A New 12kW Three-phase 18-Pulse High Power Factor AC-DC Converter with Regulated Output Voltage for Rectifier Units
|
|
- Everett Mathews
- 5 years ago
- Views:
Transcription
1 A New 12kW Three-phase 18-Pulse High Power Factor AC-DC Converter with Regulated Output Voltage for Rectifier Units Falcondes JosC Mendes de Seixas (*) and vo Barbi Federal University of Santa Catarina - Department of Electrical Engineering Power Electronics nstitute P.O. Box Florian6polis - SC - Brazil Phone: fax: falcon@inep.ufsc.br (*) s with the UNESP - SBo Paul0 State University - Abstract - This work presents a new high power factor three-phase rectifier based on a Y-connected differential autotransformer with reduced kva and 18-pulse input current followed by three DC-DC boost converters. The topology provides a regulated output voltage and natural three-phase input power factor correction. The lowest input current harmonic components are the 17'h and the 19*. Three boost converters, with constant input currents and regulated parallel connected output voltages are used to process 4kW each one. Analytical results from Fourier analyses of winding currents and the vector diagram of winding voltages are presented. Simulation results to verify the proposed concept and experimental results are shown in the paper.. NTRODUCTON n telecommunication systems, conventional input stage of power supplies is widely realized as voltage DC-link converters. n many cases, the AC supply voltage is connected to a DC link voltage by a diode rectifier with output filter capacitor. A high-frequency DC-DC converter, with regulated output voltage, is then connected in series with the DC-link voltage. Motivated by high efficiency, high power density, low cost and robustness, an uncontrolled threephase bridge directly connected to the AC supply has been used. However, this concept shows, as disadvantage, high low-frequency current harmonics, due to the output capacitor, which leads to a distortion of the AC supply voltage. Various international standards like EEE-5 19 and EC-1OOO-3-2, were proposed to maintain the THD (Total Harmonic Distortion) and the Power Factor (PF) at acceptable levels. This is especially important for guaranteeing universal applicability of telecommunication rectifiers. Furthermore, the conventional power supplies are being replaced more and more by three-phase modular rectifier systems, due to the advantages of the latter concerning operational behavior, system technology, and costs [Ol]. n the same way that the great number of works developed for power factor correction in single-phase systems, the techniques for three phase systems to operate with power factor correction are growing, either through converters with one or more associated switches, or by using specially connected transformers. n general, the techniques that use transformers or mixed systems, with transformers and static converters, operate well in higher power systems [02,03]. A parallel connection of three six-pulse bridge rectifier is used to obtain 18-pulse uncontrolled converter. Usually, an nterphase Transformer (PT) connected on the DC sides of the three bridge rectifiers is required to absorb the instantaneous voltage differences between the bridges. When a non-isolated transformer is used, two PT are needed: one connected to the positive outputs, and another connected to the negative outputs. The size, the loss and the cost of the PT are, therefore, increased. Figure 1 shows the basic diagram for a conventional non-isolated 18-pulse converter using two PT to improve parallel connection on the DC sides. SOURCE n i, Vb Non-isolated transformer 18-pulse Bridge 3 i - Bridge 3. Figure 1 : 18-Pulse Converter with Conventional PT. This work proposes an 18-pulse converter using a Y-connected differential auto-transformer. The autotransformer is designed to feed three six-pulse bridge rectifiers displaced in phase by 20'. The autotransformer power rate is only 22% of the output kva and the lowest order harmonics are the lp and the 19. n order to provide parallel-connected and regulated output voltages, without an PT, three boost converters with an additional diode [04] were proposed. Six small size high-frequency boost inductors, as shown in figure 2, replace the large interphase transformers. The continuous conduction mode and output regulated voltage are guaranteed by basic and simple control strategy of the boost converter. The inductor currents of each converter are kept constant with a little high frequency ripple /99/$ EEE
2 .L;, SOURCE 0 Vector diagram of the autotransformer winding voltages The three secondary voltage systems are obtained by the combination of ratios between primary and secondary windings. The vector diagram used to obtain all voltage system is shown in figure 4. AUTOTRANSFORMER Figure 2 Proposed Topology of the 18-Pulse Regulated Boost Converter Eiach boost converter is studied separately and a simple.passive lossless snubber circuit [05] is applied to reduce the over-current through the switch and the losses, during the diode reverse recovery. This snubber circuit provides a1 good turn-on transition for the switch. Eixperimental results with relevant waveforms to verify the power factor and details of switch commutation are presented.. ANALYSES OF THE PROPOSED 18- PULSE Y -CONNECTEDFFERENTAL AUTOTRANSFORMER. To simplify the analyses of the autotransformer, the boost converters are eliminated and, furthermore, three independent inductive loads, at the same values, are connected on the DC sides of the bridge rectifiers, as shown in figure 3. The main equations and relationships of winding voltages and currents are studied. Figure 4: Vector Diagram The primary windings of the autotransformer are formed by La, Lb and Lc, Y-connected and linked to the line voltages Va, Vb and Vc. n this connection, a virtual neutral point N is generated. The secondary windings are designed, in such way that, the turns ratio and the connection between them and the primary winding generate three different threephase systems with 20' phase-shift from each other. These voltages feed the rectifiers. All the windings of La, Lan, La1 and La2 are coupled together in the same limb core, the resulting voltages Va, Van, Val and Va2 are in phase. The same applies to phases "b" and "c", as shown in figure 4. The magnitude of the voltages across the secondary windings, is obtained as follows. sin( 20') VLbl = VLc2 = Vu. = V~ (01) sin( 100') VLcl = VLa2 = Vb. sin(20') = Vb (02) sin( 100') t Figure 3: A Simplified Circuit of Proposed Topology for Analyses The autotransformer is supplied by a three-phase balanced voltage system. The output voltages are composed by three rectifier systems of three-phase voltages, also balanced. One of these systems is placed in the same phase of the supply voltage and the others are placed of t20" and -20, with regard to the supply system. The 18-pulse converter is obtained when each output voltage system is connected to a six-pulse diode rectifier. Three identical loads with current source characteristic are used. sin( 20') = Vc VLal = VLb2 = Vc. sin(100') (03) The winding turns-ratio (n2) that ensure a displacement of 20" is given by (04). n2=va= =2.88 (04) Vbl Va This result shows that the secondary turns are 2.88 times lower than the primary turns. The magnitude voltages between each secondary terminal with respect to the virtual neutral point N are obtained as follows. sin( 60') Vbl = Vc2 = Vu. = Vu (05) sin( loo') sin( 60') Vcl = Vu2 = Vb. = Vb (06) sin( loo')
3 sin( 60') We can observed that this winding (Lan) Val = Vb2 = VC. = Vc (07) conducts the current 1013 during 120" (2n/3), starting from sin( 100') 30" (n/6). Thus, the expression of the current results: We can observe that the voltage magnitudes of each three-phase system are about 88% reduced in an (t) = :.?.? d.cos(k.b)sin(k.cn) ( 15) comparison input phase voltages. The third secondary three-phase voltage system Were, k=l, 3,5,... is in phase with the primary one. ts voltages however, The waveforms of all currents through the must be in agreement with the others secondaries. So, the secondary windings are the same, only with a 20" phasefollowing equations must be fulfilled shift among each three-phase system. The other currents VLan =VU -0,8794.V~ = V~ (08) are represented by the same equation of an as shown below. Therefore, all Dhases are adiusted. VLbn = Vb - 0,8794.Vb = Vb (09) VLcn = Vc - 0,8794.V~ = V~ (10) bn(t) = n~.e.~i.co{k.~)s~n~.[m.t+~)] 3 (16) Were, VLan, VLbn and VLcn are the magnitude of the voltages across the secondary windings Lan, Lbn and Lcn, respectively. cn(t) = 7x3 ~.~.~i.co{k.~)sin~.(at-$)] (17) The winding turns-ratio to ensure 88% from primary voltage (nl), without displacement is given by. n the other secondary three-phase system, the currents are expressed by: nl=-=---- Va Vb - Vc 1 --=8.29 (11) Van Vbn Vcn 0,1206 al(t) =:.F.F+.co@.$)i{k.[ at-%)] (18) This result shows that this secondary turns is 8.29 times lower than the primary turns. The magnitude voltages for these secondary terminals, with respect to the virtual neutral point N, are obtained as follows. Van = V~ (12) Vbn = Vb (13) Vcn = V~ (14) Analysis of winding currents The technique to eliminate harmonic of current in the multiple pulse converters requires current-mode operation to the load. n this case, the 18-pulse converter, formed by three-bridge rectifier, each converter conducts 1/3 of the load current (10/3). The currents in the secondary windings are the same to the input currents of each bridge. The waveform of the input Va and the current through one secondary winding (Lan) are shown in figure 5. These waveforms are adopted as angular reference to represent the other ones. ), + cl(t) = ~.~.Fi.co{k.~)in~.~ 140.n +%) bl =~.~.~i.co@.$)nk.( 113 (Ut (19) K3 (20) To the last system, the currents are expressed by: a2(t) =!.~.F~.co~.~)si{k.~t 1OO.K (21) a bz(t) =t..".z'.co n 3 k k + -)] c2(t) =!.E.~~.co{k.$).in[k~-~)] n 3 k k (23) The primary winding currents (a, b and C) can be obtained by considering the currents of the three secondary winding coupled to the same limb core and by turns-ratio (n1=8.29 and n2=2.88). As mentioned boton, winding with the same index (a, b or c) are coupled in the same limb. a(t) = nl 1 Figure 5: Primary Reference Voltage and Secondary Current to Phase indexed by "a" The waveform of an can be decomposed in Fourier series by the conventional way. By the way, when discontinuous function is considered, the series terms can be obtained by inspection. We can observe that this waveform presents alternate symmetry, the negative half cycle is an inverted reproduction of the positive half cycle. Thus, the even harmonic are zero and there are not terms in cosines. The average value is also zero. c(t) = Figure 6 shows the primary current Qa). t is obtained by composition of equation (24) from (04), (1 l), (15), (18) and (21). This solution is easily found and plotted through MathCad program s Figure 6: Primary Current Waveform
4 0 Anrdysis of input phase currents The input phase currents ia, ib and ic are obtained by summing all currents through windings at same node as shown in figure 3. So, the follow equations can be written. ia( t) = a(t) + an(t) + bl(t) + c2(t) (27) ib(t) = b(t)+ bn(t) + cl(t) + a2(t) (28) ic(t) = c(t) + cn(t) + al(t) + b2(t) (29) Figure 7 shows the phase currents (Ea, ib and ic). They are obtained by composition of equation (27), (28) and (29) from (15) to (26) ~... ~ - ' T l T. - 2 The Power Factor (PF) is calculated by (33). The displacement between the phase current and the phase voltage is negligible. 1 PF = da = (33) Figure 9 shows the frequency spectrum of the input phase current ia(t). We can observe that 18-pulse converter presents only harmonic orders n.(18fl), for n=1,2,3,... The lowest harmonic orders are the 17'h and the 19". 6 i %ia 5; ;... i. : in nn i Harmonic orders Figure 9: Frequency Spectrum for nput Phase Currents Figure 7: Three-phase nput Currents Figure 8 shows a detail of the current and voltage wavefonn of one phase. 4 r T... """... TT^ Figure 8: Current and Voltage Waveforms of one nput Phase Harmonic analysis for input phase current Total Harmonic Distortion (THD) is calculated by relationship between rms values of the fundamental components and all phase current harmonics. n these calculations MathCad program has considered the first lo00 harmonic components (k=1,3, ). The total rms value for all harmonics of the phase current ia and the rms current for fundamental component ial (for k=l), are calculated through (30) and (31): ia =,/-!-.rnia(t)' 2.n 0.dot Where, ia(t) is solved by (27) for k=1,3,5,... and ial(t) is solved by (27) for k=l. Now, from (30) and (31), the THD is easily obtained by (32). 0 Normalised winding currents The shape of all secondary winding currents are equal, but each one is shifted in phase to generate the three-phase systems. Anyway, all rms value of secondary currents are the same. Then, they can be calculated through (34). 1 an =o. -. ~an(t)'.doc - an= (34) 2.n o The primary winding currents have the same m value and can be expressed by (35)..dot a = o (35) a = o.,/l.rny2 2.n 0 Where, an(t) and a(t) are the secondary and the primary winding currents, respectively. Other currents are calculated with the same way. We can observe that the secondary current rate is 27.2% while the primary current rate is only 7.8% of the load current o. 0 Power rate of the autotransformer The voltage across secondary windings with the same phase than primary ones, h, Lbn and Lcn, are reduced by turns ratio nl. Therefore, the relationship between these voltages is expressed for (08), (09) and (lo), and replaced by (36).,EL VLan = Va (36) nl With VLan = VLbn = VLcn and Va = Vb = Vc The voltage across secondary windings with phase shift of 20' in relation to primary ones, Lal, La2, Lbl, Lb2, Lcl and Lc2, are reduced by turns-ratio n2. Therefore, the relationship between these voltages are expressed for (Ol), (02) and (03), and replaced by (37). Va VLal=- VLal = Va (37) n2 With VLal = VLa2 = VLbl = VLb2 = VLcl = VLc2 Expression (38) and (39) give the average voltage from output of the rectifier.
5 Vo =-. 6 2n (fi.& va.sin(ot))ht 2.a 0 Vo = Va (39) The secondary power rate VA is obtained by summing of the product of voltage and current of each winding, as in (40), from (34), (36) and (37). S2 = PO (40) The primary power rate VA is obtained from equations (35) and (39) and is expressed by (41) S1 = 0.114P0 (41) Where Po = vo.10 (42) Thus, the autotransformer power rate is given by average value between S1 and S2. Then, S = 0.218P0 (43) 14-2 Non-regulated inductor currents To verify the relevance of the boost current control for the proposed strategy, some simulation analyses have been investigated. Figure 11 shows the simulation result waveforms for current through the inductors when three nonregulated boost converters (at constant frequency) are employed. We observe that these currents oscillate in the same frequency as the rectified voltages. n addition, the boost inductance and the switching frequency define the ripple PROPOSED BOOST CONVERTER STRATEGY The boost converter is chosen because it provides a simple regulated output voltage and regulated inductor current. Furthermore, it is very easy to obtain three parallel connected boost converters. +zoo Figure'l 1: nductor Currentsfor Non-Regulated Boost Converter The amplitudes of these oscillation currents are very large in comparison with the average current values. Furthermore, the boost converter can be operate in DCM for reduced load, as shown in figure 12. These problems make the non-regulated boost converter impracticable.,ll l_l. - - ^ x m Figure 10: Parallel Connected Boost Converters 0 Parallel connected boost scheme Figure 10 shows a basic scheme to allow parallel connection of the boost converters [04]. The conventional boost converter can not be used because when two or more switches are closed, the current flowing through the first boost returns through the second one. The diodes D12, D22 and D32 added in the conventional boost can solve this problem. Another problem occurs when all switches are simultaneously open. The current flows through the first boost, through the load and returns through the second one. This problem is solved by division of each boost inductor in two series connected inductors, as shown in figure 10. After the switch turn-off, the lower inductor forces the current from upper one to comes back through it. n this way, the lower inductors L12, L22 and L32 are necessary. This connection is very important to the operating of the circuit. t improves an independent operation mode between the boost converters. Figure 12: nductor Currents for Non-Regulated Boost Converter (Reduced Load) The oscillations of the inductor currents are reflected to input phase current. To reduce the low frequency component of the inductor currents, a bigger boost inductor have used. Then, we could eliminate the boost converters and replace them by PT's. To solve this problem, the boost converters have to furnish regulated currents for all boost inductors. 0 Command circuit for regulated boost converter To improve regulated current in boost inductor and regulated output voltage, various command circuits such as constant hysteresis and average current-mode control were investigated. The simplest strategy to
6 ----- "l""_ 14-2 promote both regulated voltage and regulated current is shown in block diagram in figure 13. Current error amplifier Figure 13: Command Strategy for one Boost Converter constant frequency. Anyway, all boost converters operate independently and decoupled. Therefore, the synchronism between them is not necessary. n order to connect all boost converters in parallel, only one voltage regulator is necessary. Fortunately, the command circuit becomes simpler, as shown in figure 14. The simulation results for regulated boost inductor currents are shown in figure 15. We observed that...- ", j L, i Y lr 1) ~~ Figure 15: nductor Currents for Regulated Boost Converter V. EXPERMENTAL RESULTS Figure 14: Command Strategy for All Boost Converters This is a conventional scheme to control each boost converter. The output voltage error amplifier is used as reference by the current regulator and the output current error amplifier is connected to PWM controller at A prototype rated at 12kW, input line voltage equal to 380V and DC output voltage equal to 600V has been built and tested in the laboratory. The implemented circuit is shown in figure 16. i / BOOST 1. ;BOOST2 /...., l ~ l l h ~ : :..._.._.E :BOOST3!. +. Figure 16: Complete Circuit for one Boost Converter "33P i
7 The more relevance components and the main specifications are reported as follows. 0 Autotransformer and diode rectifiers The autotransformer circuit and the diode rectifiers are shown in figure Primary windings N(La, Lb, Lc) = 330 turns with 20AWG wire 9 Secondary windings N(Lan, Lbn, Lcn) = 40 turns with 15AWG wire 9 Secondary windings N(La1, Lbl, Lcl) = 114 turns with 15AWG wire 9 Secondary windings N(Lan, Lbn, Lcn) = 114 turns with 15AWG wire 9 Central area of the EE three-limb core = 27cm2 9 Three-phase bridge = SKD 30/08 A1 (Semikron) 0 Boost converters To reduce the stress current due the recovery diode and to reduce the turn-on losses on GBT, a regenerative snubber circuit (Ls, Dsl, Ds2 and CS) [05] is used. The more relevant components for boost converters are presented as follows. 9 Active switch S1= GBT (RG4PC3OW) > Boost inductors L11, L12 = 1mH (60 turns on core E65-26) Boost diodes D11, D12 = HFA15TB60 Snubber diodes Dsl, Ds2 = HFA15TB60 Snubber inductor Ls = 2pH (4 turns on core E30-7) Snubber capacitor Cs = 47pF Output capacitors CO = 470 pf 9 Current sensor = LA-25PN 9 PWM circuit = LM Operational amplifier = LM Optocoupler = HP 2211 Figure 17 shows a detail of the main switch tumon transition with the snubber circuit installed. TQK Stop. 250MW.S, and the THD of the input current measured are equal to 0.99 and 8.8%, respectively. TOK Run: 25.0WlS H KeS 22 Mar 1 QQQ Ref4 ioov 2.0Oms 16:11:41 Figure 18: nput Current and Voltage for Complete Circuit (2ms/Div, loov/div,.5a/div) The input phase voltage (Va) and the current through the input bridge (or through the secondary winding - an) are shown in figure 19. Rerl 10ov 2.00m.K 22 Mar !13!46 Figure 19: Bridge nput Current and Phase Voltage (2msDiv, OOVDiv, 2ADiv) Figure 20 shows the three currents displaced by 20 in phase, each one other. With this figure we can visualise one phase of each three-phase systems (al, an and a2). TOL Run. 25.0Wls HKS.. A All 1OOV 4 21 Marl Figure 17: Detail of the Main Switch Turn-on Transition (2OOnsDiv, 100VDiv, 2A/Div) Figure 18 shows the most important result of this work. t shows the waveforms for input current and input voltage in the same phase. We can observed the shape of input current between experimental result (fig. 19) and mathematical results (fig. 8) are the same. The input PF RP 22 Mar 1 QQ9 Ref3 10Omv Zooms 11:15:04 Figure 20: Bridge nput Currents for Each Three-phase System (2ms/Div, 2A/Div)
8 A detail of the boost inductor regulated current and the rectified voltage is shown in figure 21. Figure 21 : Boost nductor Current and Rectified Voltage (2Op/Div, 25OV/Div, 2ADiv) v. summary n this paper we presented a three-phase high input power factor rectifier, intended to be used in the design of (3 12kW rectifier unity for telecommunications. The converter is composed of a 18-pulse rectifier based on a differential Y-connected autotransformer and three six-pulse diode bridge, and three boost DC-DC converters;. From the studies reported in this paper, we draw the conclusion as follows: J The proposed circuit works according to the predicted models; J The input power factor and current THD are equal to 0.99 and 8.8%, respectively; J The low frequency 18-pulse autotransformer is rated at 22% of the output power. Therefore, the weight and volume are compatible with the telecclmmunication power supply specifications. J t employs three active switches that make this rectifier simpler and more reliable than the rectifier with six active switches. J t is controlled by very simple PWM dedicated integrated circuit, not requiring multipliers. 1 is the author s opinion that the proposed rectifier is a good candidate for 12 kw power supply design for telecommunications, with many advantages over the topologies presently being used in these applications. REFERENCES [Ol] J. W. Kolar, F. C. Zach A Novel Three-phase Utility nterface Minimizing Line Current Harmonics of High-Power Telecommunications Rectifier Modules, EEE Trans. on ndustrial Electronics, Vol. 44, pp Aug [02] Paice, Derek A. Power Electronic Converter Harmonic Multipulse Methods for Clean Power, N.Y., EEE Press, [03] S. Choi, P. N. Enjeti,. J. Pitel Polyphase Transformer Arrangements with Reduced kva Capacities for Harmonic Current Reduction in Rectifier-Type Utility nterface, EEE Trans. on Power Electronics, Vol. 11, pp , Set [04] G. Spiazzi, F. C. Lee mplementation of Single- Phase Boost Power-Factor-Correction Circuits in Three-phase Applications EEE Trans. on ndustrial Electronics, Vol. 44, pp Jun [05] A. Pietkiewicz and D. Tollik Snubber circuit and Mosfet Paralleling Considerations for High Power Boost-Based Power-Factor Correctors Proceedings of NTELEC 95, pp , ACKNOWLEDGEMENTS The authors gratefully acknowledge the valuable advice of ]:van Eidt Colling.
A New Three-phase Low THD Power Supply with High-Frequency Isolation and 60V/200A Regulated DC Output
A New Three-phase Low THD Power Supply with High-Frequency Isolation and 60V/200A Regulated DC Output Falcondes Jose Mendes de Seixas (*I and Ivo Barbi (**) (*) UNESP - siio Paul0 State University Department
More informationTHE converter usually employed for single-phase power
82 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 46, NO. 1, FEBRUARY 1999 A New ZVS Semiresonant High Power Factor Rectifier with Reduced Conduction Losses Alexandre Ferrari de Souza, Member, IEEE,
More informationNew Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 38, NO. 1, JANUARY/FEBRUARY 2002 131 New Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications Sewan Choi,
More informationThird Harmonics Injection Applied To Three Phase/Three Level/Three Switch Unidirectional PWM Rectifier
Third Harmonics Injection Applied To Three Phase/Three Level/Three Switch Unidirectional PWM Rectifier R.Brindha 1, V.Ganapathy 1,S.Apnapriya 1,J.Venkataraman 1 SRM University, Chennai, India ABSTRACT-This
More informationl1-i VEL SINGLE-PHASE ZCS-PWM HIGH POWER FACTOR BOOST RECTIFIER IVO Barbi Carlos A. Canesin
VEL SINGLE-PHASE ZCS-PWM HIGH POWER FACTOR BOOST RECTIFIER Carlos A. Canesin Paulista State University UNESP - FEIS - DEE - P.O. box 31 Fax: (+55) 18-7622125 e-mail: canesin@feis.unesp.br 15385-000 - Ilha
More informationA New Active Interphase Reactor for 12-Pulse Rectifiers Provides Clean Power Utility Interface
A New Active Interphase Reactor for 12-Pulse Rectifiers Provides Clean Power Utility Interface Sewan Choi* Prasad N Enjeti' Honghee Lee ** Ira J Pitel**' * * *Magna-Power Electronics *Power Electronics
More informationTHE rapid development of power electronics in recent
International Journal of Scientific & Engineering Research Volume 3, Issue 6, June-2012 1 A COMPARISON OF WITH AND WITHOUT AC- DC MULTIPULSE CONVERTER FOR VECTOR CONTROL PWM CSI IM DRIVE NAGABABU THOTA,
More informationA Double ZVS-PWM Active-Clamping Forward Converter: Analysis, Design, and Experimentation
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 16, NO. 6, NOVEMBER 2001 745 A Double ZVS-PWM Active-Clamping Forward Converter: Analysis, Design, and Experimentation René Torrico-Bascopé, Member, IEEE, and
More informationCHAPTER 3. SINGLE-STAGE PFC TOPOLOGY GENERALIZATION AND VARIATIONS
CHAPTER 3. SINGLE-STAGE PFC TOPOLOG GENERALIATION AND VARIATIONS 3.1. INTRODUCTION The original DCM S 2 PFC topology offers a simple integration of the DCM boost rectifier and the PWM DC/DC converter.
More information16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, VARIATION OF HARMONICS AND RIPPLE WITH PULSE NUMBER Pulse Number
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 693 Novel 24-Pulse Rectifier Topology based on Single 3-Phase to Four 3-Phase Transformation using Conventional Transformers for Phase Shifting
More informationTHREE-PHASE REDUCED TWO SWITCH HIGH POWER FACTOR BUCK-TYPE RECTIFIER
THREE-PHASE REDUCED TWO SWITCH HIGH POWER FACTOR BUCK-TYPE RECTIFIER D.Karthikraj 1, A.Sivakumar 2, C.Mahendraraj 3 and Dr.M.Sasikumar 4 1,2,3 PG Scholar, Jeppiaar Engineering College, Chennai, Tamilnadu,
More informationNew 24-Pulse Diode Rectifier Systems for Utility Interface of High-Power AC Motor Drives
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 33, NO. 2, MARCH/APRIL 1997 531 New 24-Pulse Diode Rectifier Systems for Utility Interface of High-Power AC Motor Drives Sewan Choi, Member, IEEE, Bang
More informationAn Active Interphase Transformer for 12-Pulse Rectifier System to Get the Performance Like 24- Pulse Rectifier System
An Active Interphase Transformer for 12-Pulse Rectifier System to Get the Performance Like 24- Pulse Rectifier System Milan Anandpara Tejas Panchal Vinod Patel Deaprtment of Electrical Engineering Deaprtment
More informationThree-phase Rectifier Using a Sepic DC-DC Converter in Continuous Conduction Mode for Power Factor Correction
20-r Three-phase Rectifier Using a Sepic C-C Converter in Continuous Conduction Mode for Power Factor Correction enizar C. Martins, Anderson H. de Oliveira and Ivo Barbi Federal University of Santa Catarina
More informationTHREE-PHASE converters are used to handle large powers
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 14, NO. 6, NOVEMBER 1999 1149 Resonant-Boost-Input Three-Phase Power Factor Corrector Da Feng Weng, Member, IEEE and S. Yuvarajan, Senior Member, IEEE Abstract
More informationPower Quality Improvement using a 28-pulse AC-DC Converter for SMPS
International Journal of Electrical Engineering. ISSN 0974-2158 Volume 5, Number 3 (2012), pp. 255-263 International Research Publication House http://www.irphouse.com Power Quality Improvement using a
More informationCHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL
14 CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL 2.1 INTRODUCTION Power electronics devices have many advantages over the traditional power devices in many aspects such as converting
More informationA THREE-PHASE THREE-SWITCH TWO-LEVEL PWM RECTIFIER
A THREE-PHASE THREE-SWTCH TWO-LEVEL PWM RECTFER Deivis Borgonovo, Yales RBmulo de Novaes, vo Barbi (Senior Member, EEE) Federal University of Santa Catarina - Department of Electrical Engineering - Power
More informationImprovement of Power Quality by Using 28-Pulse AC-DC Converter
Improvement of Power Quality by Using 28-Pulse AC-DC Converter 1 T. Suvarthan Rao, 2 A. Tejasri 1,2 Dept. of EEE, Godavari Institute of Engineering & Technology, Rajahmundry, AP, India Abstract With the
More informationChapter 2 Shunt Active Power Filter
Chapter 2 Shunt Active Power Filter In the recent years of development the requirement of harmonic and reactive power has developed, causing power quality problems. Many power electronic converters are
More informationTHE KURII CIRCUIT: A HIGH POWER FACTOR AND LOW COST THREE-PHASE RECTIFIER
THE KURII CIRCUIT: A HIGH POWER FACTOR AND LOW COST THREE-PHASE RECTIFIER Ewaldo L. M. Mehl Ivo Barbi Universidade Federal do Paraná Universidade Federal de Santa Catarina Departamento de Engenharia Elétrica
More informationA Novel Bridgeless Single-Stage Half-Bridge AC/DC Converter
A Novel Bridgeless Single-Stage Half-Bridge AC/DC Converter Woo-Young Choi 1, Wen-Song Yu, and Jih-Sheng (Jason) Lai Virginia Polytechnic Institute and State University Future Energy Electronics Center
More informationA Primary Side Clamping Circuit Applied to the ZVS-PWM Asymmetrical Half-Bridge Converter
A Primary Side Clamping Circuit Applied to the ZVS-PWM Asymmetrical Half-Bridge Converter Marcel0 Lobo Heldwein, Alexandre Ferrari de Souza and vo Barbi Power Electronics nstitute Dept. of Electrical Engineering
More informationTO LIMIT degradation in power quality caused by nonlinear
1152 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 13, NO. 6, NOVEMBER 1998 Optimal Current Programming in Three-Phase High-Power-Factor Rectifier Based on Two Boost Converters Predrag Pejović, Member,
More informationA Predictive Control Strategy for Power Factor Correction
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 8, Issue 6 (Nov. - Dec. 2013), PP 07-13 A Predictive Control Strategy for Power Factor Correction
More informationA Simple Control Strategy Applied to Three-phase Rectifier Units for Telecommunication Applications Using Single-phase Rectifier Modules
A Simple Control Strategy Applied to Three-phase Rectifier Units for Telecommunication Applications Using Single-phase Rectifier Modules Marcel0 Lobo Heldwein, Alexandre Ferrari de Souza and Ivo Barbi
More informationPower Factor Correction of Non-Linear Loads Employing a Single Phase Active Power Filter: Control Strategy, Design Methodology and Experimentation
~ Power Factor Correction of Non-Linear Loads Employing a Single Phase Active Power Filter: Control Strategy, Design Methodology and Experimentation Fabiana Pottker and vo Barbi Federal University of Santa
More informationSimplified Control Technique for Three-Phase Rectifier PFC Based on the Scott Transformer
IEEE ISIE 2006, July 9-12, 2006, Montreal, Quebec, Canada Simplified Control Technique for Three-Phase Rectifier PFC Based on the Scott Transformer A.A. Badin* and I. Barbi** Federal University of Santa
More informationMulti-Pulse Converters for High Voltage and High Power Applications. 2.1 Operating Principles
Multi-Pulse Converters for High Voltage and High Power Applications Sewan Choi, Junyong Oh Seoul National Univ. of Technology Dept. of Control and Instrumentation Eng. 72 Kongnung-Dong, Nowon-Guy Seoul
More informationCHAPTER 2 GENERAL STUDY OF INTEGRATED SINGLE-STAGE POWER FACTOR CORRECTION CONVERTERS
CHAPTER 2 GENERAL STUDY OF INTEGRATED SINGLE-STAGE POWER FACTOR CORRECTION CONVERTERS 2.1 Introduction Conventional diode rectifiers have rich input harmonic current and cannot meet the IEC PFC regulation,
More informationMUCH effort has been exerted by researchers all over
IEEE TRANSACTIONS ON CIRCUITS AND SYSTEMS I: REGULAR PAPERS, VOL. 52, NO. 10, OCTOBER 2005 2219 A ZVS PWM Inverter With Active Voltage Clamping Using the Reverse Recovery Energy of the Diodes Marcello
More informationVoltage Fed DC-DC Converters with Voltage Doubler
Chapter 3 Voltage Fed DC-DC Converters with Voltage Doubler 3.1 INTRODUCTION The primary objective of the research pursuit is to propose and implement a suitable topology for fuel cell application. The
More informationA Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 16, NO. 5, SEPTEMBER 2001 603 A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions
More informationZero Voltage Switching Scheme for Flyback Converter to Ensure Compatibility with Active Power Decoupling Capability
Zero oltage Switching Scheme for Flyback Converter to Ensure Compatibility with Active Power Decoupling Capability Hiroki Watanabe 1*, Jun-ichi toh 1 1 Department of Electrical, Electronics and nformation
More informationA Novel Single-Stage Push Pull Electronic Ballast With High Input Power Factor
770 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 48, NO. 4, AUGUST 2001 A Novel Single-Stage Push Pull Electronic Ballast With High Input Power Factor Chang-Shiarn Lin, Member, IEEE, and Chern-Lin
More informationELEC387 Power electronics
ELEC387 Power electronics Jonathan Goldwasser 1 Power electronics systems pp.3 15 Main task: process and control flow of electric energy by supplying voltage and current in a form that is optimally suited
More informationAnalysis of Utility Interactive Photovoltaic Generation System using a Single Power Static Inverter
Asian J. Energy Environ., Vol. 5, Issue 2, (2004), pp. 115-137 Analysis of Utility Interactive Photovoltaic Generation System using a Single Power Static Inverter D. C. Martins*, R. Demonti, A. S. Andrade
More informationLecture 19 - Single-phase square-wave inverter
Lecture 19 - Single-phase square-wave inverter 1. Introduction Inverter circuits supply AC voltage or current to a load from a DC supply. A DC source, often obtained from an AC-DC rectifier, is converted
More informationA THREE-PHASE HIGH POWER FACTOR TWO-SWITCH BUCK- TYPE CONVERTER
A THREE-PHASE HIGH POWER FACTOR TWO-SWITCH BUCK- TYPE CONVERTER SEEMA.V. 1 & PRADEEP RAO. J 2 1,2 Electrical and Electronics, The Oxford College of Engineering, Bangalore-68, India Email:Seema.aish1@gmail.com
More informationLiterature Review. Chapter 2
Chapter 2 Literature Review Research has been carried out in two ways one is on the track of an AC-AC converter and other is on track of an AC-DC converter. Researchers have worked in AC-AC conversion
More informationA Power Electronic Transformer (PET) fed Nine-level H-Bridge Inverter for Large Induction Motor Drives
IEEE Industrial Applications Society Annual Meeting Page of 7 A Power Electronic Transformer (PET) fed Nine-level H-Bridge Inverter for Large Induction Motor Drives Rick Kieferndorf Giri Venkataramanan
More informationSINGLE STAGE LOW FREQUENCY ELECTRONIC BALLAST FOR HID LAMPS
SINGLE STAGE LOW FREQUENCY ELECTRONIC BALLAST FOR HID LAMPS SUMAN TOLANUR 1 & S.N KESHAVA MURTHY 2 1,2 EEE Dept., SSIT Tumkur E-mail : sumantolanur@gmail.com Abstract - The paper presents a single-stage
More informationSingle switch three-phase ac to dc converter with reduced voltage stress and current total harmonic distortion
Published in IET Power Electronics Received on 18th May 2013 Revised on 11th September 2013 Accepted on 17th October 2013 ISSN 1755-4535 Single switch three-phase ac to dc converter with reduced voltage
More informationFabiana Pottker de Soma and Ivo Barbi
Power Factor Correction of Linear and Non-linear Loads Employing a Single Phase Active Power Filter Based on a Full-Bridge Current Source Inverter Controlled Through the Sensor of the AC Mains Current
More informationTHE CONVENTIONAL voltage source inverter (VSI)
134 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 14, NO. 1, JANUARY 1999 A Boost DC AC Converter: Analysis, Design, and Experimentation Ramón O. Cáceres, Member, IEEE, and Ivo Barbi, Senior Member, IEEE
More informationThree Phase Power Factor Corrected Isolated Buck for 48V/100A Rectifier with Secondary Active Clamp
7- Three Phase Power Factor Corrected solated Buck for 48V/100A Rectifier with Secondary Active Clamp Robert Sheehy, Jurien Dekter and Nigel Machin Rectifier Technologies, Melbourne, Australia mail: information@rtp.com.au
More informationA 1.2 kw Electronic Ballast for Multiple Lamps, with Dimming Capability and High-Power-Factor
A.2 kw Electronic Ballast for Multiple Lamps, with Dimming Capability and High-Power-Factor Roger Gules and vo Barbi Federal University of Santa Catarina -UFSC Power Electronic nstitute - NEP P.O. Box
More informationRESONANT CIRCUIT MODEL AND DESIGN FOR A HIGH FREQUENCY HIGH VOLTAGE SWITCHED-MODE POWER SUPPLY
RESONANT CIRCUIT MODEL AND DESIGN FOR A HIGH FREQUENCY HIGH VOLTAGE SWITCHED-MODE POWER SUPPLY Gleyson L. Piazza, Ricardo L. Alves 2, Carlos H. Illa Font 3 and Ivo Barbi 3 Federal Institute of Santa Catarina,
More informationCHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS
86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the
More informationI. INTRODUCTION. 10
Closed-loop speed control of bridgeless PFC buck- boost Converter-Fed BLDC motor drive Sanjay S Siddaganga Institute Of Technology/Electrical & Electronics, Tumkur, India Email: sanjayshekhar04@gmail.com
More informationA Three-Phase AC-AC Buck-Boost Converter using Impedance Network
A Three-Phase AC-AC Buck-Boost Converter using Impedance Network Punit Kumar PG Student Electrical and Instrumentation Engineering Department Thapar University, Patiala Santosh Sonar Assistant Professor
More informationSCOTT TRANSFORMER AND DIODE CLAMPED INVERTER FED INDUCTION MOTOR BASED ON FOC
RESEARCH ARTICLE OPEN ACCESS SCOTT TRANSFORMER AND DIODE CLAMPED INVERTER FED INDUCTION MOTOR BASED ON FOC 1, Ms. Snehal M. Khobragade, 2, Prof.B.S.Dani Mtech(IDC) pursuing Priyadarshini college of Engineering
More informationA Novel Concept in Integrating PFC and DC/DC Converters *
A Novel Concept in Integrating PFC and DC/DC Converters * Pit-Leong Wong and Fred C. Lee Center for Power Electronics Systems The Bradley Department of Electrical and Computer Engineering Virginia Polytechnic
More informationA Comparative Modelling Study of PWM Control Techniques for Multilevel Cascaded Inverter
A Comparative Modelling Study of PWM Control Techniques for Multilevel Cascaded Inverter Applied Power Electronics Laboratory, Department of Electrotechnics, University of Sciences and Technology of Oran,
More informationHighly-Reliable Fly-back-based PV Micro-inverter Applying Power Decoupling Capability without Additional Components
Highly-Reliable Fly-back-based P Micro-inverter Applying Power Decoupling Capability without Additional Components Hiroki Watanabe, Nagaoka University of technology, Japan, hwatanabe@stn.nagaopkaut.ac.jp
More informationA New Three-Phase Interleaved Isolated Boost Converter With Solar Cell Application. K. Srinadh
A New Three-Phase Interleaved Isolated Boost Converter With Solar Cell Application K. Srinadh Abstract In this paper, a new three-phase high power dc/dc converter with an active clamp is proposed. The
More informationBLDC Motor Speed Control and PFC Using Isolated Zeta Converter
BLDC Motor Speed Control and PFC Using Isolated Zeta Converter Vimal M 1, Sunil Kumar P R 2 PG Student, Dept. of EEE. Government Engineering College Idukki, India 1 Asst. Professor, Dept. of EEE Government
More informationA New Single-Phase PFC Rectifier (TOKUSADA Rectifier ) with Wide Output Voltage Control Range and High Efficiency
A New Single-Phase PFC Rectifier (TOKUSADA Rectifier ) with Wide Output Voltage Control Range and High Efficiency Yasuyuki Nishida & Takeshi Kondou Nihon University Tokusada, Tamura-cho, Kouriyama, JAPAN
More informationNeuro Fuzzy Control Single Stage Single Phase AC-DC Converter for High Power factor
Neuro Fuzzy Control Single Stage Single Phase AC-DC Converter for High Power factor S. Lakshmi Devi M.Tech(PE),Department of EEE, Prakasam Engineering College,Kandukur,A.P K. Sudheer Assoc. Professor,
More informationStudent Department of EEE (M.E-PED), 2 Assitant Professor of EEE Selvam College of Technology Namakkal, India
Design and Development of Single Phase Bridgeless Three Stage Interleaved Boost Converter with Fuzzy Logic Control System M.Pradeep kumar 1, M.Ramesh kannan 2 1 Student Department of EEE (M.E-PED), 2 Assitant
More information12-Pulse Rectifier for More Electric Aircraft Applications
12-Pulse Rectifier for More Electric Aircraft Applications G. Gong, U. Drofenik and J.W. Kolar ETH Zurich, Power Electronic Systems Laboratory ETH Zentrum / ETL H23, Physikstr. 3, CH-892 Zurich / SWITZERLAND
More informationA Fuel Cell Fed Single Stage Boost Inverter with Unique Impedance Network
A Fuel Cell Fed Single Stage Boost Inverter with Unique Impedance Network K.Sruthi 1, C.B Saravanan 2 PG Student [PE&ED], Dept. of EEE, SVCET, Chittoor, Andhra Pradesh, India 1 Associate professor, Dept.
More informationPower Factor Corrected Single Stage AC-DC Full Bridge Resonant Converter
Power Factor Corrected Single Stage AC-DC Full Bridge Resonant Converter Gokul P H Mar Baselios College of Engineering Mar Ivanios Vidya Nagar, Nalanchira C Sojy Rajan Assisstant Professor Mar Baselios
More informationA Color LED Driver Implemented by the Active Clamp Forward Converter
A Color LED Driver Implemented by the Active Clamp Forward Converter C. H. Chang, H. L. Cheng, C. A. Cheng, E. C. Chang * Power Electronics Laboratory, Department of Electrical Engineering I-Shou University,
More informationLinear Transformer based Sepic Converter with Ripple Free Output for Wide Input Range Applications
Linear Transformer based Sepic Converter with Ripple Free Output for Wide Input Range Applications Karthik Sitapati Professor, EEE department Dayananda Sagar college of Engineering Bangalore, India Kirthi.C.S
More informationPower Quality Improvement by Input Current Harmonic Reduction Using Three-Phase Multi-Pulse AC-DC Converter
Power Quality Improvement by Input Current Harmonic Reduction Using Three-Phase Multi-Pulse AC-DC Converter Sanjeev Kumar Rajoria M.Tech. Scholar, Power System, SKIT, Jaipur. Bharat Modi Reader, Department
More informationPower Factor Correction for Chopper Fed BLDC Motor
ISSN No: 2454-9614 Power Factor Correction for Chopper Fed BLDC Motor S.Dhamodharan, D.Dharini, S.Esakki Raja, S.Steffy Minerva *Corresponding Author: S.Dhamodharan E-mail: esakkirajas@yahoo.com Department
More informationA SINGLE STAGE HIGH POWER FACTOR 3 PHASE 60V/100A POWER SUPPLY USING A LINE-SIDE INTERPHASE TRANSFORMER AND AN ISOLATED PUSH-PULL CONVERTER
A SNGLE STAGE HGH POWER FACTOR 3 PHASE 60V/100A POWER SUPPLY USNG A LNE-SDE NTERPHASE TRANSFORMER AND AN SOLATED PUSH-PULL CONVERTER Wilson C. P. de Aragiio Filho, Member EEE Universidade Federal do Espirito
More informationNovelty Technique for Power factor Improvement by a Single phase Rectifier
162 Novelty Technique for Power factor Improvement by a Single phase Rectifier Baby.M 1, Poorinima.S 2, Bharani Prakash.T 3, Sudarsan.S 4 Abstract A new technique is implemented to improve the input power
More informationA Novel Three-Phase Interleaved Isolated Boot Converter With Active Clamp For Fuel Cells
A Novel Three-Phase Interleaved Isolated Boot Converter With Active Clamp For Fuel Cells Md.Karima* 1 ; Shareef Shaik 2 & Dr. Abdul Ahad 3 1 M.tech (P&ID) Student Department Of EEE, Nimra College Of Engineering
More informationPower Factor Correction of LED Drivers with Third Port Energy Storage
Power Factor Correction of LED Drivers with Third Port Energy Storage Saeed Anwar Mohamed O. Badawy Yilmaz Sozer sa98@zips.uakron.edu mob4@zips.uakron.edu ys@uakron.edu Electrical and Computer Engineering
More informationRECENTLY, the harmonics current in a power grid can
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 2, MARCH 2008 715 A Novel Three-Phase PFC Rectifier Using a Harmonic Current Injection Method Jun-Ichi Itoh, Member, IEEE, and Itsuki Ashida Abstract
More informationUnderstanding Input Harmonics and Techniques to Mitigate Them
Understanding Input Harmonics and Techniques to Mitigate Them Mahesh M. Swamy Yaskawa Electric America YASKAWA Page. 1 Organization Introduction Why FDs Generate Harmonics? Harmonic Limit Calculations
More informationComparison Between two Single-Switch Isolated Flyback and Forward High-Quality Rectifiers for Low Power Applications
Comparison Between two ingle-witch Isolated Flyback and Forward High-Quality Rectifiers for Low Power Applications G. piazzi,. Buso Department of Electronics and Informatics - University of Padova Via
More informationSLIDING MODE CONTROLLER FOR THE BOOST INVERTER
SLIDING MODE CONTROLLER FOR THE BOOST INVERTER Cuernavaca, I&XICO October 14-17 Ram6n Chceres Universidad de 10s Andes Facultad de Ingenieria Dpto. de Electronica MCrida - Edo. MCrida - Venezuela. E-mail:
More informationExperimental Verification of High Frequency Link DC-AC Converter using Pulse Density Modulation at Secondary Matrix Converter.
Experimental erification of High Frequency Link DC-AC Converter using Pulse Density Modulation at Secondary Matrix Converter. Jun-ichi Itoh, Ryo Oshima and Hiroki Takahashi Dept. of Electrical, Electronics
More informationAN IMPROVED ZERO-VOLTAGE-TRANSITION INTERLEAVED BOOST CONVERTER WITH HIGH POWER FACTOR
AN IMPROVED ZERO-VOLTAGE-TRANSITION INTERLEAVED BOOST CONVERTER WITH HIGH POWER FACTOR Naci GENC 1, Ires ISKENDER 1 1 Gazi University, Faculty of Engineering and Architecture, Department of Electrical
More information466 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 13, NO. 3, MAY A Single-Switch Flyback-Current-Fed DC DC Converter
466 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 13, NO. 3, MAY 1998 A Single-Switch Flyback-Current-Fed DC DC Converter Peter Mantovanelli Barbosa, Member, IEEE, and Ivo Barbi, Senior Member, IEEE Abstract
More informationPERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL
Journal of Engineering Science and Technology Vol. 10, No. 4 (2015) 420-433 School of Engineering, Taylor s University PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT
More informationA HIGH RELIABILITY SINGLE-PHASE BOOST RECTIFIER SYSTEM FOR DIFFERENT LOAD VARIATIONS. Prasanna Srikanth Polisetty
GRT A HIGH RELIABILITY SINGLE-PHASE BOOST RECTIFIER SYSTEM FOR DIFFERENT LOAD VARIATIONS Prasanna Srikanth Polisetty Department of Electrical and Electronics Engineering, Newton s College of Engineering
More informationImproved Power Quality Bridgeless Isolated Cuk Converter Fed BLDC Motor Drive
Improved Power Quality Bridgeless Isolated Cuk Converter Fed BLDC Motor Drive 1 Midhun Mathew John, 2 Phejil K Paul 1 PG Scholar, 2 Assistant Professor, 1 Electrical and Electronics Engineering 1 Mangalam
More informationCHAPTER 6 ANALYSIS OF THREE PHASE HYBRID SCHEME WITH VIENNA RECTIFIER USING PV ARRAY AND WIND DRIVEN INDUCTION GENERATORS
73 CHAPTER 6 ANALYSIS OF THREE PHASE HYBRID SCHEME WITH VIENNA RECTIFIER USING PV ARRAY AND WIND DRIVEN INDUCTION GENERATORS 6.1 INTRODUCTION Hybrid distributed generators are gaining prominence over the
More informationMODERN switching power converters require many features
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 1, JANUARY 2004 87 A Parallel-Connected Single Phase Power Factor Correction Approach With Improved Efficiency Sangsun Kim, Member, IEEE, and Prasad
More informationCHAPTER 3 H BRIDGE BASED DVR SYSTEM
23 CHAPTER 3 H BRIDGE BASED DVR SYSTEM 3.1 GENERAL The power inverter is an electronic circuit for converting DC power into AC power. It has been playing an important role in our daily life, as well as
More informationA Modular Single-Phase Power-Factor-Correction Scheme With a Harmonic Filtering Function
328 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 50, NO. 2, APRIL 2003 A Modular Single-Phase Power-Factor-Correction Scheme With a Harmonic Filtering Function Sangsun Kim, Member, IEEE, and Prasad
More informationA Phase-Controlled 12-Pulse Rectifier with Unity Displacement Factor without Phase Shifting Transformer
A Phase-Controlled 12-Pulse Rectifier with Unity Displacement Factor without Phase Shifting Transformer Yeddo B. Blauth Federal University of Rio Grande do Sul Electrical Engineering Department - DELET
More informationSingle Phase Bridgeless SEPIC Converter with High Power Factor
International Journal of Emerging Engineering Research and Technology Volume 2, Issue 6, September 2014, PP 117-126 ISSN 2349-4395 (Print) & ISSN 2349-4409 (Online) Single Phase Bridgeless SEPIC Converter
More informationA Comparative Study between DPC and DPC-SVM Controllers Using dspace (DS1104)
International Journal of Electrical and Computer Engineering (IJECE) Vol. 4, No. 3, June 2014, pp. 322 328 ISSN: 2088-8708 322 A Comparative Study between DPC and DPC-SVM Controllers Using dspace (DS1104)
More informationCurrent Rebuilding Concept Applied to Boost CCM for PF Correction
Current Rebuilding Concept Applied to Boost CCM for PF Correction Sindhu.K.S 1, B. Devi Vighneshwari 2 1, 2 Department of Electrical & Electronics Engineering, The Oxford College of Engineering, Bangalore-560068,
More informationDr.Arkan A.Hussein Power Electronics Fourth Class. Operation and Analysis of the Three Phase Fully Controlled Bridge Converter
Operation and Analysis of the Three Phase Fully Controlled Bridge Converter ١ Instructional Objectives On completion the student will be able to Draw the circuit diagram and waveforms associated with a
More informationGENERALLY, a single-inductor, single-switch boost
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 1, JANUARY 2004 169 New Two-Inductor Boost Converter With Auxiliary Transformer Yungtaek Jang, Senior Member, IEEE, Milan M. Jovanović, Fellow, IEEE
More informationDIRECT TORQUE CONTROL OF THREE PHASE INDUCTION MOTOR BY USING FOUR SWITCH INVERTER
DIRECT TORQUE CONTROL OF THREE PHASE INDUCTION MOTOR BY USING FOUR SWITCH INVERTER Mr. Aniket C. Daiv. TSSM's BSCOER, Narhe ABSTRACT Induction motor proved its importance, since its invention and has been
More informationA HIGHLY EFFICIENT ISOLATED DC-DC BOOST CONVERTER
A HIGHLY EFFICIENT ISOLATED DC-DC BOOST CONVERTER 1 Aravind Murali, 2 Mr.Benny.K.K, 3 Mrs.Priya.S.P 1 PG Scholar, 2 Associate Professor, 3 Assistant Professor Abstract - This paper proposes a highly efficient
More informationFirst characteristic harmonic component of output ripple on dc railway rectifiers
First characteristic harmonic component of output ripple on dc railway rectifiers J. Allan, J. H. Jin & K. Payne ^ The University ofbirmingham, UK. ^London Underground Limited, UK. Abstract A research
More informationElectrical Distribution System with High power quality Based on Power Electronic Transformer
Electrical Distribution System with High power quality Based on Power Electronic Transformer Dr. Raaed Faleh Hassan Assistant Professor, Dept. of medical Instrumentation Eng. Techniques college of Electrical
More informationDesign Criteria for Sepic and Cuk Converters as Power Factor Preregulators in Discontinuous Conduction Mode
Design Criteria for Sepic and Cuk Converters as Power Factor Preregulators in Discontinuous Conduction Mode D.S.L. Simonetti, J. Sebastiin, F. S. dos Reis and J. Uceda * Division de Electronica - E.T.S.I.
More informationA Three-Phase Buck Rectifier with High-Frequency Isolation by Single-Stage
A Three-Phase Buck Rectifier with High-Frequency Isolation by Single-Stage D. S. Greff, R. da Silva, S. A. Mussa, A. Perin and I. Barbi Federal University of Santa Caratina Power Electronics Institute-INEP
More informationSHUNT ACTIVE POWER FILTER
75 CHAPTER 4 SHUNT ACTIVE POWER FILTER Abstract A synchronous logic based Phase angle control method pulse width modulation (PWM) algorithm is proposed for three phase Shunt Active Power Filter (SAPF)
More informationKeywords: Forward Boost Converter, SMPS, Power Factor Correction, Power Quality, Efficiency.
www.semargroups.org, www.ijsetr.com ISSN 2319-8885 Vol.02,Issue.19, December-2013, Pages:2243-2247 Power Quality Improvement in Multi-Output Forward Boost Converter NARLA KOTESWARI 1, V. MADHUSUDHAN REDDY
More informationDesign and Simulation of New Efficient Bridgeless AC- DC CUK Rectifier for PFC Application
Design and Simulation of New Efficient Bridgeless AC- DC CUK Rectifier for PFC Application Thomas Mathew.T PG Student, St. Joseph s College of Engineering, C.Naresh, M.E.(P.hd) Associate Professor, St.
More information