- Characteristic impedance of cabling links is characterised by Return Loss

Similar documents
This is a preview - click here to buy the full publication

DELTA Test Report. Certification testing of generic cabling products: Unscreened channel, Class E, 4 connector model. Performed for Sterling

AESA TECHNOLOGY OF LAN CABLE

GIGABIT ETHERNET. e-ready Building Next Generation IT infrastructures. The Cabling Partnership. Mike Gilmore Managing Director, e-ready Building

This document is a preview generated by EVS

Australian/New Zealand Standard

INTERNATIONAL STANDARD

Qualification testing of 100 ohm shielded channel, Class EA. Performed for Tyco Electronics Raychem N.V.

TSB-67. Transmission Performance Specifications for Field Testing of UTP Cabling Systems

Information technology. Generic cabling systems, General requirements

RECOMMENDATION ITU-R BT.1367 *

BICSI Standards Update December Stephen Banks RCDD CDCDP

AMP NETCONNECT Category 6 System

Some considerations concerning alien crosstalk Dr.-Ing. J.-H. (Jo) Walling Consultant Beaconsfield, P.Q. Canada

Level III measurement accuracy of field testers for Twisted Pair Copper Cabling Explained in Technical Detail

Transmission Media. Two main groups:

HIGH BIT RATE OPTICAL FIBRE NETWORKS - optical fibre selection and implementation

ISO/IEC JTC 1/SC 25/WG 3 N 755 Date: Replaces ISO/IEC JTC 1/SC 25/WG 3 N n/a

Call For Interest PoE- plus. Chris Di Minico MC Communications

Fiber Optic Principles. Oct-09 1

Field Testing Update

Copper and Fiber Optic Cables

n Proper pin termination at each end n Continuity to the remote end n Shorts between any two or more conductors n Transposed pairs: n Crossed pairs.

Install & Go Cat.8 STP Trunk Cable Assembly Description

Migration to 50/125 µm in the Local Area Network

Install & Go Cat.8 S/FTP Trunk Cable Assembly Description

This document is a preview generated by EVS

TECHNICAL ARTICLE: DESIGN BRIEF FOR INDUSTRIAL FIBRE OPTICAL NETWORKS

Industrial Automation

How Bend Insensitive Multimode Fiber is Affecting Installation and Testing of Enterprise and Data Center Cabling

Install & Go SMARTen (Cat.6A) STP Trunk Cable Assembly General

XX.7 Link segment characteristics

Category 7 A /Class F A Products

125 Eugene O Neill Drive 6120 Powers Ferry Road New London, CT Suite 150 Ph (860) Atlanta, GA Fax (860)

ENY81 Coupling Network

125 Eugene O Neill Drive 6120 Powers Ferry Road New London, CT Suite 150 Ph (860) Atlanta, GA Fax (860)

The Future of Cabling -

Superiorr Essex. Suite 150

af-phy July 1996

Test Report. Test Result: PASS

Data sheet OpDAT connection cable 2x1 OS2 - bend insensitive

Test report number CRT-001b Project number CRT-001b

COPPER + LWL RAW CABLES

SPECIFICATION FOR SINGLE-MODE OPTICAL FIBRES

CXP/CFP 100G MPO Cable Assembly

Industrial Ethernet OPT cable manufactured for Petrol Forecourt Applications.

FreeSpace ZA 250-LZ / 190-HZ zone amplifier TECHNICAL DATA SHEET. Key Features. Product Overview. Product Information.

Data sheet OpDAT breakout cable 24x1 OM4 - bend insensitive

INTERNATIONAL STANDARD

Brand-Rex Optical Cables - Universal PDC Tight Buffered Premise Distribution Cables

Test Report based on DIN EN ISO/IEC 17025:2005

Independent Testing - For End User Confidence

Synergy RJ45 LCS 6 Category 6 data outlets

TEST REPORT. DANAK Reg. no. 19. Electrical performance testing of: Connecting Hardware according to IEC

OpDAT Universalkabel 1x4 OM4 - biegeunempfindlich, Klasse. Principle diagram

Why Using Fiber for transmission

UTP Cat 5e cable (200 MHz) (PVC sheath)

features and benefits

Outdoor, Fig 8 Armored, Multi Tube

NETWORK CONNECTIVITY SYSTEMS

Data sheet MC GC1000 pro23 Cat.7 S/FTP 4P LSHF-FR 1640 ft

EQCD High Speed Characterization Summary

CAT 5e UTP Cable: NETSET BOX [305m], indoor

SECTION BUILDING WIRE AND CABLE

Ship Hybrid Cable DL 58 5 x UC1500 SS22 2x SM BendBright XS G.657.A2 6x MM MaxCap-BB-OM4

White Paper: The Ins and Outs of Testing Bend Insensitive Multimode Fiber (BIMMF): The Need for Encircled Flux

INTERNATIONAL STANDARD

AC Current Probes CT1 CT2 CT6 Data Sheet

Test Report based on DIN EN ISO/IEC 17025: 2005

UNIT Write notes on broadening of pulse in the fiber dispersion?

Application Note 5044

Data sheet Patch cord Cat.6 A AWG m yellow

FCDB (Fibre-Channel Data Bus) & Ruggedized High Speed Solutions

INTERNATIONAL TELECOMMUNICATION UNION TRANSMISSION MEDIA CHARACTERISTICS CHARACTERISTICS OF A DISPERSION-SHIFTED SINGLE-MODE OPTICAL FIBRE CABLE

400G-BD4.2 Multimode Fiber 8x50Gbps Technical Specifications

Media. Twisted pair db/km at 1MHz 2 km. Coaxial cable 7 db/km at 10 MHz 1 9 km. Optical fibre 0.2 db/km 100 km

Part Number: 7953A Cat 6 600V DataTuff, (4 pr) 23 AW G Solid BC, PP/PVC/PVC, Foil Shld, CMR, CMX-Outdoor

William Stallings Data and Computer Communications 7 th Edition. Chapter 4 Transmission Media

FreeSpace ZA 250-LZ / 190-HZ zone amplifier TECHNICAL DATA SHEET. Key Features. Product Overview. Product Information.

A Few (Technical) Things You Need To Know About Using Ethernet Cable for Portable Audio

Computer Networks

NEW YORK CITY COLLEGE of TECHNOLOGY

Data sheet MC GC1200 pro22 Cat.7A S/FTP 2x4P LSHF-FR 1640 ft

Four Cat 5e 24 AW G Bonded-Pairs solid bare copper conductors, polyolefin insulation, PVC jacket.

Data sheet MC GC1200 pro22 Cat.7A S/FTP 4P LSHF-FR, class Dca s2 d2

Automatic measuring system for xdsl & LAN cables (100 MHz) Designed to measure all types of telecom and special cables

INTERNATIONAL STANDARD

DATA TRANSMISSION. ermtiong. ermtiong

Lecture 5 Transmission. Physical and Datalink Layers: 3 Lectures

There are lots of problems or challenges with fiber, Attenuation, Reflections, Dispersion and so on. So here we will look at these problems.

This Special Provision covers the requirements for the installation and testing of fibre optic modems (FOM).

Optical Systems Contents

Variation of Waveforms in Multimode Fibre

One Enterprise. One Infrastructure. One Partner. Optical Fiber Loss Testing. Optical loss testing in the field is not as simple as it seems.

Electrical Concepts For Interconnect Professionals

CONTENTS. Introduction Characteristics Product range Pages

Pluggable Transceiver Modules

Comparison of vario. ous cables & channels

High Data Rate Characterization Report

Installing the Avaya 10-Gigabit

Transcription:

ISO/IEC 11801 ISO 11801 is the principle design standard for structured cabling systems for all countries of the world that do not have more specific standards, such as ISO 11801 (European Union), TIA 568- A (United States), AS 3300 (Australia) and CSA T529 (Canada). ISO (International Organisation for Standardisation) and the IEC (International Electrotechnical Commission) have formed Joint Technical Committee JTC1/SC 25 (interconnection of information technology equipment) to write: ISO/IEC 11801 Information Technology - Generic cabling for customer premises, July 1995 Technical changes to ISO/IEC 11801 (1995) have been processed via 2 separate amendments. Both amendments have been approved and jointly published as ISO/IEC 11801: Edition 2 (Jan 2000). The main changes are: - Classes A, B, C and D channel values are introduced. - Permanent Link (PL) replaces the existing Link. - Characteristic impedance of cabling links is characterised by Return Loss - PS-NET, ELFET, PS-ELFET, Propagation Delay and Delay Skew requirements have been introduced to accommodate the requirements of 1000BASE-T. - Cable fire rating to be in accordance with IEC 61156 unless otherwise stated by local regulation. This 'Edition 2' is not to be confused with ISO 11801 2nd Edition, due in early 2001. The second edition will detail Class E (Cat 6) and Class F (Cat 7) channels as well as raising the (Edition 2) new values for Class D channel to coincide with the American TIA 568B values, which are presently slightly higher than Class D. An important test standard will be: IEC 61935 Generic specification for the testing of balanced generic cabling in accordance with ISO/IEC 11801

ISO 11801 describes an hierarchical star cabling system with 90 m horizontal cabling and up to 2000 m of backbone cabling, split into 500 m of building backbone and 1500 m of campus backbone cabling. ISO 11801 describes channels and permanent links. The Permanent Link is the Telecommunications Outlet, TO (the wall or floor outlet), the (up to 90 m ) of horizontal cabling and the Floor Distributor, FD (the patch panel). An optional Transition Point, TP, is allowed within the 90 m of horizontal cable. The Channel is the work area cable (patchlead) form the terminal equipment into the TO, the permanent link as already described, a patchcord linking two patchpanels and a final equipment cable into the LAN equipment. It is not compulsory to have two patchpanels (a cross connect), indeed most users use only one patchpanel (an interconnect). Note that in the interconnect version, i.e. just one patch panel, the combined length of the patch cords A & C is 10 m. In the cross connect model, i.e. two patch panels, the combined length of the patchcords A, B & C is 9 m. ISO 11801 and EN 50173 allow for 50% more attenuation in patchcords (flexible cables) than for the fixed, solid core cable. This is one major difference between ISO and EN standards and the American standard TIA 568A. 568A only allows for 20% more attenuation in flexible cables. The 20% attenuation generally means that a 24 AWG patchcord is required. For ISO 11801 and ISO 11801 standards a patchcord can be implemented in 26 or 24 AWG, with 26 AWG being the cheaper of the two. For horizontal cabling, the following cables are recommended: - 100 ohm balanced copper cable - 62.5/125 multimode optical fibre

- Recognised alternatives are 120 and 150 ohm balanced cables and 50/125 multimode optical fibre. For backbone cabling, the following cables are allowed: - 100, 120 or 150 ohm balanced copper cable - 50/125, 62.5/125 or singlemode optical fibre The end user must decide whether screened or unscreened cable is required and what level of fire performance is required, e.g. IEC 332-1, IEC 332-3-c etc. Other 'rules' are: - No more than two levels of cross-connect in the backbone. This allows a Floor Distributor between the horizontal and building backbone cable, and a Building Distributor between the building and campus backbone cables, with all campus cables terminating in the Campus Distributor. - A minimum of one Floor Distributor for every 1000 square metres of office space. A minimum of one Floor Distributor for every floor should be provided. For a sparsely populated floor then it is permissible to serve this floor from an adjacent floor. - A minimum of one Telecommunication Outlet shall be provided at each work area. A minimum of two TOs per ten square metres of floor space is advised. The following Permanent Link/Channel Classes are described: - Class A specified up to 100 khz - Class B specified up to 1 MHz - Class C specified up to 16 MHz - Class D specified up to 100 MHz Different channel lengths are achievable with different classes of cabling: Class of Application Class A Class B Class C Class D Frequency range 100 khz 1 MHz 16 MHz 100 MHz Max distance with Cat3 Cable 2000m 200m 100m - Max distance with Cat4 Cable 3000m 260m 150m -

Max distance with Cat5 Cable 3000m 260m 160m 100m The Standard describes the following technical parameters: - Return Loss - Attenuation (now referred to as Insertion loss) - NET - Power Sum NET* - Attenuation to Crosstalk Ratio, ACR - Power Sum ACR* - Equal Level Far End Crosstalk, ELFET* - Power Sum ELFET* - DC Loop Resistance - Propagation Delay - Delay Skew* - Longitudinal to differential conversion loss figures marked with * are new and added by Amendment 2. For the most part, all parameters are given values for both Permanent Link and Channel requirements, over the frequency range of interest. For example, ACR: Minimum ACR Frequency MHz Permanent Link Class D Channel Class D 1.0 59.1 57.8 4.0 47.7 46.1 10.0 39.4 37.0 16.0 34.5 31.4 20.0 32.0 28.7 31.25 26.6 22.9

62.5 16.7 12.1 100 8.7 3.1 Optical fibre grades have already been mentioned. The multimode fibre performance is: Wavelength nm Max attenuation db/km at 20 o C Min modal bandwidth MHz.km at 20 oc 850 3.5 200 1300 1.0 500 Singlemode fibre is specified as having an attenuation of 1 db/km or less at 1310 and 1550 nm. The SC duplex connector is specified for new installations although the STII connector (referred to in the Standard as BFOC/2.5) is allowed. Additional Information: The new test standard referred to is IEC 61935. The following tests are required as on-site acceptance tests. Either the channel or permanent link may be tested. Remember the permanent link is also called the Basic Link when two 2-metre patch cords are added to connect the test instrument. IEC 61935 Wire Map Attenuation NET pair to pair NET Powersum ELFET pair to pair ELFET Powersum Return Loss Propagation Delay Delay Skew Delay Skew The above information is offered as a summary of ISO 11801 and Amendment 2. It is not a definitive design guide and does not replace study and implementation of the Standard itself. The publisher accepts no responsibility for inaccuracies or omissions. To purchase the full Standard

go to your national standards body, e.g. British Standards Institution, Nederlands Normalisatie Instituut etc. or ISO.