1 OMICRON Seminar on Partial Discharge Diagnostics on HV Assets January 30, 2018 Beirut, Lebanon
2 Substation Asset Testing and Diagnosis LOW ACCURACY LEVEL HIGH Take better maintenance decisions through accurate and comprehensive condition diagnosis and assessment. Maximal signal-to-noise ratio due to freely-selectable filtering options and advanced noise separation tools. NOISE SUPPRESSION Increase safety due to single asset connection concept, clear connection guidance and multiple safety precautions. Condition based maintenance has widely been accepted as the most effective maintenance strategy for HV substation equipment. Through accurate knowledge of the state of condition and corresponding maintenance action, the lifetime of assets is extended while ensuring a more reliable and safe operation at the same time. The disadvantage of such a strategy are the costs due to the power outages that are required in order to perform the diagnostic measurements. At OMICRON we counter this disadvantage. We develop solutions that combine high portability, effort minimizing connection concepts and intelligent automated testing routines. This enables faster and easier testing and condition assessment than ever before without compromising on the scope of results. With diagnostic concepts that involve simultaneous time optimized testing on various HV assets the overall outage time for diagnostic measurements is greatly reduced to only a few hours. Learn more about this topic, experience what OMICRON has to offer and get an idea of just about how much this can improve your process.
3 Agenda Time Topics 08:30-09:00 Registration 09:00-10:00 Introduction 10:00 10:45 Partial Discharge Introduction and Measurement Techniques 10:45-11:15 Coffee Break 11:15 12:00 Partial Discharge Measurements on Power Transformers 12:00 12:45 Partial Discharge Measurements on Cables 12:45 13:15 Partial Discharge Measurements on Switchgear 13:15 13:30 Closing 13:30 14:30 Lunch Bavley Farid has worked as Application Engineer with a focus on Partial Discharge Diagnostics and Monitoring in OMICRON Electronics Middle east, since February He conducts theoretical and practical training courses, performs partial discharge measurements on HV assets and provides technical support to customers. He received his Bachelor s Degree in Science in Electrical Engineering with a focus on High Voltage Systems from the American University of Sharjah, United Arab Emirates in June 2015.
4 PD measurements on gas-insulated switchgear (GIS) PD measurements on gas-insulated switchgear (GIS) PD measurements within the ultra-high frequency range are very sensitive and have therefore been employed for PD detection in a long time. In new plants, UHF sensors are more and more integrated alternatively, mobile and external sensors can be used. The combination of MPD 600 and OMICRON s UHF 620 allows fast and easy PD measuring up to the UHF range and provides different frequency bandwidths. The UHF partial discharge (PD) measurement is an unconventional PD measurement technology, which can provide customers with an improved solution for sensitive PD measurements without (or fewer) interferences from external noise that limit the use of conventional/standard methods (IEC60270), especially on site. The UHF technology can make PD measurement more accurate, reliable, fast and easy. UHF stands for Ultra-High Frequency and the related PD measurement uses the frequency range of some 100 s MHz up to about GHz. This technology can be used for detection, measurement and monitoring of PD at different assets. GIS/GIL (Gas Insulated Substations / Lines) Application: PD measurements using the UHF method have been performed on GIS since more than 25 years. UHF technology is now used for the commissioning of new or maintained substations to ensure no moving parts (hopping particles) or protrusions on the conductors, which can lead to weakened insulation properties. To decouple PD signals out of the GIS, permanently mounted sensors are typically used. In some cases, retrofitting of older installations (using window couplers with an individual (depends on GIS type) design or a kinds of rubber bands with inside metallic foils for mounting at spacers (using the dialectical gap between two nearby outer conductor tubes existing at some GIS installation) is possible.these methods are described in IEC standards (e.g. IEC Chapter 6.29) or in the CIGRE (TF 15/ ).
5 PD Monitoring Systems for High-Voltage Cables For over ten years, OMICRON s Partial Discharge (PD) measuring technology has been known for its outstanding accuracy and informative value. This modern technology is now also available for online monitoring applications in quality assurance processes like e.g. after-installation testing of high-voltage cable systems (> 110 kv), joints and terminations. OMICRON Monitoring Solutions: > > Allow a condition assessment of the insulation of cable sections > > Ensure safe and reliable service operation, even in critical installations, through continuous assessment of the insulation status > > Extend the service life of high-voltage cable sections by means of continuous monitoring > > Provide early notifications for the prevention of dielectric failures Cable Joints and Terminations IEC standards prescribe type tests and routine tests to be performed by the manufacturer in order to ensure the high production quality of high-voltage cables and their accessories. The on-site installation of the high-voltage cables remains critical. Even very small dust particles and water droplets in joints and cable terminations can lead to critical defects. These defects can result in dielectric failures and thereby a reduced cable service life and serious power faults. In order to identify such weaknesses in proper time, the status of the insulation must be monitored continuously. With the OMICRON monitoring system, sensors continuously detect partial discharge activity at critical points in the cable system during operation. This data is acquired, pre-processed, stored in a database, and analyzed. Features > > Perfectly selected or adapted PD sensor, PD acquisition unit, and control computer components > > Excellent methods for data acquisition (gating, 3PARD, 3CFRD) can separate and recognize a variety of PD sources > > Visualization of individual trend curves for each individual PD source > > Customer-specific warning and alarm system HV cable joint HV cable OMS system unit HV cable termination concentrator unit inductive sensor fiber optic cable Setup of PD Monitoring Systems
6 Partial Discharge Analysis and Monitoring Partial discharge (PD) can damage insulation materials in power transformer bushings and windings. This can lead to their failure and costly outages. PD measurement is a reliable and non-destructive method used to diagnose the condition of a power transformer insulation system. OMICRON's PD analysis and monitoring solutions offer: > > Fiber optic data transmission for safe operation and improved signal-to-noise ratio > > Simultaneous and synchronous multi-channel PD measurement for more complete analysis > > Active noise suppression and gating methods for optimal accuracy despite high interference > > Powerful tools (3PARD and 3FREQ) for separating noise and multiple PD sources MPD series The MPD 500 and MPD 600 are highly developed devices for measuring partial discharges (PD). Even the smallest PD pulses can be separated from interference and analyzed. The MPD series is suitable for many different PD testing applications. PDL 650 The PDL 650 is used for acoustic PD fault localization on power transformers. The software compares the data from multiple sensors and enters it into a geometric model. This allows the fault location to be identified reliably. OMS 605 The OMS 605 is a portable partial discharge monitoring system designed to inspect high-voltage assets under load. It can be employed for temporary and periodic, condition-based monitoring.
7 Registration Please complete this form, scan it and return it via or fax to: OMICRON electronic Middle East Attn: Ms. Suzane Coelho Fernandes Please complete your details below; Yes I will attend: Seminar on Partial Discharge Diagnostics on HV Assets January 30, 2018 Phoenicia Intercontinental Hotel Beirut Registration deadline 23 January 2018 Mr Mrs Ms First Name:... Last Name:... Company:... Job Title:... Address:... Country:... Phone:... Mobile
8 OMICRON Seminar on Substation Save Testing your seat and and Diagnosis register by January 23, 2018 at the latest! October 23, 2017 Dubai, United Arab Emirates October 24, 2017 Abu OMICRON Dhabi, United electronics Arab Emirates Middle East Almoayyed Tower 39th floor Offices 3901 & 3902 Bldg Rd Block 428 Seef District - Manama, Bahrain events@omicronenergy.com Phone
OMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates
OMICRON Seminar on Substation Testing and Diagnosis October 23, 2017 Dubai, United Arab Emirates October 24, 2017 Abu Dhabi, United Arab Emirates Time Optimized Substation Asset Testing and Diagnosis Agenda
More informationWhy partial discharge testing makes good sense
Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown
More informationThe importance of partial discharge testing throughout the development and operation of power transformers
The importance of partial discharge testing throughout the development and operation of power transformers Ulrike Broniecki OMICRON Energy Solutions GmbH, Berlin Power transformers are exposed to intense
More informationMONTRANO. Continuous monitoring system for power transformers
MONTRANO Continuous monitoring system for power transformers Condition monitoring to extend transformer life Knowing the dielectric condition of insulation is vital Dielectric flashover of insulation in
More informationAfrica Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound
Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences
More informationPartial Discharge Measurement and Monitoring on High Voltage XLPE Cables
21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria
More informationDoble Solutions for Partial Discharge. Greg Topjian Solutions Manager
Doble Solutions for Partial Discharge Greg Topjian Solutions Manager 617-393-3129 gtopjian@doble.com Why do we need to conduct PD measurements PD a major cause of early failure for HV insulation. Partial
More informationNew Techniques for the Monitoring of Transformer Condition
New Techniques for the Monitoring of Transformer Condition Thomas Prevost OMICRON electronics USA IEEE T&D Conference Chicago, Illinois April 17, 2014 Agenda Monitoring Expectations & Needs Bushing Monitoring
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge
The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits
More informationPD Solutions. On-Line PD Measurement Devices
On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed
More informationDiagnostic testing of cast resin transformers
Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com
More informationCondition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology
Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of
More informationPartial Discharge Measurements on 110kV Current Transformers. Case Study. Results
2016 International Conference on Electrical Engineering and Automation (ICEEA 2016) ISBN: 978-1-60595-407-3 Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results Cristian DAN
More informationFlorian Predl and GK Papneja OMICRON
One-day Workshop on HV insulation diagnosis by means of PD detection/measurement methods by Florian Predl and GK Papneja OMICRON Date: Time: Venue: 28 November 2016 (Monday) 9:00 17:00 (8:30 for registration)
More informationTHE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.
THE POWER OF LIFE WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk. Mr. Neal Yang Pro.E.E. Engineer About Us The flaw of dielectric material
More informationInternational Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer
Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 7, July -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 Comparison
More informationSpecialists in HV and MV test and diagnostics. Testing in Substations
Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies
More informationAdvanced Test Equipment Rentals ATEC (2832)
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) MPD 500 Partial Discharge Measuring System for Routine Test Applications Partial Discharge Measurement The MPD 500 partial
More informationMPD 600. High-End Measurement and Analysis System for Partial Discharges (PD)
MPD 600 High-End Measurement and Analysis System for Partial Discharges (PD) Partial Discharge Analysis The MPD 600 partial discharge analysis system is a precise and modular high-end toolbox for detecting,
More informationTECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets
TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets Who we are TECHIMP is one of the leading providers of Condition Assessment Services Data Acquisition and Test Equipment
More informationAdvanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CP RC Resonance circuit for GIS testing A new approach to testing gas-insulated switchgear Testing gas-insulated switchgear
More informationPDL 650. Acoustic PD Fault Localization in High-Voltage Equipment
PDL 650 Acoustic PD Fault Localization in High-Voltage Equipment Identifying Problems within Steel Walls As a result of increased demand for power, high voltage equipment is being subjected to ever greater
More informationPRY-CAM BREAKTHROUGH TECHNOLOGY FOR CONDITION ASSESSMENT AND ASSET MANAGEMENT
PRY-CAM BREAKTHROUGH TECHNOLOGY FOR CONDITION ASSESSMENT AND ASSET MANAGEMENT WELCOME TO PRY-CAM A REVOLUTION IN PARTIAL DISCHARGE MANAGEMENT The worlds of partial discharge (PD) measurement, asset management
More informationMPD 500. Partial Discharge Measuring System for Routine Test Applications
MPD 500 Partial Discharge Measuring System for Routine Test Applications Partial Discharge Measurement The MPD 500 partial discharge measuring system has been specially designed for providing fast and
More informationPOWER TRANSFORMER. Failure Analysis & Troubleshooting. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E
POWER TRANSFORMER Failure Analysis & Troubleshooting H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: Electricity is high-grade energy. Working
More informationTesting of 400 kv GIS
Testing of 400 kv GIS Robert le Roux, Dermot Dorgan, Brian Perry ESB International - Ireland Paper 028 1 Introduction The 400 kv transmission is designed for critical periods of low loading. Due to critical
More informationANSE VISUAL, developed within the
ANSE VISUAL Software to Analyze Substation Robustness ANSE VISUAL, developed within the Institutional Project 1724, is a tool to analyze the robustness of electrical substations. The software carries out
More informationPartial Discharge Monitoring and Diagnosis of Power Generator
Partial Discharge Monitoring and Diagnosis of Power Generator Gao Wensheng Institute of High Voltage & insulation tech. Electrical Eng. Dept., Tsinghua University Wsgao@tsinghua.edu.cn Currently preventive
More informationHV AC TESTING OF SUPER-LONG CABLES
HV AC TESTING OF SUPER-LONG CABLES Stefan SCHIERIG, (Germany), schierig@highvolt.de Peter COORS, (Germany), coors@highvolt.de Wolfgang HAUSCHILD, IEC, CIGRE, (Germany), hauschild@highvolt.de ABSTRACT The
More informationMPD 600. High-end partial discharge measurement and analysis system
MPD 600 High-end partial discharge measurement and analysis system Partial discharge analysis Partial discharges: weak points in insulation systems Partial discharges, as defined by IEC 60270, are localized
More informationOn-line Partial Discharge Assessment and Monitoring of MV to EHV Cables
On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables William Higinbotham, Neil Davies and Victor Chan EA Technology LLC, New Jersey; USA, EA Technology Pty Ltd, Brisbane Australia; EA
More informationPartial discharge diagnostics on very long and branched cable circuits
11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA
More informationMPD 600. High-end measurement and analysis system for partial discharges
MPD 600 High-end measurement and analysis system for partial discharges Partial discharge analysis Partial discharges: weak points in insulation systems Partial discharges, as defined by IEC 60270, are
More informationKEYWORDS On-line diagnostics, cable termination, partial discharge (PD), ultra-high frequency (UHF), sensitivity check.
2, rue d Artois, F-758 PARIS B-2 CIGRE 28 http : //www.cigre.org Application of UHF method for on-line PD diagnostics of cable terminations T. KLEIN Pfisterer Kontaktsysteme GmbH Germany D. DENISSOV, W.
More informationGas-Insulated Metal-Clad Switchgears Express-Diagnostics Method on Partial Discharge Characteristics
Gas-Insulated Metal-Clad Switchgears Express-Diagnostics Method on Partial Discharge Characteristics ALEXANDRA KHALYASMAA 1, STANISLAV EROSHENKO 1, EGOR MARYSHKO 2, ALEXANDR OVSIANNIKOV 2 1 Ural Federal
More informationشركة الوقت للكهرباء والمقاوالت ذ.م.م.
CONTRACTING COMPANY W.L.L. is a leading corporate in the United Arab Emirates offering quality services in the field of High Voltage Electrical work 400, 132 & 33 kv and Medium Voltage Power Distribution
More informationPD Testing Considerations for MV Plant Cables
PD Testing Considerations for MV Plant Cables Cable Testing Philosophy Damage Mistake Aging Repair Manufacturing Transportation Installation Operation Power frequency 50/60 Hz Power frequency 50/60 Hz
More informationABB Power Products Service
Raben Naidoo, Technology days, May 21-22th, 2014, Cape Town, South Africa, Enhanced availability of transformers via transformer remote monitoring - TEC ABB Power Products Service Why a session on availability?
More informationIMPORTANCE OF ACCURATE MEASUREMENTS DURING THE LIFE CYCLE OF UTILITIES
IMPORTANCE OF ACCURATE MEASUREMENTS DURING THE LIFE CYCLE OF UTILITIES Thomas Steiner HIGHVOLT Prüftechnik Dresden GmbH Lifecycle of utilities time schedule utilities Tests during life cycle of utilities
More informationElectrical Switchgear & Power Transformer Testing. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E
Electrical Switchgear & Power Transformer Testing H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: This will provide you with practical knowledge
More informationOn-Site Partial Discharge Monitoring using the differential LEMKE PROBE LDP-5 and its accessories
Workshop 2000, lexandria, Virginia, 13 & 14 September 2000 paper No.: 8 On-Site Partial Discharge Monitoring using the differential LEMKE PROE and its accessories Dirk Russwurm, HV Technologies, Inc. bstract
More informationPD Diagnostic Applications and TechImp solutions
PD Diagnostic Applications and TechImp solutions Condition Assessment Solutions for Electrical Systems. PD based innovative tools for the Condition Based Maintenance. MD-04.05.004 - rev. 00-29/08/2006
More informationNETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT
NETWORK INNOVATION COMPETITION PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT NOVEMBER 17 Version: 1.0 Authored by: Andrew Moon Engineering Consultant and Project Manager Kevin Smith Lead
More informationIN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY
IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY Avinash Raj 1, Chandan Kumar Chakrabarty 1, Rafidah Ismail 1 and Basri Abdul Ghani 2 1 College of Engineering, University Tenaga
More informationPartial Discharge, Survey or Monitor?
July 2014 Partial Discharge, Survey or Monitor? 24-7 Partial Discharge monitoring is the ultimate tool for finding insulation weaknesses before they fail. Introduction It s well established that Partial
More informationRevision of C Guide for Application of Monitoring Equipment to Liquid Immersed Transformers and Components. Mike Spurlock Chairman
Revision of C57.143-2012 Guide for Application of Monitoring Equipment to Liquid Immersed Transformers and Components Mike Spurlock Chairman All participants in this meeting have certain obligations under
More informationEE171. H.H. Sheikh Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E
EE171 Electrical Equipment & Control System: Electrical Maintenance Transformers, Motors, Variable Speed Drives, Generators, Circuit Breakers, Switchgears & Protective Systems H.H. Sheikh Sultan Tower
More informationEI HIGH VOLTAGE INSULATION TESTING POLICY
Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and
More informationUSING DAMPED AC VOLTAGES
MODERN & TESTING DIAGNOSIS OF POWER CABLES USING DAMPED AC VOLTAGES BY EDWARD GULSKI AND ROGIER JONGEN, Onsite HV Solutions ag, Switzerland AND RALPH PATTERSON, Power Products & Solutions LLC, United States
More informationThe Application of Partial Discharge Measurement and Location on CGIS
International Journal on Electrical Engineering and Informatics Volume 4, Number 3, October 2012 The Application of Partial Discharge Measurement and Location on CGIS Min-Yen Chiu¹, Keng-Wei Liang¹, Chang-Hsing
More informationAdvancements in online partial discharge monitoring and assessment of MV through EHV Substation assets
Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Abstract: For decades it has been recognized that partial discharge assessment is an excellent method
More informationHZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL. Huazheng Electric Manufacturing(Baoding) Co.,Ltd
HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL Huazheng Electric Manufacturing(Baoding) Co.,Ltd Safety Terms and Symbols This manual may contain the terms: Warning! Indicate the conditions
More informationExpand your horizons with OMICRON testing solutions
Expand your horizons with OMICRON testing solutions Indian User Meeting November 1 3, 2017 Vivanta by Taj, New Delhi India i www.omicronenergy.com Invitation Building on the major success of the German
More informationIRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.
IRIS POWER PDTracII Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear. We have not found another test method that produces as much
More informationMEDIUM & HIGH VOLTAGE
MEDIUM & HIGH VOLTAGE TESTING EQUIPMENT VOLTAGE WITHSTAND SGM Series Resonant Systems The SGM series are used for generating high AC voltages at a fixed frequency (mainly 50 or 60 Hz) by means of an excited
More informationTesting and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl
Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank
More informationApplication Note. Detection of Partial Discharge Using Ultrasound. Detection of Partial Discharge Using Ultrasound. Problem. iriss.
Detection of Partial Discharge Using Ultrasound Problem In electrical systems, especially above 1,000 Volts, sufficient and properly maintained equipment insulation helps ensure equipment longevity. However,
More informationNOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV
NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV Paul P. SEITZ, Seitz Instruments AG, (Switzerland), pps@seitz-instruments.ch Ben QUAK, Seitz Instruments AG, (Switzerland),
More informationTRANSFORMER OPERATIONAL. Principles, Selection & Troubleshooting
TRANSFORMER OPERATIONAL Principles, Selection & Troubleshooting H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: Power and distribution transformers
More informationTHE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE
THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales
More informationNEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY
NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY Lorenzo PERETTO Luigi FODDAI Simone ORRU Luigi PUDDU Altea Switzerland ENEL Italy ENEL Italy REPL Italy lperetto@alteasolutions.com
More informationMSR Series. Modular Series Resonant Systems kV; 500kVA...60,000kVA
MSR Series Modular Series Resonant Systems - 250...2200kV; kva...60,000kva The MSR Series is designed to provide power for FEATURES tests on cables, HV and EHV transformers, gasinsulated switchgear, bushings,
More informationFRAX Series Sweep Frequency Response Analyzers
FRAX Series Highest dynamic range and accuracy in the industry Fulfills international standards for SFRA measurements Advanced analysis and decision support built into the software. FRAX 150 with built
More informationPARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES
PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES Engr. IÑIGO V. ESCOPETE, JR. ITC Level 2 Certified Thermographer PHIL-NCB NDT-UT Level 2 Partial Discharge testing is a Condition Based Maintenance tool
More informationCable fault location in power cables. Systematics for cable testing, diagnosis and cable fault location
Cable fault location in power cables Systematics for cable testing, diagnosis and cable fault location CABLE JOINTS, CABLE TERMINATIONS, CABLE GLANDS, CABLE CLEATS FEEDER PILLARS, FUSE LINKS, ARC FLASH,
More informationIRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.
IRIS POWER PDTracII Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear. We have not found another test method that produces as much
More informationUHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES
UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES D. Götz*, H.T. Putter* *Megger Germany INTRODUCTION High voltage termintions are essential components in high voltage cable
More informationIeee Guide For Partial Discharge Testing Of Shielded Power
Ieee Guide For Partial Discharge Testing Of Shielded Power We have made it easy for you to find a PDF Ebooks without any digging. And by having access to our ebooks online or by storing it on your computer,
More informationMV Power Cable Testing Training
MV Power Cable Testing Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Since power cables are used
More informationMaintenance & Diagnosis Strategies. for. High Voltage Substations
Maintenance & Diagnosis Strategies for High Voltage Substations 1/ 52 Robin Fischer, 28 April 2004 Diagnosis of Substation Equipment Power Transformers Instrument Transformers Switch-Gears Breakers Coils
More informationSimultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics
Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics Dominique Bolliger, Ph.D. HV TECHNOLOGIES, Inc. Manassas, VA, USA d.bolliger@hvtechnologies.com Abstract In
More informationEffective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Alexander Dierks, Herman Viljoen, Alectrix (Pty) Ltd, South Africa
More informationON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS
ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS Pantelis D. AGORIS 1, Sander MEIJER 1, Edward GULSKI 1, Johan J. SMIT 1, A. Jos L.M. KANTERS 2 1 Delft University of Technology - The Netherlands 2 TenneT
More informationVLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing
Cable Testing & Diagnostics Solutions for Medium Voltage Networks (1 kv - 36 kv) VLF Partial Discharge DC DAC tandelta Cable Testing Cable Diagnostics? There are two main applications for cable testing:
More informationCable test vans and systems
Cable test vans and systems Prepared for anything BAUR s cable fault location and diagnostics systems Would you like to test and assess new installations and existing cable locations efficiently? To rectify
More informationTraining Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.
Training Title POWER TRANSFORMERS Training Duration 5 days Training Venue and Dates Power transformers 5 20-24 May $3,300 Abu Dhabi In any of the 5 star hotel. The exact venue will be informed soon. Training
More informationAssuring the Reliability of Critical Power Cable Systems
Assuring the Reliability of Critical Power Cable Systems Presented by: Benjamin Lanz Manager of Application Engineering IMCORP Power Cable Reliability Consulting & Diagnostics Some of the technologies
More informationCable test vans and systems
Cable test vans and systems Prepared for anything BAUR s cable fault location and diagnostics systems Would you like to test and assess new installations and existing cable locations efficiently? To rectify
More informationMPD 600. High-end partial discharge measurement and analysis system
MPD 600 High-end partial discharge measurement and analysis system Partial discharge analysis Partial discharges: weak points in insulation systems Partial discharges, as defined by IEC 60270, are localized
More informationTECHIMP Power Transformer Monitoring
TECHIMP Power Transformer Monitoring Kontakt: Martin Hesse Techimp Germany GmbH i.g. E-Mail: mhesse@techimp.com Tel.: +49 5724 391 007 Mobil: +49 170 2364 735 PD Monitoring of Power Transformers Power
More informationCP CU1. Coupling unit for line and ground testing
CP CU1 Coupling unit for line and ground testing Line and ground test system CPC 100 The CPC 100 is a multifunctional test set for primary assets. When combined with the CP CU1 it covers the following
More informationCable testing and diagnostics
Cable testing and diagnostics To ensure the flow Cost-optimised maintenance through cable diagnostics The sheath and cable testing supports you in assessing whether a cable system is safe and ready to
More informationOnsite Mobile AC High Voltage Test System
TSGMF(T) series Onsite Mobile AC High Voltage Test System Onsite mobile AC high voltage test systems are used for withstand voltage testing, partial discharge measurement, tan delta measurement to instrument
More informationPartial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor
TRANSACTIONS ON ELECTRICAL AND ELECTRONIC MATERIALS Vol. 14, No. 4, pp. 211-215, August 25, 2013 Regular Paper pissn: 1229-7607 eissn: 2092-7592 DOI: http://dx.doi.org/10.4313/teem.2013.14.4.211 Partial
More informationEPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY
EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY EPS AUSTRALIA SERVICES COMPANY OVERVIEW EPS is a recognised company specialising in Electrical, Instrumentation, Structural, Mechanical and
More informationPartial Discharge Monitoring of Power Transformers by UHF Sensors
Partial Discharge Monitoring of Power Transformers by UHF Sensors S. Tenbohlen 1, M. Siegel², M. Beltle² 1 Institute of Power Transmission and High Voltage Technology (IEH), University of Stuttgart Pfaffenwaldring
More informationHYUNDAI HEAVY INDUSTRIES CO. LTD
HiPDS-G HYUNDAI HEAVY INDUSTRIES CO. LTD Hyundai Intelligent Preventive Diagnostic System for GIS User s Manual Version: 1.20 / 2010.02.10 File: HiPDS-G_UsersManual(ENG).doc Hyundai Heavy Industry HiPDS-G
More informationECP HV INSULATION TESTING
Document Number: ECP 11-0006 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE EPN, LPN, SPN ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing
More informationPD ANALYSIS OF GAS INSULATED MEDIUM VOLTAGE SWITCHGEAR DURING FACTORY ASSEMBLY AND SITE COMMISSIONING
PD ANALYSIS OF GAS INSULATED MEDIUM VOLTAGE SWITCHGEAR DURING FACTORY ASSEMBLY AND SITE COMMISSIONING Andreas F.X. WELSCH*, Siegfried A. RUHLAND* *AREVA Sachsenwerk GmbH - Germany andreas.welsch@areva-td.com
More informationPRODUCT PORTFOLIO TEST AND MEASURING SYSTEMS
PRODUCT PORTFOLIO TEST AND MEASURING SYSTEMS n Quality made in Germany n Standardized and customized solutions n Turn key projects, all from one hand 0.1-1/1 Product Portfolio Test and Measuring Systems
More informationCVVOZE Power Laboratories (CVVOZEPowerLab)
CVVOZE Power Laboratories (CVVOZEPowerLab) BRNO, SEPTEMBER 2016 1 Centre for Research and Utilization of Renewable Energy Centre for Research and Utilization of Renewable Energy (CVVOZE) was established
More informationPartial Discharge (PD) techniques for measuring the condition of ageing HV/MV switchgear
3100 words with case studies (US) Partial Discharge (PD) techniques for measuring the condition of ageing HV/MV switchgear By Neil Davies, Director, EA Technology International Throughout the world, the
More informationWinTech Partial Discharge Testing and Monitoring Systems
WinTech Partial Discharge Testing and Monitoring Systems Predictive maintenance to eliminate power equipment failure risk. WinTech Electric 嘉芳 Claire Huang Global Sales & Marketing +886-289110833#605 +886-972-280-102
More informationMSR Series. Modular Series Resonant Systems kV; 500kVA...60,000kVA FEATURES BENEFITS APPLICATIONS 1/6
MSR Series Modular Series Resonant Systems - 250...2200kV; 500kVA...60,000kVA The MSR Series is designed to provide power for tests on cables, HV and EHV transformers, gasinsulated switchgear, bushings,
More informationA New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol
A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to
More informationInnovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander
More informationWEIDMANN ELECTRICAL TECHNOLOGY NETA POWERTEST MARCH 2014 ELECTRICAL TECHNOLOGY. WEIDMANN DIAGNOSTIC SOLUTIONS INC. A Member of the WICOR Group
WEIDMANN ELECTRICAL TECHNOLOGY NETA POWERTEST MARCH 2014 ELECTRICAL TECHNOLOGY WEIDMANN DIAGNOSTIC SOLUTIONS INC. A Member of the WICOR Group OUR MISSION To be the leading global full-service provider
More informationH V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C
H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C S O L U T I O N S Y O U R S O U R C E F O R T O P Q U A L I T Y T E S T E Q U I P M E N T w w w. h v t e c h n o l o g i e s. c o m Company
More informationCITY SERIES. Compact, fully equipped cable fault location, test and diagnostic systems
CITY SERIES Compact, fully equipped cable fault location, test and diagnostic systems Tailored to fit to small vehicles Easy operation in restricted spaces Centrally controlled, fully automatic system
More informationPrimary Test Manager (PTM) Testing and management software for primary assets
Primary Test Manager (PTM) Testing and management software for primary assets Asset diagnostics now easier than ever How well do you know your assets? High-voltage assets are subjected to aging and wear
More information