Control of a Dynamic Voltage Restorer to compensate single phase voltage sags

Size: px
Start display at page:

Download "Control of a Dynamic Voltage Restorer to compensate single phase voltage sags"

Transcription

1 Control of a Dynamic Voltage Restorer to compensate single phase voltage sags M.V.Kasuni Perera Master of Science Thesis Stockholm, Sweden 2007

2 Acknowledgement I would like to express my sincere appreciation to my local supervisors, Dr. Sanath Alahakoon and Dr. Atputharajah Arulampalam of Electrical and Electronic Engineering Department of University of Peradeniya, Sri Lanka for their guidance and support provided during the period of my Master thesis project and also for the constructive comments they made by reviewing final manuscript of the report. Further would like to express my sincere appreciation to Dr. Arulampalam Atputharajah for his persistence in keeping me on the schedule. Also would like to thank Professor Mehrdad Ghandhari at Department of Electrical Engineering at KTH, Sweden for allowing me to do my master thesis project in my own country and Dr. Sanath Alahakoon who coordinated it from Sri Lanka end. Also I wish to thank the supervisors at KTH, Department of Electrical Engineering, Professor Mehrdad Ghandhari and Mr. Daniel Salomonsson for their guidance and valuable suggestions send to me to improve the quality of the master thesis report. The author gratefully acknowledges the support given by Department of Electrical & Electronic Engineering, University of Peradeniya Sri Lanka. And also for the Post Graduate Institute of the same Department for permitting me to carry out my Master thesis research. Thanks are due to President s Fund of Sri Lanka, who has granted me with a Scholarship to complete the Masters Degree in Electrical Engineering. Finally I would like to thank all my colleagues both in Sweden & Sri Lanka, my parents for their continuous encouragement. December i

3 Abstract Quality of the output power delivered from the utilities has become a major concern of the modern industries for the last decade. These power quality associated problems are voltage sag, surge, flicker, voltage imbalance, interruptions and harmonic problems. These power quality issues may cause problems to the industries ranging from malfunctioning of equipments to complete plant shut downs. Those power quality problems affect the microprocessor based loads, process equipments, sensitive electric components which are highly sensitive to voltage level fluctuations. It has been identified that power quality can be degraded both due to utility side abnormalities as well as the customer side abnormalities. To overcome the problems caused by customer side abnormalities so called custom power devices are connected closer to the load end. One such reliable customer power device used to address the voltage sag, swell problem is the Dynamic Voltage Restorer (DVR). It is a series connected custom power device, which is considered to be a cost effective alternative when compared with other commercially available voltage sag compensation devices. The main function of the DVR is to monitor the load voltage waveform constantly and if any sag or surge occurs, the balance (or excess) voltage is injected to (or absorbed from) the load voltage. To achieve the above functionality a reference voltage waveform has to be created which is similar in magnitude and phase angle to that of the supply voltage. Thereby during any abnormality of the voltage waveform it can be detected by comparing the reference and the actual voltage waveforms. A new control technique to detect and compensate for the single phase voltage sags is designed in this project. The simulation was checked in the EMTDC/PSCAD simulation software and has shown reliable results. ii

4 Contents Acknowledgement. i Abstract. ii Contents. iii List of abbreviations. v List of tables and figures. vi Chapter 1 Introduction. 1 Chapter 2 Literature Review 2.1 Power quality related problems in the distribution network Structure of the DVR DVR operating states DVR compensation Techniques Control techniques used in commercially available DVRs 20 Chapter 3 New control technique developed for single phase voltage sags 3.1 Background Simplified control block diagram PSCAD Implementation of control circuit PSCAD Implementation of power circuit 45 Chapter 4 Results and discussion of PECC 4.1 System System System System System 5 82 iii

5 4.6 System System Analysis of simulation results during different time intervals 88 Chapter 5 Conclusion 93 Chapter 6 Further developments and limitations 94 References.. 96 List of publications. 101 iv

6 List of Abbreviations DVR - Dynamic Voltage Restorer UPS - Uninterruptible Power Supplies V s - Supply voltage (V) A meas - Phase angle of the supply voltage (rad) V ref - Reference voltage (V) A ref - Phase angle of the reference voltage (rad) V control - Control voltage (V) U pre-sag - Pre-sag voltage (V) U sag - Sag voltage (V) U DVR - Voltage injected by the DVR (V) I load - Load current (A) ZCD - Zero crossing point detector Tri - Triangular waveform P top - Switching signal for the top inverter leg P bot - Switching signal for the bottom inverter leg v

7 List of tables and figures Table 2.1 : IEEE definitions for the voltage sags and swells Table 3.1 : Harmonic content in the normal supply voltage Table 4.2 : Different sag and load criteria Figure 2.1 : Different types of voltage sags Figure 2.2 : (a & b ) Basic operation of DVR (left) and APF (right) Figure 2.3 : DVR Power circuit Figure 2.4 : Three phase Graetz bridge and its switching arrangements Figure 2.5 : NPC inverter configuration and its switching arrangement Figure 2.6 : H-bridge inverter configuration and its switching arrangement Figure 2.7 : Different filter placements Figure 2.8 : Connection methods for the primary side of the injection transformer Figure 2.9 : Simple power system with a DVR Figure 2.10 : Pre-sag compensation technique Figure 2.11 : In-phase compensation technique Figure 2.12 : Energy optimization technique Figure 2.13 : Combining both pre-sag and in-phase compensation techniques Figure 2.14 : Simplified block diagram of a phase locked loop Figure 2.15 : Block diagram of a Software Phase Locked Loop Figure 2.16 : Simplified phasor representation of SPLL Figure 3.1 : Simplified control block diagram for the single phase DVR Figure 3.2 : Implementation method of block 1 Figure 3.3 : PSCAD implementation of block 1 Figure 3.4 : Integrator clear signal generation Figure 3.5 : Integrator clear signal Figure 3.6 : Phase angle variation of the supply voltage Figure 3.7 : Output waveforms at different output channels Figure 3.8 : Input waveform to the resettable integrator Figure 3.9 : Simulation block for the reference phase angle wave form generation vi

8 Figure 3.10 : Simplified diagram of control block 2 Figure 3.11 : Generation of angle error signal Figure 3.11 : additional block to obtain the angle error Figure 3.12 : Specifications of the comparator block Figure 3.13 : Angle error calculation Figure 3.14 : User defined parameters in the PI controller Figure 3.15 : Synchronization process Figure 3.16 : Left: Reference waveform generation & Right: Comparator specifications Figure 3.17 : Reference voltage waveform generation Figure 3.18 : Simulation block for reference voltage waveform generation Figure 3.19 : Control voltage waveform before the voltage sag Figure 3.19 : (bottom left) Control voltage waveform during the sag (in phase voltage sag) Figure 3.19 : (bottom right) Control voltage waveform during the sag (voltage sag is created with a phase shift) Figure 3.20 : Simulation block 4 Figure 3.21 : Power circuit of the DVR Figure 3.22 : Equivalent circuit of DVR power circuit Figure 3.23 : Equivalent circuit used for parameter estimation Figure 3.24 : Inverter leg switching signal generation Figure 3.25 : Switching signals for inverter legs Figure 3.26 : Low pass filter configuration Figure 3.27 : Configuration data of the voltage injection transformer Figure 3.28 : Left: Generating voltage sag for the power circuit Right: Breaker parameters Figure 3.29 : Equivalent circuit for the distribution line Figure 3.40 : Equivalent circuit before the voltage sag Figure 3.41 : Equivalent circuit during the voltage sag Figure 3.42 : Supply voltage waveform with and without harmonics Figure 3.43 : PSCAD implementation of supply harmonics Figure 4.1 : Control circuit simulation block diagram Figure 4.2 : Power circuit of the DVR Figure 4.3 : Voltage waveforms for system 1 during synchronization vii

9 Figure 4.4 Figure 4.5 Figure 4.6 Figure 4.7 Figure 4.8 Figure 4.9 Figure 4.10 Figure 4.20 Figure 4.21 Figure 4.22 Figure 4.23 Figure 4.24 Figure 4.25 Figure 4.26 Figure 4.27 Figure 4.28 Figure 4.29 Figure 4.30 Figure 4.31 Figure 4.32 Figure 4.33 Figure 4.34 Figure 4.35 Figure 4.36 Figure 4.37 Figure 4.38 Figure 4.39 Figure 4.40 Figure 4.41 Figure 4.42 Figure 4.43 Figure 4.44 Figure 4.45 Figure 4.46 : Voltage waveforms for system 1 when the DVR is engaged : Voltage waveforms for subsystem 1a during the neighborhood of sag : Voltage waveforms for subsystem 1a during the sag : Voltage waveforms for subsystem 1b during the neighborhood of sag : Voltage waveforms for subsystem 1b during the sag : Voltage waveforms for subsystem 1b during the neighborhood of sag : Voltage waveforms for subsystem 1b during the sag : Voltage waveforms for subsystem 2c during the sag : Voltage waveforms for subsystem 2d during the neighborhood of sag : Voltage waveforms for subsystem 2d during the sag : Voltage waveforms for system 3 during synchronization : Voltage waveforms for system 3 when the DVR is engaged : Voltage waveforms for subsystem 3a during the neighborhood of sag : Voltage waveforms for subsystem 3a during the sag : Voltage waveforms for subsystem 3b during the neighborhood of sag : Voltage waveforms for subsystem 3b during the sag : Voltage waveforms for subsystem 3c during the neighborhood of sag : Voltage waveforms for subsystem 3c during the sag : Voltage waveforms for subsystem 3d during the neighborhood of sag : Voltage waveforms for subsystem 3d during the sag : Voltage waveforms for system 4 during synchronization : Voltage waveforms for system 4 when the DVR is engaged : Voltage waveforms for subsystem 4a during the neighborhood of sag : Voltage waveforms for subsystem 4b during the sag : Voltage waveforms for subsystem 4b during the neighborhood of sag : Voltage waveforms for subsystem 4b during the sag : Voltage waveforms for subsystem 4c during the neighborhood of sag : Voltage waveforms for subsystem 4c during the sag : Voltage waveforms for subsystem 4d during the neighborhood of sag : Voltage waveforms for subsystem 4d during the sag : Voltage waveforms for subsystem 5a during the neighborhood of sag : Voltage waveforms for subsystem 5b during the neighborhood of sag : Voltage waveforms for subsystem 5c during the neighborhood of sag : Voltage waveforms for subsystem 5d during the neighborhood of sag viii

10 Figure 4.47 : Voltage waveforms for subsystem 6a during the neighborhood of sag Figure 4.48 : Voltage waveforms for subsystem 6b during the neighborhood of sag Figure 4.49 : Voltage waveforms for subsystem 6c during the neighborhood of sag Figure 4.50 : Voltage waveforms for subsystem 6d during the neighborhood of sag Figure 4.51 : Voltage waveforms for subsystem 7a during the neighborhood of sag Figure 4.52 : Voltage waveforms for subsystem 7b during the neighborhood of sag Figure 4.53 : Voltage waveforms for subsystem 7c during the neighborhood of sag Figure 4.54 : Voltage waveforms for subsystem 7d during the neighborhood of sag Figure 4.55 : Project settings window for system 1 Figure 4.56 : Top : Simulation of subsystem 1a with 0.9μs step time Bottom : Simulation of subsystem 1a with 1μs step time ix

11 Chapter 1 Introduction The technological advancements have proven a path to the modern industries to extract and develop the innovative technologies within the limits of their industries for the fulfillment of their industrial goals. And their ultimate objective is to optimize the production while minimizing the production cost and thereby achieving maximized profits while ensuring continuous production throughout the period. As such a stable supply of un-interruptible power has to be guaranteed during the production process. The reason for demanding high quality power is basically the modern manufacturing and process equipment, which operates at high efficiency, requires high quality defect free power supply for the successful operation of their machines [1]. More precisely most of those machine components are designed to be very sensitive for the power supply variations. Adjustable speed drives, automation devices, power electronic components are examples for such equipments [2,3]. Failure to provide the required quality power output may sometimes cause complete shutdown of the industries which will make a major financial loss to the industry concerned [4,5,6]. Thus the industries always demands for high quality power from the supplier or the utility. But the blame due to degraded quality cannot be solely put on to the hands of the utility itself [7]. It has been found out most of the conditions that can disrupt the process are generated within the industry itself. For example, most of the non-linear loads within the industries cause transients which can affect the reliability of the power supply [8,9]. Following shows some abnormal electrical conditions caused both in the utility end and the customer end that can disrupt a process [7,10]. 1

12 Chapter 1 1. Voltage sags 2. Phase outages 3. Voltage interruptions 4. Transients due to Lighting loads, capacitor switching, non linear loads, etc.. 5. Harmonics As a result of above abnormalities the industries may undergo burned-out motors, lost data on volatile memories, erroneous motion of robotics, unnecessary downtime, increased maintenance costs and burning core materials especially in plastic industries, paper mills & semiconductor plants [8,11]. Among those power quality abnormalities voltage sags and surges or simply the fluctuating voltage situations are considered to be one of the most frequent type of abnormality [4,12,13,14]. Those are also identified as short term under/over voltage conditions that can last from a fraction of a cycle to few cycles [3,4,11]. Motor start up, lightning strikes, fault clearing, power factor switching are considered as the reasons for fluctuating voltage conditions [7]. As the power quality problems are originated from utility and customer side, the solutions should come from both and are named as utility based solutions and customer based solutions respectively [3]. The best examples for those two types of solutions are FACTS devices (Flexible AC Transmission Systems) and Custom power devices. FACTS devices are those controlled by the utility, whereas the Custom power devices are operated, maintained and controlled by the customer itself and installed at the customer premises [7]. Both the FACTS devices and Custom power devices are based on solid state power electronic components [7]. As the new technologies emerged, the manufacturing cost and the reliability of those solid state devices are improved; hence the protection devices which incorporate such solid state devices can be purchased at a reasonable price with better performance than the other electrical or pneumatic devices available in the market [5]. Uninterruptible Power Supplies (UPS), Dynamic Voltage Restorers (DVR) and Active Power Filters (APF) are examples for 2

13 Chapter 1 commonly used custom power devices. Among those APF is used to mitigate harmonic problems occurring due to non-linear loading conditions, whereas UPS and DVR are used to compensate for voltage sag and surge conditions [1,5,12,15]. In this thesis the control of a Dynamic voltage restorer for single phase voltage sags has been studied. Voltage sag may occur from single phase to three phases. But it has been identified single phase voltage sags are the commonest and most frequent in Sri Lanka. Therefore the industries that use three phase supply will undergo several interruptions during their production process and they are compelled to use some form of voltage compensation equipment. In this research it was found that the most common voltage compensation equipment used in Sri Lanka is the UPS; though it s considered to be an expensive alternative to move towards a full UPS system. This is the basic reason to carry out this research in that particular area and focused into single phase voltage sags. A new control technique to detect and compensate for the single phase voltage sags was developed and simulated using the EMTDC/PSCAD software. Combination of both the pre-sag and in-phase compensation techniques was used in the above developed control to optimize the real power requirement during compensation. In the said control technique the system generates a random reference voltage waveform with the nominal voltage amplitude and the frequency with automated synchronising control. Once the DVR is connected to the system, the phase angle of this reference signal is synchronized with the supply voltage phase angle by continuously monitoring the reference phase angle using a feed back synchronsing control loop. Then by comparing this reference voltage waveform with the measured voltage waveform, any occurrence of voltage abnormalities was detected as an error. As the system detect any voltage sags as error, the power circuit in the DVR generates a voltage waveform to compensate for the voltage sag. The design of the power circuit parameters and the control circuit is discussed in the preceding chapters in detail. The simulation results show the very good performance of the controller. One problem was notified as the internal voltage drop of the DVR and it responds when harmonics presents in the supply voltage by becoming the injected voltage being non sinusoidal even under normal operating conditions. However these 3

14 Chapter 1 cases were checked in the simulation. The simulation results show that at the normal operating conditions, the injected voltage becomes less and their affect on the load voltage due to distortion is less. Therefore this thesis has contributed a strong knowledge to the research and development targeting industrial application to compensate the single-phase voltage sags. The basic flow of this report is as follows. Chapter 2 is about the Literature review, which will describe the basic operation, structure and the existing control techniques etc This chapter will give the reader a general idea about the Dynamic Voltage restorer and its functionality. Chapter 3 describes the control technique designed and developed by the author to compensate for single phase voltage sags. The designed control technique was implemented and simulated using the EMTDC/PSCAD (stands for Electromagnetic transients including DC/Power system CAD) software (Student version 4.1.0); highly recommended software for Power system simulation purposes. This chapter will give a detailed description and reasoning about the construction method of different blocks used for the simulation together with some intermediate simulation results for illustration purposes. The simulation results were illustrated and discussed under Chapter 4. Several simulations were carried out and analyzed in detail considering all the different cases and possible combination to prove the reliability of the simulated system. Chapter 5 will give the reader some hints about further development proposals of this new control technique and further the technical limitations found during the research work. Chapter 6 is the conclusion and discussed the author s views about the above research activity in overall. 4

15 Chapter 2 Literature Review 2.1 Power quality related problems in the distribution network Together with the technological developments, maintaining the power quality is one of the major requirements, the electricity consumers are demanding of. The reason is modern technology demands for an un-interrupted, high quality electricity supply for the successful operation of voltage sensitive devices such as advanced control, automation, precise manufacturing techniques [16]. Power quality may be degraded due to both the transmission and the distribution side abnormalities [3,17,18]. The abnormalities in the distribution system are load switching, motor starting, load variations and non-linear loads [10]. Whereas lightning and system faults can be regarded as transmission abnormalities [19]. To overcome the power quality related problems occurring in the transmission system, FACTS (Flexible AC Transmission System) devices play a major role. These are also referred to as Utility based solutions. Similarly Custom Power devices, which normally targeted to sensitive equipped customers, are used to overcome power quality problems in the distribution network [3]. One of the main advantages of the FACTS devices is that they allow for increased controllability and optimum loading of the lines without exceeding the thermal limits. Whereas Custom Power devices ensure a greater reliability and a better quality of power flow to the load centers in the distribution system by successfully compensating for voltage sags/dips, surges, 5

16 Chapter 2 harmonic distortions, interruptions and flicker, which are the frequent problems associated with distribution lines [7,17]. However, failure of such custom power devices cause equipment failing, maloperations, tripping of protective relays and ultimately plant shut downs, which results huge financial loss to the industry [20]. Therefore proper design of control and selection of the custom power device is very important Voltage sags and surges The most frequent power quality associated problem in the distribution network is voltage sags and surges and are shown in Figure 2.1 below [2,18]. Figure 2.1: top left - Voltage sag occurs at the zero crossing point & without a phase shift top right - Voltage surge occurs at zero crossing point & without a phase shift bottom left - Voltage sag not at the zero crossing point & without a phase shift bottom right - Voltage sag at zero crossing point with a phase shift Voltage sag/surge can simply be defined as a sudden increase/decrease in the rms voltage with duration of half a cycle to few cycles. In addition to the magnitude change of the supply voltage, there can be a phase shift during the voltage sag / surge as shown in Figure 2.1 [11,13]. The magnitude of the voltage sag will depend on the 6

17 Chapter 2 fault type and the location and also on the fault impedance [19]. The duration of the fault depends on the performance of the relevant protective device [3]. Further it has been found that the voltage sags with magnitude 70% of the nominal value are more common than the complete outages [35]. Sags and surges can be identified by the voltage magnitude and the time duration it prevails. IEEE , IEEE describes it as in Table 2.1 [10]. Disturbance Voltage Duration Voltage Sag pu cycle Voltage Swell pu cycle Table 2.1 : IEEE definitions for the voltage sags and swells For a particular disturbance (voltage sag or swell), if the voltage and time duration it remains is within the range given in Table 2.1, the custom power devices are the optimized solution to overcome the problem and compensate for the abnormality during the time period it prevails [16] Custom Power Devices The most common custom power devices to compensate for the voltage sags and swells are the Uninterruptible Power Supplies (UPS), Dynamic Voltage Restorers (DVR) and Active Power Filters (APF) with voltage sag compensation facility. Among those the UPS is the well known. DVRs and APFs are less popular due to the fact that they are still in the developing stage, even though they are highly efficient and cost effective than UPSs [3,14,21]. But as a result of the rapid development in the power electronic industry and low cost power electronic devices will make the DVRs and APFs much popular among the industries in the near future [1,22]. DVR and APF are normally used to eliminate two different types of abnormalities that affect the power quality. They are discussed based on two different load situations namely linear loads and non-linear loads. The load is considered to be a linear when both the dependent variable and the independent variable shows linear 7

18 Chapter 2 changes to each other. Resistor is the best example for a linear device. The non-linear load on the other hand does not show a linear change. Capacitors and inductors are examples for non-linear devices. (a) When the supply voltage/current consists of abnormalities, while the load is linear: In this case the custom power device together with the defected supply should be capable of supplying a defect free voltage/current to the load. To be precise the device should be able to supply the missing voltage/current component of the source. A reliable device that can be used for the above case (for voltage abnormalities) is the DVR. It compensates for voltage sags/swells either by injecting or absorbing real and reactive power [15]. (b) Power supplied is in normal condition with a non linear load: When non-linear loads are connected to the system, the supply current also becomes non-linear and this will cause harmonic problems in the supply waveform. In such situation to make the supply current as sinusoidal, a shunt APF is connected [8]. This APF injects/absorbs a current to make the supply current sinusoidal. Hence the supply treats both the non-linear load and the APF as a single load, which draws a fundamental sinusoidal current [23,24]. Figures 2.2a and b show the basic function of the DVR and the shunt APF. Figure 2.2a & b: Basic operation of DVR (left) and APF (right) 8

19 Chapter 2 From Figures 2.2a, b and the references [11,15,23,25] it is clear that the DVR is series connected to the power line, while APF is shunt connected. Among the custom power devices, UPS and DVR can be considered as the devices that inject a voltage waveform to the distribution line. When comparing the UPS and DVR; the UPS is always supplying the full voltage to the load irrespective of whether the wave form is distorted or not. Consequently the UPS is always operating at its full power. Whereas the DVR injects only the difference between the pre-sag and the sagged voltage and that also only during the sagged period. Thus DVR operating losses and the required power rating are very low compared to the UPS. Hence DVR is considered as a power efficient device compared to the UPS [12,22,26]. 2.2 Structure of the DVR The DVR basically consists of a power circuit and a control circuit. Control circuit is used to derive the parameters (magnitude, frequency, phase shift, etc ) of the control signal that has to be injected by the DVR. Based on the control signal, the injected voltage is generated by the switches in the power circuit [11,27]. Further power circuit describes the basic structure of the DVR and is discussed in this section. Power circuit mainly comprising of five units as in Figure 2.3 and the function and the requirement of each unit is discussed below [1,3,11,16,28]. Figure 2.3: DVR Power circuit 9

20 Chapter Energy Storage Unit Energy storage device is used to supply the real power requirement for the compensation during voltage sag. Flywheels, Lead acid batteries, Superconducting magnetic energy storage (SMES) and Super-Capacitors can be used as energy storage devices [3,11,13]. For DC drives such as SMES, batteries and capacitors, ac to dc conversion devices (solid state inverters) are needed to deliver power, whereas for others, ac to ac conversion is required. The maximum compensation ability of the DVR for particular voltage sag is dependent on the amount of the active power supplied by the energy storage devices [8,13]. Lead acid batteries are popular among the others owing to its high response during charging and discharging. But the discharge rate is dependent on the chemical reaction rate of the battery so that the available energy inside the battery is determined by its discharge rate [11,21] Voltage Source Inverter Generally Pulse-Width Modulated Voltage Source Inverter (PWMVSI) is used. The basic function of the VSI is to convert the DC voltage supplied by the energy storage device into an AC voltage. In the DVR power circuit step up voltage injection transformer is used. Thus a VSI with a low voltage rating is sufficient [21]. The common inverter connection methods for three phase DVRs are 3 phase Graetz bridge inverter, Neutral Point Clamp inverter [21] and H Bridge inverter [11] for single phase DVRs. a) Three-phase graetz bridge This is often called as two-level three-phase inverter. Each leg is switched according to the PWM technique used. In the case of fundamental switching is used then the switches are on for a period of 180 o with a duty ratio of 50%. The inverter configuration, switching and output waveforms for the fundamental switching are 10

21 Chapter 2 shown in Figure 2.4. This is referred to as two-level since the phase output voltage waveform consists of two output levels; +V d and 0 Volts [11,29]. Figure 2.4 : Three phase Graetz bridge and its switching arrangements b) Neutral Point Clamped Inverter This Neutral Point Clamped (NPC) inverter can be used for higher voltage levels than the graetz bridge configuration. The phase output voltage waveform consists of three levels Vdc Vdc, 0 and Volts. The inverter configuration and the 2 2 single phase output waveforms are shown in Figure 2.5. output Figure 2.5: NPC inverter configuration and its switching arrangement 11

22 Chapter 2 c) H bridge inverter In the H bridge inverter, four switches are used. When it used for multilevel arrangement specially for high voltage application, it is commonly called as chain circuits. For fundamental switching each switch is on for a duty cycle of 50% and shown in Figure 2.6 [29]. Figure 2.6: H-bridge inverter configuration and its switching arrangement Passive filters Low pass passive filters are used to convert the PWM inverted pulse waveform into a sinusoidal waveform. This is achieved by removing the unnecessary higher order harmonic components generated from the DC to AC conversion in the VSI, which will distort the compensated output voltage [30]. These filters can be placed either in the high voltage side (load side- shown in Figure 2.7-left) or in the low voltage side (inverter side-shown in Figure 2.7-right) of the injection transformers [3,15]. When the filters are in the inverter side higher order harmonics are prevented from passing through the voltage transformer. And it will reduce the stress on the injection transformer. But there can be a phase shift and voltage drop in the inverted output. This can be reduced by placing the filter in the load side. But in this case since the higher order harmonic currents do penetrate to the secondary side of the transformer, a higher rating of the transformer is necessary. However the leakage 12

23 Chapter 2 reactance of the transformer can be used as a part of the filter, which will be helpful in tuning the filter [11,15,21]. Figure 2.7: Different filter placements By-pass switch Since the DVR is a series connected device, any fault current that occurs due to a fault in the downstream will flow through the inverter circuit. The power electronic components in the inverter circuit are normally rated to the load current as they are expensive to be overrated. Therefore to protect the inverter from high currents, a by-pass switch (crowbar circuit) is incorporated to by-pass the inverter circuit [9,11]. Basically the crowbar circuit senses the current flowing in the distribution circuit and if it is beyond the inverter current rating the circuit bypasses the DVR circuit components (DC Source, inverter and the filter) thus eliminating high currents flowing through the inverter side. When the supply current is in normal condition the crowbar circuit will become inactive [8]. 13

24 Chapter Voltage injection transformers The high voltage side of the injection transformer is connected in series to the distribution line, while the low voltage side is connected to the DVR power circuit. For a three-phase DVR, three single-phase or three-phase voltage injection transformers can be connected to the distribution line, and for single phase DVR one single-phase transformer is connected [21]. For the three-phase DVR the three singlephase transformers can be connected either in delta/open or star/open configuration as shown in Figure 2.8 [15]. Figure 2.8: Connection methods for the primary side of the injection transformer Left : delta/open configuration Right : Star/open configuration The basic function of the injection transformer is to increase the voltage supplied by the filtered VSI output to the desired level while isolating the DVR circuit from the distribution network. The transformer winding ratio is pre-determined according to the voltage required in the secondary side of the transformer (generally this is kept equal to the supply voltage to allow the DVR to compensate for full voltage sag) [21]. A higher transformer winding ratio will increase the primary side current, which will adversely affect the performance of the power electronic devices connected in the VSI. The rating of the injection transformer is an important factor when deciding the DVR performance, since it limits the maximum compensation ability of the DVR [13]. Further the leakage inductance of the transformer brings to a low value to reduce 14

25 Chapter 2 the voltage drop across the transformer. In order to reduce the saturation of the injection transformer under normal operating conditions it is designed to handle a flux which is higher than the normal maximum flux requirement [21]. The winding configuration of the injection transformer mainly depends on the upstream distribution transformer. If the distribution transformer is connected in Δ-Y with the grounded neutral, during an unbalance fault or an earth fault in the high voltage side, there will not be any zero sequence currents flow in to the secondary. Thus the DVR needs to compensate only the positive and negative sequence components. As such, an injection transformer which allows only positive and negative sequence components is adequate [4]. Consequently the delta/open configuration can be used (shown in Figure 2.8-left). Further this winding configuration allows the maximum utilization of the DC link voltage [11,21]. For any other winding configurations (such as star/star earthed) of the distribution transformer, during an unbalance fault all three sequence components (positive, negative and zero) flow to the secondary side. Therefore the star/open configuration (Figure 2.8-right) should be used for the injection transformers, which can pass all the sequence components [11,21]. 2.3 DVR operating states During a voltage sag/swell on the line The DVR injects the difference between the pre-sag and the sag voltage, by supplying the real power requirement from the energy storage device together with the reactive power. The maximum injection capability of the DVR is limited by the ratings of the DC energy storage and the voltage injection transformer ratio. In the 15

26 Chapter 2 case of three single-phase DVRs the magnitude of the injected voltage can be controlled individually. The injected voltages are made synchronized (i.e. same frequency and the phase angle) with the network voltages [16] During the normal operation Since the network is working under normal condition the DVR is not injecting any voltages to the system. In that case, if the energy storage device is fully charged then the DVR operates in the standby mode or otherwise it operates in the selfcharging mode. The energy storage device can be charged either from the power supply itself or from a different source [11,21] During a short circuit or fault in the downstream of the distribution line In this particular case as mentioned in section the by-pass switch is activated to provide an alternate path for the fault currents. Hence the inverter is protected from the flow of high fault current through it, which can damage the sensitive power electronic components [8,16]. 2.4 DVR compensation techniques The compensation control technique of the DVR is the mechanism used to track the supply voltage and synchronized that with the pre-sag supply voltage during a voltage sag/swell in the upstream of distribution line. Generally voltage sags are associated with a phase angle jump in addition to the magnitude change [21]. Therefore the control technique adopted should be capable of compensating for 16

27 Chapter 2 voltage magnitude, phase shift and thus the wave shape. But depending on the sensitivity of the load connected downstream, the level of compensation of the above parameters can be altered. Basically the type of load connected influences the compensation strategy. For example, for a linear load, only magnitude compensation is required as linear loads are not sensitive to phase angle changes [11,13]. Further when deciding a suitable control technique for a particular load it should be considered the limitations of the voltage injection capability (i.e. the rating of the inverter and the transformer) and the size of the energy storage device [11]. Compensation is achieved via real power and reactive power injection. Depending on the level of compensation required by the load, three types of compensation methods are defined and discussed below namely pre-sag compensation, in-phase compensation and energy optimization technique. The circuit for a simple power system with a DVR is shown in Figure 2.9 below. The supply voltage, Load voltage, Load current and the voltage injected by the DVR are denoted by V s, V load, I load and V DVR respectively. Figure 2.9: Simple power system with a DVR When the system is in normal condition, the supply voltage (V s ) is identified as pre-sag voltage and denoted by V pre-sag. In such situation since the DVR is not injecting any voltage to the system, load voltage (V load ) and the supply voltage will be the same. During voltage sag, the magnitude and the phase angle of the supply voltage can be changed and it is denoted by Vsag. The DVR is in operative in this case and the voltage injected will be V DVR. If the voltage sag is fully compensated by the DVR, the load voltage during the voltage sag will be V pre-sag. 17

28 Chapter Pre-sag compensation This compensation strategy is recommended for the non-linear loads (e.g.: thyristor controlled drives) which needs both the voltage magnitude as well as the phase angle to be compensated. In this technique the DVR supplies the difference between the pre-sag and the sag voltage, thus restore the voltage magnitude and the phase angle to that of the pre-sag value. Figure 2.9 below describes the pre-sag compensation technique [11,13]. However this technique needs a higher rated energy storage device and voltage injection transformers. Figure 2.10: Pre-sag compensation technique In-phase compensation The DVR compensates only for the voltage magnitude in this particular compensation method, i.e. the compensated voltage is in-phase with the sagged voltage and only compensating for the voltage magnitude. Therefore this technique minimizes the voltage injected by the DVR. Hence it is recommended for the linear loads, which need not to be compensated for the phase angle [11,13]. This particular compensation technique is shown in Figure It is clear from the Figure 2.10, that there is a phase shift between the voltages before the sag and after the sag. 18

29 Chapter 2 Figure 2.11: In-phase compensation technique It should be noted that the techniques mentioned in and need both the real and reactive power 1 for the compensation, and the DVR is supported by an energy storage device Energy optimization technique In this particular control technique the use of real power is minimized (or made equal to zero) by injecting the required voltage by the DVR at a 90 phase angle to the load current. Figure 2.11 depicts the energy optimization technique. However in this technique the injected voltage will become higher than that of the in-phase compensation technique. Hence this technique needs a higher rated transformer and an inverter, compared with the earlier cases [11,13]. Further the compensated voltage is equal in magnitude to the pre sag voltage, but with a phase shift. 1 The reactive power is generated by converting part of the real power supplied into reactive power (by the reactive components used for the DVR). 19

30 Chapter 2 Figure 2.12: Energy optimization technique It is even possible to combine different compensation techniques described earlier, to achieve better efficiency and ease of controllability. One such technique is combining both the pre-sag and in-phase compensation method. In the combined technique the system initially restores the load voltage to the same phase and magnitude of the nominal pre-sag voltage (pre-sag compensation) and then gradually changes the injected voltage towards the sag voltage phasor. Ultimately the compensated voltage is in same magnitude and phase angle with the pre-sag voltage and slowly its phase angle transferred to to the sagged voltage. Figure 2.12 gives an idea about the compensation control strategy when both pre-sag and in-phase compensation techniques are combined. It is clear from the Figure when the DVR injected voltage is V DVR_1 (at the beginning of the compensation) the system used pre-sag compensation, and slowly the injected voltage phasor is moved towards V DVR_4 (in-phase compensation) [11]. 20

31 Chapter 2 1pu V pre-sag =V load_1 load_2 load_3 V DVR_3 V DVR_4 I load V sag V load_4 Figure 2.13: Combining both pre-sag and in-phase compensation techniques 2.5 Control techniques used in commercially available DVRs Most of the commercially available DVRs use either the in-phase compensation technique or energy optimization technique, owing to minimal requirement of real power injection: hence it reduces the capacity of the energy storage needed. Control technique describes the method used to quantify the DVR control voltage injected during the compensation. In simple terms it basically detects the occurrence of voltage sag. Some common control techniques used by DVR manufacturers are described in this section [11]. Irrespective of the compensation techniques used, there should be a scheme to track the phase angle and the magnitude of the supply voltage during normal operation (more specifically positive sequence component of the supply voltage) and to detect the occurrence of voltage sag. In other words there should be a voltage sag detection technique (it detects the occurrence of the sag, start and end points, sag depth and phase shift). Followings are some of the common voltage sag detection techniques. 21

32 Chapter 2 Voltage sag detection techniques (i) Fourier transform (ii) Phase Locked Loop (PLL) (iii) Vector control (Software Phase Locked Loop SPLL) (iv) Peak value detection (v) Applying the wavelet transform to each phase Out of the techniques mentioned above only the Fourier transform, Vector control and wavelet transform methods provide both the voltage magnitude and phase shift information. PLL method can provide only the phase shift information while peak value detection technique enables to get the magnitude change (voltage sag) information. Hence it is possible to combine one or more techniques mentioned above to obtain accurate voltage sag compensation Fourier Transform By applying Fourier transform to each supply phase, it is possible to obtain the magnitude and phase of each of the frequency components of the supply waveform in addition to the fundamental such as magnitude and phase information of the 5 th and 7 th harmonic components. This is the advantage of this method compared with other sag detection techniques. For practical digital implementation windowed fast Fourier transform-wfft is used which has same features as the Fourier transform [4]. Further this method can easily be implemented in real time control system. The only drawback of this method is after voltage sag has commenced it can take up to one cycle to return the accurate information about the sag depth and its phase. The reason is the calculation method used by WFFT is an averaging technique. 22

33 Chapter Phase Locked Loop Generally the DVRs use Phase Locked Loop (PLL) to keep a track of the frequency and the phase angle of the healthy supply voltage, and thereby any change from the normal operating condition can easily be detected [11,31]. Phase locked loop is a closed loop feedback control system, that generates a signal with the same frequency and the phase angle of the input signal. It consists of an oscillator which provides the output signal. The PLL internal function can be categorized as phase detector, variable oscillator and a feedback path. PLL responds to frequency changes and phase angle changes of the input signal by increasing or decreasing the frequency of the oscillator until it is matched with those of the reference input signal. Simplified PLL is shown in Figure The phase angle of the input signal is compared with the feedback output of the oscillator and produces an error signal. The error signal is generated in the form of voltage signal, proportional to the phase angle difference between the input and output. The output of the phase detector consists of harmonic components, thus it has to pass through a low pass filter. But this filtering can introduce transient delays in detecting the voltage sags, which is undesirable [4,32]. The controlled voltage output 2 of the loop filter is then feed in to the Voltage controlled oscillator and provides a phase output. This output signal (in the form of a phase angle) is negatively feedback into the phase detector. The output of the oscillator is compared with the input and if the two frequencies are different, the frequency of the oscillator is adjusted to match with the input frequency. Figure 2.14: Simplified block diagram of a phase locked loop 2 The controlled voltage output of the phase locked loop is a function of frequency. 23

34 Chapter 2 However reference [3] says that this method to track the phase angle is not accurate and not suitable for fast synchronization. Further with this method it cannot return the sag depth information and difficult to implement in real-time [4]. Hence a more accurate method to detect the phase angle is introduced and referred to as Software Phase Locked Loop (SPLL) Software Phase Locked Loop (SPLL) / Vector Control This is an improved method of PLL principal combining a voltage sag magnitude detection technique using the principal synchronous frame voltage quantities. Software implementation of this technique is more accurate, faster detection of voltage sag and can easily be implemented using Digital Signal Processing (DSP). This method is also referred to as vector control technique or simply as the synchronous reference frame model [3,4,11]. It is known that unbalance voltage sags create negative sequence voltages which will rotate in opposite direction to that of positive sequence voltages. When considering the concept of synchronous reference frame, the negative sequence component is assumed to have a frequency of twice the frequency of the fundamental. When all the sequence components (positive, negative and zero) are present in a voltage waveform it is difficult to track the positive sequence component and also the result can be erroneous [3,11]. Hence the major point of the SPLL technique is it can be used to track only the positive sequence component from the supply waveform and the block diagram is shown in Figure 2.14 [11,21,22]. Figure 2.15: Block diagram of a Software Phase Locked Loop 24

35 Chapter 2 The basic principal behind the operation of SPLL is regulating the V sqn to zero and to track the phase angle (θ) of the positive sequence voltage of the supply wave form. Initial phase angle information of the supply waveform is given by this θ. Then the voltage output of the SPLL will be equal to V sd. By comparing V sd with a set reference point any occurrence of voltage sag magnitude can be detected. The same way by comparing V sq with a set reference zero the phase angle jump can be detected. This is further explained in Figure It is clear from the figure, when V sqn tends to zero V sdn is in phase with V sn (normalized supply voltage), hence any voltage sag can easily be detected by the system. ω β q V sqn d ω γ θ б V sαn α σ = tan ( σ θ ) sin( σ θ ) = sin( γ ) sin γ = when V 1 sqn V V V sβn sαn V 2 sdn sqn + V γ = 0 and θ = σ Figure 2.16: Simplified phasor representation of SPLL 2 sqn 0, sin γ = 0, Each block in Figure 2.13 can further be described as follows [11]. Step 1 The phase voltages (V sa, V sb and V sc ) are converted into stationary reference frame voltage quantities (V sα and V sβ ) using the following transformation. 25

36 Chapter Assumption : Vs = vsα + jvsβ = ( vsa + αvsb + α vsc ) 3 V V sα sβ = V 1 2 V 3 2 V sa sb sc Eq. 2.1 Step 2 The stationary reference frame voltage quantities are converted into synchronous rotating reference frame voltage quantities (V sd and V sq ) rotating by an angle θ. V V sd sq cosθ = sinθ sinθ V cosθ V sα sβ Eq. 2.2 Step 3 The V sd and V sq values obtained in step 2 are normalized as follows. V V sdn sqn = = V V V 2 sd V 2 sd sd + V sq + V 2 sq 2 sq Eq. 2.3 Step 4 The next step is to control the angle θ such that the normalized V sqn =0. This is achieved using a PI controller. The response time can be varied by changing K p and K I values of the PI controller. Then the output of the PI controller is added to ω s, angular frequency at rated operating condition. Then pass it through a resettable integrator to obtain the desired SPLL output θ. In conclusion SPLL principle can be summarized as follows. The synchronous reference frame is locked to the positive sequence of the voltage Vs by the principle of PLL and it produces a voltage vector magnitudes V d and V q. The phase angle (theta) used in the synchronous reference frame calculations is used to generate the reference voltage vector [15]. When the system is in locked condition with the normal operating condition V d becomes same as the voltage vector magnitude and V q becomes zero. Therefore any disturbance can be identified as they make deviation on 26

37 Chapter 2 the V d and V q from their normally operated values. This is how the fast detection normally implemented Peak value detection of the supply wave form The peak value of any waveform is the point at which its gradient tends to zero. This simple phenomenon is used in this technique. The point at which voltage gradient is zero is identified as the peak value of the supply voltage [32]. It is compared with a preset reference voltage. If the voltage difference between the supply and the reference voltage exceeds a specified value (eg. 10%) then the DVR starts operating (DVR inject the difference voltage). The voltage gradient can be calculated as follows. vt vt δ t Voltage Gradient = Eq. 2.4 δt v t is the voltage at time instant t and small time step. vt δ t is the voltage at time t δt whereδt is a As in reference [32], the drawbacks of this method are the time delay (up to 0.5 sec.) in getting the sag depth information and the noise that would affect the measurements severely. Further to get the phase shift information a reference waveform is needed which has to be generated separately Applying wavelet transformation The wavelet transform is similar to the Fourier transform with the basic difference that in wavelet transform it is possible to represent a signal both in time domain and frequency domain 3, but the integral transform can perform only in one direction [33]. The shortcomings of this technique are the difficulty in directly interpreting the results and difficulty in real time implementation [4]. 3 Fourier transform is a frequency domain representation of a signal and can perform the integral transform in both directions. 27

38 Chapter 3 New control technique developed for single phase voltage sag compensation 3.1 Background The major drawback of the existing voltage sag detection techniques discussed in section 2.5 is that, it is costly and complicated to control the voltage injection for a single phase fault, where most frequent fault occurred in a targeted phase. As such it will be an easier alternative to control the voltage injection in the phases individually using three single phase DVRs. In this case the voltage injection in each phase is controlled independently to the other phases. This arrangement of DVR gives possibility of installing single-phase DVR if only one phase is identified with frequent interruptions. This project mainly focused on designing a control strategy for a single-phase Dynamic Voltage Restorer to detect single-phase voltage sags. The study has been carried out only for single-phase voltage sags, since single phase voltage sags are the most common type of voltage sag occurs in Sri Lanka than the three phase sags. In case of full compensation required, three of the single-phase DVR arrangement can be used. In this project an analogue control system was developed with a combination of pre-sag and in-phase compensation techniques as discussed in section 2.4. In presag compensation technique, always load voltage is maintained to be same as the presag voltage. But this method of compensation requires higher capacity energy storage 28

39 Chapter 3 device, which will directly affect the cost of the DVR, if the sag continues for a longer duration. In-phase compensation technique compensates only for the voltage magnitude and as a result the compensated load voltage will undergo a phase shift if the voltage sag is associated with a phase jump. Thereby the requirement of a higher capacity energy storage device can be bargained. In the developed control strategy, at the beginning of the sag the DVR compensate both for the voltage magnitude change and the phase shift as well, same as pre-sag compensation and restored the load voltage back to the pre-sag voltage. Then the controller smoothly transfers the compensation technique from pre-sag to in-phase technique thus the developed control plays an intelligent role to minimize the DVR rating while maintaining load voltage without experiencing any disturbance. Further to detect the occurrence of voltage sag, peak value of the supply voltage was constantly monitored. The measurement method was discussed under section It is important to note that the small frequency variations (within the allowable range defined by IEEE) of the supply voltage is tolerable and can be tracked by this control mechanism without any compensation. The frequency variations beyond the defined range (±1%) are assumed to be taken care by the system control of the utility. 3.2 Simplified control block diagram Voltage sag is produced by a magnitude change with or without a phase shift of the supply voltage. Thus it is necessary to quantify and correct for phase shift (if any) prior to compensate for the voltage sags. To quantify the phase shift a random reference phase angle waveform was generated and by using a feedback control loop the error (between the supply and the reference phase angle waveforms) was regulated to zero. Therefore at the steady operation of the control the reference waveform was tracked to the supply and both are synchronized in phase angle. 29

40 Chapter 3 Then the reference voltage waveform was created from the reference phase angle and rated rms load voltage. Finally, the voltage that needed to be injected by the DVR was calculated by subtracting the measured supply voltage from the reference voltage waveform. The control block diagram related to the above is shown in Figure 3.1 below. Block 1 Block 2 Block 3 Block 4 Find the phase angle of the supply waveform Find the phase angle of the reference voltage Generation of the reference voltage waveform Calculation of control voltage Figure 3.1: Simplified control block diagram for the single phase DVR Each block was implemented using EMTDC/PSCAD software for the simulation and construction method of each block is described below. 3.3 PSCAD implementation of control circuit Block 1: Determination of supply voltage phase angle Since the supply voltage waveform is measured and readily available, it is possible to obtain all the information (magnitude, frequency) related to the supply. Consequently the starting and ending point of each cycle can be easily obtained. During each cycle the phase angle of the input voltage waveform is varying from 0 rad to 2π rad (0 to 360 ). Thus the phase angle waveform of the supply voltage (A meas ) can be obtained. Figure 3.2 shows the implementation method of the block 1. Figure 3.3 shows the schematic diagram of the block 1 using EMTDC/PSCAD package. 30

41 Chapter 3 2πf Rated frequency Resettable integrator Phase angle of the supply voltage Supply voltage waveform Zero crossing point detection Limiter Clear signal to the integrator Figure 3.2: Implementation method of block 1 Input Clear 1 st Ameas Vs Zero Detector Clear_signal ZCD Figure 3.3: PSCAD implementation of block 1 As shown in Figure 3.3, the input signal to this integrator is the angular frequency of the input waveform, i.e. the 2πf= (constant), with f being the nominal supply frequency 50Hz. Then the output supply phase angle waveform (or the integrator output) is a line with a gradient of (or y= t shape) 1. This signal is re-setted at every supply cycle in order to obtain the phase angle information. This re-set function is achieved by introducing a clear signal. The clear signal is obtained from the positive zero crossing detector, made of zero crossing detector with positive side limiter, of the supply waveform This will ensure the clear signal is activated per cycle. Different components parameters of the above Figure 3.3 were selected as follows. 1 When a constant of magnitude m is integrated with respect to time the output will be in the form of y=mt, where m being the gradient of the linear output signal. 31

42 Chapter 3 1) Supply voltage (Vs): This is the input voltage signal from the particular supply phase feed from the distribution transformer. 240 V, 50 Hz sinusoidal input source with an internal series impedence of 0.01 Ω was taken. During the sag this input voltage reduced depending on the severity of the upstream fault. 2) Zero crossing detector (ZCD): This component produce an output of 1, when the input crosses the zero value axis at its positive gradient and -1 at the negative gradient zero crossing point. At all the other times the output will be zero. This is shown in Figure 3.4. Figure 3.4: Integrator clear signal generation 3) Limiter: This limits the negative signal. Thus this will detect only the positive part of the zero crossing detector s output signal. This enables to detect the cycle time of the supply voltage waveform. The output (as in Figure 3.5) is directly feed into the integrator as the clear signal. 32

43 Chapter 3 Figure 3.5: Integrator clear signal 4) Resettable integrator: This unit simply performs the integration function together with resetting to a predetermined value when the clear signal is present. The input signal is 2πf (f = 50 Hz). The integrator time constant was selected as 1s. This outputs the phase angle information of the supply voltage waveform and the output waveform is shown in Figure 3.6. Figure 3.6: Phase angle variation of the supply voltage and 3.8 below. PSCAD output waveforms at different output channels are shown in figure

44 Chapter Implementation of Block 1 Supply voltage ZCD Clear_signal Angle meas*0.1 voltage (kv) & phase angle (rad) time(s) Figure 3.7: Output waveforms at different output channels Phase angle of the supply waveform (Angle measured) is de-rated by a factor of 0.1 to show all the waveforms in a single plot. When the supply is in the normal condition the actual maximum height of the Angle measured waveform is (2πft, where t = 0.02 s, cycle time related to 50 Hz) Input signal to the resettable integrator Implementation of Block 1 time(s) Figure 3.8: Input waveform to the resettable integrator 34

45 Chapter Block 2: Reference phase angle waveform generation Aref D + - F Am eas Ameas 0.0 Angle Error A B Ctrl Ctrl = 1 * 10.0 triggering pulse Angle Error input D + - Angle Error filtered F PI output P I Clear 1 st Comparator A B Aref Figure 3.9: Simulation block for the reference phase angle wave form generation In the block as shown in Figure 3.9, a random reference phase angle signal is generated. The reference signal s phase angle is synchronized with the measured signal phase angle by slowly adjusting the gradient (angular frequency) of the randomly generated reference phase angle signal. The simulation block diagram shown in Figure 3.9 consists of 3 major blocks and is shown in Figure 3.10 and discussed in A meas Calculate the angle error and regulate it to zero Adjust the gradient of A ref according to angle error Generate the new A ref Figure 3.10: Simplified diagram of control block Calculate the angle error between the reference and the supply phase angle. Initially a random reference phase angle wave from was created for a frequency of 50Hz. Then a simple comparator block was used to calculate the angle error. As seen in the Figure 3.11 below the angle error between the two waveforms 35

46 Chapter 3 are varying from positive to negative during each cycle. Further the average error is zero. Reference phase angle Measured phase angle Angle error Average angle error = 0 Figure 3.11: Generation of angle error signal Filtered and PI controlled output of this angle error has to be added or subtracted from the reference ( ). As shown in Figure 3.10, the next step is to adjust the gradient of the A ref to synchronize it with the A meas, while regulating this angle error component to zero. Inability to identify whether this error component has to be added or subtracted (since it varying from positive to negative during each cycle) introduces an additional control block and separately shown in Figure Angle error 0.0 A Ctrl = 1 B Ctrl * 10.0 Angle Error input to the filter etc.. Am eas triggering pulse Figure 3.12: additional block to obtain the angle error 36

47 Chapter 3 The measured phase angle waveform was fixed during the normal operation. Hence it can be used as a reference to calculate the angle error. Two points closer to the middle of the phase angle waveform (2.5 rad to 3.5 rad) were selected and when the measured phase angle waveform is within those limits, the block calculates the angle error. When the measured phase angle was beyond the given limit the block doesn t calculate any angle error. This technique is used mainly to get the error which clearly differentiates the angle lead or lag and proportional to its magnitude. A range comparator was used to achieve this task and its specifications are as shown in Figure Comparator will generate an output of 1 when the input (supply phase angle in radians) is between Except this limits, it will generate a zero output as angle error. When selecting the comparator limits care has to be taken to maintain the same magnitude of the angle error. (i.e. within the selected limit the angle error should not change its sign.) Figure 3.13: Angle error calculation It is clear from Figure 3.13; the angle error is definitely a negative value (or can be definitely positive either if A ref is leading A meas ) as the points considered are 37

48 Chapter 3 only between 2.5 rad to 3.5 rad. If the comparator limits were selected closer to the ends such as 0 rad or rad then the angle error varies its sign, which is not desirable. A two way input selector switch was used to generate an output only when the triggering pulse is present i.e. when it is 1. The obtained angle error was multiplied by a factor 10 to speed up the synchronization and obtain more accurate synchronization. Then the angle error signal was passed through a filter and a PI controller Regulate the error component and reduce the harmonics The angle error wave form obtained above is a pulsed waveform consists of harmonics. To achieve better synchronization the error has to be regulated to zero, while converting the pulse signal into a smooth one. A low pass LC filter and a PI control was added to achieve that purpose and explained below Low pass filter A filter with a second order transfer function was used. It attenuates the frequencies above the characteristic frequency. A 500 Hz was selected as a reasonable value for the characteristic frequency. This passes the frequency components below the 500 Hz which will attenuate the harmonics to a reasonable level. Gain and the damping ratio of this low pass filter were selected to be 1 to maintain the same magnitude and the wave shape of the input during filtering PI controller A Proportional Integrate controller was used to regulate the error between the measured (supply) and the reference phase angle to zero. Reasons for selecting a PI controller 38

49 Chapter 3 The function of the proportional action is to respond quickly to the changes in the error deviation. Integral action is slower than the proportional response but used to remove the offsets between the input and the reference at steady state [34]. Before the DVR starts injecting voltage to the system, a considerable time period was allowed for the synchronization. The synchronization process was made according to the possible system frequency deviation. As the system frequency is not much deviate from 50 Hz the fast synchronization is not a necessity. Hence it helps the load voltage without phase jump. Therefore the derivative action is not needed and the need of PID controller was omitted 2. Tuning the PI controller In the PSCAD simulation block for the PI controller following parameters has to be defined as shown in Figure Figure 3.14: User defined parameters in the PI controller Among those parameters proportional gain (K p ) and the integral time constant (K I ) directly affect the performance of the PI controller. When tuning those two parameters special attention has to be paid. The maximum and the minimum limits of the PI controller was selected, as the output at any instant doesn t exceed those two values. (+10 and -10) At the beginning of the simulation (at t=0) the controller set to zero output. Hence the initial output is assigned to zero. 2 The derivative action of the PID controller speeds up the system response. 39

50 Chapter 3 Tuning the K p and K I parameters of the PI controller Initially K I (Integral time constant) was set at a high value and the simulations were carried out for different K p values. It has been observed that with increasing K p the time taken to reach the target decrease, K p =0.5 was selected as reasonable. Then by reducing the K I the simulation results were observed. The PI output reaches the target and stabilizes after longer time. Hence K I was selected as 0.2, which is same as 5sec time constant Generating the reference phase angle As described earlier when considering the waveforms of A ref and A meas there are two possibilities. In the first case measured phase angle leads the reference phase angle. In this case the angle error input is negative; hence the PI controller output will also become negative. To get the waveforms synchronized the gradient of the A ref has to be increased: the PI controller output (negative) has to be subtracted from the set gradient point ( ). This will happen automatically in the control as the adder is used and PI controller out put is negative. In the second case measured phase angle lags reference phase angle. In this case the angle error input is positive; hence the PI controller output will also become positive. To get the waveforms synchronized the gradient of the A ref has to be reduced: the PI controller output (positive) has to be subtracted from the set gradient point ( ). For example synchronization in both cases are described in the following Figure

51 Chapter 3 Figure 3.15: Synchronization process The next step is to generate the reference phase angle waveform. The gradient of the reference signal is known and the reference phase angle should vary from 0 to 2π (6.2832) radians. Therefore the reference phase angle waveform should be cleared when it reaches 2π. A comparator and a resettable integrator are used to achieve this resetting. The integrator clear signal is given by the comparator output. This block is shown in Figure 3.16 together with the comparator specifications. output of the summing/ differncing junction Clear 1 st Aref Comparator A B Figure 3.16: Left: Reference waveform generation Right: Comparator specifications The function of the above block is similar to block 1 described in The comparator compares the magnitude of the A ref signal with the set value (6.2832) and 41

52 Chapter 3 when the A ref > , the integrator clear signal is reset and thus the integrator output set to zero Block 3: Reference voltage waveform generation The reference phase angle was generated and synchronized with the supply (measured) phase angle. Next step is to generate the reference voltage waveform from the reference phase angle information. From the phase angle information obtained a sinusoidal waveform was generated with the nominal supply voltage magnitude as in Figure (240V rms = 340V peak) Figure 3.17: Reference voltage waveform generation The simulation control block is shown in Figure Aref Sin * 0.34 Vref Figure 3.18: Simulation block for reference voltage waveform generation 42

53 Chapter Block 4: Control voltage waveform generation The block no. 4 was used to calculate the control voltage by taking the difference between the reference and the supply voltage. When the supply voltage is in normal condition (no voltage sag), both the supply and the reference voltage waveforms are in phase and same in magnitude thus the voltage to be injected by the DVR circuit would be zero. The control voltage will be present only during the voltage sag. The shape of the control voltage waveforms for different sag conditions are shown in Figures Voltage (kv) Control voltage before the voltage sag (both the reference and the supply are in phase) reference and the supply voltages are the same zero control voltage Figure 3.19 top: Control voltage waveform before the voltage sag Figure 3.19 bottom left: Control voltage waveform during the sag (in phase voltage sag) time (sec) Figure 3.19 bottom right: Control voltage waveform during the sag (voltage sag is created with a phase shift) Control voltage during the voltage sag (both the reference and the supply are in phase) reference voltage Control voltage during the voltage sag (reference and the supply voltages are not in phase) reference voltage supply(sag) voltage Control voltage supply (sag) voltage Voltage (kv) Voltage (kv) control voltage time (sec) time (sec) 43

54 Chapter 3 It is clear from the above figures irrespective of the type of voltage sag (in phase or not with the reference voltage) the control voltage is a pure sinusoidal waveform with varying magnitude during the sag period. The simulation block diagram is shown in figure Vref D + - A Ctrl = 1 Vs F B Ctrl Vcontrol 0.0 TIME Figure 3.20: Simulation draft for block 4 When implementing this block in PSCAD simulation software a time delay of 4 sec. was introduced due to following reasons. (i.e. when the DVR is switched on, during the first 4 sec. the DVR control is disengaged internally while synchronization process is activated) 1. to eliminate unnecessary starting transients in the simulation or in practice 2. to allow the supply voltage and the reference voltage to get synchronized. The block shown in dashed lines is used to provide the time delay switching signal to start operation of the DVR. When the input time signal is above the specified value the comparator will generate a signal of 1 and 0 otherwise. When the comparator output is 1 the block starts calculating the control voltage that needs to be injected by the DVR circuit. Further it should be noted that in the simulation, the synchronization time depends on the initial phase shift between the supply voltage and the internally generated reference voltage and also the parameters of the PI controller. If both the 44

55 Chapter 3 wave forms are in phase at the beginning, then theoretically two waveforms should get synchronized from the beginning itself since the angle error is zero. But it was realized that due to the involvement of the feedback control loop and its initial setting values, still it takes some time for synchronization. By considering all of theses effects, to eliminate the start up transients it has given 4 seconds in the simulation to synchronize and stabilize the controller action. There after the controller will be ready for the DVR operation. In the block 4, the voltage that needs to be injected to the DVR was calculated. Next step is to create a power circuit consisting of the units described in section 2.2, which is capable of generating the above calculated control voltage. 3.4 PSCAD implementation of the power circuit The power circuit of the single phase DVR mainly consists of Energy storage device, inverter, filter and a voltage injection transformer and is shown in Figure Figure 3.21: Power circuit of the DVR 45

56 Chapter 3 Suitable values for V DC, C 1, L F, C F, R s, R l and transformer turn ratio n have to be determined Parameter estimation of the power circuit Capacitor C 1 is used as a DC link capacitor, and C 1 =10,000 μf is assumed to be a reasonable value as it is used with the batteries. The power circuit shown in Figure 3.21 was simplified as in Figure 3.22 and for the parameter estimation purposes Figure 3.23 was used. Figure 3.22: Simplified equivalent circuit of DVR power circuit Figure 3.23: Equivalent circuit used for parameter estimation 46

57 Chapter 3 If the DVR is capable of compensating for a full voltage sag (when V sup =0) then, V inj_max =V s =240V rms. For voltage transformer, V V = = n 1 1 inj I I L 1 Assumed that the fundamental component of the current is flowing through the X CF is small. V = X LF Eq. 3.1 n inj Einj V1 + ji1x LF = + ji1 For safety point of view n is kept at a high value to maintain a low voltage at the primary side of the transformer. Therefore the turn ratio of the transformer is selected as 4. Then, 230 V1_ peak = 4 from (1) V E inj but, E 100V is a reasonable value. inj 1_ peak = V DC 2 = 81.31V < E inj = 100V Energy storage device Two batteries of 50V each are used to provide the real power requirement during the voltage sag compensation PWM inverter Two-leg inverter consisting four IGBTs and four diodes are used for single phase voltage sag detection. Inverter legs are switched on and off accordingly, such that the desired control voltage can be obtained at the filter output point. 47

58 Chapter Inverter leg switching signal generation The control voltage output, obtained and described in section 3.3.4, is compared with a high frequency triangular waveform with a switching frequency of 5000Hz and a 100V peak output with a 50% duty cycle. High value of switching frequency (5000Hz) was selected to suppress the DVR injected voltage harmonics transferring to the load voltage in addition to voltage sag compensation. As can be seen from the Figure 3.24, the control voltage was reduced by a factor of 4, before comparing it with the triangular waveform to compensate for the transformation ratio of the voltage injection transformer. The level comparator produces two output levels as shown in Figure Tri Vcontrol Tri * 0.25 Vcontrol1 A B Comparator Pbot Figure 3.24: Inverter leg switching signal generation Ptop 1) Comparator generates an output of 1, when the magnitude of the triangular waveform is higher than that of the control voltage. (Tri > V control 1 ) 2) Produces a zero output when triangular waveform is lower than or equal to control voltage at the selected point. (V control 1 Tri) 48

59 Chapter 3 Figure 3.25: Switching signals for inverter legs The output signal of the comparator (Pbot) and the NOT operated inversion (Ptop) is fed into the inverter legs. To achieve a smooth control voltage (= injected voltage to the power line) and to filter out the unwanted higher order harmonic components from that waveform a LC filter was connected at the output of inverter Designing and tuning of the low pass filter Cut-off frequency (f) of a simple LC filter is given by the following equation. f 1 = Eq π LC Cut-off frequency should lie between the supply frequency (50Hz) and the modulating triangular waveform frequency (5000Hz). Therefore 500Hz was selected 49

60 Chapter 3 as the cut-off frequency and capacitor value was calculated assuming L = 0.6 mh. By applying L and f values to equation 3.1, the capacitor value was obtained as 168μF. But during the simulation it has been identified that with the above calculated LC values the compensated voltage could not block the harmonic up to the required level. It has been observed that by modifying the filter, the quality of the output waveform could be improved to a certain level. Therefore the filter configuration shown in Figure 3.21 was slightly modified as in Figure 3.26 to remove the harmonic effect. Figure 3.26: Low pass filter configuration For simplicity it has been assumed that the inductor value is halved for the new filter configuration, while keeping the same value for capacitance. The DVR side inductor smoothes the waveform while the grid side inductor block the harmonic injection. Further it has been observed that, better performance of the DVR could be obtained by increasing the capacitance. After comparing the results of several simulations for different Capacitances 1000μF was selected as a reasonable value. Therefore subsequent simulations the capacitance value is taken as 1000μF Voltage injection transformer Ratio of the voltage transformer was selected as 60V:240V (discussed in section 3.4.1) such that the DVR is capable of compensating the full voltage sag, provided the DC storage device is capable of supplying the full real power requirement during the compensation. Hence 100 kva rated transformer with 1:4 turns ratio was selected. 50

61 Chapter 3 Figure Specifications of the voltage injection transformer selected are shown in Figure 3.27: Configuration data of the voltage injection transformer Voltage sag generation The voltage sag was created in the distribution line by switching on a shunt connected circuit breaker together with a series reactance. This can either be a resistance, inductance or a combination. In this case for simplicity of calculations resistive fault impedance was taken for the fault and grid. This is presented in Figure

62 Chapter 3 Shunt connected circuit for voltage sag generation 0.01 BRK Vs BRK Timed Breaker Logic Open@t From the low pass filter #1 #2 Iload VInj VL Figure 3.28: Left: Generating voltage sag for the power circuit, Right: Breaker parameters From Figure 3.28 left, it is clear that the circuit breaker is initially in open position. As such there will be no sag voltage applied. To create the sag the breaker was closed at t = 5.21sec and the sag is remained for 70 msec. For further analysis the above circuit simplified as shown in Figure 3.29 Vs - Source voltage (240V rms) Rs - Source resistance (0.01 Ω) V sag - Magnitude of the voltage sag (V) V injected - Voltage injected by the DVR (V) V L - Load Voltage (V) Figure 3.29: Equivalent circuit for the distribution line Before the voltage sag, the circuit breaker is kept at open position. An open circuited path was created across the breaker. As the system is under normal condition, the DVR is not injecting any voltage to the distribution line (V injected =0V). The equivalent circuit for the above is as follows in Figure

63 Chapter 3 L s L s L L before L L s s before R R R V V R I V R R V I n n + = = + = Figure 3.30: Equivalent circuit before the voltage sag Assume a case when the voltage sag is present, but the DVR is not connected to the circuit as in Figure sag L sag L s L sag s L 2 Lsag sag L sag sag 2 sag L sag L s s sag L s s sag R R ) R (R R R R V R I V R R R I I R R R R R V ) R // (R R V I + + = = + = + + = + = Figure 3.31: Equivalent circuit during the voltage sag This analysis shows that by changing R sag parameter, the magnitude of the sag can be altered. The typical values selected for the simulation was R L =100Ω and R sag =0.01Ω. It can be seen that R L >>>>R sag. Hence, 1 1 R R sag L >>>> + Lsag V can further be simplified as follows. Ln Lsag Ln L s L s L s L s L 1 sag L s L s L sag sag L s L s Lsag V V, V R R R V R R R V R 1 R R R R V R R ) R (R R R V V hence but, < = + + < + + = + + = >>>>

64 Chapter 3 Then V period. The load voltage during the sag is less than the healthy load voltage. inj = V Ln V Lsag ; which is the voltage injected by the DVR during the sag Different sag and loading conditions The above calculations were performed assuming both the R sag and R L are resistive loads. By changing the magnitude and the type of the shunt connected fault impedance, the severity of the voltage sag can be changed. For example, if an inductive impedance is connected having the same reactance, (2πfL=R sag ), the voltage sag can be created with the same magnitude but with a phase shift. The simulations were carried out by considering the following sag and loading conditions. (i) Sag without a phase shift and the sag was created at the zero crossing point of the voltage waveform. (ii) Sag without a phase shift and the sag was created not at the zero crossing point of the voltage waveform. (iii) Sag with a phase shift and the sag was created at the zero crossing point of the voltage waveform. (iv) Sag with a phase shift and the sag was created not at the zero crossing point of the voltage waveform. The loading conditions were changed by connecting, (i) Pure resistive load of magnitude 100Ω. (ii) Pure inductive load with the same reactance. (2πfL=R L ) (iii) Combination of resistive and inductive load with a 0.8 power factor Harmonic effect During the PSCAD simulation the supply voltage maintained as a pure sinusoidal waveform. But in the practical environment this condition is no longer valid. The supply voltage contains harmonic components. To identify the harmonic 54

65 Chapter 3 components present in the supply, a harmonic analysis was carried out for practical the supply voltage using a digital power meter available in the laboratory. The measured harmonic components and their magnitudes are shown in below Table 3.1. Harmonic component Magnitude (V rms) Harmonic component Magnitude (V rms) Fundamental * * * * * * * * * * * * * * 50 0 Table 3.1 : Harmonic content in the normal supply voltage The shape of the supply waveform with healthy and with those harmonics was simulated in PSCAD and is shown in Figures 3.32 and 3.33 together with the simulation block. 55

66 Chapter 3 Voltage (kv) Voltage (kv) Supply voltage (healthy) Supply voltage (with harmonics) Time Figure 3.32: Top: Supply voltage waveform without harmonics Bottom: Supply waveform with harmonics Fundamental 2nd 3rd 4th 23rd 25th Vs Vs Supply voltage (with harmonics) Load Figure 3.33: PSCAD implementation of supply harmonics Due to the limitations in implementing all the harmonic components in PSCAD only marked * major 15 harmonics were considered for the simulation. Those harmonic components were added to the supply voltage as shown in Figure 3.43 and observed the effect on the load voltage by introducing voltage sag. 56

67 Chapter 4 Results and Discussion The simulation is carried out and the results are analyzed for different voltage sag and load conditions as discussed in chapter 3 and briefly given below. Different voltage sag conditions (i) Sag without a phase shift and the sag created at the zero crossing point of the voltage waveform. (ii) Sag without a phase shift and the sag created not at the zero crossing point of the voltage waveform. (iii) Sag with a phase shift and the sag created at the zero crossing point of the voltage waveform. (iv) Sag with a phase shift and the sag created not at the zero crossing point of the voltage waveform. The loading conditions were changed as follows. (i) Pure resistive load of magnitude 100Ω. (ii) Pure inductive load with the same reactance. (2πfL=R L ) (iii) Combination of resistive and inductive load with a 0.8 power factor. To simplify the analysis the simulations were carried out under the following different cases as shown in Table

68 Chapter 4 Sag criteria Load criteria Harmonics System Subsystem Fault [1] Phase shift [2] Start at [3] Time duration (s) [4] Load type [5] PF [6] Harmonics in the supply [7] 1a 0.01Ω-R N zc Ω-R 1 N 1b 0.01Ω-R N nzc Ω-R 1 N 1c 0.01Ω-R N nzc Ω-R 1 N 1d 0.01Ω-R N nzc Ω-R 1 N 2a 0.01Ω-R N zc Ω+0.191H-RL 0.8 N 2b 0.01Ω-R N nzc Ω+0.191H-RL 0.8 N 2c 0.01Ω-R N nzc Ω+0.191H-RL 0.8 N 2d 0.01Ω-R N nzc Ω+0.191H-RL 0.8 N 3a mH-L Y zc Ω-R 1 N 3b mH-L Y nzc Ω-R 1 N 3c mH-L Y nzc Ω-R 1 N 3d mH-L Y nzc Ω-R 1 N 4a mH-L Y zc Ω+0.191H-RL 0.8 N 4b mH-L Y nzc Ω+0.191H-RL 0.8 N 4c mH-L Y nzc Ω+0.191H-RL 0.8 N 4d mH-L Y nzc Ω+0.191H-RL 0.8 N 5a 5Ω-R N nzc Ω-R 1 N 5b 5Ω-R N nzc Ω+0.191H-RL 0.8 N 5c mH-L Y nzc Ω-R 1 N 5d mH-L Y nzc Ω+0.191H-RL 0.8 N 6a 0.01Ω-R N nzc Ω-R 1 N 6b 0.01Ω-R N nzc Ω+0.096H-RL 0.8 N 6c mH-L Y nzc Ω-R 1 N 6d mH-L Y nzc Ω+0.096H-RL 0.8 N 7a 0.01Ω-R N nzc Ω-R 1 Y 7b 0.01Ω-R N nzc Ω+0.191H-RL 0.8 Y 7c mH-L Y nzc Ω-R 1 Y 7d mH-L Y nzc Ω+0.191H-RL 0.8 Y Table 4.1: Different sag and load criteria 58

69 Chapter 4 Each system was selected in such a way that covers all possible practical situations and explained as below: [1] Describes whether the sag is resistive (R), Inductive (L) or a combination of both (RL) and the magnitude of it. [2] This specifies the sag is associated with a phase shift (Y) or not (N). This is a direct result of criteria [1] above. [3] Whether the sag has commenced at zero crossing point of the voltage (zc) or not (nzc). [4] This column indicates the duration of voltage sag. [5] The magnitude and type of load connected; resistive load (R), Inductive load (L) or a combination (RL). [6] Load power factor [7] Indicates the harmonics in the supply voltage. In the simulation, all four blocks, which were described in section 3.3 in the control circuit, is common for all the cases considered above and is shown in Figure

70 Chapter Clear 1 st Ameas Vs Zero Detector Block D st Aref Aref D + - F Ameas 0.0 A Ctrl = 1 B Ctrl * 10.0 P I F Clear Comparator A B Block 2 Ameas Vref D + - A Ctrl = 1 Aref Sin * 0.34 Vref Vs TIME F 0.0 B Ctrl Vcontrol Block 3 Block 4 Figure 4.1: Simulation draft of the control circuit blocks The power circuit in Figure 4.2, only the blocks A (fault ), B (load ), C (breaker operating conditions) and D (harmonic content in the supply) will change depending on the different cases considered in Table

71 Chapter 4 Tri Vcontrol Tri * 0.25 Vcontrol1 A B Comparator Pbot Ptop BRK C Timed Breaker Logic Open@t BRK Vs R=0 I D I D D 0.01 A Pbot Ptop Ea Eb #1 #2 VL Iload VInj R=0 I D I D B Ptop Pbot Figure 4.2: Power circuit of the DVR indicating the components change for different cases All the subsystems considered above can be identified by the parameters in the above sections A, B, C and D. 61

72 Chapter System 1 Load = 100Ω Fault = 0.01Ω Peak injected voltage during synchronization was about 11V. This is mainly due to the DVR internal voltage drop. This can also be eliminated by adding an auxiliary control to compensate the DVR internal voltage drop. Peak injected voltage just after synchronization 17V Voltage (kv) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.3: Voltage waveforms for system 1 during synchronization Voltage (kv) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.4: Voltage waveforms for system 1 when the DVR is engaged 62

73 Chapter Subsystem 1a This section shows the simulation results when fault occurred at the zero crossing voltage point without any phase shift. Sag created at, t = s Peak injected voltage during the voltage sag 135V Voltage (kv) Sub system 1a : During the sag (@ t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.5: Voltage waveforms for subsystem 1a during the neighborhood of sag Voltage (kv) Sub system 1a : During the sag (@ t= s) 0.40 Load voltage Supply voltage Vref Time Figure 4.6: Voltage waveforms for subsystem 1a during the sag 63

74 Chapter Subsystem 1b This section shows the simulation results when fault occurred at peak of the supply voltage without any phase shift. Sag created at, t = s Peak injected voltage during the first cycle after the voltage sag 230V Peak load voltage during the first cycle after the voltage sag 410V Peak injected voltage during the second cycle after the voltage sag 135V Peak load voltage during the second cycle after the voltage sag 340V Voltage (kv) Sub system 1b : During the sag (@ t= s) Supply voltage Load voltage Vinjected Time Figure 4.7: Voltage waveforms for subsystem 1b during the neighborhood of sag Voltage (kv) Sub system 1b : During the sag (@ t= s) Load voltage Vref Supply voltage Time Figure 4.8: Voltage waveforms for subsystem 1b during the sag 64

75 Chapter Subsystem 1c This section shows the simulation results when fault occurred at negative gradient point of the supply voltage without any phase shift. Sag created at, t = s Peak injected voltage during the first cycle after the voltage sag 220V Peak load voltage during the first cycle after the voltage sag 420V Peak injected voltage during the second cycle after the voltage sag 130V Peak load voltage during the second cycle after the voltage sag 335V Voltage (kv) Sub system 1c : During the sag (@ t= s) Supply voltage Load voltage Vinjected Time Figure 4.9: Voltage waveforms for subsystem 1b during the neighborhood of sag Voltage (kv) Sub system 1c : During the sag (@ t= s) Load voltage Supply voltage Vref Time Figure 4.10: Voltage waveforms for subsystem 1b during the sag 65

76 Chapter Subsystem 1d This section shows the simulation results when fault occurred at positive gradient point of the supply voltage without any phase shift. Sag created at, t = s Peak injected voltage during the first cycle after the voltage sag 186 V Peak load voltage during the first cycle after the voltage sag 375V Peak injected voltage during the second cycle after the voltage sag 134V Peak load voltage after the first cycle after the voltage sag 336V Voltage (kv) Sub system 1d : During the sag (@ t= s) Supply voltage Load voltage Vinjected Time Figure 4.11: Voltage waveforms for subsystem 1b during the neighborhood of sag Voltage (kv) Sub system 1d : During the sag (@ t= s) Load voltage Supply voltage Vref Time Figure 4.12: Voltage waveforms for subsystem 1b during the sag 66

77 Chapter System 2 Load = 80Ω+0.191H ( 0.8 lagging power factor) Fault = 0.01Ω Peak injected voltage before synchronization 11V Peak injected voltage during synchronization 15V Voltage (kv) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.13: Voltage waveforms for system 2 during synchronization Voltage (kv) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.14: Voltage waveforms for system 2 when the DVR is engaged 67

78 Chapter Subsystem 2a This section shows the simulation results when fault occurred at the zero crossing voltage point without any phase shift. Sag created at, t = s Peak injected voltage during the first cycle after the voltage sag 145V Peak load voltage during the first cycle after the voltage sag 345V Peak injected voltage during the second cycle after the voltage sag 135V Peak load voltage during the second cycle after the voltage sag 336V Voltage (kv) Sub system 2a : During the sag (@ t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.15: Voltage waveforms for subsystem 1b during the neighborhood of sag Voltage (kv) Sub system 2a : During the sag (@ t= s) 0.40 Load voltage Supply voltage Vref Time Figure 4.16: Voltage waveforms for subsystem 1b during the sag 68

79 Chapter Subsystem 2b This section shows the simulation results when fault occurred at peak of the supply voltage without any phase shift. Sag created at, t = s Peak injected voltage during the first cycle after the voltage sag 250V Peak load voltage during the first cycle after the voltage sag 420V Peak injected voltage during the second cycle after the voltage sag 175V Peak load voltage during the second cycle after the voltage sag 360V Voltage (kv) Sub system 2b : During the sag (@ t= s) Supply voltage Load voltage Vinjected Time Figure 4.17: Voltage waveforms for subsystem 2b during the neighborhood of sag Voltage (kv) Sub system 2b : During the sag (@ t= s) Load voltage Supply voltage Vref Time Figure 4.18: Voltage waveforms for subsystem 2b during the neighborhood of sag 69

80 Chapter Subsystem 2c This section shows the simulation results when fault occurred at negative gradient point of the supply voltage without any phase shift. Sag created at, t = s Peak injected voltage during the first cycle after the voltage sag 220V Peak load voltage during the first cycle after the voltage sag 430V Peak injected voltage during the second cycle after the voltage sag 180V Peak load voltage during the second cycle after the voltage sag 370V Sub system 2c : During the sag (@ t= s) Supply voltage Load voltage Vinjected Voltage (kv) Time Figure 4.19: Voltage waveforms for subsystem 2c during the neighborhood of sag Voltage (kv) Sub system 2c : During the sag (@ t= s) Load voltage Supply voltage Vref Time Figure 4.20: Voltage waveforms for subsystem 2c during the sag 70

81 Chapter Subsystem 2d This section shows the simulation results when fault occurred at positive gradient point of the supply voltage without any phase shift. Sag created at, t = s Peak injected voltage during the first cycle after the voltage sag Peak load voltage during the first cycle after the voltage sag Peak injected voltage after the first cycle after the voltage sag Peak load voltage after the first cycle after the voltage sag 190V 380V 130V 330V Voltage (kv) Sub system 2d : During the sag (@ t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.21: Voltage waveforms for subsystem 2d during the neighborhood of sag Voltage (kv) Sub system 2d : During the sag (@ t= s) 0.40 Load voltage Supply voltage Vref Time Figure 4.22: Voltage waveforms for subsystem 2d during the sag 71

82 Chapter System 3 Fault = Load = mH 100Ω Peak injected voltage before synchronization Peak injected voltage during synchronization 10V 18V Voltage (kv) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.23: Voltage waveforms for system 3 during synchronization Voltage (kv) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.24: Voltage waveforms for system 3 when the DVR is engaged 72

83 Chapter Subsystem 3a This section shows the simulation results when fault occurred at the zero crossing voltage point with a phase shift. Sag created at, t = s Peak injected voltage during the first cycle after the voltage sag 180V Peak load voltage during the first cycle after the voltage sag 330V Peak injected voltage during the second cycle after the voltage sag 190V Peak load voltage during the second cycle after the voltage sag 338V Voltage (kv) Sub system 3a : During sag (@t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.25: Voltage waveforms for subsystem 3a during the neighborhood of sag Voltage (kv) Sub system 3a : During sag (@t= s) 0.40 Load voltage Supply voltage Vref Time Figure 4.26: Voltage waveforms for subsystem 3a during the sag 73

84 Chapter Subsystem 3b This section shows the simulation results when fault occurred at peak of the supply voltage with a phase shift. Sag created at, t = s Peak injected voltage during the first cycle after the voltage sag 187V Peak load voltage during the first cycle after the voltage sag 339V Peak injected voltage during the second cycle after the voltage sag 193V Peak load voltage during the second cycle after the voltage sag 341V Voltage (kv) Sub system 3b : During sag (@t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.27: Voltage waveforms for subsystem 3b during the neighborhood of sag Voltage (kv) Sub system 3b : During sag (@t= s) 0.40 Load voltage Supply voltage Vref Time Figure 4.28: Voltage waveforms for subsystem 3b during the sag 74

85 Chapter Subsystem 3c This section shows the simulation results when fault occurred at negative gradient point of the supply voltage with a phase shift. Sag created at, t = s Peak injected voltage during the first cycle after the voltage sag 200V Peak load voltage during the first cycle after the voltage sag 338V Peak injected voltage during the second cycle after the voltage sag 188V Peak load voltage during the second cycle after the voltage sag 338V Voltage (kv) Sub system 3c : During sag (@t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.29: Voltage waveforms for subsystem 3c during the neighborhood of sag Voltage (kv) Sub system 3c : During sag (@t= s) 0.40 Load voltage Supply voltage Vref Time Figure 4.30: Voltage waveforms for subsystem 3c during the sag 75

86 Chapter Subsystem 3d This section shows the simulation results when fault occurred at positive gradient point of the supply voltage with a phase shift. Sag created at, t = s Peak injected voltage during the first cycle after the voltage sag Peak load voltage during the first cycle after the voltage sag Peak injected voltage after the first cycle after the voltage sag Peak load voltage after the first cycle after the voltage sag 200V 360V 186V 338V Voltage (kv) Sub system 3d : During sag (@t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.31: Voltage waveforms for subsystem 3d during the neighborhood of sag Voltage (kv) Sub system 3d : During sag (@t= s) 0.40 Load voltage Supply voltage Vref Time Figure 4.32: Voltage waveforms for subsystem 3d during the sag 76

87 Chapter System 4 Fault = Load = mH 80Ω+0.191H (0.8 lagging power factor) Peak injected voltage before synchronization Peak injected voltage during synchronization 10V 18V Voltage (kv) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.33: Voltage waveforms for system 4 during synchronization Voltage (kv) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.34: Voltage waveforms for system 4 when the DVR is engaged 77

88 Chapter Subsystem 4a This section shows the simulation results when fault occurred at the zero crossing voltage point with a phase shift. Sag created at, t = s Peak injected voltage during the first cycle after the voltage sag 196V Peak load voltage during the first cycle after the voltage sag 323V Peak injected voltage during the second cycle after the voltage sag 186V Peak load voltage during the second cycle after the voltage sag 330V Voltage (kv) Sub system 4a : During sag (@t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.35: Voltage waveforms for subsystem 4a during the neighborhood of sag Voltage (kv) Sub system 4a : During sag (@t= s) 0.40 Load voltage Supply voltage Vref Time Figure 4.36: Voltage waveforms for subsystem 4b during the sag 78

89 Chapter Subsystem 4b This section shows the simulation results when fault occurred at peak of the supply voltage with a phase shift. Sag created at, t = s Peak injected voltage during the first cycle after the voltage sag 185V Peak load voltage during the first cycle after the voltage sag 334V Peak injected voltage during the second cycle after the voltage sag 205V Peak load voltage during the second cycle after the voltage sag 350V Voltage (kv) Sub system 4b : During sag (@ t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.37: Voltage waveforms for subsystem 4b during the neighborhood of sag Voltage (kv) Sub system 4b : During sag (@ t= s) 0.40 Load voltage Supply voltage Vref Time Figure 4.38: Voltage waveforms for subsystem 4b during the sag 79

90 Chapter Subsystem 4c This section shows the simulation results when fault occurred at negative gradient point of the supply voltage with a phase shift. Sag created at, t = s Peak injected voltage during the first cycle after the voltage sag 215V Peak load voltage during the first cycle after the voltage sag 344V Peak injected voltage during the second cycle after the voltage sag 196V Peak load voltage during the second cycle after the voltage sag 335V Voltage (kv) Sub system 4c : During sag (@ t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.39: Voltage waveforms for subsystem 4c during the neighborhood of sag Voltage (kv) Sub system 4c : During sag (@ t= s) 0.40 Load voltage Supply voltage Vref Time Figure 4.40: Voltage waveforms for subsystem 4c during the sag 80

91 Chapter Subsystem 4d This section shows the simulation results when fault occurred at positive gradient point of the supply voltage with a phase shift. Sag created at, t = s Peak injected voltage during the first cycle after the voltage sag Peak load voltage during the first cycle after the voltage sag Peak injected voltage after the first cycle after the voltage sag Peak load voltage after the first cycle after the voltage sag 210V 360V 180V 340V Voltage (kv) Sub system 4d : During sag (@ t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.41: Voltage waveforms for subsystem 4d during the neighborhood of sag Voltage (kv) Sub system 4d : During sag (@ t= s) 0.40 Load voltage Supply voltage Vref Time Figure 4.42: Voltage waveforms for subsystem 4d during the sag 81

92 Chapter System Subsystem 5a Fault = 5 Ω Load = 100Ω Sag created at, t = s Voltage (kv) Sub system 5a : During sag (@ t= s) Supply voltage Load voltage Vinjected Time Figure 4.43: Voltage waveforms for subsystem 5a during the neighborhood of sag Subsystem 5b Fault = 5 Ω Load = 80Ω+0.191H (0.8 lagging power factor) Sag created at, t = s Voltage (kv) Sub system 5b : During sag (@ t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.44: Voltage waveforms for subsystem 5b during the neighborhood of sag 82

93 Chapter Subsystem 5c Fault = mH Load = 100Ω Sag created at, t = s Voltage (kv) Sub system 5c : During sag (@ t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.45: Voltage waveforms for subsystem 5c during the neighborhood of sag Subsystem 5d Fault = mH Load = 80Ω+0.191H (0.8 lagging power factor) Sag created at, t = s Voltage (kv) Sub system 5d : During sag (@ t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.46: Voltage waveforms for subsystem 5d during the neighborhood of sag 83

94 Chapter System Subsystem 6a Fault = 0.01 Ω Load = 50Ω Sag created at, t = s Voltage (kv) Sub system 6a : During sag (@ t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.47: Voltage waveforms for subsystem 6a during the neighborhood of sag Subsystem 6b Fault = 0.01 Ω Load = 40Ω+0.096H (0.8 lagging power factor) Sag created at, t = s Voltage (kv) Sub system 6b : During sag (@ t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.48: Voltage waveforms for subsystem 6b during the neighborhood of sag 84

95 Chapter Subsystem 6c Fault = mH Load = 50Ω Sag created at, t = s Voltage (kv) Sub system 6c : During sag (@ t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.49: Voltage waveforms for subsystem 6c during the neighborhood of sag Subsystem 6d Fault = mH Load = 40Ω+0.096H (0.8 lagging power factor) Sag created at, t = s Voltage (kv) Sub system 6d : During sag (@ t= s) 0.40 Supply voltage Load voltage Vinjected Time Figure 4.50: Voltage waveforms for subsystem 6d during the neighborhood of sag 85

96 Chapter System 7 System 7 was simulated assuming the supply voltage contains harmonic components. The magnitudes of respective harmonics were obtained using a digital power analyzer connected to the normal laboratory supply. The harmonics and its magnitudes are tabulated and described in section Subsystem 7a Fault = 0.01 Ω Load = 100Ω Supply voltage = 240V rms (contain harmonics) Sag created at, t = s Voltage (kv) Sub system 7a : During sag (@ t= s) Supply voltage Load voltage Vinjected Time Figure 4.51: Voltage waveforms for subsystem 7a during the neighborhood of sag Subsystem 7b Fault = 0.01 Ω Load = 80Ω+0.191H (0.8 lagging power factor) Supply voltage = 240V rms (contain harmonics) 86

97 Chapter 4 Voltage (kv) Sub system 7b : During sag (@ t= s) Supply voltage Load voltage Vinjected Time Figure 4.52: Voltage waveforms for subsystem 7b during the neighborhood of sag Subsystem 7c Fault = mH Load = 100Ω Supply voltage = 240V rms (contain harmonics) Sag created at, t = s Voltage (kv) Sub system 7c : During sag (@ t= s) Supply voltage Load voltage Vinjected Time Figure 4.53: Voltage waveforms for subsystem 7c during the neighborhood of sag 87

98 Chapter Subsystem 7d Fault = mH Load = 80Ω+0.191H (0.8 lagging power factor) Supply voltage = 240V rms (contain harmonics) Sag created at, t = s Voltage (kv) Sub system 7d : During sag (@ t= s) Supply voltage Load voltage Vinjected Time Figure 4.54:Voltage waveforms for subsystem 7d during the neighborhood of sag 4.8 Analysis of simulation results during different time intervals It should be noted that all the above simulations were carried out by applying the voltage sag exactly at the time duration specified in Table 4.1. Due to the technical limitations in the EMTDC/PSCAD Simulation software the simulations were carried out in time steps of 1.5sec. After the first 1.5sec the final values of the simulation will be stored in the memory as a snapshot. For the second 1.5sec time interval the simulation starts from the saved snapshot file, but the software was not upgraded to count the time from 1.5sec onwards. Instead it counts from the 0 sec onwards. 88

99 Chapter 4 In the above simulations, the systems 1 to 4 is simulated by keeping a fixed value of load and fault magnitudes, while changing the phase angles. Among those systems system 3 shows a good level of compensation for the voltage sags. It is simulated for resistive load and an inductive fault. The system 4 with inductive load and inductive sag demonstrate the next best level of compensation. Compensation in system 2 (with inductive load and resistive fault ) is comparably low. The system 5 is simulated by reducing the fault by 50%, while keeping the load unchanged. Whereas in system 6 the load is halved, without changing the fault. Simulation related to system 7 was carried out by introducing harmonics (present in the normal supply voltage) to the input voltage waveform. The simulation results are interpreted in detail in the subsequent sections During the synchronization When analyzing all the systems considered above it can be identified that there is an injected voltage of sinusoidal form of peak value 11V, during the synchronizing stage. And this will be added to the load voltage. Theoretically there shouldn t be any voltage injected to the system during synchronization until the comparator block (described in section 3.3.4) is activated. Until the control voltage is zero, voltage injected will also be zero. This injected voltage is the drop across the impedance of the power circuit components, basically the filter. This injected voltage ( 3% of the supply) is neglected assuming this drop is tolerable by the load. Further according to IEEE definitions (for voltage sag given in 2.1.1) this is considered to be a normal condition. Further at the developed stage of this DVR, this voltage drop can be eliminated by adding an additional circuit which will be explained in chapter After synchronization, before the voltage sag 89

100 Chapter 4 The DVR now is in the engaged state with the system. After the synchronization, the injected voltage is increased compared with the case before the synchronization. Theoretically there cannot be any injected voltage since the load and the supply voltage waveforms are now in the synchronized state (both in time and voltage magnitude). The same reasoning did in the previous section valid for this case too. But it can be observed that the injected voltage is slightly increased in this case due to the involvement of more power electronic components than earlier. The comparator in block 4 is switched on now. In all the above simulated systems a time period of 4sec. was allowed as the synchronization time. It can be observed after the synchronization the waveform is slightly disturbed, even though theoretically it should be a pure sinusoidal shape. Reason for this is the limitations in the EMTDC/PSCAD software. In the above simulation, the simulation time and the plot time step was set to 1 μs. If this time step is reduced the results will be more accurate and more ripple free. However, it was found that the system overall performance can be checked with these settings. For all the cases following simulation and plot time settings were used as shown in Figure Duration of a single run = 1.5 s Solution time step = 1 μs Channel plot step = 1 μs Figure 4.55: Project settings window for system 1 90

Protection from Voltage Sags and Swells by Using FACTS Controller

Protection from Voltage Sags and Swells by Using FACTS Controller Protection from Voltage Sags and Swells by Using FACTS Controller M.R.Mohanraj 1, V.P.Suresh 2, G.Syed Zabiyullah 3 Assistant Professor, Department of Electrical and Electronics Engineering, Excel College

More information

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION 1 Arsha.S.Chandran, 2 Priya Lenin 1 PG Scholar, 2 Assistant Professor 1 Electrical & Electronics Engineering 1 Mohandas College of Engineering

More information

OVERVIEW OF DVR FOR POWER QUALITY IMPROVEMENT

OVERVIEW OF DVR FOR POWER QUALITY IMPROVEMENT OVERVIEW OF DVR FOR POWER QUALITY IMPROVEMENT Shyam V. Alaspure 1, Snehal G. Vinchurkar 2, Swapnil D. Raut 1 Electronics & Telecommunication 2 Electronics & Power 3 Computer 1 Lecturer, G.H. Raisoni Polytechnic

More information

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL Saravanan.R 1, Hariharan.M 2 1 PG Scholar, Department OF ECE, 2 PG Scholar, Department of ECE 1, 2 Sri Krishna College

More information

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) VOL. 4, NO. 4, JUNE 9 ISSN 89-668 6-9 Asian Research Publishing Network (ARPN). All rights reserved. MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) Rosli Omar and Nasrudin Abd Rahim

More information

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 3 Ver. I (May Jun. 2014), PP 36-41 Analysis, Modeling and Simulation of Dynamic Voltage

More information

Literature Review for Shunt Active Power Filters

Literature Review for Shunt Active Power Filters Chapter 2 Literature Review for Shunt Active Power Filters In this chapter, the in depth and extensive literature review of all the aspects related to current error space phasor based hysteresis controller

More information

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203 Unit.2-Voltage Sag D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203 13/09/2012 Unit.2 Voltage sag 1 Unit-2 -Voltage Sag Mitigation Using

More information

Voltage Quality Enhancement in an Isolated Power System through Series Compensator

Voltage Quality Enhancement in an Isolated Power System through Series Compensator International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 12, Issue 6 (June 2016), PP.20-26 Voltage Quality Enhancement in an Isolated Power

More information

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR) Research Journal of Engineering Sciences ISSN 2278 9472 Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR) Abstract Srishti Verma * and Anupama Huddar Electrical Engineering

More information

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS 66 CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS INTRODUCTION The use of electronic controllers in the electric power supply system has become very common. These electronic

More information

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial

More information

Power Quality and the Need for Compensation

Power Quality and the Need for Compensation Power Quality and the Need for Compensation Risha Dastagir 1, Prof. Manish Khemariya 2, Prof. Vivek Rai 3 1 Research Scholar, 2,3 Asst. Professor, Lakshmi Narain College of Technology Bhopal, India Abstract

More information

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM 3.1 INTRODUCTION Static synchronous compensator is a shunt connected reactive power compensation device that is capable of generating or

More information

DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK

DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK 1 Hitesh Kumar Yadav, 2 Mr.S.M.Deshmukh 1 M.Tech Research Scholar, EEE Department, DIMAT Raipur (Chhattisgarh), India 2 Asst. Professor, EEE Department,

More information

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side 1 Jaykant Vishwakarma, 2 Dr. Arvind Kumar Sharma 1 PG Student, High voltage and Power system, Jabalpur

More information

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS SIMUATION OF D-STATCOM AND DVR IN POWER SYSTEMS S.V Ravi Kumar 1 and S. Siva Nagaraju 1 1 J.N.T.U. College of Engineering, KAKINADA, A.P, India E-mail: ravijntu@gmail.com ABSTRACT A Power quality problem

More information

Design Of An Integrated Dynamic Voltage Restorer-Ultracapacitor For Improving The Power Quality Of The Distribution Grid

Design Of An Integrated Dynamic Voltage Restorer-Ultracapacitor For Improving The Power Quality Of The Distribution Grid Design Of An Integrated Dynamic Voltage Restorer-Ultracapacitor For Improving The Power Quality Of The Distribution Grid K.Jaya Maha Lakshmi, smt M.Kumudwathi Abstract- In this paper, a new idea is presented

More information

Power Quality enhancement of a distribution line with DSTATCOM

Power Quality enhancement of a distribution line with DSTATCOM ower Quality enhancement of a distribution line with DSTATCOM Divya arashar 1 Department of Electrical Engineering BSACET Mathura INDIA Aseem Chandel 2 SMIEEE,Deepak arashar 3 Department of Electrical

More information

Power Quality Improvement using Hysteresis Voltage Control of DVR

Power Quality Improvement using Hysteresis Voltage Control of DVR Power Quality Improvement using Hysteresis Voltage Control of DVR J Sivasankari 1, U.Shyamala 2, M.Vigneshwaran 3 P.G Scholar, Dept of EEE, M.Kumarasamy college of Engineering, Karur, Tamilnadu, India

More information

Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer

Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer Deepa Francis Dept. of Electrical and Electronics Engineering, St. Joseph s College of Engineering and Technology, Palai Kerala, India-686579

More information

Performance of DVR under various Fault conditions in Electrical Distribution System

Performance of DVR under various Fault conditions in Electrical Distribution System IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 8, Issue 1 (Nov. - Dec. 2013), PP 06-12 Performance of DVR under various Fault conditions

More information

IMPROVEMENT OF VOLTAGE SAG MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR)

IMPROVEMENT OF VOLTAGE SAG MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR) IMPROVEMENT OF VOLTAGE SAG MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR) Hadi Suyono 1, Lauhil Mahfudz Hayusman 2 and Moch. Dhofir 1 1 Department of Electrical Engineering, Brawijaya University, Malang,

More information

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 98 CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE 6.1 INTRODUCTION Process industries use wide range of variable speed motor drives, air conditioning plants, uninterrupted power supply systems

More information

Investigation of D-Statcom Operation in Electric Distribution System

Investigation of D-Statcom Operation in Electric Distribution System J. Basic. Appl. Sci. Res., (2)29-297, 2 2, TextRoad Publication ISSN 29-434 Journal of Basic and Applied Scientific Research www.textroad.com Investigation of D-Statcom Operation in Electric Distribution

More information

Modelling of Dynamic Voltage Restorer for Mitigation of Voltage Sag and Swell Using Phase Locked Loop

Modelling of Dynamic Voltage Restorer for Mitigation of Voltage Sag and Swell Using Phase Locked Loop Modelling of Dynamic Voltage Restorer for Mitigation of Voltage Sag and Swell Using Phase Locked Loop Deepa Patil 1, Datta Chavan 2 1, 2 Electrical Engineering, Bharati Vidaypeeth Deemed University, Pune,

More information

Mitigation of Voltage Sag/Swell Using UPQC

Mitigation of Voltage Sag/Swell Using UPQC Mitigation of Voltage Sag/Swell Using UPQC 1 Rajat Patel, 2 Prof.Maulik A. Chaudhari 1 PG Scholar, 2 Assistant Professor Electrical Department, Government engineering college, Bhuj Gujarat Technological

More information

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE Ms. K. Kamaladevi 1, N. Mohan Murali Krishna 2 1 Asst. Professor, Department of EEE, 2 PG Scholar, Department of

More information

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013 A Statcom-Control Scheme for Power Quality Improvement of Grid Connected Wind Energy System B.T.RAMAKRISHNARAO*, B.ESWARARAO**, L.NARENDRA**, K.PRAVALLIKA** * Associate.Professor, Dept.of EEE, Lendi Inst.Of

More information

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality P.Padmavathi, M.L.Dwarakanath, N.Sharief, K.Jyothi Abstract This paper presents an investigation

More information

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System 1 G.Balasundaram, 2 Dr.S.Arumugam, 3 C.Dinakaran 1 Research Scholar - Department of EEE, St.

More information

DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY

DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY Department of Electrical Engineering Senior Design Project ELEC 499 DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY Student Names: Chresteen Baraket Marina Messiha Supervised

More information

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Modeling and Simulation of SRF and P-Q based Control DSTATCOM International Journal of Engineering Research and Development ISSN: 2278-067X, Volume 1, Issue 10 (June 2012), PP.65-71 www.ijerd.com Modeling and Simulation of SRF and P-Q based Control DSTATCOM Kasimvali.

More information

Unified Power Quality Conditioner (UPQC) using MATLAB Hiya Divyavani, Prof.(Dr.)Mohd.Muzzam Noida International University ----------------------------------------------------------------- Abstract: The

More information

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition ISSN (Online) 232 24 ISSN (Print) 232 5526 Vol. 2, Issue 7, July 24 Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition Brijesh Parmar, Prof. Shivani Johri 2, Chetan

More information

SUPERCONDUCTING MAGNETIC ENERGY

SUPERCONDUCTING MAGNETIC ENERGY 1360 IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, VOL. 20, NO. 3, JUNE 2010 SMES Based Dynamic Voltage Restorer for Voltage Fluctuations Compensation Jing Shi, Yuejin Tang, Kai Yang, Lei Chen, Li Ren,

More information

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR Rongali. Shiva Kumar P.G Student Scholar, Department of Electrical & Electronics Engineering, Gokul Group Of Institutions Abstract:

More information

Synchronous Reference Frame Theory (SRF) along with PI Controller Based Dynamic Voltage Restorer

Synchronous Reference Frame Theory (SRF) along with PI Controller Based Dynamic Voltage Restorer Research Inventy: International Journal of Engineering And Science Vol.5, Issue 5 (May 2015), PP 59-64 Issn (e): 2278-4721, Issn (p):2319-6483, www.researchinventy.com Synchronous Reference Frame Theory

More information

Series Compensation Technique for Voltage Sag Mitigation

Series Compensation Technique for Voltage Sag Mitigation IOSR Journal of Engineering (IOSRJEN) ISSN: 2250-3021 Volume 2, Issue 8 (August 2012), PP 14-24 Series Compensation Technique for Voltage Sag Mitigation 1 NAGENDRABABU VASA, 2 SREEKANTH G, 3 NARENDER REDDY

More information

p. 1 p. 6 p. 22 p. 46 p. 58

p. 1 p. 6 p. 22 p. 46 p. 58 Comparing power factor and displacement power factor corrections based on IEEE Std. 18-2002 Harmonic problems produced from the use of adjustable speed drives in industrial plants : case study Theory for

More information

Chapter 2 Shunt Active Power Filter

Chapter 2 Shunt Active Power Filter Chapter 2 Shunt Active Power Filter In the recent years of development the requirement of harmonic and reactive power has developed, causing power quality problems. Many power electronic converters are

More information

Voltage Sags in Distribution Systems with Induction Motor Loads Fed by Power Converters and Voltage Mitigation using DVR and D-STATCOM

Voltage Sags in Distribution Systems with Induction Motor Loads Fed by Power Converters and Voltage Mitigation using DVR and D-STATCOM International Journal of Electrical Engineering. ISSN 0974-2158 Volume 5, Number 7 (2012), pp. 889-902 International Research Publication House http://www.irphouse.com Voltage Sags in Distribution Systems

More information

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Design Strategy for Optimum Rating Selection of Interline D-STATCOM International Journal of Engineering Science Invention ISSN (Online): 2319 6734, ISSN (Print): 2319 6726 Volume 2 Issue 3 ǁ March. 2013 ǁ PP.12-17 Design Strategy for Optimum Rating Selection of Interline

More information

Manjeet Baniwal 1, U.Venkata Reddy 2, Gaurav Kumar Jha 3

Manjeet Baniwal 1, U.Venkata Reddy 2, Gaurav Kumar Jha 3 Application of to alleviate voltage sag and swell Manjeet Baniwal 1, U.Venkata Reddy 2, Gaurav Kumar Jha 3 123 (Electrical Engineering, AGPCE Nagpur/ RTMNU, INDIA) ABSTRACT : This paper deals with modelling

More information

SIMULATION VERIFICATION OF DYNAMIC VOLTAGE RESTORER USING HYSTERESIS BAND VOLTAGE CONTROL

SIMULATION VERIFICATION OF DYNAMIC VOLTAGE RESTORER USING HYSTERESIS BAND VOLTAGE CONTROL SIMULATION VERIFICATION OF DYNAMIC VOLTAGE RESTORER USING HYSTERESIS BAND VOLTAGE CONTROL 1 R V D Rama Rao*, 2 Dr.Subhransu Sekhar Dash, Assoc. Professor, Narasaraopeta Engineering College, Narasaraopet

More information

Power Quality improvement of a three phase four wire system using UPQC

Power Quality improvement of a three phase four wire system using UPQC International Research Journal of Engineering and Technology (IRJET) e-issn: 2395-56 Volume: 2 Issue: 4 July-215 www.irjet.net p-issn: 2395-72 Power Quality improvement of a three phase four wire system

More information

Application of Distribution Static Synchronous Compensator in Electrical Distribution System

Application of Distribution Static Synchronous Compensator in Electrical Distribution System Application of Distribution Static Synchronous Compensator in Electrical Distribution System Smriti Dey Assistant Professor, Department of Electrical and Electronics Engineering, School of Technology,

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:

More information

Voltage Variation Compensation

Voltage Variation Compensation Voltage Variation Compensation Krishnapriya M.R 1, Minnu Mariya Paul 2, Ridhun R 3, Veena Mathew 4 1,2,3 Student, Dept. of 4 Assistant Professor, Dept. of College, Kerala, India ---------------------------------------------------------------------***---------------------------------------------------------------------

More information

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side Jaykant Vishwakarma 1, Dr. Arvind Kumar Sharma 2 1 PG Student, High voltage and Power system, Jabalpur Engineering College,

More information

ISSN Vol.07,Issue.21, December-2015, Pages:

ISSN Vol.07,Issue.21, December-2015, Pages: ISSN 2348 2370 Vol.07,Issue.21, December-2015, Pages:4128-4132 www.ijatir.org Mitigation of Multi Sag/Swell using DVR with Hysteresis Voltage Control DAKOJU H V V S S N MURTHY 1, V. KAMARAJU 2 1 PG Scholar,

More information

Voltage Sag and Mitigation Using Dynamic Voltage Restorer (DVR) System

Voltage Sag and Mitigation Using Dynamic Voltage Restorer (DVR) System Faculty of Electrical Engineering Universiti Teknologi Malaysia OL. 8, NO., 006, 3 37 ELEKTRIKA oltage Sag and Mitigation Using Dynamic oltage Restorer (DR) System Shairul Wizmar Wahab and Alias Mohd Yusof

More information

Lecture 19 - Single-phase square-wave inverter

Lecture 19 - Single-phase square-wave inverter Lecture 19 - Single-phase square-wave inverter 1. Introduction Inverter circuits supply AC voltage or current to a load from a DC supply. A DC source, often obtained from an AC-DC rectifier, is converted

More information

Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM

Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM Ehsan Behrouzian 1, Massimo Bongiorno 1, Hector Zelaya De La Parra 1,2 1 CHALMERS UNIVERSITY OF TECHNOLOGY SE-412

More information

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Mr. A. S. Patil Mr. S. K. Patil Department of Electrical Engg. Department of Electrical Engg. I. C. R. E. Gargoti I. C. R. E. Gargoti

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Mitigating Voltage Sag Using Dynamic Voltage Restorer Mitigating Voltage Sag Using Dynamic Voltage Restorer Sumit A. Borakhade 1, R.S. Pote 2 1 (M.E Scholar Electrical Engineering, S.S.G.M.C.E. / S.G.B.A.U. Amravati, India) 2 (Associate Professor, Electrical

More information

Enhancement of Power Quality in Distribution System Using D-Statcom

Enhancement of Power Quality in Distribution System Using D-Statcom Enhancement of Power Quality in Distribution System Using D-Statcom Ruma Deb 1, Dheeraj Pandey 2 Gyan Ganga Institute of Technology & Sciences, Tilwara Road, RGPV University, Jabalpur (M.P) INDIA 1 ruma.deb20@gmail.com,

More information

Voltage Sag and Swell compensation using DVR to enhance Power Quality

Voltage Sag and Swell compensation using DVR to enhance Power Quality IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 12, Issue 2 Ver. III (Mar. Apr. 2017), PP 17-26 www.iosrjournals.org Voltage Sag and Swell

More information

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N. COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.Booma 2 Electrical and Electronics engineering, M.E., Power and

More information

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES 86 CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES 5.1 INTRODUCTION Distribution systems face severe power quality problems like current unbalance, current harmonics, and voltage unbalance,

More information

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER IOSR Journal of Electronics & Communication Engineering (IOSR-JECE) ISSN(e) : 2278-1684 ISSN(p) : 2320-334X, PP 68-73 www.iosrjournals.org INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE

More information

Voltage Sag Matigation in Distribution Network by Dynamic Voltage Restorer

Voltage Sag Matigation in Distribution Network by Dynamic Voltage Restorer ISSN(e): 2521-0246 ISSN(p): 2523-0573 Vol. 01, No. 11, pp: 112-121, 2017 Published by Noble Academic Publisher URL: http://napublisher.org/?ic=journals&id=2 Open Access Voltage Sag Matigation in Distribution

More information

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology Riya Philip 1, Reshmi V 2 Department of Electrical and Electronics, Amal Jyothi College of Engineering, Koovapally, India 1,

More information

A Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions

A Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions 10 th International Symposium Topical Problems in the Field of Electrical and Power Engineering Pärnu, Estonia, January 10-15, 2011 A Static Synchronous Compensator for Reactive Power Compensation under

More information

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults Enhancement of Power Quality in Distribution System Using D-Statcom for Different s Dr. B. Sure Kumar 1, B. Shravanya 2 1 Assistant Professor, CBIT, HYD 2 M.E (P.S & P.E), CBIT, HYD Abstract: The main

More information

IJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN

IJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN A novel control strategy for Mitigation of Inrush currents in Load Transformers using Series Voltage source Converter Pulijala Pandu Ranga Rao *1, VenuGopal Reddy Bodha *2 #1 PG student, Power Electronics

More information

Simulation of a Dynamic Voltage Restorer to Compensate Voltage Sag for Improving Power Quality

Simulation of a Dynamic Voltage Restorer to Compensate Voltage Sag for Improving Power Quality Simulation of a Dynamic Voltage Restorer to Compensate Voltage Sag for Improving Power Quality Vikrant singh choudhary 1, Sanjeev gupta 2, C S Sharma 3 1 Master s scholar, 2,3 Associate Professor Electrical

More information

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION POWER QUALITY A N D Y O U R B U S I N E S S A SUMMARY OF THE POWER QUALITY REPORT PUBLISHED BY THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION H YDRO ONE NETWORKS INC SEPTEMBER 2014

More information

Design and Simulation of Passive Filter

Design and Simulation of Passive Filter Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt

More information

Design and Implementation of Small -Signal model Single-Phase DVR for Voltage Sag Compensation

Design and Implementation of Small -Signal model Single-Phase DVR for Voltage Sag Compensation Design and Implementation of Small -Signal model Single-Phase DVR for Voltage Sag Compensation P.Madasamy 1, K.Ramadas 2 Assistant Professor, Department of Electrical and Electronics Engineering, Alagappa

More information

CHAPTER 2 CURRENT SOURCE INVERTER FOR IM CONTROL

CHAPTER 2 CURRENT SOURCE INVERTER FOR IM CONTROL 9 CHAPTER 2 CURRENT SOURCE INVERTER FOR IM CONTROL 2.1 INTRODUCTION AC drives are mainly classified into direct and indirect converter drives. In direct converters (cycloconverters), the AC power is fed

More information

Fast Protection of Strong Power System With Fault Current Limiters and PLL - Aided Fault Detection

Fast Protection of Strong Power System With Fault Current Limiters and PLL - Aided Fault Detection Fast Protection of Strong Power System With Fault Current Limiters and PLL - Aided Fault Detection Shaik Abdul Razak P.G. Scholar, Dept. of EEE Ch Durga Prasad P.G.Scholar, Dept. of EEE UDJV Prasad Associate

More information

Investigation of Dynamic Voltage Restorer for Compensation of Voltage Sag and Swell

Investigation of Dynamic Voltage Restorer for Compensation of Voltage Sag and Swell Investigation of Dynamic Voltage Restorer for Compensation of Voltage Sag and Swell 1 M. SURESH 2 G. RAVI KUMAR 1 M.Tech Research Scholar, Priyadarshini Institute of Technology & Management 2 Associate

More information

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller IOSR Journal of Engineering (IOSRJEN) ISSN (e): 2250-3021, ISSN (p): 2278-8719 Vol. 04, Issue 09 (September. 2014), V3 PP 11-20 www.iosrjen.org A Versatile Control Scheme for UPQC for Power Quality Improvement

More information

Volume I Issue VI 2012 September-2012 ISSN

Volume I Issue VI 2012 September-2012 ISSN A 24-pulse STATCOM Simulation model to improve voltage sag due to starting of 1 HP Induction-Motor Mr. Ajay Kumar Bansal 1 Mr. Govind Lal Suthar 2 Mr. Rohan Sharma 3 1 Associate Professor, Department of

More information

IMPORTANCE OF VSC IN HVDC

IMPORTANCE OF VSC IN HVDC IMPORTANCE OF VSC IN HVDC Snigdha Sharma (Electrical Department, SIT, Meerut) ABSTRACT The demand of electrical energy has been increasing day by day. To meet these high demands, reliable and stable transmission

More information

STUDY OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT RAJIV KUMAR SINKU

STUDY OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT RAJIV KUMAR SINKU STUDY OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT RAJIV KUMAR SINKU Department of Electrical Engineering National Institute of Technology, Rourkela May 2015 STUDY OF UNIFIED POWER

More information

Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator

Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator Priyanka Sahu Columbia Institute of Engineering and Technology, Raipur,

More information

Mitigation of Power Quality Problems Using DVR in Distribution Network for Welding Load

Mitigation of Power Quality Problems Using DVR in Distribution Network for Welding Load IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 4 Ver. I (July Aug. 2015), PP 106-112 www.iosrjournals.org Mitigation of Power Quality

More information

II. RESEARCH METHODOLOGY

II. RESEARCH METHODOLOGY Comparison of thyristor controlled series capacitor and discrete PWM generator six pulses in the reduction of voltage sag Manisha Chadar Electrical Engineering Department, Jabalpur Engineering College

More information

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p. Preface p. xv Acknowledgements p. xix Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p. 6 Power Quality Monitoring p. 7 Power

More information

Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review

Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review S.N. Bhalerao 1, P.J. Bhakre, C.O.Reddy 3 1 Student, Department of Electrical Engineering, MSS Collage Of Engineering,

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS Ramesh Kumar V 1, Dr. Dalvinder Kaur Mangal 2 1 Research Scholar, Department of Electrical Engineering, Sunrise University, Alwar 2 Asso. Prof.,

More information

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF) DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF) Rosli Omar, Mohammed Rasheed, Zheng Kai Low and Marizan Sulaiman Universiti Teknikal Malaysia

More information

A Review on Improvement of Power Quality using D-STATCOM

A Review on Improvement of Power Quality using D-STATCOM A Review on Improvement of Power Quality using D-STATCOM Abhishek S. Thaknaik Electrical (electronics & power)engg, SGBAU/DES s COET, DhamangaonRly, Maharastra,India Kishor P. Deshmukh Electrical (electronics

More information

A Five Level DSTATCOM for Compensation of Reactive Power and Harmonics

A Five Level DSTATCOM for Compensation of Reactive Power and Harmonics International Journal of Engineering Research and Development ISSN: 2278-067X, Volume 1, Issue 11 (July 2012), PP. 23-29 www.ijerd.com A Five Level DSTATCOM for Compensation of Reactive Power and Harmonics

More information

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM N.Shakeela Begum M.Tech Student P.V.K.K Institute of Technology. Abstract This paper presents a modified instantaneous

More information

Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation

Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation RESEARCH ARTICLE OPEN ACCESS Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation * G.Ravinder Reddy Assistant Professor,**M.Thirupathaiah * Assistant Professor. (Deparment of Electrical

More information

Self-Tuning PI Control of Dynamic Voltage Restorer Using Fuzzy Logic

Self-Tuning PI Control of Dynamic Voltage Restorer Using Fuzzy Logic Self-Tuning PI Control of Dynamic Voltage Restorer Using Fuzzy Logic 1 Richa Agrawal, 2 Mahesh Singh, 3 Kushal Tiwari 1 PG Research Scholar, 2 Sr. Assistant Professor, 3 Assistant Professor 1 Electrical

More information

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating P.Ankineedu Prasad 1, N.Venkateswarlu 2. V.Ramesh 3, L.V.Narasimharao 4 Assistant Professor 12 & Professor 4& Research Scholar

More information

Improvement of Power Quality Using a Hybrid Interline UPQC

Improvement of Power Quality Using a Hybrid Interline UPQC Improvement of Power Quality Using a Hybrid Interline UPQC M.K.Elango 1, C.Vengatesh Department of Electrical and Electronics Engineering K.S.Rangasamy College of Technology Tiruchengode, Tamilnadu, India

More information

International Journal of Advance Engineering and Research Development CONTROL OF REDUCED-RATING DYNAMIC VOLTAGE RESTORER

International Journal of Advance Engineering and Research Development CONTROL OF REDUCED-RATING DYNAMIC VOLTAGE RESTORER Scientific Journal of Impact Factor (SJIF): 5.71 International Journal of Advance Engineering and Research Development Volume 5, Issue 06, June -2018 e-issn (O): 2348-4470 p-issn (P): 2348-6406 CONTROL

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Mitigation of Voltage Sag/Swell by Using Battery Energy Storage DVR for Induction Motor Drive Applications

Mitigation of Voltage Sag/Swell by Using Battery Energy Storage DVR for Induction Motor Drive Applications Mitigation of Voltage Sag/Swell by Using Battery Energy Storage DVR for Induction Motor Drive Applications N.Vani Sunanda PG Student, Department of EEE, Sir C.V. Raman College of Engineering, AP, India.

More information

COOPERATIVE PATENT CLASSIFICATION

COOPERATIVE PATENT CLASSIFICATION CPC H H02 COOPERATIVE PATENT CLASSIFICATION ELECTRICITY (NOTE omitted) GENERATION; CONVERSION OR DISTRIBUTION OF ELECTRIC POWER H02M APPARATUS FOR CONVERSION BETWEEN AC AND AC, BETWEEN AC AND DC, OR BETWEEN

More information

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System Kolli Nageswar Rao 1, C. Hari Krishna 2, Kiran Kumar Kuthadi 3 ABSTRACT: D-STATCOM (Distribution Static Compensator)

More information

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM) ABHIYANTRIKI Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM) An International Journal of Engineering & Technology (A Peer Reviewed & Indexed Journal) Vol.

More information