THE NEW STOREBAELT HVDC PROJECT FOR INTERCONNECTING EASTERN AND WESTERN DENMARK J. NÄCKER R. RÖSSEL E.M. LEUTNER
|
|
- Annabelle Hampton
- 5 years ago
- Views:
Transcription
1 21, rue d Artois, F PARIS B4-104 CIGRE 2008 http : // THE NEW STOREBAELT HVDC PROJECT FOR INTERCONNECTING EASTERN AND WESTERN DENMARK J.P. KJÆRGAARD, C. RASMUSSEN, K.H. SØBRINK 1 SUMMARY J. NÄCKER R. RÖSSEL E.M. LEUTNER S. NYBERG Energinet.dk Siemens AG ABB AB Denmark Germany Sweden Denmark has two power transmission systems: one for Eastern Denmark and one for Western Denmark. Eastern Denmark is synchronous with the Nordel system, whereas Western Denmark is synchronous with the UCTE system. The construction of the Storebaelt (Great Belt) HVDC interconnection between Eastern and Western Denmark has now been approved after many years of discussion. The Danish power system has changed considerably over the last few years due to the high penetration of renewable energy sources and due to the decommissioning of several old power stations. These changes have made the HVDC interconnection technically and economically advantageous. A feasibility study has revealed that several aspects will contribute to the benefits of the new Storebaelt HVDC interconnection: Operational benefits from using the most economical power plants in Eastern and Western Denmark. Shared power reserves in Eastern and Western Denmark, thereby reducing Energinet.dk's total purchase of power reserves in the market. Counterbalance of power imbalances between production and demand in Eastern and Western Denmark across the Storebaelt HVDC interconnection. Improved market functionality achieved by reducing power producers' possibility of obtaining market dominance and thus increasing market prices. A contract for the Storebaelt HVDC project with a rating of 600 MW was signed in May 2007, and the interconnection will go into commercial operation in April KEYWORDS LCC HVDC, Light Triggered Thyristors, Multi HVDC Infeed, Cable Load Prediction System. 1 khs@energinet.dk 1
2 1 THE DANISH POWER SYSTEM The transmission system in Denmark is owned and operated by Energinet.dk, the Danish transmission system operator (TSO). The system is divided into two electrically separated systems, the Eastern system and the Western system. The Western system is synchronous with the European system, UCTE, via 400 kv and 220 kv AC transmission overhead lines. The Eastern system is synchronous with the Nordic system, Nordel, via 400 kv and 132 kv AC submarine cables. The Western system has two HVDC interconnections to Sweden, Konti-Skan pole 1 (380 MW) and pole 2 (360 MW), and three HVDC interconnections to Norway, Skagerrak pole 1 (250 MW), pole 2 (250 MW) and pole 3 (440 MW). Table 1-1: Overview of the installed production capacities Synchronous area Western System Eastern System UCTE Nordel Central power stations 3400 MW 3800 MW Local CHP plants 1700 MW 650 MW Wind power plants 2400 MW 750 MW Wind power penetration % 30-85% Combined heat and power penetration % 25-74% The Danish power system is characterised by a high penetration of distributed power sources, ie wind power and CHP (combined heat and power) plants. In the Western system, wind power penetration is 200%, which is calculated as maximum wind power production divided by minimum consumer loading, while in the Eastern system wind power penetration is 85%. As regards CHP, penetration is 136% in the Western system and 74% in the Eastern system. In order to provide sufficient short-circuit capacity and inertia in the power system, at least three central power stations must be in operation at any time in the Western and the Eastern systems, respectively. 2 THE NORDIC POWER MARKET The Danish power market is a part of the Nordic power market, and Denmark is a member of the Nordic power exchange (Nord Pool [1]), which is jointly owned by the Nordic TSOs. The Storebaelt (Great Belt) power interconnection is one of five electricity transmission projects that were recommended by Nordel [2] in 2004, and which are now in the process of being realised. The other projects that were recommended are a new HVDC link, Fenno-Skan2, between Finland and Sweden, a new HVDC interconnection, Skagerrak 4, between Denmark and Norway, a new line between central Norway and central Sweden, and, finally, a line between North and South Sweden. The new Storebaelt HVDC project was decided by Energinet.dk because it will yield economic benefits as a result of better utilisation of the power system, sharing of power reserves across the Storebaelt HVDC interconnection, synergies in a common regulating power market and better market performance due to more competition in the market. The Storebaelt HVDC interconnection is planned to be ready for commercial operation in April
3 Exchange of power on the Storebaelt HVDC interconnection The expected exchange of power on the Storebaelt interconnection has been estimated on the basis of energy balances in the Nordic system using historical hydro- and wind-power time series and on the assumption that the production at local and central power stations is optimised. The equivalent full-load hours for the Storebaelt HVDC interconnection are 4,362 h/year, and the loss hours are 3,551 h/year while operating hours amount to 7,237 h/year. Technology and rating Classic HVDC with line-commutated converters and VSC (voltage-sourced converters) were considered. In order to find the most economical solution, various ratings and technologies were considered as shown in Figure Million DKK./Year x 400 MW 1 x 600 MW 2 x 400 MW 2 x 600 MW 1 x 600 MW + 1 x 350 VSC Utility value Yearly expenses Figure 2-1: Utility value and expenses per year for the Storebaelt HVDC interconnection Because of the higher utilisation rate and the relatively higher losses in connection with VSC transmission, LCC HVDC turned out to be the most economical solution. 3 SYSTEM STUDIES The Storebaelt HVDC interconnection will be designed to operate together with the existing HVDC interconnections and the large shares of distributed generation, ie wind power and CHP in the Danish power system. In order to design the Storebaelt interconnection, dynamic system studies for the most critical and severe situations have to be investigated in order to access the overall system stability. For this purpose Energinet.dk has developed a network model of the transmission grid in Denmark which is connected to simplified equivalents of the transmission grids in the neighbouring countries of Germany, Norway and Sweden. It is not feasible to cover all possible situations so it has been decided to focus on four different loadflow scenarios designated A, B, C and D. These scenarios represent the most severe operating situations for assessment of the dynamic behaviour of the transmission grid with the new Storebaelt HVDC system. The scenarios are shown in Figure
4 Scenario A: Peak load Production, central power plants: High Production, wind turbines: Low Production, local CHP: Medium Scenario B: Low load Production, central power plants: Low Production, wind turbines: High Production, local CHP: High Scenario C: Low load Production, central power plants: Low Production, wind turbines: None Production, local CHP: None Scenario D: Low load, island operation Production, central power plants: Low Production, wind turbines: None Production, local CHP: None Flow direction on existing HVDC line: Flow direction on new HVDC line: Flow direction on existing HVAC line: Figure 3-1: The four scenarios A, B, C and D to be used for dynamic studies Type of studies The studies for the project can be classified in three groups. 1. Design studies 2. System stability studies 3. Control, protection and communication studies. 1. The design studies are required for the specification of the equipment and the main circuit parameter such as overvoltages, reactive power conditions, insulation coordination, AC filter performance and rating of AC breaker and interference conditions. 2. The system stability studies include a stability modulation frequency control (SMFC) study and a subsynchronous resonance (SSR) study and a multi HVDC infeed study. 4
5 3. The control, protection and communication studies will start in 2008, and the testing of the HVDC control system in the digital simulator will be finalised by mid HVDC CONVERTERS The HVDC project The tenders were invited for a 600 MW monopolar LCC HVDC cable system with metallic return cable, which can subsequently be expanded to a bipolar system, if required. The project is split up into different subprojects and subcontracts for HVDC converters, submarine cables, land cables, AC substations and civil works, respectively. The contract for the LCC HVDC converters and the DC cables was signed May 2007, and the contractual date for handover and commercial operation of the interconnection April HVDC ratings The ratings of the monopolar Storebaelt HVDC system is 600 MW, 400 kv DC and 1500 A DC. The HVDC converter stations located at Fraugde and Herslev are designed to transmit rated power in either direction. Additionally, the HVDC converters have a dynamic power transfer capacity of up to 810 MW in both power directions. The DC cable transmission system consists of 26 km land pole and returns cables and 32 km sea pole and return cables. A single-line diagram of the Storebaelt HVDC Interconnection is shown in Figure 4-1. HVDC Station Fraugde HVDC Station Herslev AC Bus Thyristor Valves Smoothing Reactor HV Cables (land + submarine) 16 km + 30 km + 10 km Smoothing Reactor AC Bus Converter Transformer 2 x Triple Tuned AC Filter 2 x Double Tuned AC Filter 2 x Triple Tuned AC Filter 2 x Double Tuned AC Filter Figure 4-1: Schematic single-line diagram Main circuit parameters The continuous rating is 600 MW without a redundant cooling system in service. With redundant cooling, a continuous overload of 105% of rated load is achievable. Additionally, the DC transmission permits a 2-hour overload of 1.05 p.u. rated power without redundant cooling and up to 1.1 p.u. with redundant cooling in operation. Furthermore, a 3-second overload of 1.35 p.u. is available for use up to maximum ambient temperature and for the maximum 2-hour overload as previous operating condition. 5
6 Reactive power and AC harmonic filters In order to balance the reactive power demand of the DC converter at 600 MW, a total reactive compensation of nearly 340 MVA Mvar of shunt capacitors is required per converter station. The compensation is subdivided into four filter sub-banks of rating, each to comply with the limitation on AC voltage change due to filter switching at 420 kv AC system voltage. The design of the triple tuned AC filters [7] has been chosen to satisfy harmonic performance requirements over the whole range of operation as well as a high degree of flexibility and filter redundancy. A TT 12/24/36 B DT3/12 AC Bus 420 kv, 50 Hz AC Filters Arrangement at Herslev or Fraugde Arr Fac1.1 L1 C1 R1 Arr Fac2.1 L1 C1 R1 A B A B R2 L2 C2 R2 L2 C2 R3 TT 12/24/36 DT 3/12 TT 12/24/36 DT 3/12 L3 C3 Figure 4-2: AC filters for Fraugde () and Herslev () Using a special control mode with increased firing/extinction angles, the reactive power consumption of the DC converter can be increased in order to limit the reactive power flow into the AC systems during light DC loads without additional shunt reactors. Converter transformer The converter transformer configuration comprises three single-phase three-winding transformers for each 12-pulse group. One spare converter transformer will be installed at Herslev station. Table 4-1: The converter transformer s main data Fraugde Herslev Rated power of converter transformer MVA Commutating reactance 14 % 14 % Rated voltage of line-side windings kv Rated voltage of valve-side winding of Y/y transformer kv 167.2/ / 3 Rated voltage of valve-side winding of Y/d transformer kv Required number of tap-changer steps -5/+16-5/+16 Size of one tap-changer step 1.25% 1.25% Insulation levels- line-side winding LIWL / SIWL - valve-side Y winding LIWL /SIWL - valve-side delta winding LIWL /SIWL kv kv kv 1300 / / / / / / 650 The leakage impedances were determined by taking several factors into consideration such as the permissible short-circuit current of the thyristor used and optimised ratio between rating and construction cost, etc. The selection of a load tap-changer range was adapted to the requirements of AC voltage variation range and valve capability of operating at high firing angles [6]. All the secondary bushings of the transformer will protrude directly into the valve hall. Both star and delta connections are made inside the valve hall, thereby eliminating the need for wall bushings and avoiding lightning surge stresses of the valves caused by direct strokes. 6
7 The thyristor valves The converters of the Storebaelt project are based on 4-inch direct light-triggered thyristor (LTT) technology. The thyristor valves are arranged in three towers per 12-pulse bridge, each representing one phase. Every tower consists of eight modular units, each of which includes 30 series-connected thyristor levels with auxiliary components (eg snubber circuit, voltage monitoring electronics and saturable valve reactors) (Figure 4-3). valve section n=1 valve section n=4 C g n=15 C sn R sn V L V Figure 4-3: View into an LTT thyristor modular unit The valve towers are suspended from the valve hall roof, and all joints between modules such as suspension insulators, bus work and piping are flexibly designed to allow maximum deflection. Cooling water and fibre optics are supplied from the top. All non-metallic materials used were selected in order to minimise the risk of severe fires. Capacitors are filled with insulating gases and oil is eliminated. Plastic materials for tubing and insulation have flame retardant self-extinguishing characteristics. Smoothing reactor The smoothing reactor to be installed outdoor is of the air-core dry-type design and therefore maintenance free. Considering the metallic return DC circuit configuration, the calculations indicated that a 300 mh smoothing reactor per station is an adequate size to avoid resonance at low order harmonics. This size of the smoothing reactor ensures fulfilment of further tasks as well, eg limiting the transient over-currents caused by DC side faults or commutation failures, avoiding discontinuous current operation at low DC currents, especially at operation with high firing angles at minimum load operation. The smoothing reactors are installed at the 400 kv DC busbar. The insulation level of the 400 kv busbars is LIWL/SIWL = 1175kV / 950 kv. 5 HVDC CONTROL AND PROTECTION The control and protection (C&P) system follows a hierarchical structure: SCADA level (operator control and monitoring level) 7
8 CONTROL (and protection) level FIELD level. The different levels are interconnected by powerful redundant serial communication links such as Fast Ethernet (IEEE 802.3u) and PROFIBUS DP (EN 50170). The use of standardised communication protocols, eg TCP/IP and UDP, allows easy adoption to specific requirements and flexible implementation of additional features such as a future bipole control and remote access for maintenance purposes. SCADA level For the operators, control and monitoring of the HVDC system the SCADA level in the local converter stations consist of the redundant HMI system, the remote-control interface (RCI) for communication to control centres and to the AC station controller, the transient fault recording system (TFR) and the inter-station communication system. The remote-control interface (RCI) uses the IEC protocol for communication with the control centres and the AC station. This Linux-based system runs on industrial PCs connected to the control systems via the redundant local area network (LAN). The RCI is designed as a redundant (hotstandby) system. Central GPS-based master clocks are used to provide a common time base for all interacting station equipment. Telecommunication equipment interconnects the LANs of the two converter stations and provides the interface to the control centers. Inter-station communication is routed via the Energient.dk WAN network. CONTROL level The control and protection level comprises the station control, pole control and DC protection and measuring systems. These systems, as well as the AC filter main protections, are based on programmable logic controllers The Pole Control is the heart of the HVDC control system where control functions such as power and current control as well as other related control functions are carried out. Generally the Station Control integrates the HVDC system into the existing power system and carries out administrative functions (e.g. managing the control authorities). The reactive power control as a part of the Station Control is implemented in an external AC station controller. The communication to the external AC Station controller is realized via RCI. The protective systems ensure that all potential faults are detected, selectively acted upon and announced. The protection systems are divided into main and backup systems. The protection is equipped with redundant systems where different principles cannot be used. FIELD level Redundant serial field bus systems according to standard IEC Profibus-DP are used for communication between the control systems and the decentralized digital I/O units. For each redundant control system (Pole Control, Station Control) separate redundant field buses (system 1, system2) are provided. I/O units of the type SU200 are used for data acquisition functions. The units have integrated SER functionality with time stamping (resolution 1 ms) and digital filtering for each binary hardware input. The central measuring system is connected to the different control and protection systems and providing the interface to a hybrid optical DC measuring system, see Figure 5-1. The AC and DC system quantities are transmitted to the various control and protection processors via a high-speed optical Time Division Multiplexing (TDM) bus. To achieve a very high availability and reliability, the 8
9 measuring system including the sensor heads is designed completely redundant and independent of the Pole Control and DC Protection systems. Figure 5-1: Hybrid optical DC measuring system 6 RELIABILITY The energy availability (EA) for both Storebaelt converter stations together is guaranteed to be more than 98.5% with a forced outage rate (FOR) of less than five outages per year. Fault-tolerant control systems, an intelligent redundancy and spare-parts philosophy combined with stringent quality standards ensure high component and system reliability. Additionally, intensive offsite tests are performed on the HVDC control and protection system (eg functional performance tests), to enhance the reliability, availability and quality to the highest possible level. The spare-parts philosophy requires only one spare part for each main component (transformer, filter components, etc.) stored at Herslev converter station for the use at both converter stations. The sensitive station elements are designed with redundant capacity or as dual systems (valve cooling system, auxiliary power system, control and protection systems, etc.). 7 HVDC CABELS The 400 kv HVDC pole cables are mass impregnated (MI), and the metallic return is a polymeric cable. Table 7-1: Summary of pole cable data Submarine cable Land cable Cable length 32 km 26 km Rated voltage 400 kv 400 kv Rated current 1500 A 1500 A LIWL 800 kv 800 kv SIWL 800 kv 800 kv Cross section 1700 mm mm Cable load prediction system The maximum power exchanged is limited to the maximum continuous rated current capacity of the HVCD cable. 9
10 The cable design and the continuous rated capacity of the cable are determined by burial conditions and maximum temperature at the burial depth. Cables installed in air have normally higher capacity than buried cables due to better cooling conditions. There is a thermal capacity in the cable and the ambient soil that allows for a specified short-time overload at specified times. During the cold season, the continuous transmission capacity is higher than the rated capacity, and the short-time overload capacity has increased further compared to the warm season. Temperature margins for increased continuous capacity and short-time overloading is possible if a cable load prediction system (CLPS) is installed in addition to the control system in the converter station. The CLPS allows the utilisation of available temperature margins to increase the capacity of the cable through continuous control of the cable real-time temperature. The CLPS software calculates in real time the existing temperature margins of the cable and the ambient soil are utilised without exceeding maximum allowed temperatures in the cables. Figure 7-1 shows a functional overview of the CLPS system and the control system of the converter. In this overview, SCADA is an interface system for the converter station that also stores measured values, facilitates presentation of tables, diagrams, etc., and the control is for power control of the converter bridge. All data calculated by the CLPS is sent to SCADA and treated as any measurement in the system. Figure 7-1: Overview of functional diagram Temperatures on cable surfaces and in the ground are measured with three redundant Pt100 elements. If the redundant Pt100 elements indicate different measured values, the measured values are invalid and an alarm is sent to the SCADA system. All calculated data is supervised with the local SCADA system in the substation or transferred to a dispatch centre from where the HVDC interconnection is operated. Besides the calculated real-time data, further alarms or orders are sent to the SCADA system: One temperature element erroneous Two temperature elements erroneous Five minutes left to ramp down Ramp down order. 10
11 If two elements are erroneous, the CLPS cannot calculate correct temperature profiles. In this case the predicted overload currents and maximum continuous current are changed to the contractually rated value of the cable. The contractual value is below the real-time maximum continuous value. If an overload is ordered, the real-time overload decreases successively towards maximum continuous current. Five minutes before the time for finished overload is reached, an alarm 5 minutes left is sent to SCADA. If the operator does not intervene, a ramp down order is sent to the SCADA system when the time for overload is finished. This order automatically initiates a ramp down to maximum continuous current. 8 CONCLUSION The new 600 MW Storebaelt HVDC interconnection is one of five electricity transmission projects recommended by Nordel, the body for cooperation between the Nordic TSOs. The HVDC interconnection will interconnect Eastern and Western Denmark, and it will improve the Nordic electricity power market in general and the Danish market in particular. The benefit will be gained by increased trade in the Nordic power market and by a more optimised utilisation of the Nordic power generation system. Additional gains will be achieved by improvement of the market performance. LCC HVDC and VSC HVDC technology for the Storebaelt project was evaluated. Due to the expected high utilisation of the Storebaelt HVDC interconnection and consequently the relatively high capitalisation of transmission losses for VSC HVDC, it was decided to realise the project based on classic LCC HVDC technology with a rating of 600 MW. The DC pole cable is provided with a cable load prediction system (CLPS) allowing for cable overloads at peaks larger that the rated cable current and larger continuous currents during colder seasons. The project started May 2007 and the Storebaelt HVDC interconnection is planned to go into operation April BIBLIOGRAPHY [1] [2] [3] [4] Cigré Guide WG B4-41: Systems with multiple DC infeed, Electra no. 233, August 2007 [5] J. Rittiger, D. Zhang, Yong Jing, Xiaocheng Wu, Zongming Du, Xiaoming Jin, Digital Simulation of AC/DC Hybrid Transmission System," in Proc IEE-PES/CSEE International Conference on Power Systems Conf. [6] K. Eckholz, P. Heinzig, H.V.D.C.-Transformers - A Technical Challenge," in Proc IEE- PES/CSEE International Conference on Power Systems Conf. [7] C. Bartzsch, H. Huang, K. Sadek, "Triple-Tuned Harmonic Filters - Design Principle and Operating Experience," in Proc IEE-PES/CSEE International Conference on Power Systems Conf. 11
Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years
21, rue d Artois, F-758 PARIS B4-18 CIGRE 216 http : //www.cigre.org Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years T G MAGG, Power System
More informationEast-South HVDC Interconnector II, India : in commercial operation since 2003
8006/0 5 HVDC / FACTS Highlights http://www.siemens.com/facts http://www.siemens.com/hvdc NEW! >>> Welcome to Siemens Highlights & Innovations in Transmission and Distribution East-South HVDC Interconnector
More informationHVDC High Voltage Direct Current
HVDC High Voltage Direct Current Typical HVDC Station BACK TO BACK CONVERTER STATION MONO POLAR WITH GROUND RETURN PA Back to Back Converters indicates that the Rectifiers & Inverters are located in the
More informationA cost effective hybrid HVDC transmission system with high performance in DC line fault handling
2, rue d Artois, F-758 PARIS B4-7 CIGRE 28 http : //www.cigre.org A cost effective hybrid HVDC transmission system with high performance in DC line fault handling Mats Andersson, Xiaobo ang and ing-jiang
More informationESB National Grid Transmission Planning Criteria
ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and
More informationATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for
More informationBipole III Transmission Project
Bipole III Transmission Project Clean Environment Commission Public Hearings Fall 2012 System Planning Ronald Mazur BP III Keewantinoow Limestone Kettle Kelsey Jenpeg Grand Rapids OVERVIEW Transmission
More informationInsulation Co-ordination For HVDC Station
Insulation Co-ordination For HVDC Station Insulation Co-ordination Definitions As per IEC 60071 Insulation Coordination is defined as selection of dielectric strength of equipment in relation to the operating
More informationA new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant alternating voltage
21, rue d Artois, F-758 PARIS B4_16_212 CIGRE 212 http : //www.cigre.org A new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant
More informationSYSTEM STUDIES for HVDC
INTRODUCTION The design of HVDC requires Careful study coordination, which must be achieved in compliance with the Owner s requirements. To achieve these objectives, number of highly interactive system
More informationFacilitating Bulk Wind Power Integration Using LCC HVDC
21, rue d Artois, F-758 PARIS CIGRE US National Committee http : //www.cigre.org 213 Grid of the Future Symposium Facilitating Bulk Wind Power Integration Using LCC HVDC A. HERNANDEZ * R.MAJUMDER W. GALLI
More informationDESIGN CONSIDERATIONS OF ULTRA HIGH VOLTAGE DC SYSTEM
DESIGN CONSIDERATIONS OF ULTRA HIGH VOLTAGE DC SYSTEM H. Huang V. Ramaswami D. Kumar Siemens AG Power Transmission and Distribution 91056 Erlangen, Germany TransGrid Solutions Inc., Winnipeg, Canada INTRODUCTION
More informationChapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two
Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead
More informationFixed Series Compensation
Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and
More informationHighgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES
Highgate Converter Overview Prepared by Joshua Burroughs & Jeff Carrara IEEE PES Highgate Converter Abstract Introduction to HVDC Background on Highgate Operation and Control schemes of Highgate 22 Why
More informationDesign, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter
1 Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter Nee, Staffan Norrga, Remus Teodorescu ISBN-10: 1118851560
More informationHVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N
S C I E N C E P A S S I O N T E C H N O L O G Y HVDC Transmission Michael Muhr Graz University of Technology Austria www.tugraz.at 1 Definition HV High Voltage AC Voltage > 60kV 220kV DC Voltage > 60kV
More informationVoltage Source Converter Modelling
Voltage Source Converter Modelling Introduction The AC/DC converters in Ipsa represent either voltage source converters (VSC) or line commutated converters (LCC). A single converter component is used to
More informationATC s Mackinac Back to Back. Summary
ATC s Mackinac Back to Back HVDC Project Update Michael B. Marz American Transmission Company Summary The Need For Flow Control at Mackinac Mackinac Flow Control Requirements Available Flow Control Technologies
More informationDigital Fault Recorder Deployment at HVDC Converter Stations
Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic
More informationRecent trends in High Voltage Direct Current (HVDC)Transmission Systems Abstract
Recent trends in High Voltage Direct Current (HVDC)Transmission Systems Abstract During the latest 20 years, HVDC has become the dominating technology for long distance transmission of bulk power. The
More informationVSC Transmission. Presentation Overview. CIGRE B4 HVDC and Power Electronics HVDC Colloquium, Oslo, April LCC HVDC Transmission
CIGRE B4 HVDC and Power Electronics HVDC Colloquium, Oslo, April 2006 VSC Transmission presented by Dr Bjarne R Andersen, Andersen Power Electronic Solutions Ltd Presentation Overview - Basic Characteristics
More informationPower System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )
21, rue d Artois, F-75008 PARIS SECURITY AND RELIABILITY OF ELECTRIC POWER SYSTEMS http : //www.cigre.org CIGRÉ Regional Meeting June 18-20, 2007, Tallinn, Estonia Power System Reliability and Transfer
More informationIntroduction to HVDC in GB. Ian Cowan Simulation Engineer 12 March 2018
Introduction to HVDC in GB Ian Cowan Simulation Engineer 12 March 2018 Contents 1) History of Electricity Networks 2) Overview of HVDC 3) Existing Schemes 4) Future Schemes 5) Regulation and Ownership
More informationCopyright 2012 IEEE. Paper presented at 2012 IEEE Workshop on Complexity in Engineering 11 June, Aachen,
Copyright 22 IEEE Paper presented at 22 IEEE Workshop on Complexity in Engineering June, Aachen, Germany 22 This material is posted here with the permission of the IEEE. Such permission of the IEEE does
More informationPartial Discharge Measurement and Monitoring on High Voltage XLPE Cables
21, rue d Artois, F-75008 PARIS AUCKLAND 2013 http : //www.cigre.org Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables Michael Krüger, Rene Hummel, Stefan Böhler, OMICRON Austria
More informationFundamental Concepts of Dynamic Reactive Compensation. Outline
1 Fundamental Concepts of Dynamic Reactive Compensation and HVDC Transmission Brian K. Johnson University of Idaho b.k.johnson@ieee.org 2 Outline Objectives for this panel session Introduce Basic Concepts
More information6 HVdc Converter Stations and Electrodes
6 HVdc Converter Stations and Electrodes Report by: L. Recksiedler, P. Eng. 6.1 Introduction The Labrador-Island Link HVdc system is configured as a ±320 kv 900 MW Line Commutated Converter HVdc bipolar
More informationHigh Voltage DC Transmission 2
High Voltage DC Transmission 2 1.0 Introduction Interconnecting HVDC within an AC system requires conversion from AC to DC and inversion from DC to AC. We refer to the circuits which provide conversion
More informationExcitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation
Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability
More informationApplication of SVCs to Satisfy Reactive Power Needs of Power Systems
1 Application of SVCs to Satisfy Reactive Power Needs of Power Systems H. K. Tyll, Senior Member, IEEE Abstract In the early days of power transmission problems like voltage deviation during load changes
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements
Section 502.8 SCADA Technical and Operating Applicability 1 Section 502.8 applies to: (a) the legal owner of a generating unit: (i) connected to the transmission facilities in the balancing authority area
More informationFunctional Specification Revision History
Functional Specification Revision History Revision Description of Revision By Date V1D1 For Comments Yaoyu Huang October 27, 2016 V1 For Issuance Yaoyu Huang November 21, 2016 Section 5.3 updated Transformer
More informationAORC Technical meeting 2014
http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi
More informationHVDC MULTI-INFEED PERFORMANCE
MULTI-INFEED PERFORMANCE Göran Andersson, Paulo Fischer de Toledo and Göte Liss ABB Power Systems S-771 80 Ludvika, Sweden 1 Abstract The number of power system configurations with two or more links feeding
More informationIntroduction to HVDC Transmission. High Voltage Direct Current (HVDC) Transmission
Lecture 29 Introduction to HVDC Transmission Series Compensation 1 Fall 2003 High Voltage Direct Current (HVDC) Transmission Update to Edison s Vision AC Power Generation at Relatively Lower Voltage» Step
More informationDesign and Simulation of Passive Filter
Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt
More informationApplication for A Sub-harmonic Protection Relay. ERLPhase Power Technologies
Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic
More informationThe rapid evolution of voltage Source Converters as applied to High Voltage DC power transmission Carl Barker
The rapid evolution of voltage Source Converters as applied to High Voltage DC power transmission Carl Barker Chief Engineer HVDC Applications Tuesday 30 June 2015 HVDC Today Finding an increasing market
More informationEH2741 Communication and Control in Electric Power Systems Lecture 2
KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment
More informationImportance of DC-DC Transformation in Grids of the Future
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Importance of DC-DC Transformation in Grids of the Future L. BARTHOLD 1, D. WOODFORD
More informationJoe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation
Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation Slide 1 Excerpt from the BoA BoA: Book of Acronyms MSC/MSR: Mechanically
More informationCase Study 1. Power System Planning and Design: Power Plant, Transmission Lines, and Substations
Case Study 1 Power System Planning and Design: Power Plant, Transmission Lines, and Substations Lindsay Thompson, 5203120 Presented to Riadh Habash ELG 4125 11/10/2013 1.0 ABSTRACT A power plant delivers
More informationBE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %
BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and
More informationECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control
ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections
More informationHVDC Transmission Using Artificial Neural Networks Based Constant Current and Extension Angle Control
HVDC Transmission Using Artificial Neural Networks Based Constant Current and Extension Angle Control V. Chandra Sekhar Department of Electrical and Electronics Engineering, Andhra University College of
More informationCourse ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation
Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission
More informationCurso de Transmissão em Corrente Continua Rio de Janeiro, de Junho, 2007
Curso de Transmissão em Corrente Continua Rio de Janeiro, 13 15 de Junho, 2007 DC Harmonic Filters Page 1 of 9 1 Function of the DC-Side Harmonic Filters Harmonic voltages which occur on the dc-side of
More informationCondition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology
Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements
Section 502.8 SCADA Technical and Operating Requirements Applicability 1 Subject to subsections 2 and 3 below, section 502.8 applies to: (a) (c) (d) the legal owner of a generating unit or an aggregated
More informationExperience with Connecting Offshore Wind Farms to the Grid
Oct.26-28, 2011, Thailand PL-22 CIGRE-AORC 2011 www.cigre-aorc.com Experience with Connecting Offshore Wind Farms to the Grid J. FINN 1, A. SHAFIU 1,P. GLAUBITZ 2, J. LOTTES 2, P. RUDENKO 2, M: STEGER
More informationThis is a preview - click here to buy the full publication. Performance of high-voltage direct current (HVDC) systems with linecommutated
TECHNICAL REPORT IEC/TR 60919-1 Edition 3.1 2013-04 colour inside Performance of high-voltage direct current (HVDC) systems with linecommutated converters Part 1: Steady-state conditions INTERNATIONAL
More informationShould we transform our lines to HVDC?
Should we transform our lines to HVDC? HVDC versushvac Gaurav Dabhi 1, Nishit Sanghvi 2, Pinkesh Patel 3 1 Electrical Eng., G.H. Patel college of Eng. & Tech., dabhi60@gmail.com 2 Electrical Eng., G.H.
More informationABB Power Systems AB Sweden
Ingvar Hagman Tomas Jonsson ABB Power Systems AB Sweden This paper presents the first high power verification of ABB s Capacitor Commutated Converter (CCC) concept. The high power tests were performed
More informationLARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS
LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS Giuseppe Di Marzio NTNU giuseppe.di.marzio@elkraft.ntnu.no Olav B. Fosso NTNU olav.fosso@elkraft.ntnu.no Kjetil Uhlen SINTEF
More informationHigh Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology Kanpur
High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology Kanpur Module No. # 01 Lecture No. # 03 So, in last two lectures, we saw the advantage
More informationELECTRICAL POWER TRANSMISSION TRAINER
ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering
More informationATTACHMENT - AESO FUNCTIONAL SPECIFICATION
ATTACHMENT - AESO FUNCTIONAL SPECIFICATION Functional Specification Revision History Revision Description of Revision By Date D1 For internal Comments Yaoyu Huang January 8, 2018 D2 For external Comments
More informationCompany Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System
Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels
More informationHigh Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur
High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur Module No. # 01 Lecture No. # 02 Comparison of HVAC and HVDC Systems Welcome
More informationELEMENTS OF FACTS CONTROLLERS
1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are
More informationUProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy
UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More information1400 MW New Zealand HVDC Upgrade: Introducing Power Modulation Controls and Round Power Mode
1400 MW New Zealand HVDC Upgrade: Introducing Power Modulation Controls and Mode Simon P. Teeuwsen Network Consulting Siemens AG Erlangen, Germany simonp.teeuwsen@siemens.com Abstract The existing HVDC
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements
Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission
More informationMagnetization System of Magnetically Controlled Shunt Reactors
Magnetization System of Magnetically Controlled Shunt Reactors Leonid Kontorovych, Technical Director of ZTR PJSC, PH.D. in Engineering Sciences; Igor Shyrokov, head of the department of reactors control
More informationUSE OF HVDC MULTI TERMINAL OPTIONS FOR FUTURE UPGRADE OF THE NATIONAL GRID
USE OF HVDC MULTI TERMINAL OPTIONS FOR FUTURE UPGRADE OF THE NATIONAL GRID JOS ARRILLAGA Emeritus Professor, FIEE, FIEEE, MNZM 2/77 HINAU STREET, RICCARTON CHRISTCHURCH ARRILLJ@ELEC.CANTERBURY.AC.NZ TELEPHONE
More informationCompact Systems for HVDC Applications Dr. Denis Imamovic
13. Symposium Energieinnovation, 12. -14. February 2014, Graz Compact Systems for HVDC Applications Dr. Denis Imamovic Answers for energy. Agenda Main Drivers 3 Fault Clearing in HVDC Multi- Terminals
More informationOptimization of power transformers based on operative service conditions for improved performance
21, rue d Artois, F-75008 PARIS A2-207 CIGRE 2012 http : //www.cigre.org SUMMARY Optimization of power transformers based on operative service conditions for improved performance A.Prieto, M.Cuesto, P.Pacheco,
More informationFACILITY RATINGS METHOD TABLE OF CONTENTS
FACILITY RATINGS METHOD TABLE OF CONTENTS 1.0 PURPOSE... 2 2.0 SCOPE... 3 3.0 COMPLIANCE... 4 4.0 DEFINITIONS... 5 5.0 RESPONSIBILITIES... 7 6.0 PROCEDURE... 8 6.4 Generating Equipment Ratings... 9 6.5
More informationZERO PHASE SEQUENCE VOLTAGE INJECTION FOR THE ALTERNATE ARM CONVERTER
ZERO PHASE SEQUENCE VOLTAGE INJECTION FOR THE ALTERNATE ARM CONVERTER F J Moreno*, M M C Merlin, D R Trainer*, T C Green, K J Dyke* *Alstom Grid, St Leonards Ave, Stafford, ST17 4LX Imperial College, South
More informationPower Flow Control And Total Harmonic Distortion Reduction In HVDC Link Using PI And ANN Controllers
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 13, Issue 5 Ver. I (Sep. Oct. 2018), PP 10-20 www.iosrjournals.org Power Flow Control And
More informationReactive Power and AC Voltage Control of LCC HVDC System with Digitally Tunable Controllable Capacitors
International Journal for Modern Trends in Science and Technology Volume: 03, Issue No: 06, June 2017 ISSN: 2455-3778 http://www.ijmtst.com Reactive Power and AC Voltage Control of LCC HVDC System with
More informationSPECIAL REPORT FOR SC B4 (DC and Power Electronics) C. Bartzsch M. Mohaddes Special Reporters
21, rue d Artois, F-75008 PARIS CIGRE 2018 http : //www.cigre.org B4-00 SPECIAL REPORT FOR SC B4 (DC and Power Electronics) C. Bartzsch M. Mohaddes Special Reporters Cigre study committee B4 is responsible
More informationMMC Design Aspects and Applications. John Strauss Siemens AG.
MMC Design Aspects and Applications John Strauss Siemens AG. John.Strauss@Siemens.com 1 VSC-HVDC with MMC Basic Scheme Reference HVDC PLUS Converter Arm Converter Module Power Module Electronics (PME)
More informationThe Italy - Malta interconnection. Morris Brenna
The Italy - Malta interconnection Introduction The Republic of Malta has an area of 316 km2 and a population of about 410 thousands with an energy annual consumption of about 2.3 TWh. The Maltese electric
More informationDocument C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting
Document C-29 Procedures for System Modeling: January 5 th, 2016 TFSS Revisions Clean Open Process Posting Prepared by the SS-37 Working Group on Base Case Development for the Task Force on System Studies.
More informationAssessment of Saturable Reactor Replacement Options
Assessment of Saturable Reactor Replacement Options D.T.A Kho, K.S. Smith Abstract-- The performance of the dynamic reactive power compensation provided by the existing variable static compensation (STC)
More informationB4-203 NELSON RIVER POLE 2 MERCURY ARC VALVE REPLACEMENT
21, rue d'artois, F-75008 Paris http://www.cigre.org B4-203 Session 2004 CIGRÉ NELSON RIVER POLE 2 MERCURY ARC VALVE REPLACEMENT Narinder S. Dhaliwal *, Rick Valiquette, Manitoba Hydro, Winnipeg, Canada
More informationFrequency Analysis for Planned Islanding Operation in the Danish Distribution System Bornholm
Frequency Analysis for Planned Islanding Operation in the Danish Distribution System Bornholm Yu Chen cy@elektro.dtu.dk Zhao Xu zx@elektro.dtu.dk Centre for Electric Technology, Department of Electrical
More informationPlanning the Next Nelson River HVDC Development Phase Considering LCC vs. VSC Technology
21, rue d Artois, F-75008 PARIS B4-103 CIGRE 2012 http : //www.cigre.org Planning the Next Nelson River HVDC Development Phase Considering LCC vs. VSC Technology D.A.N. JACOBSON 1, P. WANG 1, C. KARAWITA
More informationGrid West Project HVDC Technology Review
Prepared by For Reference Les Brand / Ranil de Silva / Errol Bebbington / Kalyan Chilukuri EirGrid JA4846 Date 17 th December 2014 Revision Table Revision Issue Date Description 0 12/12/2014 Final for
More informationStudies on low inertia systems and application of synchronous condensers
Studies on low inertia systems and application of synchronous condensers From Danish project SCAPP Guangya Yang Center for Electric Power and Energy Department of Electrical Engineering Technical University
More informationUnit 2. Single Line Diagram of Substations
Unit 2 Single Line Diagram of Substations Substations Electric power is produced at the power generating stations, which are generally located far away from the load centers. High voltage transmission
More informationHVDC Solutions for Integration of the Renewable Energy Resources
HVDC Solutions for Integration of the Renewable Energy Resources Comparison of Technical Alternatives and System Configurations Marcus Haeusler Energy Management, Large Transmission Solutions Siemens AG
More informationOverview of Actuation Thrust
Overview of Actuation Thrust Fred Wang Thrust Leader, UTK Professor ECE 620 CURENT Course September 13, 2017 Actuation in CURENT Wide Area Control of Power Power Grid Grid Measurement &Monitoring HVDC
More informationHybrid Simulation of ±500 kv HVDC Power Transmission Project Based on Advanced Digital Power System Simulator
66 JOURNAL OF ELECTRONIC SCIENCE AND TECHNOLOGY, VOL. 11, NO. 1, MARCH 213 Hybrid Simulation of ±5 kv HVDC Power Transmission Project Based on Advanced Digital Power System Simulator Lei Chen, Kan-Jun
More informationDynamic Performance Evaluation of an HVDC Link following Inverter Side Disturbances
174 ACTA ELECTROTEHNICA Dynamic Performance Evaluation of an HVDC Link following Inverter Side Disturbances S. HADJERI, S.A. ZIDI, M.K. FELLAH and M. KHATIR Abstract The nature of AC/DC system interactions
More informationBHARATHIDASAN ENGINEERING COLLEGE, NATTRAMPALLI DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING UNIT I
BHARATHIDASAN ENGINEERING COLLEGE, NATTRAMPALLI DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING FAQ-EE6010 HIGH VOLTAGE DC TRANSMISSION UNIT I Part -A 1. List out two merits of AC and DC transmission
More informationPower Flow Control in HVDC-Link Using Artificial Neural Networks
Power Flow Control in HVDC-Link Using Artificial Neural Networks Potnuru.Chandra Mouli M.Tech Student, Department of EEE, Sri Sivani Institute Of Technology. M.Anusha, M.Tech, Assistant Professor, Department
More informationCopyright 2012 IEEE. Paper presented at Power Africa, 9 July, Johannesburg, South Africa 2012.
Copyright 2012 IEEE Paper presented at Power Africa, 9 July, Johannesburg, South Africa 2012. This material is posted here with the permission of the IEEE. Such permission of the IEEE does not in any way
More informationDC Chopper Based Test Circuit for High Voltage DC Circuit Breakers
DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers D. Jovcic*, M.H. Hedayati *University of Aberdeen,UK, d.jovcic@abdn.ac.uk University of Aberdeen,UK, mhh@abdn.ac.uk Keywords: High Voltage
More informationSouthern Company Interconnection Requirements for Inverter-Based Generation
Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection
More informationEvaluation of Electrical Transmission Concepts for Large Offshore Wind Farms T. Ackermann 1, N. Barberis Negra 2, J. Todorovic 3, L.
Evaluation of Electrical Transmission Concepts for Large Offshore Wind arms T. Ackermann 1, N. Barberis Negra 2, J. Todorovic 3, L. Lazaridis 4 Abstract: This paper presents a comparison of the following
More informationStabilized Differential Relay SPAD 346. Product Guide
Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault
More informationResidual Current Operated Circuit-Breakers (RCCBs)
Product Overview Residual Current Operated Circuit-Breakers (RCCBs) Residual current operated circuit-breakers Number of poles Rated current A Rated residual current ma MW Auxiliary contacts can be mounted
More informationMANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS. July 2016 Version 4
MANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS July 2016 Version 4 This page intentionally blank LEGISLATIVE AUTHORITY Section 15.0.3(1) of The Manitoba Hydro Act (C.C.S.M. c. H190) authorizes
More informationApplication Example Document ID: SA Rev. - September 24, 2004
Application Example Rev. - September 24, 2004 1 Summary Phasor based control of braking resistors A case study applied to large power oscillations experienced in the Swedish grid 1997 Phasor measurement,
More informationCoil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900
Coil Products Coil Products Customer partnership around the globe More than 250,000 coil products delivered to more than 170 countries. More than 60 years of operational experience. 35,000 in Europe 13,000
More informationNew HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations
New HVDC Interaction between AC networks 233 JPE 7-3-6 New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations Chan-Ki Kim, Young-Hun Kwon * and Gil-Soo Jang ** KEPRI,
More information