, washers and nuts) EA PANE The relay may be mounted with either mounting screws or 35 mm DIN rail. Two #8-32 x 3/4" (M4 x 20) mounting screws are required for screw mounting. For DIN rail mounting, the rail should be bolted to a flat surface. Install the DIN rail vertically. Allow at least 1" (25.4 mm) of rail to extend beyond each end of the relay. Install a stop block on the DIN rail 1" (25.4 mm) from the bottom to keep the D64PBH13 in position. Secure the relay to the DIN rail ensuring the white release latch at the left side of the relay engages the rail. September, 2009 Page 10

11 3.2 EXTENA C311CT CUENT TANSFOME The D64PBH13 is designed to operate with either, a special Eaton s Cutler-Hammer C311CT zero sequence current transformer with a turns ratio of 10000:1 or, the standard family of C311CT zero sequence current transformers with a turns ratio of 500:1. Each C311CT is epoxy molded for exceptional mechanical properties and has a high-grade silicon iron core for excellent coupling characteristics. C311CTs have built-in back-to-back zeners across the output terminals to provide maximum safety in the event of an open CT secondary circuit. efer to section 4 to select the catalog number of the C311CT current transformer with the opening required for the application.. Each C311CT is epoxy molded for exceptional mechanical properties and has a high-grade silicon iron core for excellent coupling characteristics. C311CTs have built-in back-toback zeners across the output terminals to provide maximum safety in the event of an open CT secondary circuit. Phase conductors must be insulated for the system voltage when it is higher than 660 Volts. efer to Figure 1. Pass the phase conductors through the CT window. If the neutral conductor is being connected downstream, it is to be passed through the window. Do not pass ground conductors through the CT window. In applications that require shielded wires to pass through the CT window, return the shields through the CT window before connecting them to ground. Position power cables in the center of the current transformer opening. Keep cables and buswork clear of the split on split core current transformers. 3.3 CONNECTIONS All connections to the D64PBH13 are by means of screw clamp terminals rated 10 Amps, 300 Volts. Terminals will accept #26-12 AWG solid or stranded conductors. The terminals are pull apart. They have two 12 AWG screw clamps per pole with 90 and 180 orientation. A screw mounted locking block is located at each end of the terminal block for maximum security. Since the relay housing is non metallic, no chassis bond is required. For good EMC behaviour the following wiring practices are recommended: - Connect the FB ( Frame Bond ) terminal to the structure ground as close as practically possible to the component being grounded using the shortest wire. - The D64PBH13 has an isolated power supply. Therefore the N- terminal should be connected to the structure ground at the same point as the neutral of the control transformer. See figure 1. - Avoid looping or coiling any/all wires connected to the component. - Dress all conductors as close as practically possible to the back panel or grounded frame. - Use shielded twisted leads on interconnection between CT and elay. - The shield should extend the full length of the twisted interconnection leads. - Connect shield to structure ground as close as practically possible to the elay. - When stripping conductor insulation care should be taken to avoid breaking any conductor strands. Connect Volt ac/dc control voltage to terminals + & N-. efer to Figure 1 and Table 4. Decide on the connection of field devices to output circuit breaker contact terminals by comparing the desired control of the field devices under various operating conditions. Figure 1 shows a typical connection of a 120 Volt ac circuit breaker shunt trip coil (ST) to the closed contact of the output circuit breaker. Comparing the output circuit breaker contact states, it can be seen that this could be used with the NON-FAISAFE operating mode. The N.C. contact, terminals 11 & 12, (open when the circuit breaker toggle is placed in the NOMA position) would be used for the shunt trip coil circuit. September, 2009 Page 11

12 Connect the external C311CT current transformer to terminal CT1 & CT2 of the D64PBH13, using 14 AWG (minimum) twisted conductors. If a remote Test button is being used connect as shown in Figure 1. CAUTION: Internally these terminals are connected to the FB terminal via a 2.5 V DC voltage source, shunted with a 7 V transients suppressing zener diode. DO NOT connect the external transformer to ground at any other point. 4. CATAOG NUMBES D64PBH13 Ground Fault elay with Volt ac/dc control voltage, for use on maximum 660 Volt power system, current trip range: Amps with 500:1 ratio C311CTs or Amps with 10,000:1 ratio C311CTs, trip time: 25 ms 1.0 sec, trip output: toggle operated circuit breaker, for use with service protection equipment. Zero Sequence Current Transformers with 500:1 ratio: C311CT1-A2 1.81" (46 mm) inside diameter, Toroidal C311CT2-A2 3.54" (90 mm) inside diameter, Toroidal C311CT3-A2 5.9" x 6.7" (150 x 170 mm) rectangular, Split Core C311CT4-A2 3.94" x 13.78" (100 x 350 mm) rectangular, Split Core C311CT5-A2 5.7" (145 mm) inside diameter, Toroidal C311CT6-A2 9.45" (240 mm) inside diameter, Toroidal C311CT7-A2 11.8" x 11.8" (300 x 300 mm) square, Split core C311CT8-A2 1.1" (28 mm) inside diameter, Toroidal C311CT9-A2 2.56" (65 mm) inside diameter, Toroidal C311CT28-A2 1.1 (28 mm) inside diameter, Toroidal with wire leads Zero Sequence Current Transformers with 10,000:1 ratio: C311CT11 C311CT12 C311CT13 C311CT14 C311CT (65mm) inside diameter, Toroidal 5.7" (144mm) inside diameter, Toroidal 9.45" (238mm) inside diameter, Toroidal 3.75" (95mm) inside diameter, Toroidal 7.875" x (200 x 290 mm) rectangular For mounting dimensions and additional information on C311CT current transformers refer to the current Eaton s Cutler-Hammer catalog. The D64PBH13 is designed to operate with special Eaton s Cutler-Hammer C311CT current transformers having a turns ratio of 10,000:1. Each C311CT is epoxy molded for exceptional mechanical properties and has a high-grade silicon iron core for excellent coupling characteristics. C311CTs have built-in back-to-back zeners across the output terminals to provide maximum safety in the event of an open CT secondary circuit. NOTE: 5. TECHNICA SPECIFICATION For Ground Fault elay with programmable output relay and with zone grading option, suitable for use with service protection equipment; refer to D64PBH15, Pub Control voltage Volts Hz AC, 2 VA max V dc, 1 W max Operating tolerance... 55% to 110% of rated ac voltage 80% to 110% of rated dc voltage Maximum System Voltage & Frequency Volts ac, 40 to 200 Hz The D64PBH15 may be applied on higher voltage circuits providing the power conductors are insulated for the system voltage. September, 2009 Page 12

13 Output Circuit breaker: Contacts: Maximum U rating: V ac, resistive EN rating: Vac, Utilization category AC-12 Maximum fusing under EN : A Endurance:...Greater than 10,000 operations Dielectric strength V ac at 60 Hz Configuration... Voltage free form "C" 1 N.O. - 1 N.C. (3 terminals) Operating Mode (Selected on DIPswitch 12)... Non-Failsafe Failsafe Inhibit evel (Enabled - Disabled selected on DIPswitch 11) With C311CT current transformer 500:1 ratio to 100 Amps With C311CT current transformer 10,000:1 ratio to 2000 Amps (Based on selected Trip evel setting) Inhibit Time... Instantaneous Functional Test... Continuous monitoring of the external CT s connection; Open Circuit causes trip ocal Test... Double click Push button on front of relay Causes a G/F trip by voltage injection onto the CT input circuitry emote Test... One press of SPST N.C. momentary contact Push button, 3 10 V ac Causes an external CT Open Circuit trip by opening up the connection to the CT ocal eset...toggle Operated Circuit Breaker eset mode... Manual Ground Fault Circuit: Ground Fault Trip Delay...25 milliseconds Second Setting within ange... DIPswitches on front of relay Zone Grading Backup Delay milliseconds 1.00 Second Setting within ange... DIPswitches on front of relay Ground Fault Trip Current evel Amps (using 500:1 CT) Amps (using 10,000:1 CT) Setting within ange... DIPswitches on front of relay Ground Fault Trip Inhibit Backup Delay... Fixed at 1.2 Second Frequency esponse ange Hz Accuracy: Trip current... ±15% including CT accuracy Trip current epeat... ±1% Trip time... -2/+5 ms or ±2.5% of G/F Trip Delay, whichever is greater 1 1 The ground fault detection mechanism has a thermal behavior for greatly reduced noise sensitivity: the quoted delays are valid for sinusoidal currents exceeding the set point by > 10 times; for reduced current excursions the delay increases as follows: Current = 6 x set point: add 3 ms Current = 4 x set point: add 8 ms Current = 2 x set point: add 20 ms Current = 1.2 x set point: add 60 ms September, 2009 Page 13

14 Current Transformer... either C311CT current transformer with 500:1 ratio or, special C311CT current transformer 10,000:1 ratio Thermal Characteristics when using C311CT current transformer with 500:1 ratio: Short Time Withstand: 1000A... 1 second 2000A second Calculated Short Time Withstand capability when using special C311CT current transformer with 10,000:1 ratio: 10,000 Amps... 3 Seconds 50,000 Amps... 1 second 200,000 Amps Second Environment: Operating Temperature C to +66 C Storage C to +80 C Humidity... 85% (No Condensation) Dimensions: Height (including front cover & terminal block elevation) " (131 mm) Height, Front Cover (not including terminal block elevation) " (125 mm) Width, elay Enclosure (not including front cover) " (70 mm) Width, Front Cover " (95 mm) Depth, elay Enclosure (not including front cover) " (100 mm) Depth (including front cover) " (105 mm) Mounting: Through-the-Door... Mounting hardware by customer DIN rail mm Two Screw... #8 x 3/4" (M4 x 20 mm) Shipping Weight lbs. (1.10 kg) Applicable Standards: EN EN EN EN EN EN EN Electromagnetic compatibility (EMC) - Part 6-3 Generic standards Emission standard for residential, commercial and light-industrial environments (note: = lowest levels): MHz 30 dbµv at 10m distance MHz 37 dbµv at 10m distance Electromagnetic compatibility (EMC) - Part 6-2 Generic standards Immunity standard for industrial environments (note: = highest levels): MHz with 80% AM modulation up to 10 V/m at 3m distance from source Electromagnetic compatibility (EMC) for industrial-process measurement and control equipment Part 4-2: Electrostatic discharge (ESD) immunity Electromagnetic compatibility (EMC) for industrial-process measurement and control equipment Part 4-3: adiated electromagnetic field immunity Electromagnetic compatibility (EMC) for industrial-process measurement and control equipment Part 4-4: Electrical fast transient/burst immunity Electromagnetic compatibility (EMC) for industrial-process measurement and control equipment Part 4-5: Surge immunity Electromagnetic compatibility (EMC) for industrial-process measurement and control equipment Part 4-6: Conducted radio frequency field immunity September, 2009 Page 14

15 EN EN Electromagnetic compatibility (EMC) for industrial-process measurement and control equipment Part 4-11: Voltage dips/drops/variations immunity ow-voltage switchgear and controlgear Part 5-1: Control circuit devices and switching elements Electromechanical control circuit devices U U 1053 Ground-Fault Sensing and elaying Equipment, Class 1 U File E CSA CE C22.2 No. 144-M91 Ground Fault Circuit Interrupters CSA File CE mark Declaration of Conformity September, 2009 Page 15

16 FIGUE 1 - TYPICA FIED CONNECTION GOUNDED SYSTEMS - 1 Phase 2 wire - 1 Phase 3 wire - 3 Phase 3 wire - 3 Phase 4 wire POWE SOUCE CB COI CEAING CONTACT CUENT CAYING NEUTA, WHEN USED ST C311CT Current Transformer 10,000:1 atio CONTO VOTAGE: VAC/DC CONTO POWE: 2 VA/ 1W CONTACT ATING: 3A,250 VAC U ISTED 70BM Cat No. SEE MANUA FO SET-UP AND TEST INSTUCTIONS MADE IN HOAND POD. BATCH Nr. : P23509xxx D64PBH13 SE. B1 EAY CASS 1 CT 2 CBCT GOUND FAUT SENSING CT 1 AND EAYING EQUIPMENT FB EN , EN ;-3;-4;-5;-6;-11, EN ;-3 CONTACTS SHOWN IN OFF/TIPPED POSITION 14 OPEN 12 COSED 11 N VAC/DC + EMOTE TEST OAD - Use shielded twisted leads on interconnection between CT and elay. - The shield should extend the full length of the twisted interconnection leads. - Connect shield to structure ground as close as practically possible to the elay. September, 2009 Page 16

17 V AC/DC PUB FIGUE 2 - DIMENSIONS AND WEIGHTS 2.36" (60) 0.20" (5) 1.38" (35) 0.65" (16.6) 0.30" (7.5) 3.35" (85) DIN ail elease Mounting hole Dia 0.22 (5.5) 3.94" (100) 4.92" (125) D64PBH13 SE.B1 E AY CASS 1 U GOUND FAUT SENSING AND EAYING EQUIPMENT CT 2 ISTED 70BM CT 1 CBCT FB 14 CONTACTS SHOWN IN OFF / TIPPED POSITION 12 CONTACT ATING: 3A,250 VAC 11 N - + SEE MANUA FO SET-UP AND TEST INSTUCTIONS POD. BATCH Nr. : P220 MADE IN HOAND 3.94" (100) 35 mm DIN AI 3.94" (100) 2.76" (70) EA PANE MOUNTING DIN AI O 2 SCEW 0.59" (15) 4.14" (105) IGHT SIDE VIEW 0.30" (7.5) 0.16" (4) 3.15" (80) 0.16" (4) 0.30" (7.5) 2.83" (72) 4.33" (110) DOO CUTOUT 4.01" (102) 4.92" (125) Mounting Hole Dia (4) OPEN WEIGHT: 1.88 BS. (.85KG) PACKAGED WEIGHT: 2.43 BS. (1.10 KG) DIMENSIONS AE IN INCHES (MM IN BACKETS) 3.74" (95) THOUGH-THE-DOO MOUNTING September, 2009 Page 17

18 PUB TABE 1 CICUIT BEAKE TIP CONTACT STATES STATE OF CICUIT BEAKE TIP CONTACTS UNDE VAIOUS OPEATING CONDITIONS WITH DIPSWITCH 12 IN SEECTED POSITIONS OPEATING DIPSWITCH 12 IN EFT POSITION NON-FAISAFE MODE NON-FAISAFE (EFT) DIPSWITCH 12 IN IGHT POSITION FAISAFE MODE FAISAFE (IGHT) CONDITIONS CB TOGGE POSITION CB TOGGE POSITION 1. CONTO POWE OFF TIPPED TIPPED CONTO POWE OFF NOMA NOMA 3. CONTO POWE ON TIPPED TIPPED 4. CONTO POWE ON NOMA NOMA 5. OSS OF CONTO POWE NOMA TOGGE TIPS 6. CONTO POWE ON FAUT CUENT ABOVE TIP SETTING NOMA + Time Delay TIPPED = + Time Delay = + Time Delay NOMA + Time Delay TIPPED = + Time Delay = + Time Delay 7. CONTO POWE ON FAUT STI ON SYSTEM ATTEMPT TO ESET CB TIP FEE TOGGE EMAINS TIPPED TOGGE EMAINS TIPPED 8. CONTO POWE ON FAUT CEAED NO ESET TIPPED TIPPED 9. CONTO POWE ON FAUT CEAED ESET CB TOGGE NOMA NOMA 10. CONTO POWE OFF AFTE GOUND FAUT TIP, NO ESET TIPPED TIPPED 11. CONTO POWE OFF AFTE GOUND FAUT TIP, ESET CB TOGGE NOMA NOMA 12. CONTO POWE ESTOED, FAUT STI ON SYSTEM, ESET CB TOGGE NOMA + Time Delay TIPPED = + Time Delay = + Time Delay NOMA + Time Delay TIPPED = + Time Delay = + Time Delay September, 2009 Page 18

19 PUB FOM 1 - TEST ECOD GOUND FAUT TEST D64PBH13 ESET G/F TEST INTENA Double-clicking the built-in ESET TEST pushbutton invokes a test which switches an AC voltage onto the processor s CT sensor input. The voltage is scaled to simulate a Ground fault current of 1.5 times the G/F trip level set point. The output circuit breaker will trip on G/F after the set delay (plus 0.4 s) and the AC test voltage will be switched off. The red ED will turn on solid. This proves that the internal electronics and output circuit breaker are functioning. Optionally, pressing the reset button again will reset the red ED enabling the green UN ED. eclose the circuit breaker (Normal position). No external power supply is required. Provision is made for external testing if required. efer to Figure 1. Select a momentary contact single pole normally closed pushbutton rated at least 3 Amps at 10 Volts ac. Connect as shown in Figure 1. When pressed the circuit to the external CT is opened. This results in a trip and the red ED will flash four 0.25 s flashes (CT Open Circuit). This proves that the current transformer is connected and the windings are okay, the CT monitor's detection circuit is operating, and the internal electronics and output circuit breaker are functioning. The built-in ESET TEST pushbutton is used to optionally reset the red AST TIP ED in the D64PBH13. The external pushbutton cannot be used to reset the red AST TIP ED. This form provides spaces to record the date the test was performed and the results. Those in charge of the building s electrical installation should retain the form in order to be available to the authority having jurisdiction. Year Jan. Feb. Mar. Apr. May June July Aug. Sept Oct. Nov. Dec. September, 2009 Page 19

Instructions for D64RPB30 Series C1 Ground Fault Relay

Instructions for D64RPB30 Series C1 Ground Fault Relay Instructions for D64RPB30 Series C1 Ground Fault Relay Cat. No. D64RPB30 CT 24-240V AC / DC N.C. N.O. 1 2 3 4 5 6 7 8 ON F2024-01-01 FLASHES: 1 = E/F 2 = S/C 3 = BACKUP 4 = CT 5 = F/S CV LOSS CONT = TRIP

More information

MGFR. the power to protect MGFR. www. ElectricalPartManuals. com. Instruction Manual C-322

MGFR. the power to protect MGFR. www. ElectricalPartManuals. com. Instruction Manual C-322 MGF MGF GOUND Fault ELAY the power to protect Instruction Manual C-322 Ground fault relay GLOSSAY A/D DMT EMF IDMT P.U. MS TCP UPS ZSIP ZSCT Analog to Digital Definite Minimum Time Electro Motive Force

More information

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Dual-Source Power Supply Addendum to I.B. 17555 Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Table of Contents Page 1.0 Introduction...1 2.0 General

More information

Single Phase Soft Starters

Single Phase Soft Starters Submittal Data English Language/IP Units 04/14 Contact Information: Hyper Engineering, Pty. Ltd. 4 / 14 Ralph Black Dr Wollongong Nth, NSW 2500 AUSTRALIA www.hypereng.com sales@hypereng.com (877) 304-0724

More information

8 Input/8 Output AC Block I/O Module

8 Input/8 Output AC Block I/O Module 8 Input/8 Output AC Module Installation Mount the block I/O module in a vertical (recommended) or horizontal position. Allow sufficient room around the block for cooling air flow through the block module.

More information

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand

More information

Type Nominal voltage (V) Code HSV V

Type Nominal voltage (V) Code HSV V Speed control Speed control relay - mm Control of overspeed, underspeed, operating rate, stopping Measurement via discrete sensors - -wire PNP or NPN, Namur, voltage 0-0V or volt-free contact type Works

More information

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC 2CDC 251 048 F0t08 CM-MPS.11 2CDC 251 049 F0t08 CM-MPS.21 Features Monitoring of three-phase mains for phase sequence (can be switched off), phase failure, over- and undervoltage as well as phase unbalance

More information

SECTION AUTOMATIC TRANSFER SWITCH

SECTION AUTOMATIC TRANSFER SWITCH SECTION 26 36 23 PART 1 - GENERAL 1.1 THE REQUIREMENT A. Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, withstand and close-on ratings as shown on the plans.

More information

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks. 2CDC 251 052 F0t08 CM-MPS.23 2CDC 251 053 F0t08 CM-MPS.43 - relay status, timing - fault message - fault message Adjustment of the tripping delay t V Adjustment of the threshold value for overvoltage 6

More information

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase

More information

AMIK Three Phase Digital Panel Meters

AMIK Three Phase Digital Panel Meters AMIK Three Phase Digital Panel Meters USA SICE 1936 ELIAILIT EOD MEASUE Special Features 3 Line 4 Digits ultra bright LED Display (up to 9999) On site Programmable CT/PT atios User selectable CT Secondary

More information

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks. 2CDC 251 054 F0t08 CM-MPN.52 2CDC 251 055 F0t08 CM-MPN.62 2CDC 251 056 F0t08 CM-MPN.72 Features Monitoring of three-phase mains for phase sequence (can be switched off), phase failure, over- and undervoltage

More information

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet CDC 0 F0t07 Features Rated control supply voltage -8 V DC, -0 V AC Single-function timer with star-delta change-over One device includes 7 time ranges (0.0 s - 0 min) n/o contacts LEDs for status indication

More information

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103383_en_00 1 Description PHOENIX CONTACT - 06/2008 Features QUINT POWER power supply units highest system

More information

MODEL SS - DIN-RAIL SPEED SWITCH

MODEL SS - DIN-RAIL SPEED SWITCH MODEL SS - DIN-RAIL SPEED SWITCH! SIMPLE ON-LINE TRIP FREQUENCY SETTING (USING ACTUAL INPUT SIGNAL OR FREQUENCY GENERATOR)! USER SETTABLE TRIP FREQUENCY FROM 0.1 Hz to 25 KHz! OVER-SPEED, UNDER-SPEED,

More information

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks. 2CDC 251 048 F0t08 CM-MPS.11 2CDC 251 049 F0t08 CM-MPS.21 2CDC 251 050 F0t08 CM-MPS.31 2CDC 251 051 F0t08 CM-MPS.41 R/T: yellow LED - relay status, timing F1: red LED - fault message F2: red LED - fault

More information

QUINT-PS/ 1AC/24DC/20

QUINT-PS/ 1AC/24DC/20 Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data sheet 103129_en_04 1 Description PHOENIX CONTACT - 02/2010 Features QUINT POWER power supply units Maximum system

More information

02/11/2015

02/11/2015 Emergency stop and safety guard monitoring 2 channels KNE3-YS Part number 85102436 "Emergency stop" & "Safety gates monitoring" functions Single and 2-channel operation Security with redundancy and feedback

More information

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New) XUA1 AC Voltage and phase balance relay (August 1996) Manual XUA1 (Revision New) Woodward Manual XUA1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

Three-phase monitoring relays

Three-phase monitoring relays 2CDC 251 046 F0t08 Features Monitoring of three-phase mains for phase sequence, phase failure, phase unbalance Threshold value for phase unbalance adjustable as absolute value Tripping delay can be adjusted

More information

CAMTO. Arc detecting relay. system. January Revised August D D1200

CAMTO. Arc detecting relay. system. January Revised August D D1200 NEW ARC DETECTING SYSTEM FROM Based on our experience with arc protection since 1962, has developed a new. The units are built into boxes that all fit on a 35 mm DIN-rail. All front plates are dimensioned

More information

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories 2CDC 251 042 F0t08 CM-PVS.31 Features Monitoring of three-phase mains for phase sequence (can be switched off), phase failure, over- and undervoltage Threshold values for over- and undervoltage are adjustable

More information

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection DATASHEET - ETR4-70-A Delivery program Timing relay, 2W, 0.05s-100h, multi-function, 24-240VAC/DC, potentiometer connection Part no. ETR4-70-A Catalog No. 031888 Eaton Catalog No. XTTR6A100H70B EL-Nummer

More information

24V dc Analog Block I/O Module

24V dc Analog Block I/O Module 24V dc Analog Module Installation Mount the block I/O module in a vertical (recommended) or horizontal position. Allow sufficient room around the block for cooling air flow through the block module. Refer

More information

Installation / Monitoring Technique

Installation / Monitoring Technique Installation / Monitoring Technique VARIMETER RCM Residual Current Monitor, Type B for AC and DC Systems IP 5883 0249633 IP 5883 ND 5018/035 ND 5018/030 According to IEC/EN 62 020, VDE 0663 For AC and

More information

AMIK 200 / 201 Technical Data Sheet

AMIK 200 / 201 Technical Data Sheet AMIK 200 / 201 Technical Data Sheet AMIK Special Features MODBUS (RS-485) Communication available only on Amik 201 On site Programmable CT/PT Ratios User selectable CT Secondary 1A/5A User selectable PT

More information

Electronic timer CT-MFS.21

Electronic timer CT-MFS.21 2CDC 251 053 F0t07 a Rotary switch for the preselection of the time range b Potentiometer with direct reading scale for the fine adjustment of the time delay c Rotary switch for the preselection of the

More information

Overcurrent Protection / 7SJ45

Overcurrent Protection / 7SJ45 Overcurrent Protection / SJ SIPROTEC easy SJ numerical overcurrent protection relay powered by CTs Fig. / Description SIPROTEC easy SJ numerical overcurrent protection relay powered by current transformers

More information

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application

More information

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC DATASHEET - ETR4-51-A Timing relay, star-delta, 50 ms, 1W, 3-60s, 24-240VAC/DC Part no. ETR4-51-A Catalog No. 031884 Eaton Catalog No. XTTR6A60S51B EL-Nummer 0004133308 (Norway) Delivery program Product

More information

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New) XR1 Rotor Earth Fault Relay (May 2007) Manual XR1 (Revision New) Woodward Manual XR1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided

More information

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink Characteristics variable speed drive ATV12-4kW - 5hp - 200..240V - 3ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly

More information

Creating Electrical Designs

Creating Electrical Designs C h a p t e r 2 Creating Electrical Designs In this chapter, we will learn the following to World Class standards: Understanding Control and Power Circuits Drawing the Control Circuit Selecting the Pushbutton

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,

More information

Over or Under Current. Over and Under Current Monitor. Current Transducer. Current Indicator. DIN Rail Mounting Current Monitors

Over or Under Current. Over and Under Current Monitor. Current Transducer. Current Indicator. DIN Rail Mounting Current Monitors Selection Guide...8.2 Over or Under ECS... 8.4 TCS... 8.8 Over and Under Monitor ECSW... 8.6 Transducer TCSA... 8.10 DCSA... 8.12 Indicator LCS... 8.14 LPM... 8.14 DIN Rail Mounting CM-SFS CM-SRS.1 CM-SRS.2

More information

Protective Relays Digitrip 3000

Protective Relays Digitrip 3000 New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer

More information

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area. Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103129_en_01 PHOENIX CONTACT - 05/2008 1 Description QUINT POWER power supply units highest system availability

More information

ATS01N125FT soft starter for asynchronous motor - ATS01-25 A V KW

ATS01N125FT soft starter for asynchronous motor - ATS01-25 A V KW Characteristics soft starter for asynchronous motor - ATS01-25 A - 110..480V - 2.2..11 KW Main Range of product Altistart 01 Product or component type Product destination Product specific application Device

More information

ATS01N112FT soft starter for asynchronous motor - ATS01-12 A V KW

ATS01N112FT soft starter for asynchronous motor - ATS01-12 A V KW Characteristics soft starter for asynchronous motor - ATS01-12 A - 110..480V - 1.5..5.5 KW Main Range of product Altistart 01 Product or component type Product destination Product specific application

More information

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters Table of Contents Page Introduction 1 Description 1 Specifications 2 Installation 3 Calibration 4 General Maintenance

More information

INSTRUCTION LEAFLET IL17553B IQ UNIVERSAL POWER SENTINEL TM INSTALLATION INSTRUCTIONS FOR THE IQ UNIVERSAL POWER SENTINEL TM INTERNAL CT

INSTRUCTION LEAFLET IL17553B IQ UNIVERSAL POWER SENTINEL TM INSTALLATION INSTRUCTIONS FOR THE IQ UNIVERSAL POWER SENTINEL TM INTERNAL CT IQ UNIVERSAL POWER SENTINEL TM INSTALLATION INSTRUCTIONS FOR THE IQ UNIVERSAL POWER SENTINEL TM INTERNAL CT INSTRUCTION LEAFLET IL17553B IL17553B For more information visit: www.cutler-hammer.eaton.com

More information

Supplemental Motor Protection Devices Specifications

Supplemental Motor Protection Devices Specifications Technical Data Supplemental Motor Protection Devices Specifications Bulletin Numbers 809S, 813S, 814S, 817S, 1409, 1410 Topic Bulletin 809S/813S/814S/817S 2 Page Product Line Overview 2 Cat. No. Explanation

More information

1 INTRODUCTION ORDER CODE / INFORMATION

1 INTRODUCTION ORDER CODE / INFORMATION INTRODUCTION ORDER CODE / INFORMATION 269/269Plus * * * * * * 269/269Plus SV D/O.4 ORDER CODE / INFORMATION Motor management relay Standard version Drawout version Phase CT Ground CT (required for D/O

More information

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

ATV12H018F1 variable speed drive ATV kW hp V - 1ph Characteristics variable speed drive ATV12-0.18kW - 0.25hp - 100..120V - 1ph Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component

More information

Supplemental Motor Protection Devices Specifications

Supplemental Motor Protection Devices Specifications Technical Data Supplemental Motor Protection Devices Specifications Bulletin Numbers 809S, 813S, 814S, 817S, 1409, 1410 Topic Page 809S/813S/814S/817 Dedicated Function Motor Protection Relays 2 Product

More information

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C) XR1 Rotor Earth Fault Relay Manual XR1 (Revision C) Woodward Manual XR1 (EN) Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by

More information

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication: Application : RISH Master 3490 SS is a 96mm x 96mm panel mounted kilowatt hour meter it measures active energy with class 1.0 accuracy having auto-resetting 8 digit seven segment LED counter. The unit

More information

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300 Monitoring Technique VARIMETER IMD Insulation monitor RN 5897/300 0274214 Your Advantages For mobile generator sets according to DIN VDE 0100-551 Preventive fire and system protection Detection of symmetric

More information

MODEL IFMA - DIN-RAIL FREQUENCY TO ANALOG CONVERTER

MODEL IFMA - DIN-RAIL FREQUENCY TO ANALOG CONVERTER H MODEL IFMA - DIN-RAIL FREQUENCY TO ANALOG CONVERTER SIMPLE ON-LINE RANGE SETTING (Using Actual Input Signal or Signal Generator) USER SETTABLE FULL SCALE FREQUENCY FROM 1 Hz to 25 KHz FOUR OUTPUT OPERATING

More information

Power Processor - Series 700F 10KVA to 150KVA

Power Processor - Series 700F 10KVA to 150KVA Power Processor - Series 700F 10KVA to 150KVA Power Conditioning and Regulation for Commercial & Industrial Equipment General Specifications PART 1 - GENERAL 1.1 DESCRIPTION This specification defines

More information

RE17RCMU off-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RCMU off-delay timing relay - 1 s..100 h V AC - 1 OC Characteristics off-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC Main Range of product Product or component type Discrete output type Width Device short name Time delay type Time delay range Nominal

More information

Thermistor motor protection relays

Thermistor motor protection relays Thermistor motor protection relays Content Benefits and advantages... / 68 Selection table... / 68 Ordering details CM-MSE... / 69 CM-MSS... / 69 CM-MSN... / 7 PTC sensor C0... / 7 Technical data... /

More information

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

DSA150 Series. xxx Series. 150 Watts.   AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125. 15 Watts xxx Series Ultra Slim Design 15% Peak Load for 3 seconds Ambient Operation from -1 C to +7 C High Efficiency Selectable Overload Characteristic Selectable Remote Inhibit or Enable 3 Year Warranty

More information

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC Main Range of product Product or component type Discrete output type Width Device short name Time delay type Time delay range Nominal

More information

Electronic timer CT-SDS.22

Electronic timer CT-SDS.22 CDC 0 F0t07 Features Rated control supply voltage 8 V DC, 0 V AC Single function timer with star delta change over One device includes 7 time ranges (0.0 s 0 min) n/o contacts LEDs for status indication

More information

RISH Delta Energy / Demand (Multifunction instrument) Data Sheet

RISH Delta Energy / Demand (Multifunction instrument) Data Sheet ISH Delta Energy / Demand (Multifunction instrument) Data Sheet www.rishabh.co.in Page 1 of 6 Version: D 14 / 03 / 2012 Application: ISH Delta Energy measures important electrical parameters in 3 phase

More information

DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays. Model Number Structure

DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays. Model Number Structure New Product News Measuring & Monitoring Relays K8AK/K8DS Series DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays Compact 22.5 mm and 17.5 mm housings Resistant to high-frequency

More information

Electronic timer CT-SDD.22

Electronic timer CT-SDD.22 CDC 099 F0t0 a Rotary switch for the preselection of the time range b Potentiometer with direct reading scale for the fine adjustment of the time delay c U: green LED V control supply voltage applied W

More information

FOUNDATION Fieldbus Junction Box

FOUNDATION Fieldbus Junction Box Installation Instructions FOUNDATION Fieldbus Junction Box Catalog Number 1788-FBJB4R, 1788-FBJB6 Topic Page Important User Information 2 About the Junction Boxes 3 Additional Resources 3 Installation

More information

Electronic Circuit Breaker ESS1 for System SVS1

Electronic Circuit Breaker ESS1 for System SVS1 Electronic Circuit Breaker for System SVS Description The electronic circuit breaker is designed to ensure selective disconnection of individual s in industrial systems which are powered by a DC 24 V switch

More information

Current Loop Interface Module M 2025D

Current Loop Interface Module M 2025D CONTROLS Current Loop Interface Module M 2025D Current-to-Voltage Analog Converter used with the M 2001 Series Digital Tapchanger Control and M-2948 Tap Position Sensors to provide positive tap position

More information

Type 3RW RW40 7. Control electronics Rated values. Terminal. external DC supply (to DIN 19240) through terminals and IN Relay outputs

Type 3RW RW40 7. Control electronics Rated values. Terminal. external DC supply (to DIN 19240) through terminals and IN Relay outputs Function have all the same advantages as the 3RW30/31 soft starters. At the same they come with additional functions and a two-phase control method (Polarity Balancing) that is unique in the rating range

More information

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters Technical Data Sheet Alpha 20 Alpha 20 is a compact multifunction instrument which Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel

More information

Multi-voltage Multi-function. Wiring diagram (without control signal)

Multi-voltage Multi-function. Wiring diagram (without control signal) 80 Modular timers 16 A 80 Multi-function and mono-function timer range 80.01T - Multi-function & multi-voltage 80.11T - On-delay, multi-voltage Complies with EN 45545-2:2013 (protection against fire of

More information

Installation and Operating Instructions. Power IT Power Factor Controller RVC

Installation and Operating Instructions. Power IT Power Factor Controller RVC Installation and Operating Instructions Power IT Power Factor Controller RVC Table of contents Page 1. Read this first... 3 About this Instruction Manual... 3 Safety... 3 Electromagnetic compatibility...

More information

QUINT-PS/ 3AC/24DC/10

QUINT-PS/ 3AC/24DC/10 Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system

More information

Type CP-S, CP-C & CP-A Switch mode

Type CP-S, CP-C & CP-A Switch mode Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting

More information

Electronic Circuit Breaker with reset input ESS20-1..

Electronic Circuit Breaker with reset input ESS20-1.. Electronic Circuit Breaker with reset input ESS0-.. Description The special device ESS0-.. is a further extension of the product line electronic circuit breakers. Type ESS0-.. has a width of only. mm and

More information

Phase control Single function phase control relay - 7.5 mm Control of -phase networks: phase sequence, total phase failure Multi-voltage from x 08 to x 480 V Controls its own supply voltage True RMS measurement

More information

ECM3 EARTH CONTINUITY RELAY

ECM3 EARTH CONTINUITY RELAY TECHNICAL DATASHEET ECM3 EARTH CONTINUITY RELAY Electrical Protection for Hard Rock Mines Application The ECM3 has been designed to provide earth continuity protection for cables containing pilot cores.

More information

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Overcurrent Protection / 7SJ46 SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Function overview Fig. /11 Description The SIPROTEC easy 7SJ46 is a numerical overcurrent protection relay which

More information

Electronic timer CT-TGD.22

Electronic timer CT-TGD.22 2CDC 251 097 F0t06 a Rotary switch for the preselection of the time range of the ON time b Potentiometer with direct reading scale for the fine adjustment of the ON time c Rotary switch for the preselection

More information

Self-Powered Counters H7ET

Self-Powered Counters H7ET Self-Powered Counters Subminiature Time Totalizers Require No External Power Supply Subminiature 8 x 2 mm (1.89 x.9 in) Improved noise immunity Screw terminal and wire-wrap types available Printed circuit

More information

38 Series - Relay interface modules A

38 Series - Relay interface modules A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

AU INSTALLATION INSTRUCTIONS. Revision B1 Rapid City, SD, USA, 02/2010 II_201A-AU_B1

AU INSTALLATION INSTRUCTIONS. Revision B1 Rapid City, SD, USA, 02/2010 II_201A-AU_B1 INSTALLATION INSTRUCTIONS Revision B1 Rapid City, SD, USA, 02/2010 MODELS 201A-AU 201-575-AU II_201A-AU_B1 2880 North Plaza Drive, Rapid City, South Dakota 57702 (800) 843-8848 (605) 348-5580 fax (605)

More information

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian) PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian) 1.0 General This specification covers the electrical characteristics and

More information

38 Series - Relay interface modules A

38 Series - Relay interface modules A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23 and CM-MPS.43

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23 and CM-MPS.43 Data sheet Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23 and CM-MPS.43 The three-phase monitoring relays CM-MPS.x3 monitor the phase parameters phase sequence, phase failure, over- and

More information

P1-04DAL-1 Analog Output

P1-04DAL-1 Analog Output Output Specifications Output Channels Output Range ma Signal Resolution -bit Resolution Value of SB (least significant bit) Data Range 9 counts Output Type Output Value in Fault Mode ess than ma oad Impedance

More information

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING 1.0 General This specification covers the electrical characteristics and general

More information

PHOENIX CONTACT

PHOENIX CONTACT Electronic circuit breaker CLIPLINE Data sheet 102898_en_03 PHOENIX CONTACT 2010-12-17 1 Description The electronic circuit breaker can be used in applications that cover all aspects of the switched-mode

More information

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact Data sheet Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact The CT-TGD.12 is an electronic time relay with the function pulse generator. It is from the CT-D range. With their MDRC profile

More information

QUINT-PS/ 3AC/24DC/40

QUINT-PS/ 3AC/24DC/40 Primary-switched power supply unit with SFB technology, 3 AC, output current 40 A INTERFACE Data sheet 103133_en_00 1 Description PHOENIX CONTACT - 07/2009 Features QUINT POWER power supply units Maximum

More information

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features: (With All Display Parameters) Application : RISH EM 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network

More information

Model Number Structure. Ordering Information. Solid-state Power OFF-delay Timer H3DE-H. Model Number Legend. List of Models

Model Number Structure. Ordering Information. Solid-state Power OFF-delay Timer H3DE-H. Model Number Legend. List of Models Solid-state Power OFF-delay Timer H3DE-H Timers Two delay-time models available. 0.1 to 12 seconds (S Series) 1 to 120 seconds (L Series) Covers wide range of supply voltage. Model Number Structure Model

More information

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC - 1 OC Complementary Contacts material Control type [Us] rated supply voltage Voltage range Main Range of product Product or component

More information

RCMS460 and RCMS490 Series

RCMS460 and RCMS490 Series 4 T M RCMS460 and RCMS490 Series Digital Multi-Channel Ground Fault Monitor / Ground Fault Relay Grounded and High-Resistance Grounded AC/DC Systems Technical Bulletin NAE1042060 / 04.2013 BENDER Inc.

More information

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23 Data sheet Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23 The three-phase monitoring relay CM-MPS.23 monitors the phase parameters phase sequence, phase failure, over- and undervoltage

More information

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol Product datasheet Characteristics ATV12HU22M2 Complementary Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component name Variable

More information

OPERATING MANUAL SERIES R B F BRUSHLESS RACK SYSTEM

OPERATING MANUAL SERIES R B F BRUSHLESS RACK SYSTEM OPERATING MANUAL SERIES R B F BRUSHLESS RACK SYSTEM Version 3.0 (European version 1.3) This is a general manual describing a series of racks receiving Servo Amplifiers having output capability suitable

More information

XP2-R Power and Reverse Power Relay

XP2-R Power and Reverse Power Relay XP2-R Power and Reverse Power Relay Manual XP2-R (Revision C) Woodward Manual XP2-RE Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward

More information

RE17LLBM asymmetrical flashing relay s V AC - solid state output

RE17LLBM asymmetrical flashing relay s V AC - solid state output Characteristics asymmetrical flashing relay - 0.1..1 s - 24..240 V AC - solid state output Product availability : Non-Stock - Not normally stocked in distribution facility Price* : 75.00 USD Main Range

More information

Electronic Circuit Breaker ESS1 for System SVS1

Electronic Circuit Breaker ESS1 for System SVS1 Electronic Circuit Breaker for System SVS Description The electronic circuit breaker is designed to ensure selective disconnection of individual s in industrial systems which are powered by a DC 24 V switch

More information

User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters

User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters Table of Contents Page Introduction 1 Description 1 Specifications 2 Installation 3 Calibration 4 General Maintenance

More information

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6. 38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information

20 - Arc Guard Systems

20 - Arc Guard Systems Arc Guard Index Arc Guard - Arc Guard Arc Guard...1 -.14 Selection Arc Guard System, description...6...2...2 Description,...1 Description,...1 Description, with detectors...4 Description,...5 Detectors

More information

08/07/2015

08/07/2015 17.5 mm - 1 Solid State Relay 0.7A MUS2 Part number 88827004 Multi-function or mono-function Multi-range Multi-voltage Screw or spring terminals LED status indicator (relay version) Possibility of external

More information

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding

More information