ADDENDUM NO. 1 REQUEST FOR QUALIFICATIONS (RFQ) AND REQUEST FOR PROPOSALS (RFP) FOR. RFQ/RFP No. 15P40. Campus Center East HVAC Unit Replacement

Similar documents
ADDENDUM TO RFQ/P DOCUMENTS PROJECT # ADDENDUM: #01

A. Action Submittals: Written and graphic information that requires Architect's responsive action.

East Central College

James W. Moore, PE / Brandon D. Enevold, PE / Kjersten E. Kuhta, PE Dylan J. Cunningham, PE / Jacob L. Deering, PE / Joel R.

ADDENDUM NO. 1. November 6, 2016 BIDDING AND CONTRACT DOCUMENTS FOR

Answer: Qualification statement should be provided with the bid.

A. Action Submittals: Written and graphic information that requires Engineer's responsive action.

ADDENDUM TO RFP DOCUMENTS

JEFFERSON LAB TECHNICAL ENGINEERING & DEVELOPMENT FACILITY (TEDF ONE) Newport News, Virginia

ADDENDUM No. 1. RFP No Gallup Park Custom Playground Equipment Design. Due: Tuesday, August 4, 2015 by 10:00 a.m.

WATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO Job No.:

CITY OF MORRO BAY / CAYUCOS SANITARY DISTRICT

12560 W. Cedar Drive Lakewood, CO Barry Himmelman President

MISSISSIPPI STATE UNIVERSITY Office of Planning Design and Construction Administration

Cone HVAC Modernization. Thursday, September 1, 2016 Pre Proposal Conference

Bid No. B14-02 Building 100 HVAC Improvements

UNION COUNTY VOCATIONAL-TECHNICAL SCHOOLS West Hall Addition Project Raritan Road, Scotch Plains, NJ

SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION SUBMITTAL PROCEDURES

SECTION SUBMITTAL PROCEDURES

Signs, Canopies & Awnings City of Oshkosh Department of Community Development

UCCS University Hall Fire Sprinkler System Upgrade March 1, 2011 RTA SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL

NEVADA DEPARTMENT OF TRANSPORTATION Addendum 3 to RFP July 28, 2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

A. This section specifies procedural requirements for Shop Drawings, product data, samples, and other miscellaneous Work-related submittals.

DIVISION 1 - GENERAL REQUIREMENTS SECTION SUBMITTALS

MSU Barnard Hall 105 Cleanroom Installation PPA # Page 1

CLARIFICATIONS 1. See attached meeting minutes from the Pre-Bid meeting on June 14, 2017.

November 16, 2017 BOARD OF COUNTY COMMISSIONERS ORANGE COUNTY, FLORIDA. Y CH / Addendum #6 SHERRY DRIVE BRIDGE REPLACEMENT

SECTION SUBMITTAL PROCEDURES

SECTION CLOSEOUT SUBMITTALS SECTION CLOSEOUT SUBMITTALS

DESIGN REVIEW PROCESS AND APPLICATION

SAN FRANCISCO UNIFIED SCHOOL DISTRICT 2011 PROPOSITION A BOND PROGRAM Miraloma ES & Sunnyside ES Green Schoolyard ADDENDUM NO. 1

Merrick Pet Care New Distribution Center Hereford, Texas

Stantec Architecture Inc South Flores Street Suite 201 San Antonio TX Tel: (210) Fax: (210)

Section Meetings Section Material and Equipment. None Required

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

FAB GSE Remodel ITB Solicitation #1538 Invitation to Bid (ITB) for General Contracting Services. ADDENDUM #4 December 5, 2014

Software Services, Section 16748, Add as an attachment to this section Attachment A enclosed with this addendum.

Ingham County Request for Proposals Public Safety Radio System Project Manager and Consulting Services Packet #120-18

Construction Phase Project Management and Documentation

A/C Change-Out Permit Guidelines - Residential

Attached is Addendum No. 2 to SEPTA Sealed Bid APES, Install DC Stinger Distribution System - SEPTA Fern Rock Car House.

Answer: Only to ChurchWoods, LLC.

SECTION ADMINISTRATIVE REQUIREMENTS

Innovation Wireless KRONOsync GPS or NTP Wireless Clock System

Bid #3990DB - Two Way Motorola Radio System District Wide Upgrade

Humboldt Bay Piling Removal

ADDENDUM NO. 02 July 31, 2012

***************************************************************************** DRAFT UFGS- 01 XX XX (FEB 2014)

Commercial Infill Project Guide

CONVEYANCE PIPELINE AND PUMP STATION

PROJECT TITLE PROJECT NO: CONTRACT TITLE UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

ADDENDUM No. 1. ITB No Northside Interceptor Condition Assessment. Due: February 1, 2018 at 10:00 A.M. (Local Time)

September 6, 2018 CITY OF BERKELEY SHATTUCK RECONFIGURATION AND PEDESTRIAN SAFETY PROJECT SPECIFICATION NO C ADDENDUM NO.

HAMMEL ASSOCIATES ARCHITECTS, LLC 2 5 E A S T G R A N T S T R E E T, S U I T E L A N C A S T E R, P E N N S Y L V A N I A

ADDENDUM #2 September 12, 2018

CHABOT-LAS POSITAS COMMUNITY COLLEGE DISTRICT CHABOT COLLEGE CAMPUS MASTER SIGN PROGRAM, PHASE 2 BID NO

SECTION OPERATION AND MAINTENANCE DATA

COMMERCIAL / INDUSTRIAL APPLICATION FOR PLAN EXAMINATION AND BUILDING PERMIT

SECTION SUBMITTALS PART 1 - GENERAL 1.01 RELATED DOCUMENTS

ADDENDUM NOTICE INTERIOR RENOVATIONS AT THE BATHURST CLARK RESOURCE LIBRARY, 900 CLARK AVENUE WEST, VAUGHAN, ON

Anticipated schedule, Page 2. Change the Contract Term from 635 Days to be 1,127 Days.

[Note to PSC: Include these sections in the Contract Documents, even though some are not included in the U of I Facilities Standards]

State College Area School District

PLAN SUBMITTAL REQUIREMENTS

McKenzie County Healthcare Systems

Vanderbilt University Standard Specification Revised 2/6/08

State College of Florida, Manatee-Sarasota

February 18, Re: Zephyr Lakes Amenity Center Zephyrhills, Florida

8 th April 2018 ADDENDUM NO. 1

SECTION SUBMITTALS. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

TELEPHONE: (215) Addendum No Cooling Plant Replacement SDP Contracts No. B-080C, B-081C and B-082 of 2017/18

SAN FRANCISCO UNIFIED SCHOOL DISTRICT 2011 PROPOSITION A BOND PROGRAM SOTA-AAS HIGH SCHOOL MODERNIZATION ADDENDUM NO. 2

TG Glazing Design-Build

ADDENDUM NO. 4 TO THE CONTRACT DOCUMENTS SUPPLEMENTAL INFORMATION

Pledge of Allegiance Staff Introduction Bid Package Submittal Sign-In Sheet and Project Scope Q&A Process Anticipated Date Sequence General Project

ADDENDUM NO. 1 CLARIFICATION NO. 1

December 31, 2015 A. THE BID OPENING DATE IS UNCHANGED. B. Questions, Additions, and Deletions

BUILDING PLANS. BUILDING INSPECTIONS DEPARTMENT

BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX: BID PACKAGE D

DESIGN REVIEW BOARD APPLICATION EXTERIOR PLAN / LANDSCAPE PLAN

Addendum No. 1 page 1

The enclosed information is provided for consideration in the preparation of your response to the abovereferenced

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 12/12/2018

A. Section includes administrative and procedural requirements for project record documents, including the following:

05BDB ADDENDUM 002. Thomas W. Wathen Business Division Building Renovation GENERAL ITEMS:

SECTION ADMINISTRATIVE REQUIREMENTS SECTION ADMINISTRATIVE REQUIREMENTS

Company. Signed: Date:

Multi Agency Communications Center

White Lake Township Building Dept Highland Rd. (248) White Lake, MI Fax (248)

Scope of Services. Project management tasks are estimated based upon anticipated project duration of 52 weeks.

January, 2014 Page 1 of 5

Lincoln County Tax Appraisal Office Project No. RFB

APPLICATION FOR COMMERCIAL CONSTRUCTION FIRE AND LIFE SAFETY PLAN REVIEW PROJECT INFORMATION: Project phone: Project Address: City: State: Zip:

A. Section includes administrative provisions for coordinating construction operations on Project including, but not limited to, the following:

CITY OF RICHMOND SUBDIVISION PLAT AND PUBLIC INFRASTRUCTURE SUBMITTAL, REVIEW AND APPROVAL PROCEDURES

APPLICATION FOR CERTIFICATE OF APPROPRIATENESS IN THE HISTORIC DESIGN REVIEW DISTRICT

Bidders for the Oak Brook Park District Family Locker Room Renovation

ADDENDUM NO. 3, March 14, 2017 A.B.C. No

Transcription:

ADDENDUM NO. 1 REQUEST FOR QUALIFICATIONS (RFQ) AND REQUEST FOR PROPOSALS (RFP) FOR RFQ/RFP 15P40 Campus Center East HVAC Unit Replacement CHAFFEY COMMUNITY COLLEGE DISTRICT February 26, 2015 CHAFFEY COMMUNITY COLLEGE DISTRICT 5885 Haven Avenue Rancho Cucamonga, CA 91737 Page 1 of 8

RFQ-RFP : 15P40 PROJECT NAME: Campus Center East HVAC Unit Replacement CHANGES, ADDITIONS, DELETIONS, CLARIFICATIONS, CORRECTIONS AND CONTRACTOR QUESTIONS FOR CLARIFICATION & ANSWERS (FEBRUARY 26, 2015) The following changes, additions, deletions, clarifications, or corrections shall become part of the Proposal for Chaffey Community College District Campus Center East HVAC Unit Replacement at the Rancho Cucamonga Campus. All other terms, specifications, and conditions remain the same. Each proposer is responsible for transmitting this information to all affected subcontractors and suppliers prior to the receipt of proposals. Each proposer shall acknowledge receipt of this Addendum on their Proposal. Modifications are identified by clouds and the following: Deletions strikethrough Insertions/Substitutions italic-underlined. ITEM 1: CORRECTION TO SECTION VI. SUBMITTAL FORMAT AND CONTENT, PROJECT APPROACH Correction #1. Section VI. SUMITTAL FORMAT AND CONTENT, Project Approach: Strike ten (10) months and replace with forty five (45) days. f) Project Approach Describe in detail your approach and methods for carrying out the Scope of Work. Please include a proposed comprehensive schedule including all activities to complete the Project in ten (10) months. Forty five (45) days. Page 2 of 8 Campus Center East HVAC Unit Replacement

ITEM NO. 2: ADD THE CONTRACTORS QUESTIONS & ANSWERS RFC #15P40-1 Question: If you would kindly inform us as to whether we need to be prequalified for this project in order to bid as a Prime Contractor? Please see submittal evaluation crieteria. RFC # 15P40-2 Question: Is there any estimation for this job? Please see page 38 of 38 of the RFP/ RFQ RFC # 15P40-3 Question: I need to find out what the budget is for this project? Please see page 38 of 38 of the RFP/ RFQ RFC # 15P40-4 Question: Who is on the plan holders list? n/a RFC # 15P40-5 Question: I did not find the plans in the online link. Can you direct me to them? There aren t any drawings only a scope of work within the RFP/ RFQ RFC # 15P40-6 Question: What times can the removal/install of equipment (Lifts and rigging) take place? TBD (based on occupancy and safety concerns) RFC # 15P40-7 Question: What times are we allowed to start and end work? 7:30a.m. to 5:00p.m. Page 3 of 8 Campus Center East HVAC Unit Replacement

RFC # 15P40-8 Question: Are the units currently operational, has there been an inspection to make sure the units qualify for the SCE Early Retirement Program? Yes, they are operational. Yes, they have been inspected and qualify for early retirement. RFC # 15P40-9 Question: Is there fire, life, safety system that needs to be removed and reinstalled and it is contractor/vendor specific? No, they are standalone package units. RFC # 15P40-10 Question: Is there an existing automation system that needs to be removed and reinstalled and is it contractor/vendor specific? RFC # 15P40-11 Question: Is there a specific roofing contractor and/or warranty on the existing roof? RFC # 15P40-12 Question: Assumptions that all permitting and inspections are handled through the District? Yes. RFC # 15P40-13 Question: Does this bid require a bid bond to be submitted with the bid proposal? RFC # 15P40-14 Question: Is the bidding contractor to draft a proposal using his own letterhead and submit it? Please refer to section VI. Submittal format and content in the RFQ/RFP. This section provides specifics on the required proposal information and format. Page 4 of 8 Campus Center East HVAC Unit Replacement

RFC # 15P40-15 Question: Are there any current as-builts of the existing gas, electrical and existing units or are their plans showing the work available? RFC # 15P40-16 Question: Please advise the make and model number of the existing units? Carrier: AC 1, RTU Model: 48DJD024-500AA, Serial #: Not able to read Carrier: AC 2, RTU Model: 48DJD024-500AA, Serial #: Not able to read Carrier: AC 3, RTU Model: 48DJD024-500AA, Serial #: 4591F77790 RFC # 15P17-17 Question: Regarding Submittal Evaluation Criteria table, page 11 of 38, and with reference to Experience with California Community College projects, for which 25 points are allocated: Per page 6 of 38, item e, government projects are also considered. Please confirm that no point is deducted for government projects, including state universities, state colleges, school districts and/or city projects? Correct no point will be deducted for government projects, including state universities, state colleges, school districts and/ or city projects. RFC # 15P40-18 Question: Regarding Submittal Evaluation Criteria table, page 11 of 38, and with reference to Experience with Southern California Edison Early Retirements Program Projects? Contractor shall be familiar with the Southern California Edison Early Retirement Program. Contractor shall submit and fulfill any and all documentation related to Southern California Edison needed to qualify for the incentives/ rebates to the District associated with this project. RFC # 15P40-19 Question: Please clarify /confirm that a project for which owner received the Edison Early Retirement rebate through the bidder s subcontractor is considered by owner and it does meet this requirement? Please clarify requirement. Page 5 of 8 Campus Center East HVAC Unit Replacement

RFC # 15P40-20 Question: Please advise if the criteria to obtain full 25 points is the number of projects the bidder has done or the number of HVAC units for which the bidder obtained rebate for the owner? Evaluation categories are weighted based experience with California Community College projects and SCE Early Retirement Program. RFC # 15P40-21 Question: Regarding Submittal Evaluation Criteria table, page 11 of 38, and with reference to Approach to Project for which maximum 10 points is allowed; Please advise what are the owner s expectations and what approaches would earn the bidder full 10 points? Approach should be based on best practices/ industry standards associated with HVAC unit replacement. RFC # 15P40-22 Question: Regarding Submittal Evaluation Criteria, page 11 of 38, please advise how many projects, at minimum, are required to earn full points? Five (5) RFC # 15P40-23 Question: Please clarify how the actual price of the bidder factored in along with the total point the bidder has obtained from page 11, to find the most value to the owner? The District to determine best value based on all criteria. RFC # 15P40-24 Question: Per scope of work on page 37 of 38, new curbs are to be installed. Please clarify if adopter curbs are also acceptable? If new curbs are to be installed (and not adopter curbs)? Most practical, new curbs. RFC # 15P40-25 Question: Please advise if any modification of structural support on the roof or under roof needs to be done to support the new units and hold-down Purposes? Most practical curb height for new units. Page 6 of 8 Campus Center East HVAC Unit Replacement

RFC # 1540-26 Question: Please provide details if any structural modification is needed? Most practical curb height for new units. RFC # 15P40-27 Question: Please advise type of roofing and if the roof is under warranty, and if possible the roofing contractor who services the roof? The roofing type is PVC Thermoplastic. The Districts Maintenance and Operations staff services the roof. RFC # 15P40-28 Question: Please confirm that no air balance or duct cleaning is required? RFC # 15P40-29 Question: Please advise if there is any temporary air conditioning, heating or exhaust is required, during the performance of the project? Project to be scheduled to avoid need for temporary equipment. RFC # 15P40-30 Question: Please advise if there is any temporary air conditioning, heating or exhaust is required, during the performance of the project? Project to be scheduled to avoid need for temporary equipment. RFC # 15P40-31 Question: Please advise if all the three units can be removed simultaneously or there is any phasing? Yes removing all three can be completed simultaneously. RFC # 15P40-32 Question: Please advise if there is any fire alarm that needs to be reset upon the completion of the project. If the bidder needs to arrange and pay for the services, please advise which company needs to be contacted? District will reset panels if necessary. Page 7 of 8 Campus Center East HVAC Unit Replacement

RFC # 15P40-33 Question: Per scope of work new electrical disconnects need to provided. Please advise if the new disconnects need to be fusible disconnect? New disconnects shall be fusible. RFC # 15P40-34 Question: Please advise if units equal to Carrier units can be used? Carrier or equal. END OF ADDENDUM NO. 1 Page 8 of 8 Campus Center East HVAC Unit Replacement