Propagation of Lightning Overvoltages Across MV/LV Substation Measurements and Modelling.

Similar documents
Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Modeling insulation in high-voltage substations

C4-301 EXPERIMENTAL EVALUATION OF TRANSFERRED SURGES IN MV TRANSFORMERS FROM HV/LV

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

Lightning Surge Simulator LSS-F03 series

Power Quality and Reliablity Centre

Technical Specification

Choosing the right Pico Technology active differential probe

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT

7P Series - Surge Protection Device (SPD) Features 7P P P

Novità sulla IEC ; -10; -12

Measurements for validation of high voltage underground cable modelling

Combination Wave Test System

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Active: Active probes achieve low input capacitance and high sensitivity by buffering and amplifying the signal close to the point of measurement.

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

EMC of Power Converters

B.Tech III Year II Semester (R13) Regular & Supplementary Examinations May/June 2017 DIGITAL SIGNAL PROCESSING (Common to ECE and EIE)

EMC Seminar Series All about EMC Testing and Measurement Seminar 1

MPS Electrical Test Laboratory, Larsen & Toubro Limited, Mysore Campus, KIADB Industrial Area, Hebbal Hootagalli, Mysore, Karnataka

EN :2007+A1:2011 Electromagnetic compatibility Emission standard for residential, commercial and light-industrial environments

Surge Generator for MIL-STD 1275

Towards an Accurate Modeling of Frequency-dependent Wind Farm Components under Transient Conditions

SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF CABLES AND OTHER ELEMENTS OF OUTSIDE PLANT

DISCRETE FOURIER TRANSFORM AND FILTER DESIGN

LS200 TEST DATA IEC61000 SERIES

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

FFT analysis in practice

Computer Aided-Program for Validation of HV Impulse Measuring Systems from Unit Step Response

High voltage amplifiers and the ubiquitous 50 Ohm: Caveats and benefits. Falco Systems application note, version 1.0,

Transient Data Acquisition System, TAS 4-40 Potential-free measurement of fast rise pulses:

Pre location: Impulse-Current-Method (ICE)

Published in: Proceedings of the International Conference on Power Systems Transients (IPST 2009)

Proposal of double voltage transmission line pulse generator using four coaxial cables

, ,54 A

SURGES TRANSFERRED TO THE LOW-VOLTAGE NETWORK VIA TRANSFORMER THE INFLUENCE OF THE LOAD CONNECTED TO THE SECONDARY

Experimental Study and Circuit Analysis Model of Lightning Isolation Transformer for Railway Signal System

PRACTICAL GUIDE. Low-voltage power systems Protection against overvoltages

EMC standards. Presented by: Karim Loukil & Kaïs Siala

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

ABSTRACT 1 INTRODUCTION

BLS to ADF transition system

Characterization of Conducted Emissions in Time Domain

Insulation Test System

IEC Electrical fast transient / Burst immunity test

Current clamps for AC current

INVENTION DISCLOSURE- ELECTRONICS SUBJECT MATTER IMPEDANCE MATCHING ANTENNA-INTEGRATED HIGH-EFFICIENCY ENERGY HARVESTING CIRCUIT

Substation Preventive Maintenance

SERIES K: PROTECTION AGAINST INTERFERENCE

Discrete Fourier Transform (DFT)

PD Solutions. On-Line PD Measurement Devices

EE 215 Semester Project SPECTRAL ANALYSIS USING FOURIER TRANSFORM

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Chapter 1. Overvoltage Surges and their Effects

10 Mb/s Single Twisted Pair Ethernet Evaluation Board Noise Measurements Marcel Medina Steffen Graber Pepperl+Fuchs

Progress Report on Failures of High Voltage Bushings with Draw Leads By Jim McBride and Larry Coffeen, JMX Services / NEETRAC 7/26/2010

Advanced Test Equipment Rentals ATEC (2832) Lightning Surge Simulator LSS-F02.

Network Analyzer for Low-, Medium- and High-Voltage Networks

CONDUCTED IMMUNITY EMC TEST SYSTEM

GIS Disconnector Switching Operation VFTO Study

Schlöder GmbH - EMC Test and Measurement Systems Model #

V P N. Voltage transducer DVM 4200 = 4200 V

Immunity Testing for the CE Mark

Tab 8 Surge Arresters

Memo. 1 Summary. 1.1 Introduction. 1.2 Experiments. 1.3 Conclusion

Fast transient burst simulator

OFDM Channel Modeling for WiMAX

Lab 1: Pulse Propagation and Dispersion

A Self-balanced, Liquid Resistive, High Impedance HV Divider

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

Experiment No. 6 Pre-Lab Transmission Lines and Time Domain Reflectometry

SERIES K: PROTECTION AGAINST INTERFERENCE

CURRENT MEARUREMENT SHUNT CS-10/500 USER MANUAL

Investigation of PD Detection on XLPE Cables

X International Symposium on Lightning Protection

DIGITAL SIGNAL PROCESSING CCC-INAOE AUTUMN 2015

N acquisitions, all channels simultaneously, N is selectable from 4, 16, 64, and 128 Inputs

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING

Flexible AC current probes

APPENDIX D DISCUSSION OF ELECTRONIC INSTRUMENTS

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

FAULT IDENTIFICATION IN TRANSFORMER WINDING

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005

A Combined Impedance Measurement Method for ESD Generator Modeling

Protection of Electrical Networks. Christophe Prévé

High frequency transformer model for calculations of transferred overvoltages. I. UGLESIC University of Zagreb, Croatia

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

Advanced Test Equipment Rentals ATEC (2832) INA A

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

10 Mb/s Single Twisted Pair Ethernet Conducted Immunity Steffen Graber Pepperl+Fuchs

MEDIUM & HIGH VOLTAGE

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 AMETEK CO., LTD. NAGOYA OFFICE. (Main Laboratory) Onna, Atsugi-shi, Kanagawa-ken, Japan

For the electronic measurement of voltage: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Insulation Test System

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

1. General Instructions 2 2. Safety 2 3. Lamp Starting Test Instrument LSTI 5 3

Ultra640 SCSI with Receiver Equalization, 25 meters into a Backplane with 6 loads. Russ Brown Quantum Corporation

Transcription:

Bogotá D.C., Colombia. Noviembre 16-18 de 005 Propagation of Lightning Overvoltages Across MV/LV Substation Measurements and Modelling. Jarosław M. Wiater Abstract - This paper presents measurement results of lightning overvoltages propagation across MV/LV substation and co-existent grounding system. Real substation which supply television broadcaster was used for tests. It s one of few which work for TV Broadcasting Centre. On the TV area 30m high transceiver tower is placed. The risk of direct lightning strike is high. Major part of the MV/LV substation is 630kVA, 6/0.4kV, Dyn5 transformer. The results of these measurements were used to create transformer patch model. It base on measured frequency spectrum of MV/LV substation and circular convolution in frequency domain. Typical model of transformer was improved by created patch model. As a typical model it can be used any well-known transformer model. Created model was implemented to ATP/EMTP simulation program. Index Terms - Electromagnetic transient analysis, Lightning, Modelling, Transformers. T I. INTRODUCTION HE MV/LV substation takes major part in electric power distribution system. High reliability of system requires knowledge of the surge propagation in neuralgic points. This problem appears simultaneously with growing number of electronic equipped MV/LV substations. Disturbances make danger especially for electronically controlled substations. They can result in incorrect work or they can even damage some very sensitive electronic equipment. Black-out can provide financial damage. This paper presents measurement results of lightning overvoltages propagation across real MV/LV substation located in TV Broadcasting Centre. II. ANALYZED MV/LV SUBSTATION Analyzed MV/LV substation is situated on the TV Broadcasting area. There is also located sending-receiving tower 30 meters high. This substation supplies all television transmitters on 6kV voltage level. Rest of electric power devices are supply on 0,4kV voltage level. All objects are interconnected by grounding system and comprehensive data telecommunication network. Major part of MV/LV substation is distribution transformer 630kVA, 6/0.4kV, Dyn5 with middle tap position (no. 4) [1]. There were no modifications during measurements in typical MV/LV configuration. All typical substation equipment was present (for example: control devices). Substation is supply by 6kV underground cable line. Capacitor bank was installed on the low voltage bus bar - 3x39, 30µF, 7.5kVar. During measurements substation was disconnected from electric power system. Cable line was disconnected from transformer windings. Middle voltage windings were loaded with typical matching impedance 60 Ω. Low voltage bus bar was disconnected from load. No overvoltage protection was present. The lightning overvoltages were produced by the highvoltage impulse generator UCS 500M6B. The UCS 500M6B is generator to cover transient and power fail requirement according to international standards with voltage capability of up to 6.6kV. Apart from the IEC 61000-4-5 standard for surge testing it also complies to ANSI/IEEE C6.41 for surge and ringwave testing. Having a built-in CDN for single phase EUT it can be extended for testing threephase EUT's by means of an automatically controlled external coupling network. Some generator parameters are listed below []: voltage (open circuit) 50-6600V, pulse front time 1,µs +/- 30%, pulse time to half value 50µs +/- 0%, current (short circuit) 15-3300A, polarity positive/negative/alternating, direct output Via HV-coaxial connector, Zi=Ω, coupling mode: Line to line, Line(s) to ground (PE). During measurements also were used: digital oscilloscope Tektronix TDS303B 300MHz,,5GS/s, high voltage probe with 100x attenuation. Tektronix P6009 4kV, 180MHz, input capacitance.5pf, input resistance 10MΩ, cable length 9ft, MV transformer side matching impedance (characteristic impedance of the line is normally in the range 400-650Ω) we took the 60Ω value, high voltage coaxial cable Z o =50Ω, external power supply for the surge generator (petrol generator). SICELIII-30 1

used (petrol generator). Petrol generator supplies digital oscilloscope and high-voltage generator. III. MEASUREMENT RESULTS The surge generator is high voltage unit. This provides real values of voltages transferred through distribution transformers. All waveforms were recorded through voltage probe described above. Figure 4 presents voltage on the substation LV side bus bar. Surge comes between 1W transformer terminal and transformer tub. a) b) c) Fig. 1. Voltage waveform on HV generator output (Upp=,5kV). d) e) f) Fig. 4. Voltage waveform measured on the LV bus bar. Surge 1,/50µs, Upp=,5kV incoming for 1W-transformer tub terminals. a) W-N, b) V-N, c) U-N, d) W-V, e) W-U, f) V-U (0V/div, 00µs/div). Fig.. Photo of the test set-up for direct measurements. Surge generator was connected to the one of the primary transformer terminals. Different combinations were examined for different terminals configurations: phase-phase, phasetransformer tub. One of examined combinations presents figure (phase-phase). On the transformer secondary side digital oscilloscope record measurement results also in different combinations: load and no load on LV side, symmetrical and no symmetrical load on LV side, different voltage surge peak value. a) b) c) d) e) f) Fig. 3. Circuit diagram of test set-up (selected part of analyzed MV/LV substation). For safety reasons transformer neutral terminal was grounded. To avoid over coupling digital oscilloscope by high-voltage generator and grounding system external power supply was SICELIII-30

Fig. 5. Voltage waveform measured on the LV bus bar. Surge 1,/50µs, Upp=,5kV incoming for 1V-1U transformer terminals. a) W-N, b) V-N, c) U-N, d) W-V, e) W-U, f) V-U (0V/div, 500µs/div). c) Measured voltage waveforms are almost identical for this case (fig. 4a, 4b, 4c). Some different appears for interfacial voltage waveforms (fig. 4d, 4e, 4f). Figure 5 presents voltage waveforms for surge incoming on 1V-1U transformer terminals. This time for different observation point different voltage was measured. Big difference was observed in phase U (amplitude difference) and between phases W-V (no voltage waveform). These differences are caused by internal transformer structure. Surge peek value influence on measured waveforms is presented on figure 6a, 6b, 6c. For higher voltage levels different shape appears. a) Fig. 6. Voltage waveform measured on the LV bus bar. Surge 1,/50µs incoming for 1V-transformer tub terminals. a) Upp=6kV, b) Upp=3kV, c) Upp=1kV (100V/div, 00µs/div). IV. MV/LV SUBSTATION MODELLING New proposed model bases on the frequency characteristics, circular convolution calculation and Fast Fourier Transform (FFT). By the Discrete Fourier Transform (DFT) can be calculated a signal's frequency spectrum and also can be found a system's impulse response from the frequency response fig. 7. b) Fig. 7. Comparing system operation in the time and frequency domains. In the time domain, an input signal is convolved with an impulse response, resulting in the output signal [3]. SICELIII-30 3

The equations presented below describes idea of convolution: x [ n] h[ n] = y[ n] (1) X [ H[ = Y[ () where: x[n] system s input signal in time domain, h[n] system s impulse response in time domain, y[n] system s output signal in time domain, X[f] system s input signal in frequency domain, H[f] system s impulse response in frequency domain, Y[f] system s output signal in frequency domain. The convolution in the time domain corresponds to multiplication in the frequency domain. Interfacial frequency characteristics are convolution of real transformer s impulse response and typical transformer model s impulse response. This is new idea of improving any existing transformer model [4, 5, 6, 7] by real measurements for exactly precise frequency range. This operation will provide demanded transformer model in specific frequency range by frequency spectrum modification in frequency domain fig. 8. Fig. 9. Input signal (X[f]) frequency spectrum for phase 1W-1V. X [ = Re X[ + j Im X[ (3) H [ = Re H[ + j Im H[ (4) Y [ = ReY[ + j ImY[ (5) ReY[ Re X[ + ImY[ Im X[ Re H[ = Re X[ + Im X[ (6) ImY[ Re X[ ReY[ Im X[ Im H[ = Re X[ + Im X[ (7) Fig. 10. Output signal (Y[f]) frequency spectrum for phase W-N. For this case sampling time is constant and equal 400µs. A noise reduction method wasn t used because of DFT and IDFT limitations. If the noise reduction is used proper IDFT Fig. 8. Typical transformer model modification by convolution in frequency domain. of the signal is impossible. Number of points used to analysis was equal 50000. These two values provide some limitations SICELIII-30 4

on the frequency spectrum range and resolution. Patch model is valid for strict frequency range from,5khz to 31,5MHz. spectrum range. In our case it s make high frequency transformer model especially corrected for 1,/50µs surge. Measurements and simulations results are identical for 400µs window. For different observation window was observed spectrum leak. Created model was implemented to ATP/EMTP simulation program. This kind of modelling is in the first stage of investigation. Future research takes into account interfacial between phases, transformer tub etc. ACKNOWLEDGMENT The work was partially supported by the Białystok Technical University, Rector s Project No W/WE/3 /03. Fig. 11. Transformer frequency characteristics (H[f]) for phase W. REFERENCES [1] Transformer catalog ABB Poland 004. [] UCS 500M6B instruction manual, EM Test 00. [3] Steven W. Smith, "The Scientist and Engineer's Guide to Digital Signal Processing", California Technical Publishing, pp. 178, USA 1998. [4] P.Zeller, B.Richter, Protection of medium voltage transformers against overvoltages-calculation of transferred voltages, ICLP 00 Kraków. [5] M.J.Manyahi, R.Thottappillil, Transfer of lightning transients through distribution transformer circuits, ICLP 00 Kraków. [6] W.Hribernik, B.Richter, Simulation of the transfer characteristic of medium voltage power transformers for the estimation of transferred lightning overvoltages, ICLP 000, Rhodes-Greece. [7] M.Agudo, B.Hermoso, V.Senosiain, P.Martinez Cid, A.simplified distribution transformer model for calculating transferred surges, ICLP 00 Kraków. Fig. 1. ATP/EMTP algorithm used for modelling. ATP/EMTP algorithm is presented on figure 1. It start working when the equation 8 is true. Jarosław Wiater received the M.Sc. degree in Electric Power Systems from Białystok Technical University in 00 - Poland. Since 00 he has been with Białystok Technical University. His main research area is application of computer technology in damage analysis at electric power substation during direct lightning strikes. Manuscript received August 5, 005. u u υ 0 (8) 1 where: u 1 temporary voltage on primirary side of modeled substation u temporary voltage on secondary side of modeled substation υ ratio of transformation. V. CONCLUSION The results of these measurements were used to create transformer patch model. It base on measured frequency spectrum of MV/LV substation and circular convolution in frequency domain. Typical model of transformer was improved by created patch model. As a typical model it can be used any wellknown transformer model. Real transformer frequency spectrum can be multiplied with standard transformer model frequency spectrum in frequency domain. This characteristic overlaps and corrects typical transformer model for measured SICELIII-30 5