EXPERIMENTAL STUDY OF TIMBER-TO-CONCRETE DOWEL TYPE CONNECTIONS USED IN TIMBER PLATFORM FRAME

Size: px
Start display at page:

Download "EXPERIMENTAL STUDY OF TIMBER-TO-CONCRETE DOWEL TYPE CONNECTIONS USED IN TIMBER PLATFORM FRAME"

Transcription

1 EXPERIMENTAL STUDY OF TIMBER-TO-CONCRETE DOWEL TYPE CONNECTIONS USED IN TIMBER PLATFORM FRAME Summary Kenneth Leitch BSc (Hons) Research Assistant Centre for Timber Engineering, Napier University Edinburgh, Scotland Robert Hairstans BEng (Hons), PhD Lecturer School of Engineering and the Built Environment, Napier University Edinburgh, Scotland Derek Abbott Managing Director ETA Fixings (UK) Ltd Stourbridge, England Robin Dodyk Technical Director Oregon Timber Frame Ltd Selkirk, Scotland Scott McAndrew Technical Manager Cullen Building Products Ltd Glenrothes, Scotland Market forces in the U.K are dictating that timber frame houses are built with narrow frontages which contain a large percentage of openings. As a result of this, the number of full height panels which can be classified as offering resistance to racking forces is reduced and the performance requirements of the remaining panels are increased. As part of a wider project aimed at addressing this problem through the development of a hybrid racking panel, this paper considers the importance of a robust soleplate connection and its ability to offer secure anchorage. Specifically, it quantifies the degree of lateral (sliding) resistance offered by a range of commercially available fasteners. The results from an experimental test program show the lateral load-carrying capacity of each of these fasteners when used to connect a C16 or Laminated Strand Lumber (LSL) soleplate to a concrete foundation substrate. It is shown that the currently preferred method is inefficient in terms of both structural and economic performance when compared to other fasteners tested.

2 1. Introduction Modern Methods of Construction (MMC) are gaining increased popularity in the U.K due to improved quality control, speed of construction and efficient use of materials. One of the most common examples of MMC is timber platform frame which at present accounts for approximately 20% [1] of new homes built in the U.K. Timber platform frame often competes in the low cost, high volume estate market where the cost of land and client desire for detached accommodation leads to narrow properties with openings often concentrated in the shorter walls [2]. This is problematic when designing for overall structural stability as reduced width shear wall panels do not have the ability to provide sufficient resistance to sliding and overturning (racking) forces caused by the applied wind load. In order to offer a solution to this problem, research is currently being carried out into the development of a Hybrid Racking Panel (HRP) which is optimised in terms of performance, cost and installation. When considering the racking performance of a wall panel it is important to understand how the inplane forces acting upon it are resisted and transferred to the foundation (Fig. 1). In order to resist in plane loading a shear wall relies on framing members, sheathing and nail connectors all interacting closely with one another [3]. Improvements in the racking performance can be achieved if each of these variables is optimised for the required conditions and this is central to the development of an HRP. However, the successful implementation of these improvements is dependent on secure anchorage specification which must ensure applied lateral (shear) and overturning forces are transferred safely to the foundations. Compression reaction Shear reaction Applied lateral force Vertical anchor force Fig. 1 Illustration of forces acting upon a shear wall panel At present neither BS 5268 [4] nor the soon to be introduced Eurocode 5 (EC5) [5] offer a method specifically for the calculation of a timber-to-concrete connection s lateral load-carrying capacity. Research by Aicher et al [6] has proved the calculated characteristic shear load capacity of a timberto-concrete joint to be approximately the same as that obtained by using a timber design code for nailed timber-to-thick steel plate connection [7]. However, methods such as this only consider standard smooth or threaded types of fasteners. Detailed in this paper is the experimental investigation of standard and non-standard fixings when used in conditions replicating that of timber sole plate to substrate connection. The purpose of the test program was to determine the feasibility of specifying the connections detailed and these findings are reported on. Further to this, the research program was conducted in a manner which would facilitate further investigation of the fixing types and connection detailing. Research by Blass [8] identified that the three parameters influential to a joints load carrying behaviour are; (i) the bending capacity of the dowel (ii) the embedding capacity of the timber or wood based material (iii) the withdrawal capacity of the dowel. With respect to these, a supplementary test program was carried out and these results are also reported and discussed. 1.1 Site practice and detailing The structural performance as well as the accuracy of a timber platform frame build is reliant on the initial positioning and fixing of the soleplate. Table 1 shows typical soleplate material specification whilst Fig. 2 shows the soleplate in relation to a typical wall footing detail. Applied wind load

3 Table 1 Soleplate material specification Dimensions Timber type Characteristic density (ρ k) 38x89mm 45x89mm C16 ( * ) Solid sawn timber 310 kg/m 3 ( * ) Structural strength class as per BS EN 338 [9] A desktop study into practices adopted throughout Footing North America (where Timber frame accounts for 90% of low rise builds) showed that Laminated Strand Lumber (LSL) is often used in areas where high Foundation performance is required. Examples of this include shear walls designed to resist hurricane and seismic activity. As well as structural benefits, LSL is also well suited to Fig. 2 Detail of wall footing use as a soleplate material. It is more resistant to moisture and the resultant warping and twisting it causes than sawn timber. Furthermore, it also offers uniform strength properties in each axis and this gives it improved resistance to compressive forces imposed by the vertical stud ends. In the U.K the preferred method for securing the soleplate and providing lateral resistance is the shot fired dowel. This is a smooth type dowel installed via a powder actuated tool (Fig. 3). This method has found favour due to its ease and speed of installation. However, the performance of this fastener must be validated in relation to the increased shear forces which will require to be transferred by the proposed HRP. Therefore, an experimental program to evaluate the lateral resistance offered by it and other fasteners, along with the effect of using LSL as a soleplate material was developed. Fig. 3 KMN45LV tool 2. Experimental program Floor slab Wall Panel Footer Sole Plate To evaluate the performance of the shot fired dowel and provide comparative data from other fastener types an experimental investigation was carried out. Eleven commercially available dowel-type fasteners (supplied by ETA Fixings UK Ltd) which were suitable for fixing the soleplate and providing shear resistance were selected. These were divided into 4 sub categories; Masonry Screws (MSC), All purpose masonry screws (KF), Shot fired dowels (KMN) and a non standard fastener type known as an Express nail (EXPN) (Figure 4 & Tables 2-5). Wall All purpose masonry screw Shot fired dowel Masonry Screw Express Nail Fig. 4 Illustration of tested fastener range

4 Table 2 Average dimensions of tested Masonry screws Length (mm) Diameter (mm) Overall Thread Shank Thread Root Shank Head MSC MSC BTB4C BTB4C Table 3 Average dimensions of tested All purpose masonry screws Length (mm) Diameter (mm) Overall Thread Shank Thread Root Shank Head KF N/A N/A KF N/A N/A Table 4 Dimensions of tested Express Nails Length (mm) Diameter (mm) Overall Point Shank Head X section area (mm 2 ) EXPN EXPN EXPN EXPN Table 5 Dimensions of tested Shot fired dowel Length (mm) Diameter (mm) Overall Root Head Washer KMN The experimental investigation conducted replicated UK in-situ sole plate connection detailing, Dense Aggregate Block (DAB) with a characteristic strength of 7N/mm 2 was used and Damp Proof Coursing (DPC) was placed at the timber/block interface (Fig. 5), and lateral load tests were carried out in accordance with BS EN 1380 [10]. Shear plane Applied Rate 2mm/min 40mm 65mm 45mm DAB 65mm 65mm 45mm 65mm C16 Timber / LSL 40mm Fig. 5 Details of lateral load-carrying capacity set up and specimen under test

5 Installation methods for each fastener (Table 6) were carried out as per manufactures recommendations. Details of the test methods used for the supplementary program can be found in the standards given (Table 7). Table 6 Installation methods for tested fasteners Fastener type Masonry Screw All purpose masonry screw Express nail Shot fired dowel Installation method Pre-drill timber and substrate as per Manufacturer s specification. Brush and blow debris from hole. Screw into place with cross head drill bit. Pre-drill timber and substrate as per Manufacturer s specification. Brush and blow debris form hole. Screw into place with Torque bit. Pre-drill timber and substrate as per Manufacturer s specification. Brush and blow debris from hole. Drive fastener home with hammer. Install with KM45LV cartridge tool and charges Table 7 Supplementary test program details Test Carried Carried out on out to Point side Based Fasteners tested in 7N block withdrawal upon BS installed at minimum strength EN recommended depth Head side pull through strength Embedment strength 1383[11] BS EN 1382[12] BS 383[13] Fasteners tested in both C16 Solid timber and LSL Fasteners tested in both C16 Solid timber and LSL. Fig. 6 Illustration of head side pull through (l) and point side withdrawal (r) test methods. 4. Results Results from tests determining the lateral load carrying capacity (Fig. 7) of each fastener in both C16 timber and LSL show 2 particularly relevant results: 1. The current method of fixing the soleplate 6000 (KMN72) is proven to give the lowest 5000 lateral resistance of the fasteners on test By specifying LSL over C16 timber, 3000 lateral resistance can be increased. Characteristic Lateral load carrying capacity (N) MSC36070 MSC36082 BTB4C70 BTB4C82 KF7.5x80 KF7.5x100 C16 Solid timber EXPN6x60 EXPN6x100 LSL EXPN8x70 EXPN8x90 KMN72 Fig. 7 Comparison of fastener lateral load carrying capacity in both LSL and C16 timber. These findings are directly applicable to currently employed practices. Moreover, the results provide a bank of information for the future specification of fasteners based upon requirements. In all test cases the development of at least one plastic hinge in the fastener was observed. In the case of threaded fasteners, ultimate failure was found to occur through combined bending and shear forces. This lead to a sudden failure in the area where the hinge had formed. For smooth types of fastener the development of the hinge caused rotation and withdrawal of the fastener from the substrate. There was no sudden loss in connection strength but rather a predictable failure as the fastener was pulled from the substrate.

6 The angle to which this hinge developed was found to be dependent on the resistance to embedment offered by the timber member (Fig. 8). Results show the embedment resistance of LSL to be consistently higher than that of C16 timber. In line with these findings, LSL was also found to offer improved resistance to head side pull through (Fig. 9). In this respect, Fastener KF75 80/100 was found to give the highest values from tested fasteners and this was attributed the fastener being threaded over its entire length with no smooth shank. Due to this, the additional threads in the timber offered increased resistance. Since the overall withdrawal strength of the fastener is taken to be the of the lesser of the head side pull through and point side withdrawal the use of LSL and the resultant increase in head side pull through strength can, in cases, be shown to change the withdrawal parameter. In such Strength (N) cases the point side withdrawal strength becomes critical. In determining the performance of each fastener, additional findings were made; namely the importance of the installation of fasteners as per manufacturers recommendations. The point side withdrawal capacity of each fastener was found to be highly dependent on the adherence to specified penetration depths. Furthermore, incorrectly drilled holes and those which had not been properly cleared of debris were found to be detrimental in this respect. 5. Discussion In order to make these results relevant to the fastener s specified on site, additional factors such as cost and method of installation must be 3 MSC36070 taken into account. By using assumed 2.5 MSC36082 values for the amount of lateral BTB4C70 resistance required we can easily see 2 BTB4C82 the economic inefficiency of the current 1.5 KF75X80 methods of fixing (Fig. 10). A direct KF75x100 1 EXPN6x60 result of this finding has been the trial 0.5 EXPN6x100 specification of fastener KF on EXPN8x70 site. Data from the test program has 0 EXPN8x indicated that the fastener gives KMN72 Required lateral resistance (N) improved performance in relation to both lateral resistance and holding Fig. 10 Comparison of fastener cost performance down. However, its method of installation has been found to be both Cost of fasteners required (GBP) MSC36070/82 BTB4C70/82 KF7.5x80/100 Pointside withdrawal strength LSL Headside pull through EXPN6x60/100 EXPN8x70/90 KMN72 C16 Headside pull through Fig. 9 Comparison of withdrawal strengths of tested fasteners Embedment strength (N/mm 2 ) MSC36070/82 BTB4C70/82 KF7.5x80/100 C16 Timber EXPN6x60/100 LSL EXPN8x70/90 KMN72 Fig. 8 Comparison of embedment strength of tested fasteners in both C16 and LSL

7 labour intensive and time consuming. Therefore, whilst it offers improvements in performance it can not be considered a fully optimised solution. Although the primary aim of this paper was to present the results of a laboratory based test program, through the study of site practices it is understood that increases gained from improved specification will be negated if the recommended installation practice is not adhered too (Fig.11). Therefore, to ensure that the values obtained through test are replicated in live situations it is important to ensure that good practice is maintained throughout. 6. Conclusion The primary purpose of this work was to provide test data on a range of fixings suitable for connecting the soleplate to the foundation substrate. In doing so each fixings performance would be evaluated in relation to the method currently employed. The aim was to improve current fastener specification and also provide data which can be used as part of a long term collaborative research project to develop a hybrid racking panel. Although test data combined with cost analysis highlighted the potential for immediate improvements in specification, site trials of the revised specification demonstrated that it was not an optimal solution as the more onerous installation method impinged upon on-site efficiency. Additionally, the importance of observing the manufacturers specified methods and adhering to good practice throughout the installation procedure has also been highlighted. The performance of each fastener when Laminated Strand Lumber is used in place of C16 timber has also been quantified. It has been shown that connection capacity can be directly increased by specifying LSL. Further investigation is needed to determine if the improved structural performance and construction benefits fully justify the increased costs associated with engineered wood products. 7. Acknowledgements The Author would like to thank Cullen BP, ETA Fixings (UK) Ltd, Napier University and Oregon Timber Frame Ltd. Their on going support is greatly appreciated. Gratitude is also expressed towards The Royal Academy of Engineers for their assistance in attending this conference. 8. References Fig. 11 Incorrectly installed (over penetration) shot fired dowel. [1] UK Timber Frame Association (UKTFA). Timber frame facts and figures, UKTFA, The e-centre, Cooperage Way Business Village, Alloa, 2005 [2] Griffiths B., Enjily V., Blass H., and Kallsner B., A Unified Design Method for the Racking Resistance of Timber Framed Walls for Inclusion in Eurocode 5 CIB-W18, 2006 [3] Prion H.G.L, Shear walls and diaphragms In: Timber engineering Edited by Thelandersson S,. and Larsen H.J, Chichester ISBN [4] British Standards Institution (BSI) (2002) BS : 1996: Structural use of timber. Code of practice for timber frame walls. Dwellings not exceeding 4 stories.

8 [5] British Standards Institution (BSI) BS EN : Eurocode 5 Design of timber structures Part 1-1: General Common rules and rules for buildings [6] Aicher S., Klock W., Dill-Langer G., Radovic B., (2003) Nails and nail plates as shear connectors for Timber-concrete composite constructions. Otto-Graf-Journal, Volume 14, 2003, pp [7] N.N.: E DIN 1052:2000. Entwurf, Berechnung und Bemesung von Holzbauwerken. Beuth- Verlag, Berlin, [8] Blass H.J, (2003) Joints with Dowel-type Fasteners In: Timber Engineering Edited by Thelandersson S,. and Larsen H.J, Chichester ISBN [9] British Standards Institution (BSI) BS EN 338:2003 Structural Timber Strength Classes [10] British Standards Institution (BSI) BS EN 1380:1999 Timber structure- Test methods- Load bearing nailed joints. [11] British Standards Institution (BSI) BS EN 1383:1999 Timber structures Test Methods Pull through resistance of timber fastener. [12] British Standards Institution (BSI) BS EN 1382:1999 Timber structures Test Methods Withdrawal capacity of timber fasteners. [13] British Standards Institution (BSI) BS EN 383 Timber structures Test Methods Determination of embedding strength and foundation values for dowel type fasteners

The Influence of Nails and Plasterboard on the Racking Resistance of Stud Walls

The Influence of Nails and Plasterboard on the Racking Resistance of Stud Walls Building 1 Grosvenor Court, Hipley Street OLD WOKING, SURREY GU22 9LL Tel: +44 (0) 1483 769518 Fax: +44 (0) 1483 770863 E-mail: design@silvatecdesigncom Internet: wwwsilvatecdesigncom The Influence of

More information

LOAD CARRYING CAPACITY OF METAL DOWEL TYPE CONNECTIONS OF TIMBER STRUCTURES

LOAD CARRYING CAPACITY OF METAL DOWEL TYPE CONNECTIONS OF TIMBER STRUCTURES Vol. 10, Issue /014, 51-60 DOI: 10.478/cee-014-0011 LOAD CARRYING CAPACITY OF METAL DOWEL TYPE CONNECTIONS OF TIMBER STRUCTURES Jozef GOCÁL 1,* 1 Department of Structures and Bridges, Faculty of Civil

More information

SCREWS WITH CONTINUOUS THREADS IN TIMBER CONNECTIONS

SCREWS WITH CONTINUOUS THREADS IN TIMBER CONNECTIONS SCREWS WITH CONTINUOUS THREADS IN TIMBER CONNECTIONS Prof. Dr.-Ing. H. J. Blaß, Dipl.-Ing. I. Bejtka Universität Karlsruhe (TH), Germany Abstract Screws, bolts and dowels loaded perpendicular to the fastener

More information

Dowel-type fasteners. Timber Connections. Academic resources. Introduction. Deferent types of dowel-type fasteners. Version 1

Dowel-type fasteners. Timber Connections. Academic resources. Introduction. Deferent types of dowel-type fasteners. Version 1 Academic resources Timber Connections Dowel-type fasteners Version 1 This unit covers the following topics: Deferent types of dowel-type fasteners Introduction There are four criteria designers should

More information

STRUCTURAL TIMBER DESIGN

STRUCTURAL TIMBER DESIGN STRUCTURAL TIMBER DESIGN to Eurocode 5 2nd Edition Jack Porteous BSc, MSc, DIC, PhD, CEng, MIStructE, FICE Director lack Porteous Consultancy and Abdy Kernlani BSc, MSc, PhD, CEng, FIStructE, FIWSc Professor

More information

STRUCTURAL PERFORMANCE OF TIMBER EXTERNAL CLADDING

STRUCTURAL PERFORMANCE OF TIMBER EXTERNAL CLADDING STRUCTURAL PERFORMANCE OF TIMBER EXTERNAL CLADDING David Crawford 1 Dr Robert Hairstans 2 Ivor Davis 3 ABSTRACT: Although timber cladding has been used for centuries, the current design guidance for timber

More information

Connections in CLT Assemblies

Connections in CLT Assemblies Creating forest sector solutions www.fpinnovations.ca Connections in CLT Assemblies Cross Laminated Timber Symposium Vancouver, BC February 8-9, 2011 M. Mohammad Building Systems Wood Products Division

More information

The predictive model for strength of inclined screws as shear connection in timber-concrete composite floor

The predictive model for strength of inclined screws as shear connection in timber-concrete composite floor The predictive model for strength of inclined screws as shear connection in timber-concrete composite floor F. Moshiri, C. Gerber, H.R. Valipour, R. Shrestha & K.I. Crews Centre for built infrastructure,

More information

ALUMIDI. Concealed beam hanger with and without holes Aluminum alloy tridimensional perforated plate ALUMIDI - 01 CERTIFIED STEEL-ALUMINUM

ALUMIDI. Concealed beam hanger with and without holes Aluminum alloy tridimensional perforated plate ALUMIDI - 01 CERTIFIED STEEL-ALUMINUM ALUMIDI Concealed beam hanger with and without holes Aluminum alloy tridimensional perforated plate CERTIFIED Available with and without holes. The 2200 mm model is also certified FIELD OF USE Timber-to-Timber

More information

Ductility of large-scale dowelled CLT connections under monotonic and cyclic loading

Ductility of large-scale dowelled CLT connections under monotonic and cyclic loading Ductility of large-scale dowelled CLT connections under monotonic and cyclic loading Lisa-Mareike Ottenhaus 1, Minghao Li 2, Tobias Smith 3 1. PhD candidate, Department of Civil and Natural Resources Engineering,

More information

3.1 General Provisions

3.1 General Provisions WOOD FRAME CONSTRUCTION MANUAL 107 3.1 General Provisions 3.1.1 Prescriptive Requirements The provisions of this Chapter establish a specific set of resistance requirements for buildings meeting the scope

More information

Engineering Research into Traditional Timber Joints

Engineering Research into Traditional Timber Joints Engineering Research into Traditional Timber Joints Richard Harris, Wen- Shao Chang, Peter Walker (BRE CICM, The University of Bath) and Jon Shanks (CSAW Research Fellow, School of Architecture & Design,

More information

APA Performance Rated Rim Boards

APA Performance Rated Rim Boards D a t a F i l e APA Performance Rated Rim Boards A Rim Board is the wood component that fills the space between the sill plate and bottom plate of a wall or, in second floor construction, between the top

More information

BauBuche Fasteners and connections

BauBuche Fasteners and connections BauBuche Fasteners and connections Beech laminated veneer lumber Chapter under revision 05 BauBuche Fasteners and connections 05 04-18 - EN Sheet 1 / 10 Fasteners and connections Sheet CONTENTS 2 3 4 9

More information

ESR-2648 Reissued May 1, 2012 This report is subject to renewal June 1, 2013.

ESR-2648 Reissued May 1, 2012 This report is subject to renewal June 1, 2013. ICC-ES Evaluation Report ESR-2648 Reissued May 1, 2012 This report is subject to renewal June 1, 2013. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION:

More information

ESR-2024* Reissued September 1, 2011 This report is subject to renewal September 1, 2013.

ESR-2024* Reissued September 1, 2011 This report is subject to renewal September 1, 2013. ICC-ES Evaluation Report ESR-2024* Reissued September, 20 This report is subject to renewal September, 20. www.icc-es.org (800) 42-68 (62) 699-04 A Subsidiary of the International Code Council DIVISION:

More information

Butt Two pieces of wood meeting with flat sides adjoining usually at right angles. Some type of connector is needed to prevent movement.

Butt Two pieces of wood meeting with flat sides adjoining usually at right angles. Some type of connector is needed to prevent movement. Wood Connections There are basically five different types of connectors: Interlocking (carpentry joints), Dowel, Metal Connectors, Special Formed Connectors and Adhesives. I Interlocking (Carpentry Joints)

More information

Powder Actuated Fastening INTRODUCTION

Powder Actuated Fastening INTRODUCTION Powder Actuated Fastening INTRODUCTION Powder actuated fastening systems provide a cost effective method of attaching fixtures for light duty, static load conditions. Powers' systems consist of specially

More information

RlGIDITY AND STRENGTH OF WALL FRAMES BRACED WlTH METAL STRAPPING

RlGIDITY AND STRENGTH OF WALL FRAMES BRACED WlTH METAL STRAPPING RlGIDITY AND STRENGTH OF WALL FRAMES BRACED WlTH METAL STRAPPING information Reviewed and Reaffirmed March 1955 No. R1603 UNITED STATES DEPARTMENT OF AGRICULTURE FOREST SERVICE FOREST PRODUCTS LABORATORY

More information

FASTENERS C O M P AT I B L E W I T H F E R O T I E S Y S T E M S. Which FERO Tie Systems Require Fasteners?

FASTENERS C O M P AT I B L E W I T H F E R O T I E S Y S T E M S. Which FERO Tie Systems Require Fasteners? FASTENERS C O M P AT I B L E W I T H F E R O T I E S Y S T E M S Which FERO Tie Systems Require Fasteners? Structural Actions: Fastener,, or Both? With the exception of FERO tie systems that are directly

More information

SDWH TIMBER-HEX Screw

SDWH TIMBER-HEX Screw Simpson Strong-Tie Fastening Systems Structural Wood-to-Wood Connections, Including Ledgers Double-barrier coating provides corrosion resistance equivalent to hot-dip galvanization, making it suitable

More information

optimisation of pre-cast support beams

optimisation of pre-cast support beams optimisation of pre-cast support beams Design Optimisation of Pre-cast Support Beams Investigation into pile and beam systems for a client in the civil engineering industry with the following objectives:

More information

HOME STRENGTHENING GUIDE HOW TO ECONOMICALLY STRENGTHEN YOUR HOUSE AGAINST EARTHQUAKES AND HURRICANES

HOME STRENGTHENING GUIDE HOW TO ECONOMICALLY STRENGTHEN YOUR HOUSE AGAINST EARTHQUAKES AND HURRICANES HOME STRENGTHENING GUIDE HOW TO ECONOMICALLY STRENGTHEN YOUR HOUSE AGAINST EARTHQUAKES AND HURRICANES Grenville W Phillips II BSc, BEng, MASc, MURP, CEng, FIStructE, FCIHT, MAPM, MCSCE, MBAPE Chartered

More information

Featuring TJ Rim Board and TimberStrand LSL

Featuring TJ Rim Board and TimberStrand LSL #TJ-8000 SPECIFIER S GUIDE TRUS JOIST RIM BOARD Featuring TJ Rim Board and TimberStrand LSL Multiple thicknesses, grades, and products to cover all your rim board needs 1¼" Thickness matches lateral load

More information

European Technical Assessment. ETA-14/0426 of 15 December English translation prepared by DIBt - Original version in German language

European Technical Assessment. ETA-14/0426 of 15 December English translation prepared by DIBt - Original version in German language European Technical Assessment ETA-14/0426 of 15 December 2014 - Original version in German language General Part Technical Assessment Body issuing the European Technical Assessment: Trade name of the construction

More information

European Technical Assessment ETA-17/1005 of

European Technical Assessment ETA-17/1005 of ETA-Danmark A/S Göteborg Plads 1 DK-2150 Nordhavn Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet www.etadanmark.dk Authorised and notified according to Article 29 of the Regulation (EU) No 305/2011

More information

Bolt Material Types and Grades 1- Bolts made of carbon steel and alloy steel: 4.6, 4.8, 5.6, 5.8, 6.8, 8.8, 10.9 Nuts made of carbon steel and alloy

Bolt Material Types and Grades 1- Bolts made of carbon steel and alloy steel: 4.6, 4.8, 5.6, 5.8, 6.8, 8.8, 10.9 Nuts made of carbon steel and alloy Bolt Material Types and Grades 1- Bolts made of carbon steel and alloy steel: 4.6, 4.8, 5.6, 5.8, 6.8, 8.8, 10.9 Nuts made of carbon steel and alloy steel: 4, 5, 6, 8, 10, 12 2- Bolts made of stainless

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2761 Reissued 10/2017 This report is subject to renewal 10/2019. DIVISION: 06 00

More information

THE ENGINEERED WOOD ASSOCIATION

THE ENGINEERED WOOD ASSOCIATION D A T A F I L E APA Performance Rated Rim Boards A rim board is the wood component that fills the space between the sill plate and bottom plate of a wall or, in second floor construction, between the top

More information

CLT Cross Laminated Timber

CLT Cross Laminated Timber CLT Cross Laminated Timber Connections Date: 21.08.2014 Disclaimer The below presented structural analysis is an exemplified calculation. This calculation is solely a proposal for a design approach. This

More information

Design of structural connections for precast concrete buildings

Design of structural connections for precast concrete buildings BE2008 Encontro Nacional Betão Estrutural 2008 Guimarães 5, 6, 7 de Novembro de 2008 Design of structural connections for precast concrete buildings Björn Engström 1 ABSTRACT A proper design of structural

More information

POWDER-ACTUATED FASTENERS IN COLD-FORMED STEEL CONSTRUCTION

POWDER-ACTUATED FASTENERS IN COLD-FORMED STEEL CONSTRUCTION TECHNICAL NOTE On Cold-Formed Steel Construction $5.00 Light Gauge Steel Engineers Association Washington, D.C. Toll-Free: 1 (866) 465-4732 www.lgsea.com POWDER-ACTUATED FASTENERS IN COLD-FORMED STEEL

More information

European Technical Assessment. ETA-14/0426 of 21 December English translation prepared by DIBt - Original version in German language

European Technical Assessment. ETA-14/0426 of 21 December English translation prepared by DIBt - Original version in German language European Technical Assessment ETA-14/0426 of 21 December 2016 - Original version in German language General Part Technical Assessment Body issuing the European Technical Assessment: Trade name of the construction

More information

GARDEN SHED BRIGHTOLN

GARDEN SHED BRIGHTOLN ASSEMBLY INSTRUCTIONS GARDEN SHED BRIGHTOLN Dimensions: 10x10 (1 1/8") IMPORTANT Before beginning the assembly of your garden shed, please read the instructions carefully and follow them closely. By doing

More information

Attach Trusses and Rafters Faster

Attach Trusses and Rafters Faster Attach Trusses and Rafters Faster SDWC TRUSS Screw Truss-to-Plate Connections For Truss-to-Plate Connections The Strong-Drive SDWC TRUSS screw provides a truss- and rafter-to-top-plate connection. The

More information

Connection Philosophy. p NDS Chapter-by-chapter description Changes from previous editions Examples. Part 1: Member Design Webinar.

Connection Philosophy. p NDS Chapter-by-chapter description Changes from previous editions Examples. Part 1: Member Design Webinar. Outline ASD and LRFD with the 2005 NDS Part 2 Connection Design Presented by: John Buddy Showalter, P.E. Vice President, Technology Transfer Connection philosophy p NDS Chapter-by-chapter description Changes

More information

Please direct powder-actuated and screw fastening technical inquiries to your local Hilti Field Engineer or Technical Support at

Please direct powder-actuated and screw fastening technical inquiries to your local Hilti Field Engineer or Technical Support at Section 3.1.2.8 Screws should only be used in non-corrosive applications, regardless of their coating, unless they are specifically listed as being suitable for outdoor or exposed conditions. More detailed

More information

Joint Evaluation Report

Joint Evaluation Report 0 Joint Evaluation Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 ESR-2909 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION:

More information

ICC-ES Evaluation Report Reissued June 1, 2010 This report is subject to re-examination in one year.

ICC-ES Evaluation Report Reissued June 1, 2010 This report is subject to re-examination in one year. ICC-ES Evaluation Report ESR-2648 Reissued June 1, 2010 This report is subject to re-examination in one year. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council

More information

² TL Beton-StB 07 = German technical conditions for construction materials for concrete road pavements

² TL Beton-StB 07 = German technical conditions for construction materials for concrete road pavements Introduction A transverse joint frequently crossed by heavy goods traffic tends to form steps if it not perfectly doweled. This is associated with negative effects on ride comfort and driving safety as

More information

Verbindungselemente Engel GmbH Weltestraße Weingarten DEUTSCHLAND. Manufacturing plant 74437, , ,

Verbindungselemente Engel GmbH Weltestraße Weingarten DEUTSCHLAND. Manufacturing plant 74437, , , European Technical Assessment ETA-13/0536 of 20 February 2018 - Original version in German language General Part Technical Assessment Body issuing the European Technical Assessment: Trade name of the construction

More information

CLT Connections Design Seminar on CLT Design, including Connections, and Resistance to Lateral and Gravity Loads

CLT Connections Design Seminar on CLT Design, including Connections, and Resistance to Lateral and Gravity Loads CLT Connections Design Seminar on CLT Design, including Connections, and Resistance to Lateral and Gravity Loads Moncton, NB December 1, 2015 Overview Why connections in CLT are different from other EWP

More information

ICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in two years.

ICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in two years. ICC-ES Evaluation Report www.icc-es.org (800) -68 (6) 699-0 ESR-8* Reissued March, 0 This report is subject to renewal in two years. A Subsidiary of the International Code Council DIVISION: 0 00 00 CONCRETE

More information

Glulam Connection Details

Glulam Connection Details T E C H N I C A L N O T E Glulam Connection Details Note: This version is superseded by a more current edition. Check the current edition for updated design and application recommendations. ENGINEERED

More information

Building for High Wind Resistance in Light-Frame Wood Construction

Building for High Wind Resistance in Light-Frame Wood Construction Building for High Wind Resistance in Light-Frame Wood Construction DESIGN GUIDE Meeting the Challenge of High Wind Design Designing a structure to withstand the devastating forces of tornados is one of

More information

Cast-in Ferrule Connections Load/Displacement Characteristics in Shear

Cast-in Ferrule Connections Load/Displacement Characteristics in Shear Cast-in Ferrule Connections Load/Displacement Characteristics in Shear Ian Ferrier 1 and Andrew Barraclough 2 1 Product Manager - Connections, ITW Construction Systems ANZ. 2 Research and Development Manager,

More information

ESR-1254 * DELETED BY CITY OF LOS ANGELES. Reissued April 1, 2006 This report is subject to re-examination in one year.

ESR-1254 * DELETED BY CITY OF LOS ANGELES.   Reissued April 1, 2006 This report is subject to re-examination in one year. ESR-1254 Reissued April 1, 2006 This report is subject to re-examination in one year. www.icc-es.org Business/Regional Office 5360 Workman Mill Road, Whittier, California 90601 (562) 699-0543 Regional

More information

Designed for Building Designed for Living

Designed for Building Designed for Living Designed for Building Designed for iving decorative hardware Add Beauty and Strength to Your Custom Outdoor iving Structures ith Outdoor Accents, a new line of decorative timber connectors and fasteners

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC AND COMPOSITE FASTENINGS REPORT HOLDER: DEWALT

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC AND COMPOSITE FASTENINGS REPORT HOLDER: DEWALT 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3164 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 06 00

More information

Connection Design Examples

Connection Design Examples Connection Design Examples Using the 2015 NDS (DES345) Lori Koch, P.E. Manager, Educational Outreach American Wood Council Adam Robertson, M.A.Sc., P.Eng. Manager, Codes and Standards Canadian Wood Council

More information

WITHDRAWAL AND LATERAL STRENGTH OF THREADED NAILS

WITHDRAWAL AND LATERAL STRENGTH OF THREADED NAILS 238 WITHDRAWAL AND LATERAL STRENGTH OF THREADED NAILS Douglas R. Rammer, Donald A. Bender, and David G. Pollock An experimental study on the performance of threaded nails was conducted to understand and

More information

VERSA-LAM. An Introduction to VERSA-LAM Products

VERSA-LAM. An Introduction to VERSA-LAM Products 44 VERSA-LAM An Introduction to VERSA-LAM Products VERSA-LAM is one of the strongest and stiffest engineered wood products approved in the UK. 241 302 356 406 VERSA-LAM products are excellent as floor

More information

Overdriven Nails in Structural Sheathings. Overview Revised 3/22/2017

Overdriven Nails in Structural Sheathings. Overview Revised 3/22/2017 Overdriven Nails in Structural Sheathings Overview Revised 3/22/2017 SBCA has been the voice of the structural building components industry since 1983, providing educational programs and technical information,

More information

Design guide to separating distances during construction

Design guide to separating distances during construction Design guide to separating distances during construction For timber frame buildings and projects above 600m 2 total floor area Part 2 - Standard timber frame and construction process mitigation methods

More information

European Technical Assessment ETA-13/0029 of 11/07/2017

European Technical Assessment ETA-13/0029 of 11/07/2017 ETA-Danmark A/S Göteborg Plads 1 DK-2150 Nordhavn Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet www.etadanmark.dk Authorised and notified according to Article 29 of the Regulation (EU) No 305/2011

More information

Investigations on the Effectiveness of Self-tapping Screws in Reinforcing Bolted Timber Connections

Investigations on the Effectiveness of Self-tapping Screws in Reinforcing Bolted Timber Connections Investigations on the Effectiveness of Self-tapping Screws in Reinforcing Bolted Timber Connections Mohammad Mohammad Group Leader, Building Systems Forintek Canada Corp, Eastern Division Quebec, Canada

More information

ICC-ES Evaluation Report

ICC-ES Evaluation Report ICC-ES Evaluation Report ESR-6 Reissued April, 009 This report is subject to re-examination in two years. www.icc-es.org (800) 4-6587 (56) 699-054 A Subsidiary of the International Code Council DIVISION:

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 42 687 (62) 699 04 www.icc es.org ESR 2442 Reissued 0/208 This report is subject to renewal 0/209. DIVISION: 06 00 00 WOOD,

More information

Connection Solutions for Wood-frame Structures. Copyright Materials. Learning Objectives

Connection Solutions for Wood-frame Structures. Copyright Materials. Learning Objectives Connection Solutions for Wood-frame Structures Presented by: John Buddy Showalter, P.E. Vice President, Technology Transfer The Wood Products Council is a Registered Provider with. Credit(s) earned on

More information

Load Tables, Technical Data and Installation Instructions

Load Tables, Technical Data and Installation Instructions W22. W22. W22. W22. W22 W22.. Simpson Strong-Tie Fastening Systems Structural Wood-to-Wood Connections Including Ledgers Designed to provide an easy-to-install, high-strength alternative to through-bolting

More information

+ + CFA Guidance Note: Powder Actuated Fixing Systems. Ensuring best fixings practice. Contents. 1.

+ + CFA Guidance Note: Powder Actuated Fixing Systems. Ensuring best fixings practice. Contents.   1. Ensuring best fixings practice www.the-cfa.co.uk CFA Guidance Note: Powder Actuated Fixing Systems Note: The guidance given in this Guidance Note is provided in good faith but the CFA cannot accept any

More information

Umbrella Inserts and Stubby Screens

Umbrella Inserts and Stubby Screens ADHESIVE ANCHORING SPECIALISTS Umbrella Inserts and High Performance Adhesive Systems for Fastening to Hollow Base Materials DESCRIPTION/ADVANTAGES Hollow Block Fastening with A7+ Adhesive Umbrella Inserts

More information

ICC-ES Evaluation Report

ICC-ES Evaluation Report ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-2608 Reissued January 2016 This report is subject to renewal January 2017. A Subsidiary of the International Code Council DIVISION:

More information

Dowel type joints Influence of moisture changes and dowel surface smoothness. Erik Serrano and Johan Sjödin, Växjö University, Sweden

Dowel type joints Influence of moisture changes and dowel surface smoothness. Erik Serrano and Johan Sjödin, Växjö University, Sweden Dowel type joints Influence of moisture changes and dowel surface smoothness Erik Serrano and Johan Sjödin, Växjö University, Sweden Background and introduction With the increased use of glulam in large-span

More information

Load carrying capacity of dowelled connections

Load carrying capacity of dowelled connections Load carrying capacity of dowelled connections H.J. Blass, Karlsruhe Institute of Technology F. Colling, Augsburg University of Applied Sciences Keywords: Dowel, yield moment, connection 1 Introduction

More information

Optimast Installation Method Statement. F108.

Optimast Installation Method Statement. F108. Optimast Installation Method Statement. F108. Contents Page 1) Product Description. 2) Durability....... 3) Profile & Baseplate..... 4) Anchor Cradle and Foundation Stud Set Detail Drawings 4a) 127...

More information

TEST SERIES TO EVALUATE THE STRUCTURAL BEHAVIOUR OF ISOBOARD OVER RAFTER SYSTEM

TEST SERIES TO EVALUATE THE STRUCTURAL BEHAVIOUR OF ISOBOARD OVER RAFTER SYSTEM TEST SERIES TO EVALUATE THE STRUCTURAL BEHAVIOUR OF ISOBOARD OVER RAFTER SYSTEM J A Wium Institute of Structural Engineering 19 November 2007 ISI2007-3 TEST SERIES TO EVALUATE THE STRUCTURAL BEHAVIOUR

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2442 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 06 00

More information

Dowel connections in laminated strand lumber

Dowel connections in laminated strand lumber Dowel connections in laminated strand lumber Cranswick, Chad J. 1, M c Gregor, Stuart I. 2 ABSTRACT Laminated strand lumber (LSL) is a relatively new structural composite lumber. As such, very limited

More information

HUS 6 Screw anchor, Redundant fastening

HUS 6 Screw anchor, Redundant fastening HUS 6 Screw anchor, Anchor version HUS-A 6 Carbon steel Concrete Screw with hex head HUS-H 6 Carbon steel Concrete Screw with hex head HUS-I 6 Carbon steel Concrete Screw with hex head Benefits - Quick

More information

Tension Perpendicular to Grain Strength of Wood, Laminated Veneer Lumber, and a Wood Plastic Composite.

Tension Perpendicular to Grain Strength of Wood, Laminated Veneer Lumber, and a Wood Plastic Composite. Tension Perpendicular to Grain Strength of Wood, Laminated Veneer Lumber, and a Wood Plastic Composite. Tracy Hummer, Research Assistant J. Daniel Dolan, Professor Michael Wolcott, Professor Wood Materials

More information

Shear force transmission in expansion joints

Shear force transmission in expansion joints for better solutions Shear dowel Shear force transmission in expansion joints Reliable expansion joint dowelling in concrete structural elements General Single shear dowel HED Expansion joint dowelling

More information

The Wood Products Council is a Registered Provider with. . Credit(s) earned on completion of this program will be

The Wood Products Council is a Registered Provider with. . Credit(s) earned on completion of this program will be Connection Solutions for Wood-frame Structures Presented by: John Buddy Showalter, P.E. Vice President, Technology Transfer The Wood Products Council is a Registered Provider with. Credit(s) earned on

More information

LP SolidStart Laminated Strand Lumber and Laminated Veneer Lumber Louisiana-Pacific Corporation Revised May 6, 2011

LP SolidStart Laminated Strand Lumber and Laminated Veneer Lumber Louisiana-Pacific Corporation Revised May 6, 2011 LP SolidStart Laminated Strand Lumber and Laminated Veneer Lumber PR-L280 Louisiana-Pacific Corporation Revised May 6, 2011 Products: LP SolidStart 1.35E, 1.55E, and 1.75E LSL LP SolidStart 1750F b -1.3E

More information

Connection and performance of two-way CLT plates

Connection and performance of two-way CLT plates Connection and performance of two-way CLT plates by Chao (Tom) Zhang George Lee Dr. Frank Lam Prepared for Forestry Innovation Investment 1130 W Pender St, Vancouver BC V6E 4A4 Timber Engineering and Applied

More information

Tensile strength of ASSY plus VG screws wood-wood (softwood)

Tensile strength of ASSY plus VG screws wood-wood (softwood) Tensile strength of ASSY plus VG screws wood-wood (softwood) STRENGTHENS THE WOOD - INSTEAD OF SPLITTING IT 23.05.2017 Table of contents for tensile strength Determining the tensile strength - Table values

More information

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2024 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 03 00

More information

ESR-2403 Reissued October 1, 2009 This report is subject to re-examination in one year.

ESR-2403 Reissued October 1, 2009 This report is subject to re-examination in one year. ICC-ES Evaluation Report ESR-403 Reissued October, 009 This report is subject to re-examination in one year. www.icc-es.org (800) 43-6587 (56) 699-0543 A Subsidiary of the International Code Council DIVISION:

More information

ICC-ES Evaluation Report Reissued June 1, 2011 This report is subject to renewal in one year.

ICC-ES Evaluation Report Reissued June 1, 2011 This report is subject to renewal in one year. ICC-ES Evaluation Report www.icc-es.org (800) 42-658 (562) 699-054 ESR-99* Reissued June, 20 This report is subject to renewal in one year. A Subsidiary of the International Code Council DIVISION: 0 00

More information

SECTION R507 DECKS DECKING LEDGER BOARD BEAM. FOOTING BEAM SPAN CANTILEVER For SI: 1 inch = 25.4 mm FIGURE R507.2 DECK CONSTRUCTION

SECTION R507 DECKS DECKING LEDGER BOARD BEAM. FOOTING BEAM SPAN CANTILEVER For SI: 1 inch = 25.4 mm FIGURE R507.2 DECK CONSTRUCTION SECTION R507 DECKS R507.1 Application. The provisions of this section shall provide prescriptive requirements for the design and construction of all uncovered, wood-framed, single-span exterior decks.

More information

American Institute of Timber Construction 7012 South Revere Parkway Suite 140 Centennial, CO Phone: 303/ Fax: 303/

American Institute of Timber Construction 7012 South Revere Parkway Suite 140 Centennial, CO Phone: 303/ Fax: 303/ American Institute of Timber Construction 7012 South Revere Parkway Suite 140 Centennial, CO 80112 Phone: 303/792-9559 Fax: 303/792-0669 404.1. SCOPE STANDARD FOR RADIALLY REINFORCING CURVED GLUED LAMINATED

More information

European Technical Assessment ETA-04/0038 English translation prepared by DIBt. Page 2 of July 2016

European Technical Assessment ETA-04/0038 English translation prepared by DIBt. Page 2 of July 2016 European Technical Assessment ETA-04/0038 Page 2 of 15 29 July 2016 The European Technical Assessment is issued by the Technical Assessment Body in its official language. Translations of this European

More information

EVALUATION OF SCREWS USED IN LAMINATED VENEER LUMBER ROCKING CONNECTIONS

EVALUATION OF SCREWS USED IN LAMINATED VENEER LUMBER ROCKING CONNECTIONS EVALUATION OF SCREWS USED IN LAMINATED VENEER LUMBER ROCKING CONNECTIONS D. M. Carradine, M. P. Newcombe and A. H. Buchanan Dept. of Civil and Natural Resources Engineering, University of Canterbury, Private

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: SCREW PRODUCTS, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: SCREW PRODUCTS, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3654 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 06 00

More information

HK I. Anchor size (carbon steel) HK6 HK6L HK8 Resistance F Rk [kn] 2,0 5,0 5,0

HK I. Anchor size (carbon steel) HK6 HK6L HK8 Resistance F Rk [kn] 2,0 5,0 5,0 HK HK I Anchor version Benefits - well proven - small drill bit diameter - for fixing in cracked concrete, redundant fastening only, e.g. suspended ceilings a ) Redundant fastening only Approvals / certificates

More information

Canadian li ing device design for Cross Laminated Timber (CLT)

Canadian li ing device design for Cross Laminated Timber (CLT) Canadian li ing device design for Cross Laminated Timber (CLT) For detailed informa on please visit our web site www.my-!-con.com Contact: email: sales@my- -con.com Phone - Western Canada: 604-349-8426

More information

Wood Duck Nest Box Design & Assembly Directions

Wood Duck Nest Box Design & Assembly Directions Wood Duck Nest Box Design & Assembly Directions Instructions, Illustrations & Photos Courtesy of MWDI and Scott Jasion, Harford County Chapter, Ducks Unlimited Side door opening design for easy mounting

More information

Independent Containment System (ICS)

Independent Containment System (ICS) Installing the Independent Containment System (ICS) Complete these instructions to install the Independent Containment System (ICS). Prerequisites This installation requires a team of at least two people.

More information

Tech Guide. Screw Anchor Performance Why use a screw anchor? Ease in installation

Tech Guide. Screw Anchor Performance Why use a screw anchor? Ease in installation Why use a screw anchor? Screw anchors are used in medium duty applications that normally require faster installation time, close concrete edge distance, close anchor spacing and removability of anchor.

More information

eb^sv=qfj_bo UNIVERSITY OF WISCONSIN - STOUT COLLEGE OF SCIENCE TECHNOLOGY ENGINEERING & MATHEMATICS Architectural Technology AEC 233

eb^sv=qfj_bo UNIVERSITY OF WISCONSIN - STOUT COLLEGE OF SCIENCE TECHNOLOGY ENGINEERING & MATHEMATICS Architectural Technology AEC 233 eb^sv=qfj_bo UNIVERSITY OF WISCONSIN - STOUT COLLEGE OF SCIENCE TECHNOLOGY ENGINEERING & MATHEMATICS Architectural Technology AEC 233 Dr. Jason E. Charalambides fkqolar`qflk Heavy timber construction consists

More information

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 42 6587 (562) 699 054 www.icc es.org ESR 279 Reissued 08/2018 This report is subject to renewal 08/2020. DIVISION: 0 00 00 CONCRETE

More information

Glued laminated timber beams repair.

Glued laminated timber beams repair. Glued laminated timber beams repair. Master s Degree Extended Abstract Ricardo Cardoso Henriques da Silva Keywords: glulam, delamination, self-tapping screw, plywood, repair November 2014 1. INTRODUCTION

More information

ESR-1799 Reissued April 2014 This report is subject to renewal June 1, 2015.

ESR-1799 Reissued April 2014 This report is subject to renewal June 1, 2015. ICC-ES Evaluation Report www.icc-es.org (800) 42-6587 (562) 699-054 ESR-799 Reissued April 204 This report is subject to renewal June, 205. A Subsidiary of the International Code Council DIVISION: 0 00

More information

Guidance Document January 2014

Guidance Document January 2014 Guidance Document January 2014 FIXINGS AND FASTENERS FOR RAINSCREEN SYSTEMS INTRODUCTION Every rainscreen or rear vented facade system is an arrangement of various layers interconnected to each other to

More information

GLOSSARY OF TERMS SECTION 8

GLOSSARY OF TERMS SECTION 8 GLOSSARY OF TERMS SECTION 8 Anchor Bolt Angle Base Plate Bay Blocking CCB Centerline Chord Cladding Clip Closure Strip An A-307 steel bolt embedded in the concrete footing to anchor the base plate of the

More information

Ready To Go SimpleSpec tm. Installation Manual. For more information, please visit 3-form.com or call

Ready To Go SimpleSpec tm. Installation Manual. For more information, please visit 3-form.com or call Contents Overview ( 1) 3/8" Varia Panel = Cable Tensioner with Cover Plate KIT Stainless Steel: 3-15-1636-K Black Oxide: 3-15-2005-K Cable Tensioner with Cover Plate SS: 3-15-1636 BO: 3-15-2005 + M8 Thread

More information

Load-carrying capacity of timber frame diaphragms with unidirectional support

Load-carrying capacity of timber frame diaphragms with unidirectional support Load-carrying capacity of timber frame diaphragms with unidirectional support Jørgen Munch-Andersen, Danish Timber Information, 2012-06-26 Introduction The rules for determining the load-carrying capacity

More information

Available online at ScienceDirect. Procedia Engineering 114 (2015 )

Available online at  ScienceDirect. Procedia Engineering 114 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 114 (2015 ) 240 247 1st International Conference on Structural Integrity Dowel type joints of round timber exposed to static

More information

Comparison of behaviour of laterally loaded round and squared timber bolted joints

Comparison of behaviour of laterally loaded round and squared timber bolted joints Focussed on Modelling in Mechanics Comparison of behaviour of laterally loaded round and squared timber bolted joints Antonín Lokaj, Kristýna Klajmonová VŠB echnical University of Ostrava, Faculty of Civil

More information

European Technical Approval ETA-10/0038

European Technical Approval ETA-10/0038 ETA-Danmark A/S Kollegievej 6 DK-2920 Charlottenlund Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet www.etadanmark.dk Authorised and notified according to Article 10 of the Council Directive 89/106/EEC

More information