Introduction Characteristics and performance of Compact NSX circuit breakers from 100 to 250 A up to 690 V

Size: px
Start display at page:

Download "Introduction Characteristics and performance of Compact NSX circuit breakers from 100 to 250 A up to 690 V"

Transcription

1 Functions and characteristics Introduction Characteristics and performance of Compact NSX circuit reakers from to A up to 69 V PB.eps PB6_.eps PB_.eps Compact NSX/6/. Compact NSX R. Compact NSX HB. () high currents (e.g. 3rd harmonics). () ZSI: Zone Selective Interlocking using pilot wires. (3) Vigi module is not availale for reaking capacity levels HB/HB. () There is no 6 A frame, use A frame with lower rating trip units for R, HB, HB. () P circuit reaker in 3P case for B and F types, only with thermal-magnetic trip unit. A-6 Common characteristics Rated voltages Ui Impulse withstand voltage Uimp Ue AC /6 Hz 69 Suitaility for isolation IEC/EN 697- yes Utilisation category A Pollution degree IEC Circuit reakers Breaking capacity levels Electrical characteristics as per IEC 697- In Numer of poles Breaking capacity (ka rms) Service reaking capacity (ka rms) Characteristics as per Nema AB Characteristics as per UL lcu lcs AC /6 Hz / V 3/ V V V V 66/69 V AC /6 Hz / V 3/ V V V V 66/69 V Mechanical Electrical V In/ In 69 V In/ In AC /6 Hz V V 6 V AC /6 Hz V V 6 V Protection and measurements Short-circuit protection Magnetic only Overload / short-circuit protection Thermal magnetic Electronic () with ground-fault protection with zone selective () Display / I, U, f, P, E, THD measurements / interrupted-current measurement Options Power Meter display on door Operating assistance Counters Histories and alarms Metering Com Device status/control Com Earth-leakage protection By Vigi module (3) By Vigirex relay Installation / connections Dimensions and weights /3P P /3P P Connections Connection terminals Pitch Cross-section mm² Common characteristics Control Versions Manual Electrical Plug-in ase Chassis NSX NSX6 () NSX B F N H S L R HB HB B F N H S L B F N H S L R HB HB 6 (), 3, 3, (), 3, (), 3, 3, x 6 x 6 x 6 x 6 x 6 x 6 x 6 x 6 x 6 x 6 x 6 x 6 x 6 x 6 x 6 x / mm 3/ mm 3/ mm 3/ mm A-7

2 Functions and characteristics Introduction Characteristics and performance of Compact NSX circuit reakers from to 63 A up to 69 V PB66.eps PB.eps PB3.eps Compact NSX/63. Compact NSX63 R. Compact NSX63 HB. () high currents (e.g. 3rd harmonics). () ZSI: Zone Selective Interlocking using pilot wires. (3) Vigi module is not availale for reaking capacity levels HB/HB. A- Common characteristics Rated voltages Ui Impulse withstand voltage Uimp Ue AC /6 Hz 69 Suitaility for isolation IEC/EN 697- yes Utilisation category A Pollution degree IEC Circuit reakers Breaking capacity levels Electrical characteristics as per IEC 697- In Numer of poles Breaking capacity (ka rms) lcu AC /6 Hz / V 3/ V V V V 66/69 V Service reaking capacity (ka rms) Characteristics as per Nema AB Characteristics as per UL lcs AC /6 Hz / V 3/ V V V V 66/69 V Mechanical Electrical V In/ In 69 V In/ In AC /6 Hz V V 6 V AC /6 Hz V V 6 V Protection and measurements Short-circuit protection Magnetic only Overload / short-circuit protection Thermal magnetic Electronic () with ground-fault protection with zone selective () Display / I, U, f, P, E, THD measurements / interrupted-current measurement Options Power Meter display on door Operating assistance Counters Histories and alarms Metering Com Device status/control Com Earth-leakage protection By Vigi module (3) By Vigirex relay Installation / connections Dimensions and weights /3P P /3P P Connections Connection terminals Pitch Cross-section mm² Common characteristics Control Versions Manual Electrical Plug-in ase Chassis NSX NSX63 = - A = - 63 A F N H S L R HB HB F N H S L R HB HB R HB HB , 3, 3, 3, x x x x x x x x /. mm /. mm /7 mm /7 mm x x A-9

3 Functions and characteristics Protection of distriution systems Compact NS circuit reakers from 63 up to 3 A Compact circuit reakers Numer of poles Control manual electric Type of circuit reaker Connections front connection rear connection In () Compact NSL. Ui Uimp Ue Type of circuit reaker Compact NS6H. Manual lcu lcs front connection with are cales front connection rear connection Electrical lcu lcs lcw s mechanical electrical In In - - H L LB H L H H H H L LB H L H H H H L LB H L H H H B B B B B B B B B Compact NSH. () 6 C with vertical connections. See the temperature derating tales for other types of connections.

4 Functions and characteristics TM thermal-magnetic and MA magnetic trip units can e used on Compact NSX/6/ circuit reakers with performance levels B/F/H/N/S/L. TM trip units are availale in versions: TM-D, for the protection of distriution cales TM-G, with a low threshold, for the protection of generators or long cale lengths. Vigi modules or Vigirex relays can e added to all the circuit reakers to provide external earth-leakage protection. DB6.eps Protection of distriution systems TM thermal-magnetic and MA magnetic trip units TM-D and TM-G thermal-magnetic trip units Circuit reakers equipped with thermal-magnetic trip units are used mainly in industrial and commercial electrical distriution applications: TM-D, for protection of cales on distriution systems supplied y transformers TM-G, with a low pick-up for generators (lower short-circuit currents than with transformers) and distriution systems with long cale lengths (fault currents limited y the impedance of the cale). Protection... Thermal protection () Thermal overload protection ased on a imetal strip providing an inverse time curve I t, corresponding to a temperature rise limit. Aove this limit, the deformation of the strip trips the circuit reaker operating mechanism. This protection operates according to: that can e adjusted in amps from.7 to times the rating of the trip unit (6 A to A), corresponding to settings from to A for the range of trip units a non-adjustale time delay, defined to ensure protection of the cales. Magnetic protection (Im) Short-circuit protection with a fixed or adjustale pick-up Im that initiates instantaneous tripping if exceeded. TM-D: fixed pick-up, Im, for 6 to 6 A ratings and adjustale from to for and A ratings fixed pick-up for 6 to 63 A ratings. Protection against insulation faults Two solutions are possile y adding: a Vigi module acting directly on the trip unit of the circuit reaker a Vigirex relay connected to an MN or MX voltage release. Protection versions 3-pole: vv3p 3D: 3-pole frame (3P) with detection on all 3 poles (3D) vv3p D: 3-pole frame (3P) with detection on poles (D). -pole: vvp 3D: -pole frame (P) with detection on 3 poles (3D). vvp D: -pole frame (P) with detection on all poles (same threshold for phases and neutral). DB7.eps MA magnetic trip units Note: All the trip units have a transparent lead-sealale cover that protects access to the adjustment dials. In distriution applications, circuit reakers equipped with MA magnetic-only trip units are used for: short-circuit protection of secondary windings of LV/LV transformers with overload protection on the primary side. as an alternative to a switch-disconnector at the head of a switchoard in order to provide short-circuit protection. Their main use is however for motor protection applications, in conjunction with a thermal relay and a contactor or motor starter (see "Motor protection", page A-). Protection... Magnetic protection (Im) Short-circuit protection with an adjustale pick-up Im that initiates instantaneous tripping if exceeded. Im = In x... set in amps on an adjustment dial covering the range 6 to for. to A ratings or 9 to In for to A ratings. Protection versions 3-pole (3P 3D): 3-pole frame (3P) with detection on all 3 poles (3D). -pole (P 3D): -pole frame (P) with detection on 3 poles (3D). A-6

5 Thermal-magnetic trip units TM6D to D Ratings (A) In at C () Circuit reaker Compact NSX Thermal protection Compact NSX Compact NSX = In x... adjustale in amps from.7 to tripping etween. and. Time delay (s) tr non-adjustale tr at. to tr at 6 x Magnetic protection Im fixed adjustale accuracy ± % Compact NSX Compact NSX6/ to xin Time delay tm fixed Neutral protection Unprotected neutral P 3D no detection Fully protected neutral P D x Magnetic trip units MA. to Ratings (A) In at 6 C Circuit reaker Compact NSX - - Compact NSX Compact NSX Instantaneous magnetic protection accuracy ± % Im = In x... adjustale in amps from 6 to (9 settings) adjustale in amps from 9 to Time delay (ms) tm none Thermal-magnetic trip units TM6G to G Ratings (A) In at C () Circuit reaker Compact NSX Compact NSX Compact NSX Thermal protection = In x... adjustale in amps from.7 to tripping etween. and. Time delay (s) tr non-adjustale tr at. to tr at 6 x - Magnetic protection Im fixed accuracy ± % Compact NSX Compact NSX Compact NSX Time delay tm fixed Neutral protection Unprotected neutral P 3D no Fully protected neutral P D x () For temperatures greater than C, the thermal protection characteristics are modified. See the temperature derating tale. A-7

6 DB3.eps NS NS6 ( A) NSX NSX Acti 9 Compact NSX with Micrologic for total discrimination with Acti 9 devices rated y A or a C6. Better coordination etween protection functions reduces the difference in ratings required for total discrimination. Unmatched discrimination Discrimination Compact NSX provides maximum continuity of service and savings through an unmatched level of discrimination: given the high accuracy of measurements, overload discrimination is ensured even etween very close ratings for major faults, the fast processing of the Micrologic trip units means the upstream device can anticipate the reaction of the downstream device. The upstream reaker adjusts its tripping delay to provide discrimination for very high faults, the energy of the arc dissipated y the short-circuit in the downstream reaker causes reflex tripping. The current seen y the upstream device is significantly limited. The energy is not sufficient to cause tripping, so discrimination is maintained whatever the short-circuit current. For total discrimination over the entire range of possile faults, from the long-time pick-up to the ultimate short-circuit current Icu, a ratio of. must e maintained etween the ratings of the upstream and downstream devices. This ratio is required to ensure selective reflex tripping for high short-circuits. Understanding the names of Micrologic electronic trip units Protection Frame Measurements Applications : I : NSX/6/ A: Ammeter Distriution, otherwise : LS I DB9.eps DB.eps G: Generator : LSI AB: Pulic distriution () 6: LSIG M: Motors Z: 6 Hz /3 () I: Instantaneous 3: NSX/63 E: Energy L: Long time S : Short time () (fixed delay) S: Short time G: Ground fault DB.eps DB6.eps Examples Micrologic.3 Instantaneous only or 63 A Distriution Micrologic.3 LS I or 63 A Distriution Micrologic. A LSI, 6 or A Ammeter Distriution Micrologic 6.3 E-M LSIG or 63 A Energy Motor () AB-Z: except NSX R, HB, HB. () LS I protection is standard on Micrologic. To ensure discrimination, it offers short-time protection S with a non-adjustale delay and instantaneous protection. A-

7 Functions and characteristics Protection of distriution systems Micrologic and.3 M trip units Micrologic trip units can e used on Compact NSX to 63 circuit reakers with performance levels B/F/H/N/S/L. They provide: standard protection of distriution cales indication of: v overloads (via LEDs) v overload tripping (via the SDx relay module). Circuit reakers equipped with Micrologic.3 M trip units, without thermal protection, are used in certain applications to replace switch-disconnectors at the head of switchoards. Micrologic.3 M trip units are dedicated to Compact NSX/63 A circuit reakers. DB.eps Micrologic Circuit reakers equipped with Micrologic trip units can e used to protect distriution systems supplied y transformers. For generators and long cales, Micrologic G trip units offer etter suited low pick-up solutions (see page A-6). Protection... Settings are made using the adjustment dials with fine adjustment possiilities. Overloads: Long time protection () Inverse time protection against overloads with an adjustale current pick-up set using a dial and a non-adjustale time delay tr. Short-circuits: Short-time protection with fixed time delay () Protection with an adjustale pick-up. Tripping takes place after a very short delay used to allow discrimination with the downstream device. Short-circuits: Non-adjustale instantaneous protection Instantaneous short-circuit protection with a fixed pick-up. Neutral protection On 3-pole circuit reakers, neutral protection is not possile. On four-pole circuit reakers, neutral protection may e set using a three-position switch: vvp 3D: neutral unprotected vvp 3D + N/: neutral protection at half the value of the phase pick-up, i.e.. x vvp D: neutral fully protected at. DB.eps PB3377.eps Indications... Front indications Green Ready LED: flashes slowly when the circuit reaker is ready to trip in the event of a fault. Orange overload pre-alarm LED: steady on when I > 9 %. Red overload LED: steady on when I > %. SDx remote indication relay module with its terminal lock. DB6.eps Remote indications An overload trip signal can e remoted y installing an SDx relay module inside the circuit reaker. This module receives the signal from the Micrologic electronic trip unit via an optical link and makes it availale on the terminal lock. The signal is cleared when the circuit reaker is reclosed. For description, see page A-93. Micrologic.3 M for magnetic protection only A Note: all the trip units have a transparent lead-sealale cover that protects access to the adjustment dials. A- Micrologic.3 M trip units provide magnetic protection only, using electronic technology. They are dedicated to /63 A 3-pole (3P 3D) circuit reakers or -pole circuit reakers with detection on 3 poles (P, 3D) and are used in certain applications to replace switch-disconnectors at the head of switchoards. They are especially used in 3-pole versions for motor protection, see page A-.

8 Micrologic Ratings (A) In at C () 6 63 Circuit reaker Compact NSX L Compact NSX Compact NSX - - Compact NSX Compact NSX Long-time protection Io value depending on trip unit rating (In) and setting on dial tripping etween In = A Io = and. In = A Io = In = 6 A Io = In = A (NSX) Io = 6 7 In = A (NSX) Io = In = A Io = In = 63 A Io = = Io x... 9 fine adjustment settings from.9 to ( ) for each value of Io Time delay (s) tr non-adjustale accuracy to -%. x 6 x 6 7. x Thermal memory minutes efore and after tripping S Short-time protection with fixed time delay accuracy ± % = x Time delay (ms) tsd non-adjustale Non-tripping time Maximum reak time I Instantaneous protection accuracy ± % Ii non-adjustale Non-tripping time Maximum reak time ms ms for I >. Ii () If the trip units are used in high-temperature environments, the Micrologic setting must take into account the thermal limitations of the circuit reaker. See the temperature derating tale. Ii Micrologic.3 M Ratings (A) In at 6 C 3 Circuit reaker Compact NSX - Compact NSX63 S Short time protection accuracy ± % adjustale directly in amps Time delay (ms) tsd non-adjustale I Non-tripping time Maximum reak time Instantaneous protection accuracy ± % 9 settings: 6, 9,, 6,, 3, 3, 3, 6 A 6 Ii non-adjustale 6 Non-tripping time Maximum reak time 3 ms 9 settings:, 3, 3,,,,, 6, 6 A A-9

9 Functions and characteristics Protection of distriution systems Micrologic / 6 A or E trip units DB66.eps DB67.eps PB3377.eps Micrologic / 6 A (Ammeter) or E (Energy) trip units can e used on Compact NSX to 63 circuit reakers with performance levels B/F/H/N/S/L. They all have a display unit. They offer asic LSI protection (Micrologic ) or LSI and ground-fault protection G (Micrologic 6). They also offer measurement, alarm and communication functions. Measurement Display Settings Maintenance Trip unit menus. fault Faulty phase Display of interrupted current. Interrupted current DB9.eps Protection Settings can e adjusted in two ways, using the dials and/or the keypad. The keypad can e used to make fine adjustments in A steps elow the maximum value defined y the setting on the dial. Access to setting modifications via the keypad is protected y a locking function displayed on the screen and controlled y a microswitch. The lock is activated automatically if the keypad is not used for minutes. Access to the microswitch is protected y a transparent lead-sealale cover. With the cover closed, it is still possile to display the various settings and measurements using the keypad. Overloads: Long time protection () Inverse time protection against overloads with an adjustale current pick-up set using a dial or the keypad for fine adjustments. The time delay tr is set using the keypad. Short-circuits: Short-time protection () Short-circuit protection with an adjustale pick-up and adjustale time delay tsd, with the possiility of including a portion of an inverse time curve (I t On). Short-circuits: Instantaneous protection (Ii) Instantaneous protection with adjustale pick-up Ii. Additional ground fault protection (Ig) on Micrologic 6 Residual type ground-fault protection with an adjustale pick-up Ig (with Off position) and adjustale time delay tg. Possiility of including a portion of an inverse time curve (I t On). Neutral protection On -pole circuit reakers, this protection can e set via the keypad: vvoff: neutral unprotected vv.: neutral protection at half the value of the phase pick-up, i.e.. x vv.: neutral fully protected at vvosn: Oversized neutral protection at.6 times the value of the phase pick-up. Used when there is a high level of 3rd order harmonics (or orders that are multiples of 3) that accumulate in the neutral and create a high current. In this case, the device must e limited to =.63 for the maximum neutral protection setting of.6 x. With 3-pole circuit reakers, the neutral can e protected y installing an external neutral sensor with the output (T, T) connected to the trip unit. Zone selective interlocking (ZSI) A ZSI terminal lock may e used to interconnect a numer of Micrologic control units to provide zone selective interlocking for short-time () and ground-fault (Ig) protection, without a time delay. For Compact NSX to, the ZSI function is availale only in relation to the upstream circuit reaker (ZSI out). Display of type of fault... On a fault trip, the type of fault (,, Ii, Ig), the phase concerned and the interrupted current are displayed. An external power supply is required. Indications... Front indications SDx remote indication relay module with its terminal lock. Note: all the trip units have a transparent lead-sealale cover that protects access to the adjustment dials. A- Green Ready LED: flashes slowly when the circuit reaker is ready to trip in the event of a fault. Orange overload pre-alarm LED: steady on when I > 9 %. Red overload LED: steady on when I > %. Remote indications An SDx relay module installed inside the circuit reaker can e used to remote the following information: overload trip overload prealarm (Micrologic ) or ground fault trip (Micrologic 6). This module receives the signal from the Micrologic electronic trip unit via an optical link and makes it availale on the terminal lock. The signal is cleared when the circuit reaker is closed. These outputs can e reprogrammed to e assigned to other types of tripping or alarm. The module is descried in detail in the section dealing with accessories.

10 Protection Micrologic / 6 A or E trip units Ratings (A) In at C () () 6 63 Circuit reaker Compact NSX Compact NSX Compact NSX - - Compact NSX Compact NSX L Long-time protection =... dial setting value depending on trip unit rating (In) and setting on dial tripping etween In = A Io = and. In = A Io = In = 6 A Io = In = A Io = 6 7 In = A Io = In = 63 A Io = keypad setting Fine adjustment in A steps elow maximum value set on dial Time delay (s) tr =... keypad setting. 6 accuracy to - %. x 6 x x.7... Thermal memory minutes efore and after tripping S Short-time protection with adjustale time delay = x... dial setting accuracy ± % for Micrologic Fine adjustment in. x steps using the keypad keypad settings for micrologic 6 Time delay (s) tsd =... keypad setting I Adjustment in steps of. over the range. to: ( to 6 A), ( to A) or (63 A) I Off.. I On -.. Non-tripping time (ms) 3 3 Maximum reak time (ms) 3 Instantaneous protection accuracy ± % Ii = In x keypad setting Adjustment in steps of. over the range. to: ( to 6 A), ( to A) or (63 A) Non-tripping time Maximum reak time ms ms for I > Ii G Ground-fault protection - for Micrologic 6 A or E Ig = In x dial setting accuracy ± % In = A Off In > A Off Fine adjustment in. A steps using the keypad Time delay (s) tg =... keypad I Off.. setting I On -.. Non-tripping time (ms) 3 3 Maximum reak time (ms) 3 Test Ig function uilt-in () If the trip units are used in high-temperature environments, the Micrologic setting must take into account the thermal limitations of the circuit reaker. See the temperature derating tale. () For A rating, the neutral N/ adjustment is not possile. A-

11 long time.7. tr.9 (s) instantaneous x setting alarm long time alarm.7. tr.9 (s) short time instantaneous tsd I i (s) off x on I t setting delay long time alarm.7. tr.9 (s) short time instantaneous 3 tsd I i (s) on I off t x setting delay test D E tg Ig F (s)...3 C G.3. B H.. A I. on I t ground fault menu long time.7. tr.9 (s) instantaneous x setting menu alarm long time tr alarm.7..9 (s) short time instantaneous tsd 3 (s).. I i x on I off t setting delay menu long time.7. tr.9 (s) short time 3 tsd (s) on I t x setting delay D E tg Ig F (s)...3 C G.3. B H.. A I. on I t off ground fault menu alarm instantaneous I i 6 3 off test long time alarm.7. tr.9 (s) short time instantaneous 3 tsd (s).. I i off x on I t off setting delay test IΔn 3 ΔI earth leakage menu long time.7. tr.9 (s) instantaneous x setting menu alarm long time tr alarm.7..9 (s) short time instantaneous tsd 3 (s).. I i x on I off t setting delay menu long time alarm.7. tr.9 (s) short time instantaneous 3 tsd I i (s) on I off t x setting delay test D E tg Ig F (s)...3 C G.3. B H.. A I. on I t ground fault long time.7. tr alarm.9 (s) short time instantaneous. 3 tsd I i (s) x on I off t off setting delay test long time.7. tr alarm.9 (s) short time instantaneous tsd I i (s) on I off x t off setting delay test Ig D E tg F (s)...3 C G.3. B H.. A J. on I t off ground fault long time.7. tr alarm.9 (s) short time instantaneous tsd I i (s) on I off x t off setting delay test IΔn Δt (A) 3 (ms) earth leakage Functions and characteristics Micrologic control units Overview of functions indications. Micrologic name codes. E X Y Z Dependaility conducted or radiated disturances. an independent microprocessor. Accessories descried on. the documentation accessile via the Products and services menu of the we site. Current protection Micrologic : asic protection Protection: long time + instantaneous Micrologic without measurement. Micrologic. Measurements and programmale protection A: ammeter I, I, I, I N, I earth-fault, I fault indications. A Micrologic. A E: Energy P: A + power meter + programmale protection incorporates all the rms measurements of power factor, power and measurements. v calculates the current demand value v "Quickview" function for. E Micrologic. E peak peak minimeters phase sequence, reverse power or current measurements of interrupted currents, differentiated fault indications, maintenance indications, event % % X: type of protection for selective protection at 6 % at 6 % at 6 Y: control-unit generation Z: type of measurement Micrologic : selective protection Protection: long time + short time + instantaneous. Micrologic.. A Micrologic. A % %. E Micrologic. E % %. P Micrologic. P 6A N 3 at 6 at 6 at 6 6 Micrologic 6: selective + earth-fault protection Protection: long time + short time + instantaneous + earth fault 6. Micrologic A Micrologic 6. A % 6. E Micrologic 6. E % 6. P Micrologic 6. P 6A N 3 % % at 6 at 6 at 6 off off 6 Micrologic 7: selective + earth-leakage Protection: long time + short time + instantaneous + earth leakage up to 3A 7. A Micrologic 7. A % 7. P Micrologic 7. P 6A N 3 % at

12 Functions and characteristics Micrologic control units For Compact NS63 to 3 DB7.eps Micrologic.,. and 6. control units protect power circuits. Micrologic. and 6. offers time discrimination for short-circuits as well. Micrologic 6. Protection Protection thresholds and delays are set using the adjustment dials. Overload protection True rms long-time protection. Thermal memory: thermal image efore and after tripping. Setting accuracy may e enhanced y limiting the setting range using a different long-time rating plug. Overload protection can e cancelled using a specific LT rating plug "Off". Short-circuit protection Short-time (rms) and instantaneous protection. Selection of It type (ON or OFF) for short-time delay. Earth-fault protection Residual or source ground return earth fault protection. Selection of It type (ON or OFF) for delay. Neutral protection On three-pole circuit reakers, neutral protection is not possile. On four-pole circuit reakers, neutral protection may e set using a three-position switch: neutral unprotected (P 3d), neutral protection at. (P 3d + N/) or neutral protection at (P d). Indications Overload indication y alarm LED on the front; the LED goes on when the current exceeds the long-time trip threshold. Test A mini test kit or a portale test kit may e connected to the test connector on the front to check circuit-reaker operation after installing the trip unit or accessories. long time tr (s) at 6 short time 3.. x Fault indications (only for micrologic 6.) alarm 6 tsd (s) on setting Ig D E F G C H B I A I t delay Ii instantaneous 3 off 6 test tg (s) on I t off ground fault long-time threshold and tripping delay overload alarm (LED) short-time pick-up and tripping delay instantaneous pick-up fixing screw for long-time rating plug test connector indication of tripping cause earth-leakage or earth-fault pick-up and tripping delay Note: Micrologic control units are equipped with a transparent lead-seal cover as standard. A- LEDs indicate the type of fault: overload (long-time protection ) short-circuit (short-time or instantaneous li protection) earth fault or earth leakage (Ig) internal fault (Ap). Battery power The fault indication LEDs remain on until the test/reset utton is pressed. Under normal operating conditions, the attery supplying the LEDs has a service life of approximately years.

13 Micrologic. Long time Current setting (A) = In x tripping etween. and. x Time setting Time delay (s) accuracy: to -3 % accuracy: to - % accuracy: to - % Thermal memory () to - % - () to -6 % = x. 3 6 tr I Micrologic. / 6. tr (s). x 6 x 7. x Other ranges or disale y changing long-time rating plug () () minutes efore and after tripping DB3.eps Long time Current setting (A) = In x Tripping etween. and. x Time setting Time delay (s) Accuracy: to -3 % Accuracy: to - % Accuracy: to - % Thermal memory () to - % - () to -6 % Short time = x Accuracy: ± % Settings Time setting tsd (s) Earth fault Accuracy: ± % t max. resettale time: ms; max reak time: ms Protection Time delay (ms) at x (It Off or It On) Instantaneous Accuracy: ± % Time delay t. 3 6 It Off It On tsd (max resettale time) tsd (max reak time) Ii = In x 3 6 off E F G.. H.9.9 J It on tr It off tsd Ii. I Max resettale time: ms Max reak time: ms Micrologic 6. A B C D It Off.. Time setting tg (s).. It On 3 Time delay (ms) tg (max resettale time) tg (max reak time) 3 at In or A (It Off or It On) Note: all current-ased protection functions require no auxiliary source. The test / reset utton resets maximeters, clears the tripping indication and tests the attery. Ig = In x In y A A < In < A In u A Settings DB36.eps Instantaneous accuracy: ± % Time delay tr (s). x 6 x 7. x other ranges or disale y changing long-time rating plug () 6.7 () minutes efore and after tripping DB3.eps Protection A-9

14 Functions and characteristics Micrologic control units Micrologic A "ammeter" DB33.eps Micrologic A control units protect power circuits. They also offer measurements, display, communication and current maximeters. Version 6 provides earth-fault protection, version 7 provides earth-leakage protection. "Ammeter" measurements Micrologic A control units measure the true (rms) value of currents. They provide continuous current measurements from. to. In and are accurate to within. % (including the sensors). A digital LCD screen continuously displays the most heavily loaded phase (Imax) or displays the I, I, I3, IN, Ig,I n, stored-current (maximeter) and setting values y successively pressing the navigation utton. The optional external power supply makes it possile to display currents < % In. Below. In, measurements are not significant. Between.and. In, accuracy changes linearly from % to. %. Communication option In conjunction with the COM communication option, the control unit transmits the following: settings all ammeter measurements tripping causes maximeter readings. Protection Protection thresholds and delays are set using the adjustment dials. Overload protection True rms long-time protection. Thermal memory: thermal image efore and after tripping. Setting accuracy may e enhanced y limiting the setting range using a different long-time rating plug. Overload protection can e cancelled using a specific LT rating plug "Off". Short-circuit protection Short-time (rms) and instantaneous protection. Selection of It type (ON or OFF) for short-time delay. Earth-fault protection Residual or source ground return earth fault protection. Selection of It type (ON or OFF) for delay. Residual earth-leakage protection (Vigi). Operation without an external power supply. q Protected against nuisance tripping. k DC-component withstand class A up to A. Neutral protection On three-pole circuit reakers, neutral protection is not possile. On four-pole circuit reakers, neutral protection may e set using a three-position switch: neutral unprotected (P 3d), neutral protection at. (P 3d + N/), neutral protection at (P d) long-time threshold and tripping delay overload alarm (LED) at. short-time pick-up and tripping delay instantaneous pick-up earth-leakage or earth-fault pick-up and tripping delay earth-leakage or earth-fault test utton long-time rating plug screw test connector lamp test, reset and attery test indication of tripping cause digital display three-phase argraph and ammeter navigation uttons Zone selective interlocking (ZSI) A ZSI terminal lock may e used to interconnect a numer of control units to provide total discrimination for short-time and earth-fault protection, without a delay efore tripping. Overload alarm A yellow alarm LED goes on when the current exceeds the long-time trip threshold. Fault indications LEDs indicate the type of fault: overload (long-time protection ) short-circuit (short-time or instantaneous li protection) earth fault or earth leakage (Ig or I n) internal fault (Ap). Battery power The fault indication LEDs remain on until the test/reset utton is pressed. Under normal operating conditions, the attery supplying the LEDs has a service life of approximately years. Test A mini test kit or a portale test kit may e connected to the test connector on the front to check circuit-reaker operation. For Micrologic 6. A and 7. A control units, the operation of earth-fault or earth-leakage protection can e checked y pressing the test utton located aove the test connector. Note: Micrologic A control units come with a transparent lead-seal cover as standard. A-

15 Micrologic. A tr (s). x 6 x 7. x Time setting tg (s) Time delay (ms) at In or A (It Off or It On) Residual earth leakage (Vigi) Sensitivity (A) Accuracy: to - % Time delay Dt (ms) Ammeter Type of measurements Instantaneous currents tr I Max resettale time: ms Max reak time: ms Micrologic. / 6. / 7. A tr (s). x 6 x 7. x It Off It On tsd (max resettale time) tsd (max reak time) ANSI Code Ii = In x Micrologic. / 6. / 7. A Other ranges or disale y changing long-time rating plug () () minutes efore and after tripping t off D E F G.. H.9.9 J It on tr It off tsd Ii. I Max resettale time: ms Max reak time: ms ANSI Code N Ig = In x In y A A < In < A In u A Settings It Off It On tg (max resettale time) tg (max reak time) ANSI Code G IDn Micrologic 6. A A B C Micrologic 7. A. Settings Dt (max resettale time) Dt (max reak time) DB36.eps Earth fault Accuracy: ± % DB37.eps Time delay (ms) at x (It Off or It On) Instantaneous Accuracy: ± % Time delay t Protection Long time ANSI Code 9 Current setting (A) = In x Tripping etween. and. x Time setting Time delay (s) Accuracy: to -3 % Accuracy: to - % Accuracy: to - % Thermal memory () to - % - () to -6 % Short time ANSI Code = x Accuracy: ± % Settings Time setting tsd (s) Other ranges or disale y changing long-time rating plug () () minutes efore and after tripping DB3.eps Long time ANSI Code 9 Current setting (A) Tripping etween. and. x Time setting Time delay (s) Accuracy: to -3 % Accuracy: to - % Accuracy: to - % Thermal memory () to - % - () to -6 % Instantaneous ANSI Code = x Accuracy: ± % Time delay DB3.eps Protection Micrologic. /. / 6. / 7. A Range. to. I, I, I3, IN. to In Ig (6. A) to 3 A IDn (7. A). to. Current maximeters of I, I, I3, IN Note: all current-ased protection functions require no auxiliary source. The test / reset utton resets maximeters, clears the tripping indication and tests the attery. Accuracy ±. % ± % ±. % ±. % A-

16 Functions and characteristics Micrologic control units Micrologic E energy DB3.eps Micrologic E control units protect power circuits. They also offer measurements, display, communication and current maximeters. Version 6 provides earth-fault protection. "Energy meter" measurements In addition to the ammeter measurements of Micrologic A Micrologic E control units measure and display: current demand voltages: phase to phase, phase to neutral, average () and unalanced () instantaneous power: P, Q, S power factor: PF power demand: P demand energy: Ep, Eq (), Es (). Accuracy of active energy Ep is % (including the sensors). The range of measurement is the same as current with Micrologic A, depending of an external power supply module ( V DC). Communication option In conjunction with the COM communication option, the control unit transmits the following: settings all "ammeter" and "energy" measurements enale connection to FDM tripping causes maximeter / minimeter readings. Protection Protection thresholds and delays are set using the adjustment dials. Overload protection True rms long-time protection. Thermal memory: thermal image efore and after tripping. Setting accuracy may e enhanced y limiting the setting range using a different long-time rating plug. Overload protection can e cancelled using a specific LT rating plug "Off". Short-circuit protection Short-time (rms) and instantaneous protection. Selection of It type (ON or OFF) for short-time delay. Earth-fault protection Residual or source ground return earth fault protection. Selection of It type (ON or OFF) for delay. Neutral protection On three-pole circuit reakers, neutral protection is not possile. On four-pole circuit reakers, neutral protection may e set using a three-position switch: neutral unprotected (P 3d), neutral protection at. (P 3d + N/), neutral protection at (P d). Zone selective interlocking (ZSI) A ZSI terminal lock may e used to interconnect a numer of control units to provide total discrimination for short-time and earth-fault protection, without a delay efore tripping. Overload alarm A yellow alarm LED goes on when the current exceeds the long-time trip threshold long-time threshold and tripping delay overload alarm (LED) at. short-time pick-up and tripping delay instantaneous pick-up earth-leakage or earth-fault pick-up and tripping delay earth-leakage or earth-fault test utton long-time rating plug screw test connector lamp test, reset and attery test indication of tripping cause digital display three-phase argraph and ammeter navigation utton "quick View" (only with Micrologic E) navigation utton to view menu contents navigation utton to change menu Programmale contacts The programmale contacts may e used to signal events (,, Alarm, Alarm Ig, Ig). They can e programmed using the keypad on the Micrologic E control unit or remotely using the COM option (BCM ULP) and RSU software. Fault indications LEDs indicate the type of fault: overload (long-time protection ) short-circuit (short-time or instantaneous li protection) earth fault (Ig) internal fault (Ap). Trip history The trip history displays the list of the last trips. For each trip, the following indications are recorded and displayed: the tripping cause:,, li, Ig or Auto-protection (Ap) trips the date and time of the trip (requires communication option). Battery power The fault indication LEDs remain on until the test/reset utton is pressed. Under normal operating conditions, the attery supplying the LEDs has a service life of approximately years. Test () Display on FDM only. Note: Micrologic E control units come with a transparent lead-seal cover as standard. A- A mini test kit or a portale test kit may e connected to the test connector on the front to check circuit-reaker operation. For Micrologic 6. E control units, the operation of earth-fault or earth-leakage protection can e checked y pressing the test utton located aove the test connector.

17 Micrologic. E tr (s). x 6 x 7. x Earth fault Accuracy: ± % Time setting tg (s) Time delay (ms) at In or A (It Off or It On) Energy Type of measurements Instantaneous currents tr I Max resettale time: ms Max reak time: ms Micrologic. / 6. E tr (s). x 6 x 7. x It Off It On tsd (max resettale time) tsd (max reak time) ANSI Code Ii = In x Micrologic. / 6. E Other ranges or disale y changing long-time rating plug () () minutes efore and after tripping t off E F G.. H.9.9 J It on tr It off tsd Ii. I Max resettale time: ms Max reak time: ms ANSI Code N Ig = In x In y A A < In < A In u A Settings It Off It On tg (max resettale time) tg (max reak time) Micrologic 6. E A B C D DB36.eps Time delay (ms) at x (It Off or It On) Instantaneous Accuracy: ± % Time delay t Protection Long time ANSI Code 9 Current setting (A) = In x Tripping etween. and. x Time setting Time delay (s) Accuracy: to -3 % Accuracy: to - % Accuracy: to - % Thermal memory () to - % - () to -6 % Short time ANSI Code = x Accuracy: ± % Settings Time setting tsd (s) Other ranges or disale y changing long-time rating plug () () minutes efore and after tripping DB3.eps Long time ANSI Code 9 Current setting (A) Tripping etween. and. x Time setting Time delay (s) Accuracy: to -3 % Accuracy: to - % Accuracy: to - % Thermal memory () to - % - () to -6 % Instantaneous ANSI Code = x Accuracy: ± % Time delay DB3.eps Protection Micrologic. /. / 6. E Range. to. I, I, I3, IN Ig (6. E). to In. to. Current maximeters of I, I, I3, IN. to. Demand currents of I, I, I3, Ig Voltages V, V3, V3, VN, VN, V3N to 69 V Active power P 3 to kw Power factor PF to Demand power P demand 3 to kw Active energy Ep - GWh to GWh Note: all current-ased protection functions require no auxiliary source. The test / reset utton resets maximeters, clears the tripping indication and tests the attery. Accuracy ±. % ± % ±. % ±. % ±. % ± % ± % ± % ± % A-3

18 Functions and characteristics Micrologic control units Micrologic P "power" DB.eps Micrologic P control units include all the functions offered y Micrologic A. In addition, they measure voltages and calculate power and energy values. They also offer new protection functions ased on currents, voltages, frequency and power reinforce load protection in real time. Protection... + Protection settings The adjustale protection functions are identical to those of Micrologic A (overloads, short-circuits, earth-fault and earth-leakage protection). Fine adjustment Within the range determined y the adjustment dial, fine adjustment of thresholds (to within one ampere) and time delays (to within one second) is possile on the keypad or remotely using the COM option. IDMTL (Inverse Definite Minimum Time Lag) setting Coordination with fuse-type or medium-voltage protection systems is optimised y adjusting the slope of the overload-protection curve. This setting also ensures etter operation of this protection function with certain loads. Neutral protection On three-pole circuit reakers, neutral protection may e set using the keypad or remotely using the COM option, to one of four positions: neutral unprotected (P 3d), neutral protection at. (P 3d + N/), neutral protection at (P d) and neutral protection at.6 (P 3d +.6N). Neutral protection at.6 is used when the neutral conductor is twice the size of the phase conductors (major load imalance, high level of third order harmonics). On four-pole circuit reakers, neutral protection may e set using a three-position switch or the keypad: neutral unprotected (P 3d), neutral protection at. (P 3d + N/), neutral protection at (P d). Neutral protection produces no effect if the long-time curve is set to one of the IDMTL protection settings. Programmale alarms and other protection Depending on the thresholds and time delays set using the keypad or remotely using the COM option, the Micrologic P control unit monitors currents and voltage, power, frequency and the phase sequence. Each threshold overrun is signalled remotely via the COM option. Each threshold overrun may e comined with tripping (protection) or an indication carried out y an optional M6C programmale contact (alarm), or oth (protection and alarm). Load shedding and reconnection Load shedding and reconnection parameters may e set according to the power or the current flowing through the circuit reaker. Load shedding is carried out y a supervisor via the COM option or y an M6C programmale contact. Indication option via programmale contacts The M6C (six contacts) auxiliary contacts may e used to signal threshold overruns or status changes. They can e programmed using the keypad on the Micrologic P control unit or remotely using the COM option (BCM ULP) and RSU software. Communication option (COM) Long-time current setting and tripping delay. Overload signal (LED). 3 Short-time pick-up and tripping delay. Instantaneous pick-up. Earth-leakage or earth-fault pick-up and tripping delay. 6 Earth-leakage or earth-fault test utton. 7 Long-time rating plug screw. Test connector. 9 Lamp + attery test and indications reset. Indication of tripping cause. High-resolution screen. Measurement display. 3 Maintenance indicators. Protection settings. Navigation uttons. 6 Hole for settings lockout pin on cover. Note: Micrologic P control units come with a non-transparent lead-seal cover as standard. A- The communication option may e used to: remotely read and set parameters for the protection functions transmit all the calculated indicators and measurements signal the causes of tripping and alarms consult the history files and the maintenance-indicator register maximeter reset. An event log and a maintenance register, stored in control-unit memory ut not availale locally, may e accessed in addition via the COM option.

19 Earth fault Accuracy: ± % Time setting tg (s) Time delay (ms) at In or A (It Off or It On) Residual earth leakage (Vigi) Sensitivity (A) Accuracy: to - % Time delay Dt (ms) ANSI Code N Ig = In x In y A A < In < A In u A Settings tg (max resettale time) tg (max reak time) ANSI Code G IDn It Off It On Settings Dt (max resettale time) Dt (max reak time) Alarms and other protection Current Current unalance Max. demand current Earth fault alarm Voltage Voltage unalance Minimum voltage Maximum voltage() Power Reverse power Frequency Minimum frequency Maximum frequency Phase sequence Sequence (alarm) Max resettale time: ms Max reak time: ms Micrologic 6. P A B C D Micrologic 7. P off E F G.. H.9.9 J 7 3 Micrologic. / 6. / 7. P Threshold. to.6 Iaverage. In to In Delay to s to s It to % In(3) to s Uunalance Umin Umax ANSI Code to 3 % x Uaverage to s to Umax etween phases. to s Umin to etween phases. to s rp 3P to kw. to s Fmin Fmax L H to Fmax Fmin to Hz. to s. to s DØ Ø//3 or Ø/3/ s I P Threshold. to per phases kw to MW Delay % tr to % tr to 36 s Power Micrologic. / 6. / 7. P Micrologic. / 6. / 7. P Type of measurements Range Accuracy. to. ±. % Current maximeters of I, I, I3, IN Voltages V, V3, V3, VN, VN, V3N to 69 V ±. % Power factor PF ±% Frequency (Hz) DB3.eps ANSI Code 6 Iunalance Imax demand : I, I, I3, IN, Load shedding and reconnection Measured value Current Power DB.eps It Off It On tsd (max resettale time) tsd (max reak time) ANSI Code Ii = In x. DB.eps Time delay (ms) at (It Off or It On) Instantaneous Accuracy: ± % Time delay tr (s). x 6 x 7. x Micrologic. / 6. / 7. P Other ranges or disale y changing long-time rating plug () () SIT VIT EIT HVFuse DT minutes efore and after tripping DB6.eps Long time (rms) ANSI Code 9 Current setting (A) = In x Tripping etween. and. x Time setting Time delay (s) Accuracy: to -3 % IDMTL (EIT) Accuracy: to - % Accuracy: to - % IDMTL setting Curve slope Thermal memory () to - % - () to -6 % Short time (rms) ANSI Code = x Accuracy: ± % Time setting tsd (s) Settings + Micrologic. / 6. / 7. P DB7.eps Protection to. % (3) In y A 3 % () For 69 V applications, a step-down transformer must e used if the voltage exceeds the nominal value of 69 V y more A < In < A % than %. In u A % Note: all current-ased protection functions require no auxiliary source. Voltage-ased protection functions are connected to AC power via a voltage measurement input uilt into the circuit reaker. A-

20 Functions and characteristics Motor protection Micrologic. /.3 M electronic trip units Micrologic. /.3 M trip units provide uilt-in thermal and magnetic protection. They are used in -device motor-feeder solutions on Compact NSX to 63 circuit reakers with performance levels B/F/H/N/S/L. They provide protection for motors up to 3 kw at V against: short-circuits overloads with selection of a trip class (, or ) phase unalance. DB.eps Circuit reakers with a Micrologic. /.3 M trip unit include protection similar to an inverse-time thermal relay. They are comined with a contactor. PB3376.eps Protection... Settings are made using a dial. Overloads (or thermal protection): Long-time protection and trip class () Inverse-time thermal protection against overloads with adjustale pick-up. Settings are made in amperes. The tripping curve for the long-time protection, which indicates the time delay tr efore tripping, is defined y the selected trip class. Trip class (class) The class is selected as a function of the normal motor starting time. Class : starting time less than s. Class : starting time less than s. Class : starting time less than s. For a given class, it is necessary to check that all motor-feeder components are sized to carry the 7. starting current without excessive temperature rise during the time corresponding to the class. Short-circuits: Short-time protection () Protection with an adjustale pick-up. There is a very short delay to let through motor starting currents. Short-circuits: Non-adjustale instantaneous protection (li) Instantaneous protection with non-adjustale pick-up Ii. Phase unalance or phase loss (lunal) ( ) This function opens the circuit reaker if a phase unalance occurs: that is greater than the 3 % fixed pick-up Iunal following the non-adjustale time delay tunal equal to: vv.7 s during starting vv s during normal operation. Phase loss is an extreme case of phase unalance and leads to tripping under the same conditions. Indications Front indications Green Ready LED: flashes slowly when the circuit reaker is ready to trip in the event of a fault. Red alarm LED for motor operation: goes ON when the thermal image of the rotor and stator is greater than 9 % of the permissile temperature rise. Remote indications via SDTAM module Compact NSX devices with a Micrologic can e equipped with an SDTAM module dedicated to motor applications for: a contact to indicate circuit-reaker overload a contact to open the contactor. In the event of a phase unalance or overload, this output is activated ms efore circuit-reaker tripping to open the contactor and avoid circuit reaker tripping. This module takes the place of the MN/MX coils and an OF contact. SDTAM remote indication relay module with its terminal lock. Note: all the trip units have a transparent lead-sealale cover that protects access to the adjustment dials. A-

21 Micrologic. /.3 M Ratings (A) In at 6 C () 3 Circuit reaker Compact NSX Compact NSX Compact NSX - - Compact NSX Compact NSX L Overloads (or thermal protection): Long-time protection and trip class value depending on trip unit rating (In) and setting on dial tripping etween In = A = 6 3. and. In = A = In = A = In = A = In = A = 7 In = 3 A = In = A = Trip class as per IEC Time delay (s) tr. x for warm motor depending on selected trip class 6 x for cold motor 7. x for cold motor Thermal memory minutes efore and after tripping Cooling fan non-adjustale - motor self-cooled S Short-circuits: Short-time protection with fixed time delay accuracy ± % = x Time delay (ms) tsd non-adjustale Non-tripping time Maximum reak time 6 I Short-circuits: Non-adjustale instantaneous protection Ii non-adjustale accuracy ± % Time delay (ms) Non-tripping time Maximum reak time 3 Phase unalance or phase loss Iunal in % average current () > 3 % accuracy ± % Time delay (s) non-adjustale.7 s during starting s during normal operation () Motor standards require operation at 6 C. Circuit-reaker ratings are derated to take this requirement into account (see page B-). () The unalance measurement takes into account the most unalanced phase with respect to the average current. DB.eps DB66.eps Unalance of phase currents and voltages. to s Long start time limit Starting time % Motor starting and long starts. Motor-off zone Return Overrun. (Micrologic M) or Ilong (Micrologic 6 E-M) Additional technical characteristics Phase unalance An unalance in three-phase systems occurs when the three voltages are not equal in amplitude and/or not displaced with respect to each other. It is generally due to single-phase loads that are incorrectly distriuted throughout the system and unalance the voltages etween the phases. These unalances create negative current components that cause raking torques and temperature rise in asynchronous machines, thus leading to premature ageing. Phase loss Phase loss is a special case of phase unalance. During normal operation, it produces the effects mentioned aove and tripping must occur after four seconds. During starting, the asence of a phase may cause motor reversing, i.e. it is the load that determines the direction of rotation. This requires virtually immediate tripping (.7 seconds). Starting time in compliance with the class (Micrologic M) For normal motor starting, Micrologic M checks the conditions elow with respect to the thermal-protection (long-time) pick-up : current > % x (motor-off limit) overrun of. x threshold, then return elow this threshold efore the end of a s time delay. If either of these conditions is not met, the thermal protection trips the device after a maximum time equal to that of the selected class. Pick-up must have een set to the current indicated on the motor rating plate. Long starts (Micrologic 6 E-M) When this function is not activated, the starting conditions are those indicated aove. When it is activated, this protection supplements thermal protection (class). A long start causes tripping and is characterised y: current > % x (motor-off limit) with: either overrun of the long-time pick-up ( to x ) without return elow the pick-up efore the end of the long-time time delay ( to s) or no overrun of the long-time pick-up ( to x ) efore the end of the long-time time delay ( to s). Pick-up must have een set to the current indicated on the motor rating plate. This protection should e coordinated with the selected class. A-

22 Functions and characteristics Motor protection Micrologic 6 E-M electronic trip units PB3376.eps Micrologic 6.E-M is used in -device motor-feeder solutions. It provides the same protection as Micrologic M: short-circuits overloads with selection of the same trip classes (, or ), plus trip class 3 for starting of machines with high inertia. In addition, it offers specific motor-protection functions that can e set via the keypad. SDTAM remote indication relay module with its terminal lock. Note: all the trip units have a transparent lead-sealale cover that protects access to the adjustment dials. A-6 DB6 Protection The protection functions are identical to those of Micrologic M and can e fine-adjusted via the keypad. Access to setting modifications via the keypad is protected y a locking function that is controlled y a microswitch. The lock is activated automatically if the keypad is not used for minutes. Access to the microswitch is protected y a transparent lead-sealale cover. It is possile to scroll through settings and measurements with the cover closed. Overloads (or thermal), class and short-circuits The long-time, short-time and instantaneous functions are identical to those of Micrologic M. In addition, there is trip class 3 for long-time protection and a setting for self-cooled or fan-cooled motors ( ). Ground-fault protection (Ig) Residual type ground-fault protection with an adjustale pick-up Ig (with Off position) and adjustale time delay tg. Phase unalance or phase loss (lunal) This function opens the circuit reaker if a phase unalance occurs: that is greater than the Iunal pick-up that can e fine-adjusted from to % (3 % y default) following the tunal time delay that is: vv.7 s during starting vvadjustale from to seconds ( seconds y default) during normal operation. Phase loss is an extreme case of phase unalance and leads to tripping under the same conditions. Locked rotor (Ijam) This function detects locking of the motor shaft caused y the load. During motor starting (see page A-), the function is disaled. During normal operation, it causes tripping: aove the Ijam pick-up that can e fine-adjusted from to x in conjunction with the tjam time delay that can e adjusted from to 3 seconds. Under-load (Iund) This function detects motor no-load operation due to insufficient load (e.g. a drained pump). It detects phase undercurrent. During motor starting (see page A-), the function is always enaled. During normal operation, it causes tripping: elow the Iund pick-up that can e fine-adjusted from to.9 x in conjunction with the tund time delay that can e adjusted from to seconds. Long starts (Ilong) This protection supplements thermal protection (class). It is used to etter adjust protection to the starting parameters. It detects anormal motor starting, i.e. when the starting current remains too high or too low with respect to a pick-up value and a time delay. It causes tripping: in relation with a llong pick-up that can e fine-adjusted from to x in conjunction with the tlong time delay that can e adjusted from to seconds. (see "long starts" page A-) Display of type of fault On a fault trip, the type of fault (,, Ii, Ig, lunal, ljam), the phase concerned and the interrupted current are displayed. Indications Front indications Green Ready LED: flashes slowly when the circuit reaker is ready to trip in the event of a fault. Red alarm LED for motor operation: goes ON when the thermal image of the rotor or stator is greater than 9% of the permissile temperature rise. Remote indications via SDTAM or SDx module See description on page A- for SDTAM and page A-93 for SDx.

Micrologic control units 2.0 E X Y Z. Overview of functions. Functions and characteristics

Micrologic control units 2.0 E X Y Z. Overview of functions. Functions and characteristics Overview of functions All Masterpact circuit breakers are equipped with a Micrologic control unit that can be changed on site. Control units are designed to protect Power circuits and loads. Alarms may

More information

Maintenance/Connection/Installation Service life C/O cyclesx1000

Maintenance/Connection/Installation Service life C/O cyclesx1000 EasyPact MVS 2016 CPB100000 CPB100014 Circuit breaker. Switch disconnector. Common characteristics Number of poles Rated insulation voltage (V) Impulse withstand voltage (kv) Rated operational voltage

More information

SINCE 1989 Quality Products, Prompt Services, Trustful Relationships www.kmindustrialcorp.com KM Industrial Corporation has estalished itself as a trusted supplier of Electrical, Machinery and Industry

More information

from 0.5 to 125 A Electrical characteristics Sensitivity type (ma) a AC Electrical auxiliaries Auxiliary and alarm switches (OF-SD)

from 0.5 to 125 A Electrical characteristics Sensitivity type (ma) a AC Electrical auxiliaries Auxiliary and alarm switches (OF-SD) Acti 9 Acti 9 circuit reakers from 0.5 to 125 A 056903N-32_SE.eps 056806N-28_SE.eps PB104440_28.eps PB107141_28.eps Acti 9 circuit reaker C120N Numer of poles 1 2-3-4 Electrical characteristics Rated current

More information

A9 R Range Family Code Internal code Poles Code Rating (A) Code Acti 9 (A9) iid R

A9 R Range Family Code Internal code Poles Code Rating (A) Code Acti 9 (A9) iid R Earth leakage protection Principle of catalogue numers A9 R 15 2 63 Range Family Code Internal code Poles Code Rating (A) Code Acti 9 (A9) iid R 0 0 0 00 Vigi ic60 V 1P 1 0.5 70 ic60 F 2P 2 0.75 71 ik60

More information

Compact NS630b to 1600

Compact NS630b to 1600 Compact NS630 to 1600 Fixed circuit reakers The diagram is shown with circuits de-energised, all devices open, connected and charged and relays in the nmal position. Power Control unit DB8378.eps Power

More information

Micrologic 5 and 6 Electronic Trip Units User Guide

Micrologic 5 and 6 Electronic Trip Units User Guide .9 3.9.9 4 1.9 6 4 3 5.5 6 8 1.5 1 0 Micrologic 5 and 6 Electronic Trip Units User Guide for PowerPact H-, J-, and L-Frame Circuit Breakers Instruction Bulletin 48940-31-01 Rev. 04, 07/015 Retain for future

More information

Technical catalogue. Emax Low voltage air circuit-breakers. Hotline:

Technical catalogue. Emax Low voltage air circuit-breakers.   Hotline: Technical catalogue Emax Low voltage air circuit-breakers www.alobitanbd.com Hotline: 01711548558 PAGE : 02 The new Emax have received innumerable international certifications and approval by the major

More information

TeSys circuit-breakers Thermal-magnetic motor circuit-breakers types GV2, GV3 and GV7

TeSys circuit-breakers Thermal-magnetic motor circuit-breakers types GV2, GV3 and GV7 Presentation Thermal-magnetic motor circuit-breakers types GV, GV and GV7 GV-ME, GV-P, GV-ME and GV7-R motor circuit-breakers are -pole thermal-magnetic circuit-breakers specifically designed for the control

More information

Mould circ. Moulded case circuit-breakers

Mould circ. Moulded case circuit-breakers Mould circ Moulded case circuit-breakers Moulded case circuit-breakers Tmax Contents Power distribution circuit-breakers Technical Data... 7/6 Ordering details Reading information... 7/15 Tmax T1... 7/20

More information

11/0 IZM circuit-breakers, IN switch-disconnectors

11/0 IZM circuit-breakers, IN switch-disconnectors 11/0 IZM circuit-breakers, IN switch-disconnectors Contents IZM circuit-breakers, IN switch-disconnectors 11/1 from 630 A 6300 A Page Description 11/2 Technical overview 11/4 Overview of functions for

More information

3 - Protection components Circuit-breakers

3 - Protection components Circuit-breakers Contents - Protection components Circuit-breakers for the motor protection Selection guide..............................................page /2 Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

Choice of earth leakage protection devices

Choice of earth leakage protection devices Protection Choice of earth leakage protection devices DB123167 DB123168 DB123169 Choice of sensitivity The sensitivity of an earth leakage protection device depends mainly on the function it has to perform:

More information

Protective Relays Digitrip 3000

Protective Relays Digitrip 3000 New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer

More information

Application note. How to shed non-priority loads with a Compact NSX circuit breaker?

Application note. How to shed non-priority loads with a Compact NSX circuit breaker? Technical collection How to shed non-priority loads with a Compact NSX circuit breaker? Equipment, diagrams and configurations required for the load-shedding function Application note Delestage_compact_en.indd

More information

Electrical Protection System Design and Operation

Electrical Protection System Design and Operation ELEC9713 Industrial and Commercial Power Systems Electrical Protection System Design and Operation 1. Function of Electrical Protection Systems The three primary aims of overcurrent electrical protection

More information

Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11

Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11 Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11 COMMISSIONING 12-16 DRAWINGS 17-18 1 1. INTRODUCTION APPLICATION

More information

Low Voltage. Vigirex Residual-current protection relays

Low Voltage. Vigirex Residual-current protection relays Low Voltage Vigirex Residualcurrent protection relays WEB1 cat.201 Green Premium TM Endorsing ecofriendly products in the industry Schneider Electric s Green Premium ecolael is committed to offering transparency,

More information

PM5000 Series. PowerLogic PM5100, PM5300 and PM5500 series

PM5000 Series. PowerLogic PM5100, PM5300 and PM5500 series Functions and characteristics PowerLogic PM5100, PM5300 and PM5500 series PB111776 The PowerLogic applications. It provides the measurement capailities needed to allocate energy usage, perform tenant metering

More information

Low Voltage. Residual-current protection relays

Low Voltage. Residual-current protection relays Low Voltage Residual-current protection relays Class II insulated for the entire range as per standards IEC/EN 60664-1 and NFC 15-100. Front-panel mount DIN rail with clip-in toroid with mounting

More information

Siemens AG Allows easy and consistent configuration with one series of overload relays (for small to large loads)

Siemens AG Allows easy and consistent configuration with one series of overload relays (for small to large loads) Overview Features Benefits 3RU11 3RB20/3RB21 3RB22/3RB23 Sizes Are coordinated with the dimensions, connections S00...S3 S00... S12 S00... S12 and technical characteristics of the other devices in the

More information

(With the possibility of a tripping coil for remote control) (Generally optional with an electronic tripping device)

(With the possibility of a tripping coil for remote control) (Generally optional with an electronic tripping device) Page 1 of 22 Personal tools Log in / create account Circuit-breaker From Electrical Installation Guide The circuit-breaker/disconnector fulfills all of the basic switchgear functions, while, by means of

More information

Protection and control. Sepam range Sepam 2000 Metering and protection functions

Protection and control. Sepam range Sepam 2000 Metering and protection functions Protection and control Sepam range Sepam 2 Metering and protection functions Contents chapter / page metering functions 1/1 protection functions 2/1 appendix 3/1 Notation c Sepam 2 may include several

More information

TeSys H. Protection. Motor controllers. Reliable. Motor starters. Contactors. Circuit breakers. Smart. Ultra-compact 22.5 mm motor starters

TeSys H. Protection. Motor controllers. Reliable. Motor starters. Contactors. Circuit breakers. Smart. Ultra-compact 22.5 mm motor starters Low voltage Catalogue 205/206 Ultra-compact 22.5 mm motor starters Motor starters Flexible Smart Circuit breakers Protection Contactors Thermal overload relays Fuse switchdisconnectors Reliable Motor controllers

More information

Bulletin 140U Molded Case Circuit Breakers

Bulletin 140U Molded Case Circuit Breakers Bulletin 40U Multitap End Cap Optional Optional Optional 40U-J-MTLA 40U-J-MTL6A 40U-J-ECM Aluminum Aluminum Molded Housing /4 screw /4 screw lb-in lb-in.6 N m.6 N m Cu/Al Cu/Al 60/7 C 60/7 C () (6) (A)

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

Curves TeSys Model U 0 Starter-controllers

Curves TeSys Model U 0 Starter-controllers Curves TeSys Model U 0 Tripping curves for control units LUCA, LUCB, LUCD Average operating times at 0 C according to multiples of the setting current, tolerance : ± 0 %. Time (s) 000 00 0 0, LUCD, poles

More information

Phase and neutral overcurrent protection

Phase and neutral overcurrent protection Phase and neutral overcurrent protection Page 1 ssued June 1999 Changed since July 1998 Data subject to change without notice (SE970165) Features Two-phase or three-phase time-overcurrent and earth fault

More information

Merlin Gerin Circuit breaker application guide

Merlin Gerin Circuit breaker application guide Reset Micrologic 70 Ir Isd Ig Ap reset I i I n 0 1 2 5 3 push OFF push ON O OFF discharged NX 32 H 2 Ue Icu 220/440 525 690 cat.b (V) (ka) Ics = 100% Icu IEC 947-2 EN 60947-2 100 100 85 Icw 85kA/1s 50/60Hz

More information

Circuit breakers for direct current applications

Circuit breakers for direct current applications Circuit breakers for direct current applications Complementary technical information schneider-electric.com Complementary technical information Circuit breakers for direct current applications Contents

More information

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009 Catalog 00 Contactors up to 5 A Motor Starters up to 55 kw 03/009 Kraus & Naimer The development of the Blue Line rotary switch, contactor and motor starter product ranges is based on more than hundred

More information

Page 13-2 Page Page 13-7

Page 13-2 Page Page 13-7 Page -2 Page -6 MINIATURE CIRCUIT BREAKERS UP TO 63A 1P, 1P+N, 2P, 3P and 4P versions IEC rated current In: 1-63A IEC short-circuit capacity Icn: 10kA (6kA for 1P+N) Trip characteristic curve: Type B,

More information

TeSys contactors. TeSys D contactors. IEC/EN , IEC/EN , UL 508, CSA C22.2 n 14. Protection against direct fi nger contact IP 2X

TeSys contactors. TeSys D contactors. IEC/EN , IEC/EN , UL 508, CSA C22.2 n 14. Protection against direct fi nger contact IP 2X Characteristics Contactor type LC1 D09 D18 DT20 and DT25 Environment Rated insulation voltage (Ui) Conforming to IEC 097--1, overvoltage category III, degree of pollution: 3 Conforming to UL, CSA V 00

More information

Sepam protection relays, the product of experience

Sepam protection relays, the product of experience Introduction Sepam protection relays, the product of experience PE50773_SE complete range for many different needs Protection relays constantly monitor the power network and trip the circuit reakers to

More information

PD300. Transformer, generator and motor protection Data sheet

PD300. Transformer, generator and motor protection Data sheet PD300 Transformer, generator and motor protection Data sheet DSE_PD300_eng_AO No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam T&D. One of

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

L O V A G. T E S T I N S T R U C T I O N I E C / E N E d C O N D I T I O N S F O R T E S T I N G

L O V A G. T E S T I N S T R U C T I O N I E C / E N E d C O N D I T I O N S F O R T E S T I N G LTI IEC/EN 60947-4-1 Ed.3.1 L O V A G T E S T I N S T R U C T I O N I E C / E N 6 0 9 4 7-4 - 1 E d. 3. 1 C O N D I T I O N S F O R T E S T I N G C O N T A C T O R S A N D M O T O R - S T A R T E R S This

More information

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd. Functional Range - Earth Fault Relay C&S Protection & Control Ltd. 2 Contents Page No. 1. Application 2. Operating Principle. Current Transformer Connections 5. Connections, Contact Arrangement and Setting

More information

Coordination of LV protection devices

Coordination of LV protection devices Technical collection Coordination of LV protection devices Low voltage expert guides n 5 DBTP107EN_Couv.indd 1 12/06/2009 14:32:52 Sans titre-1 1 12/06/2009 14:13:13 Contents Glossary 2 The requirements

More information

Modeion OTHER ACCESSORIES OF MOULDED CASE CIRCUIT BREAKERS

Modeion OTHER ACCESSORIES OF MOULDED CASE CIRCUIT BREAKERS OTHER ACCESSORIES OF MOULDED CASE CIRCUIT BREAKERS P Other accessories DELAY UNIT Type Product code Description Weight [kg] Package [pc] BZ-BX-X230-A 36696 enables to delay the undervoltage release tripping

More information

FINAL - ET 60 - Electrician Theory Examination Marking Schedule

FINAL - ET 60 - Electrician Theory Examination Marking Schedule FINAL - ET 60 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions.

More information

Centrale de mesure Power Meter PM500 Merlin Gerin

Centrale de mesure Power Meter PM500 Merlin Gerin Notice d'installation et d'utilisation Installation and user manual Centrale de mesure Power Meter PM500 Merlin Gerin 059473_D Introduction and description Package contents c one PM500 power meter with

More information

Mini Contactors. Mini Contactor Relays 4-pole 8 Auxiliary Contact Blocks. Interface Contactor Relays. Mini Contactors 10 Auxiliary Contact Blocks

Mini Contactors. Mini Contactor Relays 4-pole 8 Auxiliary Contact Blocks. Interface Contactor Relays. Mini Contactors 10 Auxiliary Contact Blocks Mini Contactors Mini Contactor Relays 4-pole 8 Auxiliary Contact Blocks Interface Contactor Relays Mini Contactors 10 Auxiliary Contact Blocks Mini Contactors With Fast On Tab Connectors 12 Mini Contactors

More information

Circuit Breakers. Excerpt from Master Catalogue. Circuit Breakers. Specifically For You

Circuit Breakers. Excerpt from Master Catalogue. Circuit Breakers. Specifically For You Circuit Breakers Excerpt from Master Catalogue Circuit Breakers Specifically For You Hydraulic-magnetic technology ensures reduced nuisance tripping with temperature variance Always holds 00% rated current

More information

Single Phase Soft Starters

Single Phase Soft Starters Submittal Data English Language/IP Units 04/14 Contact Information: Hyper Engineering, Pty. Ltd. 4 / 14 Ralph Black Dr Wollongong Nth, NSW 2500 AUSTRALIA www.hypereng.com sales@hypereng.com (877) 304-0724

More information

Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613

Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613 Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613 Data Bulletin 0613IB1201 06/2012 Retain for future use. 0613IB1201 Modbus Communications System for Micrologic A, P, and H

More information

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features CT ratio Power Harmonics ac+dc 200ADM-P Current Injection System with Phase Shift Features 0-200A output current True RMS metering with 1 cycle capture Variable auxiliary AC voltage/current output with

More information

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz TAC ATV8, IP55 Variable Speed Drives for Asynchronous Motors. -phase. 80/460 V, 50-60 Hz E-60-24 24 May 2004 ATV 8 IP55 drives are specifically designed for pump and fan applications powered by a three-phase

More information

PowerLogic power-monitoring units. PM700 series power meter. Technical data sheet

PowerLogic power-monitoring units. PM700 series power meter. Technical data sheet PowerLogic power-monitoring units PM700 series power meter Technical data sheet 2009 Functions and characteristics The PowerLogic PM700 series power meter offers all the measurement capabilities required

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and

More information

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION GEK-00682D INTRODUCTION INTRODUCTION. PRODUCT DESCRIPTION The MDP Digital Time Overcurrent Relay is a digital, microprocessor based, nondirectional overcurrent relay that protects against phase-to-phase

More information

Miniature circuit breakers. Residential current circuit breakers. Busbar systems. Comfort functions/energy control. Residential enclosures

Miniature circuit breakers. Residential current circuit breakers. Busbar systems. Comfort functions/energy control. Residential enclosures .2..4.5.6.7 Technical data Series ME07 Standard range S, S, 0/690V/AC High performance range H, 0/690V/AC High performance range H/S, 000V/AC Disconnecting switch MET DC circuit breaker ME 6T up to 0V/DC

More information

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR). RETROFITTING Motor Protection Relay NPM800R (R2 case) and NPM800RE (R3 case) are dedicated to the refurbishment of 7000 series (R2 and R3 cases) of CEE relays providing the protection of medium voltage

More information

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS Juan Manuel Gers, PhD Protection coordination principles Relay coordination is the process of selecting settings that will assure that the relays

More information

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM SYSTEM OVERVIEW Pollution monitoring of high voltage insulators in electrical power transmission and distribution systems, switchyards and substations is essential in order to minimise the risk of power

More information

Substation applications

Substation applications Substation applications To make it easy to choose the right for a protection application, the most typical applications are presented with the type of for them. Each sample application is presented by:

More information

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE PAGE 262400-1 SECTION 262400 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

BE1-32R, BE1-32 O/U DIRECTIONAL POWER RELAY

BE1-32R, BE1-32 O/U DIRECTIONAL POWER RELAY BE1-32R, BE1-32 O/U DIRECTIONAL POWER RELAY The BE1-32R Directional Overpower Relay and the BE1-32 O/U Directional Over/Underpower Relay are solid-state devices which provide versatility and control in

More information

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator Test results and settings are saved into local memory

More information

Protection relays and transformers

Protection relays and transformers NEW ZEALAND WWW.LPINZ.CO.NZ Unit 6/22 Moselle Ave, Henderson, Auckland, New Zealand PO Box 21-872, Henderson, Auckland, New Zealand Phone:+64 9 833 5749 Email:info@LPINZ.co.nz Web: www.lpinz.co.nz Protection

More information

TD 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

TD 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers Secondary Injection Relay Test Set Designed for testing relays and transducers Two current outputs to test differential relays Convertible current and voltage generator With phase angle shifter Frequency

More information

Btdin RCD Add-on modules 63A for MCBs 1,5 modules per pole

Btdin RCD Add-on modules 63A for MCBs 1,5 modules per pole Index Pages 1. Descripton... 2 2. Product range... 2 3. Overall dimensions... 2 4. Fixing Connection... 3 5. Generl characteristics... 4 6. Compliance - Approvals... 6 7. Curves... 7 8. Auxiliares and

More information

Type: DILM80(110V50HZ,120V60HZ) Article No.: Sales text Contactor,37kW/400V,AC operated. Ordering information

Type: DILM80(110V50HZ,120V60HZ) Article No.: Sales text Contactor,37kW/400V,AC operated. Ordering information Type: DILM80(110V50HZ,120V60HZ) Article No.: 239399 Sales text Contactor,37kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current AC 3 380 V 400

More information

Type: DILM95(230V50HZ,240V60HZ) Article No.: Sales text Contactor,45kW/400V,AC operated. Ordering information

Type: DILM95(230V50HZ,240V60HZ) Article No.: Sales text Contactor,45kW/400V,AC operated. Ordering information Type: DILM95(230V50HZ,240V60HZ) Article No.: 239480 Sales text Contactor,45kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current AC 3 380 V 400

More information

3RA13, 3RA14 Contactor Assemblies

3RA13, 3RA14 Contactor Assemblies RA, RA Contactor Assemblies RA Contactor Assemblies for Wye-Delta Starting RA complete units,... kw Siemens AG 0 Overview These RA contactor assemblies for wye-delta starting are designed for standard

More information

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Dual-Source Power Supply Addendum to I.B. 17555 Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Table of Contents Page 1.0 Introduction...1 2.0 General

More information

Miniature Circuit Breakers B4/B6/B10, Residual Current Devices & Isolating Switches

Miniature Circuit Breakers B4/B6/B10, Residual Current Devices & Isolating Switches Miniature ircuit reakers 4//, esidual urrent evices & Isolating Switches The IMO range of miniature circuit breakers have been designed for protection of electrical installations against overload and short

More information

ECM3 EARTH CONTINUITY RELAY

ECM3 EARTH CONTINUITY RELAY TECHNICAL DATASHEET ECM3 EARTH CONTINUITY RELAY Electrical Protection for Hard Rock Mines Application The ECM3 has been designed to provide earth continuity protection for cables containing pilot cores.

More information

TSX Series. Modicon Manuals. Presented by: Modicon PLC. Schneider Electric Quantum Modicon Gould Gettys

TSX Series. Modicon Manuals. Presented by: Modicon PLC. Schneider Electric Quantum Modicon Gould Gettys TSX Series Modicon Manuals Presented by: Modicon PLC Schneider Electric Quantum Modicon Gould Gettys For Product Needs: Email: sales@modiconplc.com Call: 1-800-691-8511 Fax: 919-415-1614 ModiconPLC.com

More information

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Solkor R & Solkor Rf

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

Numerical Multi-Function Motor Protection Relay RHO 3. Operation & Maintenance Instruction Manual

Numerical Multi-Function Motor Protection Relay RHO 3. Operation & Maintenance Instruction Manual Numerical Multi-Function Motor Protection Relay RHO 3 Operation & Maintenance Instruction Manual RHO MANUAL Contents Section Page Description of operation 4 2 Performance specification 20 3 Relay settings

More information

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS AND MEDIUM-SIZE FACILITIES (5,000-25,000KW) CONNECTED

More information

Protection and control VIP300. Technical manual

Protection and control VIP300. Technical manual Protection and control VIP300 Technical manual contents 1. presentation of the VIP300...3 2. use and settings...4 3. choice of sensors and operating ranges...9 4. connection scheme...10 5. assembly...11

More information

Installation / Monitoring Technique

Installation / Monitoring Technique Installation / Monitoring Technique VARIMETER RCM Residual Current Monitor, Type B for AC and DC Systems IP 5883 0249633 IP 5883 ND 5018/035 ND 5018/030 According to IEC/EN 62 020, VDE 0663 For AC and

More information

DRTS-6. DRTS-6 has been designed to test: DRTS-6. Advanced Protection Relay Test Set and Measurement System

DRTS-6. DRTS-6 has been designed to test: DRTS-6. Advanced Protection Relay Test Set and Measurement System DRTS-6 Advanced Protection Relay Test Set and Measurement System MULTI-TASKING EQUIPMENT DESIGNED FOR TESTING PROTECTION RELAYS, ENERGY METERS, TRANSDUCERS POWERFUL AND LIGHTWEIGHT HIGH ACCURACY: BETTER

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

SIRCO M UL98 Load break switches standards UL and CSA 30 to 100 A

SIRCO M UL98 Load break switches standards UL and CSA 30 to 100 A The solution for Load break switches > Power distribution. sircm_100_a_1_cat Rotary switch SIRCO M 3 x 100 A Strong points > Total integration. > Wide range of accessories. > Upgradeability. > Compliance

More information

Top wiring permanent magnet latching For non-motor loads, lighting, heating NEMA sizes to 300 A 2-, 3-, and 4-pole configurations

Top wiring permanent magnet latching For non-motor loads, lighting, heating NEMA sizes to 300 A 2-, 3-, and 4-pole configurations Bulletin LP NEMA AC Permanent Magnet-Latching Lighting Contactors Product Overview/Product Selection/Wiring Diagram A, -Pole Open Type without Enclosure Bulletin LP Top wiring permanent magnet latching

More information

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks. 2CDC 251 052 F0t08 CM-MPS.23 2CDC 251 053 F0t08 CM-MPS.43 - relay status, timing - fault message - fault message Adjustment of the tripping delay t V Adjustment of the threshold value for overvoltage 6

More information

T e c h n i c a l C a t a l o g u e MCCB. Moulded Case Circuit Breaker

T e c h n i c a l C a t a l o g u e MCCB. Moulded Case Circuit Breaker T e c h n i c a l C a t a l o g u e MCCB Moulded Case Circuit Breaker contents general overview... 2 feature - company profile and certifications... 6 MCCB - NF series circuit breaker, double repulsion

More information

/2008. Altistart 22. Soft start - soft stop unit. User manual 09/2009 BBV

/2008. Altistart 22. Soft start - soft stop unit. User manual 09/2009 BBV 2354235 11/2008 Altistart 22 Soft start - soft stop unit User manual 09/2009 BBV51330 www.schneider-electric.com Content Important Information 4 Before you begin 5 Documentation structure 6 Steps for

More information

Protection components

Protection components General Application LT3-Si thermistor protection units continuously monitor the temperature of the machines to be protected (motors, generators, etc.) by means of PTC thermistor probes embedded in the

More information

Improving Network Availability with Intelligent Electronic Devices

Improving Network Availability with Intelligent Electronic Devices Improving Network Availability with Intelligent Electronic Devices Guillaume Verneau - Schneider Electric - France Yves Chollot - Schneider Electric - France Pascal Cumunel - Schneider Electric - France

More information

Replacement solution

Replacement solution Replacement solution for the ABB DPU2000R protection and control relay Specification File, Revision, Date (Pages) Replacement Relay Specification_ABB DPU2000R_0.doc, Revision 0, August 2, 2013 (37) Table

More information

04 Page. MCCBs characteristics 94. MCCBs & accessories selection guide 96. MCCBs x MCCBs x MCCBs h

04 Page. MCCBs characteristics 94. MCCBs & accessories selection guide 96. MCCBs x MCCBs x MCCBs h This section includes moulded case circuit breakers, manual and automatic transfer switches and load break switches which are utilised for the switching, protection and distribution of low voltage installations.

More information

Power Processor - Series 700F 10KVA to 150KVA

Power Processor - Series 700F 10KVA to 150KVA Power Processor - Series 700F 10KVA to 150KVA Power Conditioning and Regulation for Commercial & Industrial Equipment General Specifications PART 1 - GENERAL 1.1 DESCRIPTION This specification defines

More information

Type: DILEM 10(220V50HZ,240V60HZ) Article No.:

Type: DILEM 10(220V50HZ,240V60HZ) Article No.: Type: DILEM 10(220V50HZ,240V60HZ) Article No.: 051785 Ordering information Actuating voltage Description Connection technique 380 V 400 V I e A 8.8 Max. rating for three phase motors, 50 AC 3 220 V 230

More information

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS) AC CURRENT GENERATOR PERFORMANCES Wide range of current 50 db dynamic range Signal-to-noise ratio: 80 db open loop protection Stability < 0,1% Very low THD distortion < 0,3% External synchronization Build-up

More information

RCMS460 and RCMS490 Series

RCMS460 and RCMS490 Series 4 T M RCMS460 and RCMS490 Series Digital Multi-Channel Ground Fault Monitor / Ground Fault Relay Grounded and High-Resistance Grounded AC/DC Systems Technical Bulletin NAE1042060 / 04.2013 BENDER Inc.

More information

LC2D09BD. Main. Device short name. Utilisation category. Poles description Pole contact composition

LC2D09BD. Main. Device short name. Utilisation category. Poles description Pole contact composition Product datasheet Characteristics Main Range Product name Product or component type Device short name Contactor application Utilisation category Device presentation Poles description Pole contact composition

More information

LC2D09BL REVERSING CONTACTOR 575VAC 9A IEC

LC2D09BL REVERSING CONTACTOR 575VAC 9A IEC Product datasheet Characteristics LC2D09BL REVERSING CONTACTOR 575VAC 9A IEC Price* : 107.62 GBP Main Range Product name Product or component type Device short name Contactor application Utilisation category

More information

Integration between the MV protection and control unit REF542 and the LV protection trip unit PR123: selectivity and earth fault 1SDC007402G0201

Integration between the MV protection and control unit REF542 and the LV protection trip unit PR123: selectivity and earth fault 1SDC007402G0201 1SDC007402G0201 Index 1. Introduction... 2 2. Theoretical outline 2.1 Restricted earth fault... 3 2.2 Selectivity between medium and low voltage... 4 3. Application examples and wiring logic 3.1 Restricted

More information

Micro Contactors. Micro Contactor Relays 10. Micro Contactors 11. Micro Contactors With Solder Pins 12. Coil voltages 12. Micro Reversing Contactor 13

Micro Contactors. Micro Contactor Relays 10. Micro Contactors 11. Micro Contactors With Solder Pins 12. Coil voltages 12. Micro Reversing Contactor 13 Micro Contactor Relays 10 Micro Contactors 11 Micro Contactors With Solder Pins 12 Coil voltages 12 Micro Reversing Contactor 13 Technical Data 14 Dimensions 18 D946E 9 Micro Contactor Relays 4-pole AC

More information

Contactors & Relays. Contactors & Relays Manual Motor Starters Miniature Circuit Breakers Earth Leakage Isolators. Pg

Contactors & Relays. Contactors & Relays Manual Motor Starters Miniature Circuit Breakers Earth Leakage Isolators. Pg Contactors & Relays Contactors & Relays Manual Motor Starters Miniature Circuit Breakers Earth Leakage Isolators Pg 223 230 231 232 232 Contactors & Relays Contactor - GMC Series 3 Pole (240V) AC 1 Rati

More information

PBM. Motor management system USER S MANUAL. EN_PBM_User-Manual_R011.Docx

PBM. Motor management system USER S MANUAL. EN_PBM_User-Manual_R011.Docx PBM Motor management system USER S MANUAL EN_PBM_User-Manual_R011.Docx 1. RECEPTION, HANDLING, INSTALLATION... 6 1.1. Unpacking... 6 1.2. Reception of relays... 6 1.3. Handling electronic equipment...

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

Contents. Introduction and description Package contents Device identification PM Options... 80

Contents. Introduction and description Package contents Device identification PM Options... 80 Contents 1 Introduction and description Package contents... 77 Device identification... 77 2 Characteristics PM500... 78 Options... 80 3 Installation Front-panel cut-out... 82 Mounting... 82 4 Connections

More information

NS..S contactor relays - with spring terminals AC operated

NS..S contactor relays - with spring terminals AC operated NS..S contactor relays - with spring terminals AC operated NSES 1SBC101015F00 Description NS..S contactor relays are used for switching auxiliary and control circuits. These contactor relays are designed

More information