Pre location: Impulse-Current-Method (ICE)

Size: px
Start display at page:

Download "Pre location: Impulse-Current-Method (ICE)"

Transcription

1 1 ICE (Impulse current method three phased Ionisation delay time DIRECT MODE Output impedance of the generator 2 Surge generator as impulse source 3 High voltage test set as impulse source The current coupler Typical waveforms Evaluation of the measurement Improving the measurement accuracy Influence of a connection cable 6 2 Comparison mode I Straigt networks T eed Networks 8 The fault lies on the main conductor between generator and loop 9 Very long T eed networks Influence of a connection cable Influence of a connection cable (test lead) 13 3 Comparison mode II UnT eed Networks T eed Networks 15 The fault is located on a main conductor between generator and loop 15 The fault is located in a tee Influence of a connection cable 17 4 Differential comparison mode The differential coupler Straight networks T eed Networks 20 The fault is located on the main conductor between generator and loop 20 The fault is located in a tee Practical Application Influence of a connection cable 22 5 Loop On - Loop Off Method 23 6 Measuring system Centrix Phase selection Phase selection menu 24 Pg1

2 1. ICE (Impulse current method) three phased Four impulse current circuit methods have proven to be successful in prelocating high resistance and intermittent faults in power cables: Direct mode Comparison mode Differential-comparison mode Loop-on loop-off method 1.1. Ionisation delay time The ionisation delay time Dt is the period of time prior to the flashover at the fault during which the charge carriers are ionized. This can take up to some milliseconds. Many times a flashover only takes place after the voltage wave has passed the point of fault and has been reflected at the open cable end with the same polarity, which leads to a voltage doubling. When the voltage wave passes the fault again, usually a flashover occurs. In order to reduce the ionisation delay time Dt, it is recommended to use the maximum output energy of the generator without however exceeding the permissiblevoltage of the cable. Since the ionisation delay time can be some milliseconds, the test range to be set on the transient recorder always has to exceed the length of the faulty cable many times over DIRECT MODE A surge generator or a DC test set serve as an impulse source. Any tee between the start end of the cable and the fault will inevitably cause multiple reflections, which disturb the reflection process to be evaluated. Hence, the direct mode is only applied in cables without tees. Fig 1: Principle of operation Direct Mode The reflections in the faulty cable are recorded via a current coupler, which is connected to the faulty conductor and to a pulse reflection instrument with built-in transient recorder Output impedance of the surge generator In the direct mode, the current coupler is always positioned in direct vicinity of the generator (e.g. surge or shock wave generator - SWG). Each time a transient current wave travelling towards the start end of the cable passes the current coupler, it is almost simultaneously reflected with the Pg2

3 same polarity at the low resistance output impedance of the generator so that in this moment the outgoing and reflected waves superimpose (add up). In order to achieve a current doubling, the following must apply: Zgenerator << Zcable Zgenerator (output impedance of the generator) Zcable (characteristic impedance of the cable) Surge generator as impulse source As far as the transient phenomenon is concerned, the output impedance of the surge generator is zero. This enables a current doubling at the current coupler. High voltage test set as impulse source A current doubling is only possible by connecting a capacitor of some microfarad to the high voltage output. A surge generator, too, can serve this purpose, provided the output voltage is set to DC mode, while increasing the voltage. In this operation mode, the surge generator functions similar to a high voltage test set. The DC voltage potential at the fault increases until the breakdown voltage is reached. After a flashover appeared at the fault position, the whole energy stored in the cable and SWG discharges abruptly, thus generating a transient wave. Fig 2: High voltage test set with capacitor This test mode does not involve an ionisation delay time. In practice, the DC voltage discharge method delivers very clear, reproducible reflection diagrams. However, it will fail in the case of faults, which do not allow a charging of the cable due to a shunt resistance The current coupler The current coupler consists of an inductive pick up fixed to the high voltage output of the surge generator. The high-pass effect of the current coupler produces clear waveforms with steep rising edges. Since the current on the cable shield and in the conductor is the same and only the direction changes, it does not matter which conductor the current coupler is positioned over. Pg3

4 1.5. Typical waveforms Fig 4: Reflections at an open cable end Waveform No. 2: Fig 5: Reflection at a shorted cable end Waveform No. 3: Reflection in the event of a flashover at a discharge fault or an insulation resistance fault. Here, an ionisation delay time Δt may occur. Pg4

5 Fig 6: Reflection at a flashover fault Waveform No. 4: Similar to waveform no. 3 but with a longer ionisation delay time Dt. The fault only ignites after a reflection at the open cable end, whereby the transient voltage wave is reflected with twice the amplitude. Fig 7: Flashover fault: long ionisation delay time If the point A is difficult to determine, then the surge voltage has to be increased without exceeding the permissible voltage of the cable. The ionisation delay time Dt can thus be reduced. The resulting waveform corresponds to waveform no Evaluation of the measurement The evaluation of the waveforms is done between the negative reflections at the fault in consideration of the parasitic reflections. These parasitic reflections are caused by the inductance of the test leads of the generator. Pg5

6 X: Distance between fault and current coupler Equation 1: Calculation of the fault distance 1.7. Improving the measurement accuracy It is possible to eliminate the uncertainty of the factor v/2 and to obtain a more accurate test result by applying a surge wave to a healthy conductor (typical waveform no. 1). The total length L of the cable must be known. The parameter v/2 is changed until the cable length L is shown on the pulse reflection instrument. This v/2 value is then retained for all further measurements on this cable. Note: When using a high voltage connection cable: L = faulty cable + connection cable Influence of a connection cable When using a high voltage connection cable between the generator and the faulty cable, then the current coupler has to be placed as close to the generator as possible (point of reflection) in order to obtain a current doubling. Fig 8: Position of the current coupler with test lead In these measurements, do not forget to subtract the length of the test leads (transmission time t' or fictitious length l'). The length of the coaxial cable that connects the current coupler to the pulse reflection instrument has no effect on the measurement. 2. Comparison mode I A high voltage test set or a surge generator (with the surge button pressed) is used as an impulse source. This method is mainly used in T eed networks. Requirement: A healthy conductor must be available and it must be possible to charge the cable (no parallel resistance). Pg6

7 Fig 9: Schematic circuit diagram Comparison Mode I In this method, two traces recorded during a flashover at the fault are compared Straight (unbranched) networks First measurement: The generator charges the cable capacitance and an arc (flashover) develops at the fault position. This flashover generates a travelling wave, which propagates in both directions from the fault position. Fig 10: Measurement without loop at the cable end The reflection towards the cable end will travel at a velocity V and will be reflected between this point and the fault. This reflection will not influence the trace. The reflection towards the start end of the cable will also travel at a velocity V. At the contact points, a small part of the energy is reflected to the fault. The remaining part travels to the generator. When passing the current coupler, the transient current wave is recorded. The trace might look as follows: Fig 11: Measurement without loop at the cable end Pg7

8 Second Measurement A loop is connected at the cable end between the faulty conductor and a healthy conductor. Fig 12: Measurement with loop at the cable end An increase in voltage will lead to another flashover at the fault. The reflection towards the start end of the cable is also recorded. The start of the trace corresponds to that of the first measurement. In this case, however, the reflection towards the far end of the cable that did not have any influence in the first measurement will pass the loop and reach the start end of the cable via the healthy conductor. Only at the point where this reflection passes the current coupler, the trace will differ from the first measurement. The trace obtained could be as follows: Fig 13: Measurement with loop at the cable end 2.2. Evaluation of the measurement The distance covered by the transient current wave, which passes the loop at the cable end during the second measurement is calculated as follows: 2X + 2Y The distance covered by the transient wave, which is reflected at the fault in the first measurement is: 2X. The point of deviation of the two superimposed traces can be easily and accurately determined. The point corresponds to: 2X + 2Y - 2X = 2Y. Pg8

9 Fig 14: Comparison trace Hence, the distance of the fault from the far end of the cable is: Equation 2: Calculation of the fault distance 2.3. T eed Networks The fault is located on the main conductor between generator and loop. Fig 15: Fault on the main conductor First measurement without loop at "B": Despite the fact that the reflection in the direction of the start end of the cable has passed through the different tees, it reaches the coupler and is recorded in the transient recorder. Second measurement with loop at "B": The reflection in the direction of the far cable end, which did not have any influence on the first measurement passes the loop and returns to the start end of the cable via the healthy conductor. Pg9

10 At the point where this reflection passes the current coupler, the trace will deviate from the previous one. The tees do not have any effect on the principle. However, in each tee, only part of the signal will propagate in forward direction. Hence, the signals at the current coupler will be weakened and the deviations of the traces will be less distinct. As for a cable without tees, the measurement gives the distance of the loop to the fault. The fault is located in a tee Fig 16: Fault in in a tee The comparison of the traces recorded with and without loop at "B" is similar. The measurement gives the distance between the loop and the point of origin of the tee in which the fault lies. Now there is one uncertainty factor, since the fault can be located at any point on the tee "D-C". In order to eliminate this uncertainty, the loop has to be positioned at the end of the tee "C". Now the section "A-C" is the main current circuit and "D-B" a tee. Example: Given the following 3-phase 20 kv network with a discharge fault at the phase R at a flashover voltage of 14 kv. Fig 17: 20 kv Network The generator is connected at the start end "A" of the cable between the phases R (faulty conductor) and S (healthy conductor). The current coupler of the phase S (I2) is used. The Pg10

11 propagation velocity v/2 of 80 m/ms is an approximate value. First measurements: Trace "a" without loop. Trace "b" with loop at "E" between the phases R and S. Fig 18: Comparison with and without loop at far cable end The measurement shows the fault at a distance of 15 m from the tee "C" in the direction of "B". Considering the measuring error, especially in the propagation velocity v/2, the fault could also be located directly at "C" and possibly also in the tee "C-H". Second measurements: Trace "a" without loop. Trace "b" with loop at "H" between the phases R and S. Pg11

12 Fig 19: Comparison with and without loop at the end of the tee The measurement shows the fault at a distance of 172 m from "C" in the direction of "G". The uncertainty factor is now eliminated, since it is known that there is no other tee between these points. The main sources of error in these measurements are to be traced back to - an estimated propagation velocity v/2 - inaccurate network plans. Very long T eed networks In order to minimize the time spent for the location of faults in long cable networks, it is possible to pre-locate the fault roughly through a survey measurement so that the loop can be positioned as close to the start end of the cable as possible. Conducting a survey measurement First measurement: Surge wave on a healthy conductor. Fig 20: Measurement at a good conductor Second measurement: Surge wave on a faulty conductor Pg12

13 Fig 21: Measurement on a faulty conductor Evaluation of the measurement The superposition of the two traces shows a deviation. Fig 22: Comparison reflectogram Example: If tx + Δt = 32,5 μs, then it is known that the fault is located at a distance of less than 32.5 μs * 80 m/μs = 2600 m from the start end of the cable. For accurate measurements the ionisation delay time Δt has to be reduced and the propagation velocity on a cable with tees has to be reduced as follows: v/2» 80 - N (N: number of tees between the start end of the cable and the fault). In the subsequent accurate pre-location, the loop is positioned at the end of a tee whose origin is at least 2600 m from the start end of the cable. In this example, the loop is positioned at "B" or "C" Pg13

14 Fig 23: Positioning the loop after the survey measurement 2.4. Influence of a connection cable (test lead) If a high voltage test leads is used between the generator and the faulty cable, then the current coupler can be positioned either at the output of the generator, or at the connection point of the faulty cable. Fig 24: Positioning the current coupler In both cases, the propagation velocities in the high voltage test leads or in the coaxial cable do not influence the measurement. 3. Comparison mode II The impulse source is a high voltage test set or a surge generator (with the impulse button pressed). This method is mainly used in T eed networks. Prerequisite: At least one healthy conductor must be available and it must be possible to charge the cable (no parallel resistance). Two traces generated through rising cable voltage are compared to the resulting flashover. The method differs from the previous one only in the position of the current coupler and in the results obtained in T eed networks. Pg14

15 Fig 25: Basic circuit diagram Comparison Mode II The current coupler is connected directly at the output of the generator. Since the current in both conductors is the same, the coupler can be positioned over either of the two conductors. Fig 26: Positioning the current coupler 3.1. Straight Networks First measurement: The voltage in the cable is increased until a flashover is obtained. The trace could be as follows: Second measurement: A loop is connected at the far end of the cable between the faulty conductor and the healthy conductor. Fig 28: Measurement with loop at the far cable end. Pg15

16 An increase in voltage will cause another flashover at the fault. The trace could be as follows: Fig 29: Recorded reflectogram 2 A comparison between the two traces allows a determination of the distance of the loop at the far cable end to the fault. ty Fig 30: Comparison of the two-recorded reflectograms T eed Networks The fault is located on a main conductor between generator and loop. Fig 31: Fault in the main conductor Note: This method always indicates the distance between the loop and the fault. Pg16

17 The result of this measurement indicates a fault either at the point "X" or "X ". Hence, there is an uncertainty. It is to be noted that with the method described under 7.2.1, the fault would be prelocated directly at the point "X". The fault is located in a tee As in the preceding case, there is an uncertainty. Fig 32: Fault on a tee Note: When using the comparison mode I for fault location on tees, the fault distance indicated is the distance between the far cable end "B" and the point of origin of the tee "D". When using the comparison mode II, the fault distance indicated is the distance between the far cable end "B" and the fault position "X". A combination of the two comparison methods (I and II) enables a reduction of the number of measurements (shifting of the loop). Example: Given the following intentionally simple network: Fig 33: Network with fault on a tee A first measurement is carried out using the Comparison Mode I (coupler 1) with the loop at the end position "B". Y1 = BD (fault at the point of origin of the tee "DC"). A second measurement is conducted using the Comparison Mode II (coupler 2): Y2 = BX = BX' (fault at X or X'). Pg17

18 Conclusion: the fault is at X 3.3. Influence of a connection cable The generator can be connected to the start end of the cable by means of one or two high voltage test leads. To simplify matters, the current coupler is mostly positioned at the level of the generator. Fig 34: Connection via high voltage connection cables The propagation velocity in the high voltage connection cables has no influence on the measurement. 4. Differential comparison mode The impulse source is a surge generator. This method is mainly used in T eed networks. Prerequisite: a healthy conductor must be available. Fig 35: Basic circuit diagram of the differential comparison mode In this method, two traces that have been generated by a surge wave are compared. The surge generator is connected simultaneously to the faulty and healthy conductors The differential coupler The differential coupler consists of two identical couplers which are mounted over the conductors. Pg18

19 The software effects the difference formation. Fig 36: the differential coupler When a pulse or a reflection passes the two conductors simultaneously, then the difference of the two signals I1 and I2 will be Zero: A signal will not be coupled out. (Example: reflection at a tee). If however the reflection returns on one conductor only, then the same signal as with a single current coupler is obtained. (Example: Reflection at the flashover at the fault) Straight networks First measurement Fig 37: Connection for the first measurement If a surge wave passes at the level of the differential coupler, then it will trigger the recorder, notwithstanding the differential measurement. All identical reflections at the two conductors and at the tees will neutralize because of the differential formation. However, the reflection caused by the flashover at the fault and travels to the start end of the cable will generate a differential signal. The trace could be as follows: Pg19

20 Fig 38: Recorded reflectogram after the first measurement Second Measurement A loop is connected at the far cable end between the faulty and healthy conductors. Fig 39: Second measurement with loop A second surge wave generates another flashover at the fault and triggers the transient recorder again. The reflection travels in the direction of the start end of the cable and leads to a trace that is identical to the preceding one. The trace could be as follows: Fig 40: Recorded reflectogram after the second measurement Evaluation of the measurement The difference in the distance covered by the reflection, which passes the loop (2X+2Y) and the reflection without loop (2X) is twice as large as the distance of the loop to the fault (2Y). The corresponding time is "ty". Since the ionisation delay time Δt can vary between two measurements, the points M1 and M2 have to be superimposed for a comparison of the traces. Pg20

21 Fig 41: Superposition of the two traces Hence, the distance between the loop and the fault is: Equation 3: Calculation of the fault distance 4.3. T eed Networks The fault is located on the main conductor between generator and loop Fig 42: Network with T ees As in the comparison mode I, this measurement gives the distance between the loop and the fault, provided the fault lies on the main conductor between the generator and the loop. The fault is located in a tee Pg21

22 Fig 43: Fault indicated at the point of origin of a tee If the fault lies on a tee, then the measurement will give the distance of the loop to the base of this tee. In this case, there is an uncertainty factor, since the fault could lie anywhere on the tee "DC". In order to eliminate the uncertainty, the loop has to be mounted at the end of the tee "C". Now, "AC" is the main current circuit and "DB" a branch Practical Application Prerequisite: - Three linear couplers (I1, I2, I3) - The cable has two healthy conductors 1. Connect the surge generator and the three current couplers (I1, I2, I3) to the cable conductors (L1, L2, L3) 2. Connect a loop between the faulty and healthy conductor at the far cable end. Fig 44: Use of three couplers 3. Transmission of a surge wave and use of the differential coupler "I1-I2" (Corresponds to trace without loop). Fig 45: First measurement without loop 4. Transmission of a surge wave and use of the differential coupler "I1-I3" (Corresponds to a trace with loop). Pg22

23 Fig 46: Second measurement with loop 5. Comparison of the content of the memory after the points M1 and M2 have been shifted to superimpose. Fig 47: Both traces superimposed Conclusion: The advantage of this circuit is that if required, the traces with and without loop can be repeated several times in order to select the comparison that provides the best interpretation without having to connect and disconnect the loop. The safety factor cannot be denied (no additional contact with the cable required) Influence of a connection cable If a high voltage test leads is used between the generator and the start end of the cable, then the differential coupler can be positioned either at the level of the generator, or at the start end of the cable. Pg23

24 Fig 48: Position of differential couplers The propagation velocities in the high voltage test leads and in the coaxial cable do not have any influence on the measurement, since this is always carried out from the far end of the cable to the point of fault. 5. Loop On - Loop Off Method The impulse source is a high voltage test set or a surge generator. This method is used in unt eed networks. Prerequisite: the high voltage test leads has to be sufficiently long (l' >> 50 m). In this method, one compares to traces, first with loop and then without (loop on / loop off), whereby the loop is connected at the end of the high voltage test leads. Fig 49: Connection with high voltage test lead Pg24

25 Fig 50: Test result of the loop on / loop off method If the measurement is carried out with surge waves, then the points M have to be shifted to superimpose. If a voltage generator (e.g. surge generator with the impulse key pressed) is used for the measurement, then the left part of the waveform up to point "M" is not displayed. The measurement always gives the distance of the fault to the start end of the faulty cable. The fault distance is calculated as follows: Equation 4: Calculation of the fault 6. Measuring system Centrix 3 ICE 3PH 6.1. Phase selection For three-phase ICE measurement, the phase selection results from the following circuit diagram: In the phase selection menu a maximum of two phases can be activated for simultaneous measurement. If the operator selects three phases, the measurement cannot be started and an appropriate message is displayed. Pg25

26 6.2. Phase selection menu Connection of the test cable Simplified block diagram showing the currently activated phases (closed switch) and their polarity corresponding to the active measuring coil selection (in this case L1 and L2). Menu to select the phases applicable for measurement (in this case L1 and L2). Menu to select the measurement coil applicable for measurement (in this case P1). The phases measured by the respective coil and their polarity are shown in parentheses (corresponding to the active phase selection). For typical three-phased ICE measurements, two measurements have to be performed. For the first measurement, the test cable has to be connected as follows: Prior to the second measurement, the two selected phases (in this case L1 and L2) have to be looped at the far end of the cable as shown in the picture below: Pg26

27 Operation mode The operator can choose between two operation modes using the menu item: Operation mode Surge Charge Description The fault-flash over is forced by a capacitive discharge of an impulse current. The fault-flash over is forced by charging the cable with HV (with a surge capacitor connected in parallel). Pg27

Application guide. Cable fault location in LV, MV and HV underground cable networks. Practical experience. Author: Tobias Neier, Ing.

Application guide. Cable fault location in LV, MV and HV underground cable networks. Practical experience. Author: Tobias Neier, Ing. Application guide Cable fault location in LV, MV and HV underground cable networks Practical experience Author: Tobias Neier, Ing., MBA Content 1. Introduction...5 2. Cable types and their characteristics...6

More information

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Christian Suttner*, Stefan Tenbohlen Institute of Power Transmission and High Voltage Technology (IEH), University of

More information

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of

More information

Conventional Paper-II-2011 Part-1A

Conventional Paper-II-2011 Part-1A Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance

More information

High voltage engineering

High voltage engineering High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency

More information

Simulation of line fault locator on HVDC Light electrode line

Simulation of line fault locator on HVDC Light electrode line August 10, 2010 Simulation of line fault locator on HVDC Light electrode line Andreas Hermansson BACHELOR S THESIS Electrical Engineering, Electric Power Technology Department of Engineering Science BACHELOR

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages Session Four: ractical Insulation Co-ordination Session Four: ractical Insulation Co-ordination for Lightning Induced Overvoltages Jason Mayer Technical Director, Energy Services, Aurecon Introduction

More information

RCTrms Technical Notes

RCTrms Technical Notes RCTrms Technical Notes All measuring instruments are subject to limitations. The purpose of these technical notes is to explain some of those limitations and to help the engineer maximise the many advantages

More information

Fault Location on Land and Submarine Links (AC & DC)

Fault Location on Land and Submarine Links (AC & DC) Fault Location on Land and Submarine Links (AC & DC) Technical Brochure CIGRE Working Group B1.52 12 October 2017 Robert Donaghy (Convenor) Tutorial Contents 1. Introduction 2. Terms of Reference 3. Cable

More information

Practical aspects of PD localization for long length Power Cables

Practical aspects of PD localization for long length Power Cables Practical aspects of PD localization for long length Power Cables M. Wild, S. Tenbohlen University of Stuttgart Stuttgart, Germany manuel.wild@ieh.uni-stuttgart.de E. Gulski, R. Jongen onsite hv technology

More information

ETL-40V CABLE TEST VAN SYSTEM. tel.: +380 (57) fax: +380 (57) high voltage testing equipment

ETL-40V CABLE TEST VAN SYSTEM.  tel.: +380 (57) fax: +380 (57) high voltage testing equipment ETL-40V CABLE TEST VAN SYSTEM DC cable testing up to 40kV with 300mA max. current Burning up to 20kV / 1A Surge energy up to 2000J Precise pinpointing and fault prelocation Fault location using step voltage

More information

HVDC High Voltage Direct Current

HVDC High Voltage Direct Current HVDC High Voltage Direct Current Typical HVDC Station BACK TO BACK CONVERTER STATION MONO POLAR WITH GROUND RETURN PA Back to Back Converters indicates that the Rectifiers & Inverters are located in the

More information

Power Quality and Reliablity Centre

Power Quality and Reliablity Centre Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview

More information

OPERATIONAL AMPLIFIER PREPARED BY, PROF. CHIRAG H. RAVAL ASSISTANT PROFESSOR NIRMA UNIVRSITY

OPERATIONAL AMPLIFIER PREPARED BY, PROF. CHIRAG H. RAVAL ASSISTANT PROFESSOR NIRMA UNIVRSITY OPERATIONAL AMPLIFIER PREPARED BY, PROF. CHIRAG H. RAVAL ASSISTANT PROFESSOR NIRMA UNIVRSITY INTRODUCTION Op-Amp means Operational Amplifier. Operational stands for mathematical operation like addition,

More information

CITY SERIES. Compact, fully equipped cable fault location, test and diagnostic systems

CITY SERIES. Compact, fully equipped cable fault location, test and diagnostic systems CITY SERIES Compact, fully equipped cable fault location, test and diagnostic systems Tailored to fit to small vehicles Easy operation in restricted spaces Centrally controlled, fully automatic system

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

Underwater Spark Sources: Some experimental information.

Underwater Spark Sources: Some experimental information. Author: Dr J Nedwell SUBACOUSTECH Ltd Chase Mill Winchester Road Bishop s Waltham Hampshire SO32 1AH Tel:+44 (0) 1489 891850 Fax:+44 (0) 1489 891851 email: subacoustech@subacoustech.com website: www.subacoustech.com

More information

Chapter 5 Electromagnetic interference in flash lamp pumped laser systems

Chapter 5 Electromagnetic interference in flash lamp pumped laser systems Chapter 5 Electromagnetic interference in flash lamp pumped laser systems This chapter presents the analysis and measurements of radiated near and far fields, and conducted emissions due to interconnects

More information

Modeling insulation in high-voltage substations

Modeling insulation in high-voltage substations 38 ABB REVIEW DESIGNED FOR SAFETY DESIGNED FOR SAFETY Modeling insulation in high-voltage substations The goal of insulation coordination is to determine the dielectric strength of transformers and other

More information

Electric Stresses on Surge Arrester Insulation under Standard and

Electric Stresses on Surge Arrester Insulation under Standard and Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems

More information

Residual Current Operated Circuit-Breakers (RCCBs)

Residual Current Operated Circuit-Breakers (RCCBs) Product Overview Residual Current Operated Circuit-Breakers (RCCBs) Residual current operated circuit-breakers Number of poles Rated current A Rated residual current ma MW Auxiliary contacts can be mounted

More information

In order to minimise distribution (11 and 22 kv) feeder breaker

In order to minimise distribution (11 and 22 kv) feeder breaker Lightning protection for equipment on MV feeders By WJD van Schalkwyk and M du Preez, Eskom This article presents the influence of lightning on MV feeders supplying small power users (400/230 V) with focus

More information

First South East European Regional CIGRÉ Conference. Portoroz, Slovenia, 7 8 June Cable Fault Location on long HVAC and HVDC Cable Systems 2-13

First South East European Regional CIGRÉ Conference. Portoroz, Slovenia, 7 8 June Cable Fault Location on long HVAC and HVDC Cable Systems 2-13 First South East European Regional CIGRÉ Conference Portoroz, Slovenia, 7 8 June 2016 Location on long HVAC and HVDC Systems 2-13 Dr. Frank Petzold Dominik Nowak Matthias Müller Challenges in cable fault

More information

CONNECTING THE PROBE TO THE TEST INSTRUMENT

CONNECTING THE PROBE TO THE TEST INSTRUMENT 2SHUDWLRQ 2SHUDWLRQ Caution The input circuits in the AP034 Active Differential Probe incorporate components that protect the probe from damage resulting from electrostatic discharge (ESD). Keep in mind

More information

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding

More information

EE 521: Instrumentation and Measurements

EE 521: Instrumentation and Measurements Aly El-Osery Electrical Engineering Department, New Mexico Tech Socorro, New Mexico, USA October 18, 2009 1 / 18 1 Sources of Coherent Interference Capacitive Coupling Inductive Coupling Ground Loops Power

More information

Metaphase ULC-2. Technologies ULC. Metaphase. Technologies Version 7.X August 2015 USER MANUAL. metaphase-tech.com. pg. 1

Metaphase ULC-2. Technologies ULC. Metaphase. Technologies Version 7.X August 2015 USER MANUAL. metaphase-tech.com. pg. 1 ULC Version 7.X August 2015 USER MANUAL pg. 1 Overview Universal LED Controller () provides independent true constant-current or voltage control of two LED loads from 0.02 to 4 Amps continuous (DC) with

More information

Techno Instrumentation(India) Pvt. Ltd. Manufacturer of underground power cable fault locators

Techno Instrumentation(India) Pvt. Ltd. Manufacturer of underground power cable fault locators Techno Instrumentation(India) Pvt. Ltd. Manufacturer of underground power cable fault locators Surge Generator T-1005(7) For fault location in LT and Control cables. Inbuilt DC high voltage testing up

More information

Lab 1: Pulse Propagation and Dispersion

Lab 1: Pulse Propagation and Dispersion ab 1: Pulse Propagation and Dispersion NAME NAME NAME Introduction: In this experiment you will observe reflection and transmission of incident pulses as they propagate down a coaxial transmission line

More information

High Voltage Engineering

High Voltage Engineering High Voltage Engineering Course Code: EE 2316 Prof. Dr. Magdi M. El-Saadawi www.saadawi1.net E-mail : saadawi1@gmail.com www.facebook.com/magdi.saadawi 1 Contents Chapter 1 Introduction to High Voltage

More information

Utility System Lightning Protection

Utility System Lightning Protection Utility System Lightning Protection Many power quality problems stem from lightning. Not only can the high-voltage impulses damage load equipment, but the temporary fault that follows a lightning strike

More information

B. Equipment. Advanced Lab

B. Equipment. Advanced Lab Advanced Lab Measuring Periodic Signals Using a Digital Oscilloscope A. Introduction and Background We will use a digital oscilloscope to characterize several different periodic voltage signals. We will

More information

Appendix B Experimental equipment and procedures

Appendix B Experimental equipment and procedures 2 4 Appendix B Experimental equipment and procedures B.1 Spark generator details The detailed schematic layout for generation of high-voltage pulses used in the spark generator described in [29] is shown

More information

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS Shashi Kumar 1, Brajesh Kumar Prajapati 2, Vikramjeet Singh 3 1, 2 Students, Electrical Engineering Department Greater Noida

More information

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations Ricard Petranovic and Amir M. Miri Universität Karlsruhe, Institut für Elektroenergiesysteme und Hochspannungstechnik,

More information

University of Pennsylvania Department of Electrical and Systems Engineering ESE319

University of Pennsylvania Department of Electrical and Systems Engineering ESE319 University of Pennsylvania Department of Electrical and Systems Engineering ESE39 Laboratory Experiment Parasitic Capacitance and Oscilloscope Loading This lab is designed to familiarize you with some

More information

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems) Transmission Line Transient Overvoltages (Travelling Waves on Power Systems) The establishment of a potential difference between the conductors of an overhead transmission line is accompanied by the production

More information

Sources of transient electromagnetic disturbance in medium voltage switchgear

Sources of transient electromagnetic disturbance in medium voltage switchgear Sources of transient electromagnetic disturbance in medium voltage switchgear Dennis Burger, Stefan Tenbohlen, Wolfgang Köhler University of Stuttgart Stuttgart, Germany dennis.burger@ieh.uni-stuttgart.de

More information

Chapter 1. Overvoltage Surges and their Effects

Chapter 1. Overvoltage Surges and their Effects Chapter 1 Overvoltage Surges and their Effects 1.1 Introduction Power equipment are often exposed to short duration impulse voltages of high amplitude produced by lightning or switching transients. These

More information

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection)

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection) Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection) FIGURE 1.2 Fig.1 Earth fault loop path. Figure 1 shows the earth fault system which provides

More information

Generation of Sub-nanosecond Pulses

Generation of Sub-nanosecond Pulses Chapter - 6 Generation of Sub-nanosecond Pulses 6.1 Introduction principle of peaking circuit In certain applications like high power microwaves (HPM), pulsed laser drivers, etc., very fast rise times

More information

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS 29 th International Conference on Lightning Protection 23 rd 26 th June 2008 Uppsala, Sweden PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS Ivo Uglešić Viktor Milardić Božidar

More information

P331-2 set ESD generator (IEC )

P331-2 set ESD generator (IEC ) User manual Probe set set ESD generator (IEC 61000-4-2) Copyright January 2017 LANGER GmbH 2017.01.09 User manual Table of contents: Page 1 ESD generator (IEC 61000-4-2) 3 1.1 Design and function of the

More information

9. How is an electric field is measured?

9. How is an electric field is measured? UNIT IV - MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS PART-A 1. Mention the techniques used in impulse current measurements. Hall generators, Faraday generators and current transformers. 2.Mention the

More information

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR 621 212 DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING EE1003 HIGH VOLTAGE ENGINEERING QUESTION BANK UNIT-I OVER VOLTAGES IN ELECTRICAL POWER SYSTEM

More information

Measurement and Analysis for Switchmode Power Design

Measurement and Analysis for Switchmode Power Design Measurement and Analysis for Switchmode Power Design Switched Mode Power Supply Measurements AC Input Power measurements Safe operating area Harmonics and compliance Efficiency Switching Transistor Losses

More information

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24 LECTURER-24 GENERATION OF HIGH ALTERNATING VOLTAGES When test voltage requirements are less than about 300kV, a single transformer can be used for test purposes. The impedance of the transformer should

More information

ET 61 - Electrician Theory Examination Marking Schedule

ET 61 - Electrician Theory Examination Marking Schedule ET 61 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker

More information

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION David TOPOLANEK Petr TOMAN Michal PTACEK Jaromir DVORAK Brno University of Technology - Czech

More information

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables J Electr Eng Technol Vol. 9, No. 2: 628-634, 2014 http://dx.doi.org/10.5370/jeet.2014.9.2.628 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 A Study on Lightning Overvoltage Characteristics of Grounding

More information

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables 21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria

More information

Coaxial Cable Protection

Coaxial Cable Protection Coaxial Cable Protection 1485-005 Technical Note Coaxial Cable Protection Coaxial Cable Protection Why is coaxial cable protection needed? Skin effect is a physical phenomenon that relates to the limited

More information

Simulation of characteristics of impulse voltage generator for testing of equipment using MATLAB Simulink

Simulation of characteristics of impulse voltage generator for testing of equipment using MATLAB Simulink International Journal of Advances in Engineering, 2015, 1(2), 45-50 ISSN: 2394-9260 (printed version); ISSN: 2394-9279 (online version) url:http://www.venuspublications.com/ijae.html RESEARCH ARTICLE Simulation

More information

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

FGJTCFWPKPUVKVWVGQHVGEJPQNQI[ FGRCTVOGPVQHGNGEVTKECNGPIKPGGTKPI VGG246JKIJXQNVCIGGPIKPGGTKPI FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown

More information

RESONANT TRANSFORMER

RESONANT TRANSFORMER RESONANT TRANSFORMER Whenever the requirement of the test voltage is too much high, a single unit transformer can not produce such high voltage very economically, because for high voltage measurement,

More information

ALLOWABLE LIMITS TO SHORT TIME VOLTAGE DROPS IN HV WITHSTAND TESTS

ALLOWABLE LIMITS TO SHORT TIME VOLTAGE DROPS IN HV WITHSTAND TESTS The 19 th International Symposium on High Voltage Engineering, Pilsen, Czech Republic, August, 23 28, 2015 ALLOWABLE LIMITS TO SHORT TIME VOLTAGE DROPS IN HV WITHSTAND TESTS William Larzelere Evergreen

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi

More information

EE 1402 HIGH VOLTAGE ENGINEERING

EE 1402 HIGH VOLTAGE ENGINEERING EE 1402 HIGH VOLTAGE ENGINEERING Unit 5 TESTS OF INSULATORS Type Test To Check The Design Features Routine Test To Check The Quality Of The Individual Test Piece. High Voltage Tests Include (i) Power frequency

More information

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM Anna Tjäder Chalmers University of Technology anna.tjader@chalmers.se Math Bollen Luleå University of Technology math.bollen@stri.se ABSTRACT Power

More information

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 23 CHAPTER 2 v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 2.1 INTRODUCTION For reliable design of power system, proper insulation coordination among the power system equipment is necessary. Insulation

More information

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Analysis of lightning performance of 132KV transmission line by application of surge arresters Analysis of lightning performance of 132KV transmission line by application of surge arresters S. Mohajer yami *, A. Shayegani akmal, A.Mohseni, A.Majzoobi High Voltage Institute,Tehran University,Iran

More information

2. Current interruption transients

2. Current interruption transients 1 2. Current interruption transients For circuit breakers or other switching facilities, transient voltages just after the current interruptions are of great concern with successful current breakings,

More information

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:15 No:03 39 Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models Shen-Wen Hsiao, Shen-Jen

More information

DETECTING SHORTED TURNS

DETECTING SHORTED TURNS VOLTECH NOTES DETECTING SHORTED TURNS 104-029 issue 2 Page 1 of 8 1. Introduction Inductors are made up of a length of wire, usually wound around a core. The core is usually some type of magnetic material

More information

Testing 320 kv HVDC XLPE Cable System

Testing 320 kv HVDC XLPE Cable System Testing 320 kv HVDC XLPE Cable System H. He, W. Sloot DNV GL, KEMA Laboratories Arnhem, The Netherlands Abstract Two unique test requirements in testing of a high- voltage direct- current (HVDC) cable

More information

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE Willem DIRKSE VAN SCHALKWYK ESKOM - South Africa vschalwj@eskom.co.za ABSTRACT A high BIL (300 kv) on a MV feeder ensures that no

More information

Transmission of Electrical Energy

Transmission of Electrical Energy Transmission of Electrical Energy Electrical energy is carries by conductors such as overhead transmission lines and underground cables. The conductors are usually aluminum cable steel reinforced (ACSR),

More information

KNX Powerline PL 110. KNX Association

KNX Powerline PL 110. KNX Association KNX Powerline PL 110 Table of Contents 1 Introduction...3 2 Standardisation...3 3 Transmission Process...4 3.1 Phase Coupling...5 3.2 Telegram Transmission...6 3.2.1 Training Sequence...6 3.2.2 Preamble

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables

More information

UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET

UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS Introduction Where fuses are unsuitable or inadequate, protective relays and circuit breakers are used in combination to detect and isolate faults. Circuit breakers

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits

More information

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering

More information

TRANSISTOR SWITCHING WITH A REACTIVE LOAD

TRANSISTOR SWITCHING WITH A REACTIVE LOAD TRANSISTOR SWITCHING WITH A REACTIVE LOAD (Old ECE 311 note revisited) Electronic circuits inevitably involve reactive elements, in some cases intentionally but always at least as significant parasitic

More information

Power Engineering II. High Voltage Testing

Power Engineering II. High Voltage Testing High Voltage Testing HV Test Laboratories Voltage levels of transmission systems increase with the rise of transmitted power. Long-distance transmissions are often arranged by HVDC systems. However, a

More information

Immunity Testing for the CE Mark

Immunity Testing for the CE Mark Immunity Testing for the CE Mark Summary The European Union (EU) currently has 25 member countries with 2 additional countries to be added in 2007. The total population at that time will be nearly a half

More information

High Voltage DC Transmission 2

High Voltage DC Transmission 2 High Voltage DC Transmission 2 1.0 Introduction Interconnecting HVDC within an AC system requires conversion from AC to DC and inversion from DC to AC. We refer to the circuits which provide conversion

More information

Impulse testing of coils and magnets: present experience and future plans

Impulse testing of coils and magnets: present experience and future plans Impulse testing of coils and magnets: present experience and future plans M. Marchevsky, E. Ravaioli, LBNL G. Ambrosio, FNAL M. Marchevsky 1 Impulse testing for LARP magnets Impulse testing is a key electrical

More information

Application Note # 5438

Application Note # 5438 Application Note # 5438 Electrical Noise in Motion Control Circuits 1. Origins of Electrical Noise Electrical noise appears in an electrical circuit through one of four routes: a. Impedance (Ground Loop)

More information

Centrix 2.0 The world s most modern and powerful cable test van system

Centrix 2.0 The world s most modern and powerful cable test van system The world s most modern and powerful cable test van system Centrix 2.0 The world s most modern and powerful cable test van system Intuitive easygo operation using a touch display System powered by Li-Ion

More information

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential

More information

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Voltage (kv) Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers Li-Ming Zhou, Senior Member, IEEE and Steven Boggs, Fellow, IEEE Abstract: The high frequency attenuation

More information

EMC TEST REPORT For MPP SOLAR INC Inverter/ Charger Model Number : PIP 4048HS

EMC TEST REPORT For MPP SOLAR INC Inverter/ Charger Model Number : PIP 4048HS EMC-E20130903E EMC TEST REPORT For MPP SOLAR INC Inverter/ Charger Model Number : PIP 4048HS Prepared for : MPP SOLAR INC Address : 4F, NO. 50-1, SECTION 1, HSIN-SHENG S. RD. TAIPEI, TAIWAN Prepared by

More information

Effects of Transient Recovery Voltages on Circuit Breaker Ratings

Effects of Transient Recovery Voltages on Circuit Breaker Ratings Effects of Transient Recovery Voltages on Circuit Breaker Ratings Term Project: - EE22 - Power System Transients. Spring 28 Instructor: - Dr. Bruce Mork Team: - Himanshu Bahirat Muhammad Ali Praveen KK

More information

Operations Manual. Model NT11 & NT11-E. June 18 th 2002

Operations Manual. Model NT11 & NT11-E. June 18 th 2002 Operations Manual Model NT11 & NT11-E June 18 th 2002 3609 North 44 th Street Phoenix, AZ 85018-6023 Internet: www.northstarcontrols.com Fax: (941) 426-0807 Tel: (941) 426-6396 Manual Contents Glossary

More information

Differential-Mode Emissions

Differential-Mode Emissions Differential-Mode Emissions In Fig. 13-5, the primary purpose of the capacitor C F, however, is to filter the full-wave rectified ac line voltage. The filter capacitor is therefore a large-value, high-voltage

More information

3. Diode, Rectifiers, and Power Supplies

3. Diode, Rectifiers, and Power Supplies 3. Diode, Rectifiers, and Power Supplies Semiconductor diodes are active devices which are extremely important for various electrical and electronic circuits. Diodes are active non-linear circuit elements

More information

SINGLE PHASE CURRENT SOURCE INVERTER (C.S.I)

SINGLE PHASE CURRENT SOURCE INVERTER (C.S.I) Power Electronics Laboratory SINGLE PHASE CURRENT SOURCE INVERTER (C.S.I) OBJECT: To study the gate firing pulses. To observe and measure the voltages across the Thyristors and across the Load for a current

More information

SURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES

SURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES SURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES Jae-bong LEE, Korea Electric Power Research Institute(KEPRI), (Korea), jbonglee@kepco.co.kr Ju-yong KIM, Korea Electric Power Research

More information

OVERVOLTAGE PROTECTION OF POLE MOUNTED DISTRIBUTION TRANSFORMERS

OVERVOLTAGE PROTECTION OF POLE MOUNTED DISTRIBUTION TRANSFORMERS PERODCA POLYTECHNCA SER. EL. ENG. VOL. 41, NO. 1, PP. 27-40 (1997) OVERVOLTAGE PROTECTON OF POLE MOUNTED DSTRBUTON TRANSFORMERS Attila SOMOGY and Lasz16 VZ Department of Electric Power Systems Technical

More information

Locating Faults by the Traveling Waves They Launch

Locating Faults by the Traveling Waves They Launch Locating Faults by the Traveling Waves They Launch Edmund O. Schweitzer, III, Armando Guzmán, Venkat Mynam, Veselin Skendzic, and Bogdan Kasztenny Schweitzer Engineering Laboratories, Inc. Stephen Marx

More information

6. du/dt-effects in inverter-fed machines

6. du/dt-effects in inverter-fed machines 6. du/dt-effects in inverter-fed machines Source: A. Mütze, PhD Thesis, TU Darmstadt 6/1 6. du/dt-effects in inverter-fed machines 6.1 Voltage wave reflections at motor terminals Source: A. Mütze, PhD

More information

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection ECHNICAL NOE 2.0 Overvoltages origin and magnitudes Overvoltage protection he ECHNICAL NOES (N) are intended to be used in conjunction with the APPLICAION GIDELINES Overvoltage protection Metaloxide surge

More information

Impulse Testing as a Predictive Maintenance Tool

Impulse Testing as a Predictive Maintenance Tool Testing as a Predictive Maintenance Tool E. Wiedenbrug SM IEEE, G. Frey M IEEE, J. Wilson, M IEEE Baker Instrument Company engr@bakerinst.com Abstract: testing is an integral part of predictive maintenance

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

POWER SYSTEM TRANSIENTS - Switching Overvoltages in Power Systems - Juan A. Martinez-Velasco, Jacinto Martin-Arnedo

POWER SYSTEM TRANSIENTS - Switching Overvoltages in Power Systems - Juan A. Martinez-Velasco, Jacinto Martin-Arnedo SWITCHING OVERVOLTAGES IN POWER SYSTEMS Juan A. Martinez-Velasco Universitat Politècnica de Catalunya, Barcelona, Spain Jacinto Martin-Arnedo Estabanell Energía, Granollers, Spain Keywords: Switching overvoltages,

More information

GIS Disconnector Switching Operation VFTO Study

GIS Disconnector Switching Operation VFTO Study GIS Disconnector Switching Operation VFTO Study Mariusz Stosur, Marcin Szewczyk, Wojciech Piasecki, Marek Florkowski, Marek Fulczyk ABB Corporate Research Center in Krakow Starowislna 13A, 31-038 Krakow,

More information

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS TRANSFORMER IN GRID When surge arres t ers are installed close to a power transformer, they provide protection against lightning overvoltage ABSTRACT The aim of this research article is to determine the

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2 ACTA UNIVERSITATIS APULENSIS Special Issue SIMULATION OF LIGHTNING OVERVOLTAGES WITH ATP-EMTP AND PSCAD/EMTDC Violeta Chiş, Cristina Băla and Mihaela-Daciana Crăciun Abstract. Currently, several offline

More information