PLC communication on Egypt s LV grid for AMR

Size: px
Start display at page:

Download "PLC communication on Egypt s LV grid for AMR"

Transcription

1 PLC communication on Egypt s LV grid for AMR by A Helmy, M Abdel Rahman and MM Mansour, Ain Shams University, Electrical energy consumers are demanding better customer service, higher power quality, higher energy measurement accuracy and more timely data. Utility companies all over the world are being forced to find solutions giving greater information on the population s power consumption. The automatic meter reading system (AMR) is one of the ways in which utilities are go-getting to achieve these goals. Power lines are one of the communication mediums used in the AMR system. However, power lines are a hostile communication environment. This paper describes a prototype for AMR system using power lines showing performance and reliability tests. The measurements are carried out on a sample of Egypt s low voltage network. Considerable savings can be achieved by the utility companies by removing the need for a visual inspection of the meter at each billing term. The process is labor intensive, time consuming and prone to human error. A study shows that on average a meter reader achieves an information rate of only around 1 bps [1], which is highly inefficient in terms of modern standards. AMR also reduces the problems and costs associated with reading meters at hard to access locations. Additional significant cost savings can be achieved by identifying the tampering of meters These can be detected because most of these AMR systems offer bi-directional communications, which allows the current meter data to be checked against the historical data for any suspicious divergence. Several communication technologies are currently in use to achieve automated meter reading. Radio, telephone lines and power lines are the most used mediums where each system has its own advantages and disadvantages. This paper focuses on power line communication (PLC) and its performance as a channel for AMR system, statistical analysis and suggestions for reliable communication is presented. AMR system structure The main parts of an AMR system as shown in Fig. 1 are: Meter interface unit (MIU): Each meter at the consumer side is fit with an interface unit which acts as a transceiver for meter data on the low voltage power lines using a single phase power line modem (PLM). Data concentrator unit (DCU): The data sent by the MIU is received by the data concentrator unit located at the distribution transformer. DCU is fit with three phase PLM receiving data from all meters on different phases. Utility central unit (UCU): The data received by the DCU is then transmitted to the utility central unit. The communication link in this case may be PSTN, RF, GSM or Ethernet which is out of the paper scope. As mentioned before the communication links either between the MIUs and their DCU or between the DCUs and the UCU are bi-directional links. PLC benefits, challenges and regulations Benefits Fig. 1: AMR system structure. By using existing cable infrastructure PLC system eliminates the need for installation and maintenance of dedicated communication links. Already every building or household is connected to the electrical power grid and moreover; every room has power line contact points installed. Without doubt the extent of this existing infrastructure cannot be matched by any other telecommunication technologies that are available today. The challenge As the electric power distribution lines were not originally designed for communication purposes as a result they exhibit highly variable and unpredictable levels of channel noise, signal attenuation and distortion [8]. Standards and regulations Fig. 2: Frequency bands for CENELEC EN standard. There are many established standards that provide regulations on the operating specifications of PLC systems. Federal Communications Commission (FCC) and European Committee for Electro-technical Standardization (CENELEC) govern regulatory rules in North America and Europe respectively. For Europe the energize - November Page 13

2 regulations concerning low voltage signaling are described in CENELEC standard EN In part 1 of this EN-standardization paper the allowed frequency band and the output voltage for communication is indicated [2]. The frequency range allowed for communication is subdivided into five sub bands as shown in Fig. 2 ranges from 3 khz to 148,5 khz, with transmitted power not more than 500 mw. Frequency ranges between 9 95 khz, which is allocated for electrical utility use for applications such as AMR and load management; there is no need for access protocol when operating in this band. The rest of the frequency range ,5 khz comprises of the B, C, and D frequency bands and is reserved for end-user applications. Focus on PLC challenges Noise and disturbances Common causes of noise on the high voltage electrical power networks include corona discharge, power factor correction banks and circuit breaker operation. On the low voltage network, much of this noise is filtered by distribution transformers, so the most common interference in low voltage domestic networks can be attributed to the various household devices and office equipment connected to the network. Noise on the low voltage network is classified to [1], [4]: Noise having line components synchronous with power system frequency: The usual source of this noise are Triacs or silicon controlled rectifiers (SCRs), found domestically, for example, in light dimmers or photocopiers. Noise with a smooth spectrum: caused by universal motors that can be found in a lot of household appliances such as blenders and vacuum cleaners. Single event impulse noise: usually caused due to switching events as closing of contacts. Non synchronous noise: Is characterised by periodic components that occur at frequencies other than harmonics of the mains frequency. Major sources of this noise are televisions and computer monitors. Fluctuated channel impedance Unfortunately, a uniform distributed line is not a suitable model for PLC, since the power line has a number of loads of differing impedances connected in parallel to it for variable amounts of time. It can be seen that the channel impedance is a strongly fluctuating variable that is hard to predict. Signal attenuation Reference [3] states that the attenuation between homes in the U K ranges from 15 db to 25 db per 100 m, for the frequency range khz. The corresponding value for homes in Zurich, Switzerland, was in the range 3 13 db. In [3] analysis of signal attenuation is introduced giving some factors affecting signal attenuation as time dependency where there is a strong day and night sensitivity. Communication system Noise, fluctuated channel impedance, signal attenuation and distortion are big challenges facing selecting an efficient communication system to insure reliable data transmission through this hostile environment. However, remote meter reading and load control are examples of PLC applications with rather low demands on the communication system. This type of applications has two important characteristics: firstly, the amount of information that is transferred is small, and therefore the information bit rate (in bit/second or bps) is low. Secondly, they do not have high real time demands therefore a relatively large communication delay is acceptable. These two characteristics make it easier to establish reliable communication over the power line than other PLC high speed and real time demand applications. Many researchers and investigators have been performing important works to select a proper modulation technique, frequency shift keying (FSK) and spread spectrum (SS) are the most commercially applicable by Echelon, Intellon, ST, Itran, Phillips, Archnet the most famous PLM producers. Spread Spectrum uses wide band, noise-like signals. Because Spread Spectrum signals are noise-like, they are hard to detect. Spread Spectrum signals are also hard to Intercept or demodulate. Further, Spread Spectrum signals are harder to jam than narrowband signals. These low probability of intercept anti-jam and high noise immunity features [6] are why the military has used Spread Spectrum for so many years and it s widely used now commercially in PLC systems. Proposed system configuration The proposed system shown in Fig. 3 consists of: Master controller Unit (MCU) Remote controller Units (RCU) Laptop The main aim of this prototype to have a point-to-point system where the MCU (acting as DCU) will communicate with RCU (acting as energy meter) connected to the same phase at different distances from the The overall impedance of a low voltage network as discussed in [1] and [5] results from three main sources, impedance of the distribution transformer, characteristic impedance of cables and impedance of the devices connected to the network. Various measurements and tests were done to evaluate the impedance of the low voltage network, in [7] the CENELEC A-band maximum absolute impedances are reported increasing from 20 Ω at 20 khz to 80 Ω at 100 khz. Mean values increase from 5 Ω to 17 Ω. Clearly, channel impedance is very low. This presents significant challenges when designing a coupling network for PLC communications. Maximum power transfer theory states that the transmitter, receiver and the channel impedance must be matched for maximum power transfer. With strongly varying channel impedance, this is very difficult. Fig. 3: Proposed system for PLC testing. energize - November Page 14

3 MCU. All data transactions on the same phase are recorded with date and time stamp where various performance and reliability tests are carried out to examine the power line channel as a communication medium for the AMR system. Master control unit (MCU) MCU is shown in Fig. 4 where it mainly consists of a single phase PLM from Archnet [10] communicating with a Laptop through RS232 serial port.the Archnet PLM ATL is based on the direct sequence spectrum (DSSS) and it provides bi-directional half duplex data communication over the low voltage grid at baud rate 300 bps and it complies with CENELEC standard EN A band. Thus, the data could be transferred in bidirectionally between the Laptop and the power lines. Fig. 4 shows the MCU prototype. Remote control unit (RCU) RCU is shown in Fig. 5 where it consists as MCU of PLM communicating serially (RS232) with a microcontroller which is responsible for performing all the calculations required for electrical power quantities measurements besides receiving and sending data from and to PLM. Thus, the data could be transferred in bi-directionally between the microcontroller and the power lines. Fig. 5 shows the RCU prototype. The microcontroller is PIC18F258 from microchip [9] fit with 10 bit analog to digital converter (ADC) required for accurate current and voltage signals sampling, serial port required for interfacing with PLM, high internal bus speed up to 10 MHz and other many advanced features. Laptop The laptop computer is responsible for: firstly, sending control signals to all RCUs or one of them. Secondly, receiving and storing all data transactions with date and time stamp for analyses. Communication datagram As the system designed and constructed is still in the prototyping stage, the communication datagram used in the power line communication was designed initially without any concern for data security and improving data reliability the main aim is to find out the performance of the proposed system in the hostile environment. The data request packet is designed for the purpose of collecting meter readings. MCU sends out this packet to ask all RCU within the network for meter readings at a certain interval. All RCUs respond to this by sending back a data send packet to the source, which contains the information requested. Fig. 4: MCU structure diagram and prototype. For simplicity the data request packet sent by MCU to all RCU is one byte which is the ASCII value of letter t (stands for transmission request).while the data send packet sent by each RCU is 16 bytes with the first two bytes representing the RCU ID which is unique ID for each RCU and stored on the microcontroller. The other 14 bytes are the data reading requested of the specified RCU. Performance and reliability site tests Test method The MCU and a single RCU is communicating on the same phase at a distance 50 m apart. Tests are done at a dense residential area in Cairo the capital of Egypt. The tests involves putting the system under hard test continuously for three weeks where the laptop is programmed to send the data request packet every 60 s and waits for the data send packet sent back from the RCU. The laptop stores all the transactions done either transmitted or received this data is then checked for accuracy of response data request packet/day (1 packet/min) were sent and the results were reported for three weeks. Test objectives The site tests focused on three main objectives: Fig. 5: RCU structure diagram and prototype. Report the general performance of PLC for a medium distance (50 m) Report the best day of the week and the best hour of the day for AMR system data collection Report the influence of large number of TV sets loading the power lines where some results are reported during the African cup of nations for football (Egypt ACN 2006) which reported a large number of spectators (especially for the Egyptian team matches). energize - November Page 15

4 Test results The results are based on the accurate packets received by the MCU from the RCU. If an inaccurate packet is received by the MCU, a checksum error will be reported. However, if the MCU does not receive any reply from the RCU after a certain allocated time, a timeout error is reported. Both the checksum and timeout constitute the failure of the proposed system. Test results are collected and subdivided to: Test results based on a day of the week: samples of these results are shown in Table 1. Test results based on the same day of the week: where results from 1 are averaged for the same day of the week for the whole three weeks as shown in Table 2. Test results based on the hour of the day: Fig. 6 shows histogram samples of these results. Observations Fri 17/2/06 Sat 18/2/06 Sun 19/2/06 Mon 20/2/06 Tue 21/2/06 Wed 22/2/06 Thu 23/2/06 trials CS TO Failure ,7 17, ,7 23, ,7 28, ,3 31, ,1 17,9 Table 1: Day of the week reliability results. Based on the results obtained, the observations lie in the following areas: Reliability: As shown in Table 1 successful attempts in any day do not exceed 91 Timeout: High timeout (TO) error is noted while checksum (CS) is so rare compared to the timeout error forming a total failure percentage up to 35 and increase to 49 under heavy loading conditions Correlation with day of the week: As shown in Table 2 the average successful attempts vary from 67 to 83 depending on the day of the week. Best average results are reported on Thursdays and Saturdays. However, worst results are reported on Sundays and Wednesdays. Fig. 6b and Fig. 6c show a histogram samples for PLC performance on Sunday and Thursday respectively Correlation with time of day: The histogram of the first week of the tests reports very high failure percentage up to 100 on the hours where there is a match for Egypt football team in the ACN 2006 due to very high loading effects by TV sets, this is noted on Tuesday 7 February 2006 from 19h00 to 21h00 and Friday 10 February 2006 from 18h00 to 21h00. Fig. 6a: The histogram of the other two weeks reports very high failure rates up to 100 on the hours of the day between 11h00 to 17h00 and high successful rates up to 100 on the hours between 01h00 to 09h00 as shown in Fig. 6b and Fig. 6c. Suggestions All performance and reliability tests show fluctuating results varying with time. Thus, to overcome this we suggest the following: Initiate communication at specific times, Thursdays and Saturdays between 03h00 am to 09h00 are reported the best results. Avoid times which record high TV sets audience density. Using repeaters to reduce the timeout and one of the error correction methods to reduce the checksum. trials CS TO Failure Mon ,2 25,8 Tue ,1 25,9 Wed ,1 30,9 Thu ,5 16,5 Fri Sat ,5 18,5 Sun ,8 32,2 Table 2: Same day of the week reliability results. energize - November Page 16

5 Conclusion The power lines are a hostile environment for communication with channel parameters highly fluctuating with time. Thus, a special care about choosing the right time for data transmission must be considered by the utility central unit to acquire the meters readings through the AMR system. In spite of the satisfactory performance of the prototype system, there is still work to be carried out. It would be useful to examine the reasons for timeout error and also to determine the actual cause of all the. Error correction should be added to the system in future to increase the reliability of the system and to prevent tampering. Acknowledgement This paper was presented at the IEEE PES Power Africa 2007 conference and exhibition in Johannesburg, and in republished with persmission. References [1] H.C Ferreira, H.M Grove, O. Hooijen, Power Line Communications: An Overview IEEE AFRICON 4th, Vol. 2, Sept. 1996, pp [2] J. Newbury, Communication requirements and standards for low voltage mains signaling IEEE Transaction on Power Delivery, Vol. 13, No.1, January 1998, pp [3] D. Cooper, T. Jeans Narrowband, low data rate communications on the low-voltage mains in the CENELEC frequencies. I. Noise and attenuation IEEE Transaction on Power Delivery, Vol. 17, No. 3, July 2002 [4] R.M Vines, H.J Trussel, L.J Gale and J.B O Neal, Noise on residential power distribution circuits IEEE Transactions on Electromagnetic Compatibility, Vol. EMC-26, No.4, Nov 1984, pp [5] R.M Vines, H.J Trussel, K.S Shuey and J.B O Neal, Impedance of the residential power distribution circuit IEEE Transactions on Electromagnetic Compatibility, Vol. EMC-27, No.1, Feb 1985, pp [6] G. Marubayashi, S. Tachikawa: Spread spectrum transmission on residential power line Spread Spectrum Techniques and Applications Proceedings, IEEE 4th International Symposium on Vol. 3, Sept. 1996, pp [7] J. A. Malack and J. R. Engstrom, RF Impedance of United States and European Power Lines, IEEE Transactions on Electromagnetic Compatibility, vol. EMC-18, no. 1, February 1976, pp [8] Echelon Corporation, A Power Line Communication Tutorial Challenges and Technologies [9] Microchip Corporation, PIC18F258 Datasheet Available: microchip.com Fig. 6: PLC performance histogram. [10] Archnet Corporation, Embedded Power Line Modem ATL and ATL Manual v energize - November Page 17

sensors ISSN

sensors ISSN Sensors,, 7-; DOI: 1.9/s17 Article OPEN ACCESS sensors ISSN 1- www.mdpi.com/journal/sensors Measurements of Impedance and Attenuation at CENELEC Bands for Power Line Communications Systems I. Hakki Cavdar

More information

Home & Building Automation. parte 2

Home & Building Automation. parte 2 Home & Building Automation parte 2 Corso di reti per l automazione industriale Prof. Orazio Mirabella Technologies for Home automation Main distribution 230V TP (Twisted Pair) Socket Lighting Sun blinds

More information

High Frequency Measurements and their Applications in Distribution Network. Contents. Power Line Communication. Background.

High Frequency Measurements and their Applications in Distribution Network. Contents. Power Line Communication. Background. 1 Contents 2 High Frequency Measurements and their Applications in Distribution Network Bashir Ahmed Siddiqui Tampere University of Technology, bashir.siddiqui@tut.fi 29 March 2012 Background Power Line

More information

Characteristics of In-building Power Lines at High Frequencies and their Channel Capacity

Characteristics of In-building Power Lines at High Frequencies and their Channel Capacity Characteristics of In-building Power Lines at High Frequencies and their Channel Capacity T. Esmailian~ F. R. Kschischang, and P. G. Gulak Department of Electrical and Computer Engineering University of

More information

Statistical Model Study for Narrowband Power Line Communication Noises

Statistical Model Study for Narrowband Power Line Communication Noises Statistical Model Study for Narrowband Power Line Communication Noises Mehmet Ali Sonmez 1, Mustafa Bagriyanik 2 1 Istanbul Technical University, Istanbul, Turkey masonmez@itu.edu.tr 2 Istanbul Technical

More information

Power Line Communication Technology Update

Power Line Communication Technology Update Power Line Communication Technology Update By Walter Downey and Phil Sutterlin Echelon Corporation 415 Oakmead Parkway Sunnyvale, CA 9486 1-888-ECHELON (888-324-3566) www.echelon.com 1 Power Line Communications

More information

THE HIGH SPEED POWER LINE COMMUNICATION SOLUTION. Features

THE HIGH SPEED POWER LINE COMMUNICATION SOLUTION. Features THE HIGH SPEED POWER LINE COMMUNICATION SOLUTION Overview SM2200 is a next generation OFDMA (Orthogonal Frequency Division Multiple Access) power line communication transceiver designed for networking

More information

Metering glossary. Article Specific Number, a Landis+Gyr internal number used for production management. It can be referred to for successive orders.

Metering glossary. Article Specific Number, a Landis+Gyr internal number used for production management. It can be referred to for successive orders. Metering glossary A A advantis AM AMI AMR AMS ASN В Billing cycle С Class COSEM CS CS Active Energy Advanced metering system catering for the special needs of the liberalized energy markets. It is a complete

More information

M.Sinduja,S.Ranjitha. Department of Electrical & Electronics Engineering, Bharathiyar Institute of Engineering For Women, Deviyakurichi.

M.Sinduja,S.Ranjitha. Department of Electrical & Electronics Engineering, Bharathiyar Institute of Engineering For Women, Deviyakurichi. POWER LINE CARRIER COMMUNICATION FOR DISTRIBUTION AUTOMATION SYSTEM M.Sinduja,S.Ranjitha Department of Electrical & Electronics Engineering, Bharathiyar Institute of Engineering For Women, Deviyakurichi.

More information

GC9838-LR - INTELLIGENT HYBRID PLC-RF DIN RAIL MODEM

GC9838-LR - INTELLIGENT HYBRID PLC-RF DIN RAIL MODEM GC9838-LR - INTELLIGENT HYBRID PLC-RF DIN RAIL MODEM and a built-in sub-ghz wireless module to allow adaptive networking over different media. The wireless connectivity can be available in LoRa for tree-structure

More information

AUTOMATIC ELECTRICITY METER READING AND REPORTING SYSTEM

AUTOMATIC ELECTRICITY METER READING AND REPORTING SYSTEM AUTOMATIC ELECTRICITY METER READING AND REPORTING SYSTEM Faris Shahin, Lina Dajani, Belal Sababha King Abdullah II Faculty of Engineeing, Princess Sumaya University for Technology, Amman 11941, Jordan

More information

USB Port Medium Power Wireless Module SV653

USB Port Medium Power Wireless Module SV653 USB Port Medium Power Wireless Module SV653 Description SV653 is a high-power USB interface integrated wireless data transmission module, using high-performance Silicon Lab Si4432 RF chip. Low receiver

More information

Automated E-Billing and Supply Control using Power Line Communication

Automated E-Billing and Supply Control using Power Line Communication Automated E-Billing and Supply Control using Power Line Communication Vishal Salunke 1, Datta Barsale 2, Rushikesh Kashid 3 Jagadeesh Hallur 4 123 Student, Dept of E&TC, DYPSOET, Maharashtra, India 4 Asst.

More information

DATA COMMUNICATION THROUGH SPREAD SPECTRUM TECHNOLOGY ON POWER LINES

DATA COMMUNICATION THROUGH SPREAD SPECTRUM TECHNOLOGY ON POWER LINES 1.0 2.3 3.5 4.8 6.1 7.4 8.6 9.9 11.2 12.5 13.7 15.0 16.3 17.6 18.8 20.1 21.4 22.7 23.9 25.2 26.5 27.8 29.0 Noise Level (dbv) Latest Trends in Information Technology DATA COMMUNICATION THROUGH SPREAD SPECTRUM

More information

EMC and Variable Speed Drives

EMC and Variable Speed Drives EMC stands for electromagnetic compatibility the ability of electric and electronic devices to work properly in the environment for which they are designed. For this purpose the environment is defined

More information

Low Power with Long Range RF Module DATASHEET Description

Low Power with Long Range RF Module DATASHEET Description Wireless-Tag WT-900M Low Power with Long Range RF Module DATASHEET Description WT-900M is a highly integrated low-power half-'duplex RF transceiver module embedding high-speed low-power MCU and high-performance

More information

ZigBee Propagation Testing

ZigBee Propagation Testing ZigBee Propagation Testing EDF Energy Ember December 3 rd 2010 Contents 1. Introduction... 3 1.1 Purpose... 3 2. Test Plan... 4 2.1 Location... 4 2.2 Test Point Selection... 4 2.3 Equipment... 5 3 Results...

More information

RF7129 Ultra-low power Tranceiver module V2.0

RF7129 Ultra-low power Tranceiver module V2.0 1. General RF7129 series is a low cost, ultra-low power, high performance transparent two way semi-duplex GFSK transceiver with operation at 433/470/868/915 Mhz. It integrates with high speed MCU from

More information

Potential Impacts of khz Harmonic Emissions on Smart Grid Communications in the United States

Potential Impacts of khz Harmonic Emissions on Smart Grid Communications in the United States Potential Impacts of 9-150 khz Harmonic Emissions on Smart Grid Communications in the United States Maria Arechavaleta, S. Mark Halpin, Adam Birchfield, Wendy Pittman, W. Eric Griffin, Michael Mitchell

More information

RF ISM Transparent Transceiver Module V4.0

RF ISM Transparent Transceiver Module V4.0 RF7020-27 ISM Transparent Transceiver Module V4.0 Overview: RF7020-27 is highly integrated semi-duplex medium power transceiver module with high speed MCU and high performance RF IC. Utilizing high efficiency

More information

White Paper. Optical-based Analog Front End for Low -Speed Powerline Communications In The Home

White Paper. Optical-based Analog Front End for Low -Speed Powerline Communications In The Home Optical-based Analog Front End for Low -Speed Powerline Communications In The Home White Paper The use of high-voltage power lines to carry voice signals has a history dating back to the early 1920s, with

More information

10 Mb/s Single Twisted Pair Ethernet Noise Environment for PHY Proposal Evaluation Steffen Graber Pepperl+Fuchs

10 Mb/s Single Twisted Pair Ethernet Noise Environment for PHY Proposal Evaluation Steffen Graber Pepperl+Fuchs 10 Mb/s Single Twisted Pair Ethernet Noise Environment for PHY Proposal Evaluation Steffen Graber Pepperl+Fuchs IEEE P802.3cg 10 Mb/s Single Twisted Pair Ethernet Task Force 3/13/2017 1 Content Noise in

More information

RF1276 Long Distance Transceiver module V2.0

RF1276 Long Distance Transceiver module V2.0 1. General RF1276 series is a low cost, ultra-low power, high performance transparent two way semi-duplex LoRa modulation transceiver with operation at 169/433/868/915 Mhz. It integrates with high speed

More information

WIRELESS RF TRANSCEIVER FOR ENERGY METER READING SYSTEM

WIRELESS RF TRANSCEIVER FOR ENERGY METER READING SYSTEM International Journal of Advanced Research in Engineering ISSN: 2394-2819 Technology & Sciences Email:editor@ijarets.org May-2016 Volume 3, Issue-5 www.ijarets.org WIRELESS RF TRANSCEIVER FOR ENERGY METER

More information

POWER LINE COMMUNICATION. A dissertation submitted. to Istanbul Arel University in partial. fulfillment of the requirements for the.

POWER LINE COMMUNICATION. A dissertation submitted. to Istanbul Arel University in partial. fulfillment of the requirements for the. POWER LINE COMMUNICATION A dissertation submitted to Istanbul Arel University in partial fulfillment of the requirements for the Bachelor's Degree Submitted by Egemen Recep Çalışkan 2013 Title in all caps

More information

10 Mb/s Single Twisted Pair Ethernet Noise Environment for PHY Proposal Evaluation Steffen Graber Pepperl+Fuchs

10 Mb/s Single Twisted Pair Ethernet Noise Environment for PHY Proposal Evaluation Steffen Graber Pepperl+Fuchs 10 Mb/s Single Twisted Pair Ethernet Noise Environment for PHY Proposal Evaluation Steffen Graber Pepperl+Fuchs IEEE P802.3cg 10 Mb/s Single Twisted Pair Ethernet Task Force 3/7/2017 1 Content Noise in

More information

Frequently Asked Questions ConnexRF Products

Frequently Asked Questions ConnexRF Products ConnexRF Products Version 1.1 PKLR2400S-200A PKLR2400S-10 LX2400S-3A LX2400S-10 13256 W. 98 TH STREET LENEXA, KS 66215 (800) 492-2320 www.aerocomm.com wireless@aerocomm.com DOCUMENT INFORMATION Copyright

More information

DIGITAL DATA TRANSMISSION USING LOW VOLTAGE POWER LINE Zbigniew Mantorski Ph.D. Andrzej Sitko B.Sc.

DIGITAL DATA TRANSMISSION USING LOW VOLTAGE POWER LINE Zbigniew Mantorski Ph.D. Andrzej Sitko B.Sc. IEA ECBCS, Annex45 3 rd Expert Meeting DIGITAL DATA TRANSMISSION USING LOW VOLTAGE POWER LINE Zbigniew Mantorski Ph.D. Andrzej Sitko B.Sc. e-mail: zbigniew.mantorski@polsl.pl a.sitko@poczta.fm Innsbruck,

More information

Passive, Transformerless Coupling Circuitry for Narrow-Band Power-Line Communications

Passive, Transformerless Coupling Circuitry for Narrow-Band Power-Line Communications Passive, Transformerless Coupling Circuitry for Narrow-Band Power-Line Communications Mloyiswa P. Sibanda, Petrus A. Janse van Rensburg, and Hendrik C. Ferreira Department of Electrical Engineering Department

More information

Embedded Radio Data Transceiver SV611

Embedded Radio Data Transceiver SV611 Embedded Radio Data Transceiver SV611 Description SV611 is highly integrated, multi-ports radio data transceiver module. It adopts high performance Silicon Lab Si4432 RF chip. Si4432 has low reception

More information

KNX Powerline PL 110. KNX Association

KNX Powerline PL 110. KNX Association KNX Powerline PL 110 Table of Contents 1 Introduction...3 2 Standardisation...3 3 Transmission Process...4 3.1 Phase Coupling...5 3.2 Telegram Transmission...6 3.2.1 Training Sequence...6 3.2.2 Preamble

More information

Project 32: Optimal Topology Discovery for Automatic Meter Reading Using Powerline Carrier

Project 32: Optimal Topology Discovery for Automatic Meter Reading Using Powerline Carrier Department of Electrical & Electronic Engineering Part 4 Project 2003 Project 32: Optimal Topology Discovery for Automatic Meter Reading Using Powerline Carrier Project Supervisor: Dr. Gerard Rowe Second

More information

POWER LINE COMMUNICATION (PLC) OVERVIEW

POWER LINE COMMUNICATION (PLC) OVERVIEW National Scientific Session of the Academy of Romanin Scientists ISSN 2067-2160 Spring 2009 113 POWER LINE COMMUNICATION (PLC) OVERVIEW Alexandru-Ionut CHIUŢA 1, Cristina STANCU 2 Abstract Power line Communications

More information

SV613 USB Interface Wireless Module SV613

SV613 USB Interface Wireless Module SV613 USB Interface Wireless Module SV613 1. Description SV613 is highly-integrated RF module, which adopts high performance Si4432 from Silicon Labs. It comes with USB Interface. SV613 has high sensitivity

More information

SERIES K: PROTECTION AGAINST INTERFERENCE

SERIES K: PROTECTION AGAINST INTERFERENCE International Telecommunication Union ITU-T K.49 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (12/2005) SERIES K: PROTECTION AGAINST INTERFERENCE Test requirements and performance criteria for voice

More information

Attenuation Characteristics of High Rate Home-Networking PLC Signals

Attenuation Characteristics of High Rate Home-Networking PLC Signals IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 4, OCTOBER 2002 945 Attenuation Characteristics of High Rate Home-Networking PLC Signals Charles J. Kim, Member, IEEE, and Mohamed F. Chouikha, Member,

More information

OFDM the 3 rd generation of narrowband Power Line Communications

OFDM the 3 rd generation of narrowband Power Line Communications OFDM the 3 rd generation of narrowband Power Line Communications 4 th Annual European Utilities Intelligent Metering Barcelona, May 2008 About ADD GRUP ADD GRUP history: 1992 ADD was founded as a high

More information

An Optical Version of WIFI for Indoor Application

An Optical Version of WIFI for Indoor Application I J C T A, 9(15), 2016, pp. 8267-8274 International Science Press An Optical Version of WIFI for Indoor Application P.M. Joel* and S.T. Aarthy** ABSTRACT Visible Light Communication is an efficient bidirectional

More information

Evaluation of Code Division Multiplexing on Power Line Communication

Evaluation of Code Division Multiplexing on Power Line Communication Evaluation of Code Division Multiplexing on Power Line Communication Adriano Favaro and Eduardo Parente Ribeiro Department of Electrical Engineering, Federal University of Parana CP 90, CEP 853-970 - Curitiba,

More information

Power Line Communication Based Fault Monitoring And Control

Power Line Communication Based Fault Monitoring And Control Power Line Communication Based Fault Monitoring And Control Rutika Sanjay Abhang rutikaabhang5@gmail.com Archana Dattatraya Dighe Student of Electrical Engineering achanadighe59@gmail.com Dhanshri Arun

More information

LITERATURE REVIEW & ANALYSIS OF WIRELESS ENERGY METER

LITERATURE REVIEW & ANALYSIS OF WIRELESS ENERGY METER LITERATURE REVIEW & ANALYSIS OF WIRELESS ENERGY METER Saurabh S. Karmakar 1, Shubham V. Gedam 2, Harshal W. Nagpure 3, Amit Yadav 4, Ganesh S. Thote 5 UG Student, Department of Electrical Engineering,

More information

REMOTE METER READING OVER POWER DISTRIBUTION LINES.

REMOTE METER READING OVER POWER DISTRIBUTION LINES. REMOTE METER READING OVER POWER DISTRIBUTION LINES. K. Gamage, A. Ranaweera, J. P. Karunadasa, D. Dias* Department of Electrical Engineering, University of Moratuwa *Department of Electronic & Telecommunication

More information

Research on Development & Key Technology of PLC

Research on Development & Key Technology of PLC Research on Development & Key Technology of PLC Jie Chen a, Li Wang b College of Electronic Engineering, Chongqing University of Posts and Telecommunications, Chongqing 400065, China; avircochen@foxmail.com,

More information

Power quality Harmonics up to 40th harmonic Unbalance, rotary field indication Distortion factor THD-U / THD-I

Power quality Harmonics up to 40th harmonic Unbalance, rotary field indication Distortion factor THD-U / THD-I Harmonics Temperature input Measurement accuracy 0.5 Memory 4 MByte UMG 104 Energy measurement device for DIN rails Communication Profibus (DP / V0 optional) Modbus RTU Power quality Harmonics up to 40th

More information

SERIES G: TRANSMISSION SYSTEMS AND MEDIA, DIGITAL SYSTEMS AND NETWORKS Access networks In premises networks

SERIES G: TRANSMISSION SYSTEMS AND MEDIA, DIGITAL SYSTEMS AND NETWORKS Access networks In premises networks I n t e r n a t i o n a l T e l e c o m m u n i c a t i o n U n i o n ITU-T G.9901 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (06/2017) SERIES G: TRANSMISSION SYSTEMS AND MEDIA, DIGITAL SYSTEMS AND

More information

TSA 6000 System Features Summary

TSA 6000 System Features Summary 2006-03-01 1. TSA 6000 Introduction... 2 1.1 TSA 6000 Overview... 2 1.2 TSA 6000 Base System... 2 1.3 TSA 6000 Software Options... 2 1.4 TSA 6000 Hardware Options... 2 2. TSA 6000 Hardware... 3 2.1 Signal

More information

Wireless Communications

Wireless Communications 2. Physical Layer DIN/CTC/UEM 2018 Periodic Signal Periodic signal: repeats itself in time, that is g(t) = g(t + T ) in which T (given in seconds [s]) is the period of the signal g(t) The number of cycles

More information

Pico 900MHz 1W FHSS Module Model: p900 FCC ID: NS913P900. Applicant:

Pico 900MHz 1W FHSS Module Model: p900 FCC ID: NS913P900. Applicant: Pico 900MHz 1W FHSS Module Model: p900 Applicant: Microhard Systems Inc. 150 Country Hills Landing NW Calgary, Alberta Canada T3K 5P3 In Accordance With Federal Communications Commission (FCC) Part 15,

More information

2 GHz Licence-exempt Personal Communications Service Devices (LE-PCS)

2 GHz Licence-exempt Personal Communications Service Devices (LE-PCS) RSS-213 Issue 2 December 2005 Spectrum Management and Telecommunications Radio Standards Specification 2 GHz Licence-exempt Personal Communications Service Devices (LE-PCS) Aussi disponible en français

More information

Wideband Channel Measurements and Modeling for In-House Power Line Communication

Wideband Channel Measurements and Modeling for In-House Power Line Communication Wideband Channel Measurements and Modeling for In-House Power Line Communication Yong-Hwa Kim, Hak-Hoon Song, Jong-Ho Lee, Seong-Cheol Kim School of Electrical Engineering and Computer Science, Seoul National

More information

Optimum use of frequency thanks to reliable forecasts in planning

Optimum use of frequency thanks to reliable forecasts in planning BROADCASTING Coverage measurement systems FMTV Optimum use of frequency thanks to reliable forecasts in planning New sites for FM and TV broadcasting are planned with the aid of special software that predicts

More information

Data Communication (CS601)

Data Communication (CS601) Data Communication (CS601) MOST LATEST (2012) PAPERS For MID Term (ZUBAIR AKBAR KHAN) Page 1 Q. Suppose a famous Telecomm company AT&T is using AMI encoding standard for its digital telephone services,

More information

Standardization on Home NW in ITU-T T SG15

Standardization on Home NW in ITU-T T SG15 S2-1. Standardization on Home NW in ITU-T T SG15 March 7, 2011 NTT Advanced Technology Corp. Yoshihiro Kondo Copyright 2010 NTT Advanced Technology Corporation Outline Overview of Home NW in Q4/SG15 G.hn

More information

AT-XTR-7020A-4. Multi-Channel Micro Embedded Transceiver Module. Features. Typical Applications

AT-XTR-7020A-4. Multi-Channel Micro Embedded Transceiver Module. Features. Typical Applications AT-XTR-7020A-4 Multi-Channel Micro Embedded Transceiver Module The AT-XTR-7020A-4 radio data transceiver represents a simple and economical solution to wireless data communications. The employment of an

More information

PDL Base. Radio Modem User's Guide. Revision 0.2 (preliminary) May 1999 Copyright 1999 Pacific Crest Corporation Document M00522

PDL Base. Radio Modem User's Guide. Revision 0.2 (preliminary) May 1999 Copyright 1999 Pacific Crest Corporation Document M00522 i PDL Base Radio Modem User's Guide Revision 0.2 (preliminary) May 1999 Copyright 1999 Pacific Crest Corporation Document M00522 Pacific Crest Corporation 990 Richard Avenue, Suite 110 Santa Clara, CA

More information

Home Automation, Inc. Omnistat2. RC-1000 and RC-2000 Communicating Thermostat. Serial Protocol Description

Home Automation, Inc. Omnistat2. RC-1000 and RC-2000 Communicating Thermostat. Serial Protocol Description Home Automation, Inc. Omnistat2 RC-1000 and RC-2000 Communicating Thermostat Serial Protocol Description This document contains the intellectual property of Home Automation, Inc. (HAI). HAI authorizes

More information

OEM PRODUCTS WIRELESS WORLD LOCAL SOLUTION

OEM PRODUCTS WIRELESS WORLD LOCAL SOLUTION OEM PRODUCTS 2008 www.satel.com 2 M3 The M3 is a small and light-weight radio modem designed for integration into the user s terminal equipment. The modem and transceiver are enclosed in a steel or aluminium

More information

Lecture 9: Spread Spectrum Modulation Techniques

Lecture 9: Spread Spectrum Modulation Techniques Lecture 9: Spread Spectrum Modulation Techniques Spread spectrum (SS) modulation techniques employ a transmission bandwidth which is several orders of magnitude greater than the minimum required bandwidth

More information

ANALYSIS OF POSSIBILITIES FOR DIGITAL DATA TRANSFER USING POWERLINE

ANALYSIS OF POSSIBILITIES FOR DIGITAL DATA TRANSFER USING POWERLINE ANALYSIS OF POSSIBILITIES FOR DIGITAL DATA TRANSFER USING POWERLINE Stefan Jordanov Ovcharov, Peter Ivanov Yakimov, Nikolay Todorov Tuliev, Emiliya Georgieva Balkanska, Dobromir Georgiev Penev Department

More information

ROM/UDF CPU I/O I/O I/O RAM

ROM/UDF CPU I/O I/O I/O RAM DATA BUSSES INTRODUCTION The avionics systems on aircraft frequently contain general purpose computer components which perform certain processing functions, then relay this information to other systems.

More information

EE 304 TELECOMMUNICATIONs ESSENTIALS HOMEWORK QUESTIONS AND ANSWERS

EE 304 TELECOMMUNICATIONs ESSENTIALS HOMEWORK QUESTIONS AND ANSWERS Homework Question 1 EE 304 TELECOMMUNICATIONs ESSENTIALS HOMEWORK QUESTIONS AND ANSWERS Allocated channel bandwidth for commercial TV is 6 MHz. a. Find the maximum number of analog voice channels that

More information

WIRELESS THREE PHASE LINE FAULT MONITORING

WIRELESS THREE PHASE LINE FAULT MONITORING WIRELESS THREE PHASE LINE FAULT MONITORING Vaishnavi Kailas Pardeshi 1, Pooja Anil Kawade 2, Rutuja Ratanakar Kshirsagar 3 1,2,3 Department Electrical Engineer, Sandip Polytechnic, Nashik Maharashtra (India)

More information

A RELIABLE AND ECONOMICALLY FEASIBLE AUTOMATIC METER READING SYSTEM USING POWER LINE DISTRIBUTION NETWORK

A RELIABLE AND ECONOMICALLY FEASIBLE AUTOMATIC METER READING SYSTEM USING POWER LINE DISTRIBUTION NETWORK A RELIABLE AND ECONOMICALLY FEASIBLE AUTOMATIC METER READING SYSTEM USING POWER LINE DISTRIBUTION NETWORK M. Moghavvemi, S.Y. Tan and S. K. Wong Department of Electrical Engineering, University of Malaya,

More information

DISCONTINUED. Modulation Type Number of RF Channels 15

DISCONTINUED. Modulation Type Number of RF Channels 15 RFM Products are now Murata products. 2.4 GHz Spread Spectrum Transceiver Module Small Size, Light Weight, Built-In Antenna Sleep Current less than 3 µa FCC, Canadian IC and ETSI Certified for Unlicensed

More information

Multiple Access System

Multiple Access System Multiple Access System TDMA and FDMA require a degree of coordination among users: FDMA users cannot transmit on the same frequency and TDMA users can transmit on the same frequency but not at the same

More information

Len Schaller Prepayment (Smart Payment) Technology Manager, South Africa

Len Schaller Prepayment (Smart Payment) Technology Manager, South Africa Len Schaller Prepayment (Smart Payment) Technology Manager, South Africa PLC Technology in Metering: Challenges of and Solutions to Communicating into the customer home Agenda 1. What is split metering?

More information

The Framework of the Integrated Power Line and Visible Light Communication Systems

The Framework of the Integrated Power Line and Visible Light Communication Systems The Framework of the Integrated Line and Visible Light Communication Systems Jian Song 1, 2, Wenbo Ding 1, Fang Yang 1, 2, Hongming Zhang 1, 2, Kewu Peng 1, 2, Changyong Pan 1, 2, Jun Wang 1, 2, and Jintao

More information

National Voluntary Laboratory Accreditation Program

National Voluntary Laboratory Accreditation Program National Voluntary Laboratory Accreditation Program SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 Compatible Electronics, Inc. 114 Olinda Drive Brea, CA 92823 Mr. Jeff Klinger Phone: 714-579-0500 Fax: 714-579-1850

More information

RF1212 RF1212 Ultra-low Power ISM Transceiver Module V2.0

RF1212 RF1212 Ultra-low Power ISM Transceiver Module V2.0 RF1212 Ultra-low Power ISM Transceiver Module V2.0 Application: Features: Home automation Security alarm Telemetry Automatic meter reading Contactless access Wireless data logger Remote motor control Wireless

More information

CPSC Network Programming. How do computers really communicate?

CPSC Network Programming.   How do computers really communicate? CPSC 360 - Network Programming Data Transmission Michele Weigle Department of Computer Science Clemson University mweigle@cs.clemson.edu February 11, 2005 http://www.cs.clemson.edu/~mweigle/courses/cpsc360

More information

Serial Communications RS232, RS485, RS422

Serial Communications RS232, RS485, RS422 Technical Brief AN236 Technical Brief AN236Rev A Serial Communications RS232, RS485, RS422 By John Sonnenberg S u m m a r y Electronic communications is all about interlinking circuits (processors or other

More information

Our system solutions for consumption data recording. Flexible compatible variable

Our system solutions for consumption data recording. Flexible compatible variable Our system solutions for consumption data recording. Fleible compatible variable Innovation rooted in tradition. The QUNDIS Group The systematic QUNDIS principle. Consumption metering from a single source

More information

XBee Series 2 OEM RF Module Model No.: XBEE2 FCC ID: OUR-XBEE2. Applicant: MaxStream, Inc. 355 South 520 West Suite 180 Lindon, UT 84042

XBee Series 2 OEM RF Module Model No.: XBEE2 FCC ID: OUR-XBEE2. Applicant: MaxStream, Inc. 355 South 520 West Suite 180 Lindon, UT 84042 XBee Series 2 OEM RF Module Model No.: XBEE2 Applicant: MaxStream, Inc. 355 South 520 West Suite 180 Lindon, UT 84042 In Accordance With Federal Communications Commission (FCC) Part 15, Subpart C, Section

More information

INTRODUCTION TO CONDUCTED EMISSION

INTRODUCTION TO CONDUCTED EMISSION IEEE EMC Chapter - Hong Kong Section EMC Seminar Series - All about EMC Testing and Measurement Seminar 2 INTRODUCTION TO CONDUCTED EMISSION By Duncan FUNG 18 April 2015 TOPICS TO BE COVERED Background

More information

Power Line Carrier Communication Based Data Transmission for Tele-Operation of Devices

Power Line Carrier Communication Based Data Transmission for Tele-Operation of Devices Power Line Carrier Communication Based Data Transmission for Tele-Operation of Devices 1 Sundari.B, 2 Nandhini.N, 3 Agila.G 1 Assistant Professor, Dept of ECE, Jayam College of Engg & Technology, Tamilnadu,

More information

Design And Application Of A Control System For DC Motors Over Power Line

Design And Application Of A Control System For DC Motors Over Power Line Design And Application Of A Control System For DC Motors Over Power Line Alperen Mustafa Colak Electronic and Communication Engineering Cankaya University Ankara, Turkey alperenmustafacolak@gmail.com Ilhan

More information

Basic Communications Theory Chapter 2

Basic Communications Theory Chapter 2 TEMPEST Engineering and Hardware Design Dr. Bruce C. Gabrielson, NCE 1998 Basic Communications Theory Chapter 2 Communicating Information Communications occurs when information is transmitted or sent between

More information

Chapter 3. Data Transmission

Chapter 3. Data Transmission Chapter 3 Data Transmission Reading Materials Data and Computer Communications, William Stallings Terminology (1) Transmitter Receiver Medium Guided medium (e.g. twisted pair, optical fiber) Unguided medium

More information

TECHNICAL REQUIREMENTS FOR ELECTROMAGNETIC DISTURBANCE EMITTED FROM TELECOMMUNICATIONS EQUIPMENT

TECHNICAL REQUIREMENTS FOR ELECTROMAGNETIC DISTURBANCE EMITTED FROM TELECOMMUNICATIONS EQUIPMENT TECHNICAL REQUIREMENTS FOR ELECTROMAGNETIC DISTURBANCE EMITTED FROM TELECOMMUNICATIONS EQUIPMENT TR NO.550004 Edition 4.1 1st, April, 2015 Nippon Telegraph and Telephone Corporation Nippon Telegraph and

More information

Lecture 3 Concepts for the Data Communications and Computer Interconnection

Lecture 3 Concepts for the Data Communications and Computer Interconnection Lecture 3 Concepts for the Data Communications and Computer Interconnection Aim: overview of existing methods and techniques Terms used: -Data entities conveying meaning (of information) -Signals data

More information

X10 PROTOCOL FOR DATA COMMUNICATION

X10 PROTOCOL FOR DATA COMMUNICATION International Journal of Recent Innovation in Engineering and Research Scientific Journal Impact Factor - 3.605 by SJIF e- ISSN: 2456 2084 X10 PROTOCOL FOR DATA COMMUNICATION Tilottama Dhake 1, AntrikshGhaskatta

More information

CL4790 USER GUIDE VERSION 3.0. Americas: Europe: Hong Kong:

CL4790 USER GUIDE VERSION 3.0. Americas: Europe: Hong Kong: CL4790 USER GUIDE VERSION 3.0 Americas: +1-800-492-2320 FCC Notice WARNING: This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may

More information

Utility Communications Teleprotection Equipment TPT-200

Utility Communications Teleprotection Equipment TPT-200 Utility Communications Teleprotection Equipment TPT-200 5C Communications Inc. All rights reserved Teleprotection is designed to transfer protection commands coming, in most cases, from distance protection

More information

KLEA 220P ENERGY ANALYZER

KLEA 220P ENERGY ANALYZER KLEA 220P ENERGY ANALYZER Defining KLEA 220P Energy Analyzer in simple terms KLEA 220P Energy Analyzer is an automation device which offers 3-phase energy monitoring, analyzing and controlling the network

More information

WirelessUSB LS Radio Module FCC Testing & Verification - AN4006

WirelessUSB LS Radio Module FCC Testing & Verification - AN4006 WirelessUSB LS Radio Module FCC Testing & Verification - AN4006 Introduction One of the bottlenecks that many product developers encounter in incorporating any radio communication device is facing the

More information

Trio Q. Licensed UHF Ethernet and Serial data radio. QB450 Full Duplex

Trio Q. Licensed UHF Ethernet and Serial data radio. QB450 Full Duplex Trio Q Licensed UHF Ethernet and Serial data radio QB450 Full Duplex 1 Trio Q Data Radios are advanced, high-speed licensed digital data radios, providing both Ethernet and serial communications for complex

More information

The Effects of Triplen Harmonic Distortion and Other Electrical Stresses on an INSTEON Power Line Communications Networks

The Effects of Triplen Harmonic Distortion and Other Electrical Stresses on an INSTEON Power Line Communications Networks The Effects of Triplen Harmonic Distortion and Other Electrical Stresses on an INSTEON Power Line Communications Networks By: Anthony E., Advisor Dr. Gang Feng April 2006 Abstract In recent years, power

More information

BIODEX MULTI- JOINT SYSTEM

BIODEX MULTI- JOINT SYSTEM BIODEX MULTI- JOINT SYSTEM CONFORMANCE TO STANDARDS 850-000, 840-000, 852-000 FN: 18-139 5/18 Contact information Manufactured by: Biodex Medical Systems, Inc. 20 Ramsey Road, Shirley, New York, 11967-4704

More information

Wireless Reading of Sensirion Sensors By H. Moholdt

Wireless Reading of Sensirion Sensors By H. Moholdt Wireless Reading of Sensirion Sensors By H. Moholdt Abstract By using an off-the-shelf RF module, wireless reading of pressure-, humidity- and temperature can be achieved with a very limited design effort.

More information

Ave output power ANT 1(dBm) Ave output power ANT 2 (dbm)

Ave output power ANT 1(dBm) Ave output power ANT 2 (dbm) Page 41 of 103 9.6. Test Result The test was performed with 802.11b Channel Frequency (MHz) power ANT 1(dBm) power ANT 2 (dbm) power ANT 1(mW) power ANT 2 (mw) Limits dbm / W Low 2412 7.20 7.37 5.248 5.458

More information

Characteristics of Low Voltage Distribution Networks in the European. and FCC united Band and its Channel Capacity

Characteristics of Low Voltage Distribution Networks in the European. and FCC united Band and its Channel Capacity Characteristics of Low Voltage Distribution Networks in the European and FCC united Band and its Channel Capacity Guo Jingbo, Li Gang, Wang Zanji Department of Electrical Engineering, Tsinghua University

More information

A Study of Conducted-Emission Stable Source Applied to the EMC US and EU Standards

A Study of Conducted-Emission Stable Source Applied to the EMC US and EU Standards Fourth LACCEI International Latin American and Caribbean Conference for Engineering and Technology (LACCEI 2006) Breaking Frontiers and Barriers in Engineering: Education, Research and Practice, 21-23

More information

Wireless technologies Test systems

Wireless technologies Test systems Wireless technologies Test systems 8 Test systems for V2X communications Future automated vehicles will be wirelessly networked with their environment and will therefore be able to preventively respond

More information

SPECIAL SPECIFICATION 6744 Spread Spectrum Radio

SPECIAL SPECIFICATION 6744 Spread Spectrum Radio 2004 Specifications CSJ 0924-06-244 SPECIAL SPECIFICATION 6744 Spread Spectrum Radio 1. Description. Furnish and install spread spectrum radio system. 2. Materials. Supply complete manufacturer specifications

More information

Wireless Transmission Rab Nawaz Jadoon

Wireless Transmission Rab Nawaz Jadoon Wireless Transmission Rab Nawaz Jadoon DCS Assistant Professor COMSATS IIT, Abbottabad Pakistan COMSATS Institute of Information Technology Mobile Communication Frequency Spectrum Note: The figure shows

More information

900 MHz. Frequency Hopping RS-485 Master/Slave auto-sensing radio interface.

900 MHz. Frequency Hopping RS-485 Master/Slave auto-sensing radio interface. MDR210A-485 900 MHz. Frequency Hopping RS-485 Master/Slave auto-sensing radio interface. Black Box Corporation Lawrence, PA - http://www.blackbox.com - Ph 877-877-BBOX - Fax 724-746-0746 Table of Contents

More information

Introduction to Telecommunications and Computer Engineering Unit 3: Communications Systems & Signals

Introduction to Telecommunications and Computer Engineering Unit 3: Communications Systems & Signals Introduction to Telecommunications and Computer Engineering Unit 3: Communications Systems & Signals Syedur Rahman Lecturer, CSE Department North South University syedur.rahman@wolfson.oxon.org Acknowledgements

More information

Performance Improvement of Wireless Communications Using Frequency Hopping Spread Spectrum

Performance Improvement of Wireless Communications Using Frequency Hopping Spread Spectrum Int. J. Communications, Network and System Sciences, 010, 3, 805-810 doi:10.436/ijcns.010.310108 Published Online October 010 (http://www.scirp.org/journal/ijcns) Performance Improvement of Wireless Communications

More information

IMPLEMENTATION OF EMBEDDED SYSTEM FOR INDUSTRIAL AUTOMATION

IMPLEMENTATION OF EMBEDDED SYSTEM FOR INDUSTRIAL AUTOMATION IMPLEMENTATION OF EMBEDDED SYSTEM FOR INDUSTRIAL AUTOMATION 1 Mr. Kamble Santosh Ashok, 2 Mr.V.Naga Mahesh 1 M.Tech Student, 2 Astt.Prof. 1 Ece - Embedded System, 1 Scient Institute Of Technology, Ibrahimpatnam,

More information

SWT 3000 Teleprotection technical data siemens.com

SWT 3000 Teleprotection technical data siemens.com Power network telecommunication SWT 3000 Teleprotection technical data siemens.com Sustainable success for high-voltage power networks The SWT 3000 Teleprotection system has been the first choice for reliable

More information