New solution for feeder earth-fault protection

Size: px
Start display at page:

Download "New solution for feeder earth-fault protection"

Transcription

1 Application Note New solution to feeder earth-fault protection 1 (8) APPLICATION NOTE New solution for feeder earth-fault protection AQ-200 IED series

2 Application Note New solution to feeder earth-fault protection 2 (8) The Problem The increase of medium voltage cabling, connection of distributed generation and compensated networks (Petersen coil) along with distributed compensation has led to new challenges in earth-fault protection of distribution feeders. Challenging combinations of short cable feeders, long overhead feeders and mixed cable and overhead network is increasing significantly among distribution system operators and relaying on conventional protection methods may lead to either nuisance trips of healthy feeders or undetected faults in faulty feeders. New earth-fault protection methods have been researched with aim to improve the dependability of the protection. These new methods have often required additional hardware thus increasing the cost and reducing the mean time between failure. Another drawback has been difficulty in selecting the relay settings as additional network data has often been required. This application note describes Arcteq s novel method to increase the sensitivity of the earth-fault protection without any additional hardware. The implementation does not require any additional settings of the protected network either. Traditional operating modes of directional earth-fault protection Arcteq s AQ 200 series IEDs have different operating modes for feeder directional earthfault protection. The traditionally available modes are Unearthed, Petersen Coil Grounded and Grounded. When unearthed (capacitive) network mode is chosen the IED expects the fault current to be lagging zero sequence voltage by 90 degrees. Healthy phases of healthy feeders produce capacitive current during ground fault just like faulty feeder but current is flowing towards busbar and trough incoming transformer or grounding transformer to faulty feeder. Healthy feeders do not trip since capacitive current is flowing to opposite direction and selective tripping can be ensured. When Petersen coil grounded (compensated) network mode is chosen the IED expects the fault current to be opposite direction to zero sequence voltage. Healthy phases of healthy feeders and faulty feeder produce capacitive current similar to unearthed network. Inductance of Petersen coil is compensating the capacitive current and therefore residual current in fault location is close to zero. Size of the inductance is chosen according the

3 Application Note New solution to feeder earth-fault protection 3 (8) prospective earth fault current of the network. Desired compensation grade is achieved when k-factor is close to 1.0 and network is fully compensated. Network is over compensated when k-factor is greater than one and under compensated if the factor is smaller than one. Inductance connected to the star point of incoming transformer or like in most cases to grounding transformer compensates the capacitance of the network but due this the capacitive fault current cannot be measured anymore. Fault detection is handled by connecting a resistance on parallel with the inductance. This resistance defines the amplitude of fault current. In under or over compensated situations the resistive component during the fault does not change, therefore selective tripping is ensured even if the network is bit under or over compensated. Below figure 1 shows the operating areas of traditional Unearthed and Petersen coil grounded modes. For more details refer to AQ 200 series instruction manuals. Figure 1 Traditional directional earth-fault protection modes

4 Application Note New solution to feeder earth-fault protection 4 (8) New broad range mode with multi-criteria detection When protecting compensated long-distance cables and overhead lines it is in some cases difficult to distinguish between healthy- and faulty feeder. Merely measuring the angle and magnitude of residual voltage and currents is not always enough, but changes in symmetrical components of phase currents and voltages are also needed. Also, when protecting feeders from earth faults two modes are used depending on the network status (ungrounded or compensated). When changing between these two statuses setting group must be changed and especially in case of distributed compensation the change may be difficult or impossible to arrange. Lastly, in a compensated network protection, the relay with traditional algorithms may sporadically detect an earth-fault in a long healthy feeder due to CT errors. For all of these reasons, Arcteq has developed an improved alternative to these traditional directional earth fault protections. Figure 2 Operation of new broad range mode covers both ungrounded and compensated networks and is equipped with optional additional multi-criteria detection for compensated networks to increase the protection sensitivity New broad range mode is capable of protecting against earth-fault in both ungrounded and compensated networks not only by just combining the two stages together but using a new multi-criteria detection. This optional additional tripping condition for compensated networks uses Arcteq s patented, high-resolution intermittent earth-fault algorithm with added

5 Application Note New solution to feeder earth-fault protection 5 (8) symmetrical component calculation of phase currents and voltages. If this mode is activated the tripping criteria comprises of a measured residual current in the fourth quadrant and the symmetrical components of voltages and currents detecting a fault. No extra parameterization is required compared to traditional method. Multi-criteria algorithm can be tested with Comtrade files supplied by Arcteq. Function requires connection of 3-phase currents, residual current and residual voltage to operate correctly. To avoid unnecessary trips encroachment area against I0 CT errors in compensated long healthy lines can be added. Figure 3 Screen capture of new broad range earth fault protection stage settings with added multi-criteria detection. Setting of this protection mode requires no additional network parameters and can be tested with comtrade files supplied by Arcteq.

6 Application Note New solution to feeder earth-fault protection 6 (8) Research results The new multi-criteria earth-fault detection method has been researched using simulated PSCAD software models. Different type of networks including distributed compensation and mix network have been modeled and the new multi-criteria detection algorithm has been operating satisfactorily in these simulations. Below simulation captures show an example of mixed network where traditional earth-fault algorithms are not able to trip but Arcteq s multi-criteria detection is able to clear the fault correctly. Figure 4 Example of simulated mixed network substation with end of line fault.

7 Application Note New solution to feeder earth-fault protection 7 (8) Figure 5 Simulation result with end of line fault in mixed network. Traditional earth-fault protection would not trip but Arcteq s new multi-criteria detection is able to trip on fault and is not operating on healthy feeders Intermittent / transient earth-fault protection For a complete coverage of feeder earth-faults in compensated networks, the intermittent / transient type of earth-faults are to be protected by Arcteq s patented intermittent earth-fault protection stage available in the AQ 200 series feeder protection IEDs. For more information refer to AQ 200 series instruction manuals and intermittent earth-fault guide at and

8 Application Note New solution to feeder earth-fault protection 8 (8) REFERENCE INFORMATION Manufacturer information: Arcteq Relays Ltd. Finland Visiting and postal address: Wolffintie 36 F Vaasa, Finland Contacts: Phone, general and commercial issues (office hours GMT +2): Fax: url: sales: sales@arcteq.fi technical support: support@arcteq.fi ARCTEQ SUPPORT LINE EET 8:00 16:00.

Intermittent transient earth fault protection

Intermittent transient earth fault protection Intermittent transient earth fault protection The directional intermittent transient earth fault protection is used to detect short intermittent transient faults in compensated cable networks (figure 3).

More information

APPLICATION OF MULTI-FREQUENCY ADMITTANCE-BASED FAULT PASSAGE INDICATION IN PRACTICAL COMPENSATED MV-NETWORK

APPLICATION OF MULTI-FREQUENCY ADMITTANCE-BASED FAULT PASSAGE INDICATION IN PRACTICAL COMPENSATED MV-NETWORK 24 th International Conference on Electricity Distribution Glasgow, 2-5 June 27 Paper 967 APPLICATION OF MULTI-FREQUENC ADMITTANCE-BASED FAULT PASSAGE INDICATION IN PRACTICAL COMPENSATED MV-NETWORK Janne

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

PROTECTION of electricity distribution networks

PROTECTION of electricity distribution networks PROTECTION of electricity distribution networks Juan M. Gers and Edward J. Holmes The Institution of Electrical Engineers Contents Preface and acknowledgments x 1 Introduction 1 1.1 Basic principles of

More information

NEW METHOD FOR HIGH-IMPEDANCE FAULT DETECTION

NEW METHOD FOR HIGH-IMPEDANCE FAULT DETECTION NEW METHOD FOR HIGH-IMPEDANCE FAULT DETECTION ABSTRACT Hannu LAAKSONEN ABB Oy Finland hannu.laaksonen@fi.abb.com Correct detection of high-impedance faults (HIFs) is crucial because they produce a serious

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK

VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK Eduardo MARTÍNEZ eduardo_martinez@fcirce.es Samuel BORROY sborroy@fcirce.es Laura

More information

WHY DOES THE EARTH FAULT DETECTION METHOD BASED ON 3RD HARMONIC WORK IN LARGE MESHED 110-KV-NETWORKS

WHY DOES THE EARTH FAULT DETECTION METHOD BASED ON 3RD HARMONIC WORK IN LARGE MESHED 110-KV-NETWORKS WHY DOES THE ERTH FULT DETETION METHOD SED ON 3RD HRMONI WORK IN LRGE MESHED 0-KV-NETWORKS Gernot DRUML Oliver SKRINJEK Uwe SHMIDT Peter SHEGNER Lothar FIKERT Sprecher utomation - Energie Steiermark -

More information

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS A. Nikander*, P. Järventausta* *Tampere University of Technology, Finland, ari.nikander@tut.fi,

More information

Phase earthing system - method for faulty phase selection with phase-to-earth faults. Ari Nikander Tampere University of Technology

Phase earthing system - method for faulty phase selection with phase-to-earth faults. Ari Nikander Tampere University of Technology Phase earthing system - method for faulty phase selection with phase-to-earth faults Ari Nikander Tampere University of Technology - 2 - Preface This report has been done as a part of the research work

More information

Fault Location in MV Unearthed Distribution Network Using the Undamped Frequency of the Transient Signal

Fault Location in MV Unearthed Distribution Network Using the Undamped Frequency of the Transient Signal Fault Location in MV Unearthed Distribution Network Using the Undamped Frequency of the Transient Signal MOHD RAFI ADZMAN, MATTI LEHTONEN Department of Electrical Engineering, School of Science and Technology

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

Single Phase Earth Fault Location in the Medium Voltage Distribution Networks

Single Phase Earth Fault Location in the Medium Voltage Distribution Networks 1.2478/v1144-9-2-6 SCINTIFIC PROCDINGS OF RIG TCHNICL UNIVRSITY TH 5TH INTRNTIONL SCINTIFIC CONFRNC POWR ND LCTRICL NGINRING, OCTOBR 29 Single Phase arth Fault Location in the Medium Voltage Distribution

More information

ALI UMAIR DETECTION ALGORITHM FOR THE CROSS COUNTRY EARTH FAULTS IN MEDIUM VOLTAGE NETWORK

ALI UMAIR DETECTION ALGORITHM FOR THE CROSS COUNTRY EARTH FAULTS IN MEDIUM VOLTAGE NETWORK ALI UMAIR DETECTION ALGORITHM FOR THE CROSS COUNTRY EARTH FAULTS IN MEDIUM VOLTAGE NETWORK Masters of Science Thesis Examiner: Professor Pertti Järventausta and Dr Tech. Ari Nikander Examiner and topic

More information

Harmonic Distortion Levels Measured at The Enmax Substations

Harmonic Distortion Levels Measured at The Enmax Substations Harmonic Distortion Levels Measured at The Enmax Substations This report documents the findings on the harmonic voltage and current levels at ENMAX Power Corporation (EPC) substations. ENMAX is concerned

More information

MV Network Operation Issues and Elimination of Phase Voltage Unbalance

MV Network Operation Issues and Elimination of Phase Voltage Unbalance Transactions on Electrical Engineering, Vol. 6 (2017), No. 3 72 MV Network Operation Issues and Elimination of Phase Voltage Unbalance František Žák Analyst and Lecturer of the distribution network operation,

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding

More information

Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection

Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection Engineered Solutions for Power System Protection, Automaton and Control APPLICATION NOTE Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection 180622 Abstract This

More information

Summary of the Impacts of Grounding on System Protection

Summary of the Impacts of Grounding on System Protection Summary of the Impacts of Grounding on System Protection Grounding System grounding big impact on ability to detect ground faults Common ground options:» Isolated ground (ungrounded)» High impedance ground»

More information

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION 23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB

More information

A NEW APPROACH FOR AN EARTH FAULT DISTANCE LOCALISATION ALGORITHM IN COMPENSATED NETWORKS

A NEW APPROACH FOR AN EARTH FAULT DISTANCE LOCALISATION ALGORITHM IN COMPENSATED NETWORKS A NEW APPROACH FOR AN EARTH FAULT DISTANCE LOCALISATION ALGORITHM IN COMPENSATED NETWORKS Georg Achleitner, Clemens Obkircher, Lothar Fickert, Manfred Sakulin Graz University of Technology Inffeldgasse

More information

9 Overcurrent Protection for Phase and Earth Faults

9 Overcurrent Protection for Phase and Earth Faults Overcurrent Protection for Phase and Earth Faults Introduction 9. Co-ordination procedure 9.2 Principles of time/current grading 9.3 Standard I.D.M.T. overcurrent relays 9.4 Combined I.D.M.T. and high

More information

FAST SELECTIVE EARTH FAULT LOCALIZATION USING THE NEW FAST PULSE DETECTION METHOD

FAST SELECTIVE EARTH FAULT LOCALIZATION USING THE NEW FAST PULSE DETECTION METHOD FAST SELECTIVE EARTH FAULT LOCALIZATION USING THE NEW FAST PULSE DETECTION METHOD Gernot DRUML Christian RAUNIG Peter SCHEGNER Lothar FICKERT Trench Austria GmbH Austria TU Graz Austria TU Dresden Germany

More information

Complex Solution for the Distribution Substation REF 542plus. Application and Setting Guide

Complex Solution for the Distribution Substation REF 542plus. Application and Setting Guide Complex Solution for the Distribution Substation REF 542plus 1MRS756412 Complex Solution for the Distribution Substation REF 542plus Copyrights The information in this document is subject to change without

More information

- 1 - NEUTRAL CONNECTION TO EARTH IN MEDIUM VOLTAGE NETWORKS: OPERATION EXPERIENCE IN ENEL

- 1 - NEUTRAL CONNECTION TO EARTH IN MEDIUM VOLTAGE NETWORKS: OPERATION EXPERIENCE IN ENEL NEUTRAL CONNECTION TO EARTH IN MEDIUM VOLTAGE NETWORKS: OPERATION EXPERIENCE IN ENEL B. Ceresoli CESI S.p.A. - Italy A. Cerretti ENEL Distribuzione S.p.A - Italy E. De Berardinis CESI S.p.A - Italy A.

More information

Double Criteria Feeder-Selection Method for Single-Phase Ground Fault of Resonant Grounding System Based on Multi-State Components

Double Criteria Feeder-Selection Method for Single-Phase Ground Fault of Resonant Grounding System Based on Multi-State Components American Journal of Electrical and Electronic Engineering, 207, Vol. 5, No. 4, 44-5 Available online at http://pubs.sciepub.com/ajeee/5/4/4 Science and Education Publishing DOI:0.269/ajeee-5-4-4 Double

More information

ScienceDirect. Simulation Models for Various Neutral Earthing Methods in Medium Voltage Systems

ScienceDirect. Simulation Models for Various Neutral Earthing Methods in Medium Voltage Systems Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 1 (15 ) 118 1191 5th DAAAM International Symposium on Intelligent Manufacturing and Automation, DAAAM 1 Simulation Models for

More information

PRAOGEN, A TOOL FOR STUDYING CONNECTION OF GENERATING PLANT ONTO THE MEDIUM- VOLTAGE NETWORK

PRAOGEN, A TOOL FOR STUDYING CONNECTION OF GENERATING PLANT ONTO THE MEDIUM- VOLTAGE NETWORK PRAOGEN, A TOOL FOR STUDYING CONNECTION OF GENERATING PLANT ONTO THE MEDIUM- VOLTAGE NETWORK J.L. Fraisse, F. Boulanger, Ph. Juston, P. Lemerle, O. Jeannin EDF-DEGS; EDF-R&D, France Since early in 1990

More information

TESTING OF THE PERFORMANCE OF NOVEL ADMITTANCE CRITERION FOR INTERMITTENT EARTH FAULT PROTECTION

TESTING OF THE PERFORMANCE OF NOVEL ADMITTANCE CRITERION FOR INTERMITTENT EARTH FAULT PROTECTION UNIVERSITY OF VAASA FACULTY OF TECHNOLOGY ELECTRICAL ENGINEERING Elina Määttä S93545 SATE.3050 Sähkötekniikan erikoistyö TESTING OF THE PERFORMANCE OF NOVEL ADMITTANCE CRITERION FOR INTERMITTENT EARTH

More information

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection) Differential Protection (Unit protection) Differential Protection Differential protection is the best technique in protection. In this type of protection the electrical quantities entering and leaving

More information

System grounding of wind farm medium voltage cable grids

System grounding of wind farm medium voltage cable grids Downloaded from orbit.dtu.dk on: Apr 23, 2018 System grounding of wind farm medium voltage cable grids Hansen, Peter; Østergaard, Jacob; Christiansen, Jan S. Published in: NWPC 2007 Publication date: 2007

More information

Protection relay software models in interaction with power system simulators

Protection relay software models in interaction with power system simulators Protection relay software models in interaction with power system simulators Ivan Goran Kuliš *, Ante Marušić ** and Goran Leci * * Končar-Power Plant and Electric Traction Engineering, Zagreb, Croatia

More information

Improving Network Availability with Intelligent Electronic Devices

Improving Network Availability with Intelligent Electronic Devices Improving Network Availability with Intelligent Electronic Devices Guillaume Verneau - Schneider Electric - France Yves Chollot - Schneider Electric - France Pascal Cumunel - Schneider Electric - France

More information

DIRECTIONAL PROTECTION

DIRECTIONAL PROTECTION UNIVERSITY OF LJUBLJANA FACULTY OF ELECTRICAL ENGINEERING DIRECTIONAL PROTECTION Seminar work in the course Distribution and industrial networks Mentor: Prof. Grega Bizjak Author: Amar Zejnilović Ljubljana,

More information

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example

More information

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Dhanashree Kotkar 1, N. B. Wagh 2 1 M.Tech.Research Scholar, PEPS, SDCOE, Wardha(M.S.),India

More information

Applicability of a Hall Sensor in Directional Ground Fault Protections of MV Cable Networks with No-Effective Earthing

Applicability of a Hall Sensor in Directional Ground Fault Protections of MV Cable Networks with No-Effective Earthing http://dx.doi.org/10.5755/j01.eie.22.5.16339 Applicability of a Hall Sensor in Directional Ground Fault Protections of MV Cable Networks with No-Effective Earthing Marcin Habrych 1, Bogdan Miedzinski 2,

More information

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

thepower to protect  the power to protect i-gard LITERATURE Low and medium voltage thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors

More information

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when

More information

A Research of Single Phase Grounding Fault Location Method Based on the Component of Zero Sequence Current in Distribution Network

A Research of Single Phase Grounding Fault Location Method Based on the Component of Zero Sequence Current in Distribution Network A Research of Single Phase Grounding Fault Location Method Based on the Component of Zero Sequence Current in Distribution Network Jiaquan Yang 1, Wanshui Ling 2, Kelong Wang 2, Yong Feng 1, Wu Shao 3,

More information

BUS2000 Busbar Differential Protection System

BUS2000 Busbar Differential Protection System BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection 1 Typical Busbar Arrangements Single Busbar Double Busbar with Coupler Breaker and a Half

More information

ECM3 EARTH CONTINUITY RELAY

ECM3 EARTH CONTINUITY RELAY TECHNICAL DATASHEET ECM3 EARTH CONTINUITY RELAY Electrical Protection for Hard Rock Mines Application The ECM3 has been designed to provide earth continuity protection for cables containing pilot cores.

More information

Electrical Protection System Design and Operation

Electrical Protection System Design and Operation ELEC9713 Industrial and Commercial Power Systems Electrical Protection System Design and Operation 1. Function of Electrical Protection Systems The three primary aims of overcurrent electrical protection

More information

THE RCC GROUND FAULT NEUTRALIZER

THE RCC GROUND FAULT NEUTRALIZER REPRINT 18TH INTERNATIONAL CONFERENCE AND EXHIBITION ON ELECTRICITY DISTRIBUTION LINGOTTO CONFERENCE CENTRE, TURIN 6-9 JUNE 2005 THE RCC GROUND FAULT NEUTRALIZER A NOVEL SCHEME FOR FAST EARTH-FAULT PROTECTION

More information

Improving High Voltage Power System Performance. Using Arc Suppression Coils

Improving High Voltage Power System Performance. Using Arc Suppression Coils Improving High Voltage Power System Performance Using Arc Suppression Coils by Robert Thomas Burgess B Com MIEAust CPEng RPEQ A Dissertation Submitted in Fulfilment of the Requirements for the degree of

More information

2 Grounding of power supply system neutral

2 Grounding of power supply system neutral 2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the

More information

GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS

GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS Hannu LAAKSONEN ABB Oy Finland hannu.laaksonen@fi.abb.com ABSTRACT Medium-voltage (MV) network short-circuit protection operation time delays have

More information

Why the IT system is often the best choice for power supply systems of all types

Why the IT system is often the best choice for power supply systems of all types Why the IT system is often the best choice for power supply systems of all types Let us start initially with a clear commitment: the IT system ("unearthed system") is a type of system infrequently used

More information

The three zone distance protection, Z(1,2,3)RW is intended for systems.

The three zone distance protection, Z(1,2,3)RW is intended for systems. Page 1 Revision: - Issued: December 2002 Data subject to change without notice )HDWXUHV Intended for single or two-phase railway systems (16 2/3, 50 or 60 Hz) Full scheme distance protection, where each

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

Improving High Voltage Power System Performance. Using Arc Suppression Coils

Improving High Voltage Power System Performance. Using Arc Suppression Coils Improving High Voltage Power System Performance Using Arc Suppression Coils by Robert Thomas Burgess B Com MIEAust CPEng RPEQ A Dissertation Submitted in Fulfilment of the Requirements for the degree of

More information

1 Introduction General Background The New Computer Environment Transmission System Developments Theoretical Models and Computer Programs

1 Introduction General Background The New Computer Environment Transmission System Developments Theoretical Models and Computer Programs Modeling Techniques in Power Systems 1 General Background The New Computer Environment Transmission System Developments Theoretical Models and Computer Programs 2 Transmission Systems Linear Transformation

More information

SPAD 346 C Stabilized differential relay

SPAD 346 C Stabilized differential relay SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Post-fault oscillation phenomenon in compensated MV-networks challenges earth-fault protection

Post-fault oscillation phenomenon in compensated MV-networks challenges earth-fault protection 3 rd International Conference on Electricity Distribution Lyon, 1-18 June 1 ost-fault oscillation phenomenon in compensated MV-networks challenges earth-fault protection aper 14 ri WHLROOS, Janne LTONEN

More information

Amir Farughian

Amir Farughian Uudet tekniikat sähköverkon vikatilanteiden ja hajautetun tuotannon hallinnassa Amir Farughian Overview Single-phase earth fault location Review of the existing methods Improving a method Sequence currents

More information

SYNCHRONISING AND VOLTAGE SELECTION

SYNCHRONISING AND VOLTAGE SELECTION SYNCHRONISING AND VOLTAGE SELECTION This document is for Relevant Electrical Standards document only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept any liability for any

More information

A Guide to the DC Decay of Fault Current and X/R Ratios

A Guide to the DC Decay of Fault Current and X/R Ratios A Guide to the DC Decay of Fault Current and X/R Ratios Introduction This guide presents a guide to the theory of DC decay of fault currents and X/R ratios and the calculation of these values in Ipsa.

More information

Line protection with transformer in the protection zone

Line protection with transformer in the protection zone Line protection with transformer in the protection zone www.siemens.com/siprotec5 Three-end line protection with transformer in the protection range SIPROTEC 5 Application Three-end line protection with

More information

Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11

Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11 Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11 COMMISSIONING 12-16 DRAWINGS 17-18 1 1. INTRODUCTION APPLICATION

More information

ACTIVE CURRENT INJECTION METHOD FOR LIMITING GROUND FAULT CURRENT HARMONICS IN UNDERGROUND COAL MINES

ACTIVE CURRENT INJECTION METHOD FOR LIMITING GROUND FAULT CURRENT HARMONICS IN UNDERGROUND COAL MINES University of Kentucky UKnowledge Theses and Dissertations--Mining Engineering Mining Engineering 2014 ACTIVE CURRENT INJECTION METHOD FOR LIMITING GROUND FAULT CURRENT HARMONICS IN UNDERGROUND COAL MINES

More information

Babak Enayati National Grid Thursday, April 17

Babak Enayati National Grid Thursday, April 17 2014 IEEE PES Transmission & Distribution Conference & Exposition Impacts of the Distribution System Renewable Energy Resources on the Power System Protection Babak Enayati National Grid Thursday, April

More information

Application of Low-Impedance 7SS601 Busbar Differential Protection

Application of Low-Impedance 7SS601 Busbar Differential Protection Application of Low-Impedance 7SS601 Busbar Differential Protection 1. Introduction Utilities have to supply power to their customers with highest reliability and minimum down time. System disturbances,

More information

DISTRIBUTION PROTECTION RELAY SOFTWARE MODELS IN INTERACTION WITH POWER SYSTEM SIMULATORS

DISTRIBUTION PROTECTION RELAY SOFTWARE MODELS IN INTERACTION WITH POWER SYSTEM SIMULATORS 23 rd International Conference on Electricity Distribution Lyon, 15-18 June 215 Paper 149 DISTRIBUTION PROTECTION RELAY SOFTWARE MODELS IN INTERACTION WITH POWER SYSTEM SIMULATORS Ivan Goran KULIŠ Končar

More information

Overcurrent relays coordination using MATLAB model

Overcurrent relays coordination using MATLAB model JEMT 6 (2018) 8-15 ISSN 2053-3535 Overcurrent relays coordination using MATLAB model A. Akhikpemelo 1 *, M. J. E. Evbogbai 2 and M. S. Okundamiya 3 1 Department of Electrical and Electronic Engineering,

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering) R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between

More information

A New Adaptive High Speed Distance Protection Scheme for Power Transmission Lines

A New Adaptive High Speed Distance Protection Scheme for Power Transmission Lines A New Adaptive High Speed Distance Protection Scheme for Power Transmission Lines M.M. Saha, T. Einarsson, S. Lidström ABB AB, Substation Automation Products, Sweden Keywords: Adaptive distance protection,

More information

Upgrading Your Electrical Distribution System To Resistance Grounding

Upgrading Your Electrical Distribution System To Resistance Grounding Upgrading Your Electrical Distribution System To Resistance Grounding The term grounding is commonly used in the electrical industry to mean both equipment grounding and system grounding. Equipment grounding

More information

Teaching Distance Relay Using Matlab/Simulink Graphical User Interface

Teaching Distance Relay Using Matlab/Simulink Graphical User Interface Available online at www.sciencedirect.com Procedia Engineering 53 ( 2013 ) 264 270 Malaysian Technical Universities Conference on Engineering & Technology 2012, MUCET 2012 Part 1 - Electronic and Electrical

More information

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES U AJMAL, GE Grid Solutions UK Ltd, usman.ajmal@ge.com S SUBRAMANIAN, GE Grid Solutions UK Ltd, sankara.subramanian@ge.com H Ha GE Grid Solutions

More information

COPYRIGHTED MATERIAL. Index

COPYRIGHTED MATERIAL. Index Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,

More information

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8] Code No: RR320205 Set No. 1 1. (a) Explain about Bewley s Lattice diagrams and also mention the uses of these diagrams. [6+2] (b) A line of surge impedance of 400 ohms is charged from a battery of constant

More information

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays

More information

MV network design & devices selection EXERCISE BOOK

MV network design & devices selection EXERCISE BOOK MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

Fatima Michael college of Engineering and Technology

Fatima Michael college of Engineering and Technology Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric

More information

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions 1 Transmission transformers are important links in the bulk power system. They allow transfer of power from generation centers, up to the high-voltage grid, and to bulk electric substations for distribution

More information

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) 1MRS752324-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) Contents 1. Introduction... 2 1.1

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS Ljubomir KOJOVIC Cooper Power Systems - U.S.A. Lkojovic@cooperpower.com INTRODUCTION In steel facilities that use Electric Arc Furnaces (EAFs) to manufacture

More information

ET 40 - Electrician Theory Examination Marking Schedule

ET 40 - Electrician Theory Examination Marking Schedule ET 40 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker

More information

Digital Fault Recorder Deployment at HVDC Converter Stations

Digital Fault Recorder Deployment at HVDC Converter Stations Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic

More information

High voltage engineering

High voltage engineering High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency

More information

The CABLETROLL 3600 FCI is capable of discriminating between PTP and PTG faults, and indicating the direction of the latter type.

The CABLETROLL 3600 FCI is capable of discriminating between PTP and PTG faults, and indicating the direction of the latter type. Directional fault current indicator for underground systems Presentation CABLETROLL 3600 directional Fault Current Indicators (FCI) are designed to help the operator locate faults on underground lines.

More information

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION David TOPOLANEK Petr TOMAN Michal PTACEK Jaromir DVORAK Brno University of Technology - Czech

More information

The Research on Neutral Grounding Scheme of Fengxian 35 kv and 10 kv Power Grid

The Research on Neutral Grounding Scheme of Fengxian 35 kv and 10 kv Power Grid Energy and Power Engineering, 2013, 5, 897-901 doi:10.4236/epe.2013.54b172 Published Online July 2013 (http://www.scirp.org/journal/epe) The Research on Neutral Grounding Scheme of Fengxian 35 kv and 10

More information

Unit Protection Differential Relays

Unit Protection Differential Relays Unit Protection PROF. SHAHRAM MONTASER KOUHSARI Current, pu Current, pu Protection Relays - BASICS Note on CT polarity dots Through-current: must not operate Internal fault: must operate The CT currents

More information

INSTRUCTION MANUAL. AQ F3x0 Feeder protection IED

INSTRUCTION MANUAL. AQ F3x0 Feeder protection IED INSTRUCTION MANUAL AQ F3x0 Feeder protection IED Instruction manual AQ F3x0 Feeder protection IED 2 (173) Revision 1.00 Date November 2010 Changes - The first revision. Revision 1.01 Date January 2011

More information

Slide 1. New Delhi India Oct CIGRE AORC Meeting New Delhi October 2017

Slide 1. New Delhi India Oct CIGRE AORC Meeting New Delhi October 2017 Slide 1 CIGRÉ AORC Panel B1 Insulated Cables Victorian REFCL Program Update (Rapid Earth Fault Current Limiter) Russell Wheatland : Principal Engineer - Asset Management CIGRE AORC Meeting New Delhi October

More information

Grounding Recommendations for On Site Power Systems

Grounding Recommendations for On Site Power Systems Grounding Recommendations for On Site Power Systems Revised: February 23, 2017 2017 Cummins All Rights Reserved Course Objectives Participants will be able to: Explain grounding best practices and code

More information

Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602

Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602 Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602 1 / 12 1 INTRODUCTION This document provides guidelines for the performance calculations required for high impedance differential

More information

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Expo - Nov. 3, 2014 Index Normal Distribution System

More information

LIMITING THE DANGER OF ELECTRIC CURRENT SHOCK IN RELATION TO THE MEAN OF NEUTRAL POINT EARTHING IN THE MV NETWORKS

LIMITING THE DANGER OF ELECTRIC CURRENT SHOCK IN RELATION TO THE MEAN OF NEUTRAL POINT EARTHING IN THE MV NETWORKS LIMITING THE DANGER OF ELECTRIC CURRENT SHOCK IN RELATION TO THE MEAN OF NEUTRAL POINT EARTHING IN THE MV NETWORKS Witold Hoppel, Józef Lorenc!" ph.+48 61 8782279 - FAX + 48 61 8782280 Jerzy Andruszkiewicz

More information

Product Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016.

Product Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016. Title Grounding System Introduction Date October, 2016 Related Products Key words All industrial automation products Grounding, Earthing, TN, TT, IT, Introduction The automation industry of today has adopted

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

SIPROTEC Protection Technology. The Basis for Highest Availability of Supply

SIPROTEC Protection Technology. The Basis for Highest Availability of Supply SIPROTEC Protection Technology The Basis for Highest Availability of Supply Unrestricted Siemens AG 2016 www.siemens.com/ Objectives of this Brochure Objective The following examples give an overview of

More information

Ironing out resonance

Ironing out resonance Ironing out resonance Ferroresonance prevention in MV voltage transformers Wojciech Piasecki, Marek Florkowski, Marek Fulczyk, Pentti Mahonen, Mariusz Luto, Wieslaw Nowak, Otto Preiss Every engineer knows

More information