Partial Discharge Monitoring of Power Transformers by UHF Sensors

Similar documents
Application of UHF Sensors for PD Measurement at Power Transformers

Parameters influencing Partial Discharge Measurements and their Impact on Diagnosis, Monitoring and Acceptance Tests of Power Transformers

Automated PRPD Pattern Analysis using Image Recognition

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS

Diagnostic testing of cast resin transformers

PD Solutions. On-Line PD Measurement Devices

Open Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer

APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS

Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

MONTRANO. Continuous monitoring system for power transformers

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

Mots clés Power Transformer, Condition Assessment, On-line Monitoring Internet. Par S. Tenbohlen *, T. Stirl, M. Rösner * * ALSTOM T&D, Germany

UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES

Autotransformer Condition Monitoring Systems

TECHIMP Power Transformer Monitoring

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages

OMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon

Why partial discharge testing makes good sense

PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS

Partial Discharge Monitoring and Diagnosis of Power Generator

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

- Continuous real-time measurement and PD trend analysis; not multiplexed data collection.

The importance of partial discharge testing throughout the development and operation of power transformers

Performing reliable and reproducible frequency response measurements on power transformers

State of the Art and Future Trends of Unconventional PD-Measurement at Power Transformers

Power Transformer Condition Assessment Based on Standard Diagnosis

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

NETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

Partial discharge diagnostics on very long and branched cable circuits

KEYWORDS On-line diagnostics, cable termination, partial discharge (PD), ultra-high frequency (UHF), sensitivity check.

Practical aspects of PD localization for long length Power Cables

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

ABB Power Products Service

New Techniques for the Monitoring of Transformer Condition

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission

DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER

Doble Solutions for Partial Discharge. Greg Topjian Solutions Manager

ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS

IN ELECTRICAL ENGINEERING - I C M E T CRAIOVA

Why is water killing power transformer insulation? Water is a slow but deadly poison for power transformers

Comparison of capacitive and inductive sensors designed for partial discharges measurements in electrical power apparatus

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

Maintenance & Diagnosis Strategies. for. High Voltage Substations

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Partial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor

PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics

Software System for Finding the Incipient Faults in Power Transformers

Revision of C Guide for Application of Monitoring Equipment to Liquid Immersed Transformers and Components. Mike Spurlock Chairman

Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

The Generators and Electric Motor Monitoring and Diagnostics Systems

The Application of Partial Discharge Measurement and Location on CGIS

Sources of transient electromagnetic disturbance in medium voltage switchgear

MPD 600. High-End Measurement and Analysis System for Partial Discharges (PD)

Transformer Shunt Fault Detection using Two Techniques

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

MPD 500. Partial Discharge Measuring System for Routine Test Applications

Advanced Test Equipment Rentals ATEC (2832)

USING DAMPED AC VOLTAGES

PARTIAL DISCHARGE DETECTION - AN OVERVIEW

Testing of 400 kv GIS

HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL. Huazheng Electric Manufacturing(Baoding) Co.,Ltd

NEW APPROACH FOR HIGH VOLTAGE CABLE ON-SITE TESTING

Design of Meander Antenna for UHF Partial Discharge Detection of Transformers

INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES

IRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.

PARTIAL DISCHARGE MEASUREMENT

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Effective maintenance test techniques for power transformers

Evaluation of Partial Discharge in Power Transformers by Acoustic Emission Method and Propagation Modeling of Acoustic Signal

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

PRY-CAM BREAKTHROUGH TECHNOLOGY FOR CONDITION ASSESSMENT AND ASSET MANAGEMENT

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

IRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

Transformer condition assessment with an integrated test van

Electrical Equipment Condition Assessment

Detektion und Ortung von Teilentladungen durch UHF Messmethode Detection and localization of partial discharges with UHF measuring method

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH

Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and Waveform Characteristics

PD Testing Considerations for MV Plant Cables

PD Diagnostic Applications and TechImp solutions

Diagnostic measurements on instrument transformers. Part II. A classification and overview of diagnostic measurements DIAGNOSIS EVENTS ABSTRACT

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES

HV AC TESTING OF SUPER-LONG CABLES

SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE

Coherence and time-frequency analysis of impulse voltage and current measurements

We can classify test failure modes in power transformers according to transformer components

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

Benefits of SFRA - Case Studies

MPD 600. High-end measurement and analysis system for partial discharges

Transcription:

Partial Discharge Monitoring of Power Transformers by UHF Sensors S. Tenbohlen 1, M. Siegel², M. Beltle² 1 Institute of Power Transmission and High Voltage Technology (IEH), University of Stuttgart Pfaffenwaldring 47, D-70569 Stuttgart, Germany e-mail: stefan.tenbohlen@ieh.uni-stuttgart.de ²BSS Hochspannungstechnik GmbH Hohenheimer Str. 9, D-70184 Stuttgart, Germany e-mail: martin.siegel@bss-hs.de, michael.beltle@bss-hs.de Abstract The reliability of electrical energy networks depends on both, the quality and the reliability of its electrical equipment, e.g. power transformers. Local failures inside their insulation can lead to breakdowns and hence to high outage and penalty costs. Usually, power transformers are tested on partial discharge (PD) activity before commissioning. UHF PD monitoring can be used to prevent these events during service. Continuous monitoring exceeds the benefits of singular diagnostic measurements. Diagnostic PD measurements can provide snapshot information but no trend information. Also, temporary measurements can cause misleading interpretations due to the volatile nature of PD as measurements performed during low PD activity do not prove the general absence of PD. These drawbacks can be avoided by using continuous PD monitoring. In the first part, this contribution presents two different types of ultra-high frequency (UHF) sensors for PD measurement and their installation at power transformers including an UHF PD monitoring system. The second part is about a use case providing three years of UHF PD monitoring data of a power transformer, where the PD data is correlated with the transformer s load, temperature and the dissolved gas analysis. Keywords Power Transformers, Monitoring, Partial Discharge, UHF Sensors I. INTRODUCTION Power transformers can be considered as an essential part concerning the reliability of the electrical grid. Hence, the reliable operation of power transformers is important for supply security because transformer failures tend to lead to significant damage with accordant costs. Therefore, all kinds of internal damages should to be recognized as early as possible. Different diagnostic methods have been established to meet the deriving demands for on- and offsite measurements [1]. Partial discharges (PD) measurement for example has been developed to detect local defects in the insulation that can be initiated and enlarged by the destructive nature of PD. Mainly, there are three different ways of PD monitoring: indirect detection by dissolved gas analysis (DGA), directly by either electrical PD measurements according to IEC 60270 [2] or by electromagnetic measurements in the ultra-high frequency range (UHF: 300 MHz 3 GHz) [3]. As DGA only provides an indication about PD being active, an increasing number of transformers are monitored using one of the direct measurement methods. PD measurement is suitable to detect damages in the insulation of power transformers at an early stage and thereby helps minimizing the risk of failure [4]. Its importance is accommodated by standardized electrical measurement according to IEC 60270 which is required for acceptance certificates at routine testing. The apparent charge Q IEC has become an indicating factor for transformer quality. Especially in terms of monitoring and onsite diagnostic measurements, the electromagnetic UHF method gains in importance [5]. The electromagnetic emission of PD is measured using an UHF antenna which is inserted into the transformer tank. The generalized propagation paths of the methods are shown in Figure 1. Electrical signals travel through the galvanic coupling along the winding and are decoupled at the measurement capacity of the bushing (for online monitoring) or with an external coupling capacitor (not shown). Electromagnetic signals are not bound to the galvanic coupling and can radiate directly through the oil filled transformer. Usually, UHF PD measurements are shielded electromagnetically against external disturbances due to the Faraday shielding of the transformer tank [6] and low-pass filters provided by high voltage bushings. Therefore, UHF is less sensitive to external interferences compared to the electrical method. This creates an advantage for measurements in noisy environments, for example at on-site/online measurements and for monitoring. Cigré Working Group WG A2-27 recommends in brochure 343 to install DN50 valves in order to ensure highest flexibility for the later fitting of UHF probes. Alternatively, dielectric windows can be used for UHF sensors [7]. UHF sensors for installation at DN50 valves and dielectric windows are presented in the next chapter. 1

Corona Electrical PD (IEC 60270) Internal PD UHF Sensor UHF PD II. UHF SENSORS Figure 1 Signal propagation of UHF and conventional PD measurement at a power transformer with internal PD (red) and external PD (blue) [8] An UHF sensor for power transformers consists of a broadband antenna suited for the UHF frequency range radiated by PDs and of its mechanical adaption for the installation at power transformers. Mainly two UHF sensor technologies for internal PD measurement at transformers are used for practical applications. a. UHF DRAIN VALVE SENSOR An UHF drain valve sensor is designed as retrofit solution for transformers which have standardized DN50 or DN80 gate valves, see Figure 2 a). A standardized gate valve with straight duct where an UHF drain valve sensor can be installed is shown in Figure 2 b). Ball and guillotine valves can also be used for sensor installation. Figure 2 c) demonstrates a counterexample that is not suitable for drain valve sensor application. It illustrates a globe valve without straight opening. Other valve types without straight opening (diaphragm and butterfly valves) are also popular in some regions. As they are not applicable for UHF sensor installation, it is recommended to use only straight opening valves at new transformers. a) b) c) Gate valve straight opening Globe valve without straight opening Figure 2 a) UHF drain valve sensor for installation at standardized DN50/DN80 gate valves [9] b) Gate valve as example for oil valves suited for UHF sensor installation c) Globe valve as example for oil valves not suited for UHF sensor installation Sensor application can be done even at transformers in service. At first, the UHF sensor is mounted on the valve. Secondly, the valve is opened slowly and de-aerated by a small ventilation valve on the sensor s mounting plate. Afterwards, the oil valve can be opened completely in order to insert the sensor into the transformer tank. The head of UHF sensor (the RF antenna) has to reach into the transformer for sufficient sensitivity. Usually, an insertion depth of approx. 50 mm has been proven as reasonable value. An installation of the RF antenna inside the pipe of the gate valve leads to low sensitivity due to electromagnetic shielding [3]. Besides sensitivity considerations, a minimum distance between UHF sensor and parts on high potential must be preserved to ensure save operation. UHF drain valve sensors are mainly used during diagnostic measurements on-site because their design allows them to be installed at power transformers in service. Nevertheless, permanent installation as part of an online PD monitoring system is possible as well. 2

b. UHF PLATE SENSOR UHF plate sensors as shown in Figure 3 a) can be mounted directly to the tank wall which is suitable e.g. for newly built transformers. A dielectric window is integrated into the tank wall. It consists of a stainless-steel welding ring and a high-performance plastic which resists mineral oil and high temperatures. The plastic has a permittivity similar to mineral oil which allows UHF signals to pass through to the UHF sensor with low damping. The plate sensor is mounted into the dielectric window. Its RF antenna reaches into the transformer tank through the window that acts as oil barrier. In contrast to the drain valve sensor, plate sensors allow UHF measurements and sensor swapping without oil handling. Figure 3 b) shows a dielectric window and welding ring for installation at transformer tank walls. Plate sensors can be included into the transformer tank at any suited position. Even if no sensors are installed at the delivery of a transformer, oil-sealed dielectric windows with a blank cover can be mounted onto the tank wall during production to allow an easy retrofit of UHF PD monitoring during service. In Figure 3 c), a test installation of three UHF plate sensor prototypes at a power transformer is shown. a) b) c) Figure 3 a) UHF plate sensor for direct installation at transformer tank wall [9] b) 3-dimensional drawing of welding ring (left), dielectric window with gasket (middle) and UHF plate sensor (right) [9] c) Test installation of UHF plate sensor prototypes at a power transformer III. UHF MONITORING SYSTEM This chapter presents a synchronous 4-channel UHF monitoring system which can be used to either monitor one transformer with up to four UHF sensors or up to four transformers with each only one UHF sensor in a substation. Figure 4 shows the monitoring system with one UHF drain valve sensor installed at a transformer. Figure 4 UHF monitoring system installed at a transformer with UHF drain valve sensor at a DN50 gate valve The 4-channel monitoring system uses a vertical resolution of 12 bit per channel. It is able to synchronously detect UHF signals between noise level at approx. U noise = 1 mv and U max = 2000 mv at all 4 channels. The phase resolution in 50 Hz and 60 Hz systems is φ = 1. Therefore, detailed phase resolved partial discharge patterns (PRPDs) can be recorded for expert evaluation [10]. A trend view of UHF amplitude and PDs/min is provided for long term evaluation and correlation with other measured values (voltage, load, temperature). A more detailed trend view can be used for tracing of PD patterns: a time-resolved PRPD pattern allows recognizing changes in PRPDs in direct correlation with other measured values. A description of this timeresolved PRPD including example is given in the next chapter. 3

The UHF monitoring system is connected to a server or a desktop PC via Ethernet for storage and evaluation. The monitoring system can be accessed easily by a graphical user interface (GUI) used for system parametrization (including alarm/warning thresholds) and visualization of the measured real-time data. Figure 5 shows a screenshot of the UHF PD monitoring GUI. Real-time UHF PRPDs (left) and trend views (right) of two UHF sensors are presented. All diagrams can be parametrized and exported into standard images (jpg-files) either for single measurements or periodically (e.g. a snapshot can be exported every hour). Alarm thresholds can be defined for signal amplitude and counted PDs per interval. The trend data can be exported to csv-files for post-correlation with other operational data (e.g. on load tap changer (OLTC) position). There is also the option to reimport historical trend data for replay and PRPD generation. The provided toolset can assist asset managers to surveil and evaluate the actual status of transformers in service. It also helps PD experts for a better understanding of PD failures by continuous observing of PD and possibility of correlation to other measured data. Figure 5 GUI of UHF PD monitoring software with real-time visualization of PRPD and trends (screenshot) [8] IV. USE CASE: 120 MVA GENERATOR STEP-UP-UNIT This use case presents PD monitoring data of an approx. 50-year-old unit generator transformer with 110/10 kv rated voltage and 120 MVA rated power, which is by now monitored for more than six years. Prior to this, the transformer was out of service for 8 years. A condition assessment before bringing the unit back into service indicated PD: conventional PD measurements according to IEC 60270 were performed using external coupling capacitors. PRPD patterns indicated that the transformer has more than one active PD at nominal voltage. Due to the lack of common rules and threshold values for aged transformers, it was decided that the unit can only be put back into service if it is monitored continuously. For permanent observation of PD data, an online UHF PD monitoring system with an UHF drain valve sensor was installed. Furthermore, voltages, load currents, top-oil/ ambient temperatures, mechanical vibrations and dissolved gases (using a Hydran sensor) were recorded. The PD trend is used as indicator if the insulation defects are getting worse. PRPD monitoring data confirms the presence of more than one PD source. The PDs are not present permanently at constant voltage conditions. As the measured PDs show no clear trends, alarm thresholds are set slightly over the normal PD behavior. Alarm parameters are given by the maximum signal amplitude of UHF PD (in mv) and by the counted PD events per minute. 4

Amplitude / mv Hydran value / ppm Amplitude / mv Phase ARWtr2016 The following represents a case with exceeded alarm levels. Figure 6 a) shows a UHF PRPD pattern and Figure 6 b) PRPD data over time whereas the color gradient in a) represents the number of recorded PD per minute and in b) the UHF amplitude in mv. a) b) # PDs Amplitude / mv Phase Time / min Figure 6 a) UHF PRPD (240 min 420 min in b)) b) 2-dimenisonal simplification of time domain PRPD (no #PDs shown) The UHF PRPD pattern in Figure 6 a) shows the PRPD data from Figure 6 b) from t 1 = 240 min to t 2 = 420 min. High UHF signals occur in this timeframe which triggered the amplitude alarm of the system. During the observation of the event, the amplitude and number of PDs stayed constant and did not worsen so it was decided to keep the transformer in service. After 3 h of high amplitudes, the PD event vanished and PD activity normalized. The measured combined dissolved fault gases represented by the Hydran value started to increase approx. 4 h after the PD event was over. Figure 7 shows the trend view of the PD amplitude correlated to the Hydran value. Hydran Gaswert / ppm Amplitude / mv 40 30 20 10 0 200 150 100 50 0 240 300 360 420 480 540 600 660 720 780 840 900 Time Zeit / min / Minuten 240 300 360 420 480 540 600 660 720 780 840 900 Time Zeit / min / Minuten Figure 7 Max. UHF PD value (in mv) correlated with Hydran value (in ppm) The alarm threshold for the fault gas value was exceeded approx. 7 h after the PD event started. This delay between generating H 2 and the increased values at the gas sensor is due to the gas solubility and dispersion in the transformer. This example shows the advantage of direct PD monitoring. The UHF PD monitoring system gives a real-time alarm in case of PD events and the PD can be observed using PRPDs and trend views. In contrast, the DGA monitoring only gives an alarm with several hours delay (in this case) and no detailed information about the PD itself. V. CONCLUSION Partial discharge measurement is common practice for transformer type tests and diagnostic measurements. It represents a suitable tool to detect local defects in the insulation before these defects can emerge to a breakdown. Hence, the method suggests itself for asset management in terms of continuous monitoring. Monitoring exceeds the benefits of conventional diagnostic (singular) measurements. Diagnostic PD measurements can provide snapshot information, but do not provide any trend information. Also, temporary 5

measurements can cause misleading interpretations due to the volatile nature of PD as measurements performed during low PD activity do not prove the general absence of PD. These drawbacks can be avoided by using continuous PD monitoring. PD can be detected directly by electrical, standardized PD measurements according to IEC 60270 or by UHF measurements using antennas. The UHF method is advantageous for monitoring of on-site/online transformers, because UHF sensors are not galvanically coupled to the high voltage, do not require bushing measurement taps and are less affected by external PD sources (e.g. corona at bus bars). Sensors can either be applied at transformers online/on-site using UHF drain valve sensors at DN50/DN80 valves or at new/refurbished transformers at the factory using UHF plate sensors with a dielectric window. A case study illustrates PD monitoring at a generator step-up unit in combination with gas-monitoring over several years. Long-term evaluation proves PD being highly volatile. A severe rise of fault gases correlates with a significant gain in PD activity which caused both monitoring systems to raise alarms. The systems differ in their alarm delay: the PD alarm was triggered 7 hours earlier than the gas alarm (due to the high time constants of dissolving gases). Hence, a combined monitoring is considered as ideal asset management. PD monitoring can provide the fastest response times. Correlations, e.g. with gas measurements, can be used to affirm the transformer s status. After such an incident, the historical databases of monitoring systems can help asset managers and experts to decide the next steps. REFERENCES [1] S. Tenbohlen, M. Heindl, M. Jovalekic, A. Müller, M. Siegel, Trends of the Diagnosis of High Voltage Equipment (Trends in der Diagnostik von Hochspannungs-Betriebsmitteln), in ETG Diagnostik Elektrischer Betriebsmittel, Fulda, Germany, 2012. [2] International Electrotechnical Commission (IEC), IEC 60270 High Voltage Test Techniques - Partial Discharge Measurements, Geneva, Switzerland, 2000. [3] S. Coenen, Measurements of Partial Discharges in Power Transformers using Electromagnetic Signals, Universität Stuttgart: Books on Demand GmbH, ISBN 978-3-84821-936-0, 2012. [4] J. Fuhr, Procedure of Identification and Localization of Dangerous PD Sources in Power Transformers, IEEE Transactions on Dielectrics and Electrical Insulation Vol. 12, No. 5, 2005. [5] M. Judd, Power Transformer Monitoring Using UHF Sensors: Installation and Testing, IEEE International Symposium on Electrical Insulation, Anaheim, USA, 2000. [6] M. Judd, Partial Discharge Monitoring for Power Transformers Using UHF Sensors Part 2: Field Experience, IEEE Electrical Insulation Magazine, Vol. 21, No. 3 May/June 2005. [7] CIGRE WG A2.27, Recommendations for Condition Monitoring and Condition Assessment Facilities for Transformers, Cigre Brochure 343. [8] S. Tenbohlen, M. Siegel, M. Beltle, M. Reuter, Suitability of Ultra High Frequency Partial Discharge Measurement for Quality Assurance and Testing of Power Transformers, CIGRE SC A2 & C4 Joint Colloquium, Zürich, Switzerland, 2013. [9] BSS Hochspannungstechnik GmbH, online datasheet, 19.07.2016, www.bss-hochspannungstechnik.de [10] CIGRE WG.21.03, Recognition of Discharges, CIGRE Electra, No.11, December 1969. 6