1 ELEC9713 Industrial and Commercial Power Systems CABLES AND BUSBAR SYSTEMS 1. Introduction Electrical power distribution in buildings and industrial sites is achieved primarily by use of cables or busbars. Cables are used for the full range of current levels at low (400/230V) and high voltage (3.3, 6.6 and 11kV). Busbars are mostly used for the very high range of current carrying capacity, usually at medium/low voltage (400/230V). In addition to simple electrical energy supply, cables are also extensively used for control and communications functions in building and industrial sites. The choice of cable voltage for purely electrical energy supply depends on the size of the building or industrial site. Most mains installations will have cable systems operating at 400/230V and busbar systems will also operate at 400/230V. For extensive sites or for large loads the cables may be high voltage, at 11kV in modern sites or at 6.6 or 3.3kV in older sites (mainly industrial). Other types of cable may be used in some more sensitive areas: for example mineral insulated metal sheathed cable (MIMS - Pyrotenax) where fire resistance is required, or simply fire resistant cable which uses mica tape sheaths over the conductor and under the main insulation. ELEC9713: Industrial and Commercial Power Systems p. 1

2 2. Cable structure The cables used may be either multicore or single core in structure (see Figures 1 and 2). At low voltage, single core cables consist of a single conductor (usually stranded copper or aluminium) with a main insulation layer of any of PVC (polyvinyl chloride), XLPE (cross linked polyethylene) or EPR (ethylene propylene rubber). In addition, there is usually an outer sheath of PVC or HDPE (high density polyethylene) or HEPR (hard ethylene propylene rubber) to provide some mechanical protection. As mentioned above, for sites where a high level of fire resistance is required, copper clad mineral insulated metal sheathed (MIMS or Pyrotenax ) cable may be used or other fire resistant cables of the mica-glass taped type. At higher voltage the cables may be oil or mass impregnated paper insulation if the installation is relatively old (more than about 20 years), but will be XLPE or EPR in modem installations, except in high voltage DC applications where paper insulation is still best. PVC is not used at voltages higher than 400V because of its high loss factor (DDF) which generates too much dielectric heat loss above 400V. XLPE and EPR, which do not soften as their temperature increases are examples of thermosetting synthetic insulating materials. They are vulcanized to improve their temperature withstand ability. XLPE is a very good high voltage insulant in that it has very low DDF losses and a high withstand voltage. ELEC9713: Industrial and Commercial Power Systems p. 2

3 PVC is an example of the thermoplastic class of synthetic insulation. These materials soften as their temperature increases but regain their original form (but not necessarily their shape) when they cool. Paper insulation is a natural cellulosic fibre which is used in cables with the paper impregnated by a hydrocarbon oil or thick grease type compound. Although the paper in oil composite is a very good insulator, it has some drawbacks in that the cable joints and terminations are much more difficult to make and they must have a metal outer sheath to contain the oil. Multicore cables at low voltage usually have four conductors with three phases and a neutral. They may be either stranded copper or aluminium or, more often, solid section aluminium. The conductors are often sector shaped to give a better packing density in the overall structure. At high voltage the cables will be paper insulated if older style or XLPE or EPR in modern cables. The higher voltage cables will be 3-core, with three main phase conductors and an outer metal sheath as the neutral of earth. EPR insulation is much more flexible than XLPE and is used more often in locations requiring high cable flexibility, such as for trailing cables in underground mines and similar applications. Figures 1 and 2 show some examples of typical cable designs and configurations. ELEC9713: Industrial and Commercial Power Systems p. 3

4 Fig.1: single-core, multi-core. ELEC9713: Industrial and Commercial Power Systems p. 4

5 Figure 2: Examples of LV and HV cables ELEC9713: Industrial and Commercial Power Systems p. 5

6 3. Requirements of cable system designs There are some general installation requirements for power cable systems, in addition to the primary selection considerations of rating and voltage. These secondary installation requirements include: Separation of power and control/communication cabling systems to prevent induced interference Protection of cables from physical damage Use of additional cable ducts to allow for future expansion Care in the preparation of joints to prevent high contact resistance or low insulation levels The major considerations to be applied in the selection of cables or busbar systems are: The current carrying capacity [determined by the maximum permissible steady state temperature rise]. The voltage drop and regulation of the cable/busbar circuit at full load The short circuit rating [determined by the maximum permissible transient temperature rise with fault current] The insulation requirements and associated factors [jointing and termination: the cable accessories]. The required level of fire resistance of the cable and busbar systems. ELEC9713: Industrial and Commercial Power Systems p. 6

7 3.1 Current carrying capacity: [the thermal rating] This is an important criterion in selection. The temperature of the insulation of the cable or busbar system must be kept below well-defined values to limit the ageing of the cable insulation. For this reason an accurate determination of the current capacity is necessary to ensure that the temperature will remain within allowable limits and thus not cause accelerated ageing. In general, a 10 o C increase in the continuous operating temperature would halve the insulation life. Figure 3 show the limiting temperatures for various types of insulated cables. Fig. 3: Limiting temperatures for insulated cables (Table 1 AS ) ELEC9713: Industrial and Commercial Power Systems p. 7

8 This rating determination must be done for all cables and conductors. For some circuits there is no need to perform detailed calculations as there are specific requirements laid down by regulations for specified cable sizes in various situations. For example, the minimum rating for consumers mains cables is 32A and for sub-mains cables it is 25A. However, above this minimum level the ratings must be calculated with reasonable accuracy. The calculation is complicated by a number of variable parameters which may have a significant effect on the capacity. These parameters include the ambient temperature, the enclosure of the cable (if any), bundling of multiple cables etc. It is usual, and sufficiently accurate in most cases, to use the tables which are given in the Australian Standards AS3000 (The Wiring Rules) and in standard AS3008.1, an accompanying standard to AS3000, to determine the current rating capacity. Tables 3-21 of AS give ratings for a variety of cable types and enclosures that cover most usual applications. Figures 4-9 are some typical examples. In the calculations the maximum load demand figures must be used as the basis for cable size determination and some allowance should be made for future expansion, de-rating from mutual heating of bundled cables, any effects of harmonics and frequency of current. Special attention must also be given to the current carrying capacity of the neutral conductor. This is often of smaller cross-section than phase conductors and this can sometimes lead to problems if there are out of balance loads, but particularly if the load is non- ELEC9713: Industrial and Commercial Power Systems p. 8

9 linear and generates triplen harmonic currents. These 3- phase triplen harmonic currents do not cancel in the neutral but superimpose because of their phase relationship and may overload the neutral conductor. Fig.4: Current-carrying capacity (Table 3 AS3008.1) ELEC9713: Industrial and Commercial Power Systems p. 9

10 Fig.5: Current-carrying capacity (Table 4 AS3008.1) ELEC9713: Industrial and Commercial Power Systems p. 10

11 Fig.6: Current-carrying capacity (Table 9 AS3008.1) ELEC9713: Industrial and Commercial Power Systems p. 11

12 Fig.7: Current-carrying capacity (Table 12 AS3008.1) ELEC9713: Industrial and Commercial Power Systems p. 12

13 Fig.8: Current-carrying capacity (Table 15 AS3008.1) Fig.9: Current-carrying capacity (Table 16 AS3008.1) ELEC9713: Industrial and Commercial Power Systems p. 13

14 3.2 External influences on cable capacity The current-carrying capacity of a cable can be affected by external influences such as: Grouping of cables Ambient temperature Depth of laying Thermal resistivity of soil Varying load conditions Effect of thermal insulation Effect of direct sunlight Thus capacity values given in Tables 3-21 of AS should be corrected by applying an appropriate rating factor. A common situation is the grouping of cables in close proximity such that they are not independently cooled by the ambient air or ground. The appropriate de-rating factors are given in Tables 22 to 26 of the Standard. Fig.10: Cable grouping derating (Table 22 AS3008.1) ELEC9713: Industrial and Commercial Power Systems p. 14

15 Fig.11: Cable grouping de-rating (Table 23 AS3008.1) The current-carrying capacity specified in Tables 3 to 21 of AS is based on an ambient air temperature of 40 o C and soil temperature of 25 o C. If the ambient temperature varies from this standard, the cable capacity needs to be ELEC9713: Industrial and Commercial Power Systems p. 15

16 adjusted using the rating factors given in Table 27 of the Standard (see Figure 12 below). Fig.12: Rating factors for variation in ambient temperature (Table 27 AS ) When calculating voltage drop along a cable the cable conductor resistance is an important factor that be know accurately. However it is dependent on the conductor temperature, so that if the cable current is lower than the maximum rated value (as is likely in most cases), it is necessary to calculate the conductor operating temperature to obtain accurate R values for voltage drop, using R = R 20 [1 + α(θ 0 20) ELEC9713: Industrial and Commercial Power Systems p. 16

17 Where R 20 is the resistance at 20 0 C, α is the temperature coefficient of resistance and θ 0 is the actual operating temperature of the cable conductor. For operating current (I o ) which is different to rated current (I R ), the conductor temperature can be calculated using the equation: 2 I o θo θ A = I R θr θ A where: I o = operating current I R = rated current given in Tables 3-21 θ o = operating temperature of cable θ R = rated operating temperature of cable θ A = ambient air or soil temperature The inductive reactance X of the cable is not temperature dependent. 3.3 Voltage drop and regulation The Wiring Rules have quite specific requirements for minimum voltage drop levels in consumers' circuits. They allow for a maximum of only 5% voltage drop between the consumers terminals (where supply is taken from the utility) and the load end of the longest sub-circuit in the building. Thus, if the supply is at the nominal value of 230V, the minimum permissible voltage anywhere in the ELEC9713: Industrial and Commercial Power Systems p. 17

18 consumer's circuit is 218.5V. This is roughly the general lower limit at which most 240V equipment will still operate satisfactorily. There is also a general upper limit of voltage rise of 5% above the supply level. This may occur if some highly capacitive loads are in use Allocation of voltage drop in consumer's circuits For a building distribution system, the typical allocation of voltage drop would be as follows: Consumers mains wiring connections: % Consumers sub-mains wiring connections: % Consumers final sub-circuit connections: 2-3 % The designer must choose and design for allocations from the bands such as to give a total of no more than 5% voltage drop at maximum demand loading. The actual voltage drop (V d ) can be calculated from: L I Vc Vd = volts 1000 where: L = cable length (m) I = current carried by cable (A) V c = unit of voltage drop (mv/a.m) For a single-phase, two-wire supply system, if using the same conductor type for the active and neutral: 2 L I V Vd 1 φ = 1000 c ELEC9713: Industrial and Commercial Power Systems p. 18

19 For a balanced three-phase supply system, no current flows in the neutral. The voltage drop per phase to neutral is voltage drop in one conductor and the voltage drop between phases is therefore: Thus: 3 L I V Vd 3 φ = 1000 c 1φ voltage drop = x 3φ voltage drop 3φ voltage drop = x 1φ voltage drop Tables of AS provide 3φ voltage drop values for various cable configurations, types, conductor size and operating temperatures. If we know cable impedance (Tables of AS3008.1) and the load power factor, the voltage drop can be estimated accurately from: Single-phase: Vd1 φ = 2IL( Rccosθ ± Xcsinθ ) Three-phase: V = IL( R ± X ) d3φ 3 ccosθ csinθ Note that the voltage drop will depend on the following factors: power factor, current level, cable or conductor resistance, temperature effect on resistance inductive reactance, length. ELEC9713: Industrial and Commercial Power Systems p. 19

20 Fig.13: three-phase voltage drop (Table 41 AS3008.1) ELEC9713: Industrial and Commercial Power Systems p. 20

21 Fig.14: three-phase voltage drop (Table 42 AS3008.1) For unbalanced 3φ circuits, voltage drop calculations can be performed on a 1φ basis by geometrically summing the voltage drop in the heaviest loaded phase and the voltage drop in the neutral conductor. Another approach would be to assume balanced 3φ load conditions and perform calculations using the current flowing in the heaviest loaded phase. ELEC9713: Industrial and Commercial Power Systems p. 21

22 Fig.15: three-phase voltage drop (Table 47 AS3008.1) Power factor correction In some cases of low factor loads (less than about 0.9) it may be necessary (to satisfy utility requirements) to install power factor correction equipment to limit current and hence voltage drop. It will also decrease the cost of the supply utility charge for power in most cases. ELEC9713: Industrial and Commercial Power Systems p. 22

23 As most low power factors are lagging (inductive) loads, power factor correction is achieved by installation of compensating power capacitors used to generate leading reactive power. The capacitors may be either series connected or, most commonly in buildings and industry, shunt connected. Installation of power factor correction equipment must be done carefully to avoid the potential effects of harmonic currents caused by non-linear loads. These effects may be amplified by the decrease in net impedance at the harmonic frequencies caused by the reactive power reduction in the circuit. It may be necessary to install filters to avoid such effects. 3.4 Short Circuit Temperature Rise Depending on the insulation material in use with the cables or busbar systems, the permissible temperatures of cables and busbars under short circuit conditions are different and thus a cable will have different continuous (thermal) rating temperature and short circuit temperature limits. Depending on the insulation type used these temperature limits will vary from cable to cable. The permissible temperatures are higher for short circuits on the basis that the duration of the short circuit is typically only about 1-3 seconds before protection operates. For this period of time there will be little deterioration of the cable ELEC9713: Industrial and Commercial Power Systems p. 23

24 material. The choice of maximum short circuit temperature is more likely to be based on softening or mechanical effects rather than pure insulation damage. The maximum permissible short-circuit temperatures (for duration up to 5 seconds) are detailed in Tables of AS ELEC9713: Industrial and Commercial Power Systems p. 24

25 Fig.16: Maximum permissible short-circuit temperatures. The short circuit heating formula is derived from the more general equation which covers adiabatic heating of the cable during the short duration of the transient short circuit. This equation incorporates the temperatures of the ambient medium and the insulation temperature of the cable at the instant that the short circuit occurs. It also includes constants which incorporate properties of the conductor materials. The equation that is used is given below and 2 simply provides a maximum Itvalue relating to the cable type and temperature conditions and limitations. It includes the non-linear effect of resistance increase of the conductor as the temperature rises: It= KS where: I = short-circuit current (rms over duration), in amps t = duration of short circuit, in seconds S = cross-section area of conductor, in (mm) 2 ELEC9713: Industrial and Commercial Power Systems p. 25

26 K ( 1 20) ln ( 1 ) ( 1 ) = δ c α + ρ α + θ α + θ c = specific heat of the conductor material ρ 20 = electrical resistivity of conductor at 20 o C δ = conductor material density θ 0, θ 1 = initial and final temperatures α = temperature coefficient of resistance Values for the constant K can also be readily obtained from Table 51 of AS Fig.17: Table 51 AS The maximum phase conductor temperature on short circuit is often taken as 120 o C. However it may also be that other conductors are also limiting factors. Thus, copper wire or ELEC9713: Industrial and Commercial Power Systems p. 26

27 tape screens have a limiting temperature of 350 o C, lead sheath of 200 o C and aluminium sheath of 200 o C. And in some cases these may be the limiting factor if the return fault current passes through the sheath, say, which may have a higher resistance that the main conductor and thus generate mare heating. For some multicore cables, it may be electrodynamic forces between the phase conductors rather than thermal constraints that determine the short current rating of such a cable. In such cases, a current limitation of the fault level by HRC fuse rather than an I 2 t limitation is required. 3.5 Insulation Effects The particular type and thickness of insulation of cables and conductors will depend on the voltage of operation and also on the application. For modern high voltage distribution systems, XLPE is almost exclusively used. For low voltage applications, there are many insulation types in use. These include: PVC XLPE Elastomeric (ethylene propylene rubber [EPR]) Mineral insulated (MIMS) ELEC9713: Industrial and Commercial Power Systems p. 27

28 Other factors that need to be considered in the insulation choice are flexibility, hardness, resistance to mechanical effects, effects of moisture and contamination etc. A major factor in the choice of insulation used is the effects of fire on the cable insulation. 3.6 Fire behaviour There are many problems generated by the potential damage to cables which are involved in fires. The fires may be either self-generated, by the cable, or externallygenerated but causing significant damage to the cable insulation. The problems that arise are: 1. The cables may provide substantial flammable material in the chemical structure of their insulation 2. They generate significant smoke and soot when they burn and this can cause considerable damage to equipment otherwise unaffected by the fire heat. 3. Many of the fire products from insulation combustion are toxic and thus represent a significant health hazard. 4. Many products of the insulation combustion are corrosive and can substantially damage electronic equipment for example. 5. The cables should ideally be able to operate after significant damage by a fire: however this is not possible if the polymeric insulation burns away: there may be total loss of insulation integrity in this case. ELEC9713: Industrial and Commercial Power Systems p. 28

29 The last problem is a particularly important consideration in buildings where power may be required during and after a fire to operate emergency equipment. Thus there is a requirement for fire-resistant cables in buildings and many circuits within a building, particularly high rise buildings, will be designated to have such cabling installed. Item 4 above is an increasingly important aspect because of the large penetration of computers and general electronic and communications equipment in modem commercial buildings. The major problem in this situation is with PVC which generates very large amounts of hydrogen chloride gas when it burns and this can cause havoc with metal in electrical and electronic circuits, particularly when moisture resulting from fire hose and extinguisher use is present. The HCl is also very injurious to health. The response to this problem has been the development of a range of cables able to withstand the effects of fires or able to maintain insulation integrity after a fire. These will be outlined in the next section. In some cases, PVC has been banned for use in buildings and similar areas for general distribution. 4 Cable Types in Use The cable types in use in the overall building supply context are: ELEC9713: Industrial and Commercial Power Systems p. 29

30 4.1 Aerial cables or lines These are used between buildings in site complexes or as service lines to buildings. The bare lines with no insulation covering use aluminium or copper or (less likely for buildings) ACSR (Aluminium conductor with steel reinforcement). The insulated overhead cables (which may be either aerial bundled cables (ABC) or simply covered conductors) are installed as either an aerial service line type of application or in some case are mounted on the side fascia of buildings. The insulation may be PVC or some other material which has been treated to be able to withstand the effects of UV radiation. UV radiation from sunlight causes degradation of insulation and is the primary problem with polymeric insulation when used outdoors. ABC can be high voltage (up to 11kV) but the simple covered conductors are always low voltage cables. 4.2 Indoor distribution cables For main circuits these may be either single core or 3-core or 4-core. The insulation may be paper (unlikely in new installations) or XLPE, PVC, elastomer (EPR) etc. at low and medium voltage. The multi-core conductor types may be stranded cores, sector cores, with or without neutral or armour. Typically they will have PVC or PE outer sheathing for protection. ELEC9713: Industrial and Commercial Power Systems p. 30

31 4.3 Fire Resistant cables Fire resistant cables are required in specific situations where emergency supply needs to be maintained even in the event of severe fire interaction with the cable. Such cables need to be able to supply power up to two hours after being engulfed in conflagrations. Some common types of such fire resistant cables are described below: MIMS Mineral insulated metal sheathed. Single or multi core. The insulant is magnesium oxide powder. There is an outer copper sheath. The powder is not as good an electrical insulant as the normal cable polymeric materials but is able to withstand extreme fire temperatures ( o C) without any damage. Sealing of the metal sheath must be done carefully to prevent moisture ingress as this will destroy the insulation integrity of the powder Radox This has a glass-mica tape layer wound over the insulation. The insulation is a polyolefin material and is halogen-free to prevent the production of chemically active and toxic halogen based by-products from the fire Firestop This has a mica glass tape wound over the conductor. The insulation is XLPE. Firestop uses halogen-free insulation. ELEC9713: Industrial and Commercial Power Systems p. 31

32 Fire resistant cables must be tested to resist the effects of fires. This is particularly the case with the last two types where there is substantial loss of polymer in the fire, leaving only the mica glass tape as the insulant. The test involves exposure to fire at about 1000 o C for three hours with the cores live. No short circuits can occur. This is followed by removal from the oven and subjecting the burnt cables to a water spray test to simulate the effect of fire extinguishers. Again, no short circuit can occur if the cable is to pass the test. 4.4 Other cable types There are many other cables in use in buildings, primarily of the communications type. These will be discussed at a later lecture. As stated earlier it is necessary to segregate the communications/control cables from power cables to prevent EM coupling effects which may lead to incorrect information transfer. 4.5 Magnetic interference from cables A recurring and increasing problem with power cables is the effect of the magnetic field generated by the power frequency current in such cables. There are two major areas of concerns in buildings: interference with IT equipment (e.g. computer terminals) and the less tangible one of the potential hazard to personnel. The end result is that some care must be exercised in location and arrangement of ELEC9713: Industrial and Commercial Power Systems p. 32

33 cables to minimise these effects. This aspect will be covered later in the course. 5 Cable Enclosures and Conduits These include the following types of enclosure systems: (they should all be halogen-free, if made of insulating material, for fire damage minimisation) Conduits: steel, rigid PVC, corrugated flexible PVC Tubes and pipes: metal, non-metal plastic, earthenware etc Ducts: metal or non-metal Cable support systems: cable trays, cable ladders troughs etc Trunking systems: mainly for busbars. In the case of metal enclosures or support systems, the potential for eddy current heating must be taken into account. Insulation of sections may be necessary to prevent this effect. Also the enclosures may need to be earthed to prevent problems of electric shock by indirect contact if a fault occurs by insulation failure to the metal enclosure. The conduits and other enclosures must have appropriate IP numbers to prevent ingress of moisture and dust to susceptible areas. Some care must also be given to a determination of the impact of the enclosure on the thermal dissipation from the cables and the effect that this will have on the cable rating. ELEC9713: Industrial and Commercial Power Systems p. 33

34 It will often be necessary to de-rate the cable current carrying capacity because of thermal limitations caused by enclosures. 6 Busbars and busbar trunking systems (BTS) etc 6.1 Busbars For very high current capacity systems it is common to use rigid busbar systems of either aluminium or copper rectangular section [See Figure 13]. These are normally segmented (laminated) for very high ratings. This 'lamination' achieves two purposes: one is to improve heat loss by providing greater surface area for thermal dissipation and the other is to limit increase of resistance due to skin effect. Both skin effect and proximity effect are significant problems that must be considered for high current AC busbar systems. The segmentation or lamination of the individual phase conductors limits the eddy current generation level which is the basis of the skin and proximity effects in AC conductors. DC systems are not affected in this way and thus only require such segmentation to assist with improving thermal dissipation. The orientation of the busbar sections can have a very significant effect on the thermal dissipation by virtue of the impact on natural convection flows set up in the ambient air and this will affect the current carrying capacity of the bars. Similarly, a matt (non-shiny) surface with a high radiative ELEC9713: Industrial and Commercial Power Systems p. 34

35 emissivity will also enhance the current rating substantially through increasing the radiative heat loss. Busbars are prone to potential resonance effects caused by the electrodynamic forces between the conductors. Because of the very small spacing at low voltages and the high currents, the forces on busbars even at normal operating conditions can be significant. With the busbar support being normally at spaced intervals of perhaps a metre or two, the busbar acts as a fixed beam under the lateral electrodynamic force and it will thus have a natural resonant frequency, the value of which will depend on the spacing of the supports, the size of the conductor and the elasticity coefficient of the material. It is a necessary requirement to calculate this natural frequency of resonance and if it is close to the 100 Hz frequency of the electrodynamic forces generated, then the support spacing must be altered to change the resonant frequency to move it further away from the electrodynamic force frequency. The bars may be insulated or uninsulated, although the modem trend in large buildings is for insulated bus bars, often in a trunking system (busbar trunking system [BTS]). ELEC9713: Industrial and Commercial Power Systems p. 35

36 Fig.18: Current-carrying capacity of busbars. ELEC9713: Industrial and Commercial Power Systems p. 36

37 6.2 Busbar Trunking systems The trunking system consists of a tightly packaged sandwich of the three busbars and the neutral, with an insulating foil (melinex typically) between layers. It may require external fins for cooling because of the densely packed nature of the sandwich. They will also require some protection against ingress of moisture as this can be taken by capillary action to the live conductor and create a creepage path. Trunking systems are now being used with structures which are able to be joined with relative ease to connect plug-in systems. Feeder BTSs can have ratings from a few hundred amps to 10,000 amps. Plug-in systems can have ratings from about 100 amps up to 1500 amps. The outer metal enclosure must be earthed and the same precautions for eddy currents must be taken as in metal bus bar enclosures. They must be type tested and routinely tested before installation. Tests must look at, in particular, the following aspects: Temperature rise at rated load Short circuit temperature rise Clearances Creepage paths IP ratings Mechanical strength etc. ELEC9713: Industrial and Commercial Power Systems p. 37

38 6.3 Flexible copper straps In addition to the rigid trunking systems, flexible insulated copper straps are now being used. These have the advantage of being able to be easily shaped on site to match the installation requirements. They can be used in small switchboards for example where space is limited. ELEC9713: Industrial and Commercial Power Systems p. 38

39 Example 1: Assume: 3φ voltage drop in consumer mains: V d = 3V balanced loads, i.e. disregard current in neutral Subcircuits wired with multi-core V-75 insulated and sheathed copper conductors, installed in single circuit configuration, unenclosed in air, clipped to a wall. Choose conductor size to satisfy voltage drop requirement. Three-phase circuit: 30A load. From Table 12 column 4, conductor size of 6mm 2 has current-carrying capacity of 37A. Total maximum permissible voltage drop: 5% 400 = 20V Hence, voltage drop allowed in 3φ final subcircuit: 20 3 = 17V Maximum unit value of voltage drop: 1000V d Vc = = = 6.3mV/A.m L I ELEC9713: Industrial and Commercial Power Systems p. 39

40 Select Table 42 for multicore cables with copper conductors. Select 75 o C column for normal operating temperature of V75 cables. The nearest lower unit value is 3.86mV/A.m. From column 1, this corresponds to cable size of 10mm 2. Single-phase circuit: 30A load. From Table 9 column 4, conductor size of 4mm 2 has current-carrying capacity of 34A. Total maximum permissible voltage drop: 5% 230 = 11.5V Hence, voltage drop allowed in final subcircuit: 11.5 ( 3 3) = 9.77V Maximum unit value of voltage drop: 1000V d Vc = = = 3.62mV/A.m L I Convert to three-phase value: Vc3 φ = Vc 1φ = = 3.14mV/A.m Select Table 42 for multicore cables with copper conductors. Select 75 o C column for normal operating temperature of V75 cables. The nearest lower unit value is 2.43mV/A.m. From column 1, this corresponds to cable size of 16mm 2. Note: in both final subcircuits, cable size had to be increased to comply with voltage drop requirements. ELEC9713: Industrial and Commercial Power Systems p. 40

41 Example 2: Underground 1500A 3φ supply is constructed using parallel circuits of 400mm 2 V-75 single-core insulated and sheathed Cu cables. Determine the minimum number of active conductors required. (a) All cables in one conduit Capacity of one 400mm 2 cable= 510A (Table 6, col. 16) Refer to Table 22 for derating factor: = 1530A (b) Groups of conduits Refer to Table 26(2) for derating factor: = 1612A ELEC9713: Industrial and Commercial Power Systems p. 41

42 Example 3: 3-φ circuit is to supply a load of 125A per phase. Use two V-75 four-core Cu conductor, insulated and sheathed cables bunched together on a surface in a confined ceiling space where ambient temperature is 50 o C. Determine minimum conductor size and maximum route length if allowable voltage drop is 3%. Derating factor for cable bunching = 0.8 (Table 22, col.5) Derating factor for 50 o C ambient = 0.82 (Table 27.1, col.9) Required minimum current-carrying capacity: = 190.5A for two parallel cables or 95.25A per cable. From Table 12, column 4, the conductor minimum size is 35mm 2. 3-φ permissible voltage drop: Vd = = 12V Unit voltage drop (Table 42): V c = 1.11 mv/a.m Maximum route length: 1000 Vd L = = I V c 173m ELEC9713: Industrial and Commercial Power Systems p. 42

43 Example 4: 1-φ circuit comprised of two 16mm 2 Cu single-core sheathed cable, V-75 insulation, installed unenclosed on a wall. Circuit is to supply 55A resistive load. Determine 1-φ voltage drop value when ambient air temperature is 40 o C and 25 o C. Operating current I o = 55A o From Table 1, rated operating temperature θ R = 75 C From Table 3, current-carrying capacity is = 72A. (a) Ambient temperature θ A = o 40 C 2 I o θo θ A = operating temperature I R θr θ A o Use θ o = 60 C then from Table 41: I R θ o = o 60.4 C 3φ voltage drop = 2.32 mv/a.m thus 1φ voltage drop = = 2.68 mv/a.m o (b) Ambient temperature θ A = 25 C From Table 27, correction factor = θo 25 = o θ o = 44.9 C o Use θ o = 45 C then from Table 41: 3φ voltage drop = 2.20 mv/a.m thus 1φ voltage drop = = 2.54 mv/a.m ELEC9713: Industrial and Commercial Power Systems p. 43

Power Cables and their Application

Power Cables and their Application Power Cables and their Application Parti Materials Construction Criteria for Selection Project Planning Laying and Installation Accessories Measuring and Testing Editor: Lothar Heinhold 3rd revised edition,

More information

Chapter 6. WIRING SYSTEMS Safe Electrical Design

Chapter 6. WIRING SYSTEMS Safe Electrical Design Chapter 6 WIRING SYSTEMS Safe Electrical Design Topic 6-3 CABLE SELECTION BASED ON CURRENT CARRYING CAPACITY REQUIREMENTS INSTALLATION CONDITIONS Current carrying capacity (CCC) is the maximum continuous

More information

Notes 3 Explanatory Information 4-10

Notes 3 Explanatory Information 4-10 Low Voltage Cables Section Three SECTION THREE - LOW VOLTAGE CABLES PAGE Notes 3 Explanatory Information 4-10 Construction 4 Current Ratings 5 Rating Factors 6 Voltage Drops 8 Selection Procedures 10 Minimum

More information

Flexitime! Our flexible cables save you time and money.

Flexitime! Our flexible cables save you time and money. Flexitime! Our flexible cables save you time and money. We re flexible so you won t have to be. With our improved range of flexible cables we ve brought flexibility to a completely new level. From now

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables

More information

Basic Principles and Operation of Transformer

Basic Principles and Operation of Transformer Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core

More information

P Low Voltage Catalogue Cables Australia Powering your Project

P Low Voltage Catalogue Cables Australia Powering your Project P +61 8 9367 8978 Low Voltage Catalogue Cables Australia Powering your Project CABLES AUSTRALIA PTY LTD LOW VOLTAGE CATALOGUE ABOUT US Cables Australia is a locally owned and operated distributor of high

More information

INTRODUCTION NUHAS OMAN QUALITY & RELIABILITY.

INTRODUCTION NUHAS OMAN QUALITY & RELIABILITY. INTRODUCTION Nuhas Oman LLC, an integral part of The Al Bahja Group of Companies, is a Quality producer of: HV, MV and LV Cables Enamelled Copper Wires Oxygen Free Continuous Cast Copper Wire Rods Drawn

More information

CIR (Crush & Impact Resistant) VFD Power Cable

CIR (Crush & Impact Resistant) VFD Power Cable 37-2 CIRVFD CIR (Crush & Impact Resistant) VFD Power Cable Gexol Insulated Three Conductor 2kV Rated 90 C UL Listed as Type TC-ER Power Conductors (x3) Soft annealed flexible stranded tinned copper per

More information

Collection of standards in electronic format (PDF) 1. Copyright

Collection of standards in electronic format (PDF) 1. Copyright Collection of standards in electronic format (PDF) 1. Copyright This standard is available to staff members of companies that have subscribed to the complete collection of SANS standards in accordance

More information

Medium Voltage Power Cables

Medium Voltage Power Cables N2XSY 6/0, /20, /30 NA2XSY 6/0, /20, /30 N2XS2Y 6/0, /20, /30 NA2XS2Y 6/0, /20, /30 N2XS(F)2Y 6/0, /20, /30 NA2XS(F)2Y 6/0, /20, /30 N2XSEY 3 x 6/0 Medium Voltage Power Cables Photo: HELUKABEL Q 47 Medium

More information

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the

More information

Sizing conductors and selecting protection devices

Sizing conductors and selecting protection devices Sizing conductors and selecting protection devices 04 POWER GUIDE 2009 / BOOK 04 INTRO Careful selection of the sizes of the conductors in wiring systems and the characteristics of protection devices will

More information

MV Power Cable Testing Training

MV Power Cable Testing Training MV Power Cable Testing Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Since power cables are used

More information

ER 87 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) ESR 27(2) (2 marks) ESR 74A(1AA)

ER 87 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) ESR 27(2) (2 marks) ESR 74A(1AA) ER 87 Electrician Regulations Answer Schedule Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The

More information

Armoured Power and Control Cables Fire Resistant

Armoured Power and Control Cables Fire Resistant Armoured Power and Control Cables Fire Resistant Low Smoke Zero Halogen TAC. MGT. EPR. ZH. GSWB. SW, 00/00V Application Armoured cables for fixed wiring in ships and offshore units where circuit integrity

More information

Armoured Power and Control Cables to BS7917

Armoured Power and Control Cables to BS7917 1 Armoured Power and Control Cables to BS Fire Resistant, TAC. MGT. EPR. ZH. GSWB. SW, 00/00 V. Low Smoke Zero Halogen Application Armoured cables for fixed wiring in ships and offshore units where circuit

More information

Chapter G Sizing and protection of conductors

Chapter G Sizing and protection of conductors Chapter G Sizing and protection of conductors 1 2 3 4 5 6 7 8 Contents General 1.1 Methodology and definition G2 1.2 Overcurrent protection principles G4 1.3 Practical values for a protective scheme G4

More information

OFFSHORE CABLES GENERAL CATALOGUE. Offshore Cables. technergy INTEGRATED CABLING SOLUTIONS

OFFSHORE CABLES GENERAL CATALOGUE. Offshore Cables. technergy INTEGRATED CABLING SOLUTIONS OFFSHORE CABLES GENERAL CATALOGUE Offshore Cables technergy INTEGRATED CABLING SOLUTIONS TM 1 TEOF Offshore Cables INTEGRATED CABLING SOLUTIONS TM technergy Introduction Every offshore platform requires

More information

1. general. 1.1 methodology and definitions. methodology

1. general. 1.1 methodology and definitions. methodology 1. general 1.1 methodology and definitions component parts of an electric circuit and its protection are determined such, that all normal and abnormal operating constraints are satisfied. methodology Following

More information

Underground System Design TADP 547

Underground System Design TADP 547 Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards

More information

SINGLE CORE CABLE-2491X PVC H05V-K CABLE 300/500V

SINGLE CORE CABLE-2491X PVC H05V-K CABLE 300/500V LEDBURN CABLES IS AN INDEPENDENTLY OWNED CABLE DISTRIBUTOR. SINGLE CORE CABLE-2491X PVC H05V-K CABLE 300/500V Internal equipment wire. Also used in instrumentation panels of power switchgear. Suitable

More information

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers SPECIFICATION GUIDE ABB VACUUM CAST COIL DRY TRANFORMERS CONTENTS 1. General 1.1. Codes and standards 1.2. Service conditions 1.3. System characteristics 1.4. Documentation 2. Design and construction 2.1.

More information

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes FINAL - ER 70 Electrician Regulations Answer Schedule Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions.

More information

Fatima Michael college of Engineering and Technology

Fatima Michael college of Engineering and Technology Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric

More information

DESIGN OF A 45 CIRCUIT DUCT BANK

DESIGN OF A 45 CIRCUIT DUCT BANK DESIGN OF A 45 CIRCUIT DUCT BANK Mark COATES, ERA Technology Ltd, (UK), mark.coates@era.co.uk Liam G O SULLIVAN, EDF Energy Networks, (UK), liam.o sullivan@edfenergy.com ABSTRACT Bankside power station

More information

Busbar and Modular Wiring Systems

Busbar and Modular Wiring Systems Chapter 11 Busbar and Modular Wiring Systems 11.1 BUSBAR SYSTEM The wide range of busbar system is available and can be used for single or three-phase distribution to many types of applications ranging

More information

Armoured Power and Control Cables to BS6883

Armoured Power and Control Cables to BS6883 Armoured Power and Control Cables to BS Low Smoke Zero Halogen Single-Core - T.A.C EPR, SW, TPBWB. SW 00/00 V Multicore - T.A.C EPR, SW, GSWB, SW 00/00 V Application Armoured cables for fixed wiring in

More information

Kerman & Kavian Cable Industries ( KCI )

Kerman & Kavian Cable Industries ( KCI ) KCI Kerman & Kavian Cable Industries ( KCI ) KCI Cables for control and instrumentation circuits 150/250 V (300 V) According to of IEC 60092-376 (2003) Electrical installations in ships - Part 376: Kerman

More information

6419X Conduit Cable. Dungannon Electrical Wholesale Tel: Page 1 of 10

6419X Conduit Cable. Dungannon Electrical Wholesale Tel: Page 1 of 10 6419X Conduit Cable Application: Industrial and commercial wiring, these cables are intended for installation in trunking and conduit. They may also be used inside fixed, protected installations such as

More information

EDS LV WAVEFORM MAINS CABLE RATINGS

EDS LV WAVEFORM MAINS CABLE RATINGS Document Number: EDS 02-0033 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 02-0033 LV WAVEFORM MAINS CABLE RATINGS EPN, LPN, SPN This standard details the technical and practical information required

More information

Copper Sheathed Cable Sheath Currents

Copper Sheathed Cable Sheath Currents Pyrotenax Copper heathed Cable heath Currents ingle Conductor Cable ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations

More information

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Cables

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Cables Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Cables NO: 452-1 Office

More information

EXTREMELY LOW MAGNETIC FIELD (ELMF) XLPE INSULATED CABLES, TYPE N2XY/FR1 0.6/1 KV

EXTREMELY LOW MAGNETIC FIELD (ELMF) XLPE INSULATED CABLES, TYPE N2XY/FR1 0.6/1 KV CABLE DESCRIPTION Single- or multi-phase electric cable for creating a weak external magnetic field,so as to obtain a cable wherein at last one of the conductors is assembled from two or more insulated

More information

DISTRIBUTION TRANSFORMERS

DISTRIBUTION TRANSFORMERS The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 4 DISTRIBUTION TRANSFORMERS A transformer is a static device that

More information

Installation Recommendations

Installation Recommendations Installation Recommendations Cable pulling recommendations The process of pulling electrical cables on board marine vessels is a relatively standard procedure. Nevertheless, NEXANS would suggest the following

More information

DOWNSTREAM POWER, CONTROL & INSTRUMENTATION CABLES

DOWNSTREAM POWER, CONTROL & INSTRUMENTATION CABLES DOWNSTREAM POWER, CONTROL & INSTRUMENTATION CABLES DOWNSTREAM FACILITY CABLES El Dorado, Arkansas Made in America CIR (Crush & Impact Resistant) CIR is a next-generation cable designed to replace older-technology

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

Module 2 Unit 6, 7, 8

Module 2 Unit 6, 7, 8 Module 2 Unit 6, 7, 8 1. What is the definition of an ideal conductor? Material that will carry the greatest current with the lowest temperature rise 2. How much does copper weigh compared to aluminum?

More information

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum. FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared

More information

VFD CABLES 100% EMI CONTAINMENT FOR INDUSTRIAL APPLICATIONS

VFD CABLES 100% EMI CONTAINMENT FOR INDUSTRIAL APPLICATIONS VFD CABLES 100% EMI CONTAINMENT FOR INDUSTRIAL APPLICATIONS INDUSTRIAL VFD CABLES Index n Variable Frequency Drive (VFD) Power Cables Extra Flexible VFD Power Cable............... 2-3 Crush & Impact Resistant

More information

POWER AND COMMUNICATION CABLES Theory and Applications

POWER AND COMMUNICATION CABLES Theory and Applications POWER AND COMMUNICATION CABLES Theory and Applications Edited by R. Bartnikas, Editor Institut de Recherche dhydro-quebec Varennes, Quebec, Canada K. D. Srivastava, Coeditor University of British Columbia

More information

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS 1.0 SCOPE 2.0 BONDING METHODS 2.1 Introduction 2.2 Design 2.3 Single-Point Bonding 2.4 Cross Bonding 2.5 Sheath Sectionalizing Joints 2.6 Sheath Standing Voltage 2.7 Sheath Voltage at Through Fault 2.8

More information

Collection of standards in electronic format (PDF) 1. Copyright

Collection of standards in electronic format (PDF) 1. Copyright Collection of standards in electronic format (PDF) 1. Copyright This standard is available to staff members of companies that have subscribed to the complete collection of SANS standards in accordance

More information

ET 40 - Electrician Theory Examination Marking Schedule

ET 40 - Electrician Theory Examination Marking Schedule ET 40 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker

More information

14 AWG 2 AWG: 600 Volt

14 AWG 2 AWG: 600 Volt INDUSTRIAL AUTOMATION & PROCESS CONTROL CABLES 18.70 600V Type MC Metal Clad and Teck-Style Cables Overview Metal Clad Interlocked PVC Outer Jacket Teck-Style PVC Outer Jacket Introduction Polyester Wrap

More information

LIST OF IS STANDARDS FOR ELECTRICAL PROJECTS

LIST OF IS STANDARDS FOR ELECTRICAL PROJECTS SL NO. NAME OF SPECIFICATION IS 1 Specification for High-Voltage Alternating-Current Circuit-Breakers IS 13118 2 Guide for testing of circuit breakers with respect to out-of-phase switching IS 9135 3 Bushings

More information

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems Arild Furnes,ATPA OGP/Petrobras workshop, 22.09.09 Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems September 24, 2009 Slide 1 Transformers for Ships and Offshore -

More information

CONTINUING EDUC ATION

CONTINUING EDUC ATION 3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

DOWNSTREAM POWER, CONTROL & INSTRUMENTATION CABLES

DOWNSTREAM POWER, CONTROL & INSTRUMENTATION CABLES DOWNSTREAM POWER, CONTROL & INSTRUMENTATION CABLES DOWNSTREAM FACILITY CABLES Made in America CIR (Crush & Impact Resistant) CIR is a next-generation cable designed to replace older-technology cables like

More information

Cast resin transformers HARMONY TM

Cast resin transformers HARMONY TM Cast resin transformers HARMONY TM HARMONY TM the optimum solution for higher performance At a time when we are all seeking to preserve our way of life, the production of equipment whilst ensuring safety

More information

Cables. Cables. Power. Fire Resistant WILSON CABLES PRIVATE LIMITED. Distributed By :

Cables. Cables. Power. Fire Resistant WILSON CABLES PRIVATE LIMITED. Distributed By : Power Cables Fire Resistant Cables Distributed By : WILSON CABLES PRIVATE LIMITED 142, Gul Circle, Jurong Industrial Estate, Singapore 629602 Tel : + 65 68617888 Fax : + 65 68617871 E-mail : exports@wilson-cables.com.sg

More information

A6.6 9 th International Conference on Insulated Power Cables A6.6

A6.6 9 th International Conference on Insulated Power Cables A6.6 Development Process of extruded HVDC cable systems Dominik HÄRING, Gero SCHRÖDER, Andreas WEINLEIN, Axel BOSSMANN Südkabel GmbH, (Germany) dominik.haering@suedkabel.com, gero.schroeder@suedkabel.com, andreas.weinlein@suedkabel.com,

More information

Conductors and Raceway Design

Conductors and Raceway Design IEEE Southern Alberta Section, Industrial Applications and Power & Energy Chapter Technical Program Conductors and Raceway Design Blair Sackney, Southwire Canada George Morlidge SMIEEE, Fluor Canada May

More information

EE 340 Transmission Lines. Spring 2012

EE 340 Transmission Lines. Spring 2012 EE 340 Transmission Lines Spring 2012 Physical Characteristics Overhead lines An overhead transmission line usually consists of three conductors or bundles of conductors containing the three phases of

More information

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another.

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another. TRANSMISSION LINES PRELIMINARIES Generators and loads are connected together through transmission lines transporting electric power from one place to another. Transmission line must, therefore, take power

More information

For information transmission at dry and moist production sites, in and under plaster, outdoors for fixed installation.

For information transmission at dry and moist production sites, in and under plaster, outdoors for fixed installation. Telecommunication and fire alarm cables For information transmission at dry and moist production sites, in and under plaster, outdoors for fixed installation. J-YY Bd 14 J-YY BMK 15 J-Y(St)Y Lg 16 J-Y(St)Y

More information

PROTECTION AGAINST FAULT CURRENT

PROTECTION AGAINST FAULT CURRENT PROTECTION AGAINST FAULT CURRENT Short-circuit current the short-circuit current that could flow during fault is known as the prospective short-circuit current (PSCC), and any device installed to protect

More information

Evaluation of Distribution Line Spacers through the Leakage Current Monitoring

Evaluation of Distribution Line Spacers through the Leakage Current Monitoring Tsinghua University, Beijing, China, August -9, H-6 Evaluation of Distribution Line Spacers through the Leakage Current Monitoring A. G. Kanashiro *, W. Pinheiro and G. F. Burani Institute of Electrotechnics

More information

EE 741. Primary & Secondary Distribution Systems

EE 741. Primary & Secondary Distribution Systems EE 741 Primary & Secondary Distribution Systems Radial-Type Primary Feeder Most common, simplest and lowest cost Example of Overhead Primary Feeder Layout Example of Underground Primary Feeder Layout Radial-Type

More information

An Effective Cable Sizing Procedure Model for Industries and Commerial Buildings

An Effective Cable Sizing Procedure Model for Industries and Commerial Buildings International Journal of Electrical and Computer Engineering (IJECE) Vol. 6, No. 1, February 2016, pp. 34~39 ISSN: 2088-8708, DOI: 10.11591/ijece.v6i1.8391 34 An Effective Cable Sizing Procedure Model

More information

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Calculation of Isc by the impedance method In a 3-phase installation Isc at any point is

More information

Climatic, Environmental and Fire Behaviour (C2 E2 F1) Test of Cast Resin Transformer

Climatic, Environmental and Fire Behaviour (C2 E2 F1) Test of Cast Resin Transformer American Journal of Electrical Power and Energy Systems 2018; 7(1): 11-15 http://www.sciencepublishinggroup.com/j/epes doi: 10.11648/j.epes.20180701.12 ISSN: 2326-912X (Print); ISSN: 2326-9200 (Online)

More information

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards. 8.3 Induced Voltage Purpose The purpose of this instruction is to provide awareness of Electrostatic and Electromagnetic induced voltages and the method required to reduce or eliminate it. An induced voltage

More information

Tests on Extruded Cables

Tests on Extruded Cables Tests on Extruded Cables Pierre Argaut Chairman of CIGRE SC B1 October 26 th, 2011 At least, once in your life, you have heard these words: Development Tests Long-term Tests Prequalification Tests Extension

More information

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES 1. Qualifying Requirement of AB Cable Manufacture/Supplier The manufacturer should have manufactured, successfully type tested

More information

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

INSTALLATION, OPERATION AND MAINTENANCE GUIDE INSTALLATION, OPERATION AND MAINTENANCE GUIDE FOR INDOOR/OUTDOOR SINGLE PHASE ENCAPSULATED TRANSFORMERS Indoor/Outdoor Encapsulated Transformers The pictures used in this guide are only a representation

More information

TMC Transformers TMC

TMC Transformers TMC TMC Product & Technology Presentation Cast Resin Transformer (CRT) History Cast resin transformers first appeared in Germany during the 1960s. This new style of dry type transformer was developed with

More information

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date

More information

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection)

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection) Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection) FIGURE 1.2 Fig.1 Earth fault loop path. Figure 1 shows the earth fault system which provides

More information

Armoured Instrumentation Cables to BS6883

Armoured Instrumentation Cables to BS6883 Armoured Instrumentation Cables to BS Low Smoke Zero Halogen Pairs/Triples - Collectively Screened. TAC, EPR, SCRN, SW, GSWB, SW 0/0V Application Armoured control and instrumentation cables for fixed wiring

More information

INTRINSIC SAFETY BASIC PRINCIPLES

INTRINSIC SAFETY BASIC PRINCIPLES INTRINSIC SAFETY BASIC PRINCIPLES IGNITION TRIANGLE Ignition Energy In many industrial processes, the presence of flammable materials (gases, vapours, liquids, dusts, fibres and flyings) requires the adoption

More information

Contents. Introduction 3 Cable Components 4 Cable Handling 8 Health, Safety and Environment 9 Quick Reference Guide 10 Underground Mining - Coal 12

Contents. Introduction 3 Cable Components 4 Cable Handling 8 Health, Safety and Environment 9 Quick Reference Guide 10 Underground Mining - Coal 12 Mining Cables Contents Introduction 3 Cable Components 4 Cable Handling 8 Health, Safety and Environment 9 Quick Reference Guide 10 Underground Mining - Coal 12 Type 241 and 241SF 14 Type 245SF 16 Type

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

Single & Three Phase Transformers SAMPLE. Learner Workbook. Version 1. Training and Education Support Industry Skills Unit Meadowbank

Single & Three Phase Transformers SAMPLE. Learner Workbook. Version 1. Training and Education Support Industry Skills Unit Meadowbank Single & Three Phase Transformers Learner Workbook Version 1 Training and Education Support Industry Skills Unit Meadowbank Product Code: 5634 Table of Contents Introduction... 5 Section 1. Transformer

More information

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

Neutral Earthing. For permanent or temporary neutral earthing in HV systems Neutral Earthing Resistors RESISTORS For permanent or temporary neutral earthing in HV systems For continuous or temporary low-resistance neutral grounding in medium voltage systems Neutral point connection

More information

Chapter Seven. Under Ground Cables

Chapter Seven. Under Ground Cables Chapter Seven Under Ground Cables Construction of cables In the fig (7.1)below, shows the general construction of (3-condctor) cable The various part of cable are : 1- Core or conductor A cable may have

More information

UNIVERSITY OF TECHNOLOGY By: Fadhil A. Hasan ELECTRICAL MACHINES

UNIVERSITY OF TECHNOLOGY By: Fadhil A. Hasan ELECTRICAL MACHINES UNIVERSITY OF TECHNOLOGY DEPARTMENT OF ELECTRICAL ENGINEERING Year: Second 2016-2017 By: Fadhil A. Hasan ELECTRICAL MACHINES І Module-II: AC Transformers o Single phase transformers o Three-phase transformers

More information

Medium Voltage YOUR ENERGY, OUR SYSTEMS, ANYWHERE

Medium Voltage YOUR ENERGY, OUR SYSTEMS, ANYWHERE Medium Voltage YOUR ENERGY, OUR SYSTEMS, NYWHERE Contents Introduction 3 Cable Components 4 Cable Handling 7 Product Codes 8 Health, Safety and Environment 9 Exploded Cable View 11 Copper 1.9/3.3kV 12

More information

Addison Medium Voltage Cables

Addison Medium Voltage Cables Addison Medium Voltage Cables www.addison-cables.com www.addison-tech.com 1 Caledonian Medium Voltage Cables(ICEA) Company Profile Caledonian. established in 1978.offers one of the most complete lines

More information

EE 340 Transmission Lines

EE 340 Transmission Lines EE 340 Transmission Lines Physical Characteristics Overhead lines An overhead transmission line usually consists of three conductors or bundles of conductors containing the three phases of the power system.

More information

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01 SEC DISTRIBUTION GROUNDING STANDARD SDCS-03 Part-II Rev.01 SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING Rev. 01 This specification is property of SEC

More information

Cable Data Collector (CDC): Application Guide

Cable Data Collector (CDC): Application Guide Cable Data Collector (CDC): Application Guide Contents 1. Introduction... 1 2. PD in cables... 1 3. Principle of operation... 2 4. Advantages and disadvantages... 6 5. Assessing circuit suitability...

More information

CORFLEX VFD CORFLEX VFD Part Number: Drive Cable

CORFLEX VFD CORFLEX VFD Part Number: Drive Cable Part Number: Drive Cable Armored Variable Frequency Drive Cable UL Type MC HL, 600V, 90 C rated - LEAD FREE Description 3 conductor with 3 ground wires, continuous corrugated and welded, impervious aluminum

More information

2 METHODOLOGY. The method of reactive power compensation, proposed in this research is suitable

2 METHODOLOGY. The method of reactive power compensation, proposed in this research is suitable 2 METHODOLOGY 2.1 BASE LOAD REACTIVE POWER REQUIREMENT The method of reactive power compensation, proposed in this research is suitable to meet the base reactive power requirement of the network. The base

More information

H05Z-K / H07Z-K BS EN LSZH Wire

H05Z-K / H07Z-K BS EN LSZH Wire Application: In pipes or ducts and internal wiring of appliances with maximum operating temperatures of 90 C, and generally in areas (such as public and government buildings) where smoke and toxic fumes

More information

III/IV B.Tech (Regular/Supplementary) DEGREE EXAMINATION

III/IV B.Tech (Regular/Supplementary) DEGREE EXAMINATION Hall Ticket Number: 14EE503 October, 2018 Fifth Semester Time: Three Hours Answer Question No.1 compulsorily. Answer ONE question from each unit. III/IV B.Tech (Regular/Supplementary) DEGREE EXAMINATION

More information

DC utilization of existing LVAC distribution cables

DC utilization of existing LVAC distribution cables DC utilization of existing LVAC distribution cables D. Antoniou, A. Tzimas and S. M. Rowland The University of Manchester School of Electrical and Electronic Engineering M13 9PL, UK Abstract Low Voltage

More information

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured)

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured) WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (A Govt. of West Bengal Enterprise) Office of the Chief Engineer, Procurement & Contracts Department Vidyut Bhavan, 4 th. floor, Bidhannagar,

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge The University of New South Wales School of Electrical Engineering and Telecommunications High Voltage Systems ELEC9712 Appendix Partial Discharge Content Introduction Quantities measured Test circuits

More information

Industrial and Commercial Power Systems Topic 7 EARTHING

Industrial and Commercial Power Systems Topic 7 EARTHING The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 7 EARTHING 1 INTRODUCTION Advantages of earthing (grounding): Limitation

More information

Licensed Electricians Practical Assessment (LEP)

Licensed Electricians Practical Assessment (LEP) Licensed Electricians Practical Assessment (LEP) Surname: Given Names: Date: Time: Location: Assessment Time (includes reading and preparation time): At the end of this time you will be asked to stop.

More information

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES ( Data Sheets ) 11 kv XLPE-Insulated Three-Core Underground Cables (3x240 mm 2 ) ADWEA/ADDC/AADC STANDARD : D-AAA-CAB-11-3Cx240

More information

ELEC Transmission i and

ELEC Transmission i and ELEC-1104 Lecture 5: Transmission i and Distribution ib ti Power System Layout Transmission and Distribution The transmission system is to transmit a large amount of energy from the power stations s to

More information

VSD cables in. Working with. industrial & automation applications

VSD cables in. Working with. industrial & automation applications Cable Efficiency in Automation Connectivity Cabinet Control Working with VSD cables in industrial & automation applications Description of a VSD System A functional VSD system consists of at least three

More information

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES White Paper Tim Wylie, Ampcontrol s Chief Technology Officer discusses the impact of Variable Speed Drives (VSDs) on earth fault limited networks.

More information

GROUNDING SYSTEMS. Prepared by :Eng Walid Naim. Grounding.Doc 1/18

GROUNDING SYSTEMS. Prepared by :Eng Walid Naim. Grounding.Doc 1/18 GROUNDING SYSTEMS Prepared by :Eng Walid Naim Grounding.Doc 1/18 INTRODUCTION NETWORKS In the most industrial countries, the power generation stations are located far from cities and centres of consumption.

More information

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017 Ref: ART-B22-D70, ART-B22-D125, ART-B22-D175, ART-B22-D300 Flexible clip-around Rogowski coil for the electronic measurement of AC current with galvanic separation between the primary circuit (power) and

More information

Sample Specification Electrical Heat Tracing Cables Metric Units

Sample Specification Electrical Heat Tracing Cables Metric Units Sample Specification Electrical Heat Tracing Cables Metric Units January 2008 ELECTRIC HEAT TRACING CABLES SPECIFICATION TABLE OF CONTENTS PAGE 1.0 HEATER CABLES... 3 1.1 SELF-REGULATING... 3 1.2 FLEXIBLE

More information