Power Distribution System SVS18

Similar documents
Power distribution system SVS25

Power Distribution System SVS20

Power Distribution System SVS02

Power Distribution System SVS02

Electronic circuit breaker ESS30-Sxxx-DC24V

Electronic Circuit Breaker with reset input ESS20-1..

Electronic Circuit Breaker ESS1 for System SVS1

Electronic Circuit Protector ESX10-T

Electronic circuit protector REX12

Switched mode power supply for DIN rail mounting type SMP23 DC24V/40A

Electronic Circuit Breaker ESS1 for System SVS1

Switched mode power supply for DIN rail mounting type SMP21 DC24V/10A

Electronic Circuit Breaker ESS20-0..

PHOENIX CONTACT

Electronic Circuit Protector ESX10

REX12 Electronic Circuit Protector

Electronic Circuit Breaker ESS1 for System SVS1

PHOENIX CONTACT

Smart Power Relay E I...

REX12 Electronic Circuit Protector

PHOENIX CONTACT - 09/2009

Datasheet. Electronic Circuit Protection ESX10-T

Solid State Remote Power Controller E

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

MINI-PS AC/24DC/1.3

MCR-SL-CUC Universal current transducer. Data sheet _en_05. 1 Description

QUINT-PS/ 1AC/24DC/20

Power supply CP-E 24/2.5

QUINT-PS/ 3AC/24DC/10

120/240 Watt AC-DC Front End with PFC W Series Convert Select 120 Convert Select 240

Power supply CP-E 24/20.0

Power supply CP-T 24/20.0 Primary switch mode power supply

Installation and Operating Instructions for Phase Demodulator Type _.2

QUINT-PS/ 3AC/24DC/40

QUINT-PS-24DC/24DC/10

Power supply CP-E 12/10.0 Primary switch mode power supply Data sheet

Power supply CP-T 24/10.0 Primary switch mode power supply

Switching power supplies CP range, Linear power supplies CP-L range. Content

Power supply CP-E 24/0.75

QUINT-PS AC/24DC/40

Power supply CP-E 24/2.5

Power supply CP-T 24/40.0 Primary switch mode power supply

Power supply CP-T 48/20.0 Primary switch mode power supply

Type CP-S, CP-C & CP-A Switch mode

EPSITRON Electronic Circuit Breakers For Secondary Side DC Protection

Device circuit breakers Selective power distribution: branch out, individual adaptation, modular extension

Power supply CP-E 48/5.0 Primary switch mode power supply Data sheet

Electronic circuit protector ESX10-Sxxx-DC24V-1A-10A

Power supply CP-D 24/4.2 Primary switch mode power supply

DT1100 xx xx xx PS. Isolators, Isolator / Power Supplies. Operating Instructions

Power supply CP-T 48/5.0 Primary switch mode power supply

PowerPlex Compact Module PP-C-COM24

Control module CP-A CM

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

Electronic Air / Fuel Ratio Control System

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

Adjustable Digital Process Instrument MDK480

EMD-FL-C-10. Current Monitoring Relay. Data Sheet. Functions. Structure 08/2004

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

Digital electronic module 4DO DC24V/2A HF (6ES7132-4BD30-0AB0) SIMATIC

Installation and Operational Instructions for ROBA -switch Type 017._00.2

Power supply CP-D 24/1.3

VEO. V2PF480Y/277VS01 Art.Nr.: B TECHNICAL DATA

Circuit Breakers. Excerpt from Master Catalogue. Circuit Breakers. Specifically For You

MINI-PS AC/2X15DC/1

User and Safety Manual ProLine P224xx P1

DT1100 E xx xx (PS) Galvanic Isolators. Operating Instructions

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

EPSITRON Electronic Circuit Breakers Compact and Precise ECBs for DC Circuits

Increasing security. Saving space. Gaining flexibility. Signal Conditioners for Industrial Automation

V2UM230V10 Art.Nr.: V2UM230V10P Art.Nr.: Control elements. Tripping delay. Function selector. Status indication 230 V AC/DC

(1,5 modules per pole)

TRIO-PS-2G/1AC/24DC/5

Add-on modules DX 3 63A for MCBs DX 3 1,5 modules per pole

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

Power supply CP-D 12/2.1

Short-circuit-proof switching amplifier for inductive loads up to 10 A

Series P. Applications

Thermistor motor protection relays

Output of three-phase motors at 50 Hz and 400 V

Digital Input Output Module 24 V for Ex n Zone 2 Series 9472/35

Industrial motor controller for brushed DC motors 24 VDC

FIB / FIC. r with Overcurrent Protection (RCBO) Doepke. » effi cient. » reliable. » fl exible. » future-oriented

CP-T range Product group picture

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

Assembly. Front view. DIP switch. LED yellow: Relay output 1. LED yellow: Relay output Power Rail

Power Electronics. POWERSWITCH Solid-State Contactor BF 9250, BH 9250

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters

High Performance Current Transducer IT 200-S ULTRASTAB = A. ε L

Switching Devices Contactors and Contactor Assemblies for Switching Motors

Low profile safety relay with forcibly guided double contacts FEATURES. Relay height, 14.5mm. 4a2b

FEATURES OPTIONAL FEATURES

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

Industrial motor controller for brushed DC motors 24 VDC

Residual Current Operated Circuit-Breakers (RCCBs)

Installation and Operational Instructions for ROBA -switch Type 017._00.2

CP-T range Benefits and advantages

Transcription:

Power Distribution System SVS8 Description The power distribution system SVS8 optimises the DC V distribution in automation and process control, in the production area of the chemical industry and in power plants. The power distribution system SVS8 DIN rail mounting distributes all voltage potentials supplied by a V power supply (SMPS) onto /0 ways F to F/F0 (arranged from right to left). The system offers integral redundancy diodes in each protected load output and selectively protects the connected loads such as controls, transformers, actuators, magnetic yoke subassemblies, bus modules etc. by means of the circuit breaker fitted. With a max. total current of A and a typical load current of 3 A per way (max. A in limited continuous duty) the SVS8 provides ease of distribution and sub-distribution in short-circuit-limited DC V applications. All auxiliary contacts (make contacts) of the plugged-in circuit breakers are connected in series and allow group signalling in accordance with the closed-circuit principle. The protected»l+«load outputs with redundancy diodes per way significantly reduce the otherwise standard wiring time. All terminals of the DC V supply, load outputs with 0 V return conductor as well as the signalling terminals are screwless spring-loaded terminals. Suitable for the following E-T-A circuit breaker types: electronic circuit breaker ESS0-00DCVmax. A electronic circuit breaker ESS30-0DCVmax. A electronic circuit protector ESX0-0DCVmax. A Features and benefits l Systematic integration of overcurrent protection, power distribution and signalling on one board l Power distribution and selective protection of DC V load circuits fed by a single power supply (SVS8-0) or by two separate power supplies (SVS8-0) l Clear distribution concept, two each redundancy diodes (typically. A, max. 3 A per diode) connected in parallel integral in each load output l Terminal block for group signalling (make contacts) l Profitability through significant reduction of wiring time l Reduced time and expenses for planning, design and installation l Ease of maintenance, diagnosis and system extension Technical data (T amb = C, U B = DC V) Application Modular power distribution system for short circuit current limited DC V applications. Use with switch-mode power supply, e.g. type Quint DC V / 0 A (manufactured by Phoenix Contact) Supply SVS8-0 Rated voltage: DC V (8...30 V) Total current: max. A, continuously DC V (+) = X L/L DC V (-) = X // L: supply potential for F F : 0 V return conductor Terminals Supply SVS8-0 Rated voltage: Total current: Terminals screwless block, -pole max. cable cross section 0,...0 mm DC V (8...30 V), supply potentials L and L possible Caution: L and L are bridged when delivered max. A, continuously DC V (+) = X L/L DC V (+) = X L/L DC V (-) = X // L: supply potential for F//F/F L: supply potential for F/F/F/F8/F9/F0 : 0 V return conductor for L and L screwless block, -pole max. cable cross section 0...0 mm F-positions SVS8-0 Input Output L slots F to F for electronic circuit breakers, prepared for types ESS0-003, ESX0-03: placed from right (F) to left (F) F F: input connected to V-voltage L F F: Output via redundancy diodes to X/L X/L (terminals, each) Please plug jumper SB--P-0--A into free slots (to be ordered separately, see accessories) Caution: When using an electronic circuit breaker rated > 3 A, the redundancy diodes have to be connected in parallel. The jumper for connecting the diodes in parallel has to be plugged in. 33 www.e-t-a.de

Power Distribution System SVS8 Technical data (T amb = C, U B = DC V) Technical data (T amb = C, U B = DC V) F-positions SVS8-0 0 slots F to F0 for electronic circuit breakers, prepared for types ESS0-003, ESS30-03, ESX0-03: placed from right (F) to left (F0) Input F,, F, F: input connected to V-voltage L F, F, F, F8, F9, F0: input connected to V-voltage L Output L F,, F, F: Output via redundancy diodes to X/L, X3/L, X/L, X/L (terminals, each) Output L F, F, F, F8, F9, F0: Output via redundancy diodes to X/L, X/L, X/L, X8/L, X9/L, X0/L (terminals, each) Please plug jumper SB--P-0--A into free slots (to be ordered separately, see accessories) Caution: When using an electronic circuit breaker rated > 3 A, the redundancy diodes have to be connected in parallel. The jumper for connecting the diodes in parallel has to be plugged in. outputs per way Rated voltage DC V (8 30 V) Current max. A per terminal block (X X/X0) / per slot (F F/F0) Caution: max. load current has to be observed typically 3 A per slot / typically. A per diode (standard redundancy operation) max. A per slot / max. 3 A per diode (for 8 hrs at T amb 0 C) Condition as supplied: load output bridge plugged in, the diodes are connected in parallel Example: On slot F, the diodes D. and D. and thus also the outputs (, ) are connected in parallel on terminals X/L. Number protected load outputs L (/) joint negative return conductors of load (/) Terminals plug-in-terminal block, pole, max., mm Signalling Signalling terminal X3 ( x pole) for group signal (3//)(//) of slots F F/F0 (3= x signal supply, = x signal-outputs) Rated voltage DC V (8 8 V) Total current max. 0, A Caution: please provide fast external protection 0. A or feed current-limited signal (e.g. DC-OK-output of power supply) Terminals block, pole, max.. mm Termination Supply terminals - terminal block (X) Plug-in terminal block, -pole max. cable cross section flexible with wire end ferrule (with plastic sleeve) 0. 0 mm stripping length 8 mm load output / Minus- and signalling terminal block (X X/X0/X3) Push-In-terminal block, pole / pole max. cable cross section flexible with wire end ferrule (with plastic sleeve) 0.. mm flexible with wire end ferrule (without plastic sleeve) 0.. mm stripping length with wire end ferrule 8 mm General Data Mounting rail mounting to EN 0 3 x. Temperature range 0...0 C (without condensation) Storage -0...+0 C temperature Housing material plastic Protection class to DIN 000: terminals IP0, diods IP00 Insulation voltage Dimensions Mass Ordering information to IEC 093: 0. kv see drawings (tolerances to DIN ISO 8 part IT3) SVS8-0-C0 / approx 00 g SVS8-0-C0 / approx 30 g Type SVS8 power distribution system for ESS0-003, ESS30-03, ESX0-03 l For short circuit current limited DC V-applications l Max. A cont. load l Integral group signalling terminals X3, DC V / max. 0. A, have to be protected separately l Incl. isolated bridge for terminal L and L pushed in upon receipt l Incl. 0 isolated bridges for load outputs, parallel connection of diodes Dx. and Dx., pushed in upon receipt l Accessories: jumpers SB--P-0--A (for free slots), order separately Version, max. number of circuit breakers on the power distribution system circuit breakers (F...F) 0 circuit breakers (F...F0) Fitted version, load output and signalling terminals C0 standard: completed fitted with push-in-terminals (max.. mm², without wire end ferrule SVS8-0 - C0 ordering example Accessory: jumper, see Accessories www.e-t-a.de 33

Power Distribution System SVS8 Notes Mounting position l The max. total current of A must not be exceeded. l The max. current load of the redundancy diodes of typically. A, max. 3 A per diode, must be strictly observed. In the event of parallel connection of the two diodes, a load current of typically 3 A (max. A in limited continuous duty) must strictly be observed. l The signal circuit (max. 0. A) has to be protected separately or supplied via the current-limited DC-o.k.-output of a switch-mode power supply. l Jumpers type SB-S-P-0--A have to be inserted into free slots. l The user has to ensure that the proper cable cross section of the load circuit in question is chosen in relation to the rating of the load / circuit breakers. l Technical data of the circuit breakers have to be observed. l In addition special precautions have to be taken in the plant or machinery (e.g. use of a safety PLC) to prevent inadvertent startup of (parts of) the system (cf. Machinery Directive 00//EG and EN 00, Safety of Machinery). In the event of a failure (short circuit/overload) the load circuit will be disconnected by circuit breakers. l The power distribution system must only be installed by skilled personnel. l It is exclusively meant for the use with low voltages (= V). l Only after expert installation may the assembly be connected to a power supply. l After tripping of the circuit breaker and before reset, the cause of the tripping (short circuit or overload) must be remedied. l The national and international standards (e.g. DIN VDE 000 for Germany) must be observed with respect to installation and selection of cables. l Connection to higher or not reliably disconnected voltages may be hazardous or cause damages. Caution: Warning of hot surface, the diodes could be hot, do not touch risk of injury. 33 www.e-t-a.de 3

Power Distribution System SVS8 Wiring example: SVS8-0 with ESS0-003 and group signalling X3 + 3 + DC V max. 0, A -F -F - -F -F -F SO SO SO SO SO SO Wiring example: SVS8-0 with ESS0-003 and group signalling X3 + 3 + DC V max. 0, A -F0 -F9... -F -F - -F -F SO SO SO SO SO SO SO Schematic diagram SVS8-0-C0 DC V / max. A X L L F F F F F DC V / max. 0. A X3 D. D. D. D. D3. D3. D. D. D. D. D. D. F0 F9 F8 F F F 3 X0/L X9/L X8/L X/L X/L X/L (typically, A pro diode (typically, A pro diode (typically, A pro diode (typically, A pro diode (typically, A pro diode (typically, A pro diode www.e-t-a.de 33

Power Distribution System SVS8 Schematic diagram SVS8-0-C0 DC V / max. A X L L F0 F9 F8 F F F F F F L L DC V / max. 0, A X3 D0. D0. D9. D9. D8. D8. D. D. D. D. D. D. D. D. D3. D3. D. D. D. D. F0 F9 F8 F F F F F F 3 X0/L X9/L X8/L X/L X/L X/L X/L X3/L X/L X/L (typically, A pro diode (typically, A pro diode (typically, A pro diode (typically, A pro diode (typically, A pro diode (typically, A pro diode (typically, A pro diode (typically, A pro diode (typically, A pro diode (typically, A pro diode Dimensions: SVS8-0-C0 ca.,, rail mounting EN 0-3x, (not part of the product) DCV/A X L L Typ: 9 Typ: 9 Typ: 9 Typ: 9 Typ: 9 Typ: 9,3 G E R M A N Y D. D. D. D. D3. D3. D. D. D. D. D. D. Typ: SVS8-0-C0 Made in Germany F F F F F 3 X3 X/L X/L X3/L X/L X/L X/L terminals: power supply 0 mm -pole / max. A group signalling:, mm / max. 0, A load outputs load output bridge:, mm / pole, mm / -pole typically 3 A typically, A per diode in redundancy operation for diode (exchangeable) 33 www.e-t-a.de

Power Distribution System SVS8 Dimensions: SVS8-0-C0 ca., 8 rail mounting EN 0-3x, (not part of the product) jumper all-insulated -pole DC V / A Typ: SVS8-0-C0 X L L L L Typ: 9 Typ: 9 Typ: 9 Typ: 9 Typ: 9 Typ: 9 D. D. D. D. D. D. D8. D8. D9. D9. D0. D0. Typ: 9 D. D. Typ: 9 D3. D3. Typ: 9 D. D. Typ: 9 D. D.,3 F0 F9 F8 F F F F F F 3 X0/L X/L X/L X/L X3 X9/L X8/L X/L X/L X3/L X/L terminals: power supply 0 mm -pole / max. A group signalling:. mm / max. 0, A load outputs load output bridge:. mm / pole. mm / -pole typically 3 A typically. A per diode in redundancy operation for diode (exchangeable) www.e-t-a.de 33

Power Distribution System SVS8 Application example: SVS8--C0 fitted with ESS0-003 and ESX0-03 rail mounting EN 0-3-. (not part of the product). DC V / A X L L.3 approx. ESX0-... approx. 9 () ESS0-... Typ: 9 G E R M A N Y Typ: D. D. D. D. D3. D3. D. D. D. D. D. D. SVS8-0-C0 Made in Germany F F F F F 3 X3 X/L X/L X3/L X/L X/L X/L 33 www.e-t-a.de

Power Distribution System SVS8 Application example: SVS8-0-C0 fitted with ESS0-003 and ESX0-03 rail mounting EN 0-3-. (not part of the product) 8 approx. ESX0-... approx. 9 () ESS0-... Typ: SVS8-0-C0 DC V / A X.3 L L D0. D0. D9. D9. D8. D8. D. D. D. D. D. D. D. D. D3. Typ: 9 D. D. D3. Typ: 9 D. D. F0 F9 F8 F F F F F F Plug-in modules (circuit breakers) to be ordered separately. 3 X3 X/L X/L X/L X0/L X9/L X8/L X/L X/L X3/L X/L 8 www.e-t-a.de 33

Power Distribution System SVS8 Application example: jumper instead of circuit breaker (e.g. ESX0-003) If the power distribution system is not completely populated with circuit breakers, the open way can be closed with a plugged-in jumper type SB-S-P-0--A. The signalling pathway of the group signalling is as follows: - feed-in of DCV potential in X3 terminal (3) - via all aux. make contacts / of the fitted circuit breakers type ESX0-03 (or ESS0-003, ESS30-03) - back to the signal outputs of the group signal X3(////) In operating condition (i.e. all circuit breakers plugged in and ON) the signalling pathway from X3/3 to X3/ is closed. DC V / A 3 X3 Typ: SVS8-0-C0 X L L F0 F9 F8 F F F X/L X/L X/L X0/L X9/L X8/L X/L X/L X3/L X/L F F F Signalbrücke Signal Loop Accessories Jumper SB-S-P-0--A top view Signal loop SB-S-P-0--A 0.3 0.0. Made in Germany xxxx AC 0 V / DC V, A 3 0.3 Signal loop disconnected.3.8 terminals 3+ bridged blade terminals DIN A.0.8 All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved.product markings may not be exactly as the ordering codes. Errors and omissions excepted. 33 www.e-t-a.de 9