Princo Model L4660 Series Four-Wire SmartSonic Smart Narrow-Beam Ultrasonic Level transmitter

Size: px
Start display at page:

Download "Princo Model L4660 Series Four-Wire SmartSonic Smart Narrow-Beam Ultrasonic Level transmitter"

Transcription

1 Instrumentation designed with the user in mind Instruction Manual Princo Model L4660 Series Four-Wire SmartSonic Smart Narrow-Beam Ultrasonic Level transmitter Rev 2, Sept 2011 PRINCO INSTRUMENTS INC., 1020 INDUSTRIAL BLVD., SOUTHAMPTON, PA PHONE: or FAX: WEB SITE:

2 C O N T E N T S 1 INTRODUCTION ORDER CODES TECHNICAL DATA Data of SmartSonic for liquids Accessories Maintenance and Repair INSTALLATION Liquid Level Measurement Open Channel Flow Measurement Installation & Electrical Connections PROGRAMMING Programming without Display Module Programming of the SmartSonic with the SAP-200 Programming Module PARAMETERS DESCRIPTIONS AND PROGRAMMING Measurement Configuration Current Output Relay Output Measurement Optimization Volume Measurement Flow Measuring Point Linearization Informational Parameters Additional Open Channel Flow Metering Features Test Parameters Simulation Mode Access Lock DIAGNOSTICS AND TROUBLESHOOTING / ERROR CODES SOUND VELOCITIES IN DIFFERENT GASES PARAMETER TABLE...34 L4660 Four-Wire Instruction Manual Page i Rev 2, Sept 2011 o

3 1 INTRODUCTION The SmartSonic ultrasonic level transmitters from PRINCO are excellent tools for level measurement of liquids and free-flowing solids. This manual applies to four-wire units with model numbers beginning with L4660- ST_- or L4660-SB_-. For other Princo Model L4660 Series units refer to manuals designated for Two-Wire Smartsonic and Remote Two-Wire Smartsonic. The units are available with two input power options: 85 to 255Vac and 10.5 to 40Vdc. Application The level measurement technology is based on the noncontacting ultrasonic principle. It is especially well suited for applications where, for any reason, no physical contact may be established with the material being measured. Such reasons may include corrosive attack by the process medium against the measuring device material (acids), possible contamination (sewage) or, particles of the process medium adhering to the measuring device (adhesive materials). Principle of Operation The ultrasonic level measurement technology is based on the principle of measuring the time required for the ultrasound pulses to make a round trip from the sensor to the level to be measured and back again. The sensor emits an ultrasonic pulse train and receives the reflected echoes. This intelligent electronic device processes the received signal by selecting the echo reflected by the surface and calculating the time of flight. Thus, the SmartSonic measures distance only. All other parameters, such as level, flow and volume are calculated by the unit based on this highly accurate distance measurement and on specific application data programmed into the unit by the user. The unit calculates level by subtracting the measured distance from the programmed value of the maximum measuring distance. Advanced Features The SmartSonic contains numerous features that enhance its reliability and accuracy beyond that of previous generations of ultrasonic devices. Simplified and Full Programming Modes Many basic level measurement applications can be set up using an abbreviated programming mode called Quickset. This saves the personnel involved the time required to program in the Full Parameter Access mode. The same SAP-100 plug-in display module may be used for either programming mode. The module is transportable and can be used for any number of SmartSonic units. Metric or US Engineering Units The SmartSonic may be easily set up to display either metric or US engineering units. Mathematical Algorithms for Volume and Flow The SmartSonic contains within its memory a wide array of algorithms by which it can calculate volumes based on various tank geometries, and flow rates based on various flume and weir specifications. 32-point Linearization The unit may be programmed by the user with a 32-point linearization table for applications not included in the unit s set of internal algorithms. Echo tracking and Selection The reliability of the SmartSonic is enhanced by its ability to select the correct echo if more than one echo is present. The nature of ultrasonic measurement technology is such that a device emitting an ultrasonic signal will often receive more than one return signal. The geometries of the holding vessel may diffract the return signal into different signals returning to the sensor at different times. The SmartSonic maintains a measurement window around the signal that it is tracking, disregarding other signals. If there are two signals within the measurement window, it will normally track the stronger of the two signals, but can be programmed to track the first one received. The SmartSonic can also be programmed to ignore up to two fixed objects that lie within its signal path, as well as to ignore signals within a certain proximity of the sensor or within a certain distance from the bottom of the vessel. The unit can also be set up to read accurately through atmospheres other than air. Sound travels at different speeds through different gases. This affects the accuracy of the measurement. The SmartSonic can be programmed for the sound velocity of whatever gas is present. The default setting is the sound velocity in air (343.8 m/sec, 1128 ft/sec.) Informational and Self-diagnostic Functions The SmartSonic automatically displays error codes for certain self-diagnostic functions. The codes may be interpreted according to the Error Code chart in Section 7. The SmartSonic memory also records the following information which may be read out on the SAP-100 display by the user: overall operating hours, time elapsed since last switch-on, actual temperature of transducer, and the maximum and minimum recorded temperatures of transducer. The unit will also provide data that is useful for problem diagnosis. These include the number of echoes the unit is presently receiving and the relative amplitudes of these L4660 Four-Wire Instruction Manual Page 1 of 34 Pages Rev 2, Sept 2011

4 echoes, the amplitude of the echo in the measurement window, the echo time in milliseconds and the signal to noise ratio of the echo. The SmartSonic also has a current output test whereby the unit can be programmed to put out specified currents in the range of 3.9 to 20.5 ma. Additional Flow Metering Parameters Additional flow metering parameters include headwater value and re-settable and non-re-settable totalizer values. Basic Measurement Concepts Total Beam Angle A total beam angle of 5 to 7 at 3 db is featured by most of Princo s SmartSonic transducers ensuring a reliable measurement in narrow silos with uneven side walls as well as in process tanks with various protruding objects. Furthermore, as a result of the narrow beam angle, the emitted ultrasonic signals have an outstanding focus. Deep penetration through gases, vapor and foam is ensured. Dead Band X Dead Band is a feature common to all ultrasonic level meters. The unit cannot successfully make a level reading of a material that is within a minimum distance from the transducer. It is specified as the Minimum measuring distance in the Technical Data Table. Measurement within this range cannot be interpreted. Minimum measuring distance, Xm (Close-end Blocking) Minimum measuring distance (Xm) is the distance from the transducer (determined by the design of the unit) within which measurement is not possible (dead band). This distance can be extended by programming in order to avoid possible disturbing echoes coming from fixed objects. (Close-end Blocking). Maximum measuring distance (XM) Maximum measuring distance (XM) is the greatest distance (determined by the design of the unit) which can be measured by the unit under ideal conditions. The maximum measuring distance of the actual application (H) must not be greater than XM. The unit may be programmed for a smaller maximum measuring distance in order to ignore the disturbing effects of stirrers or heaters at the bottom of the tank. D X D (meters) (meters) (feet) (inches) Diameters corresponding to a 5 beam angle. Notes on Beam Angle: The basic formula for calculating the target area of the ultrasonic beam is D=tanΘ * X where D = the diameter of the target area, X = distance from the face of the transducer to the zero level point and Θ = the beam angle of the unit (in most cases 5 degrees). The example in the above chart is calculated for a unit with a 5 degree beam angle. A distance of.122 meters has been added to the result to account for a.122m diameter transducer. As a practical matter, when determining the distance a unit should be mounted away from a sidewall or other obstruction, calculate the target diameter (D above) and divide the result by two. Make sure that the outer diameter of the transducer (not the center) is at least this far from the sidewall or obstruction. L4660 Four-Wire Instruction Manual Page 2 of 34 Pages Rev 2, Sept 2011

5 BASIC CONCEPTS AND ELEMENTS OF THE ULTRASONIC MEASUREMENT Min measuring distance (dead band) X m DEFAULT value of P05 Close end blocking (programmed value X M Max measuring distance of the device DEFAULT value of P04 Max measurement range of the device Max measuring distance of the application (H) programmed value of P04 Programmed measurement range of the application DIST= distance (measured) LEV= level calculated; H - DIST) VOL= volume (calculated from DIST P06 Far end blocking LEV) 2 ORDER CODES The order codes of the SmartSonic for liquids: Note: not all combinations are possible SmartSonic L4660- S TYPE CODE TRANSDUCER / HOUSING CODE MEASURING RANGE * CODE MOUNTING CODE SUPPLY OUTPUT CO Transmitter T PP/Aluminium A 82 ft / 25 m 2 NPT thread N 85 to 265 Vac 4 to 20m + relays 1 Transmitter with local indicator B PVDF/Aluminium B 49 ft./ 15 m # ANSI Flange A PTFE/Aluminium T 33 ft/ 10 m # ANSI Flange B 85 to 265 Vac 4 to 20m + relays + HART 3 St. St./Aluminum S 26 ft / 8 m # ANSI Flange C PP/Plastic P 20 ft./ 6 m # ANSI Flange D 10.5 to 40 Vdc 10.5 to 28 Vac 4 to 20m + relays 2 PTFE/ Plastic F 8 150# ANSI Flange E PVDF/ Plastic V 10.5 to 40 Vdc 10.5 to 28 Vac 4 to 20m + relays + HART 4 St. St./Plastic M * Units with PTFE and St. St. (stainless steel) transducers have shorter measuring ranges: see Technical Data Table. L4660 Four-Wire Instruction Manual Page 3 of 34 Pages Rev 2, Sept 2011

6 3 TECHNICAL DATA 3.1 Data of SmartSonic for liquids General data Product name Product description Transducer materials SmartSonic ST/SB-400 series Compact type ultrasonic level transmitter Polypropylene (PP) Kynar (PVDF) Teflon (PTFE) Stainless Steel (DIN , AISI SS316Ti) Housing material Plastic: PBT fiber-glass reinforced, flame-retardant (DuPont ) Process temperature Ambient temperature Pressure (Absolute) Seals Mechanical protection Power supply / Consumption Accuracy* Resolution Outputs Digital Communication Electrical connections Electrical protection Aluminum: Powder paint coated PP, PTFE and PVDF versions: -30 C to +90 C (-22ºF to +194ºF) Stainless Steel versions : -30 C to +100 C (-22ºF to +212ºF); [120 C / 248ºF for max. 2 hours] Plastic housing: -25 C to +70 C (-13ºF to +158ºF). Aluminum housing: -30 C to +70 C (-22ºF to +158ºF). With SAP-200 prog. module: -25 C to +70 C (-13ºF to +158ºF). If necessary, protect the device from over-heating from direct sunlight. Plastic versions: 0.5 to 3 bar (7.25 to 43.5 psi). Stainless steel versions: 0.9 to 1.1 bar (13.1 to 15.9 psi). PP transducer: EPDM All other transducer versions: FKM (Viton ) 1 Sensor: IP68 (submersible) Housing: IP67 (NEMA 6) High voltage version: 85 to 255 Vac / 6 VA Low voltage version: 10.5 to 40 Vdc / 3.6 W 10.5 to 28 Vac / 4 VA Galvanic isolation: protection against surge transients ± (0.2% of the measured distance plus 0.05% of the range) Depending upon the distance to be measured: < 2 m: 1 mm, 2 to 5 m: 2 mm, 5 to 10 m: 5 mm, > 10 m: 10 mm <16.4 ft:.01 ft, 16.4 ft to 32.8 ft:.02 ft, > 32.8 ft,.03 ft Analog: 4 to 20 ma into 600 Ohm, isolated protection against surge transients SPDT relay: 250 Vac, 3 Aac SPDT relay: 30 Vdc, 1 Adc Display (SAP-200): 6 digit LCD with icons and bargraph HART interface (optional) 2 x Pg16 and 2 x ½ NPT Wire cross section: 0.5 to 2.5 mm 2 (20 AWG to 13 AWG) SELV: Protection Class III Protection Class I with aluminum housing Protection Class II with plastic housing * Under optimal circumstances of reflection and stabilized transducer temperature. 1 Viton is a registered trademark of DuPont Performance Elastomers L4660 Four-Wire Instruction Manual Page 4 of 34 Pages Rev 2, Sept 2011

7 Special data of SmartSonic for liquids with PP and PVDF transducers Type ST-48- SB-48- ST-47- SB-47- ST-46- SB-46- ST-44- SB-44- ST-42- SB-42- Transducer material PP or PVDF PP or PVDF PP or PVDF PP or PVDF PP or PVDF Maximum measuring distance * [m / ft] Min. measuring distance* (Dead band) [m / ft] 6 / 20 8 / / / / / / / / / 2.0 Total beam angle (-3 db) Measuring frequency 80 khz 50 khz 60 khz 40 khz 20 khz Process connection 2 thread 2 thread 3 Flange 5 Flange 6 Flange * taken from the transducer face Special data of SmartSonic for liquids with PTFE and Stainless Steel transducers Type STT-48- SBT-48- STT-47- SBT-47- STS-46- STM-46- SBS-46- STS-44- STM-44- SBS-44- STS-42- STS-42- SBS-42- Transducer material PTFE PTFE St. St. St. St. St. St. Maximum measuring distance * [m/ft] Min. measuring distance* (Dead band) [m/ft] 5 / 16 6 / 20 7 / / / / / / / / 2.2 Total beam angle (-3 db) Measuring frequency 80 khz 50 khz 60 khz 40 khz 40 khz Process connection 2 thread 2 thread 3 Flush flange 5 Flush flange 6 Flush flange * taken from the transducer face SAP-200 Programming Module Field indication Ambient temperature 6 digits custom LCD with icons, engineering units and bargraph -25 C to +70 C (-13ºF to +158ºF) Housing material PBT fiber-glass reinforced plastic, flame-retardant (DuPont ) L4660 Four-Wire Instruction Manual Page 5 of 34 Pages Rev 2, Sept 2011

8 Dimensions (in mm) of SmartSonics for liquids L4660- S / PP, PVDF, PTFE L4660- S / PP, PVDF, PTFE L4660- S / PP, PVDF L4660- S / PP, PVDF L4660- S / PP, PVDF L4660- S S-46 - / St. St. 316 L4660- S S-44 - / St. St. 316 L4660- S S-42 - / St. St Accessories Installation and Programming Manual 2 x Pg16 cable glands SAP-200 Display Module (optional) Eview Light software, CD-ROM (HART units only) 3.3 Maintenance and Repair The SmartSonic series does not require maintenance on a regular basis. In some instances, however, the transducer may need to be cleaned of deposited material. This must be carried out gently, without scratching or pressing the surface of the transducer. Repairs during or after the warranty period are carried out exclusively by the manufacturer. The equipment sent back for repairs should be cleaned or neutralized (disinfected) by the user. L4660 Four-Wire Instruction Manual Page 6 of 34 Pages Rev 2, Sept 2011

9 4 INSTALLATION 4.1 Liquid Level Measurement POSITION The optimal position of the SmartSonic is on the radius r = (0.3 to 0.5) R of the (cylindrical) tank / silo. (Also review Notes on Beam Angle on page 3.) OBSTACLES Make sure that no in-coming flow, or objects (e.g. cooling pipes, ladders, bracing members, thermometers, etc.), or tank wall with ragged surfaces protrude into the sensing cone of the ultrasonic beam. Two fixed objects in the tank / silo that disturb the measurement can be blocked out by the appropriate programming of the SmartSonic (Parameters P29, P30) SENSOR ALIGNMENT The sensor face has to be parallel to the surface of the liquid within ± 2 to FOAM Foaming of the liquid surface may render ultrasonic level metering impossible. If possible, a location should be found, where foaming is the least (device should be located as far as possible from liquid inflow) or a stilling pipe or well should be used WIND Intensive air (gas) movements in the vicinity of the ultrasonic cone should be avoided. A strong draft of wind may "blow away" the ultrasound. Devices with lower measuring frequency (40, 20 khz) are recommended where air flow is a factor TEMPERATURE Make sure that the transmitter will be protected against overheating by direct sunshine. Sunshade FUMES / VAPORS For closed tanks containing chemicals or other liquids which create fumes and/or gases above the liquid surface, especially for outdoor tanks exposed to the sun, a strong reduction of the nominal measuring range of the ultrasonic device may occur. This must be considered during device selection. Devices with lower measuring frequency (40, 20 khz) are recommended in these cases MECHANICAL INSTALLATION When installing units with threaded transducers, be sure to grip only by the hexagonal area above the threads and avoid over-tightening. Twisting the unit by the head can cause serious damage including breaking the wire harness connection to the transducer and breaking the waterproof L4660 Four-Wire Instruction Manual Page 7 of 34 Pages Rev 2, Sept 2011

10 seal between the transducer and the head. Once installed, the head may be turned a maximum of 360 degrees to obtain best viewing angle. There is a stop which will prevent it from being turned further STAND-OFF PIPE The structure of a stand-off pipe should be rigid; the inner rim (r) where the ultrasonic beam leaves the pipe should be rounded. Princo SmartSonic Models of S-32 with plastic transducer must not be installed in standoff pipes since its transducer face has to protrude into the tank. L (mm / inches) NPT-Threaded Transducers Dmin (mm / inches) S - 49 S - 48 S / / / / / / / / / / / / / / / / / / / / / 4.7 LØ D Stainless Steel Transducers L (mm / Dmin (mm / inches) inches) S_S-46 S_S-44 S_S / / / / / /5.9 L Ø D r Flange-mounted Tranducers L (mm / Dmin (mm / inches) inches) S - 46 S / / 3.2 * 150 / 5.9 * 200 / / 3.2 * 250 / 9.8 * 300 / 11.8 * 350 / / 3.4 * 500 / / 3.5 * *For values consult your distributor. L4660 Four-Wire Instruction Manual Page 8 of 34 Pages Rev 2, Sept 2011

11 4.2 Open Channel Flow Measurement For best accuracy, install the sensor as close as possible above the expected maximum water level (see minimum measuring range). Install the device in a place defined by the characteristics of the metering channel along the longitudinal axis of the flume or weir. In some cases foam may develop on the surface. Make sure that the surface opposite to the sensor remains free of foam for proper sound reflection. With respect to measurement accuracy, the length of the channel sections preceding and following the measuring flume and their method of joining to the measuring channel section are of critical importance. Despite the most careful installation, the accuracy of flow metering will be less than that specified for distance measurement. It will be determined by the features of the flume or weir. 4.3 Installation & Electrical Connections Screw the unit into its place. Use open end wrench for tightening. Maximum torque is 20Nm. After tightening the enclosure can be rotated to the proper position. (Safety bolt prevents rotation of more than 350 degrees. The unit may be damaged by electrostatic discharge (ESD), via terminals. Thus, apply the precautions commonly used to avoid electrostatic discharge such as touching a grounded point before removing cover. Tightening, Aligning To access the wiring terminals, loosen the screw on the side of the unit and lift the hinged cover. The 4 to 20 ma signal cable the power supply cable and the output relay cable must be separated by shielding. Units with aluminum housings may be grounded either by using the grounding screw terminal on the outside of the housing, or when using a three-wire power cable, connecting the ground wire to the internal grounding screw terminal. Units with plastic housings are insulated and have no ground terminals. Thread wires through the ½ NPT or Pg16 conduit openings and fasten to appropriate terminal block connections per drawing below for AC or DC powered unit as applicable. Wiring Connections L4660 Four-Wire Instruction Manual Page 9 of 34 Pages Rev 2, Sept 2011

12 5 PROGRAMMING The SmartSonic is delivered with the following Factory Default settings: Current output, display and bargraph: LEVEL 4 ma: assigned to the minimum (0%) level 20 ma: assigned to the maximum (100%) level Error indication by the current output: hold last value Damping: 60 sec for liquids, 300 sec for solids 5.1 Programming without Display Module Programming is only possible if the SmartSonic is in Level Measuring Mode and receives valid echo i.e. ECHO LED is lit! The following can be programmed without display module: Assignment of the 4 ma to a required min. level / max. distance Assignment of the 20 ma to a required max. level / min. distance Error indication by the current output (Hold, 3.6 ma or 22 ma) Damping (10, 30 or 60 sec) Reset to the factory default Note: Current output can also be assigned in inverted mode: 4 ma = 100% (Full), 20 ma = 0% (Empty) Procedure of programming: press button in the relevant sequence and check the state of the LED s. Symbols for the states of the LED s: = LED is off, = LED is blinking, = LED is on, = LEDs are blinking alternatively = Don t care Minimum level, (0%, empty tank) assignment to 4 ma Action Led state following the action 1) Check for a valid ECHO = Valid ECHO, transmitter programmable 2) Press NEXT button steadily. Both LED s go off. 3) While still holding NEXT button, press UP button steadily. Both LED s will light. Hold until LED s off. = SmartSonic in programming mode = 4 ma assigned to the distance (see picture). 4) Release buttons = Programming completed B Use level in tank or a fix target e.g. the wall B Maximum level (100%, full tank) assignment to 20 ma Action Led state following the action 1) Check for a valid ECHO = Valid ECHO, transmitter programmable 2) Press NEXT button steadily. Both LED s go off. = SmartSonic in programming mode B B 3) While still holding NEXT button, press DOWN button steadily. Both LED s will light. Hold until LED s off. = 20 ma as signed to the distance (see picture) 4) Release buttons = Programming completed Use level in tank or a fix target e.g. the wall L4660 Four-Wire Instruction Manual Page 10 of 34 Pages Rev 2, Sept 2011

13 Error state indication by the analog signal (Check for a valid echo as above) As a result of this setting the value of the analog output will be 3.8 ma, 22 ma or the display will hold the last measured value until error ceases. Action Led state following the action 1) Press button steadily. Both LED s go off. = SmartSonic in programming mode 2) While still holding button, press DOWN, or ENTER E, or NEXT button steadily.. Both LED s will light. Hold until LED s off. hold last value = or 3.6 ma or 22 ma 3) Release buttons. = Programming completed Damping time setting (Check for a valid echo as above) Action Led state following the action 1) Press ENTER E button steadily. Both LED s go off. = SmartSonic in programming mode 2) While still holding ENTER E button, press NEXT, or UP, or DOWN button steadily. Both LED s will light. Hold until LED s off. 10 sec = or 30 sec or 60 sec 3) Release buttons. = Programming completed RESET: Returning to the default (Check for a valid echo as above) Action Led state following the action 1) Press NEXT button steadily. Both LED s go off. = SmartSonic in programming mode 2) While still holding NEXT button, press ENTER E button steadily. Both LED s will light. Hold until LED s off. = Default loaded Indication of mistakes (by LEDs) made during programming Action Led state following the action Possible correction Attempted programming Attempted programming = blinking twice = no Echo Find a valid Echo = blinking three times = no access possible With SAP-200 only See 5.2 (P99) Attempted programming = blinking four times = SmartSonic not in Level Measurement Mode With SAP-200 only See 5.2 (P01) L4660 Four-Wire Instruction Manual Page 11 of 34 Pages Rev 2, Sept 2011

14 5.2 Programming of the SmartSonic with the SAP-200 Programming Module The SmartSonic should be adjusted to the process by programming the parameters. The SAP-200 Display Module can be used to display the parameters during programming and to display measurement values during continuous operation. The SAP-200 supports two separately accessible programming modes representing 2-layers of programming complexity, depending on user choice. QUICKSET PLUG-IN DISPLAY MODULE FULL PARAMETER ACCESS QUICKSET (5.2.4) Recommended as a simple and fast way to set up the SmartSonic using 6 basic parameters labelled with easy to remember abbreviations. Engineering units for the display, metric or US. (AP) Maximum measuring distance. (H) Assignment of min level to 4 ma. (4) Assignment of max level to 20 ma. (20) Error indication by the current output. (Er) Damping time. (dt) Full Parameter Access (5.2.5) All features of the SmartSonic, labelled with parameter numbers 00 through 99, such as: Measurement configuration Outputs Measurement optimization 11 pre-programmed tank shapes for volume calculation 21 pre-programmed formula for flow metering 32-point linearization Informational and self-diagnostic features SAP-200 Display ModuleSymbols used on the LCD: Symbols used on the LCD: DIST Distance (measuring) mode LEV Level (measuring) mode VOL Volume (measuring) mode FLOW Open channel (flow metering) mode PROG - Programming mode (device under programming) RELAY C2 circuit of relay is closed T1 - TOT1 volume flow totalizer (re-settable aggregate) T2 - TOT2 volume flow totalizer (aggregate) FAIL - Measurement / device error - Level changing direction Bargraph assigned to the current output or echo strength Symbols used on the frame: M Metric system m3 cubic meters m meters cm centimeters l - liters US US calculation system ft3 cubic feet ft feet in inches gal - gallons LEDS lit: COM digital (Hart) communication ECHO presence of valid echo L4660 Four-Wire Instruction Manual Page 12 of 34 Pages Rev 2, Sept 2011

15 5.2.2 Steps of the SAP-200 Display Module Programming is performed by the pressing and releasing the relevant one or two keys (simultaneously). Single key pressing ENTER E NEXT UP DOWN Double key pressing to select parameter address and go to parameter value to save parameter value and return to parameter address to move the blinking (sign of change) of the digit to the left to increase value of the blinking digit to decrease value of the blinking digit Press the two keys simultaneously for desired programming step. Double key pressing Press the two keys simultaneously for desired programming step. yy :xxxx yy parameter address (P00 to P99) xxxx parameter value (dcba) bargraph Enter into or quit programming modes E Full Parameter Access Quickset Basic steps while parameter address is blinking E Cancel all modifications ** Return to default* Default * LOAD readout ** CANCEL readout Parameter value Basic steps while parameter value is blinking E Cancel all modifications return to parameter address* Display default value * cancellation immediately active Actual Parameter value GET LEVEL function Special function used only in level and distance measurement modes: UP + DOWN Notes: If after pressing ENTER E blinking does not spring over from the parameter address to the parameter value this means that: the parameter is either a read-out type, or the secret code prevents the modification (see P99) If the modification of the parameter value is not accepted i.e. the parameter value keeps blinking after pressing ENTER E, the modified value is either out of the range, or the code entered is not a valid code L4660 Four-Wire Instruction Manual Page 13 of 34 Pages Rev 2, Sept 2011

16 5.2.3 INDICATIONS OF THE SAP-200 AND LED STATUS (Vol/Flow) See P01 for possible readouts SAP-200 indications Depending on the measurement, one of the below symbols will be lit and the process value displayed (see P00 section 6.1). Engineering units will be indicated directly ( C, F and ma) and by the lit arrow pointing towards them on the frame DIST:distance LEV: level VOL: volume FLOW: flow T1/T2: totalized values FAIL: (blinking) Error code displayed For paging readouts the NEXT key should be pressed. The following process values can be displayed Volume / Flow if programmed so Level if programmed so Distance if programmed so Warning indications FAIL blinking Display screens can be scrolled by pressing NEXT key. To return to the screen of the selected measurement mode ENTER E key should be pressed (see P01 Section 6.1) (Distance) (Error) Temperature can be displayed by pressing UP. ( C/ F) Current output value can be displayed by pressing DOWN. LED indication (ma) Note: ECHO and COM LED s appear on both the SAP-200 module and on the face of the L4660 when no module is plugged in. ECHO LED - lit in case of valid echo. COM LED - see description of HART QUICKSET Recommended as a simple and fast way to start up SmartSonic. QUICKSET programming (aided by 6 screens) is used in uncomplicated level metering applications to set the 6 basic parameters. The other parameters can only be modified in the Full Parameter Access Mode. See 6.1 ENTER Keys (P00). Note that the QUICKSET mode modifies parameters in the Full Parameter Access memory. Locations are noted in the table. The instructions of this programming mode are also to be found on the front panel above the Display Module socket. Function E + DOWN (press for min 3 sec) Enter or exit QUICKSET programming mode UP, DOWN, NEXT Increase/decrease and move left the blinking digit UP + DOWN GET LEVEL" - display actual level measured by the SmartSonic ENTER E Save readout and step to the next screen NEXT + UP Quit Current Output Scaling without saving the modifications (CANCEL) NEXT + DOWN Display of the DEFAULT value. L4660 Four-Wire Instruction Manual Page 14 of 34 Pages Rev 2, Sept 2011

17 Screens AP :xxyy H :xxxx APplication Actions xx= select EU (European) for metric or US for US engineering units (Use UP keys) yy= indicating Li for liquids DEFAULT: US (Modifies Full Parameter Access Mode P00) / DOWN Programming of this parameter will result in loading the factory default with the corresponding engineering units. H = xxxx maximum measuring distance Distance between transducer face and tank bottom Manual: set value (Use UP / DOWN / NEXT keys) and save it (by ENTER E ) Automatic: use the GET LEVEL function (UP + DOWN ) to obtain actual measured value with level in tank or a fixed target, i.e. wall ( GET LEVEL functions only if ECHO LED is lit) and save it as above. DEFAULT: maximum measuring distance [m]. See Technical Data Table. (Modifies Full Parameter Access Mode P04) 4 ma xxxx level value assigned to 4 ma current output 4:xxxx Manual: set level value (by UP / DOWN / NEXT keys) and save it (by ENTER E ) Automatic: use the GET LEVEL function (UP + DOWN ) to display the actual measured value with level in tank or a fixed target, i.e. wall ( GET LEVEL functions only if ECHO LED is lit) and save it as above. DEFAULT: 0 m (0%, Empty tank) (Modifies Full Parameter Access Mode P10) 20 ma xxxx level value assigned to 20 ma current output 20:xxxx Er :xxxx Manual: set level value (Use UP / DOWN / NEXT keys) and save it (by ENTER E ) Automatic: use the GET LEVEL function (UP + DOWN ) to obtain actual measured value with level in tank or a fixed target, i.e. wall ( GET LEVEL functions only if ECHO LED is lit) and save it as above. DEFAULT: max. level = max. measuring distance dead band [m] (100%, Full tank). (See Technical Data Table). (Modifies Full Parameter Access Mode P11) Error indication by the current output select Hold, 3.6 ma or 22 ma (by UP key) and save it as above. DEFAULT: hold last value (Modifies Full Parameter Access Mode P12) / DOWN dt: xxxx damping time: select required damping time (by UP / DOWN key) and save it as above. DEFAULT: 60 sec (Modifies Full Parameter Access Mode P20) NOTES: Current output can also be programmed for inverted operation: 4 ma= 100% (Full), 20 ma= 0% (Empty) Description of failures can be found under the chapter 7 Error codes. L4660 Four-Wire Instruction Manual Page 15 of 34 Pages Rev 2, Sept 2011

18 5.2.5 FULL PARAMETER ACCESS Full Parameter Access is the highest programming level. It accesses all features provided by the SmartSonic. Description of all parameters can be found under the chapter Parameters Description and Programming (Chapter 6.). Keys ENTER E + NEXT (press for 3 seconds) To enter or exit the Full Parameter Access programming mode: Function Enter or exit Full Parameter Access programming mode. In this programming mode, the display will indicate: yy :xxxx yy Parameter Address (P00 to P99) xxxx Parameter Value (dcba) bargraph Note: Measuring is going on during programming in accordance with the old parameter set. The new parameter set will be valid after returning to the Measurement Mode. ENTER E Steps and indications of the Full Parameter Access programming mode: pressing Keys while Parameter Address is blinking while Parameter Value is blinking Go to the Parameter Value NEXT + UP Cancel all modifications of the actual programming phase. Pressing for 3 sec is required while CANCEL will be displayed for warning. NEXT + DOWN Reset entire device to Factory Default. NEXT Since this action will reset all parameters, LOAD will appear on the display: - to confirm, press E - to escape, press any other key - Exception: clearing TOT 1 (See P77.) Move blinking (changeability) of the digit to the left. Save the modification of the Parameter Value and return to the Parameter Address. Neglect the modification of the Parameter Value and return to the Parameter Address without saving the modifications. Display default of the Parameter Values. (It can be saved by pressing ENTER E ). UP / DOWN Modify the blinking digit (increase, decrease) or scroll up/down. L4660 Four-Wire Instruction Manual Page 16 of 34 Pages Rev 2, Sept 2011

19 6 PARAMETERS DESCRIPTIONS AND PROGRAMMING 6.1 Measurement Configuration P00: - cba Application/Engineering Units Programming of this parameter will result in loading the factory default with the corresponding engineering units. a Operating (measurement) mode Display indication 0 Liquid level measurement Li 1 Free flowing solids level measurement So Engineering units b (according to c ) Metric US 0 m ft 1 cm inch Attention: mind the sequence! When programming this parameter the right value a will be blinking first. Examples: 110 US, inches, liquid 000 metric, meters, liquid c Calculation system 0 Metric 1 US FACTORY DEFAULT: 000 P01: - ba Measurement Mode, Bargraph Parameter value a will determine the basic measurement value that will be displayed proportional with the current output. Depending on the value of a, process values as listed in the 4th column (Displayed values) can also be displayed by pressing NEXT. Tor return to the display of the basic value the ENTER E key should be pressed. a Measurement Mode Display symbol Displayed values 0 Distance DIST Distance 1 Level LEV Level, Distance 2 Level in percentage LEV% Level%, Level, Distance 3 Volume VOL Volume, Level, Distance 4 Volume in percentage VOL% Volume%, Volume, Level, Distance 5 Flow FLOW Flow, TOT1, TOT2, Level, Distance Attention: mind the sequence! When programming this parameter the right value a will be blinking first. Parameter value b will determine whether the height of the bargraph will be proportional to the current output or to the echo strength. b Bargraph indication 0 Echo strength 1 Current output FACTORY DEFAULT: 11 P02: - cba Calculation units a Temperature Attention: mind the sequence! 0 C When programming this parameter the right 1 F value a will be blinking first. This table is interpreted according to P00(c), P01(a) & P02(c) and is irrelevant in case of percentage measurement ( P01(a)= 2 or 4 ). b Volume Weight (set also P32) Volume flow Metric US Metric US Metric US 0 m 3 ft 3 - lb (pound) m 3 /time ft 3 /time 1 liter gallons tons tons liter/time gallons/time c Time 0 Sec 1 Min 2 Hour 3 Day FACTORY DEFAULT: 000 L4660 Four-Wire Instruction Manual Page 17 of 34 Pages Rev 2, Sept 2011

20 P03: a Values Displayed-Rounding It is important to keep in mind that the instrument is measuring distance as basic quantity. Measured distance X min 2m 2m 5m 5m 10m over 10m Displayed VOL or FLOW Resolution 1mm 2mm 5mm 10mm Displayed value Displayed form x.xxx xx.xx xxxx xxxxx xxxxxx. x.xxxx : e 1 million *10 9 (exponential form) over 1*10 10 (overflow) Err4 Rounding Parameter value a Steps in the displayed value 0 1 no rounding The resolution depending on the distance can be considered as a kind of rounding that will be contained in all further values (of level, volume or volume flow) calculated. Therefore if programmed for DIST or LEV measurement the setting of P03 is irrelevant. Obviously the decimal position will be shifted with increasing value displayed. (See table at the left). Values over one million will be displayed in exponential format where the value e represents the exponent. Over the value of 1x10 10 Err4 (overflow) will be displayed. A couple of millimeters of fluctuation of the basic DIST value (e.g. due to waves) will be enlarged by the mathematical operations. This enlarged fluctuation in displaying VOL or FLOW can (if disturbing) be avoided by rounding to be set in P03. Rounding value 2, 5, 10 etc represents the steps by which the calculated value will be changed in its (one or two) last digit(s). Examples: P03=1 steps by 2: 1,000; 1,002; 1,004 P03=5 steps by 50: 1,000; 1,050; 1,100 or 10,00; 10,05(0); 10,10(0); 10,15(0) (the 0 from the steps 50, 100, 150 etc will not be displayed) FACTORY DEFAULT: 0 P04: Maximum measuring distance The maximum distance to be measured is the greatest distance between the surface of the transducer and the level to be measured. This is the only parameter that has to be programmed for each application other than distance. (However, to avoid the disturbing effects of possible multiple echoes, it is recommended to do this for distance measurement applications also.) Values of the maximum measuring distance will be displayed as below. The DEFAULT value of P04 (see table below) can also be displayed by double key pressing NEXT + DOWN. Engineering Unit Display Format m x.xxx or xx.xx cm xxx.x ft xx.xx or xxx.x inch xxx.x The factory programmed DEFAULT values the greatest distances which can be measured by the units - are listed in the table below. For the actual application, the maximum distance to be measured, i.e. the distance between the sensor and the bottom of the tank, should be entered in P04. To obtain the best accuracy, measure this distance in the empty tank with the SmartSonic by using the GET LEVEL function (by double key pressing of UP + DOWN ), provided the bottom is flat. Enter the actual measured value displayed as P04. L4660 Four-Wire Instruction Manual Page 18 of 34 Pages Rev 2, Sept 2011

21 SmartSonic Transducer material PP / PVDF Maximum measuring distance [m/ft] Transducer material PTFE Transducer material Stainless Steel S-38 6 / 20 5 / S-37 8 / 26 6 / S / / 23 S / / 39 S / / 49 Keep in mind that LEVEL (as the result of the measurement) = P04 (programmed) DISTANCE (measured by the device) The accuracy of level and all further calculated values depend on the accuracy of the maximum measuring distance of the application which is the distance between the sensor face and the tank / silo bottom. P05: Minimum measuring distance (Close-end blocking) The SmartSonic will not accept any echo within the blocking distance set here. Automatic Close-end-blocking (Automatic Dead Band control) By using the factory default value, the unit will automatically set the smallest possible close-end-blocking distance, i.e. the dead band. Manual close-end-blocking Manual close-end-blocking would be used, for example, to block out the echo originating from the bottom rim of a stand-off pipe or from any object protruding into the ultrasonic cone near the transmitter. By entering a value higher than the factory default, the minimum measuring range will be extended and fixed to the specified value. To display factory default of the minimum measuring distance press NEXT + DOWN. SmartSonic Transducer material PP / PVDF Minimum measuring distance [m/ft] Transducer material PTFE Transducer material Stainless Steel S / / S / / S / / 1.3 S / / 1.8 S / / 2.2 FACTORY DEFAULT: automatic dead band control per above table P06: Far-end blocking Far end blocking is used to ignore incorrect level/volume readings and output actions below a pre-set level programmed into P06. A). Level measurement The far-end blocking can be used to avoid disturbing effects of stirrer or heaters at the bottom of the tanks. ma 20 ma 4 ma If the level of the medium sinks below the blocked out range: - Sub 0 will be indicated for the level and volume. - Distance value is not interpretable. - Current output will hold the value corresponding to the far end blocking level. Level Volume "SUB 0" indication below this level P06 Far end blocking If the medium level is above the blocked out range: The calculation of level and volume will be based on the programmed tank dimensions. Therefore the measured or calculated process values will not be influenced in any way by the far end blocking value. L4660 Four-Wire Instruction Manual Page 19 of 34 Pages Rev 2, Sept 2011

22 B). Open channel flow metering Far end blocking will be used for those small levels below which the accurate volume flow calculation is no longer possible. If the liquid level in the flume/weir falls below the blocked out range: The SmartSonic will act as follows: - Indicate No Flow on the Display. - Hold last valid data on the current output. If the level in the flume/weir is above the blocked out range: The calculation of volume flow will be based on the programmed flume/weir data; therefore the measurement values will not be influenced in any way, by the far end blocking value. FACTORY DEFAULT: Current Output P10: Value (of distance, level, volume or flow) assigned to 4 ma current output P11: Value (of distance, level, volume or flow) assigned to 20 ma current output Values are interpreted according to P01(a) and P02 (b & c). Level or Volume %: Please note that in case of programming for (LEV or VOL) % measurement, the min and max values have to be entered in the relevant engineering units of LEV (m, ft) or VOL (m 3, ft 3 ). Maximum Value: The largest number that can be entered into these parameters is Certain volume and flow applications may exceed this value. Therefore it may be necessary to convert the value to a workable unit of measure. For example, it may be necessary to convert gallons/hour to cubic feet/hour, or to convert liters to cubic meters in order to have a value of 9999 or less. This will require also making the equivalent change in P02. Inverse Proportion: Assignment can be made such that the relationship between the change of the (measured or calculated) process values and the change of the current output will be either direct or inverse. E.g., level of 1 m assigned to 4mA and level of 10 m assigned to 20 ma represents direct proportion and level of 1 m assigned to 20 ma and level of 10 m assigned to 4 ma represents the inverse proportion. FACTORY DEFAULT: P10 0 level (max distance) P11 max level (min distance) H P12: a Error indication by the current output In case of error the SmartSonic will provide one of the current outputs below. (For errors and their interpretation see Chapter 7). This parameter may be set to meet the alarm needs of the particular application. a 0 Hold last value ma 2 22 ma FACTORY DEFAULT: 0 ERROR INDICATION L4660 Four-Wire Instruction Manual Page 20 of 34 Pages Rev 2, Sept 2011

23 6.3 Relay Output P13: a Relay function a Relay function Also set: 0 DIFFERENTIAL LEVEL CONTROL (Hysteresis control) Relay is energized if the measured or calculated value exceeds the value set in P14 Relay is de-energized if the measured or calculated value descends under the value set in P15 P14, P15 There is a need to set (in level min 20mm) hysteresis between P14 and P15 1 Relay is energized in case of Echo Loss - 2 Relay is de-energized in case of Echo Loss - 3 COUNTER Used for open channel flow metering. A 140 msec pulse is generated every 1, 10, 100, or m 3 according to P16. In de-energized state of the device the C1 circuit is closed. The relay LED is on when the C2 circuit is closed. FACTORY DEFAULT: 2 P14: Relay parameter Setpoint value FACTORY DEFAULT: 0 P15: Relay parameter Setpoint value FACTORY DEFAULT: 0 P16: Relay parameter Pulse rate FACTORY DEFAULT: Measurement Optimization P16= 0: 1m 3 P16= 1: 10 m 3 P16= 2: 100 m 3 P16= 3: m 3 P16= 4: m 3 P20: a Damping Use this parameter to reduce unwanted fluctuation of the display and output. a Damping LIQUIDS FREE FLOWING SOLIDS time None/moderate Heavy/dense fume or Granules Powders (seconds) fume or waves turbulent waves >2-3 mm < 2-3 mm 0 no filter Recommended for testing only 1 3 applicable not recommended not applicable not applicable 2 6 recommended not recommended not applicable not applicable 3 10 recommended recommended not applicable not applicable 4 30 recommended recommended not applicable not applicable 5 60 recommended recommended applicable applicable applicable applicable recommended recommended applicable applicable recommended recommended not applicable not applicable recommended recommended not applicable not applicable applicable applicable FACTORY DEFAULT: for Liquids: 60 sec, for Solids: 300 sec P22: a Dome top tank compensation To reduce disturbing effect of possible multiple echoes. a Compensation Applied 0 OFF In case the SmartSonic is mounted not in the center of the top and the top is flat. 1 ON In case the SmartSonic is mounted in the center of a tank with dome-shaped top FACTORY DEFAULT: 0 L4660 Four-Wire Instruction Manual Page 21 of 34 Pages Rev 2, Sept 2011

24 P23: a Angle of repose (repose formation) only for free flowing solids applications This parameter provides information for the QUEST+ software for optimizing the echo-search pattern. a Estimated angle of repose 0 No angle of repose (default) 1 Below 15 (α) 2 Over 15 (α) The optimal setting of this parameter can be achieved by monitoring parameter P72. Parameter P72 indicates the echo amplitude in db. The ideal setting of P23 is that at which the parameter value in P72 becomes the best (nearest 0). 1). Set P23 for a= 1, confirm it with [E] and switch to Measurement Mode then return to Programming Mode. 2). Observe the change of echo amplitude in P72 and record an average value. 3). Perform the above with the P23 = 2 setting. 4). Finally set P23 with the value of (a) at which the amplitude value in P72 is nearest to 0. FACTORY DEFAULT: 0 P24: a Target tracking speed a Tracking speed Remark 0 Standard For most applications 1 Fast For fast changing level 2 Special Only for special applications (measuring range is reduced to 50% of the nominal value). The measuring window is inactive and the SmartSonic will respond practically instantly to any target. Recommended to fast target tracking, but usually not applicable for level metering. FACTORY DEFAULT: 0 P25: a Selection of Echo within the measuring window A so-called measuring window is formed around the echo signal. The position of this measuring window determines the flight time for calculation of the distance of the target. (The picture below can be seen on a test oscilloscope.) Received signal amplitude Echo 1. Echo 2. "t" ultrasound flight time t Some applications involve multiple (target + disturbing) echoes even within the measuring window. Basic echo selection will be done by the Quest + software automatically. This parameter only influences the echo selection within the measuring window. a Echo in the window to be Remark selected 0 With the highest amplitude For most applications (both with liquids and solids) 1 First one For liquids applications with multiple echoes within the Measuring Window 2 Largest one Recommended for certain free flowing solids applications FACTORY DEFAULT: 0 L4660 Four-Wire Instruction Manual Page 22 of 34 Pages Rev 2, Sept 2011

25 P26: (m/h) Level elevation rate (filling speed) Very heavy fuming P27: (m/h) Level descent rate (emptying speed) Very heavy fuming These parameters provide additional protection against echo loss in applications involving very heavy fuming. The parameters must not be smaller than the fastest possible filling/emptying rate of the actual technology. For all other applications, use the factory default setting. FACTORY DEFAULT: 2000m/h or 6562ft/h for both P26 and P27 P a Echo-loss handling a Echo-loss error indication Remark 0 Delayed During echo-loss, display and analog output will hold last value. If the echo-loss prevails for 10 sec plus the time period set in P20 (damping time), the reading on the display will change to "no Echo" and the outputs will change according to the "Error Indication Mode" preset in P12. 1 None For the time of echo-loss, display and analog output will hold last value. 2 Advance to full During echo-loss in case of filling, the reading on the display and analogue output will shift towards the "full" tank/silo state with a level elevation rate (filling speed) preset in P26 3 Immediate In case of echo-loss, the display will immediately change to no Echo and the outputs will change according to the "Error Indication Mode" preset in P12. 4 No echo-loss indication in case of empty tank/silo Echo-loss may occur in completely empty tanks with a spherical bottom due to deflection of the ultrasonic beam, or in case of silos with an open outlet. If the echo is lost when the tank/silo is completely empty, the indication will correspond to empty tank, in all other cases echo-loss indication will function according to the Delayed. FACTORY DEFAULT: 0 P29 Blocking out of object #1 P30 Blocking out of object #2 Up to two fix objects in the tank/silo that disturb the measurement can be blocked out. Enter the distance of the object from the transducer. Use the Echo Map (P70) to read out the precise distance of disturbing objects. FACTORY DEFAULT: 0 P31: Sound velocity at 20 C (m/sec or ft/sec depending on P00(c) ) Use this parameter if the sound velocity in the gases above the measured surface differs largely from that of in air. Recommended for applications where the gas is more or less homogeneous. If it is not, the accuracy of the measurement can be improved using the 32-point linearization (P48, P49). For sound velocities in various gases see section 8, Sound Velocities. FACTORY DEFAULT: Metric (P00: EU ): m/s, US (P00: US ): 1128 ft/s P32: Weight If you enter a value (other than 0 ) in this parameter, the weight will be displayed instead of VOL. In order to display weight instead of volume, enter the weight per unit volume of the process material. The units of volume, as defined by P00 and P02, must be either m 3 or ft 3. Thus the number entered must be in either kg/m 3 or lb/ft 3. The volume will be multiplied by the value entered. This parameter will not function when the units are set to read gallons or liters. FACTORY DEFAULT: 0 [kg/m 3 ] or [lb/ft 3 ] depending on P00(c) and P02(b) must be set to 0. L4660 Four-Wire Instruction Manual Page 23 of 34 Pages Rev 2, Sept 2011

INSTALLATION and PROGRAMMING MANUAL

INSTALLATION and PROGRAMMING MANUAL INSTALLATION and PROGRAMMING MANUAL 3 rd edition Manufacturer: NIVELCO Process Control Co. H-1043 Budapest, Dugonics u. 11. Phone.: (36-1)-369-7575 Fax: (36-1)-369-8585 e-mail:sales@nivelco.com http://www.nivelco.com

More information

Princo Model L4660 Series SmartSonic for Free-Flowing Solids

Princo Model L4660 Series SmartSonic for Free-Flowing Solids Instrumentation designed with the user in mind Instruction Manual Princo Model L4660 Series SmartSonic for Free-Flowing Solids Smart Narrow-Beam Ultrasonic Level transmitter Rev. 1, 31 Aug 07 PRINCO INSTRUMENTS

More information

Ultrasonic level indicator type INOWAFE

Ultrasonic level indicator type INOWAFE General description KFG s two decades of experience with ultrasonic level metering is an asset we gladly share with our customers. A specialised team of experts is working day by day to convert this experience

More information

EchoTREK. SE/SG-300 series two-wire compact ultrasonic level transmitters

EchoTREK. SE/SG-300 series two-wire compact ultrasonic level transmitters EchoTREK SE/SG-300 series two-wire compact ultrasonic level transmitters Manufacturer: NIVELCO Process Control Co. H-1043 Budapest, Dugonics u. 11. Phone: (36-1) 889-0100 Fax: (36-1) 889-0200 E-mail: sales@nivelco.com

More information

EchoTREK. S-300 compact ultrasonic level transmitter series for free flowing solids

EchoTREK. S-300 compact ultrasonic level transmitter series for free flowing solids EchoTREK S-300 compact ultrasonic level transmitter series for free flowing solids Manufacturer: NIVELCO Process Control Co. H-1043 Budapest, Dugonics u. 11. Phone: (36-1) 889-0100 Fax: (36-1) 889-0200

More information

EchoTREK. SE/SG-300 series two-wire compact ultrasonic level transmitters

EchoTREK. SE/SG-300 series two-wire compact ultrasonic level transmitters EchoTREK SE/SG-300 series two-wire compact ultrasonic level transmitters Manufacturer NIVELCO Process Control Co. H-1043 Budapest, Dugonics u. 11. Phone: (36-1) 889-0100 Fax: (36-1) 889-0200 E-mail: sales@nivelco.com

More information

NUS-4. Ultrasonic Level Transmitter. for Liquids and Solids

NUS-4. Ultrasonic Level Transmitter. for Liquids and Solids Ultrasonic Level Transmitter for Liquids and Solids measuring monitoring analyzing 4 Measuring Ranges: Liquids: Up to 25 meters (80 feet) Solids: Up to 10 meters (32 feet) Accuracy: ± 0.2 % of Reading

More information

PROGRAMMING MANUAL For SCA-3!!-4 models with HART

PROGRAMMING MANUAL For SCA-3!!-4 models with HART PROGRAMMING MANUAL For SCA-3!!-4 models with HART 1 st edition Manufacturer: NIVELCO Process Control Co. H-1043 Budapest, Dugonics u. 11. Tel.: (36-1)-369-7575 Fax: (36-1)-369-8585 E-mail:sales@nivelco.hu

More information

EchoTREK. ST/SB-400 series four-wire compact ultrasonic level transmitters. Installation and Programming Manual. 2 edition

EchoTREK. ST/SB-400 series four-wire compact ultrasonic level transmitters. Installation and Programming Manual. 2 edition EchoTREK ST/SB-400 series four-wire compact ultrasonic level transmitters Installation and Programming Manual nd 2 edition Manufacturer NIVELCO Process Control Co. H-1043 Budapest, Dugonics u. 11. Phone:

More information

INSTALLATION and PROGRAMMING MANUAL

INSTALLATION and PROGRAMMING MANUAL INSTALLATION and PROGRAMMING MANUAL 7 th edition 0408 Manufacturer: HiTECH Technologies, Inc./NIVELCO Process Control Co. 301 Oxford Valley Road, Bldg 505, Yardley, PA 19067 USA Tel.: 215. 321. 6012 Fax:

More information

Instruction manual Ultrasonic Level Transmitter

Instruction manual Ultrasonic Level Transmitter Instruction manual 2260 Ultrasonic Level Transmitter Content 1. Safety and responsibility... 3 1.1 Intended use... 3 1.2 Safety regulations for the Ex approved units... 3 2. Transport and storage... 3

More information

Various Technics of Liquids and Solids Level Measurements (Part 4)

Various Technics of Liquids and Solids Level Measurements (Part 4) (Part 4) In part one of this series of articles, level measurement using a floating system was discusses and the instruments were recommended for each application. In the second part of these articles,

More information

SuperMini SonicLaser

SuperMini SonicLaser INSTRUCTION MANUAL SuperMini SonicLaser Ultrasonic Level Transmitter HiTECH Technologies, Inc. 301 Oxford Valley Road - Building 505A - Yardley, PA 19067-7706 Tel: 215. 321. 6012; Fax: 215. 321. 6067 Tech

More information

INSTALLATION and PROGRAMMING MANUAL

INSTALLATION and PROGRAMMING MANUAL INSTALLATION and PROGRAMMING MANUAL 1 st edition HiTECH/NIVELCO Process Control Co. 301Oxford Valley Road, Bldg 505, Yardley, PA 19067 Tel: (215) 321-6012 Fax: (215) 321-6067 E-mail:info@hitechtech.com

More information

Instruction Manual for Ultrasonic Level Meter. Model: NUS-4...

Instruction Manual for Ultrasonic Level Meter. Model: NUS-4... Instruction Manual for Ultrasonic Level Meter Model: NUS-4... 1. Contents 1. Contents... 2 2. Note... 4 3. Instrument Inspection... 4 4. Regulation Use... 4 5. Operating Principle... 5 6. Mechanical connection...

More information

Ultrasonic level transmitter, non-contact

Ultrasonic level transmitter, non-contact Ultrasonic level transmitter, non-contact Type 8175 can be combined with... Compact, remote versions for level measurement up to 10 m Multi language menu control Interference echo filter Automatic calibration:

More information

KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB

KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh PA 15205 Phone (412) 788-2830 Fax (412)-788-4890 Manual-NEO_5003-4_1-17

More information

The transducer component converts the measured signal and displays the actual value.

The transducer component converts the measured signal and displays the actual value. Digital inductive conductivity transmitter System Integration Provides low Total Cost of Ownership PEEK/PPA version for CIP applications TEACH IN and SIMULATION Function Approval PVDF Version PEEK Version

More information

prosonic T FMU230, FMU231

prosonic T FMU230, FMU231 Technical Information prosonic T FMU230, FMU231 Ultrasonic Level Measurement Compact transmitters for non-contact level measurement of fluids and coarse bulk materials Application The compact transmitters

More information

Echotel Model 338 Non-Contact Ultrasonic Two-Wire Transmitter for Level, Volume, or Open Channel Flow

Echotel Model 338 Non-Contact Ultrasonic Two-Wire Transmitter for Level, Volume, or Open Channel Flow Echotel Model 338 Non-Contact Ultrasonic Two-Wire Transmitter for Level, Volume, or Open Channel Flow DESCRIPTION Echotel Model 338 is a two-wire, loop-powered noncontact transmitter for liquid level,

More information

Main features. Operation. LEVEL Transmitters

Main features. Operation. LEVEL Transmitters Non-contact microwave level transmitters pilotr GNRAL DSCRIPTION The 25 GHz (-band) Pulse Radars are regarded as the most progressive non-contact level transmitters of the industrial process automation

More information

Operation. LEVEL Transmitters

Operation. LEVEL Transmitters Ultrasonic compact level transmitters for liquids echork GNRL DSCRIPION he high performance level transmitters are based on NIVLCO s 30 years of experience with ultrasonic level measurement. Whether for

More information

U Series Non-Contact Ultrasonic Transmitter

U Series Non-Contact Ultrasonic Transmitter U Series Non-Contact Ultrasonic Transmitter Form 1035 This new SOR Ultrasonic Transmitter is a proven solution offering more flexibility and reliability than similar transmitters. With unique features,

More information

LST400 Ultrasonic level / open channel flow transmitter

LST400 Ultrasonic level / open channel flow transmitter Data sheet DS/LST400 EN Rev.C LST400 Ultrasonic level / open channel flow transmitter Measurement made easy Reduced installation cost Easy access terminations Integrated echo display makes for easy troubleshooting

More information

Georg Fischer Piping Systems Point, Ultrasonic & Radar Level Products

Georg Fischer Piping Systems Point, Ultrasonic & Radar Level Products Georg Fischer Piping Systems Point, Ultrasonic & Radar Level Products Presented to valued clients attending the Technology Summit hosted by: Kendall Group/ J.O.Galloup +GF+ Offering Level Measurement Continuous

More information

Mobrey Ultrasonic. MSP422, MSP400RH, and MSP900GH Level Transmitters. Product Data Sheet February 2015 IP2045, Rev EA

Mobrey Ultrasonic. MSP422, MSP400RH, and MSP900GH Level Transmitters. Product Data Sheet February 2015 IP2045, Rev EA Mobrey Ultrasonic Product Data Sheet February 215 IP245, Rev EA MSP422, MSP4RH, and MSP9GH Level Transmitters Non-contacting measurement with no moving parts Integral LCD and push-buttons as standard for

More information

solids ULTRASONIC LEVEL METERS FOR COMPACT TRANSMITTERS TWO-PART MEASURING SYSTEM EchoTREK NIVOSONAR Excellent sensor focusing: 5 total beam angle

solids ULTRASONIC LEVEL METERS FOR COMPACT TRANSMITTERS TWO-PART MEASURING SYSTEM EchoTREK NIVOSONAR Excellent sensor focusing: 5 total beam angle ULTRASONIC LEVEL METERS Compact Transmitters: STD, SBD 300 series Two part Systems: SID and SM 300 series FOR solids COMPACT TRANSMITTERS EchoTREK MODBUS Excellent sensor focusing: 5 total beam angle Highly

More information

LPU-2127 User Manual

LPU-2127 User Manual LPU-2127 User Manual Doc #9004169 Rev A1, 04/15 Table of Contents Introduction... iii Warranty and Warranty Restrictions... iv Chapter 1: Specifications and Options... 1 Dimensions...1 Specifications...

More information

SP-300, SP-300 series t wo-wire compact ult rasonic level t ransmit t er

SP-300, SP-300 series t wo-wire compact ult rasonic level t ransmit t er SP-300, SP-300 series t wo-wire compact ult rasonic level t ransmit t er INSTALLATION AND PROGRAMMING MANUAL 2 nd edition 0408 HiTECH/NIVELCO 301 Oxford Valley Road, Bldg 505, Yardley, PA 19067 Tel.: (215)

More information

ABB MEASUREMENT & ANALYTICS DATA SHEET. Ultrasonic level LST400 Open channel flow transmitter

ABB MEASUREMENT & ANALYTICS DATA SHEET. Ultrasonic level LST400 Open channel flow transmitter ABB MEASUREMENT & ANALYTICS DATA SHEET Ultrasonic level LST400 Open channel flow transmitter 2 ULTRASONIC LEVEL LST400 / OPEN CHANNEL FLOW TRANSMITTER DS/LST400 EN REV. D Measurement made easy Reduced

More information

Model Sono-Trak Transit Time

Model Sono-Trak Transit Time Model Sono-Trak Transit Time Ultrasonic Flow Meter Engineered for performance excellence, the Sono-Trak Transit Time ultrasonic meter combines non-invasive, bi-directional measurement with advanced ultrasonic

More information

Digital conductivity transmitter

Digital conductivity transmitter Digital conductivity transmitter Compact version with integrated conductivity electrodes Remote version with seperated transmitter for short (15 ft.) or long (1500 ft.) distance Commissioning is easy due

More information

MP Series Radar Transmitter Installation & Operation Manual

MP Series Radar Transmitter Installation & Operation Manual IOM MP Series Radar Transmitter Installation & Operation Manual MP Series Radar Transmitter Installation & Operation Manual CONTENTS I. HANDLING AND STORAGE... 1 Inspection and Handling Disposal and Recycling

More information

FLOW SWITCH 600 Series Velocity Flow Sensor. Instruction Manual

FLOW SWITCH 600 Series Velocity Flow Sensor. Instruction Manual SWITCH 600 Series Velocity Flow Sensor Instruction Manual Ultrasonic Velocity Sensor using Doppler Technology Model: FS-600 Manual Release Date: November, 2009 ECHO Process Instrumentation, Inc. CONTENTS

More information

Princo MagneLevel Model LML

Princo MagneLevel Model LML Instrumentation designed with the user in mind Instruction Manual Princo MagneLevel Model LML Two-Wire Magnetic Coupled Level Transmitter 11 Nov 05 PRINCO INSTRUMENTS INC., 1020 INDUSTRIAL BLVD., SOUTHAMPTON,

More information

SL300 Snow Depth Sensor USL300 SNOW DEPTH SENSOR. Revision User Manual

SL300 Snow Depth Sensor USL300 SNOW DEPTH SENSOR. Revision User Manual USL300 SNOW DEPTH SENSOR Revision 1.1.2 User Manual 1 Table of Contents 1. Introduction... 3 2. Operation... 3 2.1. Electrostatic Transducer... 4 2.2. SL300 Analog Board... 4 2.3. SL300 Digital Circuit

More information

AUTOMATION. Operator s Manual. DCR-1005 and DCR Rev. A4, 10/08 Doc

AUTOMATION. Operator s Manual. DCR-1005 and DCR Rev. A4, 10/08 Doc AUTOMATION P R O D U C T S G R O U P, I N C. Operator s Manual DCR-1005 and DCR-1006 Rev. A4, 10/08 Doc. 9002664 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com

More information

Non-Submersible Industrial Pressure Transducer

Non-Submersible Industrial Pressure Transducer Non-Submersible Industrial Pressure Transducer KPSI Transducers Series 27, 28, 30 FEATURES Custom Pressure Ranges up to 2000 (13,790 kpa) Accuracy to ±0.10% FS Analog Outputs of 4-20 ma or VDC Welded 316

More information

Level Transmitter / Controller / Indicator. 3-in-1 package that is simple to install and use. With expanded ranges and improved chemical resistance.

Level Transmitter / Controller / Indicator. 3-in-1 package that is simple to install and use. With expanded ranges and improved chemical resistance. Level Transmitter / Controller / Indicator 3-in-1 package that is simple to install and use. With expanded ranges and improved chemical resistance. 2.1 NEW Class 1, Division 1 Hazardous Areas Approved

More information

HART PROFIBUS. EchoTREK ULTRASONIC LEVEL TRANSMITTERS LEVEL TRANSMITTERS

HART PROFIBUS. EchoTREK ULTRASONIC LEVEL TRANSMITTERS LEVEL TRANSMITTERS HAR PROFIUS EchoREK ULRASONIC LEVEL RANSMIERS O U R P R O F E S S I O N I S Y O U R L E V E L LEVEL RANSMIERS O U R P R O F E S S I O N EchoREK LEVEL RANSMIERS FOR LIQUIDS MAIN FEAURES Max. 25 m Digital

More information

Electro-Magnetic Flowmeters COPA-XE

Electro-Magnetic Flowmeters COPA-XE Data Sheet Electro-Magnetic Flowmeters COPA-XE 10DX4311 Flowmeter system utilizes a smart microprocessor converter System accuracy of ± 0.5% of rate Field configurable via integral pushbuttons, eliminates

More information

INSTALLATION AND OPERATION MANUAL

INSTALLATION AND OPERATION MANUAL Version 2.2 MS1016 MTF SERIES VIBRATING PROBES FOR LIQUIDS AND HYC-PKK-312 SWITCHING ISOLATOR INSTALLATION AND OPERATION MANUAL Hycontrol Limited, Larchwood House, Orchard Street, Redditch, Worcestershire,

More information

Propagation of Electromagnetic Waves

Propagation of Electromagnetic Waves Propagation of Electromagnetic Waves REFLECTOR (Water) RADAR ANTENNA Speed of electromagnetic waves used in radar = 300,000,000m/s Speed of electromagnetic waves changes due to temperature, pressure and

More information

Rosemount 3101, 3102, and 3105

Rosemount 3101, 3102, and 3105 Product Data Sheet February 2013 00813-0100-4840, Rev DA Rosemount 3101, 3102, and 3105 Ultrasonic Liquid Level Transmitters Non-contacting measurement with no moving parts Integral LCD and buttons as

More information

Instruction Manual Ultrasonic Level Meter Model: NUS

Instruction Manual Ultrasonic Level Meter Model: NUS Instruction Manual Ultrasonic Level Meter Model: NUS KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh PA 15205 Phone (412) 788-2830 Fax (412)-788-4890 www.koboldusa.com Manual-NUS-8-13-02 Contents

More information

LR10, LR15, LR20, LR25 & LR30 Series Manual

LR10, LR15, LR20, LR25 & LR30 Series Manual Radar Liquid Level Transmitter LR10, LR15, LR20, LR25 & LR30 Series Manual Flowline, Inc. 10500 Humbolt Street, Los Alamitos, CA 90720 p 562.598.3015 f 562.431.8507 w flowline.com MN301700 Rev B1 Introduction

More information

Digital flow transmitter for continuous flow measurement

Digital flow transmitter for continuous flow measurement Digital flow transmitter for continuous flow measurement Compact or remote version for DN 06 to 400, PN10 Shows both flow rate and volume (with two totalizers) Automatic-calibration: TEACH-IN Simulation:

More information

MK372/Ultrasonic Sensor System. Installation & Setting up Instructions. Comprising. MK372 Indicator/Controller Ultrasonic Transmitter

MK372/Ultrasonic Sensor System. Installation & Setting up Instructions. Comprising. MK372 Indicator/Controller Ultrasonic Transmitter MK372/Ultrasonic Sensor System Installation & Setting up Instructions Comprising MK372 Indicator/Controller Ultrasonic Transmitter 1 Contents page Page 1.0 Overview 3 2.0 General Specification MK372 4

More information

WATERFLUX 3000 Quick Start

WATERFLUX 3000 Quick Start WATERFLUX 3000 Quick Start Electromagnetic flow sensor The documentation is only complete when used in combination with the relevant documentation for the signal converter. KROHNE CONTENTS WATERFLUX 3000

More information

TEK-F LEX 4100A. Guided Wave Radar Level Transmitter. LEVEL. Technology Solutions

TEK-F LEX 4100A. Guided Wave Radar Level Transmitter.   LEVEL. Technology Solutions Technology Solutions TEK-F LEX 4100A Guided Wave Radar Level Transmitter LEVEL www.tek-trol.com Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys Introduction Featuring TDR (Time Domain

More information

No E. General Information. Ultrasonic Level Meters C O M PACT TRANSMITTERS T W O - PART MEASURING SYSTEM HITROL CO., LTD.

No E. General Information. Ultrasonic Level Meters C O M PACT TRANSMITTERS T W O - PART MEASURING SYSTEM HITROL CO., LTD. No. 2001-01E Ultrasonic Level Meters C O M PACT TRANSMITTERS T W O - PART MEASURING SYSTEM HITROL CO., LTD. Fields of Application Ultrasonic Level Meters offer you excellent tools for liquid level and

More information

SITRANS F flowmeters SITRANS F US. Transmitter FUS060. Overview

SITRANS F flowmeters SITRANS F US. Transmitter FUS060. Overview Overview Function Displays and keypad Operation of the SITRANS FUS060 transmitter can be carried out using: Keypad and display unit HART communicator PC/laptop and SIMATIC PDM software via HART communication

More information

Digital inductive conductivity transmitter

Digital inductive conductivity transmitter Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

Rod probe With coaxial tube reference probe

Rod probe With coaxial tube reference probe Capacitive level transmitters GENERAL DESCRIPTION NIVOCAP 2-wire capacitive level transmitters provide an ideal solution for level measurement of conductive or non-conductive liquids. The probe of the

More information

Digital flowmeter for continuous flow measurement

Digital flowmeter for continuous flow measurement 8025 Flowmeter INSERTION Digital flowmeter for continuous flow measurement Compact or remote version for DN06 to DN400, PN10 Displays both flow rate and volume (with two totalizers) On site calibration

More information

2-wire level transmitter

2-wire level transmitter Badger Meter Europa GmbH 2-wire level transmitter Model L2xx INSTALLATION AND OPERATION MANUAL July 2002 Version UF-L2xx-07/02-e Contents Contents Page 1. Installation 1 1.1 Mounting the instrument 1 1.2

More information

Ultrasonic Level Transducer Type: MPUL06 Article No.: ca. 122

Ultrasonic Level Transducer Type: MPUL06 Article No.: ca. 122 Type: Article No.: 0067720.006 Dimensions ø95 PG7 45.25 16 101 ca. 122 ø53 NPS 2" Figure 1: Ultrasonic Level Transducer Description and application The MPULxx is an ultrasonic transducer used for determining

More information

K-BAND RADAR FOR LIQUIDS

K-BAND RADAR FOR LIQUIDS K-BAND RADAR FOR LIQUIDS LEVEL TRANSMITTERS PULSE BURST RADAR LEVEL TRANSMITTERS O U R P R O F E S S I O N PiloTREK NON-CONTACT MICROWAVE LEVEL TRANSMITTERS FOR LIQUIDS MAIN FEATURES 2-wire K-band Pulse

More information

OEM radar transmitter, for aggressive media level measurement

OEM radar transmitter, for aggressive media level measurement OEM radar transmitter, for aggressive media level measurement C ompact for level measurement up to 20 m 4... 20 ma/hart - 2 wires Adjustable with P C ATEX approvals Type 8136 can be combined with... Type

More information

Type PLC Fitting. Valve for Continuous control. Diaphragm valve. Output

Type PLC Fitting. Valve for Continuous control. Diaphragm valve. Output Digital Inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

Flow Measurement SITRANS F M

Flow Measurement SITRANS F M Overview Mode of operation The flow measuring principle is based on Faraday s law of electromagnetic induction according to which the sensor converts the flow into an electrical voltage proportional to

More information

6GHz Intelligent Radar Level Meter Product Manual. Model:KRD520 SERIES

6GHz Intelligent Radar Level Meter Product Manual. Model:KRD520 SERIES 6GHz Intelligent Radar Level Meter Product Manual Model:KRD520 SERIES Directory 1 Product Overview...1 2 Product Introduction...2 3 The Installation Requirements...4 4 The Electrical Connection...6 5 Instrument

More information

Features. NULL-KOTE Circuitry Makes the sensor immune to adverse effects of conductive coating build up.

Features. NULL-KOTE Circuitry Makes the sensor immune to adverse effects of conductive coating build up. Model L2610 Instrumentation designed with the user in mind. NULL-KOTE Self-Diagnostic Analog Level Transmitter Electronic, RF Impedance sensing, with the innovative NULL-KOTE system, which ignores product

More information

Series GWL - Radar Level Transmitter for Liquids

Series GWL - Radar Level Transmitter for Liquids TM Series GWL - Radar Level Transmitter for Liquids Bulletin L-GWL Specifications - Installation and Operating Instructions 4-7/16 [112.63] Ø3-19/32 [90.96] 1-9/16 [39.42] 5-19/32 [142.07] 3-17/32 [89.95]

More information

Digital flowmeter for continuous flow measurement

Digital flowmeter for continuous flow measurement 8025 Flowmeter INSERTION Digital flowmeter for continuous flow measurement Compact or remote version for DN06 to DN400, PN10 Displays both flow rate and volume (with two totalizers) On site calibration

More information

Operating instructions Electronic level sensor LK / / 2008

Operating instructions Electronic level sensor LK / / 2008 Operating instructions Electronic level sensor LK31 UK 704046 / 00 01 / 2008 Contents Safety instructions...2 Menu structure...3 Controls and indicating elements...4 Function and features...5 Functional

More information

Ultrasonic Transmitter

Ultrasonic Transmitter Ultrasonic Transmitter Instrucciones Generales General Instructions Table of Contents Page Topic 2...Quick Start Installation Guide 4...Safety/Protection 5...Typical Mounting Guidelines 6...Mounting -

More information

USER MANUAL MODEL USFT-CS ULTRASONIC FLOW TRANSMITTER. Rev04009 USER MANUAL DEI MODEL USFT-CS

USER MANUAL MODEL USFT-CS ULTRASONIC FLOW TRANSMITTER. Rev04009 USER MANUAL DEI MODEL USFT-CS Rev04009 USER MANUAL DEI MODEL USFT-CS USER MANUAL MODEL USFT-CS ULTRASONIC FLOW TRANSMITTER The Model USFT-CS is an ultrasonic transit time flow meter designed to accurately and reliably report the flow

More information

Micropilot M FMR250. Technical Information

Micropilot M FMR250. Technical Information Technical Information Micropilot M FMR250 Level-Radar Continuous and non-contact level measurement in solids. Cost-effective 4 to 20 ma 2-wire technology. Application The Micropilot M performs continuous,

More information

Ultrasonic level meters ULM 70

Ultrasonic level meters ULM 70 průmyslová elektronika Ultrasonic level meters ULM 70 For continuous level measurement of liquids (even if polluted), mash and paste materials in open or closed vessels, sumps, open channels, drains, etc.

More information

process measurement solutions Mobrey MSP IP wire 24V loop powered ultrasonic level transmitters

process measurement solutions Mobrey MSP IP wire 24V loop powered ultrasonic level transmitters process measurement solutions Mobrey MSP 2 wire 24V loop powered ultrasonic level transmitters IP2045 MSP Advanced ultrasonics This new family of ultrasonic non-contacting liquid level transmitters is

More information

MJK Expert 700 / 800 / 900 / 1100 / 2100 MJK Expert 1400 / 3400

MJK Expert 700 / 800 / 900 / 1100 / 2100 MJK Expert 1400 / 3400 Data Sheet MJK Expert 700 / 800 / 900 / 1100 / 2100 MJK Expert 1400 / 3400 Submersible Hydrostatic s Rugged and versatile We reserve the right to continuously improve our products and make any change in

More information

Ultrasonic Level Transmitter.

Ultrasonic Level Transmitter. Ultrasonic Level Transmitter www.fine-tek.com INTRODUCTION The ultrasonic level transmitter is a non-contact, low-cost and easy-to-install measuring device. It can be applied to most industrial applications

More information

FOSTEN AUTOMATION SÉRIE F500-RD

FOSTEN AUTOMATION SÉRIE F500-RD FOSTEN AUTOMATION SÉRIE Guided Wave Radar Level Transmitter Guided wave radar level transmitter. Low maintenance, auto calibrated references. Easy installation, directly in tanks or auxiliary vessels.

More information

Ultrasonic level measuring device, non-contact

Ultrasonic level measuring device, non-contact Ultrasonic level measuring device, non-contact For level measurement up to 8 m 4... 20 ma/hart - 2 wires Suitable for solids ATEX approvals Type 8177 can be combined with... Type 8611 Type 8793 Type 8802-GB

More information

Ultrasonic Level Detection Technology. ultra-wave

Ultrasonic Level Detection Technology. ultra-wave Ultrasonic Level Detection Technology ultra-wave 1 Definitions Sound - The propagation of pressure waves through air or other media Medium - A material through which sound can travel Vacuum - The absence

More information

RCM DIRECT READING FLOWMETER

RCM DIRECT READING FLOWMETER RCM DIRECT READING FLOWMETER Flow Pressure Level Temperature measurement monitoring control Special Features Compact Design Easy to Install For Horizontal or Vertical Pipes Rugged Construction Accuracy:

More information

WHITE PAPER HOW TO SELECT A CONTINUOUS LEVEL SENSOR BINVENTORY. Jenny Christensen Todd Peterson. BinMaster

WHITE PAPER HOW TO SELECT A CONTINUOUS LEVEL SENSOR BINVENTORY. Jenny Christensen Todd Peterson. BinMaster HOW TO SELECT A CONTINUOUS LEVEL SENSOR Jenny Christensen Todd Peterson BinMaster 1 Using a continuous level sensor to monitor the material level in your storage vessels can help you keep material flowing

More information

WATERFLUX 3000 Quick Start

WATERFLUX 3000 Quick Start WATERFLUX 3000 Quick Start Electromagnetic flowmeter The documentation is only complete when used in combination with the relevant documentation for the signal converter. KROHNE CONTENTS WATERFLUX 3000

More information

MiniMe Two-Wire Ultrasonic Level Transmitter Model LU11/12/13/14 Owner s Manual

MiniMe Two-Wire Ultrasonic Level Transmitter Model LU11/12/13/14 Owner s Manual Warranty, Service & Repair To register your product with the manufacturer, go to the Flowline website for on-line registration. The website address is as follows: www.flowline.com On-line Warranty Registration

More information

Overtravel of 3.5 mm max. Power source DC D5C-1DS0 D5C-1DP0 D5C-1DA0 AC D5C-1AS0 D5C-1AP0 D5C-1AA0 Antenna only D5C-00S0 D5C-00P0 D5C-00A0

Overtravel of 3.5 mm max. Power source DC D5C-1DS0 D5C-1DP0 D5C-1DA0 AC D5C-1AS0 D5C-1AP0 D5C-1AA0 Antenna only D5C-00S0 D5C-00P0 D5C-00A0 Touch Switch Unique 18 mm Capacitive Touch Switch with Choice of Three Actuators is Activated with Only a Very Slight Physical Contact Lightweight objects, such as thin wire or foil can be accurately detected.

More information

Ult r a s o n i c le v e l me t e r s ULM 70

Ult r a s o n i c le v e l me t e r s ULM 70 preliminary data průmyslová elektronika Ult r a s o n i c le v e l me t e r s ULM 70 For continuous non-contact level measurement Suited to level measurement of various liquid and bulk-solid materials

More information

Application Examples. Features. Ultrasonic Displacement Sensor E4PA-N. Now, more advanced with a new mutual interference prevention function.

Application Examples. Features. Ultrasonic Displacement Sensor E4PA-N. Now, more advanced with a new mutual interference prevention function. Ultrasonic Displacement Sensor Now, more advanced with a new mutual interference prevention function. Long-distance detection of up to 6,000 mm supports a wide variety of applications. The Sensor is not

More information

MSLU Ultrasonic Level Meters

MSLU Ultrasonic Level Meters MSLU Ultrasonic Level Meters For continuous level measurement of liquids (even if polluted), mash and paste materials in open or closed vessels, sumps, open channels, etc. Variants of level meter with

More information

Application Examples. Features. Ultrasonic Displacement Sensor E4PA-N. Now, more advanced with a new mutual interference prevention function.

Application Examples. Features. Ultrasonic Displacement Sensor E4PA-N. Now, more advanced with a new mutual interference prevention function. Ultrasonic Displacement Sensor Now, more advanced with a new mutual interference prevention function. Application Examples Detecting slackness in sheet materials Detecting liquid levels Remotely detecting

More information

Level Measurement Continuous level measurement Radar transmitters

Level Measurement Continuous level measurement Radar transmitters Overview Benefits Process Intelligence for advanced signal processing and quick and easy adjustment Self-guided quick start wizard for plug and play startup 2 GHz provides superior reflective properties

More information

PiloTREK SZINTTÁVADÓK LEVEL TRANSMITTERS PU L S E BU RS T R A DA R LE V E L TR A NSMIT TERS K- BA N D R A DA R FO R LI Q U I DS

PiloTREK SZINTTÁVADÓK LEVEL TRANSMITTERS PU L S E BU RS T R A DA R LE V E L TR A NSMIT TERS K- BA N D R A DA R FO R LI Q U I DS 3 YEARS WARRANTY PiloTREK SZINTTÁVADÓK LEVEL TRANSMITTERS PU L S E BU RS T R A DA R LE V E L TR A NSMIT TERS K- BA N D R A DA R FO R LI Q U I DS MAIN FEATURES 2-wire K-band Pulse Burst Radar 25 GHz frequency

More information

Level Measurement Continuous level measurement Radar transmitters

Level Measurement Continuous level measurement Radar transmitters Overview Configuration Mounting on a nozzle is a 2-wire 25 GHz pulse radar level transmitter for continuous monitoring of solids and liquids in storage vessels including extreme levels of dust and high

More information

SITRANS F flowmeters SITRANS F M. Flow sensor MAG /48 Siemens FI Overview

SITRANS F flowmeters SITRANS F M. Flow sensor MAG /48 Siemens FI Overview Siemens AG 2009 Overview Integration The complete flowmeter consists of a flow sensor and an associated transmitter MAG 5000, 6000 or 6000 I. The flexible communication concept USM II simplifies integration

More information

ULTRASONIC LEVEL INDICATOR

ULTRASONIC LEVEL INDICATOR ULTRASONIC LEVEL INDICATOR REFLEX/SCANFLEX MULTIFLEX MINIFLEX LR MICROFLEX-C TYPICAL NON-CONTACT LEVEL METER! OUTSTANDING SOFWARE MAKES HIGHLY STABLE AND RELIABLE. A WIDE RANGE OF S FROM SOLIDS TOLIQUIDS,

More information

PhD Inline Vortex. Performance Specifications Accuracy. Operating Specifications

PhD Inline Vortex. Performance Specifications Accuracy. Operating Specifications Description The Vortex PhD vortex shedding flowmeter measures process fluid flow by detecting the frequency at which vortices are shed from an obstruction in the process fluid line (the bluff body). A

More information

UNICONT. PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1. pmg4111a0600p_01 1 / 24. ST edition

UNICONT. PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1. pmg4111a0600p_01 1 / 24. ST edition UNICONT PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1 ST edition pmg4111a0600p_01 1 / 24 TABLE OF CONTENTS 1. GENERAL DESCRIPTION... 3 2. ORDER CODE... 3 3. TECHNICAL DATA...

More information

Flow Measurement SITRANS F M. Flow sensor MAG /49. Overview

Flow Measurement SITRANS F M. Flow sensor MAG /49. Overview Siemens AG 2010 Flow Measurement Overview Mode of operation The flow measuring principle is based on Faraday s law of electromagnetic induction according to which the sensor converts the flow into an electrical

More information

Phase-sequence Phase-loss Relay

Phase-sequence Phase-loss Relay Phase-sequence Phase-loss Relay K8AB-PH Three-phase Phase-sequence Phase-loss Relay Using Voltage Detection Method Prevents reverse motor rotation due to incorrect wiring. Distinguishes between positive

More information

EchoSonic II Ultrasonic Level Transmitter LU23, LU28 & LU29 Series Quick Start NEMA 4X Enclosure

EchoSonic II Ultrasonic Level Transmitter LU23, LU28 & LU29 Series Quick Start NEMA 4X Enclosure EchoSonic II Ultrasonic Level Transmitter LU23, LU28 & LU29 Series Quick Start NEMA 4X Enclosure QS300480 Rev B 2013 Flowline, Inc. All Rights Reserved Made in USA 10500 Humbolt Street, Los Alamitos, CA

More information

Sonicont USG. Ultrasonic filling level transmitter Non-contact measurement of filling levels in liquids, pastes and coarse bulk materials

Sonicont USG. Ultrasonic filling level transmitter Non-contact measurement of filling levels in liquids, pastes and coarse bulk materials Sonicont USG Ultrasonic filling level transmitter Non-contact measurement of filling levels in liquids, pastes and coarse bulk materials Technical manual 04.14 Main features Non-contact filling level measurement

More information

Intrinsically safe pressure transmitter MBS 4201, MBS 4251, MBS 4701 and MBS 4751

Intrinsically safe pressure transmitter MBS 4201, MBS 4251, MBS 4701 and MBS 4751 Data sheet Intrinsically safe pressure transmitter MBS 420, MBS 425, MBS 470 and MBS 475 The intrinsically safe pressure transmitter program is designed for use in hazardous environments and offers a reliable

More information

Ultrasonic Sensor (HART)

Ultrasonic Sensor (HART) Characteristics 500 - LEVEL - DISTANCE - MODULAR - ECONOMIC - Input: - Ranges - Output: - Voltage supply: - Accuracy: - Process connection: - Electrical connection: - Temperature range: - Limit value contacts:

More information

Echotel Model 355 Non-Contact Ultrasonic Two-Wire Transmitter for Level, Volume, or Open Channel Flow

Echotel Model 355 Non-Contact Ultrasonic Two-Wire Transmitter for Level, Volume, or Open Channel Flow Echotel Model 355 Non-Contact Ultrasonic Two-Wire Transmitter for Level, Volume, or Open Channel Flow D E S C R I P T I O N Echotel Model 355 is a two-wire, loop-powered, noncontact ultrasonic transmitter

More information

INTRODUCING SOME GREAT NEW PRODUCTS FROM OUR DWYER INSTRUMENTS RANGE:

INTRODUCING SOME GREAT NEW PRODUCTS FROM OUR DWYER INSTRUMENTS RANGE: Unit 1 / 14 Biscayne Way Jandakot WA 6104 P.O. Box 3232, Success WA 6964 Tel: (08) 9414 7666 Fax: (08) 9414 7677 Email: dg@dginstruments.com.au Website: www.dginstruments.com.au A.B.N: 59 113 005 959 DATE:

More information