Qualification of Fan-Generated Duct Rumble Noise Part 2: Results

Size: px
Start display at page:

Download "Qualification of Fan-Generated Duct Rumble Noise Part 2: Results"

Transcription

1 2008, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA SL (RP-1219) Qualification of Fan-Generated Duct Rumble Noise Part 2: Results Joshua Kading J. Adin Mann, III, PhD Michael B. Pate, PhD Associate Member ASHRAE Member ASHRAE Member ASHRAE This paper is based on findings resulting from ASHRAE Research Project RP ABSTRACT Duct rumble noise in HVAC air distribution systems is commonly attributed to the poor aerodynamic discharge conditions of fan outlets. To date, qualitative descriptors published in ASHRAE Handbooks have been used as design guidelines for engineers to limit the amount of duct rumble noise. ASHRAE funded a project, RP1219, to quantify the rumble noise as the fan discharge orientation and distance from a duct is varied. A test system was built and verified to measure discrete frequency and one-third octave spectra in an adjoining room to the fan room. Tones, associated with vibration, were removed from the spectra, so that the one-third octave band data focused on analysis of the aerodynamic noise. Results for the fan discharge orientation and distance relative to a 90 degree elbow are presented. Some trends are identified; however, overall the results indicate a need for testing with additional fans and coupling the testing with measurements of the fan discharge air flow. INTRODUCTION The discharge configuration of a fan affects the amount of low frequency duct rumble noise downstream of the fan. Rumble noise, defined for this study as noise in the 16 Hz to 300 Hz one third octave bands, is considered by many practicing engineers as an indication of turbulence caused by poorly designed fan discharge conditions. With the goal of replacing qualitative design recommendations with quantitative design tools in the ASHRAE Applications Handbook (2003), ASHRAE funded a research project, RP1219, to obtain data on the correlation of rumble noise to the fan and duct configuration. If successful, the result would be a prediction tool that could be used to compare design alternatives such as weighing the cost of modifying the orientation and position of the fan compared to a noise control measure such as lagging or lining the duct. In Kading (2006) the design and verification of the test facility and procedures were presented. The specification on the design of the test system was that four different fan discharge conditions could be tested with four different lengths of duct from the fan outlet to the first duct transition in the system, which in all but one case was a 90 degree elbow. The measurements were to be performed at 8 operating points of the fan, to be accomplished by varying inlet restriction to the fan and the fan speed. A companion paper, Kading et.al. (2008) contains a summary of the test system and verification of the test system. In this paper, the focus is on the key results and suggestions for future work. TEST SYSTEM The system consists of three rooms shown in Figure 1: a fan room, a measurement room and an outlet room. A more detailed description of the test system is given in a companion paper (Kading.et. al and Kading 2006). The fan room was the inlet to the duct system, the measurement room is acoustically isolated from the rest of the system and the outlet room was open to the rest of the building, including the fan room. The fan was a double wide/double inlet, forward curve 18-inch diameter wheel, scroll fan. The inlet to the fan room Joshua Kading is an engineer at Stanley Consultants, Inc., Muscatine, IA. J. Adin Mann III is an associate professor and Michael B. Pate is a professor in the Department of Mechanical Engineering, Iowa State University, Ames, IA ASHRAE Published in Vol. 114, Part 2

2 2008, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA was controlled with a hole in the door with adjustable area, thus acting as the volume damper. The system was built so that flow rate, fan speed, fan configuration, and duct length could be varied. The measured quantities were flow rate, average sound level (discrete frequency spectra and one-third octave band) in the measurement room, and sound levels in selected points inside the duct. The uncertainty in the measured one-third octave band sound level was determined to be ±1.7 db when retesting and rebuilding a configuration. FAN DISCHARGE CONDITIONS The four fan configurations are shown in Figure 2. In each configuration, the distance from the fan outlet to the transition piece was varied: Configuration 1: the fan was in front blast, blowing directly in to the expansion duct. Distances of 0D and 1D were tested. Configuration 2: the fan discharged air to a 90 degree elbow turned with the fan rotation. Distances of 0D, 1D, 2D, and 2.3D were tested. Configuration 3: the fan discharged air to a 90 degree elbow turned against the fan rotation. Distances of 0D, 1D, 2D, and 2.3D were tested. Configuration 4: the fan discharged air to a 90 degree elbow turned perpendicular to the fan rotation plane. In this configuration there was a 7 transition piece at the elbow that directed the air into the duct system. Distances of 0D, 1D, 2D, and 2.3D were tested. SELECTION OF OPERATING CONDITIONS The required operating points for the fan were stated in the research request for proposals (RFP). These populate the fan curve to give a representation of the effects on sound level at different typical operating points, Figure 3 and Table 1. The fan curve in Figure 3 was used as a basis for setting all of the operating points. Table 2 provides the AMCA 300 Predicted inlet sound levels using fan vendors modeling program. DATA REPRESENTATION Processing and visualizing this large data set was a challenge. Figure 4 gives an example of the measured one-third octave band sound levels for Configuration 1 with the fan one duct diameter (1D) from the transition duct. Since there are significant changes in the spectra as a function of the operating point, the changes by configuration would have not been clear if the measured spectra were used directly. Therefore, as shown in Figure 5, the difference of spectra compared to a reference was used. The reference could change, however, in most cases the reference was Configuration 1 at a distance of 1D. Within the space constraints of the test facility this case represented the closest to the ideal configuration. REMOVING TONES In the cases where the sound levels were low, tones entering the sound measurements from the fan and motor vibration were a concern. This issue was remedied by removing the tones from the discrete frequency spectra, and then calculating the one-third octave band levels from the modified spectra. Figure 6 shows an example of a discrete frequency spectrum with significant tones along with the spectrum with the tones removed. The tones were removed manually. The data file was modified by setting the values at the frequencies of the tones to the nearby broadband levels. A similar approach was used to separate the tone and broadband noise in a fan noise study, The 4th, 8th, and 12th harmonics were left since they were correlated to an aerodynamic noise source on the fan (Kading 2006 and Kading et. al 2008). Figure 7 shows one third octave spectra for one case. In the top plot, the original sound levels are presented and in the Figure 2 Figure 1 Test system layout. Four fan outlet configurations with distance D as the variable length (0 to 24 in configuration 1, 0 to 55 in Configurations 2 and 3, and 7 to 55 in Configuration 4). Published in Vol. 114, Part 2 29

3 2008, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Figure 3 Operating conditions setpoints along the fan curve. Table 1. Operating Points Studied for Every Configuration Flow Rate (% of wide open flow) Pressure Drop Across Fan (in water) % X 80% X X 60% X X X 35% X X Table 2. AMCA 300 Predicted Inlet Sound Levels Using Fan Vendors Modeling Program %WOF Flow Rate (cfm) Fan Pressure Drop (in. wt) Fan Speed (rpm) Inlet Sound Power Level in db Octave Band, Hz k 2k 4k 8k LwA Published in Vol. 114, Part 2

4 2008, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Figure 5 Figure 4 Example of sound levels and sound level differences. Average one-third octave band sound levels in db at Configuration 1, 1 duct diameter. (a) 1.0 inch water pressure drop. (b) 2.5 inch water pressure drop. (c) 4.0 inch water pressure drop. bottom plot, the one-third octave levels with the tones removed are presented. In general, removing the tones, as in the case of Figure 7, has the greatest effect in the 31.5 Hz onethird octave band. Since the spectra with tones removed is more indicative of the aerodynamic noise, the rest of the results will focus on the spectra with the tones removed. RESULTS: OBSERVED TRENDS The results overall showed more complexity than was originally expected, however, there were some trends that were identified. Figure 8 shows all configurations for the case of the fan outlet being 1D from the transition. Each plot contains data for one operating point and shows the sound level change for Configurations 2, 3, and 4 relative to Configuration 1. As a general statement, Configuration 4 is the loudest, followed by Configuration 3 and then Configuration 2. The noise levels increase by as much as 5 to 10 db. However, the difference varies with operating point. In all cases, the difference decreases with frequency. For Configurations 2 and 4 and all the operating points, Figures 9 and 10 show the changes in sound level as a function of distances between the fan discharge and the transition. Each case has the smaller distance as the reference, thus positive Figure 6 Example of a measured spectrum and the spectrum with tones removed. 60% WOF, 1inch Pressure drop, Configuration 2, 0 Duct diameters. numbers represent a lowering of the sound level as distance is increased. Figure 9 shows a sound reduction of 2 to 4 db when increasing the distance from 0D to 1D for Configuration 2. However, for Configuration 4, the noise level generally increases by up to 6 db for certain operating points as the distance increases. One can hypothesize that in the case of Configuration 2, there is an aerodynamic interaction between the fan discharge and the transition that is reduced as the distance between the fan discharge and transition is increased. In some cases for Configuration 4, one can hypothesize that being close to the transition may stop an aerodynamic effect from being generated. Figure 10 shows that for the case of Configuration 2, the noise is more greatly decreased when increasing the distance from the fan discharge to the transition from 1D to 2D. However, the changes are limited to the 20 to 63 Hz one third octave bands. In the case of Configuration 4, the sound level decreases with increasing distance from 1D to 2D, but the change is smaller than changes in other cases such as Configuration 2. This would Published in Vol. 114, Part 2 31

5 2008, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Figure 7 Difference between Configuration 3 and Configuration 2 at operating point 35%WOF and 2.5 inch pressure drop. A) original and B) After tones are removed. Figure 8 Four discharge configurations at the eight different operating points. The first columns of plots are the 1.0 inch pressure drop sound level differences (90%, 80%, and 60% WOF). The second is the 2.5 inch pressure drop sound level differences (80%, 60%, 35%). The third column is the 4.0 inch pressure drop sound level differences (60%, 35%). 32 Published in Vol. 114, Part 2

6 2008, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Figure 9 Sound Level Reduction at 1D compared to 0D. A positive value indicates a lower sound level at 1D than 0D. Figure 10 Sound Level Reduction at 2D compared to 1D. A positive value indicates a lower sound level at 2D than 1D. Published in Vol. 114, Part 2 33

7 2008, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA suggest that at 1D, the aerodynamic effects are fully formed so that increasing the distance decreases the noise generation and that the aerodynamic noise is dominated by the fan and discharge flows rather than the flow interacting with the elbow. It is assumed that since the fan operating points are the same for all these comparisons that the sound level changes are caused by changes in the aerodynamic noise generated between the fan discharge and the elbow. Measurements of the air flow in this region could help correlate the sound changes to the aerodynamic phenomena. Figure 11 shows the one-third octave band changes and the discrete frequency spectra for the same cases. The point of these plots is to show that the low frequency changes in these cases is caused by a significant change in the broad band noise when increasing the distance from 0D to 2D. Assuming that the broadband noise is dominated by turbulent flow, it seems reasonable to conclude that the noise level changes are caused by changes in the aerodynamic noise sources when the distance between the fan discharge and elbow are increased. Comparison of the discrete frequency spectra and the one-third octave sound level changes does indicate several cases where the sound level change is dominated by the 4th, 8th, or 12 th harmonic tones changing. Figure 12 is a generalized representation of the operating points that are dominated by tone noise and those by broad band noise. It also indicates which operating points generally did not follow trends for the configuration. Finally, Table 3 shows a compilation of all the results but in octave bands. The cells are coded with dark gray indicating a sound level increase of 2 db or more and light gray indicated Figure 11 Comparison of one-third octave levels and discrete frequency spectra levels showing broad band changes. 34 a sound level decrease of 2dB or more relative to Configuration 1 at 1D. There is no clear pattern to the results. CONCLUSIONS The results show that varying the fan configuration and distance from the fan discharge to the elbow can cause changes in low frequency noise over a 14 db range. The greatest changes occur in the one-third octave bands from 20 Hz to 63 Hz. For most configurations and operating points, the change decreases to below 2 db above the 125 Hz onethird octave band. An overriding conclusion from the work was that there was no simple relationship between the configuration, duct length between the fan discharge and 90 degree elbow inlet, and fan operating condition. In general, the expected trends were seen for selected operating points; however, for some operating points and distances between the fan outlet and elbow, the configurations considered non-ideal (Configurations 3 and 4) were quieter by 5 to 10 db. A primary outcome of the work is conclusions on how future work could be done differently to answer the questions originally raised in the RFP. The data suggests that the aerodynamics near the fan have a complex behavior that requires additional diagnostic tools to be used and that the experimental setup be redesigned to separate confounding effects and tone noise. The recommendations for future work fall into four categories. A discussion of each follows. 1. Use diagnostic tools to study the fluid flow from the fan exit through the elbow. 2. Reduce potential confounding of the aerodynamic noise generation and the breakout noise from the duct in the measurement room. Figure 12 Schematic representation of regions on the fan curves where tones dominate the sound level changes and where the change did not closely follow identified trends for the configuration. Published in Vol. 114, Part 2

8 2008, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Table 3. Compiled Octave Band Data for All Cases* Configuration 1 Configuration 2 Configuration 3 Configuration 4 0D 1D 0D 1D 2D %D 0D 1D 2D %D 0D 1D 2D %D Inch Pressure Drop 2.5 Inch Pressure Drop 1 Inch Pressure Drop 35% WOF 60% WOF 35% WOF 60% WOF 80% WOF 60% WOF 80% WOF 90% WOF * Configuration 1, 1D, is given as the reference. All levels are db difference. (Positive value indicated increases sound level.) Dark gray cells are noise increases greater than 2 db and light graycells are noise decreases by greater than 2 db. Published in Vol. 114, Part 2 35

9 2008, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( ESL-PA Redesign the fan and motor support structure to reduce vibration. 4. Study additional fans and select fans with lower tone noise. An approach that has been successful in cooling fan noise is to use measure flow data to verify and tune computational fluid dynamic (CFD) models of the air flow and then use the CFD models to evaluate fan designs. CFD has been demonstrated for HVAC design (Herrin et. al. 2007). Measuring the complex three dimensional flow is a very difficult task and would require advances in some of the available full field diagnostic tools, however there has been some success with using Particle Image Velocimetry (PIV) (Laage 2005) to study the complex flow at the outlet of a blower fan. Combining CFD with measured flow data is an approach that generates confidence in the CFD results and then allows the three dimensional spatial detail available of the CFD results to be used to better identify and understand the key flow phenomena that are dominating the rumble noise. The second recommendation is that the experimental configuration be redesigned so that experiments are designed to study two issues separately: 1) the aerodynamic noise generated from the fan outlet to elbow, and 2) the transmission of low frequency noise down the duct and the breakout noise in a room. The impact of these two issues was likely confounded in the results presented for this study. Therefore, it is recommended that two experimental setups are considered. In one case measurements of the sound power inside the duct is measured, where the duct is rigid down stream of the elbow. And in a second configuration, a typical duct is used down stream of the elbow and the break out noise is measured, as was done in this study. The third recommendation is that the experimental setup be changed to reduce the tonal noise. One cause of the tone noise was the flexibility in the structure supporting the fan and motor over a range of heights from on the ground to over 5 feet in the air. This was done so that the outlet duct was kept fixed and in a typical configuration in the measurement room. Therefore it is recommended that the future configuration be with a system rotated 90 degrees, so that the motor and fan are mounted near the floor and are moved along the floor, rather than raised, to increase the distance between the fan outlet and elbow. Such a system could be designed with the fan and motor support secured rigidly to the floor at each position of the fan outlet to elbow distance. A successful design will likely reduce the need for the tone removal. The fifth recommendation is that all these changes be implemented in a study of additional fans to identify the variation between fans and the degree to which the data obtained here provides a general characterization of the fan discharge design issues. In particular, fans with low tonal noise components should be studied in order to further reduce or eliminate the need for the tone removal. REFERENCES Herrin D.W., Tao Z., Carter A.E., Liu J., and Seybert A.F., Using Numerical Methods to Analyze Multicomponent HVAC Systems (RP-1218), 2007, Vol. 113, pt 1 Kading, J, Qualification of Duct Rumble Noise Test System MS thesis, Iowa State University, Kading, J., Mann, J.A., and Pate, M.P., Qualification of Fan Generated Duct Rumble Noise: Part 2: Results (Rp 1219),, submitted for publication in 2008 Annual Meeting. Laage, J.W., Mahendra, P., Melzer, P.J., Olsen, M.G., Mann J.A., Yarbough, D.,Yu, D., Measurement Tools for Studying Fan Noise, Proceedings of. Noise-Con 2004, pp Laage, J.W., Armstrong, A.J., Eilers, D.J., Olsen, M.G., and Mann J.A., Air Flow Measurement Techniques Applied to Noise Reduction of a Centrifugal Blower, Proceedings of Noise-Con 2005, Minneapolis, Minnesota, October 17-19, Published in Vol. 114, Part 2

10 ESL-PA Reproduced with permission of the copyright owner. Further reproduction prohibited without permission. Published in Vol. 114, Part 2

ANALYTICAL NOISE MODELLING OF A CENTRIFUGAL FAN VALIDATED BY EXPERIMENTAL DATA

ANALYTICAL NOISE MODELLING OF A CENTRIFUGAL FAN VALIDATED BY EXPERIMENTAL DATA ANALYTICAL NOISE MODELLING OF A CENTRIFUGAL FAN VALIDATED BY EXPERIMENTAL DATA Beatrice Faverjon 1, Con Doolan 1, Danielle Moreau 1, Paul Croaker 1 and Nathan Kinkaid 1 1 School of Mechanical and Manufacturing

More information

High intensity and low frequency tube sound transmission loss measurements for automotive intake components

High intensity and low frequency tube sound transmission loss measurements for automotive intake components High intensity and low frequency tube sound transmission loss measurements for automotive intake components Edward R. Green a) Sound Answers, Inc., 6855 Commerce Boulevard, Canton, Michigan, 48187 USA

More information

Acoustics. Randy Zimmerman Chief Engineer

Acoustics. Randy Zimmerman Chief Engineer Acoustics Randy Zimmerman Chief Engineer Instructor Randy Zimmerman Chief Engineer 972.212.4811 rzimmerman@titus-hvac.com What You Will Learn Sound power vs sound pressure Sound quality AHRI 880/885 NC

More information

SOUND SPECTRUM MEASUREMENTS IN DUCTED AXIAL FAN UNDER STALL CONDITIONS AT FREQUENCY RANGE FROM 9000 HZ TO 9600 HZ

SOUND SPECTRUM MEASUREMENTS IN DUCTED AXIAL FAN UNDER STALL CONDITIONS AT FREQUENCY RANGE FROM 9000 HZ TO 9600 HZ Int. J. Mech. Eng. & Rob. Res. 2012 Manikandapirapu P K et al., 2012 Research Paper ISSN 2278 0149 www.ijmerr.com Vol. 1, No. 2, July 2012 2012 IJMERR. All Rights Reserved SOUND SPECTRUM MEASUREMENTS IN

More information

Multi-channel Active Control of Axial Cooling Fan Noise

Multi-channel Active Control of Axial Cooling Fan Noise The 2002 International Congress and Exposition on Noise Control Engineering Dearborn, MI, USA. August 19-21, 2002 Multi-channel Active Control of Axial Cooling Fan Noise Kent L. Gee and Scott D. Sommerfeldt

More information

Active Control of Energy Density in a Mock Cabin

Active Control of Energy Density in a Mock Cabin Cleveland, Ohio NOISE-CON 2003 2003 June 23-25 Active Control of Energy Density in a Mock Cabin Benjamin M. Faber and Scott D. Sommerfeldt Department of Physics and Astronomy Brigham Young University N283

More information

On the accuracy reciprocal and direct vibro-acoustic transfer-function measurements on vehicles for lower and medium frequencies

On the accuracy reciprocal and direct vibro-acoustic transfer-function measurements on vehicles for lower and medium frequencies On the accuracy reciprocal and direct vibro-acoustic transfer-function measurements on vehicles for lower and medium frequencies C. Coster, D. Nagahata, P.J.G. van der Linden LMS International nv, Engineering

More information

Design of a System to Control the Noise of Dry Fluid Coolers

Design of a System to Control the Noise of Dry Fluid Coolers International Journal of Advanced Mechanical Engineering. ISSN 2250-3234 Volume 4, Number 7 (2014), pp. 839-848 Research India Publications http://www.ripublication.com Design of a System to Control the

More information

FAN NOISE & VIBRATION

FAN NOISE & VIBRATION FAN NOISE & VIBRATION SECTION INDEX 01. FAN NOISE 02. VIBRATION 03. RESONANT FREQUENCIES & HARMONICS 04. SOUND DATA & GURANTEE EXCLUSIONS 05. SOUND DATA MEASURED AT AMCA APPROVED LAB IN USA PFCSL/01 Page

More information

Acoustic Performance of Helmholtz Resonator with Neck as Metallic Bellows

Acoustic Performance of Helmholtz Resonator with Neck as Metallic Bellows ISSN 2395-1621 Acoustic Performance of Helmholtz Resonator with Neck as Metallic Bellows #1 Mr. N.H. Nandekar, #2 Mr. A.A. Panchwadkar 1 nil.nandekar@gmail.com 2 panchwadkaraa@gmail.com 1 PG Student, Pimpri

More information

Analysis on Acoustic Attenuation by Periodic Array Structure EH KWEE DOE 1, WIN PA PA MYO 2

Analysis on Acoustic Attenuation by Periodic Array Structure EH KWEE DOE 1, WIN PA PA MYO 2 www.semargroup.org, www.ijsetr.com ISSN 2319-8885 Vol.03,Issue.24 September-2014, Pages:4885-4889 Analysis on Acoustic Attenuation by Periodic Array Structure EH KWEE DOE 1, WIN PA PA MYO 2 1 Dept of Mechanical

More information

Design of Barrier to Control the Noise of Fin Tube Heat Exchangers

Design of Barrier to Control the Noise of Fin Tube Heat Exchangers Research Article International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347-5161 2014 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Design

More information

Transformer core noise and vibration prediction methodology

Transformer core noise and vibration prediction methodology Transformer core noise and vibration prediction methodology Parmatma Dubey, Manager Technology Sarang Dev, Executive- Technology Atul Daga, Sr. Executive- Technology Date: June 11, 2014 CG Background Avantha

More information

NOISE REDUCTION OF A RECIPROCATING COMPRESSOR BY ADDING A RESONATOR IN SUCTION PATH OF REFRIGERANT

NOISE REDUCTION OF A RECIPROCATING COMPRESSOR BY ADDING A RESONATOR IN SUCTION PATH OF REFRIGERANT NOISE REDUCTION OF A RECIPROCATING COMPRESSOR BY ADDING A RESONATOR IN SUCTION PATH OF REFRIGERANT Yogesh V. Birari, Mayur M. Nadgouda Product Engineering Department, Emerson Climate Technologies (India)

More information

CHAPTER 7 FAULT DIAGNOSIS OF CENTRIFUGAL PUMP AND IMPLEMENTATION OF ACTIVELY TUNED DYNAMIC VIBRATION ABSORBER IN PIPING APPLICATION

CHAPTER 7 FAULT DIAGNOSIS OF CENTRIFUGAL PUMP AND IMPLEMENTATION OF ACTIVELY TUNED DYNAMIC VIBRATION ABSORBER IN PIPING APPLICATION 125 CHAPTER 7 FAULT DIAGNOSIS OF CENTRIFUGAL PUMP AND IMPLEMENTATION OF ACTIVELY TUNED DYNAMIC VIBRATION ABSORBER IN PIPING APPLICATION 7.1 INTRODUCTION Vibration due to defective parts in a pump can be

More information

Development of a Reactive Silencer for Turbo Compressors

Development of a Reactive Silencer for Turbo Compressors Development of a Reactive Silencer for Turbo Compressors Jan Smeulers Nestor Gonzalez TNO Fluid Dynamics TNO Fluid Dynamics Stieltjesweg 1 Stieltjesweg 1 2628CK Delft 2628CK Delft jan.smeulers@tno.nl nestor.gonzalezdiez@tno.nl

More information

Generic noise criterion curves for sensitive equipment

Generic noise criterion curves for sensitive equipment Generic noise criterion curves for sensitive equipment M. L Gendreau Colin Gordon & Associates, P. O. Box 39, San Bruno, CA 966, USA michael.gendreau@colingordon.com Electron beam-based instruments are

More information

Summary. Page SEG SEG Denver 2014 Annual Meeting

Summary. Page SEG SEG Denver 2014 Annual Meeting Seismo-acoustic characterization of a seismic vibrator Claudio Bagaini*, Martin Laycock and Colin Readman, WesternGeco; Emmanuel Coste, Schlumberger; Colin Anderson, Siemens PLM Software Summary A seismic

More information

Please refer to the figure on the following page which shows the relationship between sound fields.

Please refer to the figure on the following page which shows the relationship between sound fields. Defining Sound s Near The near field is the region close to a sound source usually defined as ¼ of the longest wave-length of the source. Near field noise levels are characterized by drastic fluctuations

More information

Experimental study of broadband trailing edge noise of a linear cascade and its reduction with passive devices

Experimental study of broadband trailing edge noise of a linear cascade and its reduction with passive devices PhD Defense Experimental study of broadband trailing edge noise of a linear cascade and its reduction with passive devices Arthur Finez LMFA/École Centrale de Lyon Thursday 1 th May 212 A. Finez (LMFA/ECL)

More information

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE Copyright SFA - InterNoise 2000 1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 3.8 THE FIRST 1000

More information

NASA Langley Activities on Broadband Fan Noise Reduction via Novel Liner Technologies

NASA Langley Activities on Broadband Fan Noise Reduction via Novel Liner Technologies NASA Langley Activities on Broadband Fan Noise Reduction via Novel Liner Technologies Michael G. Jones NASA Langley Research Center, Hampton, VA CEAS/X-Noise Workshop on Broadband Noise of Rotors and Airframe

More information

Proposal. Analysis of Parallel Vibration Paths with Potential Application to Vehicle Noise. Reduction. Submitted to. The Engineering Honors Committee

Proposal. Analysis of Parallel Vibration Paths with Potential Application to Vehicle Noise. Reduction. Submitted to. The Engineering Honors Committee Proposal Analysis of Parallel Vibration Paths with Potential Application to Vehicle Noise Reduction Submitted to The Engineering Honors Committee 119 Hitchcock Hall College of Engineering The Ohio State

More information

Microphone Array Measurements for High-speed Train

Microphone Array Measurements for High-speed Train Microphone Array Measurements for High-speed Train Korea Research Institute of Standards and Science Hyu-Sang Kwon 2016. 05. 31 2 Contents Railway Noise Sound Images Flow Noise Railway Noise Measurement

More information

FEM Analysis and Optimization of Two Chamber Reactive Muffler by using Taguchi Method

FEM Analysis and Optimization of Two Chamber Reactive Muffler by using Taguchi Method American International Journal of Research in Science, Technology, Engineering & Mathematics Available online at http://www.iasir.net ISSN (Print): 23-3491, ISSN (Online): 23-3580, ISSN (CD-ROM): 23-3629

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 10302-1 First edition 2011-01-15 Acoustics Measurement of airborne noise emitted and structure-borne vibration induced by small air-moving devices Part 1: Airborne noise measurement

More information

Silent Transformers to Help Consolidated Edison Meet New York City s Ultrastrict Noise Ordinances

Silent Transformers to Help Consolidated Edison Meet New York City s Ultrastrict Noise Ordinances BY DR. RAMSIS GIRGIS, ABB INC. The Sound of Silence: Silent Transformers to Help Consolidated Edison Meet New York City s Ultrastrict Noise Ordinances S ilence is a source of great strength. Although these

More information

EXPERIMENTAL INVESTIGATIONS OF DIFFERENT MICROPHONE INSTALLATIONS FOR ACTIVE NOISE CONTROL IN DUCTS

EXPERIMENTAL INVESTIGATIONS OF DIFFERENT MICROPHONE INSTALLATIONS FOR ACTIVE NOISE CONTROL IN DUCTS EXPERIMENTAL INVESTIGATIONS OF DIFFERENT MICROPHONE INSTALLATIONS FOR ACTIVE NOISE CONTROL IN DUCTS M. Larsson, S. Johansson, L. Håkansson and I. Claesson Department of Signal Processing Blekinge Institute

More information

LIQUID SLOSHING IN FLEXIBLE CONTAINERS, PART 1: TUNING CONTAINER FLEXIBILITY FOR SLOSHING CONTROL

LIQUID SLOSHING IN FLEXIBLE CONTAINERS, PART 1: TUNING CONTAINER FLEXIBILITY FOR SLOSHING CONTROL Fifth International Conference on CFD in the Process Industries CSIRO, Melbourne, Australia 13-15 December 26 LIQUID SLOSHING IN FLEXIBLE CONTAINERS, PART 1: TUNING CONTAINER FLEXIBILITY FOR SLOSHING CONTROL

More information

Directivity Loss at a Duct Termination

Directivity Loss at a Duct Termination Directivity Loss at a Duct Termination Daniel Potente, Stephen Gauld and Athol Day Day Design Pty Ltd, Acoustical Consultants, Sydney, Australia www.daydesign.com.au ABSTRACT This paper investigates the

More information

Numerical Study of a High Head Francis Turbine with Measurements from the Francis-99 Project

Numerical Study of a High Head Francis Turbine with Measurements from the Francis-99 Project Journal of Physics: Conference Series OPEN ACCESS Numerical Study of a High Head Francis Turbine with Measurements from the Francis-99 Project To cite this article: H Wallimann and R Neubauer 2015 J. Phys.:

More information

Development of a reactive silencer for turbocompressors

Development of a reactive silencer for turbocompressors Development of a reactive silencer for turbocompressors N. González Díez, J.P.M. Smeulers, D. Meulendijks 1 S. König TNO Heat Transfer & Fluid Dynamics Siemens AG Energy Sector The Netherlands Duisburg/Germany

More information

Particle Image Velocimetry

Particle Image Velocimetry Markus Raffel Christian E. Willert Steve T. Wereley Jiirgen Kompenhans Particle Image Velocimetry A Practical Guide Second Edition With 288 Figures and 42 Tables < J Springer Contents Preface V 1 Introduction

More information

Visualization of Shock Waves by using Schlieren Technique

Visualization of Shock Waves by using Schlieren Technique Lab # 3 Visualization of Shock Waves by using Schlieren Technique Objectives: 1. To get hands-on experiences about Schlieren technique for flow visualization. 2. To learn how to do the optics alignment

More information

The Effects of Meter Orientation Downstream of a Short Radius Elbow on Electromagnetic Flow Meters

The Effects of Meter Orientation Downstream of a Short Radius Elbow on Electromagnetic Flow Meters Utah State University DigitalCommons@USU All Graduate Theses and Dissertations Graduate Studies 2016 The Effects of Meter Orientation Downstream of a Short Radius Elbow on Electromagnetic Flow Meters Jared

More information

Characterization and Validation of Acoustic Cavities of Automotive Vehicles

Characterization and Validation of Acoustic Cavities of Automotive Vehicles Characterization and Validation of Acoustic Cavities of Automotive Vehicles John G. Cherng and Gang Yin R. B. Bonhard Mark French Mechanical Engineering Department Ford Motor Company Robert Bosch Corporation

More information

ACOUSTIC BEHAVIOR OF MULTIPHASE FLOW CONDITIONS IN A VERTICAL WELL

ACOUSTIC BEHAVIOR OF MULTIPHASE FLOW CONDITIONS IN A VERTICAL WELL ACOUSTIC BEHAVIOR OF MULTIPHASE FLOW CONDITIONS IN A VERTICAL WELL An Undergraduate Research Scholars Thesis by NURAMIRAH MUSLIM Submitted to Honors and Undergraduate Research Texas A&M University in partial

More information

ECOACCESS GUIDELINE FOR THE ASSESSMENT OF LOW FREQUENCY NOISE

ECOACCESS GUIDELINE FOR THE ASSESSMENT OF LOW FREQUENCY NOISE ECOACCESS GUIDELINE FOR THE ASSESSMENT OF LOW FREQUENCY NOISE Cedric Roberts Environmental Operations, Integrated Assessment, Queensland Environmental Protection Agency, 160 Ann Street, Brisbane, Queensland,

More information

CHAPTER 5 FAULT DIAGNOSIS OF ROTATING SHAFT WITH SHAFT MISALIGNMENT

CHAPTER 5 FAULT DIAGNOSIS OF ROTATING SHAFT WITH SHAFT MISALIGNMENT 66 CHAPTER 5 FAULT DIAGNOSIS OF ROTATING SHAFT WITH SHAFT MISALIGNMENT 5.1 INTRODUCTION The problem of misalignment encountered in rotating machinery is of great concern to designers and maintenance engineers.

More information

A SYSTEM IMPLEMENTATION OF AN ACTIVE NOISE CONTROL SYSTEM COMBINED WITH PASSIVE SILENCERS FOR IMPROVED NOISE REDUCTION IN DUCTS SUMMARY INTRODUCTION

A SYSTEM IMPLEMENTATION OF AN ACTIVE NOISE CONTROL SYSTEM COMBINED WITH PASSIVE SILENCERS FOR IMPROVED NOISE REDUCTION IN DUCTS SUMMARY INTRODUCTION A SYSTEM IMPLEMENTATION OF AN ACTIVE NOISE CONTROL SYSTEM COMBINED WITH PASSIVE SILENCERS FOR IMPROVED NOISE REDUCTION IN DUCTS Martin LARSSON, Sven JOHANSSON, Lars HÅKANSSON, Ingvar CLAESSON Blekinge

More information

Validation of the Experimental Setup for the Determination of Transmission Loss of Known Reactive Muffler Model by Using Finite Element Method

Validation of the Experimental Setup for the Determination of Transmission Loss of Known Reactive Muffler Model by Using Finite Element Method Validation of the Experimental Setup for the etermination of Transmission Loss of Known Reactive Muffler Model by Using Finite Element Method M.B. Jadhav, A. P. Bhattu Abstract: The expansion chamber is

More information

Wavelet Transform for Bearing Faults Diagnosis

Wavelet Transform for Bearing Faults Diagnosis Wavelet Transform for Bearing Faults Diagnosis H. Bendjama and S. Bouhouche Welding and NDT research centre (CSC) Cheraga, Algeria hocine_bendjama@yahoo.fr A.k. Moussaoui Laboratory of electrical engineering

More information

8th AIAA/CEAS Aeroacoustics Conference June 16 18, 2002/Breckenridge, CO

8th AIAA/CEAS Aeroacoustics Conference June 16 18, 2002/Breckenridge, CO AIAA 22-2416 Noise Transmission Characteristics of Damped Plexiglas Windows Gary P. Gibbs, Ralph D. Buehrle, Jacob Klos, Sherilyn A. Brown NASA Langley Research Center, Hampton, VA 23681 8th AIAA/CEAS

More information

CFD Simulation on Forced Air Cooled Dry-type Transformers. W. WU ABB Inc. USA

CFD Simulation on Forced Air Cooled Dry-type Transformers. W. WU ABB Inc. USA 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2016 Grid of the Future Symposium CFD Simulation on Forced Air Cooled Dry-type Transformers W. WU ABB Inc. USA SUMMARY

More information

2013 Assessment Report. Design and Visual Communication (DVC) Level 2

2013 Assessment Report. Design and Visual Communication (DVC) Level 2 National Certificate of Educational Achievement 2013 Assessment Report Design and Visual Communication (DVC) Level 2 91337 Use visual communication techniques to generate design ideas. 91338 Produce working

More information

AD-A 'L-SPv1-17

AD-A 'L-SPv1-17 APPLIED RESEARCH LABORATORIES.,THE UNIVERSITY OF TEXAS AT AUSTIN P. 0. Box 8029 Aujn. '"X.zs,37 l.3-s029( 512),35-i2oT- FA l. 512) i 5-259 AD-A239 335'L-SPv1-17 &g. FLECTE Office of Naval Research AUG

More information

PIV STUDY OF STANDING WAVES IN A RESONANT AIR COLUMN

PIV STUDY OF STANDING WAVES IN A RESONANT AIR COLUMN PIV STUDY OF STANDING WAVES IN A RESONANT AIR COLUMN Pacs: 43.58.Fm, 43.20.Ye, 43.20.Ks Tonddast-Navaei, Ali; Sharp, David Open University Department of Environmental and Mechanical Engineering, Open University,

More information

Tangential Fans - Basic principles. Expertise, performance, innovation

Tangential Fans - Basic principles. Expertise, performance, innovation Tangential Fans - Basic principles Expertise, performance, innovation Fans 1 Stove jacket cooling, storage heaters, wood-burning stoves, underfloor convectors, tanning beds, air conditioners and heaters

More information

Module 1: Introduction to Experimental Techniques Lecture 2: Sources of error. The Lecture Contains: Sources of Error in Measurement

Module 1: Introduction to Experimental Techniques Lecture 2: Sources of error. The Lecture Contains: Sources of Error in Measurement The Lecture Contains: Sources of Error in Measurement Signal-To-Noise Ratio Analog-to-Digital Conversion of Measurement Data A/D Conversion Digitalization Errors due to A/D Conversion file:///g /optical_measurement/lecture2/2_1.htm[5/7/2012

More information

Simulation of Cylindrical Resonator with Spiral Neck and Straight Neck to Attenuate the Low Frequency Noise of Muffler

Simulation of Cylindrical Resonator with Spiral Neck and Straight Neck to Attenuate the Low Frequency Noise of Muffler Simulation of Cylindrical Resonator with Spiral Neck and Straight Neck to Attenuate the Low Frequency Noise of Muffler Dr. Amit Kumar Gupta 1 Devesh Kumar Ratnavat 2 1 Mechanical Engineering Department,

More information

EXPERIMENTS ON PERFORMANCES OF ACTIVE-PASSIVE HYBRID MUFFLERS

EXPERIMENTS ON PERFORMANCES OF ACTIVE-PASSIVE HYBRID MUFFLERS EXPERIMENTS ON PERFORMANCES OF ACTIVE-PASSIVE HYBRID MUFFLERS Hongling Sun, Fengyan An, Ming Wu and Jun Yang Key Laboratory of Noise and Vibration Research, Institute of Acoustics, Chinese Academy of Sciences,

More information

Acoustic Filter Copyright Ultrasonic Noise Acoustic Filters

Acoustic Filter Copyright Ultrasonic Noise Acoustic Filters OVERVIEW Ultrasonic Noise Acoustic Filters JAMES E. GALLAGHER, P.E. Savant Measurement Corporation Kingwood, TX USA The increasing use of Multi-path ultrasonic meters for natural gas applications has lead

More information

Proceedings of Meetings on Acoustics

Proceedings of Meetings on Acoustics Proceedings of Meetings on Acoustics Volume 19, 2013 http://acousticalsociety.org/ ICA 2013 Montreal Montreal, Canada 2-7 June 2013 Engineering Acoustics Session 1pEAa: Active and Passive Control of Fan

More information

Appendix 8. Draft Post Construction Noise Monitoring Protocol

Appendix 8. Draft Post Construction Noise Monitoring Protocol Appendix 8 Draft Post Construction Noise Monitoring Protocol DRAFT CPV Valley Energy Center Prepared for: CPV Valley, LLC 50 Braintree Hill Office Park, Suite 300 Braintree, Massachusetts 02184 Prepared

More information

Improvements to the Two-Thickness Method for Deriving Acoustic Properties of Materials

Improvements to the Two-Thickness Method for Deriving Acoustic Properties of Materials Baltimore, Maryland NOISE-CON 4 4 July 2 4 Improvements to the Two-Thickness Method for Deriving Acoustic Properties of Materials Daniel L. Palumbo Michael G. Jones Jacob Klos NASA Langley Research Center

More information

REPORT DOCUMENTATION PAGE

REPORT DOCUMENTATION PAGE REPORT DOCUMENTATION PAGE Form Approved OMB NO. 0704-0188 The public reporting burden for this collection of information is estimated to average 1 hour per response, including the time for reviewing instructions,

More information

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE Copyright SFA - InterNoise 2000 1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 7.2 MICROPHONE T-ARRAY

More information

ECMA-74. Measurement of Airborne Noise emitted by Information Technology and Telecommunications Equipment. 15 th Edition / June 2018

ECMA-74. Measurement of Airborne Noise emitted by Information Technology and Telecommunications Equipment. 15 th Edition / June 2018 ECMA-74 15 th Edition / June 2018 Measurement of Airborne Noise emitted by Information Technology and Telecommunications Equipment Reference number ECMA-123:2009 Ecma International 2009 COPYRIGHT PROTECTED

More information

University of Houston Master Construction Specifications Insert Project Name SECTION MECHANICAL SCOPE OF WORK PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION MECHANICAL SCOPE OF WORK PART 1 - GENERAL SECTION 23 00 10 - MECHANICAL SCOPE OF WORK PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01

More information

Noise from Pulsating Supercavities Prepared by:

Noise from Pulsating Supercavities Prepared by: Noise from Pulsating Supercavities Prepared by: Timothy A. Brungart Samuel E. Hansford Jules W. Lindau Michael J. Moeny Grant M. Skidmore Applied Research Laboratory The Pennsylvania State University Flow

More information

Copyright 2017 by Turbomachinery Laboratory, Texas A&M Engineering Experiment Station

Copyright 2017 by Turbomachinery Laboratory, Texas A&M Engineering Experiment Station HIGH FREQUENCY VIBRATIONS ON GEARS 46 TH TURBOMACHINERY & 33 RD PUMP SYMPOSIA Dietmar Sterns Head of Engineering, High Speed Gears RENK Aktiengesellschaft Augsburg, Germany Dr. Michael Elbs Manager of

More information

LOCALIZATION OF WIND TURBINE NOISE SOURCES USING A COMPACT MICROPHONE ARRAY WITH ADVANCED BEAMFORMING ALGORITHMS

LOCALIZATION OF WIND TURBINE NOISE SOURCES USING A COMPACT MICROPHONE ARRAY WITH ADVANCED BEAMFORMING ALGORITHMS BeBeC-2012-25 LOCALIZATION OF WIND TURBINE NOISE SOURCES USING A COMPACT MICROPHONE ARRAY WITH ADVANCED BEAMFORMING ALGORITHMS Rakesh C. Ramachandran, Hirenkumar Patel and Ganesh Raman Fluid Dynamic Research

More information

A Study on Correlation of AE Signals from Different AE Sensors in Valve Leakage Rate Detection

A Study on Correlation of AE Signals from Different AE Sensors in Valve Leakage Rate Detection A Study on Correlation of AE Signals from Different AE Sensors in Valve Leakage Rate Detection 113 A Study on Correlation of AE Signals from Different AE Sensors in Valve Leakage Rate Detection Watit Kaewwaewnoi

More information

CREATING OF EXPERIMENTAL ACOUSTIC DATABASE FOR AN ISOLATED HELICOPTER`S MAIN ROTOR

CREATING OF EXPERIMENTAL ACOUSTIC DATABASE FOR AN ISOLATED HELICOPTER`S MAIN ROTOR CREATING OF EXPERIMENTAL ACOUSTIC DATABASE FOR AN ISOLATED HELICOPTER`S MAIN ROTOR G.N. Barakos 1, A.S. Batrakov 2, A.N. Bozhenko 2, L.I. Garipova 2, A.N. Kusuymov 2, S.A. Michailov 2, V.V. Pakhov 2, R.P.

More information

Review of splitter silencer modeling techniques

Review of splitter silencer modeling techniques Review of splitter silencer modeling techniques Mina Wagih Nashed Center for Sound, Vibration & Smart Structures (CVS3), Ain Shams University, 1 Elsarayat St., Abbaseya 11517, Cairo, Egypt. mina.wagih@eng.asu.edu.eg

More information

Technical Approach for Preventing Thermal Distortion in Machine Tools

Technical Approach for Preventing Thermal Distortion in Machine Tools TECHNICAL REPORT Technical Approach for Preventing Thermal Distortion in Machine Tools Y. KUBO Thermal distortion in machine tools greatly affects the dimensional tolerances of workpieces and causes various

More information

Investigating High Frequency Magnetic Activity During Local Helicity Injection on the PEGASUS Toroidal Experiment

Investigating High Frequency Magnetic Activity During Local Helicity Injection on the PEGASUS Toroidal Experiment Investigating High Frequency Magnetic Activity During Local Helicity Injection on the PEGASUS Toroidal Experiment Nathan J. Richner M.W. Bongard, R.J. Fonck, J.L. Pachicano, J.M. Perry, J.A. Reusch 59

More information

Feedback Systems in HVAC ASHRAE Distinguished Lecture Series Jim Coogan Siemens Building Technologies

Feedback Systems in HVAC ASHRAE Distinguished Lecture Series Jim Coogan Siemens Building Technologies Feedback Systems in HVAC ASHRAE Distinguished Lecture Series Jim Coogan Siemens Building Technologies ASHRAE, Madison Chapter October, 2014 Agenda Definitions: feedback and closed-loop control Types of

More information

PWM. Design, Installation, and Operation. (Pulse Width Modulation Zone Controller)

PWM. Design, Installation, and Operation. (Pulse Width Modulation Zone Controller) Small Duct Heating, Cooling and Indoor Air Quality Systems www.hi-velocity.com TM PWM (Pulse Width Modulation Zone Controller) Design, Installation, and Operation Includes: PWM Design PWM Installation

More information

ECMA-74. Measurement of Airborne Noise emitted by Information Technology and Telecommunications Equipment. 12 th Edition / December 2012

ECMA-74. Measurement of Airborne Noise emitted by Information Technology and Telecommunications Equipment. 12 th Edition / December 2012 ECMA-74 12 th Edition / December 2012 Measurement of Airborne Noise emitted by Information Technology and Telecommunications Equipment Reference number ECMA-123:2009 Ecma International 2009 COPYRIGHT PROTECTED

More information

Understanding How Frequency, Beam Patterns of Transducers, and Reflection Characteristics of Targets Affect the Performance of Ultrasonic Sensors

Understanding How Frequency, Beam Patterns of Transducers, and Reflection Characteristics of Targets Affect the Performance of Ultrasonic Sensors Characteristics of Targets Affect the Performance of Ultrasonic Sensors By Donald P. Massa, President and CTO of Massa Products Corporation Overview of How an Ultrasonic Sensor Functions Ultrasonic sensors

More information

Welcome Contents Back 1

Welcome Contents Back 1 Welcome Contents Back 1 Active silencers for air-conditioning units P. Leistner, H.V. Fuchs 1. Introduction The noise emission of air-conditioning units can be reduced directly at the fan during the design

More information

Proceedings of Meetings on Acoustics

Proceedings of Meetings on Acoustics Proceedings of Meetings on Acoustics Volume 19, 2013 http://acousticalsociety.org/ ICA 2013 Montreal Montreal, Canada 2-7 June 2013 Physical Acoustics Session 4aPA: Nonlinear Acoustics I 4aPA8. Radiation

More information

A cellular automaton for urban traffic noise

A cellular automaton for urban traffic noise A cellular automaton for urban traffic noise E. Salomons TNO Science and Industry, Stieljesweg 1, 2628CK Delft, Netherlands erik.salomons@tno.nl 6545 Propagation of traffic noise in a city is a complex

More information

Performance Data. Single Deflection Register, DDFRSDS 5 Double Deflection Register, DDFRDDS 5

Performance Data. Single Deflection Register, DDFRSDS 5 Double Deflection Register, DDFRDDS 5 An enterpise of United McGill Corporation Founded in 1951 Single Deflection Register, DDFRSDS 5 Double Deflection Register, DDFRDDS 5 Average discharge velocity (fpm) 300 400 500 600 700 800 900 1000 1100

More information

WITHIN GENERATOR APPLICATIONS

WITHIN GENERATOR APPLICATIONS POWER SYSTEMS TOPICS 9 Measuring and Understanding Sound WITHIN GENERATOR APPLICATIONS INTRODUCTION When selecting a generator, there are many factors to consider so as not to negatively impact the existing

More information

Comparison of Transmissibility of Non-Metallic Materials For Vibration Isolation

Comparison of Transmissibility of Non-Metallic Materials For Vibration Isolation IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X PP. 57-61 www.iosrjournals.org Comparison of Transmissibility of Non-Metallic Materials For Vibration A.

More information

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards The Solo, Select and Sync PWM boards provide a pulse-width modulated (PWM) signal to the EC motor to control fan speed.

More information

A System to Measure Instantaneous Compressor Crankshaft Speed

A System to Measure Instantaneous Compressor Crankshaft Speed Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 972 A System to Measure Instantaneous Compressor Crankshaft Speed R. R. McConnell Purdue

More information

Technical Development Program

Technical Development Program Technical Development Program COMMERCIAL DISTRIBUTION SYSTEMS PRESENTED BY: Ray Chow Duct Design Level 1 Fundamentals Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Introduction

More information

ACTIVE LOW-FREQUENCY MODAL NOISE CANCELLA- TION FOR ROOM ACOUSTICS: AN EXPERIMENTAL STUDY

ACTIVE LOW-FREQUENCY MODAL NOISE CANCELLA- TION FOR ROOM ACOUSTICS: AN EXPERIMENTAL STUDY ACTIVE LOW-FREQUENCY MODAL NOISE CANCELLA- TION FOR ROOM ACOUSTICS: AN EXPERIMENTAL STUDY Xavier Falourd, Hervé Lissek Laboratoire d Electromagnétisme et d Acoustique, Ecole Polytechnique Fédérale de Lausanne,

More information

Modeling Physical PCB Effects 5&

Modeling Physical PCB Effects 5& Abstract Getting logical designs to meet specifications is the first step in creating a manufacturable design. Getting the physical design to work is the next step. The physical effects of PCB materials,

More information

ACOUSTIC PROPERTIES OF THE VIRGINIA TECH STABILITY WIND TUNNEL

ACOUSTIC PROPERTIES OF THE VIRGINIA TECH STABILITY WIND TUNNEL ACOUSTIC PROPERTIES OF THE VIRGINIA TECH STABILITY WIND TUNNEL December 6th, 1999 Jon Vegard Larssen and William J. Devenport Department of Aerospace and Ocean Engineering Virginia Polytechnic Institute

More information

Resonant characteristics of flow pulsation in pipes due to swept sine constraint

Resonant characteristics of flow pulsation in pipes due to swept sine constraint TRANSACTIONS OF THE INSTITUTE OF FLUID-FLOW MACHINERY No. 133, 2016, 131 144 Tomasz Pałczyński Resonant characteristics of flow pulsation in pipes due to swept sine constraint Institute of Turbomachinery,

More information

From concert halls to noise barriers : attenuation from interference gratings

From concert halls to noise barriers : attenuation from interference gratings From concert halls to noise barriers : attenuation from interference gratings Davies, WJ Title Authors Type URL Published Date 22 From concert halls to noise barriers : attenuation from interference gratings

More information

NVH analysis of a 3 phase 12/8 SR motor drive for HEV applications

NVH analysis of a 3 phase 12/8 SR motor drive for HEV applications NVH analysis of a 3 phase 12/8 SR motor drive for HEV applications Mathieu Sarrazin 1, Steven Gillijns 1, Jan Anthonis 1, Karl Janssens 1, Herman van der Auweraer 1, Kevin Verhaeghe 2 1 LMS, a Siemens

More information

Experimental round robin evaluation of structure borne sound source force power test methods

Experimental round robin evaluation of structure borne sound source force power test methods Experimental round robin evaluation of structure borne sound source force power test methods Lai, HK, Moorhouse, AT and Gibbs, BM http://dx.doi.org/10.3397/1/376369 Title Authors Type URL Experimental

More information

MEASURING SOUND INSULATION OF BUILDING FAÇADES: INTERFERENCE EFFECTS, AND REPRODUCIBILITY

MEASURING SOUND INSULATION OF BUILDING FAÇADES: INTERFERENCE EFFECTS, AND REPRODUCIBILITY MEASURING SOUND INSULATION OF BUILDING FAÇADES: INTERFERENCE EFFECTS, AND REPRODUCIBILITY U. Berardi, E. Cirillo, F. Martellotta Dipartimento di Architettura ed Urbanistica - Politecnico di Bari, via Orabona

More information

Vibration Tests: a Brief Historical Background

Vibration Tests: a Brief Historical Background Sinusoidal Vibration: Second Edition - Volume 1 Christian Lalanne Copyright 0 2009, ISTE Ltd Vibration Tests: a Brief Historical Background The first studies on shocks and vibrations were carried out at

More information

Section 7 - Measurement of Transient Pressure Pulses

Section 7 - Measurement of Transient Pressure Pulses Section 7 - Measurement of Transient Pressure Pulses Special problems are encountered in transient pressure pulse measurement, which place stringent requirements on the measuring system. Some of these

More information

Abstract of PhD Thesis

Abstract of PhD Thesis FACULTY OF ELECTRONICS, TELECOMMUNICATION AND INFORMATION TECHNOLOGY Irina DORNEAN, Eng. Abstract of PhD Thesis Contribution to the Design and Implementation of Adaptive Algorithms Using Multirate Signal

More information

NEW YORK STATE TEACHER CERTIFICATION EXAMINATIONS

NEW YORK STATE TEACHER CERTIFICATION EXAMINATIONS NEW YORK STATE TEACHER CERTIFICATION EXAMINATIONS TEST DESIGN AND FRAMEWORK June 2018 Authorized for Distribution by the New York State Education Department This test design and framework document is designed

More information

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE Copyright SFA - InterNoise 2000 1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 4.1 INVESTIGATIONS

More information

High Performance Blower San Ace B97 9BMC Type

High Performance Blower San Ace B97 9BMC Type New Products Introduction High Performance Blower San Ace B97 9BMC Type Munenori Takakuwa Toshiya Nishizawa Akira Nakayama Koji Ono Hiromitsu Kuribayashi 1. Introduction Thanks to its compact design and

More information

Texture characterization in DIRSIG

Texture characterization in DIRSIG Rochester Institute of Technology RIT Scholar Works Theses Thesis/Dissertation Collections 2001 Texture characterization in DIRSIG Christy Burtner Follow this and additional works at: http://scholarworks.rit.edu/theses

More information

Sunlight Supply, Inc.

Sunlight Supply, Inc. FCC Part 18 Subpart C Non-Consumer For RF Lighting Equipment Electromagnetic Compatibility Test Report Sunlight Supply, Inc. Commercial Ballast 1000 Watt - July 18, 2017 Tests Conducted by:, LLC 20811

More information

Acoustic resolution. photoacoustic Doppler velocimetry. in blood-mimicking fluids. Supplementary Information

Acoustic resolution. photoacoustic Doppler velocimetry. in blood-mimicking fluids. Supplementary Information Acoustic resolution photoacoustic Doppler velocimetry in blood-mimicking fluids Joanna Brunker 1, *, Paul Beard 1 Supplementary Information 1 Department of Medical Physics and Biomedical Engineering, University

More information

Experimental Investigation of Unsteady Pressure on an Axial Compressor Rotor Blade Surface

Experimental Investigation of Unsteady Pressure on an Axial Compressor Rotor Blade Surface Energy and Power Engineering, 2010, 2, 131-136 doi:10.4236/epe.2010.22019 Published Online May 2010 (http://www. SciRP.org/journal/epe) 131 Experimental Investigation of Unsteady Pressure on an Axial Compressor

More information

PIV Measurements of Flow immediately above Woven Fabrics

PIV Measurements of Flow immediately above Woven Fabrics PIV Measurements of Flow immediately above Woven Fabrics Haiya Peng Master of Applied Science in Mechanical Engineering University of British Columbia May 4, 2011 PaperCon 2011 Page 2158 Introduction Paper

More information

Design of a Line Array Point Source Loudspeaker System

Design of a Line Array Point Source Loudspeaker System Design of a Line Array Point Source Loudspeaker System -by Charlie Hughes 6430 Business Park Loop Road Park City, UT 84098-6121 USA // www.soundtube.com // 435.647.9555 22 May 2013 Charlie Hughes The Design

More information