TRS 9 35MM 78MM 150MM 78MM THICKNESS END SPAN INTERNAL SPAN MINIMUM PITCH 0.55MM 2.30M 3.20M 3 DESCRIPTION TRS 9 profile is designed for commercial and industrial roofing. The profile is suitable for low pitch roofing as well as curved roofing. Commercial and industrial roofing G550 grade steel with minimum 0.55 BMT gives more resilience to damage. SPECIFICATION AT A GLANCE GENERAL Minimum Roof Pitch 3 Degree Effective Cover 910mm Max. Unsupported Overhang Contact "" SPANS End Span 0.55 BMT 2300mm Internal Span 0.55 BMT 3 DRAPE CURVE 0.55mm BMT G300 Min. 90m Radius WALL CLADDING FIINGS Cladding fixing on 20mm, 12 Gauge class 4 screws with neo washers, miss 2 pans, miss 3pans, every H 3.1 treated batterns second on ends ROOF FIINGS Low / Medium wind Zone Timber: class 4 14 x 75mm with neo washer and embossed washer Steeltite: 12 x 65mm with neo washer and embossed washer High wind Zone Timber: class 4 14 x 75mm with neo washer and embossed washer, approved profile's metal washer and EPDM washer Steeltite: 12 x 65mm with neo washer and embossed washer, approved profile's metal washer and EPDM washer Very High Wind Zone Contact "" Specific Design Wind Zone Contact "" ROOF FIING LENGTHS Dark Colour Up To 8 Meters Solid fix Light Colour Up To 12 Meters Solid fix sheet lengths Excess Above* Oversize holes required for movement *Contact for further information on specific design FIINGS, FASTENING AND UNDERLAY All fixings and fasteners are to be of an approved type, compatible with all materials, the environment and meeting the requirements of the NZ Building Code. Installation is to be in accordance with the NZ Metal Roof and Wall Cladding Code of Practice or manufacturer's instructions. Fix every crest to: Ridge, Hip, Valley, Gutter and Periphery area. Underlay as per the project specification is to be used. COATINGS AND COMPLIANCE WITH AS/NZS 2728 (CORROSION RESISTANCE) The KiwiColour brand is available in two different product lines designed specifically to suit different environmental and atmospheric conditions; KiwiColour VITOR & KiwiColour ZENE. Independent laboratory tests have confirmed that KiwiColour VITOR complies with the corrosion resistance performance requirements of AS/NZA 2728 with regards to Product Type 4 (the corrosivity category into which most populated areas of New Zealand fall) in all aspects of salt spray performance and humidity resistance and including other product properties such as coating thickness, gloss and cross hatch adhesion(gloss category 2 ). Independent testing demonstrated that Kiwicolour ZENE samples met the corrosion resistance performance requirements of AS/NZS 2728:2007 for Product Types 3 and 4. Refer to Product literature for selection of suitable finishing and warranty. All kiwi colour materials are available on Master spec. 38MM C-TRS9-00 PRODUCT TECHNICAL DATA NTS
ROLL TOP RIDGE FLASHING RIDGE FLASHING PURPOSE MADE TO MATCH ROOF PITCH STOPEND SHEET PROFILED FOAM CLOSURE (only required in high risk situations of wind blown moisture entering) ROOF PITCH 3 MIN. SCREW FIING WITH 12x55 STEEL TEK & NEO WITH SELECTED WASHER SYSTEM BMT 0.55 RIDGE FLASHING NOTCHED TURN-DOWN OVER ROOFING, 5mm MA GAP TO CLEAR OF TROUGH OR ROOFING ROOFING UNDERLAY LAID OVER SAFETY NETTING STEEL PURLIN & CLEAT STRUCTURAL STEEL ROOF PITCH 10 VERY HIGH OR ETRA WIND ZONE. ROOF PITCH < 10 130mm C-TRS9-01 TOP RIDGE DETAIL - SQUARE TOP
1255 STEELTEK & NEO WITH SELECTED WASHER SYSTEM ROOF PITCH 3 MIN. ROOF UNDERLAY SAFETY MESH STEEL PURLIN & CLEAT C-TRS9-02 TYPICAL ROOF LAYOUT
35 MIN. LAP 1255 STEELTEK & NEO WITH SELECTED WASHER SYSTEM, FASTEN EAVES AT EVERY CREST 50mm MIN. OVERHANG 125mm MIN. COVER ROOF PITCH 3 MIN. DRIP EDGE ROOFING UNDERLAY LAID OVER SAFETY NETTING EAVE FLASHING HEM TO TOP EDGE WALL CLADDING WALL UNDERLAY C-TRS9-03 GUTTER FLASHING DETAIL - ETERNAL
5 Y 10 SCREW FIING WITH 12x25 TYPE 17 TEK & NEO OR 4.8mm ALUM RIVETS MIDSPAN WHERE APPLICABLE 5mm MA GAP TO CLEAR OF TROUGH OR ROOFING BMT0.55 BARGE FLASHING STOP END SHEET PROFILED FOAM CLOSURE (Foam closure strip only required in high risk situations) NOTCHED FLASHING FOLDED & FIED THROUGH RIBS WITH 12g 55mm STEEL TEK SCREW Z ROOFING UNDERLAY LAID OVER SAFETY NETTING 12x55mm STEEL TEK & NEO WITH SELECTED WASHER SYSTEM WALL CLADDING STEEL PURLIN WALL UNDERLAY (if required) Y Z ROOF PITCH 10 50mm STEEL GIRT VERY HIGH WIND ZONE. ROOF PITCH < 10 70mm ETRA HIGH WIND ZONE. 90mm C-TRS9-04 BARGE DETAIL
SCREW FIING WITH 12x55 STEEL TEK & NEO WITH SELECTED WASHER SYSTEM TURN-DOWN TO SUIT ROOFING PROFILE, 5mm GAP MA TO CLEAR OF ROOFING ROOF PITCH 3 MIN. MIN. COVER PROFILED FOAM CLOSURE (Foam closure strip only required in high risk situations of wind blown moisture entering) STOPEND SHEET BMT0.55 BARGE FLASHING Z 1240 TYPE 17 TIMBER TEK PROFILED FOAM CLOSURE (Foam closure strip only required in high risk situations) ROOFING UNDERLAY LAID OVER SAFETY NETTING NOTCHED FLASHING FOLDED & FIED THROUGH RIBS WITH 12g 65mm STEEL TEK SCREW WALL CLADDING STRUCTURAL STEEL WALL UNDERLAY (if required) Z STEEL GIRT & CLEAT ROOF PITCH 10 VERY HIGH WIND ZONE. ROOF PITCH < 10 ETRA WIND ZONE. 130mm 50mm 70mm 90mm C-TRS9-05 HEAD BARGE DETAIL
35 100 METAL OVER FLASHING CHASE INTO 20x10 GROOVE AND SEALED WITH SEALANT PROFILED FOAM CLOSURE (only required in high risk situations of wind blown moisture entering) CONCRETE WALL SCREW FIING WITH 12x55 STEEL TEK & NEO WITH SELECTED WASHER SYSTEM HEM TO FLASHING EDGE BMT 0.55 APRON FLASHING NOTCHED TURN-DOWN OVER ROOFING, 5mm GAP MA TO CLEAR OF TROUGH OR ROOFING ROOF PITCH 3 MIN. ROOFING UNDERLAY LAID OVER SAFETY NETTING 20 MIN. GAP STOPEND SHEET STEEL PURLIN STRUCTURAL STEEL ROOF PITCH 10 130mm VERY HIGH WIND ZONE. ROOF PITCH < 10 ETRA WIND ZONE. C-TRS9-06 APRON DETAIL - HEAD - CHASED
35 100 90 E 50mm H3.2 TIMBER CAPPING SUPPORT ON DPC SEPERATION BARRIER BETWEEN CONCRETE & FLASHING (SELF ADHESIVE TAPE OR SIM) BMT 0.55 PARAPET FLASHING 5 MIN. FI CAPPING TO CONCRETE WITH MASONRY FASTENERS AT 600mm crs PROFILED FOAM CLOSURE (only required in high risk situations of wind blown moisture entering) SCREW FIING WITH 12x55 STEEL TEK & NEO WITH SELECTED WASHER SYSTEM HEM TO FLASHING EDGE BMT 0.55 APRON FLASHING NOTCHED TURN-DOWN OVER ROOFING, 5mm GAP MA TO CLEAR OF TROUGH OR ROOFING ROOF PITCH 3 MIN. CONCRETE WALL ROOFING UNDERLAY LAID OVER SAFETY NETTING STOPEND SHEET STEEL PURLIN STRUCTURAL STEEL 20 MIN. GAP ROOF PITCH 10 130mm VERY HIGH WIND ZONE. ROOF PITCH < 10 ETRA WIND ZONE. C-TRS9-07 APRON DETAIL - HEAD - PARAPET
5 35 75 min gap min. cover METAL OVER FLASHING CHASE INTO 20x10 GROOVE AND SEALED WITH SEALANT BMT 0.55mm 2 PIECE APRON FLASHING TO COVER 12x55mm STEEL TEK & NEO WITH SELECTED WASHER SYSTEM CONCRETE WALL SCREW FIING WITH 12x25 TYPE 17 TEK & NEO OR 4.8mm ALUM RIVETS MIDSPAN WHERE APPLICABLE 10 Y HEM TO FLASHING EDGE 5mm GAP MA TO CLEAR OF TROUGH OR ROOFING ROOFING UNDERLAY LAID OVER SAFETY NETTING STEEL PURLIN Y ALL WIND ZONES C-TRS9-08 APRON DETAIL - SIDE - CHASED
5 35 75 min gap min. cover E 50mm H3.2 TIMBER CAPPING SUPPORT ON DPC SEPERATION BARRIER BETWEEN CONCRETE & FLASHING (SELF ADHESIVE TAPE OR SIM) BMT 0.55 PARAPET FLASHING BMT 0.55mm 2 PIECE APRON FLASHING TO COVER 5 MIN. FI CAPPING TO CONCRETE WITH MASONRY FASTENERS AT 600mm crs Z 12x55mm STEEL TEK & NEO WITH SELECTED WASHER SYSTEM SCREW FIING WITH 12x25 TYPE 17 TEK & NEO OR 4.8mm ALUM RIVETS MIDSPAN WHERE APPLICABLE 10 Y HEM TO FLASHING EDGE 5mm GAP MA TO CLEAR OF TROUGH OR ROOFING CONCRETE WALL ROOFING UNDERLAY LAID OVER SAFETY NETTING STEEL PURLIN ROOF PITCH 10 VERY HIGH WIND ZONE. ROOF PITCH < 10 ETRA WIND ZONE. Z 50mm 70mm 90mm C-TRS9-09 APRON DETAIL - SIDE - PARAPET
PIPE EPDM FLEIBLE CONE SLEEVE MALLEABLE FLANGE, SCREW OR RIVET FIED, AND SEALED TO ROOFING PROFIL FIT NEOPRENE WASHERS TO ALL SCREW FIINGS Fall NOTE: (1) MA. ROOF PITCH FOR THIS FLASHING 45, MINIMUM PITCH 10 IF BASE OF FLANGE COVERS OVE OR MORE COMPLETE TROUGHS. (2) FOR PIPES UP TO 85mm DIAMETER (3) NZMRM CODE OF PRACTICE ALLOWS LARGER THAN 85mm DIAMETER PENETRATION PROVIDED THE FLASHING DOES NOT ETEND TO MORE THAN 50% OF PAN WIDTH (4) INSTALL ADJACENT TO PURLIN FOR SUPPORT WHERE POSSIBLE. NO PANS TO BE FULLY BLOCKED OFF BY PIPE OR DEKTITE FLASHING FIED DIAGONALLY TO ROOFING PROFILE TIO MINIMISE HOLDING OF DIACHARGE WATER C-TRS9-10 NTS PIPE PENETRATION DETAIL UPTO 85mm
TOP RIDGE SOAKER FLASHING TO BE FULLY SUPPORTED BY ROOFING UNDER HEM TO EDGE SEAL AND FASTEN ROOF FIING NOTCHED TURN-DOWN OVER TRS 9. 5mm MA. GAP BETWEEN PAN AND EDGE OF FLASHING EPDM FLEIBLE BOOT FLASHING SCREW FIED AND SALED TO METAL SOAKER FLASHING. FIT NEOPRENE WASHERS UNDER SCREWS 130mm NOTE: (1) SUITABLE FOR PIPES FROM 86mm TO 500mm DIAMETER (2) SUITABLE ONLY FOR ROOF PITCHES OF 10 OR MORE VERY HIGH OR ETRA WIND ZONE. C-TRS9-11 1:30 NTS PIPE PENETRATION DETAIL UPTO 500mm