IEEE Major Revision of Interconnection Standard

Similar documents
IEEE Std Bulk System Opportunities from New Distributed Energy Resource Interconnection and Interoperability Standards

IEEE sion/1547revision_index.html

Inverter Source Requirement Document of ISO New England (ISO-NE)

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

Revised IEEE 1547 Standard for Interconnecting Distributed Energy Resources with Electric Power Systems- National Grid Solar Program

Ameren Illinois Company d/b/a Ameren Illinois Smart Inverter Specifications

Implementation of Revised IEEE Standard 1547

IEEE SCC Standards Update

DER Ride-Through Performance Categories and Trip Settings Presentation at PJM Ride-Through Workshop, Philadelphia, PA, October 1-2, 2018

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

Rule 21 Working Group 3.

IEEE sion/1547revision_index.html

Possible Future Modifications to IEEE 1547

E N G I N E E R I N G M A N U A L

Preview of the New Interconnection Standard

Table of Contents. Introduction... 1

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Testing Advanced Photovoltaic Inverters Conforming to IEEE Standard 1547 Amendment 1

BED INTERCONNECTION TECHNICAL REQUIREMENTS

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

TechSurveillance. Revision of IEEE Standard New Disturbance Response Requirements. Business & Technology Strategies.

Technical information Grid Support Utility Interactive Inverters for Sunny Central-US and Sunny Central Storage-US

Common Functions for Smart Inverters. 4 th Edition

Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

Technical information SUNNY BOY 3.0-US / 3.8-US / 5.0-US / 6.0-US / 7.0-US / 7.7-US

Technical information SUNNY TRIPOWER CORE1-US

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Generation Interconnection Requirements at Voltages 34.5 kv and Below

Wind Power Facility Technical Requirements CHANGE HISTORY

Southern Company Interconnection Requirements for Inverter-Based Generation

1

Inverter-Based Resource Disturbance Analysis

Final ballot January BOT adoption February 2015

Protective Relaying for DER

Company Directive STANDARD TECHNIQUE: SD1E/2. Technical Requirements for Customer Export Limiting Schemes

1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report

Requirements for Generators European Network Code High Level Implementation Issues

Grid Converters for Photovoltaic

The EU Network Code on Requirements for Generators A Summary

Parameters related to frequency stability

Target Mchunu and Themba Khoza Eskom Transmission Division, System Operator Grid Code Management

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.

Harmonizing the Changing Resource Mix Keeping the Grid Together

Standard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules. 45-day Formal Comment Period with Initial Ballot June July 2014

SELECTING NATIONAL MW BOUNDARIES

Standard VAR b Generator Operation for Maintaining Network Voltage Schedules

Standard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules

Standard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)

ENTSO-E Draft Network Code on High Voltage Direct Current Connections and DCconnected

Common Information Model (CIM) Extensions and Messaging for the Integration of Renewable Distributed Energy Resources (DER)

Generation and Load Interconnection Standard

Response of Grid Interconnected Solar PV inverters to Transmission System Faults

Transmission Interconnection Requirements for Inverter-Based Generation

Technical Requirements For Generation Connected to The ODEC System

Public Consultation on the Regulatory Framework for Small Scale Grid Connected Solar PV Systems Standards Technical Standards

DRAFT. City of Lethbridge Electric ENGINEERING STANDARDS GUIDELINE FOR GENERATOR INTERCONNECTION THE CITY OF LETHBRIDGE ELECTRIC DISTRIBUTION SYSTEM

A Roadmap for Commercializing Microgrids in California

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Generation and Load Interconnection Standard

Load-Frequency Control and Reserves Network Code. David Bunney JESG 19 March 2013

TechSurveillance. Revision of IEEE Standard New Reactive Power and Voltage Regulation Capability Requirements. Business & Technology Strategies

Education & Training

DRAFT PROPOSAL FOR STORAGE CONNECTION REQUIREMENTS

RENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana

The Connecticut Light and Power Company

WFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS

GUIDE FOR GENERATOR INTERCONNECTION THE WIRES OWNER DISTRIBUTION SYSTEM

Connection of Embedded Generating Plant up to 5MW

Risk of unintentional islanding in the presence of multiple inverters or mixed generation types

Loss of Solar Resources during Transmission Disturbances due to Inverter Settings II

Impact of High PV Penetration on Grid Operation. Yahia Baghzouz Professor of Electrical engineering University of Nevada Las Vegas

Industry Webinar Draft Standard

Performance of Distributed Energy Resources During and After System Disturbance Voltage and Frequency Ride-Through Requirements

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC

Anti-IslandingStrategyforaPVPowerPlant

TECHNICAL GUIDELINE FOR THE INTERCONNECTION OF DISTRIBUTED ENERGY RESOURCES TO EPCOR DISTRIBUTION AND TRANSMISSION INC. S DISTRIBUTION SYSTEM

Parameters related to voltage issues

ECE 528 Understanding Power Quality

NEMA Standards Publication ESS Standard for Uniformly Measuring and Expressing the Performance of Electrical Energy Storage Systems

Modelling Parameters. Affect on DER Impact Study Results

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods

BPS-Connected Inverter-Based Resource Performance

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

Embedded Generation Information Package

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

Energy Networks Association

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction

Information and Technical Requirements For the Interconnection of Distributed Energy Resources (DER)

Standard PRC Coordination of Generating Unit or Plant Voltage Regulating Controls with Generating Unit or Plant Capabilities and Protection

Performance of Distributed Energy Resources During and After System Disturbance Voltage and Frequency Ride Through Requirements

each time the Frequency is above 51Hz. Continuous operation is required

Reliability Guideline: Generating Unit Operations During Complete Loss of Communications

ReliabilityFirst Regional Criteria 1. Disturbance Monitoring and Reporting Criteria

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1

Transcription:

IEEE 1547-2018 - Major Revision of Interconnection Standard NRECA & APA s Emerging Priorities in Energy Research Day, Anchorage, AK Charlie Vartanian PE Secretary, IEEE 1547 Working Group October 31, 2018

Disclaimer This presentation on IEEE 1547-2018 are the author s views and are not the formal position, explanation or position of the IEEE nor PNNL The author acknowledges the contribution of the IEEE 1547-2018 Working Group, Balloters, and Officers 2

Presentation Outline 1) IEEE 1547 Background 2) Featured Changes to 1547-2018, relevant to advanced grid technologies and practices including grid-interactive microgrids VAR and Voltage Control Capabilities Voltage & Frequency Ride Through Interoperability Intentional Islanding 3

IEEE 1547-2018 Scope and Purpose Title: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces Scope: This standard establishes criteria and requirements for interconnection of distributed energy resources (DER) with electric power systems (EPS), and associated interfaces. Interconnection System Distributed Energy Resource (DER) Communications interface Power interface Electric Power System (Area EPS) Purpose: This document provides a uniform standard for the interconnection and interoperability of distributed energy resources (DER) with electric power systems (EPS). It provides requirements relevant to the interconnection and interoperability performance, operation, and testing, and, safety, maintenance and security considerations. Interconnection system: The collection of all interconnection equipment and functions, taken as a group, used to interconnect DERs to an area EPS. Note: In addition to the power interface, DERs should have a communications interface. Interface: A logical interconnection from one entity to another that supports one or more data flows implemented with one or more data links. 4

IEEE 1547 Evolution of Grid Support Functions IEEE 1547-2003 Shall NOT actively regulate voltage Shall trip on abnormal voltage/frequency IEEE 1547a-2014 (Amendment 1) May actively regulate voltage May ride through abnormal voltage/frequency May provide frequency response 1 (frequency-droop) IEEE 1547-2018 Shall be capable of actively regulating voltage Shall ride through abnormal voltage/frequency Shall be capable of frequency response 2 May provide inertial response 3 1 Frequency response is capability to modulate power output as a function of frequency 2 Mandatory capability for Categories II and III under high frequency conditions, Mandatory for Categories II and III under low frequency conditions, optional for Category 1 3 Inertial response is capability for DER to modulate active power in proportion to the rate of change of frequency 5

IEEE 1547-2018 Document Outline 1. Normative references 2. Definitions and acronyms 3. General specifications and requirements 4. Reactive power, voltage/power control [normal operation conditions] 5. Response to Area EPS abnormal conditions 6. Power quality 7. Islanding 8. Distribution secondary grid and spot networks 9. Interoperability 10. Test and verification 11. Seven new annexes (Informative) 6

Active Voltage Regulation Requirements Normal Operation Conditions The DER shall provide voltage regulation capability by changes of reactive power. The approval of the Area EPS Operator shall be required for the DER to actively participate in voltage regulation. Capability required for all DER (Cat A, B) Constant power factor mode Constant reactive power mode ( reactive power priority ) Voltage-reactive power mode ( volt-var ) State-of the art DER Cat B Active power-reactive power mode ( watt-var ) Voltage-active power mode ( volt-watt ) The area EPS operator shall specify the required voltage regulation control modes and the corresponding parameter settings. 7

Grid Support Requirements - Abnormal Operating Conditions Ride-through ability to withstand voltage or frequency disturbances Required 1. Voltage ride-through 2. Frequency ride-through 3. Rate-of-change (ROCOF) 4. Voltage phase angle change 5. Frequency droop 1,2 Other allowed capabilities Inertial response 3 1 Frequency response is capability to modulate power output as a function of frequency 2 Mandatory capability for Categories II and III under high frequency conditions, Mandatory for Categories II and III under low frequency conditions, optional for Category 1 3 Inertial response is capability for DER to modulate active power in proportion to the rate of change of frequency 8

Interoperability Requirements The capability of two or more networks, systems, devices, applications, or components to externally exchange and readily use information securely and effectively (IEEE 2030). Mandatory communications capability A DER shall have provisions for a local DER interface capable of communicating Information to be exchanged: Nameplate: as-built characteristics of the DERs (read Configuration: present capacity and ability of the DERs to perform functions (read/write) Monitoring: present operating conditions of the DERs (read) Management: information to update the functional and mode settings for the DERs (read/write) Communication performance requirements: Availability of communication (DER is operating in continuous or mandatory operation region) Information read response times ( 30 s, maximum amount of time to respond to read requests) Communication protocol requirements: Shall support at least one of three protocols: IEEE Std 2030.5(SEP), IEEE Std 1815(DNP3.0), SunSpec- Modbus 9

Interoperability Scope Scope of IEEE 1547-2018 Interoperability Requirements Individual DER DER Managing Entity Networks Network Adapters /Modules DER with System/ Plant Controller Out of Scope Communication Network Specifics In Scope Local DER Interface Out of Scope Internal DER Specifics IEEE 1547 interface (mandatory) other interfaces (optional) out of scope Source: 1547-2018 Approved Draft 10

Intentional Islands: what s in-scope? An intentional island that contains any part of the Area EPS is inscope. Intentional island behavior at the PCC, and impacts on the Area EPS, are in-scope. What happens behind the meter within a microgrid that does not include any Area EPS elements is out-of-scope. 11

1547-2018 and intentional Islands (II) Two types of transitions into II mode (on-grid to off-grid): scheduled and unscheduled. - Scheduled: initiated by manual action or dispatch. - Unscheduled: automatically initiated due to abnormal Area EPS conditions. Power systems designated by the AHJ as Emergency, Legally Required, or Critical Operations are exempted. 12

13 1547 s Island Terminology Intentional Island: one that is planned, has a defined boundary, and has V/F regulation controls. Types: - Microgrid - Emergency/standby power supply - Island power system (as in, on an actual island) - Remote community grid - Military bases - Remote resource extraction operations Unintentional island: one that isn t planned and doesn t have V/F regulation control. 1547 does not permit unintentional islands. 13

Thanks! Questions? Charlie Vartanian Charlie.vartanian@pnnl.gov (626) 818-5230

BACKUP SLIDES

Background- Evolution of the Grid Current Power System Future Power Systems New Challenges New energy technologies and services Penetration of variable renewables in grid New communications and controls (e.g., Smart Grids) Electrification of transportation Integration of distributed energy storage Regulatory Advances 16

Importance of IEEE 1547 17 Energy Policy Act (2005) Cites and requires consideration of IEEE 1547 Standards and Best Practices for Interconnection; all states use or cite 1547. Energy Independence and Security Act (2007) IEEE cited as a standards development organization partner to NIST as Lead to coordinate framework and roadmap for Smart Grid Interoperability standards and protocols {IEEE 1547 & 2030 series being expanded}; Federal ARRA (2009) Smart Grid & High Penetration DER projects {use IEEE stds}. 17

18 Striking a new balance IEEE 1547-2018 mandates BOTH: Tripping requirements, and Ride-through requirements Ride-through is not a setting, it is a minimum capability of the DER shall ride through for at least seconds I.e., it is the minimum required DER robustness to withstand voltage and frequency disturbances May or may not be fully utilized, or it may be exceeded Trip thresholds and clearing times are maximum operational settings shall trip at latest by seconds May differ from default settings and are adjustable over a range of allowable settings Specified ranges do not allow DER tripping to seriously compromise bulk power system reliability Tripping points specified by the distribution utility may account for utility-specific practices but may also be constrained by the regional reliability coordinator Distribution Grid Safety Bulk System Reliability 18

Voltage Ride-Through (All Categories) based on IEEE 1547-2018 19

Frequency Ride-Through (Default Values for All Categories) Based on IEEE -2018 20

Driver for new ride-through requirements - Potential for widespread DER tripping (Cont) Voltage profile for 345 kv fault in East Mass., all BPS power plants online IEEE 1547-2018 mandates BOTH: Tripping requirements, and Ride-through requirements Ride-through is not a setting, it is a capability of the DER i.e., it is the DER s robustness Source: ISO-New England System frequency is defined by balance between load and generation Frequency is the same across entire interconnection; all DER may trip simultaneously during disturbance Impact the same whether or not DER is on a high-penetration feeder Tripping points are adjustable over an allowable range Range does not allow DER tripping to seriously compromise BPS security Tripping points specified by the Area EPS Operator (utility) within constraints of the regional reliability coordinator Slide courtesy Dr. Jens Boemer, EPRI 21

Specific Performance Terminology Trip cessation of output without immediate return to service; not necessarily disconnection Cease to energize no active power delivery, limitations to reactive power exchange; Does not necessarily mean physical disconnection. Can be either a momentary cessation or a trip Permissive operation DER may either continue operation or may cease to energize, at its discretion Mandatory operation required active and reactive current exchange Momentary cessation cessation of energization for the duration of a disturbance with rapid recovery when voltage or frequency return to defined range Return to service re-entry of DER to service following a trip Restore output DER recovery to normal output following a disturbance that does not cause a trip. 22

Assignment of new IEEE 1547 Performance Categories Normal and abnormal operating performance categories DER Vendors Market Analysis Category I Category III Category II Category A Category B Control / trip settings Ranges of allowable settings Default parameters Ride- Through Costs Market segment Etc. 1 Regulatory agencies, public utility commissions, municipalities, cooperative governing boards, etc. Voltage Regulation Authorities Governing Interconnection Requirements (AGIRs) 1 Stakeholder Engagement Distribution utilities. Bulk system operators & planners. DER developers. Others. Impact Assessment Technical conditions: type & capacity & future penetration of DER, type of grid configuration, etc. Non-technical issues: DER use case, impacts on environment, emissions, and sustainability, etc. Courtesy of Dr. J. Boemer/EPRI 23

Importance Of Interoperability Functions - Hawaii Case Study In 2014, Hawaii was headed for a repeat of Germany s 50.2 Hz problem o Inverters could trip en masse due to frequency excursion, worsening excursion and potentially blacking out grid In February 2015, Enphase remotely reprogrammed 800,000 inverters (154 MW) in Hawaii to enable frequency ride-through Required close coordination between utility and inverter manufacturer Oahu feeder PV penetration Enphase inverter locations Figure credit: https://www.gr eentechmedia. com/articles/re ad/enphase-tohelp-hawaiiride-its-solarenergywave#gs.4gz7w 1Q Slide used with courtesy of Dr. Andy Hoke, NREL 24

What is an island? An electric power island is a section of a power system with its own sources and loads, so that it can self-power or self-excite. Possible island 25 25

26 When can an II leave the grid? When conditions are met that are mutually agreedto by the Area EPS and DER operators; If any of the abnormal voltage or frequency trip conditions is met; or If an unintentional island is detected. For these latter two cases, one may substitute entry into intentional island mode for tripping. 26

Limits on Area EPS impact when leaving the Area EPS If an II disconnects from the Area EPS for any of the reasons listed on the previous slide, it shall do so without causing a voltage fluctuation greater than ±5% of the nominal voltage at any PCC between the Area EPS and the intentional island. There are two exceptions to this requirement: - If the II takes its load with it i.e., when the II leaves the grid, it causes an amount of load equal to 90% to 110% of its rating to leave the grid also; - The II is an emergency or standby generator that is ongrid for testing purposes only. 27 27

Limits on an II coming back onto the Area EPS An II can reconnect when the return-to-service requirements of Clause 4.10 are met (basically, the voltage and frequency are within defined limits). When the II reconnects, the requirements of Clause 4.10.4 ( synchronization, which defines how well synched to the grid the II must be in both voltage and frequency). 28 28