POWER Data Sheet CSV2000BP 2000 Watts Distributed Power System Front-end Bulk Power Total Output Power: 2000 W Input Voltage: 80 to 265 Vac Special features 2000 W output power U power supply Active Power Factor Correction EN6000-3-2 Harmonic compliance Inrush current control 80PLUS Platinum efficiency N+N Redundant Hot-pluggable Active current sharing PMBus compliant Two-year warranty Compliance Conducted/Radiated EMI Class A Limits RoHS IEC 60950 SAFETY UL/cUL CB Test Certificate CE Mark KC CQC BSMI BIS TÜV Electrical Specifications Input Input range Frequency Efficiency Max input current Inrush current Conducted EMI Radiated EMI Power factor Hold-up time Leakage current Output 80-264 Vac : 2000 W 98-264 Vac: 2000 W 47 Hz to 63 Hz 940% peak, platinum rating 0 A or 0 A 30 Apk Class A Class A >09 beginning at 0% load 2 ms at full load 0575 ma Main DC Output Standby DC Output MIN NOM MAX MIN NOM MAX Nominal setting -020% 22 020% -35% 20 +35% Total output regulation range 59 V 28 V 4 V 26 V Dynamic load regulation range 59 V 28 V 34 V 305 V Output ripple 20 mvp-p 20 mvp-p Output current 0 A 2 639 A 05 A 30 A Current sharing Within ±0% of full load rating, starting at 30% of rated load N/A Capacitive loading 00 µf 25,000 µf 50 µf 500 µf Start-up from AC to output 3,000 ms 2,500 ms Output rise time 5 ms 50 ms ms 25 ms For UL covered area that allows A input current rating 2 Minimum current for transient load response testing only Unit is designed to operate and be within output regulation range at zero load
Electrical Specifications Protections Main Output MIN NOM MAX Overcurrent protection 2 69 A 205 A Overvoltage protection 34 V Undervoltage protection 00 V Overtemperature protection Fan fault protection Standby Output Overcurrent protection 3 385 A 395 A Overvoltage protection 3 38 V Undervoltage protection 00 V Latch mode 2 THROTTLE warning of at least second before latching off 3 Standby protection is auto-recovery LED Indicators Input Good (Green) Output Good (Green) Fault (Yellow) Output ON and OK On On Off Standby mode (input present, main output off) or zero output mode On Blinking Hz Off No input/input out of range Off Off Off OCP, or over-subscription fault, or OVP, or fan failure, or OTP On Off On Environmental Specifications Operating temperature 5 to 50 C Operating altitude up to 0,000 feet Operating relative humidity +8% to 93%, non-condensing Non-operating temperature -40 to +70 C Shipping and storage relative humidity +5% to 00%, including condensing Non-operating altitude up to 50,000 feet Vibration and shock Standard operating/non-operating random shock and vibration RoHS compliance MTBF 500 k hours at 40 C, 70% load, nominal input Operating life Minimum of 5 years at typical conditions PSU ambient temperature derated at C per 600 ft above 3000 ft Ordering Information Model Name Ordering Part Number Nominal Main Output Standby Output Airflow Direction CSV2000BP-3 700-04265-000 22 V @ 639 A 2 V @ 30 A Standard (forward)
Timing Diagram AC Input T sb_hold-up T sb_on -5% Vout_stby EPOW T ACOK_off_dwell T AC_On_Delay T Vout_Hold-up -5% Vout_main T ACOK_PWOK_Delay T PWOK_On T PWOK_Off PWOK T PSON_On_Delay T PSON_PWOK PSON Timing Specifications Description Min Max Unit T sb_on Delay from AC being applied to standby output being within regulation 2500 ms T Vout_rise Rise time of output voltage going from 0% to 90% of the nominal regulation 50 ms T AC_On_Delay Delay from AC being applied to main output being within regulation 3000 ms T PWOK_On Delay from output voltages within regulation limits to PWOK assertion 80 220 ms T ACOK_PWOK_Delay Delay from ACOK going low to deassertion of PWOK 6 ms T Vout_Hold-up Delay from loss of AC to main output being within regulation 2 ms T sb_hold-up Delay from loss of AC to standby output being within regulation 50 000 ms T PWOK_Off Delay from deassertion of PWOK to output falling out of regulation 2 ms T PSON_PWOK Delay from deassertion of PSON to deassertion of PWOK ms T PSON_On_Delay Delay from PSON assertion to output being within regulation 5 00 ms
Mechanical Outline 0±05 705±05 2020±04 800±03 950 400±03 385±03 DIMENSION AND TOLERANCE NEED TO BE HELD AT THE EDGE OF THE STANDOFF LOCATIONS ONLY 40±025
Connector Definitions Output connector part number Card-edge Mating connector part number FCI Amphenol HPCE 022238-320424FLF Power Supply Output Card Edge (Top Side) P29-P36 *Not actual image P2-28 S24 P9/20 Power Supply Output Card Edge ( Bottom Side) P-P8 P9-P8 S3 Output Connector Pin Assignment Pin Pos Name Pin Pos Name S Reserved S3 SMBus_RESET# S2 Reserved S4 Reserved S3 +MAIN_VRS / +Vsense S5 ADDRESS S4 Reserved (Gnd at system side) S6 PSON_L S5 RESERVED S7 PSON_L S6 DC_GOOD / PWOK S8 EPOW# / ACOK S7 PRESENT# S9 Reserved S8 SMBALERT# S20 Throttle# S9 ISHARE S2 Reserved S0 GND / RETURN S22 -MAIN_VRS / -Vsense S SDA S23 Reserved S2 SCL S24 Reserved P-P8 2Vout P29-P36 2Vout P9-P8 RETURN P2-P28 RETURN P9-P20 2Vaux *Not actual image S S2 Power Supply Addressing (pin S5) Resistance (pull-down at system side, % tol or better) Voltage (nom) Hex Address OPEN 200 V D0 280 k 049 V D2 22 k 90 V D4 68 k 755 V D6 402 k 600 V D8 237 k 445 V DA 33 k 298 V DC 576 k 50 V DE WORLDWIDE OFFICES Americas 2900 SDiablo Way Tempe, AZ 85282 USA + 888 42 7832 Europe (UK) Waterfront Business Park Merry Hill, Dudley West Midlands, DY5 LX United Kingdom +44 (0) 384 842 2 Asia (HK) 4/F, Lu Plaza 2 Wing Yip Street Kwun Tong, Kowloon Hong Kong +852 276 3333 wwwartesyncom Artesyn Embedded Technologies, Artesyn and the Artesyn Embedded Technologies logo are trademarks and service marks of Artesyn Embedded Technologies, Inc All other names and logos referred to are trade names, trademarks, or registered trademarks of their respective owners Specifications are subject to change without notice 207 Artesyn Embedded Technologies, Inc All rights reserved For full legal terms and conditions, please visit wwwartesyncom/legal For more information: wwwartesyncom/power For support: productsupportep@artesyncom CSV2000BP DS May208