1 214 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 1, JANUARY 2011 Overhead Lines Lightning Protection by Multi-Chamber Arresters and Insulator-Arresters Georgij V. Podporkin, Senior Member, IEEE, Evgeniy Yu Enkin, Evgeniy S. Kalakutsky, Vladimir E. Pilshikov, and Alexander D. Sivaev Abstract Reported are results of research and development of multi-chamber arresters and insulators that combine characteristics of insulators and arresters. The devices permit to protect overhead power lines rated at 3 to 35 kv and above against induced overvoltages and direct lightning strokes without using shield wire. Index Terms Insulators-arresters, lightning protection, multichamber arresters, overhead power lines, power arc. I. INTRODUCTION L IGHTNING protection of overhead lines by multiple sparkover gaps has a long history. For example, gear-type arresters (those with multiple parallel gaps) were developed in 1886 for protection of a 2-kV telegraph system [1]; several series gaps installed at overhead power line poles were suggested in [2], etc. The main problem of these solutions was their limited quenching ability. They were found to be inefficient at high values of power follow current. A unique device comprising metal pads laid over the surface of a wooden pole or crossarm, a so-called Darverter [3] did improve the quenching ability owing to gas generating properties of wood but its application area was limited to overhead lines with wooden crossarms or poles. Multigap systems are successfully used in combination with a series nonlinear resistor in well-known silica carbide (SiC) arresters [4] for the protection of substation equipment; however, because these gapped arresters cannot withstand direct lightning strokes, they are not as suitable for lightning protection of overhead lines. Multigap systems are also used as diverters on fiberglass radomes (protective housings for aircraft radar antennae) [5]. Long flashover arresters with a multielectrode system based on the creeping discharge effect were proposed in [6]. While they can be used for lightning protection of medium-voltage (MV) overhead lines, their fairly large dimensions make them unsuitable for high-voltage (HV) applications. Over recent years, the authors of this paper have been active in developing arresters with a multichamber system (MCS), succeeding in the production of new 10- to 35-kV arresters as well as a novel device called a multichamber insulator arrester Manuscript received April 05, 2010; revised June 13, 2010; accepted July 19, Date of publication October 28, 2010; date of current version December 27, Paper no. TPWRD The authors are with the Streamer Research and Production Company, St. Petersburg , Russia ( georgij.podporkin@streamer.ru). Color versions of one or more of the figures in this paper are available online at Digital Object Identifier /TPWRD (MCIA), which combines the properties and functions of the arrester and insulator. The application of MCIAs makes it possible to ensure lightning protection of overhead lines of any voltage ratings: the higher the line voltage is, the larger the number of units in a string and, thus, the higher the rated voltage and the arc-quenching capacity are of a string of insulator arresters. Various designs of insulators with arrester properties are possible. An MCIA is generally a production glass, porcelain, or composite insulator fitted with an MCS. The installation of an MCS confers arrester properties to the insulator without any deterioration of its insulating capacity. For this reason, the application of MCIA on overhead lines makes shield wire redundant, while the height, weight, and cost of poles or towers goes down. At a lower overall cost and with better lightning performance, this line features a noticeably reduced number of lightning failures, cuts damage from the undersupply of energy, and lowers maintenance costs. MCIAs hold much promise in the protection of railway overhead contact systems against direct lightning strokes (DLS). A. MCS Principle II. MULTICHAMBER SYSTEM (MCS) The base of multichamber arresters (MCA), including MCIA, is the MCS shown in Fig. 1. It comprises a large number of electrodes mounted in a length of silicon rubber. Holes drilled between the electrodes and going through the length act as miniature gas discharge chambers. When a lightning overvoltage impulse is applied to the arrester, it breaks down gaps between electrodes. Discharges between electrodes occur inside chambers of a very small volume; the resulting high pressure drives spark discharge channels between electrodes to the surface of the insulating body and, hence, outside into the air around the arrester. A blow-out action and an elongation of interelectrode channels lead to an increase of the total resistance of all channels (i.e., that of the arrester), which limits the lightning overvoltage impulse current. B. Experimental Samples, Test Facility and Test Procedure A large number of MCAs featuring different shapes of steel electrodes were tested (see Fig. 1), including 8-mm-diameter and 2 mm-thick washers; 10-mm-long and 2-, 3-, and 4-mm diameter pieces of steel rods, and 10-mm diameter balls. Intermediate electrodes were spaced 0.5 to 2 mm apart. The diameter of chamber openings varied from 2 to 5 mm, while the chambers were 1 to 5 mm deep. The most interesting results /$ IEEE

2 PODPORKIN et al.: OVERHEAD LINES LIGHTNING PROTECTION BY MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS 215 Fig. 1. Multichamber system (MCS): (a) Diagram showing the discharge onset instant. (b) Diagram showing the discharge end instant. (c) Tests of MCS helically wound around 50-mm diameter cable: 1) silicon rubber length, 2) electrodes, 3) arc quenching chamber, and 4) discharge channel. Fig. 2. Circuit diagram of test facility. C = 700 F; L = 14 mh; L = 2.7 mh; R = ; L = 0.2 mh; C = 50 nf; R = 0.01 ); C = 1000 pf; C 1000 nf(c =C 1000), R = }, C =0:5 F. were obtained for the MCA with ball-shaped intermediate electrodes; for this reason, a bulk of findings is reported further for this MCA design. In order to determine the follow-up current quenching efficiency of MCS, use was made of a test setup including a 50-Hz oscillator and a high-voltage lightning impulse generator. The circuit diagram of the test facility is shown in Fig. 2. To make the test MCS operate, a 250-kV output impulse generator was connected to the arrester across the resistance. The alternating voltage was generated by a capacitance-inductance oscillatory circuit with an oscillation frequency close to 50 Hz. Energy was first stored in a 700- F capacitor bank at. The power frequency voltage was ensured by the oscillatory circuit, by operation of the arrester actuated by the overvoltage impulse from the impulse generator. The test MCS was connected to the 50-Hz oscillator across the resistor and the reactor. The reactor was used to disconnect the capacitor from the MCS at the instant of arc quenching at voltage recovery frequencies. The resistor simulated resistance in the arrester circuit on the line, for instance, the pole footing resistance. Tests were carried out for two values of and 10. The value 0 corresponds to a case of direct lightning stroke to an overhead line and to phase-to phase short circuit (see Fig. 12), while 10 corresponds to the indirect lightning stroke (i.e., to induced overvoltages and flashover of arresters installed at different poles and different phases at an overhead line of MV) (e.g., 10 kv). The voltage recovery frequency was set by the coil and the capacitor. The design voltage recovery frequency was set at 50 khz for a 60- impedance of the circuit MCS,,. MCS current and voltage were measured and recorded with the help of the capacitance voltage divider, the current shunt resistor, connecting cables, and a digital memory oscilloscope. The test procedure was as follows: first, the capacitor bank and the impulse generator were charged; operation of the impulse generator led to the breakdown of the test MCS and the auxiliary arrester. Thus, a lightning overvoltage impulse and the ac voltage were applied to test the MCS simultaneously. As the lightning overvoltage impulse ends, only the power frequency voltage remains applied to the arrester. Voltage and current oscillograms were recorded during the tests (see Fig. 3). Fig. 3(b) also presents additional computer oscilloscope patterns of arc dynamic resistance obtained by dividing the digital oscilloscope pattern of voltage by the oscilloscope pattern of current. Studies have shown that spark discharge quenching can take place in two instances: 1) when the instantaneous value of lightning overvoltage impulse drops to a level equal to or larger than the instantaneous value of power frequency voltage (i.e., the lightning overvoltage current gets extinguished with no follow current in the grid (this type of discharge quenching is further referred to as impulse quenching [see Fig. 3(a)] and 2) when 50-Hz follow current crosses zero (this type of discharge quenching is further referred to as zero quenching [see Fig. 3(b)]. The most common test procedure was as follows. First, the capacitor bank was charged to a certain level corresponding to the grid voltage crest value [see Fig. 3(a)]. The aforementioned procedure was further used throughout the test, and the resulting voltage and current oscilloscope patterns served as the basis for recording quenching or non-quenching findings. In the quenching case, the voltage was raised to the next step (generally 1 kv) and the test was continued until the non-quenching stage. Further, after non-quenching, the voltage was lowered by a half-step (generally by 0.5

3 216 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 1, JANUARY 2011 Fig. 4. Oscilloscope patterns for MCS with different electrode numbers m: 1 50; 2 100; It was shown by the tests that quenching occurs in impulse at low values of but in zero as increases. Fig. 3. Voltage, current, and resistance oscillograms in power follow current quenching tests of MCS m =100: (a) Impulse quenching. (b) Zero quenching t 0 application of ac voltage and lightning impulse, t 0 quenching of lightning impulse, and t 0 quenching of power follow current. kv) and the test was repeated. The highest value of was assumed to be the final quenching crest value of grid voltage. In case of impulse quenching [Fig. 3(a)], the respective effective phase voltage of the grid is found as. In the zero quenching case, is, where is the crest voltage of the second half-cycle. C. Test Results Of interest is the fact that at impulse quenching [Fig. 3(a)] and at zero quenching Fig. 3(b)], voltage does not get chopped to zero, as occurs in standard rod-plane and rod-rod gaps, and considerable residual voltage exists. At zero quenching, this residual voltage is a voltage drop in the arc channel, while at impulse quenching, it is a voltage drop in the spark discharge channel. Fig. 4 shows oscilloscope patterns obtained for various numbers of MCA electrodes; Fig. 5 displays the minimum residual voltage on the arrester versus the number of electrodes at positive and negative polarities of the applied voltage impulse. The tests were carried out for three resistance values of the series-connected generator ( 100, 200, and 700 ). As shown in Fig. 5, the residual voltage grows linearly with the increase of the number of MCS chambers and virtually does not depend on ; in other words, does not depend on the impulse current over a range from 0.4 to 3 ka, characteristic of induced overvoltages. Fig. 6 presents the voltage current characteristic for an MCS with 40 obtained from Fig. 3(b). The characteristic is seen to be highly nonlinear, exhibiting a fairly sharp arc voltage drop. With current varying from 1000 A to 2500 A, residual voltage remains near constant at 2.6 kv. As seen from Fig. 5, the minimum residual voltage Ures increases linearly with the number of chambers m. For 100, Ures is around 6.5 kv; for a larger number of m (e.g., 1000), Ures would be about 65 kv. It means that power follow current will be sufficiently limited, with arc quenching becoming more efficient. Fig. 7 shows the experimental values of grid voltage in which follow current is quenched versus the number of MCS chambers. The data of Fig. 7 make it possible to estimate the necessary number of MCS channels for the arresters of different voltage classes. MCSs underwent electrodynamic stability tests using 4/10 mcs 65 and 100 ka (max) current impulses. MCS prototypes withstood five exposures to 65-kA impulses or two exposures

4 PODPORKIN et al.: OVERHEAD LINES LIGHTNING PROTECTION BY MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS 217 Fig. 7. Follow current-quenching grid voltage versus the number of MCS chambers: 1) impulse quenching (instantaneous value) ; 2) zero quenching at R = 0 (effective value) ; 3) zero quenching at R =10(effective value). Fig. 5. Minimum residual voltage versus the number of MCS electrodes: 1 U at impulse quenching at different generator resistances R : 0100 ; ; ; 2 U at zero quenching and R = 0. Fig. 6. Voltage current characteristic of of MCS m = 40 [obtained from Fig. 3(b)]. Fig. 8. The 10-kV multichamber arrester MCA-10-I for protection against induced overvoltages. to 100-kA impulses, which proves that MCSs can withstand an electrodynamic impact at DLS. III. MULTICHAMBER ARRESTERS (MCAS) A. MCA kv The principal components of a kV MCA (see Figs. 8 and 9) are an MCS, a fiberglass bearing rod, and an assembly for securing arresters to insulator pins. Arresters are mounted on insulator pins with air gaps of 3 to 6 cm between the top ends of the arresters and the conductor. A lightning overvoltage first breaks down the air spark gap, followed by the arrester s MCS, which ensures the extinction of follow current as described in Section II. Fig. 8 shows an arrester with 20 gas discharge chambers intended for the protection of 10-kV overhead lines (12 kv max.) against induced overvoltages. One piece of this model is installed on each phase-interlacing pole (Fig. 10). In this case, the path of ac follow currents that are associated with lightning overvoltage induced multiphase includes the tower-grounding resistance circuits. Thanks to an extra resistance of the pole grounding circuit, follow currents are made lower, which raises the quenching efficiency of the arrester. For principal performance data, see Table I. Shown in Fig. 9 is an arrester with 40 gas discharge chambers (see Table I). It can be used on 10-kV overhead lines for DLS protection and on 20-kV (24 kv max.) lines to fight induced overvoltages. In the latter case, the aforementioned 10-kV procedure has proved practical, with one arrester installed on each phase-interlacing pole (Fig. 11). A direct lightning stroke on a kv medium-voltage (MV) line causes a flashover of insulators of all three phases on one or several poles. To warrant reliable DLS protection,

5 218 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 1, JANUARY 2011 TABLE I ARRESTER PERFORMANCE DATA Fig. 9. Multichamber arresters for DLS protection of 10-kV lines and induced overvoltage protection of 20-kV lines. Fig. 11. Arrester arrangement for protection against induced overvoltages. Fig. 10. Multichamber arrester for 20-kV DLS protection (MCA-20-DLS). arresters should be installed in parallel with each insulator of the line (or those line sections that should be protected against DLS (see Fig. 12). About 1800 arresters of this type (Fig. 9) were installed at 6-kV overhead power lines of Lukoil Oil Company (Russia) in March Tests of the arrester with a 3-cm conductor-arrester air gap (Fig. 9) have shown its 50% sparkover voltage to remain practically unchanged at about 85 kv after ten zero quenchings. Fig. 10 shows an arrester with 120 discharge chambers designed for DLS protection of 20-kV lines (see Table I). Its operating principle and installation procedure are similar to those described before (see Fig. 12). Fig. 12. Arrester arrangement for protection against direct lightning strokes. B. MCA-35 kv This MCA consists of an MCS, its bearing component, and a composite insulator with discharge rods assuring an air spark gap (see Fig. 13). The bearing component is a piece of polyethylene-covered cable with a fiberglassplastic core and metal terminals. The outside diameter of the cable is 50 mm. The cable cover consists of a thick inner layer of insulating polyethylene and a 2-mm outer layer of light-stabilized, trekking-resistant polyethylene. The 8-mm diameter fiberglass plastic rod is

6 PODPORKIN et al.: OVERHEAD LINES LIGHTNING PROTECTION BY MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS 219 Fig. 13. Illustration of MCA 35 kv on the tangent tower: (1) tower, (2) insulator, (3) line conductor, (4) MCS, (5) bearing component, (6) composite insulator, (7) discharge rods, and (8) arrester s grounding conductor. press-fitted into the terminals. The design ensures a high mechanical strength of the arrester. MCS is spiraled around the bearing component. An overvoltage on a line conductor caused, for instance, by a DLS (see Fig. 13), first triggers an air spark gap between discharge rods on the composite insulator followed by the MCS. The lightning overvoltage current flows through the arrester s grounding conductor to the tower and then to the ground. Excellent discharge-quenching characteristics of the MCS warrant either zero or impulse extinction of the overvoltage current and the power transmission line keeps working without failure. The principal performance data of the 35-kV MCS are shown in Table I. Fig. 19 shows a photograph of a commercial 35-kV overhead line of the Kamyshin Grid of Volgogradenergo Utility (Russia) with two MCS installed on its outer phases. IV. MULTICHAMBER INSULATOR ARRESTERS (MCIA) Fig. 14 features photos of an MCIA based on a porcelain rod insulator which is widely used in 3-kV dc railway overhead contact systems. The MCS is mounted over three quarters of the circumference of an insulator shed. The left and right ends of the MCS are approached by the upper and lower feed electrodes, respectively, which are installed on the upper and lower terminals; there are spark air gaps between the feed electrodes and the ends of the MCS. When the MCIA is stressed by an overvoltage, the air gaps get sparked over first, and the MCS comes next. The lightning overvoltage current flows from the lower terminal and its feed electrode via the spark channel of the lower spark gap to the MCS and on to the upper terminal via the discharge channel of the upper spark gap and the upper feed electrode. Note that there are no intervening electrodes between the upper and lower feed electrodes on the MCS-bearing silicon rubber shed; thus, the discharge develops over the MCS, taking some three quarters of the shed s circumference, rather than between the feed electrodes. A direct lightning stroke on the contact system or on its support brings about a sparkover, as described before. After the lightning overvoltage is over, with its current directed to the Fig. 14. Multichamber insulator arrester based on the porcelain insulator used in 3-kV dc railway overhead contact systems. (a) MCIA photo: (1) insulating body, (2) upper terminal, (3) lower terminal, (4) upper feed electrode, (5) lower feed electrode, (6) multichamber system, (7) upper spark discharge gap, and (8) lower spark discharge gap. (b) Tests of MCIA. Fig. 15. The 20-kV multichamber insulator arrester based on the SDI-37 insulator. ground via the support with the help of the MCS, an impulse extinction of the discharge occurs without any follow current, so that the contact system keeps working without outage. Fig. 15 shows a multichamber insulator arrester based on the SDI-37 pin insulator. It functions very similar to the MCIA shown in Fig. 14, but it is intended for protection of 6 10 kv lines against DLS and 20-kV lines against induced overvoltages. Fig. 16 shows a multichamber insulator arrester based on the glass cap-and-pin insulator type U120AD (MCIA-U120AD), during power follow current extinction tests with zero quenching. Fig. 17 shows a photo of an MCIA string during lightning impulse tests. With an overvoltage applied to a conductor as well as to the lower feed electrode closest to the conductor, the lower spark discharge gap gets broken down and voltage gets applied to the MCS (the left side of it is in Fig. 17). The MCS gets actuated, the upper spark air gap between the right end of the MCS and the upper feed electrode gets flashed over, voltage is fed to the second insulator, and so it goes on. After all, the MCIA of the string has been actuated, the lightning overvoltage current flows via the tower to the ground,

7 220 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 1, JANUARY 2011 Fig. 16. tests. MCIA with insulator U120AD during power follow current extinction Fig. 18. Commercial 35-kV overhead line (Kamyshin Grid, Volgogradenergo Utility) with the MCS on outer phases and MCIA on the central phase. TABLE II TESTS OF 220-kV MULTICHAMBER INSULATOR-ARRESTER STRINGS (MCIAS-220) Fig. 17. Photo of a three-mcia string during lightning impulse tests: (1) sheds of the insulating body, (2) cap, (3) pin, (4) upper feed electrode, (5) lower feed electrode, (6) multichamber system, (7) upper spark discharge gap, (8) lower spark discharge gap, and (9) conductor. followed, however, by ac power follow current. At the zero crossing, the arc is extinguished and the line keeps operating without outage or reclosure. In March 2009, a batch of 300 MCIAs-35 kv was installed for prototype operation in the Kamyshin Grid Area of the Volgogradenergo Utility (Fig. 18). Federal Grid Co., which is the sole owner of all overhead power lines rated at 220 kv and above in Russia, is interested in the MCIA technology and organized a 220-kV line R&D program. Table II gives a list of tests fulfilled on strings of 14 MCIAs. MCIAs-220 have successfully passed all of the tests listed in Table I. The test results will be reported at a later stage. V. CONCLUSION 1) Multichamber systems (MCSs) have been developed that ensure quenching of discharge that follows a lightning overvoltage impulse. 2) MCSs make it possible to develop simple, inexpensive, and efficient arresters. 3) In 3-kV dc railway overhead contact systems, MCSs quench discharge immediately after a lightning overvoltage impulse with no follow current. 4) MCIAs have been developed, comprising production insulators and MCSs that are mounted over the perimeter of the insulating body without adversely affecting the insulating properties of insulators. 5) In principle, the application of MCIAs can warrant reliable protection of overhead lines of any rated voltage against induced overvoltages and direct lightning strokes. 6) Further research-and-development work that would include complex electric, mechanical, and climatic tests, as well as experimental field exploitation is expedient. REFERENCES [1] C. R. Morey and T. C. Oehne, Jr, Lightning arresters and schemes for testing, B.S. thesis, Armour Inst. Technol., Paul V. Galvin Libr., Ill. Inst. Technol., [2] A. O. Austin, Transmission line, U.S , Mar. 1, [3] M. Darveniza, A Lightning Protective Device for Overhead Lines Using the ARC Quenching Properties of Wood. Brisbane, Australia: Univ. Queensland, [4] Non-Linear Resistor Type Gapped Surge Arresters for A/C. Systems, , IEC Std [5] R. E. Baldwin, Lightning protection for aircraft radomes, U.S , Apr. 22, [6] G. V. Podporkin, V. E. Pilshikov, and A. D. Sivaev, Development of long flashover arresters with multi-electrode system for lightning overvoltage and conductor-burn protection of 6 to 35 kv overhead lines, in Proc. 28th Int. Conf. Lightning Protection, 2006, pp

8 PODPORKIN et al.: OVERHEAD LINES LIGHTNING PROTECTION BY MULTI-CHAMBER ARRESTERS AND INSULATOR-ARRESTERS 221 [7] G. V. Podporkin and E. S. Kalakutsky, Lightning arrester and overhead power line equipped with the arrester, Russia PCT/RU2009/000006, [8] G. V. Podporkin, High voltage insulator and overhead power line using the insulator, Russia PCT/RU2009/000142, Evgeniy S. Kalakutsky was born on August 8, He received the D.S. and M.S. degrees from the St. Petersburg State Polytechnic University in Currently, he is an Engineer with Streamer Research and Production Company, St. Pertersburg, Russia. Georgij V. Podporkin (SM 94) was born on August 26, He received the B.S., Ph.D., and D.Sc. degrees in electrical engineering from the St. Petersburg Technical University, St. Petersburg, Russia, in 1973, 1977, and 1990, respectively. From 1973 until 1991, he was a Research Scientist at the Extra High Voltage Laboratory of the St. Petersburg Technical University. During , he was a Scientific Consultant at CEPEL, Rio de Janeiro, Brazil. His fields of interest are lightning protection and insulation of overhead transmission and distribution lines. Currently, he is Director of Research at the Streamer Research and Production Company and a Part-Time Professor at the St. Petersburg Technical University. Vladimir E. Pilshikov was born on January 24, He received the B.S. and Ph.D. degrees in electrical engineering from the St. Petersburg Technical University, St. Petersburg, Russia, in 1973 and 1979, respectively. Since 1973, he has been a Research Scientist at the High Voltage Department of the St. Petersburg Technical University in the field of internal and external insulation of high voltage apparatus. Evgeniy Yu Enkin was born on April 7, He received the B.S. degree from the St. Petersburg State Communication Lines University (Electromechanical Department) in Currently, he is an Engineer with Streamer Research and Production Company. Alexander D. Sivaev was born on July 22, He received the B.S. and Ph.D. degrees in electrical engineering from St. Petersburg Technical University, St. Petersburg, Russia, in 1978 and 1999, respectively. From 1981 until 1995, he was a Research Scientist at the Extra High Voltage Laboratory, St. Petersburg Technical University, in the field of insulation and lightning protection of overhead transmission lines. Currently, he is Technical Director of the Streamer Research and Production Company.

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES G. V. Podporkin, V. E. Pilshikov, A. D. Sivaev Streamer Electric

More information

High voltage engineering

High voltage engineering High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency

More information

ABSTRACTS of SESSION 6

ABSTRACTS of SESSION 6 ABSTRACTS of SESSION 6 Paper n 1 Lightning protection of overhead 35 kv lines by antenna-module long flashover arresters Abstract: A long-flashover arrester (LFA) of a new antenna-module type is suggested

More information

Tab 8 Surge Arresters

Tab 8 Surge Arresters s en em Tab 8 Surge Arresters Si Distribution System Engineering Course Unit 10 2017 Industry Inc., All Rights Reserved Surge Arresters The main protective devices against system transient overvoltages.

More information

Lightning performance of a HV/MV substation

Lightning performance of a HV/MV substation Lightning performance of a HV/MV substation MAHMUD TAINBA, LAMBOS EKONOMOU Department of Electrical and Electronic Engineering City University London Northampton Square, London EC1V HB United Kingdom emails:

More information

High-Voltage Test Techniques

High-Voltage Test Techniques High-Voltage Test Techniques Dieter Kind Kurt Feser 2nd Revised and Enlarged Edition With 211 Figures and 12 Laboratory Experiments Translated from the German by Y. Narayana Rao Professor of Electrical

More information

EE 1402 HIGH VOLTAGE ENGINEERING

EE 1402 HIGH VOLTAGE ENGINEERING EE 1402 HIGH VOLTAGE ENGINEERING Unit 5 TESTS OF INSULATORS Type Test To Check The Design Features Routine Test To Check The Quality Of The Individual Test Piece. High Voltage Tests Include (i) Power frequency

More information

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Analysis of lightning performance of 132KV transmission line by application of surge arresters Analysis of lightning performance of 132KV transmission line by application of surge arresters S. Mohajer yami *, A. Shayegani akmal, A.Mohseni, A.Majzoobi High Voltage Institute,Tehran University,Iran

More information

Electric Stresses on Surge Arrester Insulation under Standard and

Electric Stresses on Surge Arrester Insulation under Standard and Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems

More information

HIGH VOLTAGE Insulation Coordination

HIGH VOLTAGE Insulation Coordination HIGH VOLTAGE Insulation Coordination Assistant Professor Suna BOLAT KRÖGER Eastern Mediterranean University Department of Electric & Electronic Engineering Insulation coordination The term Insulation Co-ordination

More information

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES 21, rue d'artois, F-75008 Paris http://www.cigre.org A3-308 Session 2004 CIGRÉ HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES G.E. Agafonov, I.V. Babkin, B.E. Berlin Y. F. Kaminsky, S. V. Tretiakov,

More information

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 23 CHAPTER 2 v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 2.1 INTRODUCTION For reliable design of power system, proper insulation coordination among the power system equipment is necessary. Insulation

More information

Analysis of current distribution among long-flashover arresters for 10 kv overhead line protection against direct lightning strikes

Analysis of current distribution among long-flashover arresters for 10 kv overhead line protection against direct lightning strikes 2014 International onference on Lightning Protection (ILP), Shanghai, hina nalysis of current distribution among long-flashover arresters for 10 kv overhead line protection against direct lightning strikes

More information

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Power Frequency Withstand Voltage On-site testing of 400 kv GIS Power Frequency Withstand Voltage On-site testing of 400 kv GIS D. Anaraki Ardakani, A. Omidkhoda, M. Solati High Voltage Engineering Center ACECR Tehran, Iran Da_ardakani@yahoo.com Paper Reference Number:

More information

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc. Surge Arresters Secondary Arresters and Protective Gaps Electrical Apparatus 235-10 GENERAL INFORMATION The necessity of providing surge arrester protection on low-voltage circuits is fundamentally the

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation IOSR Journal of Engineering (IOSRJEN) ISSN (e): 2250-3021, ISSN (p): 2278-8719 Vol. 04, Issue 05 (May. 2014), V2 PP 32-36 www.iosrjen.org Computer Based Model for Design Selection of Lightning Arrester

More information

A SEMINAR REPORT PRESENT ON AIR BLAST CIRCUIT BREAKER

A SEMINAR REPORT PRESENT ON AIR BLAST CIRCUIT BREAKER A SEMINAR REPORT PRESENT ON AIR BLAST CIRCUIT BREAKER Submitted by :- submitted to:- Tazinder singh E.E. 3 rd year (BBDNIIT) 1 Acknowledgement 2 content Topic Page no. Air blast circuit breaker 04 Principle

More information

High Voltage Engineering

High Voltage Engineering High Voltage Engineering Course Code: EE 2316 Prof. Dr. Magdi M. El-Saadawi www.saadawi1.net E-mail : saadawi1@gmail.com www.facebook.com/magdi.saadawi 1 Contents Chapter 1 Introduction to High Voltage

More information

Multi-Chamber Arrester Field Test Experience on Medium Voltage Overhead Line in Asia Matthieu Zinck, Jean-Baptiste Frain

Multi-Chamber Arrester Field Test Experience on Medium Voltage Overhead Line in Asia Matthieu Zinck, Jean-Baptiste Frain Multi-Chamber Arrester Field Test Experience on Medium Voltage Overhead Line in Asia Matthieu Zinck, Jean-Baptiste Frain Abstract this paper discuss issues on medium voltage overhead lines related to lightning

More information

Generation of Sub-nanosecond Pulses

Generation of Sub-nanosecond Pulses Chapter - 6 Generation of Sub-nanosecond Pulses 6.1 Introduction principle of peaking circuit In certain applications like high power microwaves (HPM), pulsed laser drivers, etc., very fast rise times

More information

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR 621 212 DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING EE1003 HIGH VOLTAGE ENGINEERING QUESTION BANK UNIT-I OVER VOLTAGES IN ELECTRICAL POWER SYSTEM

More information

Capacitive voltage transformers

Capacitive voltage transformers Capacitive voltage transformers Outdoor operation Oil-paper insulated ECF (72 550) kv General description Capacitive voltage transformers of type ECF are used in high-voltage switchgears from 72 to 550

More information

Power Quality and Reliablity Centre

Power Quality and Reliablity Centre Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview

More information

Insulation Co-ordination For HVDC Station

Insulation Co-ordination For HVDC Station Insulation Co-ordination For HVDC Station Insulation Co-ordination Definitions As per IEC 60071 Insulation Coordination is defined as selection of dielectric strength of equipment in relation to the operating

More information

CVVOZE Power Laboratories (CVVOZEPowerLab)

CVVOZE Power Laboratories (CVVOZEPowerLab) CVVOZE Power Laboratories (CVVOZEPowerLab) BRNO, SEPTEMBER 2016 1 Centre for Research and Utilization of Renewable Energy Centre for Research and Utilization of Renewable Energy (CVVOZE) was established

More information

Overvoltage Protection

Overvoltage Protection Overvoltage Protection S T U D E N T M A N U A L March 31, 2005 2 STUDENT TRAINING MANUAL Prerequisites: Single-Phase Transformer Load Checks Objectives: From memory, you will be able to describe the electrical

More information

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

FGJTCFWPKPUVKVWVGQHVGEJPQNQI[ FGRCTVOGPVQHGNGEVTKECNGPIKPGGTKPI VGG246JKIJXQNVCIGGPIKPGGTKPI FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown

More information

The Simulation Experiments on Impulse Characteristics of Tower Grounding Devices in Layered Soil

The Simulation Experiments on Impulse Characteristics of Tower Grounding Devices in Layered Soil International Journal of Engineering and Technology, Vol. 9, No., February 7 The Simulation Experiments on Impulse Characteristics of Tower Grounding Devices in Layered Soil Leishi Xiao, Qian Li, Zhangquan

More information

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage Swati Agrawal Assistant Professor, MATS University, Raipur (C.G) Abstract: This paper describes the usage of surge

More information

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS 29 th International Conference on Lightning Protection 23 rd 26 th June 2008 Uppsala, Sweden PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS Ivo Uglešić Viktor Milardić Božidar

More information

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral

More information

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid 1 Arpan K. Rathod, 2 Chaitanya H. Madhekar Students Electrical Engineering, VJTI, Mumbai, India

More information

Protection against unacceptable voltages in railway systems

Protection against unacceptable voltages in railway systems Bernhard Richter*, Alexander Bernhard*, Nick Milutinovic** SUMMERY Based on the system voltages for AC and DC railway systems the required voltage ratings for modern gapless MO surge arresters are given.

More information

Abstract. 1 Introduction

Abstract. 1 Introduction Energy Production and Management in the 21st Century, Vol. 1 345 Investigation of the electrical strength of a contact gap of the high voltage live tank circuit breaker 126 kv class using an intelligent

More information

Lightning overvoltage and protection of power substations

Lightning overvoltage and protection of power substations Lightning overvoltage and protection of power substations Mahmud Trainba 1, Christos A. Christodoulou 2, Vasiliki Vita 1,2, Lambros Ekonomou 1,2 1 Department of Electrical and Electronic Engineering, City,

More information

RESULTS OF EXPERIMENTAL HIGH CURRENT IMPULSE 4/10 s OF METAL OXIDE VARISTORS ZINC IN THE HIGH VOLTAGE 220KV SURGE ARRESTER

RESULTS OF EXPERIMENTAL HIGH CURRENT IMPULSE 4/10 s OF METAL OXIDE VARISTORS ZINC IN THE HIGH VOLTAGE 220KV SURGE ARRESTER RESULTS OF EXPERIMENTAL HIGH CURRENT IMPULSE 4/10 s OF METAL OXIDE VARISTORS ZINC IN THE HIGH VOLTAGE 220KV SURGE ARRESTER PhD. Nguyen Huu Kien National Key Laboratory for High Voltage Techniques - Institute

More information

PANIMALAR ENGINEERING COLLEGE Department of Electrical and Electronics Engineering

PANIMALAR ENGINEERING COLLEGE Department of Electrical and Electronics Engineering PANIMALAR ENGINEERING COLLEGE Department of Electrical and Electronics Engineering 1. Write some applications of high voltage? High Voltage Engineering 2 mark Question with answers Unit I Overvoltages

More information

Harmonic Components Analysis of Leakage Current for Standard and Anti-Fog Suspension Insulators under Humidity Conditions

Harmonic Components Analysis of Leakage Current for Standard and Anti-Fog Suspension Insulators under Humidity Conditions Harmonic Components Analysis of Leakage Current for Standard and Anti-Fog Suspension Insulators under Humidity Conditions R. Hajian M. Mirzaie Babol University of Technology, Iran Reza.hajian.7@gmail.com,

More information

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS TRANSFORMER IN GRID When surge arres t ers are installed close to a power transformer, they provide protection against lightning overvoltage ABSTRACT The aim of this research article is to determine the

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY Dr. Karthik Reddy VENNA Hong URBANEK Nils ANGER Siemens AG Germany Siemens AG Germany Siemens AG Germany karthikreddy.venna@siemens.com

More information

Investigation of skin effect on coaxial cables

Investigation of skin effect on coaxial cables Investigation of skin effect on coaxial cables Coaxial cables describe a type of cables that has an inner conductor surrounded by an insulator, which is surrounded by another layer of conductor and insulator

More information

EE High Voltage Engineering UNIT IV - MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS PART-A 1. Mention the techniques used in impulse current

EE High Voltage Engineering UNIT IV - MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS PART-A 1. Mention the techniques used in impulse current EE6701 - High Voltage Engineering UNIT IV - MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS PART-A 1. Mention the techniques used in impulse current measurements. Hall generators, Faraday generators and

More information

Introduce system protection relays like underfrequency relays, rate of change of frequency relays, reverse - power flow

Introduce system protection relays like underfrequency relays, rate of change of frequency relays, reverse - power flow Module 1 : Fundamentals of Power System Protection Lecture 3 : Protection Paradigms - System Protection Objectives In this lecture we will: Overview dynamics in power systems. Introduce system protection

More information

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation M. Kondalu1, P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. 1 Kondalu_m@yahoo.com

More information

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 1), Cairo University, Egypt, December 19-1, 1, Paper ID 1. Simplified Approach to Calculate the Back Flashover Voltage

More information

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR CIRCUIT BREAKER SF 6 ING. VÁCLAV JEŽEK PROF. ING. ZDENĚK VOSTRACKÝ, DRSC., DR.H.C. Abstract: This article describes the analysis of faults interrupted by generator

More information

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS 1. Introduction 2. Classification of High Voltage Tests 3. Test Voltages 4. High Voltage Testing of Electrical Apparatus 1. INTRODUCTION Purpose

More information

B2-301 IMPROVING DOUBLE CIRCUIT TRANSMISSION LINE RELIABILITY THROUGH LIGHTNING DESIGN

B2-301 IMPROVING DOUBLE CIRCUIT TRANSMISSION LINE RELIABILITY THROUGH LIGHTNING DESIGN 21, rue d'artois, F-7008 Paris http://www.cigre.org B2-301 Session 200 CIGRÉ IMPROVING DOUBLE CIRCUIT TRANSMISSION LINE RELIABILITY THROUGH LIGHTNING DESIGN J. A. (TONY) GILLESPIE & GLENN STAPLETON Powerlink

More information

Capacitive voltage transformers

Capacitive voltage transformers Capacitive voltage transformers Outdoor operation Oil-paper insulated ECF (72 550) kv General description Capacitive voltage transformers of type ECF are used in high-voltage switchgears from 72 to 550

More information

Testing 320 kv HVDC XLPE Cable System

Testing 320 kv HVDC XLPE Cable System Testing 320 kv HVDC XLPE Cable System H. He, W. Sloot DNV GL, KEMA Laboratories Arnhem, The Netherlands Abstract Two unique test requirements in testing of a high- voltage direct- current (HVDC) cable

More information

Modeling insulation in high-voltage substations

Modeling insulation in high-voltage substations 38 ABB REVIEW DESIGNED FOR SAFETY DESIGNED FOR SAFETY Modeling insulation in high-voltage substations The goal of insulation coordination is to determine the dielectric strength of transformers and other

More information

Lightning transient analysis in wind turbine blades

Lightning transient analysis in wind turbine blades Downloaded from orbit.dtu.dk on: Aug 15, 2018 Lightning transient analysis in wind turbine blades Candela Garolera, Anna; Holbøll, Joachim; Madsen, Søren Find Published in: Proceedings of International

More information

Coherence and time-frequency analysis of impulse voltage and current measurements

Coherence and time-frequency analysis of impulse voltage and current measurements Coherence and time-frequency analysis of impulse voltage and current measurements Jelena Dikun Electrical Engineering Department, Klaipeda University, Klaipeda, Lithuania Emel Onal Electrical Engineering

More information

Protection of low power mains against pulse power of natural lightning using spark gap arresters. Abstract

Protection of low power mains against pulse power of natural lightning using spark gap arresters. Abstract Protection of low power mains against pulse power of natural lightning using spark gap arresters. J Meppelink*, E.G. Jordan.**, J.Trinkwald*** *University of Paderborn,* BET Blitzschutz-und EMV Technologiezentrum

More information

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad Day 2 - Session IV-A High Voltage 163 Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad B. Kondala Rao, Gopal Gajjar ABB Ltd., Maneja, Vadodara, India Introduction Circuit breakers play

More information

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation M. Kondalu1, Dr. P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. 1 Kondalu_m@yahoo.com

More information

MAHALAKSHMI ENGINEERING COLLEGE

MAHALAKSHMI ENGINEERING COLLEGE MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI 621213 QUESTION BANK -------------------------------------------------------------------------------------------------------------- Sub. Code : EE2353 Semester

More information

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM SYSTEM OVERVIEW Pollution monitoring of high voltage insulators in electrical power transmission and distribution systems, switchyards and substations is essential in order to minimise the risk of power

More information

The line-lightning performance and mitigation studies of shielded steelstructure

The line-lightning performance and mitigation studies of shielded steelstructure The line-lightning performance and mitigation studies of shielded steelstructure distribution lines ASNAWI MOHD BUSRAH, MALIK MOHAMAD Energy System Group TNB Research Sdn Bhd No 1, Lorong Ayer Hitam, 43000

More information

DC VACUUM CIRCUIT BREAKER

DC VACUUM CIRCUIT BREAKER DC VACUUM CIRCUIT BREAKER Lars LILJESTRAND Magnus BACKMAN Lars JONSSON ABB Sweden ABB Sweden ABB Sweden lars.liljestrand@se.abb.com magnus.backman@se.abb.com lars.e.jonsson@se.abb.com Marco RIVA ABB Italy

More information

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems PPLICATION GUIDELINES OVERVOLTAGE PROTECTION Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems Foreword Up until 1998 no international standards

More information

Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse

Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse A. Elzowawi, A. Haddad, H. Griffiths Abstract the electric discharge and soil ionization phenomena have a great effect

More information

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:15 No:03 39 Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models Shen-Wen Hsiao, Shen-Jen

More information

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002 569 Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System Li-Ming Zhou, Senior Member, IEEE,

More information

Shunt Reactor Switching

Shunt Reactor Switching Shunt Reactor Switching Dielectric stresses produced by circuit-breakers to shunt reactors. Presentation made during the IEEE Transformers Committee meeting, Amsterdam, Netherlands, April 2001 Presented

More information

Vacuum Interrupters for Medium Voltage

Vacuum Interrupters for Medium Voltage for Medium Voltage Reliable, Maintenance-Free and Environmentally Friendly Today, vacuum as an arc extinguishing medium provides the most cost-effective solution for medium-voltage circuit-breakers. Siemens

More information

3. COMBINED TRANSFORMERS Oil-paper insulation

3. COMBINED TRANSFORMERS Oil-paper insulation 3. COMBINED TRANSFORMERS Oil-paper insulation 123 kv Combined transformers. 26 Instrument transformers High voltage INTRODUCTION Combined instrument transformers contain a current transformer and an inductive

More information

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical

More information

VariSTAR Type AZL heavy-duty distribution-class MOV arrester

VariSTAR Type AZL heavy-duty distribution-class MOV arrester Surge s Catalog Data CA235006EN Supersedes TD235007EN September 2014 COOPER POWER SERIES VariSTAR Type AZL heavy-duty distribution-class MOV arrester General Eaton incorporates the latest in metal oxide

More information

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES Shohreh Monshizadeh Islamic Azad University South Tehran Branch (IAU), Tehran,

More information

METHODS AND CIRCUITS FOR POWER ARC TEST IN AC CURRENT OF THE SIMPLE AND DOUBLE INSULATOR SETS WITH COMPOSITE MATERIAL FOR AERIAL ELECTRIC LINES

METHODS AND CIRCUITS FOR POWER ARC TEST IN AC CURRENT OF THE SIMPLE AND DOUBLE INSULATOR SETS WITH COMPOSITE MATERIAL FOR AERIAL ELECTRIC LINES METHODS ND CIRCUITS FOR POWER RC TEST IN C CURRENT OF THE SIMPLE ND DOUBLE INSULTOR SETS WITH COMPOSITE MTERIL FOR ERIL ELECTRIC LINES George CURCNU, Constantin INCU, Corneliu CHICIU ICMET-Craiova, Calea

More information

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP IJSTE - International Journal of Science Technology & Engineering Volume 3 Issue 2 August 216 ISSN (online): 2349-784X Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

More information

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables J Electr Eng Technol Vol. 9, No. 2: 628-634, 2014 http://dx.doi.org/10.5370/jeet.2014.9.2.628 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 A Study on Lightning Overvoltage Characteristics of Grounding

More information

MAHALAKSHMI ENGINEERING COLLEGE

MAHALAKSHMI ENGINEERING COLLEGE MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI 621213 QUESTION BANK -------------------------------------------------------------------------------------------------------------- Sub. Code : EE2353 Semester

More information

Experimental Investigations and Calculations in 6-35 kv Networks with Various Neutral Conditions

Experimental Investigations and Calculations in 6-35 kv Networks with Various Neutral Conditions PQ20 June 16-18, 2010 Kuressaare Experimental Investigations and Calculations in 6-35 kv Networks with Various Neutral Conditions A. Shirkovets, A. Vasilyeva, A. Telegin LLC BOLID, Novosibirsk, Russia

More information

24 th International Conference on Electricity Distribution Glasgow, June Paper 0881 ABSTRACT STATE OF THE ART INTRODUCTION ECOTAP VPD

24 th International Conference on Electricity Distribution Glasgow, June Paper 0881 ABSTRACT STATE OF THE ART INTRODUCTION ECOTAP VPD A NEW GENERATION VOLTAGE REGULATION DISTRIBUTION TRANSFORMER WITH AN ON LOAD TAP CHANGER FOR POWER QUALITY IMPROVEMENT IN THE ELECTRICAL DISTRIBUTION SYSTEMS Sudheer MOKKAPATY Jens WEISS Frank SCHALOW

More information

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering

More information

In power system, transients have bad impact on its

In power system, transients have bad impact on its Analysis and Mitigation of Shunt Capacitor Bank Switching Transients on 132 kv Grid Station, Qasimabad Hyderabad SUNNY KATYARA*, ASHFAQUE AHMED HASHMANI**, AND BHAWANI SHANKAR CHOWDHRY*** RECEIVED ON 1811.2014

More information

Integrated Electro-optic Sensor based Transient Voltage Measuring System and its Applications

Integrated Electro-optic Sensor based Transient Voltage Measuring System and its Applications International Conference on Lightning Protection (ICLP), Shanghai, China Integrated Electro-optic Sensor based Transient Voltage Measuring System and its Applications Chijie Zhuang, Hai Wang, Rong Zeng,

More information

SURGE ARRESTERS AND TESTING. Keith Hill Doble Engineering Company

SURGE ARRESTERS AND TESTING. Keith Hill Doble Engineering Company SURGE ARRESTERS AND TESTING Keith Hill Doble Engineering Company Surge arresters are often overlooked when performing Power Factor tests on transformers, breakers and other apparatus in a substation. Often

More information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING YEAR / SEM : IV / VII UNIT I OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What

More information

High Voltage Generation

High Voltage Generation High Voltage Generation Purposes (Manfaat) Company Logo High DC High AC Impulse Electron microscopes and x-ray units (high d.c. voltages 100 kv) Electrostatic precipitators, particle accelerators (few

More information

In order to minimise distribution (11 and 22 kv) feeder breaker

In order to minimise distribution (11 and 22 kv) feeder breaker Lightning protection for equipment on MV feeders By WJD van Schalkwyk and M du Preez, Eskom This article presents the influence of lightning on MV feeders supplying small power users (400/230 V) with focus

More information

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING 1 PRACTICAL PROBLEMS WITH SUBSTATION EARTHING Dr Hendri Geldenhuys Craig Clark Eskom Distribution Technology This paper considers the issues around substation sites where the soil resistivity is of particularly

More information

The Testing Of High Voltage Silicon Carbide Lightning Arresters

The Testing Of High Voltage Silicon Carbide Lightning Arresters The Testing Of High Voltage Silicon Carbide Lightning Arresters Ass Lect. Arkan A. Hussein University Of Tikrit / Engineering College / Electrical Engineering Department ABSTRACT The majority of high voltage

More information

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC Xiaojun Chena *, Wenjie Zhengb, Shu Huangc, Hui Chend Electric Power Research Institute

More information

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping P. Mestas, M. C. Tavares Abstract. The optimization of the grounding neutral reactor is a common practice

More information

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation M. Kondalu1, Dr. P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering College,

More information

X International Symposium on Lightning Protection

X International Symposium on Lightning Protection X International Symposium on Lightning Protection 9 th -13 th November, 2009 Curitiba, Brazil LIGHTNING SURGES TRANSFERRED TO THE SECONDARY OF DISTRIBUTION TRANSFORMERS DUE TO DIRECT STRIKES ON MV LINES,

More information

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N S C I E N C E P A S S I O N T E C H N O L O G Y HVDC Transmission Michael Muhr Graz University of Technology Austria www.tugraz.at 1 Definition HV High Voltage AC Voltage > 60kV 220kV DC Voltage > 60kV

More information

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE Willem DIRKSE VAN SCHALKWYK ESKOM - South Africa vschalwj@eskom.co.za ABSTRACT A high BIL (300 kv) on a MV feeder ensures that no

More information

Type Test of a 145 kv Termination Type TS 145-II

Type Test of a 145 kv Termination Type TS 145-II Test Report No 2009-125/2 Type Test of a 145 kv Termination Type TS 145-II Client: 3 M Deutschland GmbH Carl-Schurz-Str.1 41453 Neuss Reporter: Dr.-Ing. R. Badent Dr.-Ing. B. Hoferer This report includes

More information

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS -1- INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION June 2013 SPECIFICATION No 150 kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS I. SCOPE This specification

More information

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages Session Four: ractical Insulation Co-ordination Session Four: ractical Insulation Co-ordination for Lightning Induced Overvoltages Jason Mayer Technical Director, Energy Services, Aurecon Introduction

More information

The Many Uses of Transmission Line Arresters

The Many Uses of Transmission Line Arresters Introduction It was not realized at the time, but the 1992 introduction of the polymer-housed transmission line arrester (TLA) was clearly a game changer in the practice of lightning protection of transmission

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

International Journal of Advance Research in Engineering, Science & Technology

International Journal of Advance Research in Engineering, Science & Technology Impact Factor (SJIF): 3.632 International Journal of Advance Research in Engineering, Science & Technology e-issn: 2393-9877, p-issn: 2394-2444 (Special Issue for ITECE 2016) Multistage Impulse Voltage

More information

INVESTIGATION OF A HIGH VOLTAGE, HIGH FREQUENCY POWER CONDITIONING SYSTEM FOR USE WITH FLUX COMPRESSION GENERATORS

INVESTIGATION OF A HIGH VOLTAGE, HIGH FREQUENCY POWER CONDITIONING SYSTEM FOR USE WITH FLUX COMPRESSION GENERATORS INVESTIGATION OF A HIGH VOLTAGE, HIGH FREQUENCY POWER CONDITIONING SYSTEM FOR USE WITH FLUX COMPRESSION GENERATORS K. A. O Connor ξ and R. D. Curry University of Missouri-Columbia, 349 Engineering Bldg.

More information