Actuators SQN7... Siemens Building Technologies HVAC Products. for air dampers and control valves of oil or gas burners

Similar documents
SQN7... Actuators. Building Technologies HVAC Products

Electronic Air / Fuel Ratio Control System

ASZ... Potentiometers. Building Technologies HVAC Products. ASZxx.3x

Universal Controller

ASZ... Potentiometers. Siemens Building Technologies HVAC Products. ASZxx.7xx or ASZxx.8xx

GLB...9. Ball Valve actuators. Building Technologies HVAC Products. for valves VAI61... AC 24 V / AC 230 V

Rotary actuators for ball valves

Air damper actuators. OpenAir GDB..1E. Electronic motor driven actuators for open-close, three-position and modulating control

Rotary actuators for ball valves

Electromotoric actuators

Air damper actuators Rotary version with spring return, AC 24 V / DC V / AC 230 V

Configured air damper actuators 6FU11xx-xDxxx-xxxx

Room Temperature Controllers. for heating and cooling systems

SAT.. Electromotoric actuators for valves ACVATIX. with a 5.5 mm stroke and 300 N positioning force

Room Temperature Controllers. for heating and cooling systems

RS /M MZ SERIES

SAL.. ACVATIX Electromotoric rotary actuators for butterfly or slipper valves. with 90 rotary angle

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems

Air damper actuators. OpenAir GSD...1A. Electric motor-driven rotary actuators for open-close, three-position and modulating control

Rotary actuators for ball valves

Rotary actuators for ball valves

Outside Temperature Sensors

Room Temperature Controllers. for heating and cooling systems

Rotary actuators for ball valves

QFM21... Duct sensors. Symaro. for relative humidity and temperature

Power consumption Operation At rest Wire sizing

Servomotor for butterfly valves VF, VFH. delta-elektrogas.com EE157-01/16

NEXUS NX50-1, -2 Servo Motor Installation. Fireye DESCRIPTION SAFETY INFORMATION

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

Electromotoric actuators for stroke valves

Technical data sheet. Technical data. Safety notes

Rotary actuators for ball valves

Spring Return DuraDrive Proportional Actuator

Electronic plugs for valves MSE

Technical data. Safety notes. Power consumption In operation At rest For wire sizing

Technical data V phase cut, input impedance 8.2 k Position feedback (measuring voltage U) DC V, max. 0.5 ma Start point DC

Technical data. T2-SM230ASR en v Subject to changes / 3. Electrical data Nominal voltage AC

Power consumption In operation At rest For wire sizing

Technical data. Parameterisable damper actuator in the

AC/DC 24 V, 50/60 Hz. Functional data Variable Settings. DC V, max. 0.5 ma. End point DC V... 4 ma ma Non-variable

Technical data. Safety notes

MODUBLOC MB SE SERIES

Position switches FM series

FA-3300 Heavy Duty Electric Actuator. Features and Benefits. FA-3300 Actuator with VG8000 valve. Constant running time. Fixed close-off force.

Overview of types. Technical data

Technical data. Safety notes. T3-LR24A-SR en v Subject to changes 1 / 2

SVP CONTROL AND VISUALIZATION OF VOLTAGE, PHASE AND FREQUENCY IN THREE-PHASE LINES WITH NEUTRAL

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V. Power consumption In operation At rest For wire sizing

RS /E-EV BLU SERIES

Overview of types. Technical data. T5-NRDVX24-SR-T-.. en v Subject to changes 1 / 3

RS /E-EV BLU SERIES

SAV.. ACVATIX Electromotoric actuators for valves. with a 20/40 mm stroke

Power consumption In operation At rest For wire sizing

EMD-FL-3V-400. Electronic monitoring relay for voltage monitoring in three-phase networks. INTERFACE Data sheet _en_03. 1 Description.

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

Power supply CP-D 24/4.2 Primary switch mode power supply

GI/EMME SERIES

SAY..P.. A6V ACVATIX Electromotoric actuators for VPI46. with a 15 mm stroke

Power supply CP-D 24/1.3

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

STEP-UPS/24DC/24DC/3. Uninterruptible power supply. Data sheet. 1 Description. Features

RoHS. High shaft load capacity. Shock / vibration resistant

RS /E-EV BLU SERIES

Electronic relays. Monitoring. Monitoring

Power consumption In operation At rest For wire sizing. Auxiliary switch NRF24A-SR-S2 NRF24A-SR-S2-O

Power consumption In operation At rest For wire sizing

J7M-AM/-BM. Motor--protective circuit--breaker system. J7M -BM System IEC 947, EN IEC 947, EN 60947

Power consumption In operation At rest For wire sizing. 1.5 W at nominal torque 0.4 W 4 VA Connection Cable 1 m, 3 x 0.75 mm 2

Wireless Room Thermostat Installation and Operation Y6630D1007

Electromotoric actuators for valves

SAX.. ACVATIX Electromotoric actuators for valves. with a 20 mm stroke

Room Sensors. for relative humidity and temperature

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz

SAY..P.. A6V ACVATIX Electromotoric actuators for valves. with a 15 mm stroke

Functional data Factory settings Variable Settings

s Climatix extension module 26 I/Os POL985.00/XXX

Room Sensors. In ventilating and air conditioning plants to acquire relative humidity and temperature in rooms. Humidity measuring range

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009

Absolute encoders - SSI

SAX.. Electromotoric actuators for valves ACVATIX. with a 20 mm stroke

SAX..P. Electromotoric actuators for valves ACVATIX. with a 20 mm stroke

TeSys contactors. TeSys D contactors. IEC/EN , IEC/EN , UL 508, CSA C22.2 n 14. Protection against direct fi nger contact IP 2X

Rudder or propeller angular position transmitter KINAX WT720

Type 3374 Electric Actuator

PHOENIX CONTACT - 09/2009

Motor Protection Circuit Breaker Series 8146/5-V27

EC centrifugal fan. backward curved, single inlet

ph or ORP Transmitter

Type: DILM80(110V50HZ,120V60HZ) Article No.: Sales text Contactor,37kW/400V,AC operated. Ordering information

Instruction manual for STA 1 sectional door operator

Type: DILM95(230V50HZ,240V60HZ) Article No.: Sales text Contactor,45kW/400V,AC operated. Ordering information

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.

Power supply CP-D 12/2.1

High Performance Current Transducer IT 200-S ULTRASTAB = A. ε L

21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque

Differential pressure sensors

PHOENIX CONTACT

SAX.. ACVATIX Electromotoric actuators for valves. with a 20 mm stroke

General Installation Instructions

Transcription:

7 804 SO 900 Actuators SQN70... / SQN7... for air dampers and control valves of oil or gas burners SQN74... / SQN75... SQN7... eversible electromotoric actuators with torques up to 2.5 Nm un times: - SQN70... / SQN7... 4...30 s - SQN74... / SQN75... 4...60 s Versions: - Clockwise or counterclockwise rotation - With integrated electronic modules - Choice of drive shafts With 2 end and 2...4 auxiliary switches, some with fine adjustment Geartrain can be disengaged SQN70... / SQN7... - With adapter for direct replacement of actuators type SQN30... / SQN3... SQN74... / SQN75... - Drive shafts, fixing holes and cable entries are matched to the same type of actuator supplied by Conectron or Berger Versions with UL listing for use in the U.S. and Canada The SQN7... and this Data Sheet are intended for use by OEs which integrate the actuators in their products! Use The SQN7... actuators are designed for driving air and gas dampers of oil or gas burners of small to medium capacity and afford load-dependent control of the amount of gas, oil or combustion air in connection with single- or 2-wire control, or 3-position controllers, or directly via the burner control 09.04.2003 HVAC Products

Warning notes To avoid injury to persons, damage to property or the environment, the following warning notes should be observed! Do not interfere with or modify the actuators! Before performing any wiring changes in the connection area of the actuator, completely isolate the equipment from the mains supply (all-polar disconnection) Ensure protection against electric shock hazard by providing adequate protection for the terminals and by securing the housing cover Check to ensure that wiring is in an orderly state Fall or shock can adversely affect the safety functions. Such units may not be put into operation, even if they do not exhibit any damage ounting notes Ensure that the relevant national safety regulations are complied with nstallation notes nstallation work must be carried out by qualified staff Commissioning notes Commissioning work must be carried out by qualified staff Prior to commissioning, ensure that wiring is in an orderly state Norms and standards Conformity to EEC directives - Electromagnetic compatibility EC (immunity) 89 / 336 EEC - Low-voltage directive 73 / 23 EEC Service notes aintenance work must be carried out by qualified staff Each time a unit has been replaced, check to ensure that wiring is in an orderly state Disposal notes The actuator contains electrical and electronic components and may not be disposed of together with household waste. Local and currently valid legislation must be observed. 2/22

echanical design Housing - ade of impact-proof and heat-resistant plastic Color: SQN70... / SQN7...: Geartrain housing dark-grey, cover light-grey SQN74... / SQN75...: Completely black Drive motor Coupling Adjustment of switching points Position indication Electrical connections Geartrain Drive shaft ounting and fixing Printed circuit boards - eversible and locking-proof synchronous motor - Drive shaft can be manually disengaged from geartrain and motor - Automatic reengagement - By means of adjustable cams - Scales beside the cams indicate the angle of the switching point - Assignment of cams to the end and auxiliary switches is color-coded (refer to «Connection diagrams») - Some of the cam switches feature fine adjustment; they can be changed with a standard screwdriver - The other cams can be adjusted manually or with the enclosed hook-spanner or similar tool - nternally: Scale at the beginning of the camshaft on the geartrain side - Screw terminals - aintenance-free - ade of black-finished steel - eady fitted to the front of the geartrain - Different versions available - Front of the geartrain is used as the mounting surface - Actuator is secured via through-holes - ade of glass-fiber reinforced epoxy resin - etalized through-holes 3/22

Type summary Actuators SQN70... / counterclockwise rotation 9 ) Diagram no. Drive shaft ¹) no. un time at 50 Hz 2) for 90 s Nominal torque 6) Nm Holding torque Nm AS elays Length of AC 230 V ³) AC 0 V 4) SQN7... replaces 0) ) housing ¹) +0 % -5 % +0 % -5 % 50...60 Hz 50...60 Hz pcs. pcs. mm Type reference 8) Type reference Type reference 7) 2 0 4.5 0.7 2 2 7 SQN70.224A20 --- --- 4 0 4.5 0.7 2 3 7 SQN70.244A20 --- SQN30.2A2700 6 0 4.5 0.7 2 --- 80 SQN70.264A20 --- SQN30.0A2700 9 0 4.5 0.7 2 7 SQN70.294A20 --- SQN30.A2700 2 0 6.5 0.7 2 2 7 SQN70.324A20 --- SQN30.5A2700 2 0 2 2.5.2 2 2 7 SQN70.424A20 --- --- 5 0 2 2.5.2 2 3 7 SQN70.454A20 --- --- 6 0 2 2.5.2 2 --- 80 SQN70.464A20 --- --- 6 3 2 2.5.2 4 --- 80 SQN70.464A23 --- --- 2 0 30 2.5.3 2 2 7 SQN70.624A20 --- --- 6 3 30 2.5.3 2 --- 80 SQN70.664A23 --- SQN30.40A2730 Actuators SQN7... / clockwise rotation 9 ) Diagram Drive shaft ¹) un time at 50 Hz ²) for 90 Nominal torque 6) Holding torque AS 0) elays ) Length of housing ¹) AC 230 V ³) +0 % -5 % 50...60 Hz AC 0 V 4) +0 % -5 % 50...60 Hz SQN7... replaces no. no. s Nm Nm pcs. pcs. mm Type reference 8) Type reference Type reference 7) 2 0 4.5 0.7 2 2 7 SQN7.224A20 --- SQN3.5A2700 6 0 4.5 0.7 2 --- 80 SQN7.264A20 --- SQN3.0A2700 2 0 2 2.5.2 2 2 7 SQN7.424A20 --- --- 6 0 30 2.5.3 2 --- 80 SQN7.664A20 --- SQN3.40A2700 Actuators SQN74... / counterclockwise rotation 9 ) Diagram Drive shaft ¹) un time at 50 Hz ²) for 90 Nominal torque 6) Holding torque AS 0) elays ) AC 230 V ³) +0 % -5 % 50...60 Hz AC 0 V 4) +0 % -5 % 50...60 Hz no. no. s Nm Nm pcs. pcs. Type reference 8) Type reference 9 4.5 0.7 2 SQN74.294A2 --- Actuators SQN75... / clockwise rotation 9 ) Diagram Drive shaft ¹) un time at 50 Hz ²) for 90 Nominal torque 6) Holding torque AS 0) elays ) AC 230 V ³) +0 % -5 % 50...60 Hz AC 0 V 4) +0 % -5 % 50...60 Hz no. no. s Nm Nm pcs. pcs. Type reference 8) Type reference 2 4.5 0.7 2 2 SQN75.224A2 --- 2 6 4.5 0.7 4 2 SQN75.224A26 --- 4 4.5 0.7 2 3 SQN75.244A2 --- 4 6 4.5 0.7 4 3 SQN75.244A26 --- 9 4.5 0.7 2 SQN75.294A2 --- 9 4.5 0.7 4 SQN75.294A26 --- F 4.5 0.7 4 3 SQN75.2F6A2 --- 2 2 2.5.2 2 2 SQN75.424A2 --- 2 6 23 2.5.2 4 2 SQN75.524A26 --- K 30 2,5,3 2 --- SQN75.6K4A2 SQN75.6K4A 6 3 30 2.5.3 4 --- SQN75.664A26 --- 9 30 2.5.3 2 SQN75.694A2 --- 4/22

Legend to «Type summary» ¹) efer to «Dimensions» ²) At 60 Hz, run times are about 20 % shorter ³) AC 220...240 V +0 % / -5 % possible, but in the case of undervoltage torque is reduced by about 20 % 4 ) AC 00...20 V +0 % / -5 % possible, but in the case of undervoltage torque is reduced by about 20 % 6 ) Under nominal conditions; under extreme conditions (e.g. +60 C, AC 230 V 5 %) approx. 25 % 7 ) efer to «eplacement of SQN30... / SQN3...» 8 ) Actuator types in normal printing and other types are available on request 9 ) When facing the drive shaft and when control voltage is present at end switch 0 ) Auxiliary switches (in addition to the 2 end switches) ) ntegrated relays Ordering When ordering, please give type reference of actuator and accessories according to «Type summary». Following item must be ordered separately and is also supplied as a separate item: Adapter AGA70.3 for replacing SQN3... Accessories Adapter AGA70.3 Not suited for use with SQN74... / SQN75...! For mounting the SQN70... / SQN7... in place of the SQN3...; fitted to the SQN70... / SQN7... with a self-tapping screw. Screw and washer are included in the supply. 5/22

Technical data General actuator data Actuator ains voltage AC 230 V 5 % +0 % AC 0 V 5 % +0 % ains frequency 50...60 Hz ±6 % Safety class - SQN70... / SQN7... to VDE 063 - SQN74... / SQN75... to VDE 063 Drive motor synchronous motor Power consumption 6 VA On time 60 %, max. 3 min. continuous operation Angular adjustment max. 60, scale range 0...30 ounting position optional Degree of protection - All types P 40 to DN 40050, provided adequate cable entries and fixing screws are used - SQN74... / SQN75... Cable entry - SQN70... / SQN7... - SQN74... / SQN75... Cable connections Ferrules Direction of rotation Nominal and holding torque un times - SQN70... / SQN7... - SQN74... / SQN75... Coupling Backlash between drive motor and drive shaft - As supplied - After 250,000 cycles Weight (average) P 20 to DN 40050, provided lateral knockout hole for cable is used insertable cable gland holder with thread for 2 x Pg9, no locknut required openings for locknut for fixing cable glands Type of locknut x Pg9 Pg9 DN 46320 S x Pg Pg9 DN 46320 S additional lateral knockout hole for lose introduction of 2 cables with a max. dia. of 6 mm, cable strain relief to be provided by the user (also refer to «Degree of protection»). Pg glands and locknuts are not part of the delivery. screw terminals for min. 0.5 mm² and max. 2.5 mm² cross-sectional area matching the dia. of the stranded wire refer to «Type summary» refer to «Type summary» 4...30 s for 90 4...60 s for 90 disengagement of drive shaft / geartrain with a pin.2 ±0.3.5 ±0.3 approx. 500 g 6/22

Technical data (cont d) End and auxiliary switches Number of end switches 2 Number of auxiliary switches SQN70... / SQN7......2 SQN74... / SQN75... 2...4 Actuation via camshaft, color-coded cams (refer to «Connection diagrams» Breaking voltage Perm. loading on terminals at cos ϕ = 0.9: Connection diagram 0 Terminals, 2, 3, 4 Terminals 5, 6, 7 Connection diagram Terminals, 2, 6, 7 Terminals 3, 4 Connection diagram 2 Terminals, 2, 3 Terminal 4 Terminal 5 Terminal 6 Terminal 7 Terminal 8 Connection diagram 3 Terminals, 2, 3, 8, Terminals 4, 5, 7, 0 Connection diagram 4 Terminals, 3 Terminal 4 Terminal 5 Terminal 6 Terminal 7 Terminal 8 Connection diagram 5 Terminals, 2, 3 Terminal 4 Terminal 5 Terminal 6 Terminal 7 Terminal 8 Connection diagram 6 Terminals, 2, 3, 4, 5 Terminal 6 Terminal 7 Terminal 8 Connection diagram 9 Terminals, 2, 3, 4, 5 Terminal 6 Terminal 7 Terminal 8 Connection diagram F Terminals 2...7 Terminals, 8, 9 switches with fine adjustment - SQN70... / SQN7... : and - SQN74... / SQN75... : and V AC 24...250 V 2 A (4 A) ¹) 2 A (4 A) ¹) 3 A (4 A) ¹) 3 A (4 A) ¹) 2 A (4 A) ¹) 2 A (4 A) ¹) 7/22

Connection diagram K Terminals, 2 Terminals 3, 4, 5, 6,7,8 ¹) Amperages in parentheses are permitted as short-time peak loads for max. 0.5 seconds Adjustment of cams - Without fine adjustment - With fine adjustment infinitely Norms and standards Environmental conditions Transport DN EN 60 72-3-2 Climatic conditions class 2K2 echanical conditions class 22 Temperature range -50...+60 C Humidity < 95 % r.h. Operation DN EN 60 72-3-3 Climatic conditions class 3K5 echanical conditions class 32 Temperature range -20...+60 C Humidity < 95 % r.h. Condensation, formation of ice and ingress of water are not permitted! Function The synchronous motor drives the drive shaft which carries the camshaft. The camshaft actuates the end and auxiliary switches. Using the associated cam, the switching position of each end and auxiliary switch can be adjusted within the working range. Some of the actuator versions are equipped with electronic modules that perform auxiliary functions in connection with the end and auxiliary switches or with external devices, such as controllers (refer to «Connection diagrams»). The functions and technical data of both lines of actuators SQN70... / SQN7... and SQN74... / SQN75... are nearly identical. eplacement of SQN30... / SQN3... Using an adapter (refer to «Accessories»), actuators type SQN30... and SQN3... can be replaced by the SQN70... / SQN7.... There are no mechanical modifications required. The different terminal assignments of the 2 types of actuators must be observed, however. The «Type summary» contains the SQN3... that can be replaced by SQN7...actuators. The SQN30... and SQN3... listed in «Type summary» refer to the SQN7... AC 230 V versions. The respective SQN3... AC 0 V versions use the same type reference as the AC 230 V versions, with one exception: Type suffix..a27.. is replaced by..a7... are versions with no facility for fitting a potentiometer (refer to Data Sheet 7808) 8/22

Connection diagrams 2-stage operation Prepurge at low-fire position <KL> (see <S5>) GP LOA... / LO... AL 3) 2 0 8 OW OH ) 3 7 6 4 5 2 2) QB Z S2) SB GP /W OH OW FS SB HS N 8 4 5 3 2 7 6 00 % min. 0 % 0 N L a B A SQN7x.x44xxx b c b2 a2 C 7804a0/0502 V 4 LKP NL KL zu S4) S5) t TSA t4 V V 7804d09/0 t 7804d2/00 Nr. 4 LOA24.7.../LOA24.73.../LOA24.74.../LOA24.57.../LOA25.../LOA26... LOA28.../LOA36.../LO24.../LO44... LOA... / LO... A B C D tw t t4 LK V ed Blue Orange V Black For notes on <S...S5> refer to <Notes on connection diagrams> ) Without oil preheater 2) efer to Data Sheet 78 3) LOA... / LO... with oil preheater: f contakt <OW> opens during operation, there will be a complete new start 9/22

Connection diagrams (cont d) LOA... / LO... 2 0 8 OW 3 7 6 4 5 2 2) QB SB GP /W LOA... / LO... A B C D t t4 GP OH Z AL S2) V FS 00 % HS N 8 0 SB 2 3 4 5 7 6 LK min. 0 % c N L LKP NL C SQN7x.x94Axxx 7804a07/0502 V 9 7804d02/202 Nr. 9 LOA... / LO24.../LO44... 2-stage operation Prepurge at low-fire position <KL> (see <S5>) ) ) Program sequence without oil preheater ) Voltage at terminal no. 8 of the SQN7... 2) efer to Data Sheet 78 V KL S5) V ed Blue Orange V Black zu* t TSA t4 7804d3/0 * When burner is <OFF>, the air damper maintains position <KL>. No <Damper CLOSED> position, refer to notes on connection diagrams <S3>. Connection diagram no. 4 LOA... / LO... used the same function with air damper closed when burner is <OFF>. t For notes on <S...S5> refer to <Notes on connection diagrams> 0/22

Connection diagrams (cont d) 0 HS GP 2 0 8 3 6 9 5 7 EK2 2 Z 4 FE N 4 5 3 2 8 6 7 b2 N L A a SQN7x.x24xxx b a2 B 7804a04/0502 7804d03/00 Nr. 2 LGB22... / LGB32... and LG22... 2-stage or modulating operation Prepurge at nominal load position <NL> LGB 22 / 32... LG 22... 2 AL LP S) GP/SB /W LP LGB22... / LGB32... / LG22... A B C D tw t FS SB LK V 9 00 % min. 0 % ed Blue Orange V Black V 2 Program sequence diagrams show 2-stage operation. For modulating operation, refer to <S>. LKP NL KL zu t TSA V V 7804d07/090 t t4 For notes on <S...S5> refer to <Notes on connection diagrams> /22

Connection diagrams (cont d) 0 HS GP LGB 22 / 32... LG 22... 2 2 0 AL 8 EK2 3 6 LP 5 9 7 Z 4 FE SB N 5 4 3 2 8 6 7 b2 a c N L LKP NL C A 7804a03/0502 7804d04/00 Nr. 5 LGB22... / LGB32... and LG22... 2-stage operation Prepurge at nominal load position <NL> S2) 2 SB GP /W LP FS 2 LGB22... / LGB32... / LG22... A B C D tw t LK V 9 00 % min. 0 % ed Blue Orange V Black SQN7x.x54xxx b a2 B V 5 KL zu t TSA For notes on <S...S5>, refer to <Notes on connection diagrams> t4 V V 7804d0/090 t 2/22

Connection diagrams (cont d) HS 0 LGB 2... LG 2... / 22... / 25... 2 2 0 8 3 EK2 LP 6 9 7 4 * Z 5 FE AL GP S2) FS N 8 4 5 3 2 7 6 b2 LKP N L a NL c KL B A SQN7x.x44xxx b a2 C 7804a02/0502 7804d02/00 Nr. 4 LGB2... / LG2... 2-stage operation Prepurge at low-fire position <KL> (see <S5>) GP/SB /W Z LGB2... / LG2... / LG22... / LG25... A B C t SB LK V Auf Zl/Kl Zu V V S5) ed Blue Orange V Black V 4 zu t TSA 7804d08/0 t4 t * equired only with LGB2... For notes on <S...S5>, refer to <Notes on connection diagrams> D 3/22

Connection diagrams (cont d) HS 0 LFL... / LGK6... / LAL... / LOK6... 2 9 20 0 8 8 9 2 A Z SB S) * V* V LK* FS t 00 % min. 0 % S) N 2 3 4 5 7 6 8 N L 7804a06/0502 7804d06/090 Nr. 6 LFL... / LGK6... / LAL... / LOK6... 2-stage or modulating operation Prepurge at nominal load position <NL> LFL... / LGK6... / LAL... / LOK6... B C D * odulating Program sequence diagrams show modulating operation. For 2-stage operation, refer to <S> LKP NL KL ed Blue Orange V Black SQN7x.x64xxx V 6 zu t TSA For notes on <S...S5>, refer to <Notes on connection diagrams> t4 7804d/090 t 4/22

Connection diagrams (cont d) LFL... / LGK6... / LAL... / LOK6... 2 9 9 20 0 8 8 2 A B Z SB S2) FS t LKP NL HS N 8 2 0 c N L 3 4 5 7 6 C V 7804a05/0502 7804d05/090 Nr. 9 LFL... / LGK6... / LAL... / LOK6... 2-stage operation Prepurge at nominal load position <NL> LFL... / LGK6... / LAL... / LOK6... LK V 00 % min. 0 % KL zu t TSA t4 V V 7804d0/090 t ed Blue Orange V Black SQN7x.x94xxx 9 For notes on <S...S5>, refer to <Notes on connection diagrams> C D 5/22

Connection diagrams (cont d) 7804d9/202 Nr. F LAL... / LFL... 3-stage operation Prepurge at stage 3 LFL... / LAL... ) LFL... / LAL... A B C D 2 4 4 3 2 5 9 20 0 8 9 8 2 SB W LP ϑ ST.2 ST. Z ST. ST. ST.2 ϑ ST.3 ST.3 C BV3 HS 0 N L c BV3 N 7 5 6 4 3 8 9 2 B b a LK 0% FS V V V t Diagram not possible with SQN70... / SQN7... LKP ST.3 V ST.2 V ST. ZU** t t BV3 V For notes on <S...S5>, refer to <Notes on connection diagrams> 7804d20/202 ed Blue Orange V Yellow V Black V Green ST...3 Stage...3 b2 a2 A SQN75.2F6xxx A S4) 7804a4/0403 F 6/22

Connection diagrams (cont d) TG740 TO720 8 3 4 9 5 b / 2** 4 6 NL 2 N 7 6 5 2 3 4 8 L2 B SQN74.x5xxx SQN75.x5xxx b a a A a2 7804a09/202 b a b a * V V NL KL zu V resp. 6 * ed Blue Orange V Orange V Black Nr. TG740 / TO720 2-stage operation Prepurge at nominal load position <NL> TG... / TO... are devices of other manufacture; they are neither made nor supplied by us. The combination with our actuator proposed here must be checked with the supplier of the TG... / TO... while taking into consideration safety aspects and the current version of the burner control. The user assumes full responsibility for this application. Wiring diagram no. corresponds to wiring diagram no. 3 of the SQN3... Application only possible with SQN74... / SQN75... LKP V V V 7804d6e/0403 * Cams and V are rigidly connected V V t ** TO720 terminal no. 6 TG740 terminal no. 2 For notes on <S...S5>, refer to <Notes on connection diagrams> 7/22

Connection diagrams (cont d) Nr. 0 fi Universal use N 3 2 4 6 5 7 ed Blue Orange SQN7x.x03xxx 0 7804a0/0 Nr. K fi Universal use N N 2 3 4 5 7 6 8 ed Blue Orange V Black SQN7x.xK4xxx V K 7804a/0 For notes on «S...S5», refer to «Notes on connection diagrams» 8/22

Legend No. 2 Number corresponds to the designation number or letter of the internal circuit of the SQN7... (second character after the dot in the type code) AL emote indication of fault (alarm) Fuel valve stage Fuel valve stage 2 BV3 Fuel valve stage 3 EK2 External remote reset button FE onization probe FS Flame signal amplifier GL Air / gas ratio controller GP Gas pressure switch HS ain switch KL Low-fire L Live LK Air damper LKP Air damper position LP Air pressure switch Load controller (also refer to «S») Burner or fan motor Actuator s drive motor Without postpurge 2 With postpurge N Neutral conductor NL Nominal load OH Oil preheater OW Oil preheater s readiness contact QB... Photoresistive flame detector Temperature or pressure controller elay V Controller damper SA Actuator Fuse SB Safety limiter ST... Stage t... / T... Program time (refer to the Data Sheet of the relevant burner control) TSA Safety time esistance Z gnition transformer ZU Damper fully closed Direction of rotation OPEN Direction of rotation CLOSE Program sequence diagrams A Burner ON A B Startup of burner B C Burner operation / load control operation, modulating or 2-stage C Burner OFF C D Overrun time D End of program, burner control ready for new start 9/22

Notes on connection diagrams S) Controller for: 2-stage operation Burner control 7804a2e/0402 Thermostat or similar, with changeover contact (2-wire control). n place of, it is possible to use a control damper that is rigidly connected to the air damper (shown in broken lines). SA V odulating operation Burner control SA 7804a3e/0402 load controller for temperature or pressure control Type WF40... Digital PD universal controller for temperature or pressure control 2-stage or modulating operation, and with special functions for heat generation plant (refer to Data Sheet 7865) LK GL V 3-position controller for OPEN / CLOSE positioning pulses with neutral position in between (2-wire control). is not used. Air / gas ratio control is used instead. This can be accomplished in the form of a control damper «V» that is rigidly connected to the air damper, or an air / gas ratio controller «GL» type SKP70... (refer to Data Sheet 765) that if combined with safety shutoff is used in place of (shown in broken lines) S2) S3) S4) Thermostat or similar with N.O. contact (single-wire control). n heating systems where the air damper does not fully close in the case of burner OFF, thermal uplift occurs in the flueways (boiler, stack), causing the boiler to cool down rather quickly, thus giving rise to increased heat losses. f, during the program sequence, a damper position switch is approached from both sides, it is not actuated in the same damper position, due to the switching differential. To ensure that actuation takes place in the same position, the program sequence makes certain the required damper position will be passed for a short period of time. S5) The prepurge rate of the heat generation system (boiler, stack, etc.) prior to establishment of the flame must be in compliance with country-specific regulations. As a general rule, the prepurge rate with oil burners should be 3 times the volume of the heat generation system, and with gas burners, 5 times that volume. But these are only guide values. The effective prepurge volume required depends primarily on the type of construction of the heat generation system and is entirely the responsibility of the manufacturer of that system. f prepurging is selected for the low-fire position, the prepurge time is to be appropriately extended (against prepurging for the nominal load) to attain the required air volume. For supplementary connections on the burner controls, refer to the relevant Data Sheets For auxiliary switches with fine adjustment, refer to «Technical data» n the connection diagrams, the positions of the end and auxiliary switches...v in the actuator for the working range are shown between 0 and the adjusted angular position of the cams, that is, in the start position 20/22

Dimensions Dimensions in mm SQN70... / SQN7... 6 AGA70.3 36 26 24 24, 6 T ø 5,3 90, 66,5 7804m0e/0502 6 ø 2xPg9 4) > = 65 x 3/8" adapter (connector) 5) for U.S. and Canada 8 22 80 2) 7 2) > = 05 2 33 66 Drive shaft versions Side view Drive shaft versions Cross-section ) Drive shaft no. 7 8 h9 45 25 7 0 0.05 0 +0,05 5 0 6,5 0 h9 3 3) 6 25 +0,03 8 0,09 3 25 9,5 +0,08 - +0,05 3 0 9 ) Drive shafts are shown in their fully closed position (voltage present at end switch ) Drive shaft no. is identical with the 6th character after the dot in the type reference Example: SQN70.664A23 = drive shaft no. 3 2) Length of housing depends on the type of actuator (refer to «Type summary») 3) Center slot: 6.3 mm deep Hole dia. 5. mm: 6.5 mm deep (including depth of center slot) 4) Not part of the delivery 5) Supplied with types SQN7x.xxxxx Fixing positions matched to SQN3... (for -to- replacement by SQN70... / SQN7..., use AGA70.3) Through-hole 5.3 mm dia. T Knockout hole 5.3 mm dia. 2/22

Dimensions (cont d) Dimensions in mm SQN74... / SQN75... 6 Pg9 30,5 9 9,5 Pg ø4 6 A 03,5 26 26 A 7804m02e/0402 04,5 5 65 > = 00 Drive shaft version Side view Drive shaft version Cross-section ) Drive shaft no. 90 7 76,5-0,09 3,5 0 0,05 25 8 h9 ) Drive shaft shown in fully closed position (voltage present at end switch ) A Knockout hole for lose cable entry Through-hole 5.3 mm dia. Fixing positions matched to Conectron LKS 60 and Berger STA Pg nuts, not part of the delivery (for type reference, refer to «Technical data») 22/22 2003 Subject to change!