LED MC+ Switch Input Mdule - User Manual Item n.: LC-004-301 1. Prduct Descriptin The MC+ is a Cmpact Multi Cntrl mdule with 4 freely prgramable swithcing inputs (ptential-free clsing cntacts). The supply f the mdule directly via the Line. The mduel can be used in a flush bx directly behind a light switch 2. Specificatin supply typ. current cnsumptin input utput cnnecting wire crss sectin wiring length t mmentary switches Prduct Dimensins (L x W x H) in mm Weight via signal line 4.1mA 4 x GPI 0.5-1.5 mm2 50 cm 40 x 28 x 15 mm 10g 3. Descriptin 1. Cmpact cntrl unit with 4 general purpse inputs 2. Each input can be cnfigured fr digital r analg input signals 3. Mmentary switches r 100kΩ ptentimeters are cnnected directly t the MC+ 4. The fllwing standard cmmands can be assigned t switching actins: dim up, dim dwn, ff, recall min, recall max, gt scene 1-16, direct arcpwer in % as well as predefined and self-cnfigured macrs ( cmmand sequences). 5. Clur temperature adjustment is supprted. Implemented DT8-cmmands are STEP COO- LER and STEP WARMER 6. Fr analg inputs the input signal is cnverted directly int a arc pwer level. The cnversin can be triggered peridically r by a predefined event.
7. AA switching actin r a change in the input vltage signal (>2%) can be selected as trigger event fr the cnversin. 8. The MC+ als has an adjustable pwer-up -functin. In ther wrds a user-defined cmmand can be sent n pwer up (e.g. after a pwer failure) 9. Individual addresses (1-64), grup addresses (1-16) r bradcast can be set as destinatin. 10. Cnfiguratin can be set up with Cckpit and -USB interface 11. Multiple MC+ mdules can be used n the same -line Addressing and Cnfiguratin Via a -USB interface the -Cckpit sftware tl can cmmunicate with the MC+. S the desired functinality can be cnfigured easily n PC. The -Cckpit sftware is a free cnfiguratin tl fr systems. Hence standard ballasts can be addressed and cnfigured as well as the MC+1. Cckpit and -USB Interface are required fr cnfiguratin nly and can be remved fr standard peratin (see typical installatin drawing). Fr mre details check the instructin manual f the Switch, the Tutrial and the descriptin f the Cckpit. Fr simple applicatins the factry settings can be sufficient (dim&switch functin). In this case there is n need fr a USB interface and a cnfiguratin tl. The factry setting is described belw. Destinatin Address: Bradcast Input T1: digital, switch t last recent level Input T2: digital, dim up Input T3: digital, switch ff Input T4: digital, dim dwn Adjustable ality With the help f the -Cckpit the MC+ can be cnfigured. Any input can be cnfigured fr analgue r digital input signals. When used as analgue input the input signal is either cnverted directly t a dim level r be prcessed by a threshld algrithm and handled like a digital input signal. When cnfigured as analgue input an ffset value fr the input value range can be defined. Belw this value the utput is 0, furthermre the trigger fr the cnversin can be defined. Optins fr the trigger are peridic cnversin r event based trigger. Fr each digital input a high level n flexibility and individualism is ffered due t the parameters available. Switching mde, destinatin addresses and cmmands belng t the settings fr a mmentary switch. By means f the switching mde different actins fr brief and lng depress time can be defined fr the mmentary switches fr miscellaneus applicatins. The functins vary frm simple push buttns r tggle push buttns via lighting based push buttn dimming keys t standard stairwell functin with cnfigurable delay time.
A cmplete verview is given in the table belw. Actin Descriptin 1 Push Buttn shrt/lng: 1 * cmmand X Briefly pressing r hlding dwn the push buttn will send cmmand X ne time 2 Push Buttn shrt: 1 * cmmand X lng: 1 * cmmand X then 1 * Briefly pressing r hlding dwn the push-buttn will send cmmand X ne time Hlding dwn the push buttn will send cmmand X nce and then nce 3 Push Buttn shrt: 1 * cmmand X lng: 1 * cmmand X then repeatedly Briefly pressing r hlding dwn the push-buttn will send cmmand X ne time Hlding dwn the push buttn will send cmmand X nce andthen repeatedly 4 Push Buttn Tggle 5 Push Buttn Tggle 6 Push Buttn Dimming Key 7 Stairwell shrt: tggle between cmmand X and Y shrt: tggle between cmmand X and Y lighting status based shrt: tggle between cmmand X and Y, lighting status based lng: dimming, lighting status based shrt/lng: cmmand X, after run-n time 8 Push Buttn shrt: 1*cmmand X n release lng: repeated 9 Push Buttn 1 * cmmand X, then repeated withut lng buttn delay Briefly pressing the push buttn will alternate between sending cmmands X and Y Briefly pressing the push buttn will alternate between sending cmmands X and Y lighting based: If the light was previusly switched ff -> cmmand X If the light was previusly switched n -> Briefly pressing the push buttn will alternate between sending cmmands X and Y lighting based: If the light was previusly switched ff -> cmmand X If the light was previusly switched n -> Hlding dwn the dimmer switch dims r brightens the lighting. If the pushbuttn is pressed, cmmand X is sent and the runn time starts. Once the run-n time elapsed, is sent. Briefly pressing the push buttn and release will send cmmand X Hlding dwn the push buttn will send repeated Briefly pressing the push buttn and release will send cmmand X and thereafter repeatly (withut lng press)
In additin t the switching mde the reactin n a depress actin has t be defined. It cnsists f a cmmand and up t 4 destinatin addresses. Individual addresses (1-64), grup addresses (1-16) r bradcast can be set as destinatin address. In the table belw a summary f the cmmands available is given. In the table belw a summary f the cmmands available is given. cmmand number cmmand name - DIRECT ARC direct arc pwer Level in % POWER 0 OFF ff 1 UP dim up (using fade rate) 2 DOWN dim dwn (using fade rate) 3 STEP UP increases light level by ne increment 4 STEP DOWN decreases light level by ne increment 5 RECALL MAX recalls MAX value 6 RECALL MIN recalls MIN value 7 STEP DOWN AND OFF decreases light level by ne increment, if value at MIN switch ff 8 ON AND STEP UP increases light level by ne increment, if OFF switch n 16-31 GO TO SCENE ruft Lichtszene 0-15 auf As an alternative t the transmissin f any single cmmand initiated by a depress actin, it is pssible t transmit a set f cmmands within a -macr. This ptin can be used fr either predefined prcesses (such as a scene sequencer) r any userdefined sequence f -cmmands. macr (required memry) G Hme (2 Byte) Sequential Scenes (3 Byte) Dynamic Scenes (9 Byte) Light dims dwn t P 0 with predefined fade time, then fade time is set back t a prgrammable value Selectable scenes (r OFF) will be sent sequentially with each buttn press. Dynamic sequence f up t 4 selectable scenes, fadetimes and delays, stps with next buttn press
macr (required memry) -Reset (1 Byte) User defined Cmmands (5 Byte je Befehl, 19 Befehle max.) DT8 Cler 3x (0 Byte) DT8 Warmer 3x (0 Byte) Switch On (4 Byte) Switch Off (3 Byte) Dim Up (after Switch Off) (3 Byte) Sends -Reset (address can be deleted ptinally) A user defined macr file can be laded t the switch Activates DT8 and sends STEP COOLER cmmand 3x Activates DT8 and sends STEP WARMER cmmand 3x Switches t last recent level, wrks nly in cmbinatin with Switch Off Stres last recent level and switches ff Allws t Dim Up frm OffState t MAXLEVEL, when having used Switch Off befre Fr each push buttn a macr memry f 96 bytes max is available. The sum f CmdX and CmdY macr memry may nt exceed this value. Fr mre details n the selectin f predefined macrs and the ability t create custm macr files check the manual f the -Cckpit cnfiguratin sftware. Anther cnfigurable feature is the pwerup -functin. This is a user-defined reactin n a pwer up. The fllwing ptins are available fr the Switch Crss: n actin OFF g t scene 0-15 T take the startup-time f -ballasts int accunt a delay time can be cnfigured between pwer up and the start f transmissin f the selected cmmand. This functinality f the MC+ can thus be interpreted as an extensin fr cntrl gears. Althugh thse ballasts have a POWER ON LEVEL fr mains pwer up, they dn t have a predefined dim level fr bus vltage return. With the help f this feature the SYSTEM FAILURE LEVEL (which is set at a bus vltage lss) can be verruled. Slave Mde The MC+ ffers the pssibility t read ut the state f the switches and the analgue values f the inputs. Hence the mdule can be used fr evaluating analgue and digital input signals nly. Instructin Set The MC+ perates as cntrl device n the -line and transmits the predefined -cmmands when a mmentary switch is pressed. It is based n the standard fr Cntrl Gears (IEC 62386-102). In additin t the cmmands mentined abve the special cmmand fr writing the data transfer register and cmmand 47 (STORE DTR AS FADE RATE) are implemented. Furthermre the ACTIVATE cmmand and the DT8- cmmands STEP COOLER and STEP WARMER are used fr clur temperature cntrl.
4. Dimensins 5. Wiring Diagram The MC+ is cnnected t the -line. It is pwered like all mdules directly by a PS via the signal line. A typical value f the Switch current cnsumptin is <4 ma. The cnnectin t the -line is plarity free and prtected against vervltage f up t 270Vac. The cmpact MC+ can easily be installed in recessed cnduit bxes. COM T4 T3 T2 T1 Taster Eingänge Switch Inputs MC+ Tastereingangsmdul Switch Input Mdule LC-004-301 230V~ POWER L N PE L N POWER IN 230V~ PS2 Bus Strmversrgung Leuchteneinbau Bus Pwer Supply Fitting In Luminaires LC-004-150 OUTPUT max. 220mA ca.16v= Max. 64 Aktren Max. 64 Actuatrs
6. Safety warnings 6.1. T avid installed the prduct in minefield, strng magnetic field and high vltage area. 6.2. T ensure the wiring is crrect and firm aviding shrt circuit damages t cmpnents and cause fire. 6.3. Please install the prduct in a well ventilated area t ensure apprpriate temperature envirnment. 6.4. The prduct must be wrked with DC cnstant vltage pwer supply. Please check the cnsistence f input pwer with the prduct, if the utput vltage f the pwer cmply with that f the prduct. 6.5. Cnnect the wire with the pwer n is frbidden. Ensure prper wiring first then check t ensure n shrt-circuit, then pwer n. 6.6. Dn t repair it by yurself whenever an errr ccur. Cntact the supplier fr any inquiry.