EY-EM 522, 523: Remote I/O module, ecolink522, 523

Similar documents
EY-EM 527: Remote I/O module, ecolink527

EYL225: nova225, Compact automation station

NRT 105: Electronic fan-coil controller, equiflex

Overview of types. Technical data

Functional data Factory settings Variable Settings

NRT 300: Electronic air-conditioning controller, heating/cooling, equiflex

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque

CONTA-ELECTRONICS. Converter Units

Highlights Very compact EtherCAT I/O system in IP 20 for plug-in into a circuit board (signal distribution board)

Fan-coil intelligent unitary controller

11 VA Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque (nominal torque) Motor Spring return

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

s Climatix extension module 26 I/Os POL985.00/XXX

LED Driver Compact dimming

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals

PHASED OUT. LED Driver Compact dimming. Driver LCAI 55W 900mA 1750mA ECO C ECO series

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electronic Step Controller

LED Driver Compact dimming

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

PHASED OUT. LED Driver Linear / area dimming. Driver LCAI 20W 150mA 400mA ECO lp ECO series

Electronic Circuit Breaker ESS1 for System SVS1

Electronic Air / Fuel Ratio Control System

LED Driver Linear / area dimming

EYK220: nova220, Compact automation station with BACnet interface

Excel 800 / Excel Web II CABLE SPECIFICATIONS

PHASED OUT. LED Driver Linear / area dimming. Driver LCAI 20W 350mA 550mA ECO lp ECO series

LED Driver Linear / area dimming. Udriver LCAI 20W 350mA 550mA ECO lp ECO series

POINTAX 6000L2 Point Recorder

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

PHASED OUT. LED Driver Compact dimming. Driver LCAI 20W 350mA 900mA ECO SR ECO series

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Analogue temperature controllers

ZITARES ICD SELV constant current control gear, 2-channel, dimm- and programmable

PHASED OUT. LED Driver Compact dimming. Driver LCAI 55W 900mA 1750mA ECO SR ECO series

ECB-103 BACnet B-ASC 10-Point Programmable Controllers

02/11/2015

em4 local - Robust Specific characteristics Part number

PHASED OUT. LED Driver Linear / area fixed output. Driver LCI 20W 150mA 400mA TOP lp TOP series. Product description

LED Driver Compact fixed output

PHASED OUT. LED Driver Linear / area dimming. Driver LCAI 100W 350mA 900mA ECO INDUSTRY sl ECO series

This data sheet is only valid in association with the IL SYS INST UM E user manual.

PHOENIX CONTACT - 03/2007

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

MCR-T-UI(/NC) MCR-T-UI-E(/NC)

US2, US4, US6 Electronic step controllers

ZITARES NCD FX-30 Non-SELV (isolated), constant current control gear, 1-channel, dimmable

Electronic Circuit Breaker ESS1 for System SVS1

PHASED OUT. LED Driver Linear / area fixed output. Driver LCI 35W 350mA 900mA TOP lp TOP series

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

modu420: Automation station

B850 Boiler House Energy Monitor

PHOENIX CONTACT - 09/2009

B850 Boiler House Energy Monitor

Current consumption ma solenoid current consumption ( max 300 ma) Hz % V ma. Housing dimensions mm 120(d) x 99(h) x 23(w)

Isolators A3/1. Temperature Transmitter Field Circuit Non-Ex i Series

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

PHASED OUT. LED Driver Compact fixed output. Driver LCI 10W 150mA 400mA TOP C TOP series. Product description

Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version

UniStream Uni-I/O Modules

XIOC technology and networking modules

02/11/2015

Intelligent Drive Systems, Worldwide Services SK 700E F 3070 GB

02/11/2015

ZITARES CCD 2 nd Generation SELV constant current control gear, 1-channel, dimm- and adjustable

02/11/2015

AC 01.2 HART Technical data Actuator controls

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

PHASED OUT. LED Driver Compact fixed output. Driver LCI 10W 350mA 900mA TOP C TOP series

Isolators A3/1.

General Specifications

ZITARES ICD SELV constant current control gear, 2-channel, dimm- and programmable

The universal input/output device is a DIN rail mounted device. It is connected to the EIB via a bus connecting terminal.

RAD-IN/OUT-8D. Digital extension modules for the bidirectional wireless system. INTERFACE Data sheet _en_05. 1 Description

em4 em4 alert em4 alert 2G

PHASED OUT. LED Driver Compact fixed output. Driver LCI 20W 350mA 900mA TOP C TOP series

Type CP-S, CP-C & CP-A Switch mode

MODEL: M2XU MODEL: M2XU [1][2] [3][4]

02/11/2015

EMD-FL-3V-400. Electronic monitoring relay for voltage monitoring in three-phase networks. INTERFACE Data sheet _en_03. 1 Description.

ZITARES NCD FX-30 Non-SELV (isolated), constant current control gear, 1-channel, dimmable

JUMO Wtrans Receiver Universal Receiver for JUMO Wireless Measuring Probes

MD-45 AC MD-45 LV/HV INSTALLATION MANUAL

CP-T range Product group picture

CAN-IO Custom IO remote module

PowerPlex Compact Module PP-C-COM24

Operating Instruction

Description of functions Controller system VR660 / A200R

Custom "Compact" range with display CD20 Custom Part number

VersaPoint I/O Module

Power supply CP-D 24/4.2 Primary switch mode power supply

KNX ENO 620/622 (32-channel AP)

SEM1600T RTD/TC/SLIDE WIRE SIGNAL CONDITIONER

ZITARES NCD 2 nd Generation Non-SELV, constant current control gear, 1-channel, dimmable

Operating instructions Measured signal converter for temperature sensors. TP323x / / 2010

Transcription:

Product data sheet 94.077 EY-EM 522, 523: Remote I/O module, ecolink522, 523 How energy efficiency is improved Regulation, control, monitoring and optimisation of operational systems, e.g. room automation or HVAC engineering, in combination with an automation station Features Part of the SAUTER EY-modulo 5 system family Remote I/O module for ecos500, 504, 505 and modu521 Switching and dimming of up to 4 lamps Can be located up to 500 m from the automation station EY-EM522F001 Technical data Power supply Power supply 230 V~, ±10%, 50...60 Hz Current consumption Ma. 20 ma (typically 14 ma) Without load current of relays Power loss Ma. 2.5 W (typically 1.5 W) Ambient conditions Inputs/outputs Relay outputs Operating temperature 0...45 C Storage and transport temperature -25...70 C Admissible ambient humidity 10...85% rh, no condensation 0-I relay, NO contacts 230 V~ with voltage applied Load 230 V~/5 A resistive load Total ma. 10 A Switching frequency > 3 105 cycles DIM 10V outputs 1...10 V passive output for electronic ballasts as per EN 60929 Electrically isolated Analogue outputs 0...10 V / 2 ma Universal inputs Analogue 0...10 V / 0...1 V Digital O-I Resistance 100 2500 Ω Potentiometer 1...10 kω Ni1000/Pt1000-20...100 C Activation From ecos500, 504, 505, modu521 Interface RS-485 Protocol SLC Interfaces and communication Connection to automation station Line 4-wire, twisted, shielded Cable length1) Up to 500 m with bus termination EY-EM523F001 Construction Dimensions W H D 105 95 60 mm Weight 0.32 kg of protection2) IP 00 (EN 60730) Protection class II (EN 60730-1) Environment class 3K3 (IEC 60721) Standards and directives 1) 2) See the section Engineering notes IP 20 with terminal cover (accessory 0900240020); IP 40 at front when mounted Right of amendment reserved 2015 Fr. Sauter AG 4.1 1/9

CE conformity according to EMC Directive 2004/108/EC 3) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 Overview of types EY-EM522F001 EY-EM523F001 Description Low-voltage directive 2006/95/EC EN 60730-1 Remote I/O module, 230 V~, 4 normally-open relay contacts, 4 DIM outputs Remote I/O module, 230 V~, 4 DIM outputs Overview of I/O mi EY-EM 522 EY-EM 523 Normally-open relay contacts (with voltage applied) 4 - DIM-10V 4 4 Analogue outputs 4 4 Universal inputs 4 4 Accessories Description 0949360003 Plug-in connector for ecolink RS-485, 10 pcs 0900240020 Terminal cover Description of operation The ecolink family is comprised of a range of remote I/O modules for operating on automation stations (AS) of the modulo 5 system family. ecolink modules can be used to epand the I/O mi of the inputs and outputs of automation stations. By placing the modules directly beside the actuators or sensors in the room and the digital RS-485 connection to the AS, the wiring needed can be reduced considerably. The inputs/outputs (I/O) of the modules are controlled directly by the automation program of the AS. No additional programming of the ecolink modules is required. The modules in the ecolink522, 523 series are typically used to actuate dimmable lamps with presence detectors and light sensors, as well as valves and fans, with a linear control signal. Intended use This product is only suitable for the purpose intended by the manufacturer, as described in the Description of operation section. All related product regulations must also be adhered to. Changing or converting the product is not admissible. Engineering notes The ecolink field modules can be fitted using a DIN rail directly in the cabinet or at a suitable location in the system. ) Note In the ecolink modules, the ground terminals ( ) are connected to the common connection (c) of the RS-485 interface (the RS-485 interface is not electrically isolated). In the EY-modulo 5 ecos, the ground terminals ( ) are internally connected with the earth connector (PE). The ma. admissible bus length depends on the cable type used and the correct termination with terminating resistors. In general, a 4-wire shielded cable with twisted wire pairs must be used. Observe the correct polarity of all signals. The wire shield of the entire bus line must be connected continuously, and connected to the protective earth as directly as possible (ma. 8 cm) at one location, for optimum resistance to interference. For Ethernet CAT-5 cables, as well as IYST-Y cables, a bus length of up to 500 m is possible. For RS-485 interfaces, the bus cabling must be in a line topology. Star, tree or branch topologies are not recommended. The devices do not have internal terminating resistors. Therefore, a terminating resistor of 120 Ω (0.25 W) must be connected at the start and end of the bus line, parallel to the D+/Ddata lines. Parallel laying of sensor lines and high-power current-carrying cables must be avoided. For the conduction of analogue signals, such as 0...10 V inputs/outputs and Ni/Pt1000 inputs, a separate grounding must be provided for every input and output from the ecolink module to the relevant sensor or actuator. Shared ground wires lead to measurement errors that may particularly affect small measuring signals. 3) EN 61000-6-2: In order to meet the European standard, the power cables for the inputs and outputs must not eceed 30 m in length 2/9 4.1 Right of amendment reserved 2015 Fr. Sauter AG

Addressing/baud rate Off On Value 1 2 4 8 16 Off On 1 2 4 8 All ecolink modules that are operated on a bus line must be uniquely addressed. An 8-position DIL switch is provided for this, with the settings coded in binary. The valid address range is 1-31 and can be restricted by the connected automation station. Address 15 is set as an eample in the image. The baud rate is fied at 115 kbaud. Fitting and power supply ecolink field modules are compact units suitable for wall mounting or for DIN 43880 installation on a 35 mm DIN rail. The plant devices are connected using screw terminals. The following conditions must be observed: Connection may only be performed when the system is disconnected from the electrical supply. The unit must be protected against contact. The universal input (terminals 20...26), analogue output (terminals 27...33) and RS-485 (D-, D+, C) connections are SELV electrical circuits. SELV electrical circuits must be laid separately from the mains supply circuits (low voltage) and the functional etra low voltage (FELV). The DIM connections (terminals 5...12) are control circuits designed for connection to electronic ballasts for lamps as per IEC 60929. DIM control circuits may be laid together with mains supply circuits; cables that are admissible for 230 V mains voltage must be used. The DIM electrical circuits are electrically isolated from all the SELV/PELV electrical circuits in the ecolink device and must not be connected with SELV/PELV electrical circuits at any point. 0 10 V analogue outputs must not be misused as DIM outputs. The relay connections (terminals 1...4) are mains supply circuits that are connected internally with connection L (phase). For terminals 01...33, the admissible conductor cross-section is min. 0.8 mm 2 (AWG 18), ma. 2.5 mm 2 (AWG 13). The national standards and installation rules must be adhered to. Communication wires must be laid professionally and must be separated from other power-carrying wires. Special standards such as IEC/EN 61508, IEC/EN 61511, IEC/EN 61131-1 and -2 were not taken into account. Local requirements regarding installation, usage, access, access rights, accident prevention, safety, dismantling and disposal must be taken into account. Installation standards EN 50178, 50310, 50110, 50274, 61140 and similar must also be observed. For further information, see fitting instructions P10013055. Terminal cover Accessory 0900240020. When the cover is on, together with the ecolink module, it ensures protection class IP 20. When mounted, the protection class on the front is IP 40. The customer must attach a cord grip for the connected lines. Technical specification of the inputs and outputs Universal inputs (UI) Four universal inputs are available. The functions for the inputs and the input ranges are parameterised via CASE Engine. Right of amendment reserved 2015 Fr. Sauter AG 4.1 3/9

of inputs Protection against eternal voltage: Input impedance (Ri) Scan rate Update rate Voltage (U) Measuring range Current (I) Measuring range Ni1000 Pt1000 Voltage (U) Current (I) Digital input (DI) Ni1000/Pt1000 Resistance (R) Potentiometer (Pot) ±30 V/24 V~ (without destruction) 80 kω 10 bits 100 ms (analogue/digital values) 300 ms (EY-modulo 5 ecos) 0 (2)...10 V / 0 (0.2) 1 V 0.1 V / 0.01 V ±0.2 V / ±0.02 V 0 (4)...20 ma With eternal resistance and voltage input (U) Measuring range 0 (2) 10 V: 500 Ω Measuring range 0 (0.2) 1 V: 50 Ω DIN43760 IEC751 Measuring range -20 100 C Measuring current Resistance (R) Measuring range Measuring current Potentiometer Measuring range Nominal resistance Output 10V (terminal 20), ma. load Digital input Potential-free contacts Output current Voltage signal Meter input Voltage measurement (U) 0.3 K ±1 K 1 ma 100 2500 Ω 5 Ω ±25 Ω 1 ma 0 100% (position) 1 10 kω 1 % of measuring range ±2 % of measuring range 10 ma (i.e. 1 kω) Connected to ground I: < 1.5 kω 0: > 7 kω 1 ma I: 0...1.5 V 0: 3...11 V Ma. 2 Hz (min. pulse duration 250 ms) The voltage to be measured is connected between an input terminal and a ground terminal. The signal must be potential-free. Two measuring ranges are available 0 10 V and 0 1 V. Current measurement (I) A current measurement 0(4) 20 ma is possible via eternal resistance. The current to be measured is connected parallel to the resistance at one of the input terminals and a ground terminal. The accuracy of the current measurement results from the accuracy of the voltage input and the tolerance of the resistance. It is preferable to use a 50 Ω resistance in order to keep the effect of self-heating on the accuracy to a minimum. The current signal must be potential-free. A separate ground terminal must be used for the current measurement. Otherwise, zero-point shifts may lead to imprecise measurements in the case of other measuring signals. 4/9 4.1 Right of amendment reserved 2015 Fr. Sauter AG

Temperature measurement (Ni/Pt); resistance measurement (R) The Ni/Pt1000 sensors and resistors are connected using two wires between one of the input terminals and a ground terminal. The inputs require no calibration and can be used immediately. Line resistance of 2 Ω is pre-compensated as standard. With the correct line resistance of 2 Ω (cable crosssection 1.5 mm 2 ), the power cable (wire) may be no more than 85 m long. Larger line resistances can be compensated by the parameterisation in CASE Engine. The measuring range for the resistance measurement is limited to 2500 Ω. If line break detection is desired, a threshold of, for eample, 2400 Ω can be set in the ecos 5 automation program. Potentiometer (Pot) This configuration is used to record the position of the potentiometer in the range 0 100%. The nominal resistance of the potentiometer is connected between the 10 V output (terminal 20) and a ground terminal. The sliding contact of the potentiometer is connected to one of the input terminals. Terminal 20 is used eclusively to supply the potentiometers, as shown in the connection diagram. The output must not be connected to other devices. If multiple potentiometers are connected to terminal 20, the specified ma. load must be adhered to. The ratiometric measuring method compares the sliding contact voltage at the input with the voltage at the 10 V output and determines the position of the potentiometer in the range 0 100%. No calibration and parameterisation of the nominal resistance are required. A line resistance of less than 10 Ω does not affect the measuring range (corresponds to appro. 400 m for a cable cross-section of 1.5 mm 2 ). A greater line resistance restricts the measuring range accordingly. Digital inputs (DI) The digital input function can be used with both potential-free contacts and voltage signals. Potentialfree contacts and voltage signals are connected between an input terminal and a ground terminal. Digital inputs are generally used as alarm/status inputs. Therefore, an open contact corresponds to the state 0 - INACTIVE (bit=0). A closed contact corresponds to the state I - ACTIVE (bit=1). This assignment, defined as normal polarity, can be inverted using CASE Engine if required. Analogue outputs (AO) Number of outputs 4 of outputs Load Update rate Settling time 0(2)...10 V 2 ma 0.1 V ± 0.4 V 200 ms (EY-modulo 5 ecos) 1 s The output voltage is taken from between the relevant output terminal and a ground terminal. Every output can be subjected to a load of 2 ma (the outputs do not have an active sink capability). The analogue output is short circuit-proof and grounded and is protected against eternal voltages. Permanent short-circuiting of multiple outputs leads to their thermal destruction. Relay outputs The relay outputs are supplied via a common feed (L). When the relays are used to switch lamps, window blinds or fans directly, neither the nominal load nor the specified start-up current of the relays may be eceeded. Some lamps and electronic ballasts of lamps have very large start-up currents, which are specified on the manufacturer s data sheet. Inductive loads must be suppressed correctly. Number of outputs Ma. 4 of outputs Nominal load per contact Start-up current Total current for all contacts Switching frequency Update rate 0-I relay, normally-open contacts (NO) 230 V~, 5 A resistive load 3A inductive load (cosφ > 0.4) 30 A for ma. 20 ms 10 A > 3 10 5 cycles for nominal load 200 ms (EY-modulo 5 ecos) Right of amendment reserved 2015 Fr. Sauter AG 4.1 5/9

DIM 10V outputs Number of outputs 4 of outputs Sink capability Update rate Settling time 1...10 V passive output for electronic ballasts with basic insulation 2 ma 8 bits 200 ms (EY-modulo 5 ecos) 1 s The outputs are sized with an 1 10 V interface for the control circuits of electronic ballasts (EB). The control output is provided by the EB (current source ma. 0.6 ma as per EN 60929). The output is passive and only provides the interference-proof DC voltage signal of 1 10 V in combination with the current source of the EB. 1 V is the minimum brightness (EB control circuit short-circuited, i.e. 1 V or less), 10 V is the maimum brightness (control circuit open). Accordingly, no active voltage is supplied to the output terminals of the DIM output. The sink capability (eternal voltage distribution) is linear to the internal specification (0 100% corresponds to 0 10 V) for the approved electronic ballasts (EB). Only one EB should be connected per DIM output. If multiple EBs are connected in parallel, they influence each other, so that, on the one hand, the signal range can be restricted and, on the other, there is non-linear behaviour. To connect multiple EBs to one DIM output, signal amplifiers from the EB manufacturer must be used. EBs are dimmed using the control circuit via the DIM-10V outputs. A relay output must be used to switch the EB power line on/off. The DIM-10V output must be connected to the EB with the correct polarity (+/-). Approved ballast devices The following ballast devices have been checked: Manufacturer OSRAM Philips Quicktronic intelligent: QT/-T/E 1 18-57 DIM HF-R 1 26-42 PL-T/C EII Vossloh Schwabe ELXd 142-806 Safety instructions for EB devices The control circuits of EBs only have basic insulation from mains supply circuits and therefore are not SELV current circuits (safety etra low voltage). For this reason, the DIM-10V outputs of the ecolink module are potentially isolated (secure electrical isolation) via opto-couplers from all the SELV/PELV current circuits of the ecolink module (universal inputs, analogue outputs, communication). DIM-10V outputs must not be connected with SELV/PELV current circuits. Based on the insulation capability of the ecolink module, all the connected ballasts must be connected to the same phase of the power supply. The safety instructions from the EB manufacturer must be adhered to during installation. LED indicator Status LED off Green light Flashing green Red light Flashing red Pulsating red Orange light Description Device not in operation Device in operation Device is communicating with the AS but is not being addressed Device is not ready for operation (no program loaded) Device is not communicating with the AS Internal device error or short circuit of an output Power-up phase, configuration Start-up behaviour/monitoring functions The communication between the AS and the ecolink modules is monitored. If the communication fails for more than the monitoring time of 10s, the affected ecolink modules switch to the safety status. The data points in the AS are marked with the status unreliable. All outputs of the affected eco- Link modules are switched to the defined value for the safety state ( relinquish default ). 0-I transitions (i.e. not actuated - actuated) of relays are delayed by 1s. This applies both when reaching and when leaving the safety state. This can prevent damage due to immediate switchovers of actuators 6/9 4.1 Right of amendment reserved 2015 Fr. Sauter AG

such as window blinds. The inputs of the modules in question remain frozen at their last value while the safety status is in force. Additionally, if there are internal device errors, appropriate data points are mapped via the Reliability property. The start-up behaviours (power-up) of the AS and ecolink are different. The power-up timer parameter in the ecolink (default value = 1 s) defines the waiting time of the ecolink until the communication monitoring starts. This parameter can be set individually for each ecolink module (value range 1...254 s). Settings are made using the SAUTER CASE Suite software. Until the power-up timer has elapsed, the outputs will be maintained in the same manner as when the device is without power. The power-up timer parameter can be used to define a start-up sequence for the ecolink modules or to synchronise the start-up behaviour with the AS. The operation behaviours differ as follows: a) AS in operation, ecolink module power-up The ecolink module maintains its outputs in a powerless state during power-up. If the AS detects an ecolink power-up, communication with this module starts immediately. After the parameterised power-up timer has elapsed and communication with the AS is successful, the module switches to normal operation. If communication with the AS cannot be established within the monitoring time, the module switches to the safety state. b) AS and ecolink module power-up Start-up proceeds in the same manner as the process described under a). Because the AS start-up takes longer than the monitoring period, the ecolink modules will enter the safety state until the AS has started completely, after which they switch to the normal mode. If this is not desired, the power-up timer parameter can be set to a value > 120s. c) ecolink in operation, AS power-down A power-down of the AS has the same effect as a communication interruption (see communication monitoring). If the AS is then powered up, communication with the ecolink modules is automatically established. The modules leave the safety state as previously described. Integration of ecolink modules via CASE Suite The ecolink modules are engineered using CASE Suite. The integration is described using the eample of the eco500: When an ecos 5 is selected as the automation station, it can be set up for one, two or up to eight room segments (function segments). The types and addresses of the required ecolink modules are then defined in the Definition module within CASE Engine. After this, all the inputs/outputs of the eco- Link modules can be used in CASE Engine and be mapped to BACnet data points. Additional information Fitting instructions Declaration on materials and the environment P100013055 MD 94.077 Disposal When disposing of the product, observe the currently applicable local laws. More information on materials can be found in the Declaration on materials and the environment for this product. Right of amendment reserved 2015 Fr. Sauter AG 4.1 7/9

Connection diagram EY-EM 522 LN 01 02 03 04 05 06 07 08 09 10 11 12 L' L' L' L' + - + - + - + - DIM 1 DIM 2 DIM 3 DIM 4 4 Light Dimming DIM- 10V Power In 4 Relay NO RS485 Run+ 10V 4 Universal Input (UI) 4 Analog Output 20 22 24 21 26 23 25 28 30 32 27 29 31 33 D- D+ C NC + - Pot. DI 0...10 V 50...500 Ω + - R/Ni/Pt 0...20 ma EY-EM 523 230V~ LN 05 06 07 08 09 10 11 12 + - + - + - + - Power In DIM 1 DIM 2 DIM 3 DIM 4 4 Light Dimming DIM- 10V RS485 Run+ 10V 4 Universal Input (UI) 4 Analog Output 20 22 24 21 26 23 25 28 30 32 27 29 31 33 D- D+ C NC + - Pot. DI 0...10 V 50...500 Ω + - R/Ni/Pt 0...20 ma RS-485 bus wiring, ecolink modules only AS 1) V 0,25 W 0,25 W 1) AS = automation station 8/9 4.1 Right of amendment reserved 2015 Fr. Sauter AG

Dimension drawing Fr. Sauter AG Im Surinam 55 CH-4016 Basel Tel. +41 61-695 55 55 www.sauter-controls.com Right of amendment reserved 2015 Fr. Sauter AG 4.1 9/9