1 Indicator and alarm signalling unit 10/ EN Dimensions 36 mm x 144 mm Can either stand vertically or lie horizontally Comprehensively explosion-protected Robust moving-coil system Contactless alarm pickups Maximum 2 alarms Replaceable range boxes (for Arucomp amplifiers) The Indicomp 2 is a space-saving device for displaying measured values and an alarm signalling unit with a display facility for depicting and monitoring changeable process variables. The device s explosion protection also makes it suitable for use throughout the chemical industry. Mounting outside the hazardous area: Type of protection II (2) G [EEx ib] IIC Mounting within the hazardous area: Type of protection II 2 G EEx ib IIC T4 For alarm signalling, inductive taps are used that work contactless and without delay.
2 Technical data Measuring unit Deviation in measurements Class 1.5 acc. to DIN (in normal position 2b Class I also possible) Effect of temperature 1 % / 10 K Effect of voltage 0.5 % / 10 % mains voltage change Response time < 2.5 s Scale 100 mm, exchangeable Test voltage 2 kv input relay output 2 kv input initiator output 2 kv input power supply 3 kv for protected devices Measuring circuit with no amplifiers Direct current from 1 ma ma; at 20 ma: R i 30 W; L i 0.02 mh Measuring circuit with Ω amplifier (Pt 100 IEC) from R = 10 Ω...1 kω Lead balancing: 2-wire: 10 Ω 3-wire: no balancing in the range Ω Measuring circuit (exchangeable) with Arucomp amplifiers Meas. range Application Example W 21 Thermocouple or mv C, type J 20 C acc. to mv W 21 KV Thermocouple with refer C, type J junction compensation 20 C acc. to mv W 22 K Thermocouple or mv with C, type J electronic zero elevation 20 C acc. to mv W 22 KV Thermocouple with reference C, type K junction compensation 20 C acc. to mv W 23 K Thermocouple or mv with C, type K electronic zero suppression 20 C acc. to mv W 24 K Resistance thermometer C in a 2-wire circuit Pt 100 IEC W 25 K Resistance thermometer C in a 3-wire circuit Pt 100 IEC W 28 Current measurement ma W 28 K Current measurement with ma zero suppression Lead balancing at mv: Ω no balancing Pt wire: 10 Ω Pt wire: Ω no balancing Input resistance 100 Ω/mV, however 20 kω Thermometer current 2 ma Measuring range limit values from mv to V from µa to ma from Ω to Ω Alarm unit Set points 1 max. value and 1 min. value Setting range min. value: %; max. value % Switching difference Χ Sd 1 % of the scale length Relay output (NC contact operation) Floating change-over contacts max. 250 V max. 5 A (cosϕ 0.7) max. 1 A (cosϕ 0.5) Minimum breaking capacity: > 24 V DC; > 10 ma Initiator output For each switch point 1 initiator to DIN for connecting to switching amplifiers with the following data: U L = 7.7 V...9 V DC; R i = Ω Distance between switch centres adjusted for U L = 8.2 V DC R i = 1000 Ω, at 20 C Oscillation frequency approx. 550 khz if required the shielding must be removed Effect of temperature: < 0.2 % / 10 K Power supply unit For devices with a measuring amplifier and/or with a relay output Alternating voltage 230 V, 110 V, 24 V, ± 10 %; Hz; approx VA Direct voltage 24 V not electrically isolated 24 V electrically isolated; -10 %, + 20 % max. ripple content 1.5 % Internal fuse protection to DIN V DC T C 24 V AC M 0.1 C M C (relay output) 110 V AC T C M 0.1 C (relay output) 220 V AC T C Page 2 of
3 Technical data General and safety data Environmental capabilities Ambient temperature C Transportation and storage temperature C Relative humidity 75 % on annual average, short-term 95 %, occasional and slight condensation permissible. Corresponds to climatic class JWE (to DIN 40040) Mechanical features 1/2 acc. to H&B company standard (normal) Impact: 15 g/11 ms Vibration: 2.5 g; Hz 2/2 acc. to H&B company standard (special) Impact: 30 g/ 11 ms Vibration: 2.5 g; Hz Material Plastic Terminals Wire or stranded wire up to 2.5 mm 2 Blade-type terminals (not in protected devices or the Arucomp amplifier) 6.3 mm 0.8 mm Type of protection Case IP 54 Terminals IP 20 (in protected devices also IP 54) Blade-type terminals IP 00 Installation position Vertical (for horizontal see Supplementary Ordering Information) Weight kg Technical data for explosion protection Mounting in hazardous areas Type of protection II 2 G EEx ib IIC T4 Manufacturer s identification code 49/30-XX Ex Certificate of conformity PTB-No. PTB01 ATEX 2079 Design 12 Connection to current source Signal input circuit in type of protection EEx ib IIC/IIB Initiator circuit in type of protection EEx ib IIC/IIB L i 250 mh, C i 50 nf Maximum values for each circuit U 16 V; I 52 ma; P 169 mw Ambient temperature C Mounting outside a hazardous area Type of protection II (2) G [EEx ib] IIC Manufacturer s identification code 49/30-XX Ex Certificate of conformity PTB-No. PTB01 ATEX 2080 Design 22 Connection to current source with 13 intrinsically-safe circuits 24 With measurement amplifier for resistive remote pickup 13 (passive) 25 With Arucomp measurement amplifier Signal input circuit in type of protection EEx ib IIC Relay circuits Alternating current 250 V, 5 A, cosϕ 0.7 Direct current 60 V, 0.5 A, L/R 200 ms Initiator circuits Operating values U 10 V; I 10 ma These circuits can only be operated in pairs as either intrinsically-safe or not intrinsically-safe Not intrinsically-safe Operating voltage of the device to be connected < 250 V Intrinsically-safe in type of protection EEx ib IIC/IIB L i 250 mh, C i 50 nf Maximum values for each circuit U 16 V; I 52 ma; P 169 mw Type of protection Case IP 54, terminals IP 20 Ambient temperature C Page 3 of 9
4 Technical data for explosion protection Indicomp 2-Ex data Sensor data Design Measuring circuit Design without ATEX certification ATEX certified designs (available only until ) 12/ without amplifier Voltages and currents Ω Meas. amplifier Resistive sensors Arucomp Measuring amplifier W21, W21K, W21KV, W22K, W22KV, W23K, W23KV, W27K, W28, W28KV W24K W25K W26K Ω Measur. amplifier Resistive sensors Arucomp Measuring amplifier W21, W21K, W21KV, W22K, W22KV, W23K, W23KV, W27K, W28 1), W28K W24K W25K W26K L i 0.02 mh 3.1 mh ~ 0 ~ 0 ~ 0 C i ~ 0 ~ µf 60 nf 60 nf No-load volt. U o passive 8.4 V 12 V 12 V 8.4 V 12 V 12 V Short circ. curr. I o passive 131 ma 133 ma 133 ma 130 ma 132 ma 132 ma Max. out. pow. P o passive 0.4 W 0.4 W 0.4 W 300 mw 300 mw 300 mw L o Sensor values 0.5 mh 0.5 mh 1 mh 0.2 mh 0.5 mh 1.7 mh 0.6 mh 1.6 mh minus L i C o Sensor values 200 nf 580 nf 440 nf 40 nf 200 nf 2.5 µf 100 nf 800 nf Voltage U i 60 V 60 V 1 V 1 V 13 V 13 V Current L i 150 ma 95 ma 100 ma 50 ma 50 ma 50 ma Max. out. pow. P i 1.3 W 1.3 W 0.2 W 1) for W28 with R i > 25 Ω. W28 with R i < 25 Ω please ref. to PTB certification Dimensional drawings (dimensions in mm) 144 4, ,8 Pg ) 273 (186) 5) 281 2) 263, ,4 1) (170) 293,5 4) 5) 129,6 Panel cutout ,2 Z EN 1) Device with measuring circuit setup ) Device with blade-type connector or screw terminal 3) Devices with explosion-protected terminal boxes and types ) Devices with explosion-protected lid types 11, 12, ) Short version of device Page 4 of
5 Ordering information for Indicomp 2 without amplifier Catalog No. EUR Deliv. time Indicator V30424A wks. Alarm signalling unit V30426A- 0 Design 1 min. and 1 max. relay 5) 3 800,00 1 min. and 1 max. initiator output 2) 6 598,00 Indicator (with no limit values) 8 256,00 Power supply none (only an indicator or alarm signalling unit with initiator) V AC 1 45,00 24 V AC 4 45,00 24 V DC 1) 5 - Input 3) ma ma 4) 2 - other (see special features) 0 - Explosion protection none 1 - Installed outside the hazardous area II (2) G [EEx ib] IIC Design 22 Indicator ma/v 3 65,00 Design 22 Alarm Signalling Unit ma/v 5 74,00 Installed inside the hazardous area II 2 G EEx ib IIC T4 6) Design 12 Indicator/Alarm Signalling Unit ma/v 7 86,00 Type of connection Screw terminals 2 Bezel grey (RAL 7037) 1 - black 2 - grey (RAL 7032) 3 16,00 1) not in explosion protected devices 2) pay attention to special features "output" 3) normal scaling is %, any other should be specified through Code No. 4) here, zero correction is no longer used 5) alarm signalling units with min./min. or max./max. relays on request 6) not for relay output Page 5 of 9
6 Ordering information for Indicomp 2 with amplifier Catalog No. EUR Deliv. time Indicator/Alarm signalling unit with amplifier V30428A- 0 Design 1 min. and 1 max. relay 5) 3 940,00 1 min. and 1 max. initiator output 2) 6 739,00 Indicator (with no limit values) 8 400,00 Power supply 230 V AC V AC 3-24 V AC 4-24 V DC with no electrical isolation 1) 5-28,00 24 V DC with electrical isolation 7) 6 22,00 Input 3) Ohm measuring amplifier with 2-wire-circuit 5 - Ohm measuring amplifier with 3-wire-circuit 6 - Arucomp measuring amplifier (with no range box 4) ) 7 210,00 Explosion protection none 1 - Installed outside the hazardous area II (2) G [EEx ib] IIC Design 24 Ohm measuring amplifier 3 128,00 Design 25 Arucomp measuring amplifier 4 134,00 Installed inside the hazardous area [EEx] eis G4 6)8) Design 14 Ohm measuring amplifier 6 164,00 Design 15 Arucomp measuring amplifier 7 170,00 Type of connection Screw terminals 2 - Bezel grey (RAL 7037) 1 - black 2 - grey (RAL 7032) 3 16,00 1) not in explosion-protected devices or devices with Arucomp amplifier 2) pay attention to special features "output" 3) Additional ordering information measuring range required 4) complete details with Code Nos. 5) Alarm Signalling Units with min./min. or max./max. relays on request 6) not with relay output 7) not in devices with Arucomp amplifier 8) no ATEX certificate, only available up to Page 6 of
7 Supplementary ordering information and special features Code EUR Deliv. time Measuring range for measuring circuit with no amplifier Direct current, direct voltage according to measuring range table page 9, group 5 or 6 (Code No.) for measuring circuit with Ω amplifier according to range table page 9 (Code No.) Lead balancing 3 x 10 Ω in 3-wire circuit for measuring circuit with Arucomp amplifier with no range box according to measuring range table page 9 (Code No.) 331-1) with range box W (clear text) ,00 W...K (clear text) ,00 W...KV (clear text) ,00 Special measuring ranges (clear text) ,00 Class 1 (only for devices with ma input or a measuring amplifier) (clear text) ,00 Scale % ZSP linear linear, final values according to standard sequence (1-1,2-1,5-2-2, and decimal multiples) with any unit (e.g. 250 t/h) (clear text) ,00 special division (clear text) ,00 blank, start and end marked additional division linear from ,00 according to parameter (clear text) ,00 red line by scaled value (clear text) ,00 blue line by scaled value (clear text) ,00 extra test attached to scale (clear text) ,00 Output intrinsically-safe with intrinsically-safe measuring circuit not intrinsically-safe with intrinsically-safe measuring circuit normally open contact operation with relay output with 1 safety initiator (tested by TÜV) SJ 3,5 SN ,00 with 2 safety initiators (tested by TÜV) SJ 3,5 SN ,00 Normal position 2a, vertical scale 390-2b, horizontal scale as specified Case Terminal box IP 54 2) ,00 Low-glare front plate (not with explosion-protected design) ,00 Satisfies mechanical tests to class 2/ ,00 short casing version (170 mm) 3) ,00 Operating manual 4) german Z1D 5,00 english Z1E 5,00 french Z1F 5,00 spanish Z1S 5,00 1) specify the measuring range box fully, e.g. W 21 KV 2) only possible with terminal connection (version Ex includes design 14 and 15) 3) only possible for devices with no amplifier an no relay that do not incorporate an explosion-protected design 4) 1 copy in German included in the basic supply; no specification required; extra Operating Manuals must be paid (please specify number) Page 7 of 9
8 Connection diagrams Measuring inputs ma U H (+) (-) 13(E) (-) U H (+) (-) (-) - 11(A) 52 Z Signal outputs No/type of signal outputs Pointer position in scale range Connection diagrams and operational schemes with available power supply ( = power fail) Relais outputs (NC contact operation) Initiator outputs In C A B Min Max (+) (-) (+) (-) Max 1 Min A Max Rs Min U X / IX U H Max I In1 In Min I In2 U X / IX U H In1 > 2,2 ma In2 > 2,2 ma B C I In1 I In1 I In2 I In2 In1 < 1,0 ma In2 > 2,2 ma In1 > 2,2 ma In2 < 1,0 ma Z Page 8 of
9 Measuring range table, positions for normal use The measuring ranges shown in the tables are selected acc. to frequency of use. Attention should be paid to the measuring range limits when ordering. Unnamed measuring ranges can be ordered under special features (surcharge). Resistive pickups Resistance thermometer Ref. No. Pt100 IEC C P C P C P C P C P C P C P C P C P C P C P C P C P C P C P C P C P C P C P C P02 Voltage, Current Basic sequence of meas. ranges Basic meas. 2nd pos. 5 of the measur. range voltage Direct design. no. Ref. No. 6 Direct current Ref. No. ranges Factor Factor (mv) (ma) (mv) (ma) (V) (ma) (V) Measuring range = Basic range x Factor Example: Required measuring range ma DC from basic sequence Direct current 6 Factor 10 4 Mounting positions Reference No. to state Page 9 of 9
10 ABB Automation Products GmbH Hoeseler Platz Heiligenhaus, Germany Tel: Fax: Subject to technical changes. Printed in the Fed. Rep. of Germany 10/ EN 05.02
Digital Indicator DS 96/24
Data Sheet 10/33-2.11-EN Digital Indicator DS 96/24 This indicator is suitable for measuring direct voltage or direct current. By using potentiometers, the digital display can be assigned to any input
More informationTransmitter for temperature and direct current variables in four-wire circuit. Contrans T TEU 315, TEU 315-Ex, TEU 325, TEU 325-Ex 11-3.
TEU 315, TEU 315-Ex, TEU 325, TEU 325-Ex Transmitter for temperature and direct current variables in four-wire circuit Transmitters TEU 315 and TEU 325 are designed for direct and alternating voltage measurement
More informationDigital Indicator DS 96/48 PK
Data Sheet 10/33-2.1-EN Digital Indicator DS 9/48 P Digital Indicator DS 9/48 PK Inputs Direct current, direct voltage Thermocouple Resistance thermometer Programmable via front keys or PC software Limit
More informationFieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex
Data Sheet 10/-8.54 EN Level 0: Information FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex HART programmable, Pt 100 (RTD), thermocouples, electrical isolation Resistance thermometer (2,
More informationTR 104, TR 104-Ex Rail mounted Temperature Transmitters
Data Sheet 10/-8.48-EN Rev. A TR 104, TR 104-Ex Rail mounted Temperature Transmitters Analog, Pt 100 (RTD), fixed measuring ranges Input Resistance thermometer (two-wire and three-wire circuit) Optionally
More informationContrans T TEU 471, TEU 471-Ex. Intelligent four-wire temperature transmitters EN
Contrans T TEU 471, TEU 471-Ex Intelligent four-wire temperature transmitters Input/sensor connection: Resistance thermometers (2-, 3-, 4-wire circuit) Thermocouples (without, with internal/external reference
More informationRail mounted Temperature Transmitter TH102/TH102-Ex
Data Sheet 10/-8.54 EN Rail mounted Temperature Transmitter TH102/TH102-Ex HART programmable, Pt 100 (RTD), thermocouples, electrical isolation Input Resistance thermometer (2, 3, 4 wire circuit) Thermocouples
More informationSINEAX TI 807 Passive DC signal isolator. SINEAX TI 807 Passive DC signal isolator
SINEAX TI 807 without power supply, Ex- and non-ex version, in housing N17 or S17 for rail and wall mounting 0102 II (1) G resp. II (2) G Application The signal isolator SINEAX TI 807 serves to electrically
More informationSINEAX TI 807 Passive DC signal isolator
without power supply, Ex- and non-ex version, in housing N17 or S17 for rail and wall mounting 0102 II (1) G resp. II (2) G Application The signal isolator SINEAX TI 807 serves to electrically insulate
More informationElectronic alarm signalling unit TES 20. for temperature and standard signals ENA EN
Electronic alarm signalling unit TES 20 ENA117.01 EN for temperature and standard signals Universal alarm signalling unit (constructional width 4 T) for Temperature (temperature monitor) with Pt 100 IEC
More information2 Safety Barriers. Single-Channel Safety Barriers with Electronic Current Limitation Series 9004
2 Safety Barriers Single-Channel Safety Barriers with Electronic Current Limitation Series 9004 Broad product range for all standard applications in the world of automation Flexible and space saving Time
More informationSINEAX / EURAX 2I1 Passive DC signal isolator
SINEAX / EURAX I without power supply 0 II () G resp. II () G Application The DC signal isolator SINEAX/EURAX I (Figs. and ) serve to isolate load-independent DC current signals. It suppressed noise voltages
More informationTF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels
TF 0 / TF 0-Ex Head mounted temperature transmitters, FOUNDATION Fieldbus (H), Pt 00 (RTD), thermocouples, or independent channels 0/-8.5 EN Input Resistance thermometer (,, wire circuit) Thermocouples
More informationTemperature transmitter itemp PCP DIN rail TMT 121
Technical information TI 087R/09/en 510 03671 Temperature transmitter itemp PCP DIN rail TMT 121 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage
More informationTZIF 4. Current-to-Pulse Converter 10/ EN
TZIF 4 Current-to-Pulse Converter Conversion of direct current or voltage signals into a proportional pulse frequency Integration and average value formation of analog signals for quantity counting/remote
More informationHead mounted Temperature Transmitter TF02/TF02-Ex
Data Sheet Head mounted Temperature Transmitter TF0/TF0-Ex FOUNDATION Fieldbus H, Pt 00 (RTD), thermocouples, or independent channels Input Resistance thermometer (-, -, -wire circuit) Thermocouples Resistance
More informationSINEAX B 811 Power Pack with additional Functions
SINEA B 8 for intelligent and conventional s, in housing S7 for rail and wall mounting 002 II () G Application The power supply unit SINEA B 8 (Figure ) provides the DC power supply for s and transfers
More informationFieldIT Temperature Transmitter, field mounted TH202/TH202-Ex
Data Sheet 0/-8.6 EN Level 0: Information FieldIT Temperature Transmitter, field mounted TH0/TH0-Ex HART programmable, Pt 00 (RTD), thermocouples, electrical isolation Input Resistance thermometer (,,
More informationFieldIT Temperature Transmitter, head mounted TH02/TH02-Ex
Data Sheet 0/-8.9 EN Level 0: Information FieldIT Temperature Transmitter, head mounted TH0/TH0-Ex HART programmable, Pt 00 (RTD), thermocouples, electrical isolation Input Resistance thermometer (,, wire
More informationOperator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique
Operator Manual Transmitters Series KAT-... Analog transmitters in 2-wire technique Important Safety Notes! In the case of non-observance of the installation and safety notes or improper use of the transmitter
More informationSINEAX V 624 Programmable Temperature Transmitter for RTD and TC inputs
SINEAX V 6 for rail mounting in housing P/7 or P/7 St 00 II () GD Application SINEAX V 6 (Figs. and ) is designed for measuring temperature in combination with thermocouples or resistance thermometers.
More informationDigital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting
Electrical Temperature Measurement Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting WIKA Data Sheet TE 12.03
More information... for hydraulic and general applications in hazardous areas
ATEX Approved Inductive... for hydraulic and general applications in hazardous areas Inductive Namur sensors Explosion protected Ignition class "intrinsically safe" when used together a suitable certified
More informationSINEAX TV 808, 1 channel Isolating Amplifier unipolar/bipolar
For electrically insulating, amplifying and converting DC signals 0102 II (1) G Application The purpose of the isolating amplifi er SINEAX TV 808 (Fig. 1 and 2) is to electrically insulate input and output
More informationJUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter)
JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net
More information3 Ex i Isolators. Switching Repeater with Power Relay (250 V / 4 A) Type 9170/ Type 9170/
3 Ex i Isolators Switching Repeater with Power Relay Intrinsically safe input [Ex ia] IIC Galvanic isolation between input, output and power supply Open-circuit / short-circuit monitoring and messaging
More informationKSR-Level sensor KSR-Schwimmer-Magnetschalter KSR Contact Protection Relays
KSR-Level sensor KSR-Schwimmer-Magnetschalter 1001-5 KSR Contact Protection s 1 KSR Contact Protection Type KR230-Ex and KR24-Ex General Description The contact protection relays KR230-Ex and KR24-Ex transmit
More informationitemp HART DIN rail TMT112
Temperature transmitter itemp HART DIN rail TMT112 Universal temperature transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage transmitters, incorporating HART protocol Application
More informationSingle-Channel Safety Barriers with Electronic Current Limitation Series 9004
Single-Channel Safety Barriers with Electronic Current Limitation > Broad product range for all standard applications in the world of automation > Flexible and space saving > Time saving installation due
More informationOperating Instructions
Level and Pressure Operating Instructions VEGATOR 620, 621, 622 max. 0 10 min. 0 10 on VEGATOR 622! 6 7 8 9 10 11 12 13 14 in out Contents Contents Safety information... 2 Note Ex area... 2 1 Product description
More informationSafety Instructions Nivotester FTC625, FTC325
XA01351F-A/00/EN/01.14 71273077 Products Solutions Services Safety Instructions FTC625, FTC325 [Ex ia Ga] IIC/IIB TÜV 13.0903 X Segurança TÜV INMETRO OCP 0004 Document: XA01351F-A Safety instructions for
More informationTemperature Input Module for Zone 1 Series 9482/32
www.stahl.de > 8 channels for temperature sensors > Intrinsically safe inputs Ex ia > For Pt-, Ni- and Cu-resistance temperature detectors according to DIN, IEC and GOST in 2-, 3- and 4-wire circuits >
More informationDigital Input Module NAMUR Ex i / I.S. Inputs, 16 Channels for Zone 1 / Div. 1 Series 9470/22
www.stahl.de > 16 channels for contacts and NAMUR proximity switches (EN 60947-5-6) > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit
More informationBinary Output without Power Supply Series 9176
Binary Output without Power Supply Series 9176 > For intrinsically safe operation of Ex i solenoid valves, indicators and horns > Power supply by control circuit, loop powered > Intrinsically safe output
More informationDigital Input Module 24 V Ex n Inputs, 16 Channels Series 9471
> 16 channels for active 0 / 24 V signals > Zone 2 / Division 2 version for connection of circuits acc. to Ex nl, Ex na, Nonincendive and Non-Ex > Galvanic separation between inputs and system > Two channels
More informationIsolators A3/1. Vibration Transducer Supply Unit Series
> For vibration, acceleration and speed sensors in 2- and 3-wire design > Space-saving dual-channel version > Signal frequencies up to 50 khz > Easy setting by means of front-side rotary switch > Galvanic
More informationJUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter)
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net
More informationSINEAX TV 808, 1 channel Isolating Amplifier, output Ex or non-ex
for electrically insulating, amplifying and converting DC signals, also designed for FSK 1 0102 II (1) G Application The purpose of the isolating amplifi er SINEAX TV 808 (Fig. 1) is to electrically insulate
More informationBinary Output Series 9175
Binary Output > Intrinsically safe output [Ex ia] IIC / [Ex ib] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring (can be switched off) > For use
More informationIntrinsically Safe Compact Controller CTR 210i. Intrinsically Safe Bargraph Indicator. BGI 210i
Intrinsically Safe Compact Controller CTR 210i Intrinsically Safe Bargraph Indicator BGI 210i DMT 02 ATEX E 148 2. Supplement also grahics display Revision 4 IBS BatchControl GmbH Im Sträßchen 2 4 Tel.:
More information3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5.
Ex i Isolators Temperature Transmitter with Output 0/4... 20 ma, without Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe
More informationDIGEM f 96 x 48 EK. Applications. Description
3-349-002-03 1/7.98 Front panel dimensions: 96 x 48 mm LED display: red or green, 14 mm high Max. display range: 19 999 to + 32 765 Modular connectors for flexible use Simple adjustments at front panel
More information3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/.
Ex i Isolators Temperature Transmitter without Output 0/4... 20 ma, with Limit Value Contact Field Circuit Ex i) One unit for nearly all temperature sensors indivdually configurable Intrinsically safe
More informationJUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: 49 661 60030 Fax: 49 661 6003607 Email: mail@jumo.net Internet: www.jumo.net JUMO
More informationAnalogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting
Electrical Temperature Measurement Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting WIKA Data Sheet TE 24.01 Applications T Machinery, plant construction T Process industry
More informationIsolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160
Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de
More informationInductive sensor slot-type SI2-K08-AP7
SI2-K08-AP7 Slot sensor, height 8 mm Plastic, polypropylene Mechanical end stop, removable, for analog pointer instruments 3-wire DC, 10 30 VDC NO contact, PNP output Cable connection Wiring diagram Type
More informationPlug-in module SIRAX V 606, 1 or 2 channels Programmable Temp. Transmitter for RTD and TC inputs
Plug-in module, or channels Application The programmable transmitter (Fig. ) is designed for measuring temperature in combination with thermocouples or resistance thermometers. Thermocouple non-linearities
More informationJUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: 49 661 60030 Fax: 49 661 6003607 Email: mail@jumo.net Internet: www.jumo.net JUMO
More informationTemperature head transmitter itemp PCP TMT 181
Technical information TI 070R/09/en Mat.-Nr.: 510 01110 Temperature head transmitter itemp PCP TMT 181 Universal head transmitter for resistance thermometers (RTD), thermocouples, resistance and voltage
More informationDigital Input Output Module for Zone 2 Series 9470/33
www.stahl.de > 16 channels can be adjusted in pairs as digital input or output > Intrinsically safe inputs/outputs Ex ia > For contacts, NAMUR proximity switches and low-power solenoid valves > Up to 8
More informationAnalog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/
> 4 channels for 2-wire HART transmitters and 4 channels for 4-wire HART transmitters > Intrinsically safe inputs Ex ia IIC > Galvanic separation between inputs and system > Open-circuit and short-circuit
More information0 2 1 â Ó. itemp HART TMT182. Technical Information
Technical Information itemp HART TMT182 Temperature head transmitter Head transmitter for resistance thermometers (RTD), thermocouples (TC), resistance and voltage transmitters (mv), HART -protocol, for
More informationMACX MCR-EX-T-UI-UP. Extract from the online catalog. Order No.:
Extract from the online catalog MACX MCR-EX-T-UI-UP Order No.: 2865654 Freely programmable Ex-i temperature transducer with analog output and 1 limit value relay, standard configuration, resistance thermometer
More informationTemperature Transmitters TMT 136, TMT 137
Technical Information TI 066R/09/en Part No. 51000855 Temperature Transmitters TMT 136, TMT 137 For Pt100 Resistance Thermometers 2-wire head transmitter Standard- and instrinsically safe versions Head
More informationSALES SERVICE +358 (0)
SALES SERVICE +358 (0)17 262 3555 info@econosto.fi ADCATROL ELECTRO-PNEUMATIC POSITIONERS PE 986 (ATEX) DESCRIPTION The ADCATROL PE986 positioner requires an input signal of 4 20 ma for proportional control
More informationTemperature Transmitter itemp RTD DIN rail TMT 127
Technical Information TI 095R/09/en No. 51004790 Temperature Transmitter itemp RTD DIN rail TMT 127 Temperature Transmitter for Pt100 Resistance Thermometer Application Temperature transmitter with fixed
More informationIsolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F
Series 9160 Rev. F > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2, special version up to SIL 3 (IEC 61508) > High accuracy www.stahl.de
More informationElectronic Thermostat TE-1 Version according to EN
JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 3639 Fulda, Germany Postal address: 3635 Fulda, Germany Phone: +49 661 63- Fax: +49 661 63-67 e-mail: mail@jumo.net Internet: www.jumo.net JUMO
More informationSingle-Channel Safety Barriers Series 9001
Single-Channel Safety Barriers Series 9001 > Broad product range for all standard applications in the world of automation > Flexible and space saving single and dual channel versions available > Time saving
More informationAll-or-nothing relay RH(M) 1000 in plug-in case and case for top-hat rail or wall mounting
Data Sheet 10/86-2.36-EN All-or-nothing relay RH(M) 1000 in plug-in case and case for top-hat rail or wall mounting Compact robust power relay Type RH(M) 1003: 3 changeover contacts Type RH(M) 1004: 4
More informationAssembly. Front view. Power Rail
Thermometer Resistance Repeater Features Assembly 1-channel isolated barrier 24 V DC supply (Power Rail) RTD/resistance input Resistance output Accuracy 0.1 % Front view Removable terminals blue Function
More informationPreset counters, electronic
The Codix 716 / 717 can be used universally. These preset pulse, tachometers or preset timers with up to 2 presets can solve a wide variety of control and monitoring tasks in every application. With their
More information10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units
BETA Switching Transformers, Bells and Socket Outlets /2 Product overview /3 4AC3 0, 4AC3 1 bell transformers /5 4AC3 4... 4AC3 transformers for permanent loads /8 4AC2 4 power supply units / 7LQ2 2 bells
More informationDigital Input Output Module for Zone 1 Series 9470/32
www.stahl.de > 16 can be adjusted in pairs as digital input or output > Intrinsically safe inputs/outputs Ex ia > For contacts, NAMUR proximity switches and low-power solenoid valves > Up to 8 can be used
More information0 2 1 â Ó. itemp HART TMT182. Technical Information
Technical Information itemp HART TMT182 Temperature head transmitter Head transmitter for resistance thermometers (RTD), thermocouples (TC), resistance and voltage transmitters (mv), HART -protocol, for
More informationTGE5, TGE5-Ex. Transmitter for angular position. Operating instructions 42/14-33 EN Rev. 04
TGE5, TGE5-Ex Transmitter for angular position Operating instructions 42/14-33 EN Rev. 04 Contents Page Applications and description 4 1 Mounting and connection................... 4 1.1 Parts supplied
More informationCATALOGUE ISOLATING SWITCHING AMPLIFIERS POWER SUPPLIES ATEX
CATALOGUE ISOLATING SWITCHING AMPLIFIERS POWER SUPPLIES ATEX Registration No.: 1327-1 Testing laboratory accredited according to DIN EN 451 Reg.-No. DAT-P-48/95- For all transactions, the newest version
More informationDigital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version
Temperature Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version WIKA data sheet TE 15.01 for further approvals see page 10 Applications
More informationRemote Switching Unit nivotester FTL 320
Technical Information TI 203F/24/ae Remote Switching Unit nivotester For connection to intrinsically safe Liquiphant level limit switches Applications Limit detection of fluids and bulk solids in tanks
More informationDigital Input Output Module for Zone 2 Series 9470/33
www.stahl.de > 16 can be adjusted in pairs as digital input or output > Intrinsically safe inputs/outputs Ex ia > For contacts, NAMUR proximity switches and low-power solenoid valves > Up to 8 can be used
More informationFloat Switches with Permanent Magnet For Vertical Installation Model RSM
Level Measurement Float Switches with Permanent Magnet For Vertical Installation Model RSM WIKA Data Sheet LM 30.01 Applications Level measurement for almost all liquid media Pump/level control and monitoring
More information09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i
Temperature Transmitter Series 9182 www.stahl.de > One unit for nearly all temperature sensors indivdually configurable > Intrinsically safe input [Ex ia] IIC > Signal duplication possible > Galvanic isolation
More informationPositioner with HART Communication Type 3780
Positioner with HART Communication Type 780 Application Single-acting or double-acting positioner for attachment to pneumatic control valves. Supplied with an electric input signal from to 20 ma Travels
More informationitemp PA TMT184 Technical information
Technical information itemp PA TMT184 Temperature head transmitter with PROFIBUS-PA interface. Supply and digital communication using PROFIBUS-PA, for installation in a Form B sensor head. Features and
More information06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500
Switching Repeater Series 9170 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit / short-circuit monitoring and messaging (can be switched
More informationIsolators A3/1.
> Compact limit value switch with 2 configurable limiting values and 4... 20 ma output > Suitable for 2-, 3-wire transmitters, 2-wire HART transmitters and ma sources > Intrinsically safe input [Ex ia]
More informationInstallation guide 877 FDI Field Display & Interface
Installation guide 877 FDI Field Display & Interface November 2008 Part no. 4416.264 Rev. 5 Enraf BV PO Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100 Fax : +31 15 2701 111 E-mail : enraf-nl@honeywell.com
More informationElectrical Alarm Contacts
Accessories Electrical Alarm Contacts T Model 821, Magnetic Snap-Action Contacts T Model 831, Inductive Alarm Sensors T Model 830 E, Electronic Contacts WIKA Data Sheet AC 08.01 Applications T Control
More informationLINAX 4000L Continuous-line recorder
-48-852-0 4/2.99 1 to 4 line channels Format 144 mm x 144 mm, mounting depth 250 mm Combined recording table for roll chart (2 m) or fanfold chart (16 m) Measuring channels electrically isolated Rugged
More informationTwo-channel safety barriers Series 9002
Two-channel safety s Series 00 > Wide product range for all standard applications of the automation > Flexible and space-saving available in single and double channel versions > Time-saving installation
More informationfor DC currents or voltages, temperature sensors, remote sensors or potentiometers II (1) G Application Features / Benefits
SINEAX VC 603, Programmable for DC currents or voltages, temperature sensors, remote sensors or potentiometers 0102 II (1) G Application The SINEAX VC 603 (Figs. 1 and 2) converts the input variable a
More informationIsolators A3/1. Ex i Power Supply Field Circuit Ex i Series
> Intrinsically safe output [Ex ib] IIC/IIB > Stable output voltage > Galvanic isolation between output and power supply > Power supply or 85... 230 V AC > Compact design www.stahl.de 07673E00 Basic function:
More informationConnection. Input EEx ia IIC. Sense. Fine tuning adjustment. Fine tuning amplifying. Amplifying. Adjustment. Output. Composition
Converter Connection 1-channel EEx ia IIC for 4-wire and 6-wire bridges Analogue output 0/4 ma... 20 ma or 4mA...-12mA Full bridge load cells and strain gauges circuit for resistance bridges up to 17 Ω
More informationGlass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 20 ms. 60 ms. 60 ms. Approx. 1.3 kg. Approx. 0.9 kg. Approx. 5.
General data Mounting On linear actuators On quarter turn actuators ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR) Range of stroke: 3... 130 mm Integrated to VDI/VDE 3847-2 or VDI/VDE 3845 Angle
More informationDigital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version
Electrical temperature measurement Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version WIKA data sheet TE 15.01 Applications Process industry Machine building
More informationLevel Limit Switch nivotester FTL 370, FTL 372
Technical Information TI 98F/00/en Limit Switch nivotester FTL 370, FTL 37 With intrinsically-safe signal circuits for connection to sensors Liquiphant, Nivopuls, Soliphant. Features at a Glance High operational
More informationWeighing Instruments
GHM Messtechnik GmbH Sales Center International Schloßstraße 6 88453 Erolzheim Germany Fon +49-7354-937233-0 Fax -88 www.ghm-messtechnik.de info@ghm-messtechnik.de Weighing Instruments System Evaluation
More informationIsolators A3/1.
Temperature Transmitter Series 9182 > One unit for nearly all temperature sensors indivdually configurable > Signal duplication possible > Galvanic isolation between input, output, power supply and configuration
More informationSITRANS T measuring instruments for temperature
Overview Our field devices for heavy industrial use HART, Universal 4 to 20 ma, universal Field indicator for 4 to 20 ma signals The temperature transmitter SITRANS TF works where others feel uncomfortable.
More informationInstallation guide 971 SmartRadar LTi
Installation guide 971 SmartRadar LTi March 2009 Part no. 4416.715 Revision 3 Enraf B.V. P.O. Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100 Fax : +31 15 2701 111 E-mail : enraf-nl@honeywellenraf.nl
More informationIsolators A3/1. Temperature Transmitter Field Circuit Non-Ex i Series
Temperature Transmitter Series 9182 > One unit for nearly all temperature sensors indivdually configurable > Signal duplication possible > Galvanic isolation between input, output, power supply and configuration
More informationIsolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series
Transmitter Supply Unit Series 9160 > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > Open-circuit and short-circuit monitoring and messaging for input
More informationGlass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.
General data Mounting On linear actuators On quarter turn actuators ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR) Range of stroke: 3... 130 mm Integrated to VDI/VDE 3847-2 or VDI/VDE 3845 Angle
More information600T Series Transmitters. Specification Sheet. Model 653T Electronic temperature transmitter (PC programmable)
Specification Sheet 600T Series Transmitters Model 65T Electronic temperature transmitter (PC programmable) High flexibility and wide rangeability Single transmitter accepts RTD/THC/mV/ohm Galvanically
More informationTwo-channel safety barriers Series 9002
Two-channel safety s Series 00 > Wide product range for all standard applications of the automation > Flexible and space-saving available in single and double channel versions > Time-saving installation
More informationUniversal Intelligent 2-wire DIN Rail Transmitters
Universal Intelligent 2-wire DIN Rail Transmitters IPAQ-L is a universal and intelligent 2-wire DIN rail transmitter for temperature and other measurement applications. IPAQ-LX is the Intrinsic Safe version
More informationKINAX WT 717 Programmable Transmitter for Angular Position
Ruggedized version Application The KINAX WT 717 (Fig. 1) converts the angular position of a shaft into a load-independent direct current signal, proportional to the angular position. The unit is contact
More informationAnalog Universal Module HART for Zone 2 Series 9468/33
> 8 channels can be adjusted individually as analog inputs or outputs > Intrinsically safe inputs/outputs Ex ia > For 0/4 20 ma + HART signals > Line fault monitoring per channel > Diagnostics based on
More informationIsolating Repeater Input Series 9163
> For 4-wire HART transmitters and voltage sources > Intrinsically safe input [Ex ia] IIC > Galvanic isolation between input, output and power supply > For use up to SIL 2 (IEC 61508) > High accuracy www.stahl.de
More information