2 Configuration and Connection Examples

Size: px
Start display at page:

Download "2 Configuration and Connection Examples"

Transcription

1 0.00 onfiguration and onnection Examples onfiguration and onnection Examples NGER The device must be disconnected from its voltage supplies ( V electronics and link / mains voltage) before the control and encoder leads are connected or disconnected!. ompact PLUS type units.. Single-axis drive The single-axis drive (see Fig. -) is used if only single-drive tasks need to be accomplished or if power equalization through several axes is either undesired or not possible. For this purpose, a converter is used that is directly connected to the - phase via an external main contactor, a line filter and a line reactor as necessary. ny regenerative energy is stored in the capacitor module or reduced in the braking resistor... ulti-axis drive up to axes the case of multi-axis drives (see Fig. -) a converter (-) can be combined with inverters (-). The converter rectifies the line voltage and supplies the inverters with direct voltage via the link bus module. The power integrated in the converter further provides the V voltage for the electronics of a maximum of inverters. UTON f more than inverters are connected, the V for the electronics must be provided by an external power. The total rated output currents of the inverters supplied by a converter must not exceed the rated output current of the feeding converter (in the case of SE0-0EP0 only half the rated output current). The regenerative energy generated in one axis can either be used up by the other motors, stored in the capacitor module or reduced in the braking resistor. Siemens G SE0-QX0 (Version E) SOVERT STERRVES ompendium Vector ontrol -

2 onfiguration and onnection Examples ulti-axis drive the case of multi-axis drives (see Fig. -) with more than axes, several inverters are connected to the line voltage via a common rectifier unit. n external power is required for the V voltage for the inverter electronics. The regenerative energy originating in one axis can be used by the other motors, stored in the capacitor module or dissipated in the braking resistor. SE0-QX0 (Version E) Siemens G - ompendium Vector ontrol SOVERT STERRVES

3 0.00 onfiguration and onnection Examples ux. power 0 m Bidirectional digital inputs and outputs out 0 m puts igital inputs Ri =. kω Reference voltage P0 V / N0 V m X00 X0 ontroller P / V V bidirectional digital inputs/outputs V V V V 0 V V icrocontroller PU X0 BOOT O Jog Fault Run +/- Reset OPS 0 P RSN. RS Tx PV BOOT RSP. RS Rx n.c. External V - V output Serial interface (RS) puts nalog input (non-floating) bit + sign Rin = 0 kω nalog output 0 bit + sign U: m nalog output 0 bit + sign U: m : m nalog input (non-floating) bit + sign U: Rin = 0 kω : Rin = 0 Ω (close S) igital input Ri =. kω Floating contact switch 0 V / 0. V + X ternal V-SNT PV RSP RSN URT O X0 P0 N0 S O S 0 HS HS ON OFF S Switch for USS bus termination Serial interface V V m Serial interface (RS) Slot Slot B X0 S Tacho Track Track B zero ontrol Tacho P ottemp BS ottemp 0 Pulse encoder 0 m otor temperature sensor KTY or PT thermistor 0-0 Hz 0-0 V L L L ain switch ON/OFF Q ontrol voltage 0 V Line filter X X X X link bus module U V W H G X 0-0 V X apacitor module ompact PLUS type + V == ~ 0 V ontrol voltage 0 V. X. X0 X X0. X converter ompact PLUS type X0 U V W X Options are shaded in gray G ~ Braking resistor USS bus O Jog Fault Run +/- Reset OPS 0 P Fig. - onfiguration example of a single-axis drive of the ompact PLUS type Siemens G SE0-QX0 (Version E) SOVERT STERRVES ompendium Vector ontrol -

4 onfiguration and onnection Examples 0.00 ux. power 0 m Bidirectional digital inputs and outputs out 0 m puts Reference voltage P0 V / N0 V m X00 X0 ontroller P / V V bidirectional digital inputs/outputs V V V V V V icrocontroller Jog Fault Run +/- Reset OPS O 0 P RSN. RS Tx PV igital inputs Ri =. kω PU X0 BOOT RSP. RS Rx n.c. External V - V output Serial interface (RS) puts nalog input (non-floating) bit + sign Rin = 0 kω nalog output 0 bit + sign U: m nalog output 0 bit + sign U: m : m nalog input (non-floating) bit + sign U: Rin = 0 kω : Rin = 0 Ω (close S) igital input Ri =. kω Floating contact switch 0 V / 0. V + X ternal V-SNT PV RSP RSN URT 0 O X0 P0 N0 S O S 0 HS HS ON OFF S Switch for USS bus termination Serial interface V V m BOOT Serial interface (RS) Slot Slot B X0 Tacho S Track Pulse encoder Track B 0 m zero ontrol Tacho P ottemp BS otor temperature ottemp 0 sensor KTY or PT thermistor 0-0 Hz 0-0 V L L Options are shaded in gray L ain switch ON/OFF Q ontrol voltage "Safe STOP" 0 V Line filter heckback ontrol Braking resistor 0 V: open: "Safe STOP" "Safe STOP" X X X X link bus X.... U V W H G module X 0-0 V X X X apacitor modulel ompact PLUS type X.. X00.. V ~. == 0 V. X0. X0.. X0 X ontrol. voltage V - converter ompact PLUS type U V W Supply voltage + V X00. X00. 0 V USS bus X0 X0 X0 X0 X0 X X0. X Fault. Run Jog +/- Re set - inverter - inverter ompact PLUS type ompact PLUS type U V W U V W X OPS X X G ~ G ~ G ~ + O 0 P Fig. - onfiguration example of a multi-axis drive with up to axes of the ompact PLUS type SE0-QX0 (Version E) Siemens G - ompendium Vector ontrol SOVERT STERRVES

5 0.00 onfiguration and onnection Examples ux. power 0 m Rectifier unit ompact PLUS type Braking resistor Bidirectional digital inputs and outputs out 0 m puts Reference voltage P0 V / N0 V m X00 X0 ontroller P / V V bidirectional digital inputs/outputs V V V V 0 V V icrocontroller Jog Fault Run +/- Reset OPS To further X capacitor modules X ontrol voltage 0 V "Safe STOP" Options are shaded in gray heckback ontrol X.... link bus module 0-0 V X X. Supply voltage + V X00. X00. 0 V USS bus X0 X0 X0 X0 X0 X X0 X Fault.. Run To further inverters ompact PLUS - - inverter - inverter ompact PLUS type ompact PLUS type U V W U V W O 0 P RSN. RS Tx PV igital inputs Ri =. kω PU X0 BOOT BOOT RSP. RS Rx n.c. External V V output Serial interface (RS) puts nalog input (non-floating) bit + sign Rin = 0 kω nalog output 0 bit + sign U: m nalog output 0 bit + sign U: m : m nalog input (non-floating) bit + sign U: Rin = 0 kω : Rin = 0 Ω (close S) igital input Ri =. kω Floating contact switch 0 V / 0. V + X ternal V-SNT PV RSP RSN URT O X0 P0 N0 O S S 0 HS HS ON OFF S Switch for USS bus termination Serial interface V V m Serial interface (RS) Slot Slot B X0 Tacho S Track Pulse encoder Track B 0 m zero ontrol Tacho P V- ottemp BS otor temperature ottemp 0 sensor KTY or PT thermistor OFF ON L 0-0 Hz L 0-0 V L Q X.. X H G X X U V W. X. X X ~ G G ~ V + V apacitor module ompact PLUS type ain switch X0 0 X Line filter 0 V: open: "Safe STOP" "Safe STOP" Jog +/- Reset OPS O 0 P Fig. - onfiguration example of a multi-axis drive with rectifier unit of the ompact PLUS type Siemens G SE0-QX0 (Version E) SOVERT STERRVES ompendium Vector ontrol -

6 onfiguration and onnection Examples onfiguration and onnection Examples (ompact PLUS) NOTE ) Line contactor Q ) Line fuses ) Line commutating reactor ) V power ) ON/OFF ) OFF switch The following explanations refer to the numbered gray triangles in Figs. - to -. These figures are just examples of possible configurations of drives. The necessary individual components have to be clarified according to the specific task. The information and notes required for dimensioning the individual components and the respective order numbers can be found in the atalog. ll the equipment is connected to the line via the line contactor, which is used to separate it from the line if required or in the event of a fault. The size of the line contactor depends on the power rating of the connected converter or inverter. f the line contactor is controlled from the converter, the main contactor checkback time P00 should be set to at least 0 ms. ccording to their response characteristic and to suit the requirements, the line fuses protect the connected cables and also the input rectifier of the unit. The line commutating reactor limits current spikes, reduces harmonics and is necessary for keeping system perturbations to within the limits laid down by VE 00. The external V is used to maintain the communication and diagnostics of the connected-up units even with powered-down line voltage. The following criteria apply regarding dimensioning: current of must be provided for the rectifier unit, and a current of for each inverter connected. When the V is powered up, an increased inrush current will be generated that has to be mastered by the power. No controlled power unit has to be used; the voltage must be between 0 V and 0 V. the case of a single drive and a multi-axis drive without a rectifier unit, a switch is used to energize or de-energize the line contactor. When they are switched off, the drives are not brought to a controlled standstill, but are braked only by the load. the case of a multi-axis drive with a rectifier unit, a pushbutton is used to energize the line contactor. The line contactor is kept energized by means of a lock-type contact connected to the fault signaling relay of the rectifier unit, as long as no fault is detected at the rectifier unit. Operating the OFF switch causes the line contactor to open immediately. The drives are not brought to a controlled standstill, but are braked only by the load. SE0-QX0 (Version E) Siemens G - ompendium Vector ontrol SOVERT STERRVES

7 0.00 onfiguration and onnection Examples ) Fault signaling relay ) ternal USS bus ) X0 0) X0 interface of the rectifier unit ) X0 serial interface ) Precharging the capacitor module ) put contactor ) Line filter ) otor line ) Safe STOP (Option) ) uxiliary contactor ) Pulse generator f a fault occurs in the rectifier unit, a fault message is output via the connecting contacts of the signaling relay. When the V is connected, the relay closes as long as no fault is present. the event of a fault, the lock of the line contactor is opened, the contactor drops out and the drives coast down. The USS bus is used for the internal communication of the units and only has to be connected if it is required. The digital inputs and outputs and the analog input and output have to be assigned according to the requirements of the drives. UTON: Terminal X0. may not be connected with the external V. The X0 interface of the rectifier unit serves only for permanently connecting the user-friendly OPS operator control panel and for connection to the on-line inverters. Please refer to the relevant operating instructions for the applicable measures and notes for correct operation. The serial interface is used to connect the user-friendly OPS operator control panel or a P. t can be operated either according to the RS or the RS protocol. Please refer to the relevant operating instructions for the applicable measures and notes for correct operation. When a capacitor module is used, the terminals for precharging the capacitors must be connected. The use of an output contactor is purposeful if a motor needs to be electrically isolated from the converter/inverter with the link charged. Use of a line filter is necessary if the radio interference voltages generated by the converters or rectifier units need to be reduced. The Siemens cables described in the catalog should be used for connecting the converter and the motor to each other. The "Safe Stop" option enables the power for the transmission of pulses into the power section to be interrupted by a safety relay. This ensures that the unit will not generate a rotating field in the connected motor. The auxiliary contactor is used to interrupt the self-holding condition of the main contactor in the event of a fault signal. t must be used if the control voltage for line contactor Q is 0 V. The auxiliary contactor is not required if a line contactor with a control voltage of V is used. Used to acquire the motor speed and allows speed-controlled operation with the highest degree of dynamic response and precision. Siemens G SE0-QX0 (Version E) SOVERT STERRVES ompendium Vector ontrol -

8 onfiguration and onnection Examples 0.00 Braking resistor Encoder cable NGER The brake choppers are already included in the ompact PLUS rectifier units and converters. Only a suitable external braking resistor has to be connected up, if required. See also hapter.. You will find preassembled encoder cables in atalog.0, chapter. Please note that different encoder cables are required for encoders and multiturn encoders. f the wrong encoder cable is used for one or the other, fault F0 (during operation) or alarm 0 or 0 is generated. The encoder cable must only be connected and plugged in when the converter is disconnected from the ( V and link). amage to the encoder could result if this advice is not heeded. SE0-QX0 (Version E) Siemens G - ompendium Vector ontrol SOVERT STERRVES

9 0.00 onfiguration and onnection Examples. ompact and chassis-type units.. Water-cooled units Type B to G Type J f you are using water-cooled STERRVES please note that the permissible operating pressure depends on the construction type. Operating pressure bar. Operating pressures above bar not permitted! f the system is to be operated at higher pressure, the pressure on each unit must be reduced to bar initial pressure. Operating pressure. bar. Operating pressures above. bar not permitted! f the system is to be operated at higher pressure, the pressure on each unit must be reduced to. bar initial pressure... Single units The following two configuration examples show the wiring of a converter (-) and an inverter (-). The mains and motor connections and the connection to the braking unit and fan can be seen on the right-hand side of the diagram. The control terminal strips of the UV control board (Vector ontrol) are shown enlarged for clarity on the left-hand side of the diagram. Fig. - shows wiring examples for analog and digital inputs and outputs. You will also find descriptions of the terminals in the operating instructions in the chapter entitled "onnecting-up". Siemens G SE0-QX0 (Version E) SOVERT STERRVES ompendium Vector ontrol -

10 onfiguration and onnection Examples Hz 00-0 V uxiliary power 0 m Bidirectional digital inputs and outputs out 0 m puts 0 X0 / ontroller PV V V bidirectional digital inputs/ outputs V V +/- Reset icrocontroller igital inputs V V Ri =, kω V puts V RSP Serial interface USS (RS) RSN URT BOOT Slot Slot PU X00 P ontrol voltage 0 V O Jog Fault Run ontrol voltage 0 V OPS Reference voltage P0 V / N0 V m P0 UX N0 UX nalog input (non-floating) +V Switch for USS bus termination X0 L L L Line circuit breaker K ains filter re For converters 00-0 V sizes - and chassis-type units from size E: terminal / (kv) instead of / (kv) X U L V L W L L+ L- X 0 V V 0 V + V X 0 X0 0 Standard connections see left of diagram X0 X X - converter compact or chassis U V W Braking unitt G H X External braking resistor PT/KTY G ~ Options on gray background 0 P n.c. Ref. potential RS S X0 Slot Slot E Slot F Slot G X0 +V Switch for USS bus termination nalog input (non-floating) nalog output nalog output bits + sign U: Rin = 0 kω : Rin = 0 Ω (close S) 0 bis + sign U: m : R 00 Ω 0 S S O O S V m S V m S Tacho Track Track B Zero pulse ontrol Tacho P ottemp BS ottemp S 0 Pulse encoder 0 m otor temperature sensor KTY or PT resistor Q ON/OFF S X ϑ Filter PV RS Tx RSN RS Rx RSP BOOT Fig. - onfiguration example for compact or chassis-type unit (-) SE0-QX0 (Version E) Siemens G -0 ompendium Vector ontrol SOVERT STERRVES

11 0.00 onfiguration and onnection Examples puts essage "No fault" puts Reference voltage P0 V / N0 V m nalog input (non-floating) 0 X0 Regulator PV icrocontroller / V V bidirectional digital inputs/ outputs V V V V V V RSP P0 UX N0 UX BOOT Slot PU X00 O Jog Fault Run +/- Reset OPS 0-0 V P +V Switch for USS bus termination X0 ontrol voltage 0 V 0 V 0 0 V / 0 V V + V X X X0 X PT/KTY G 0 U L V L W L Standard connections see left of diagram - inverter compact or chassis X0 U V W ~ L+ L- X X Braking unit G H X External braking resistor Options on gray background 0 P n.c. Ref. potential RS nalog input (non-floating) nalog output f act nalog output 0 X0 RSN URT S +V Switch for USS bus termination S S O O S V S m V m Slot Slot Slot E Slot F Slot G S Tacho Track Track B Zero pulse ontrol Tacho P ottemp BS ottemp S 0 Pulse encoder 0 m otor temperature sensor KTY or PT resistor PV RS Tx RSN RS Rx RSP BOOT Example: Terminal assignment for factory setting with P = 0 essage "Operation" (Jumper -) BO data set Free cknowledge fault OFF ON / OFF for BO data set Set P. = for fsetp from analog input in BO data set X0 X depends on unit size L L L For sizes to and 0 V only heckback "Safe stop" N contact "Safe stop" ain contactor activation 0 V, 0. Fan voltage /~ 0 V (for chassis-type units) ompact unit Size : F0 F0 Pay attention to transformer connection! P X X ϑ Filter f Fig. - onfiguration example for compact or chassis-type unit (-) Siemens G SE0-QX0 (Version E) SOVERT STERRVES ompendium Vector ontrol -

12 onfiguration and onnection Examples onfiguration example with rectifier/regen.feedback unit ontrol voltage 0 V ontrol voltage 0 V L L L 0 0 V V + V 0 V X 0 V X X X00 P X0 0 X0 0 0 P.00/00 P.00/00 OFF or pulse blocking ain contactor control unit 0 V /0. N contact "safe stop" heckback signal "safe stop" Fault Run 0 V 0 V P 0 V/ 0 V + V 0 V Rectifier/regenerative feedback unit X U V W X U V W O Jog P +/- Reset OPS L L L Line filter Q ain switch 0-0 Hz 0-0 V V 0-0 V Options are shown with a grey background X X U L V L W L L+ X X00 X0 0 X0 X0 - inverter compact or chassis X U V W Filter PT/KTY G ~ L- P 0 V/ 0 V + V 0 V X X U L V L W L L+ X X00 X0 0 X0 X0 - inverter compact or chassis X U V W Filter PT/KTY G ~ L- 0 Fig. - onfiguration example with rectifier/regenerative feedback unit SE0-QX0 (Version E) Siemens G - ompendium Vector ontrol SOVERT STERRVES

13 0.00 onfiguration and onnection Examples.. Explanations relating to the configuration examples (ompact and chassis-type units) NOTE The following explanations refer to the numbered gray triangles in Figs. - to -. These diagrams each show a drive configuration example. The need for the individual components must be clarified according to the given application. the catalog you will find the necessary information and notes concerning the ratings of the individual components and the pertinent order numbers. ) Line fuses ) Line contactor K ) Radio interference suppression filter ) Line commutating reactor ) ontrol terminal strip X ) Fan power for inverter devices The line fuses afford protection against short circuit and, depending on their utilization category (gl, gr or ar), also protect the connected conductors and rectifier or input rectifier of the unit. The converter or rectifier units, or infeed/regenerative feedback unit is connected to the power via the line contactor and disconnected in case of need or in the event of a fault. The system is dimensioned according to the output of the connected converter, rectifier unit or rectifier/regenerative feedback unit. radio interference suppression filter is required whenever the radio interference voltages originating from converters or rectifier units must be reduced according to EN 00-. The line commutating reactor limits current peaks and reduces harmonics. t is also required, among other things, for compliance with the permissible system perturbations according to EN 0 and compliance with the radio interference suppression voltages. The X / control terminals are provided with a connection for ing devices requiring an external V control voltage. Terminals X / on the compact units (inverters) and X / on the chassis units (converter and inverter) allow the output of an isolated digital signal, e.g. to control a main contactor. Function "SFE STOP" on compact inverters and input units (converters and inverters) with option K0 With the "SFE STOP" function, a safety relay can be used to interrupt the power for pulse transmission in the power section. This ensures that the inverter cannot operate the connected motor. On all chassis and compact units of type, a voltage of 0 V 0/0 Hz is required for the fans. The chassis units are connected via X:. and the compact units are connected directly to fan fuses F0 and F0. Siemens G SE0-QX0 (Version E) SOVERT STERRVES ompendium Vector ontrol -

14 onfiguration and onnection Examples ) V auxiliary power ) X00 serial interface ) put reactors ) Sine wave filter du/dt-filter ) put contactor ) Pulse generator ) otor fan 0) Freewheeling diode ) Fuse ) Phase failure relays The external V power serves to back up the communications and diagnostics functions of the connected devices when the line voltage is switched off. Rectifier units always require an external V power. The following criteria apply to dimensioning: urrents (see atalog.0) When the V is switched in, an inrush current has to be dealt with by the power. There is no need to install a stabilized power ; the voltage range must be kept between 0 V and 0 V. The serial interface is used for connecting the OPS operator pane or a P. t can be operated according to the RS or the RS protocol, as desired. Please refer to the operating instruction for information concerning proper operation. Limit the capacitive currents arising from long motor cables and make it possible to operate motors situated a long way from the converter/inverter. (See atalog.0 hapter ). Limit the rate of voltage rise occurring at the motor terminals and the voltage peak (du/dt-filter) or generate a sinusoidal voltage characteristic (sine wave filter) at the motor terminals (see atalog.0, hapter ). n output contactor serves a useful purpose wherever, with charged link, a motor has to be electrically isolated from the convert/rectifier unit. Used to acquire the motor speed and allows speed-controlled operation with the highest degree of dynamic response and precision. s to be operated in the case of separately ventilated motors. For protection of the connected inverters against commutation failure. To protect the signal cables of a phase failure relay. Types suitable for a system voltage of 00 V : Siemens TT0 suitable for TN systems old L000 suitable for TN, TT and T systems ddress: E. old & Söhne KG, PF, Furtwangen Tel.: + /0, Fax.: + / The maximum response delay time is 0 ms. The phase failure relays must be connected according to their construction type. SE0-QX0 (Version E) Siemens G - ompendium Vector ontrol SOVERT STERRVES

15 0.00 onfiguration and onnection Examples ) Voltage transformer ) f the voltage deviates from 00 V, voltage transformers with a primary voltage corresponding to voltage U and U = 00 V on the secondary side must be used. The voltage transformers should correspond to class 0. or ; size V Transformers available on request from: Ritz esswandler GmbH & o. Salomon-Heine-Weg -0 Hamburg Tel.: + 0/-0, Fax.: + 0/- ELGE Elektro-pparate GmbH Grenzweg - Neunkirchen Tel.: + / The output of the phase failure relay controls a digital input of the rectifier/regenerative feedback unit on the UR. epending on the requirements of the system, this input is assigned function US (trip command with direct pulse disable P.i) and disables the thyristors to avoid a commutation failure very effectively. Siemens G SE0-QX0 (Version E) SOVERT STERRVES ompendium Vector ontrol -

16 onfiguration and onnection Examples Examples of motor junction wiring.. Shielded cabling meeting E requirements to maintain E limit values The limit values of class for industrial plants are met with the cabling as shown in Fig. - and Fig. -. The limit values of class B for public networks are met with the cabling as shown in Fig. -. e.g. NYWY L L L / concentric U shield () ½ (Lx) Transformer/ SOVERT STERRVES abinet busbar U V W Plant/factory ground U V W ~ Fig. - Protodur power cable: NYY -0./kV NYWY -0./kV SE0-QX0 (Version E) Siemens G - ompendium Vector ontrol SOVERT STERRVES

17 0.00 onfiguration and onnection Examples e.g. Protoflex EV plus / / L L L e.g. Protoflex EV L L L concentric U shield / concentric U shield Transformer/ SOVERT STERRVES abinet busbar U V W Transformer/ SOVERT STERRVES abinet busbar U V W Plant / factory ground Plant / factory ground U V W ~ U V W ~ Fig. - Protoflex power cable YSLY-J -0./kV Siemens G SE0-QX0 (Version E) SOVERT STERRVES ompendium Vector ontrol -

18 onfiguration and onnection Examples Unshielded cabling abling installed according to the following figure is sufficient for technical operation of the drive. e.g. NYY-J L L L Transformer/ SOVERT STERRVES abinet busbar U V W Plant / factory ground U V W ~ Fig. - Protodur power cable NYY-J -0./kV SE0-QX0 (Version E) Siemens G - ompendium Vector ontrol SOVERT STERRVES

19 0.00 onfiguration and onnection Examples. "Safe STOP" function NOTE The "SFE STOP" function of SOVERT STERRVES (also known as "Starting lockout" in SORVE ) satisfies EN 0 0-/N VE 0 Part Section., "evices for switching off and preventing unexpected starting", but does not satisfy Section., ain switch function (isolating from the power ). The main switch function can be performed only by the use of an electrically isolating switching element. The "SFE STOP" function is also suitable for implementing the stop function according to ategory 0 and as defined by EN 0 0- / VE 0 Part, Section... The requirements for the behavior of the control functions in the case of a fault (EN 00-, Section.) are met by fulfillment of the requirements of EN - acc. to ategory. Purpose of the "SFE STOP" function NOTE Residual risk The SFE STOP function is supplied as standard with SOVERT STERRVES of the compact series of inverter units in sizes to (with the exception of converters and inverters for 0 V to 0 V ). the case of chassis units and ompact PLUS units, this function is obtainable in the form of the K0 option. The "SFE STOP" function prevents unexpected starting from standstill of the connected motor. The "SFE STOP" function should not be activated until after the drive is at standstill, because otherwise no further braking is possible. That is why the drive must be brought to standstill and secured by means of an external machine control. The "SFE STOP" function interrupts the power used to drive the GBT modules. residual risk remains in the event of two faults occurring at the same time. The drive can then turn through a small angle (permanent-field synchronous servomotors, e. g. FT, FK: -pole 0, -pole 0, -pole ; asynchronous motors: in the remanence range max. slot division, or about to ). The "SFE STOP" function does not electrically isolate the equipment and therefore gives not protection from "electric shock". The whole machine must be isolated from the system by opening the main switch (EN 00/.) in the event of production shutdowns or for maintenance, repair and cleaning work on the machine or plant. Siemens G SE0-QX0 (Version E) SOVERT STERRVES ompendium Vector ontrol -

20 onfiguration and onnection Examples 0.00 When used with the positively-driven signal contacts of the compact inverter units, the "SFE STOP" function has to be connected to terminal strip X: / (chassis units: terminal strip X: /) in the line contactor circuit or EERGENY OFF circuit. f there is any doubt as to whether the SFE STOP relay is functioning correctly with respect to the operating mode of the machine, the drive concerned must be electrically isolated from the power, e. g. by means of a line contactor. The "SFE STOP" function and the associated mode of operation must not be used again until after the fault has been remedied. NOTE When the "SFE STOP" function is activated, it is possible in some cases for the "Operating" status signal to be generated at the converter/inverter. But the pulses are not released and so the motor cannot turn. hazard is therefore ruled out. From the control, with the aid of heckback SFE STOP (X Pin /; X Pin /), make sure that the SFE STOP function cannot be deactivated in converter statuses other than REY FOR ORTON or REY FOR SWTHNG ON. order that the converter/inverter control recognizes the SFE STOP status and proceeds to process this status in the sequencing control, a binary input of the UV control unit must be activated, thereby generating the OFF command (cf. P...P) and hence a starting lockout. When the OFF command is activated via "SFE STOP", the converter status changes to Starting lockout. SE0-QX0 (Version E) Siemens G -0 ompendium Vector ontrol SOVERT STERRVES

21 0.00 onfiguration and onnection Examples U V W X X (Option K 0) P V PV X0 U X SOVERT STERRVES U V W X: igital input, with OFF Pi00 and i00 Fig. -0 onfiguration of the "Safe STOP" function in a SOVERT STERRVES unit Siemens G SE0-QX0 (Version E) SOVERT STERRVES ompendium Vector ontrol -

22 onfiguration and onnection Examples 0.00 Operating principle of "SFE STOP" The power to the individual motor windings is controlled by means of the inverter power sections. pulse formation logic drives the GBT power transistors in a rotating-field-oriented pattern. each transistor arm, an optocoupler/fiber optic cable is connected between the control logic and the control amplifier of the power section for potential isolation. s it cannot be ruled out that the inverter electronics will generate a pulse pattern capable of producing a rotating field (without a start command being present), a method was found of safely preventing the pulse pattern from reaching the ignition and control inputs of the GBTs. The "SFE STOP" TVE function implements an electrical separation (interrupt) between the power and the driver electronics of the GBT inverter, thereby preventing the motor from turning. The "SFE STOP" function is activated by an external NO contact and is active when the "SFE STOP relay" has dropped out. the event of failure of the "SFE STOP" function, the "SFE STOP" checkback contacts must separate the drive from the power by means of a line contactor or the EERGENY STOP circuit. No rotating-field-oriented operation of the power transistors is possible while the "SFE STOP" function is active. Simultaneous welding of two GBTs is the worst case leading to the residual risk described in the above. NOTE The motor can no longer develop torque while the "SFE STOP" function is activated. Non-self-locking drives must be secured by means of a mechanical brake. The "SFE STOP" function is not suitable for bringing a running motor to a standstill as quickly as possible, because this function turns off the control pulses and so the motor is braked only by the load. dvantage: The "SFE STOP" function makes it unnecessary to provide motor contactors. SE0-QX0 (Version E) Siemens G - ompendium Vector ontrol SOVERT STERRVES

23 0.00 onfiguration and onnection Examples onnection of the "SFE STOP" function the case of compact inverter units, the "SFE STOP" function is addressed via terminal strip X:/, while in the case of chassis units it is addressed via terminal strip X:/. When dropped out, the SFE STOP relay activates the "SFE STOP" function. losure of terminals X:/, or terminals X:/ signifies that the "SFE STOP" function is active. These terminals provide a potentialfree signal of the status of the "SFE STOP" function. X Terminal esignation escription Range + V (in) V voltage V. 0 V Reference potential 0 V ontact "Safe STOP" checkback ontact "Safe STOP" checkback 0 V P "Safe STOP" voltage m Switched signal "Safe STOP" control input 0 V HV control ain contactor control Not connected Not used HV control ain contactor control 0 V, 0. onnectable cross-section:. mm² (WG ) Table - Terminal connections of external aux. voltage V, Safe STOP, main contactor control for compact units X Terminal esignation escription Range P "Safe STOP" voltage V Switched signal "Safe STOP" control input 0 m ontact "Safe STOP" checkback 0 V ontact "Safe STOP" checkback ) onnectable cross-section:. mm² (WG ) Table - Terminal connections of the K0 Option "Safe STOP" on chassis units ) ompact PLUS tpye: Siemens G SE0-QX0 (Version E) SOVERT STERRVES ompendium Vector ontrol -

Page ENSC387 - Introduction to Electro-Mechanical Sensors and Actuators: Simon Fraser University Engineering Science

Page ENSC387 - Introduction to Electro-Mechanical Sensors and Actuators: Simon Fraser University Engineering Science Motor Driver and Feedback Control: The feedback control system of a dc motor typically consists of a microcontroller, which provides drive commands (rotation and direction) to the driver. The driver is

More information

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13 Index A A Group functions 3 9 AC reactors 5 3 Acceleration 1 15, 3 8 characteristic curves 3 26 second function 3 24 two-stage 4 19 Acceleration stop function 3 21 Access levels 3 5, 3 36, 4 25 Access

More information

S100A40AC SERIES BRUSHLESS SERVO AMPLIFIERS Model: S100A40AC

S100A40AC SERIES BRUSHLESS SERVO AMPLIFIERS Model: S100A40AC S100A-AC Series S100A40AC SERIES BRUSHLESS SERVO AMPLIFIERS Model: S100A40AC FEATURES: Surface-mount technology Small size, low cost, ease of use Optical isolation, see block diagram Sinusoidal drive and

More information

The design is the newest member of the MASTER- DRIVES VC (Vector Control) family and compliments the spectrum in the lower power range. The MASTER- DR

The design is the newest member of the MASTER- DRIVES VC (Vector Control) family and compliments the spectrum in the lower power range. The MASTER- DR 0.55 kw to 8.5 kw Product Overview October 200 The proven series with optimized power density. The design is ideally suited for applications where space is at a premium. drives together with the PH7 or

More information

Service Manual Inverter Systems and Motors

Service Manual Inverter Systems and Motors Service Manual Inverter Systems and Motors Edition: Jan. /2001 HEIDENHAIN Service Manual for Inverter Systems and Motors Changes / Enhancements We are constantly advancing the technical development of

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

Appendix C, Paper 3 C-17

Appendix C, Paper 3 C-17 Appendix C, Paper 3 C-17 C-18 C-19 C-20 C-21 C-22 C-23 C-24 C-25 C-26 Appendix D USER S MANUAL SEMITEACH Based Converter System for Electrical Machines Jawwad Zafar Copyright 2010 by the Université Libre

More information

Intelligent Drive Systems, Worldwide Services SK 700E F 3070 GB

Intelligent Drive Systems, Worldwide Services SK 700E F 3070 GB Intelligent Drive Systems, Worldwide Services SK 700E Universal application Modular High-Performance Inverter NORDAC SK 700E The NORDAC SK 700E frequency inverter is designed for the power range between

More information

IRT AT-Small. Technical Manual. quality IN MOTION. quality IN MOTION

IRT AT-Small. Technical Manual. quality IN MOTION.   quality IN MOTION IRT quality IN MOTION www.irtsa.com 2000 AT-Small Technical Manual IRT quality IN MOTION E2 0 8 4 1 5 September 2013-Rev. 4 UL Requirements Drives Series 2000 / 4000 AT 1. Field wiring terminal to use

More information

Cover sheet. Handling the Demo Case. SINAMICS G120 with CU250S-2 Vector. FAQ October Service & Support. Answers for industry.

Cover sheet. Handling the Demo Case. SINAMICS G120 with CU250S-2 Vector. FAQ October Service & Support. Answers for industry. Cover sheet Handling the Demo Case SINAMICS G120 with CU250S-2 Vector FAQ October 2013 Service & Support Answers for industry. Question This article originates from the Siemens Industry Online Support.

More information

IRT Mini Evo. Technical Manual. quality IN MOTION. quality IN MOTION

IRT Mini Evo. Technical Manual. quality IN MOTION.   quality IN MOTION IRT quality IN MOTION www.irtsa.com 2000 Mini Evo Technical Manual IRT quality IN MOTION Contents 1. INTRODUCTION 3 2. DESCRIPTION 5 3. TECHNICAL DATA 7 3.1 GENERAL DATA FOR ALL TYPES 7 3.2 SPECIFIC DATA

More information

TOSHIBA International Corp

TOSHIBA International Corp TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification

More information

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability

More information

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS) AC CURRENT GENERATOR PERFORMANCES Wide range of current 50 db dynamic range Signal-to-noise ratio: 80 db open loop protection Stability < 0,1% Very low THD distortion < 0,3% External synchronization Build-up

More information

Large-Capacity Variable-Speed AC Drive

Large-Capacity Variable-Speed AC Drive Large-Capacity Variable-Speed AC Drive asakazu Yoshida asato ochizuki Naoki Kanazawa 1. Introduction With the increasing range of applications for motor driver inverters and customer satisfaction with

More information

ELECTRONIC CONTROL OF A.C. MOTORS

ELECTRONIC CONTROL OF A.C. MOTORS CONTENTS C H A P T E R46 Learning Objectives es Classes of Electronic AC Drives Variable Frequency Speed Control of a SCIM Variable Voltage Speed Control of a SCIM Chopper Speed Control of a WRIM Electronic

More information

Preliminary Data Sheet Single-Channel, High Power IGBT Gate Driver for Applications from 1.7kV to 6.5kV

Preliminary Data Sheet Single-Channel, High Power IGBT Gate Driver for Applications from 1.7kV to 6.5kV Preliminary Data Sheet Single-Channel, High Power IGBT Gate Driver for Applications from 1.7kV to 6.5kV Abstract The IGBT Driver 1KD21114_4.0 is a low power consumption driver with V CE-desat detection

More information

VARAN Stepper Module VST 012

VARAN Stepper Module VST 012 VARAN Stepper Module VST 012 The VST 012 is a VARAN module designed for the control of a stepper motor up to a maximum 10 A RMS. The available operating modes are full step, half step and micro step. The

More information

Microprocessor Control Board Set Up Procedures (OR PLC)

Microprocessor Control Board Set Up Procedures (OR PLC) Microprocessor Control Board Set Up Procedures (OR-00 PLC) SWITCHES/PUSHBUTTONS Push Buttons at display SW Enter button SW Back button SW Down SW UP Back light on/off switch Rotary switches on main board

More information

HOW TO CHECK SERVOPACK:

HOW TO CHECK SERVOPACK: HOW TO CHECK SERVOPACK: Labels (models number) 1. Write down the model number of the drive. The model number starts with CACR-SR******* 1 2. Before turning off the power, check what numbers or letters

More information

Integrated servo motor

Integrated servo motor R88E-AECT@, R88S-EAD@ Integrated servo motor Motor and drive integrated for space optimization Wide range of motors from 2.55 Nm to 25 Nm 3000 rpm rated speed Peak torque 300% of rated torque IP65 protection

More information

AC Drive Technology. An Overview for the Converting Industry. Siemens Industry, Inc All rights reserved.

AC Drive Technology. An Overview for the Converting Industry.  Siemens Industry, Inc All rights reserved. AC Drive Technology An Overview for the Converting Industry www.usa.siemens.com/converting Siemens Industry, Inc. 2016 All rights reserved. Answers for industry. AC Drive Technology Drive Systems AC Motors

More information

Generator Speed Controller Model GSC 1

Generator Speed Controller Model GSC 1 enerator Speed Controller odel SC 1 RA 29 977/09.95 Replaces: 4.92 Self contained controller for driving electrical power generators with a hydrostatic transmission 16 Bit microprocessor based controller

More information

Residual Current Operated Circuit-Breakers (RCCBs)

Residual Current Operated Circuit-Breakers (RCCBs) Product Overview Residual Current Operated Circuit-Breakers (RCCBs) Residual current operated circuit-breakers Number of poles Rated current A Rated residual current ma MW Auxiliary contacts can be mounted

More information

Chapter. F0-04AD-1, 4-Channel Analog Current Input. In This Chapter...

Chapter. F0-04AD-1, 4-Channel Analog Current Input. In This Chapter... F0-0-, -hannel nalog urrent Input hapter In This hapter... Module Specifications... Setting the Module Jumper... onnecting and isconnecting the Field Wiring... Wiring iagram... Module Operation... Special

More information

Ambient Conditions Storage Conditions Installation Minimum Clearances and Air Flow...2 3

Ambient Conditions Storage Conditions Installation Minimum Clearances and Air Flow...2 3 CHAPTER INSTALLATION 2 AND WIRING Contents of this Chapter... Ambient Conditions..............................2 2 Storage Conditions...............................2 2 Installation.....................................2

More information

Analog Servo Drive. Peak Current 16 A (11.3 A RMS )

Analog Servo Drive. Peak Current 16 A (11.3 A RMS ) Description The PWM servo drive is designed to drive three phase brushless motors with sine wave current at a high switching frequency. The drive requires two sinusoidal command signals with a 120-degree

More information

In the event of a failure, the inverter switches off and a fault code appears on the display.

In the event of a failure, the inverter switches off and a fault code appears on the display. Issue 03/05 Faults and Alarms 5 Faults and Alarms 5.1 Fault messages In the event of a failure, the inverter switches off and a fault code appears on the display. NOTE To reset the fault code, one of three

More information

ROLL TO ROLL FUNCTION MANUAL FR-A (0.4K)-04750(90K)-R2R FR-A (0.4K)-06830(280K)-R2R FR-A (315K)-12120(500K)-R2R

ROLL TO ROLL FUNCTION MANUAL FR-A (0.4K)-04750(90K)-R2R FR-A (0.4K)-06830(280K)-R2R FR-A (315K)-12120(500K)-R2R INVERTER ROLL TO ROLL FUNCTION MANUAL FR-A820-00046(0.4K)-04750(90K)-R2R FR-A840-00023(0.4K)-06830(280K)-R2R FR-A842-07700(315K)-12120(500K)-R2R Roll to Roll Function The FR-A800-R2R inverter has dedicated

More information

Inverter MICROMASTER 410

Inverter MICROMASTER 410 Inverter MICROMASTER 40 /2 Description /4 Circuit diagrams /6 Technical data /7 Selection and ordering data /8 Options /0 Dimension drawings Siemens DA 5.2 2005/2006 / MICROMASTER 40 Description Inverter

More information

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection Quick Start Guide TECO F510 Inverter This guide is to assist you in installing and running the inverter and verify that it is functioning correctly for it s main and basic features. For detailed information

More information

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 06401 807-0 Fax: 06401 807-259 Insulation fault locator Insulation fault locator for DC IT systems with high system leakage capacitances

More information

1 340XRi / 680XRi / 1220XRi Applications. 340XRi, 680XRi, 1220XRi Application manual.

1 340XRi / 680XRi / 1220XRi Applications. 340XRi, 680XRi, 1220XRi Application manual. 1 340XRi / 680XRi / 20XRi Applications 340XRi, 680XRi, 20XRi Application manual. www.sprint-electric.com - Data Product manuals Technical help Drive glossary FAQ Brochures Images Data Product manuals 340XRi

More information

13. Before making a service call Trip information and remedies

13. Before making a service call Trip information and remedies . Before making a service call Trip information and remedies.1 Trip causes/warnings and remedies When a problem arises, diagnose it in accordance with the following table. If it is found that replacement

More information

FEATURES DESCRIPTION THE OEM ADVANTAGE

FEATURES DESCRIPTION THE OEM ADVANTAGE FEATURES PMAC2 controller from Delta-Tau controls amp bridge directly MODEL POWER I-CONT (A) I-PEAK (A) 7229AC 32~132VAC 10 20 7429AC 32~264VAC 10 20 Serial digital current feedback from U & V phases Mini

More information

CROSS Chassis from 160 A to 450 A

CROSS Chassis from 160 A to 450 A CROSS Chassis from 160 A to 450 A STS CATALOGUE Important note! The technical data enclosed is for general information. Please note that the operating instructions and references indicated on the products

More information

Excitation Systems RG3 - T4. Transistorized Excitation Systems for Synchronous Generators. Power Generation

Excitation Systems RG3 - T4. Transistorized Excitation Systems for Synchronous Generators. Power Generation Excitation Systems RG3 - T4 Transistorized Excitation Systems for Synchronous Generators Power Generation Operating Characteristics Reliability High availability Digital control facilities Very good control

More information

Inverter Systems for HEIDENHAIN Controls. Information for the Machine Tool Builder

Inverter Systems for HEIDENHAIN Controls. Information for the Machine Tool Builder Inverter Systems for HEIDENHAIN Controls Information for the Machine Tool Builder April 2011 HEIDENHAIN Inverter Systems The inverter systems from HEIDENHAIN are suitable for HEIDENHAIN controls with digital

More information

7.5 Induction motor control with analog setpoint interface

7.5 Induction motor control with analog setpoint interface .5 nduction motor control with analog setpoint interface 02.98 08.98.5 nduction motor control with analog setpoint interface 6SN1122 0BA1 0AA The following appropriate control components are available

More information

FUJI Inverter. Standard Specifications

FUJI Inverter. Standard Specifications FUJI Inverter o Standard Specifications Norminal applied motor The rated output of a general-purpose motor, stated in kw. That is used as a standard motor. Rated capacity The rating of an output capacity,

More information

[ 4 ] Using pulse train input (F01 = 12)

[ 4 ] Using pulse train input (F01 = 12) [ 4 ] Using pulse train input (F01 = 12) Selecting the pulse train input format (d59) A pulse train in the format selected by the function code d59 can give a frequency command to the inverter. Three types

More information

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units BETA Switching Transformers, Bells and Socket Outlets /2 Product overview /3 4AC3 0, 4AC3 1 bell transformers /5 4AC3 4... 4AC3 transformers for permanent loads /8 4AC2 4 power supply units / 7LQ2 2 bells

More information

CC-Link Compatible AC Servo Amplifier <MR-J3-T type> with Built-in Positioning Function

CC-Link Compatible AC Servo Amplifier <MR-J3-T type> with Built-in Positioning Function MO LM/ G T P R M Fn SHIFT ES E B 1STEP. F PRU03 TEST F ST OP RESET General-Purpose Servo MELSERO-J3 ew Product Release S0-E -Link ompatible Servo mplifier with Built-in Positioning Function

More information

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances _D00108_00_D_XXEN/05.2015 ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances

More information

Solid-State Soft Starters

Solid-State Soft Starters Selection and ordering data Rated operational voltage U e V Soft starters for three-phase asynchronous motors 3RW30 25-1B14 3RW30 35-1B14 t ambient temperature 40 C Size Order No. Price Weight Pack. Rated

More information

15P0161B1 - DCREG for Applications to Electromagnets - SW Rev. D3.09 R.03 - Updated 01/04/04

15P0161B1 - DCREG for Applications to Electromagnets - SW Rev. D3.09 R.03 - Updated 01/04/04 POWER CONNECTIONS AND DCREG PROTECTING DEVICES DCREG thyristor converter can be used to power very inductive loads, such as electromagnets. Applications problems due to this type of load that can be compared

More information

XIOC technology and networking modules

XIOC technology and networking modules / XIO XIO digitale and analog input/output modules XIO technology and networking modules XIO the compact I/O and much more XIO are local expansion modules for direct connection to all Xontrol controllers.

More information

BLuAC5 Brushless Universal Servo Amplifier

BLuAC5 Brushless Universal Servo Amplifier BLuAC5 Brushless Universal Servo Amplifier Description The BLu Series servo drives provide compact, reliable solutions for a wide range of motion applications in a variety of industries. BLu Series drives

More information

S1 Minor (usually reversible) injury S2 Serious (normally irreversible) injury including death

S1 Minor (usually reversible) injury S2 Serious (normally irreversible) injury including death General data Application Classification of a machine in categories acc. to EN 954- The 98/3/EG machinery directive stipulates that every machine must comply with the applicable guidelines and standards.

More information

Analog Servo Drive. Continuous Current. Features

Analog Servo Drive. Continuous Current. Features Description Power Range The PWM servo drive is designed to drive three phase brushless motors with sine wave current at a high switching frequency. The drive requires two sinusoidal command signals with

More information

Ametek, Inc. Rotron Technical Products Division. 100 East Erie St., Suite 200 Kent, Ohio User's Guide. Number Revision F

Ametek, Inc. Rotron Technical Products Division. 100 East Erie St., Suite 200 Kent, Ohio User's Guide. Number Revision F Ametek, Inc. Rotron Technical Products Division 100 East Erie St., Suite 200 Kent, Ohio 44240 User's 120 Volt, 800 Watt and 240 Volt, 1200 Watt Brushless Motor Drive Electronics 5.7" (145 mm) and 7.2"

More information

Operating Instruction

Operating Instruction Level and Pressure Operating Instruction VEGASEL 643 6 5 + + 3 5 + + max. min. on VEGASEL 643 5 6 7 8 9 10 11 12 13 14 in out Contents Contents Safety information... 2 1 Product description 1.1 Function

More information

HPVFP High Performance Full Function Vector Frequency Inverter

HPVFP High Performance Full Function Vector Frequency Inverter Advanced User Manual HPVFP High Performance Full Function Vector Frequency Inverter HP VER 1.00 1. HPVFP Parameter Set Overview...3 1.1. About this section...3 1.2. Parameter Structure Overview...3 1.3.

More information

SixPac Series of SCR AC Controller and DC Converters

SixPac Series of SCR AC Controller and DC Converters SixPac Series of SCR AC Controller and DC Converters Complete Series of SCR Three-Phase Power Control Units Features Include: Compact, rugged construction Applications include: Windmill Converters Motor

More information

3 Instructions for Design of Drives in Conformance with EMC Regulations

3 Instructions for Design of Drives in Conformance with EMC Regulations 11.2000 Instructions for Design of Drives in Conformance with EMC Regulations 3 Instructions for Design of Drives in Conformance with EMC Regulations 3.1 Foreword The modular design of SIMOVERT MASTERDRIVES

More information

Technical manual. Microstep driver SMC11. NANOTEC ELECTRONIC GmbH & Co. KG Gewerbestraße 11 D Landsham near Munich, Germany

Technical manual. Microstep driver SMC11. NANOTEC ELECTRONIC GmbH & Co. KG Gewerbestraße 11 D Landsham near Munich, Germany Technical manual Microstep driver NANOTEC ELECTRONIC GmbH & Co. KG Gewerbestraße 11 D-85652 Landsham near Munich, Germany Tel. +49 (0)89-900 686-0 Fax +49 (0)89-900 686-50 info@nanotec.de Editorial Editorial

More information

Fan and Pump AC Inverter

Fan and Pump AC Inverter Fan and Pump AC Inverter Key Features for Fan and Pump Applications PID and Auto Energy Saving Functions. Input Phase Loss and Output Phase Loss Protection. LCD Keypad can be used to copy parameter settings

More information

A Subsidiary of Regal-Beloit Corporation. AC Inverter Terminology

A Subsidiary of Regal-Beloit Corporation. AC Inverter Terminology AP200-9/01 Acceleration The rate of change in velocity as a function of time. Acceleration usually refers to increasing velocity and deceleration to decreasing velocity. Acceleration Boost During acceleration,

More information

PP300T060-ND. 3-Phase POW-R-PAK IGBT Assembly 300 Amperes/600 Volts

PP300T060-ND. 3-Phase POW-R-PAK IGBT Assembly 300 Amperes/600 Volts Powerex, Inc., 173 Pavilion Lane, Youngwood, Pennsylvania 15697 (724) 925-7272 www.pwrx.com 3-Phase POW-R-PK IGT ssembly T E K P (4 PLES) +D Q (7 PLES) PIN 1 F K L G F D J H D R +D -D P1 Outline Drawing

More information

150 C 30 F B D 8L 152H C 30 F BD 43 8L

150 C 30 F B D 8L 152H C 30 F BD 43 8L ulletin SM - Smart Motor ontrollers atalog Number Explanation Open and Non-ombination F D L a b c d e f g a ulletin Number Solid-State ontroller b ontroller Type SM- c mpere s N F d Enclosure Type Open

More information

CHAPTER 3 WIRING DANGER

CHAPTER 3 WIRING DANGER CHAPTER WIRING DANGER Hazardous Voltage Before accessing the AC drive: Disconnect all power to the AC drive. Wait five minutes for DC bus capacitors discharge. Any electrical or mechanical modification

More information

Power connections, minimum and maximum wiring capabilities, tightening torque

Power connections, minimum and maximum wiring capabilities, tightening torque Wiring - power terminals Power Observe the cable cross-sectional areas recommended in the standards. The soft starter must be grounded to conform to the regulations concerning leakage currents. If the

More information

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase

More information

PR Rectifier Module

PR Rectifier Module PR500-280 Rectifier Module Block Diagram External Resistor R2 R1 AC (L) Inrush Current Limit Circuit +V External Electrolytic Capacitor + AC (N) -V Power Supply Input Sensing Sequency Timing Diagram More

More information

MTY (81)

MTY (81) This manual describes the option "d" of the SMT-BD1 amplifier: Master/slave electronic gearing. The general information about the digital amplifier commissioning are described in the standard SMT-BD1 manual.

More information

ESR. The Dynamic Solution. Main Characteristics. Applications. ESR Pollmeier GmbH

ESR. The Dynamic Solution. Main Characteristics. Applications. ESR Pollmeier GmbH Modular Multi-Axis Servo System for Any Type of Servo Motors Servo Power Modules for Direct Mains Connection Motion Control Modules for Coordinated Axis Motion MidiDrive C (3 400/480 V AC) Servo Power

More information

System configuration. Ratings 400 V Class three-phase 90 to 800 kw 690 V Class three-phase 90 to 1000 kw SX-D. Frequency inverters.

System configuration. Ratings 400 V Class three-phase 90 to 800 kw 690 V Class three-phase 90 to 1000 kw SX-D. Frequency inverters. ~ ~ SX High performance Vector Control IP54 full range. Compact design & Robustness Built-in Filter according to C3 Class Built-in Fusses (From 200 kw) Safety according EN13849-1 and EN62061 standards

More information

Conventional Paper-II-2013

Conventional Paper-II-2013 1. All parts carry equal marks Conventional Paper-II-013 (a) (d) A 0V DC shunt motor takes 0A at full load running at 500 rpm. The armature resistance is 0.4Ω and shunt field resistance of 176Ω. The machine

More information

EY-EM 527: Remote I/O module, ecolink527

EY-EM 527: Remote I/O module, ecolink527 Product data sheet 94.078 EY-EM 527: Remote I/O module, ecolink527 How energy efficiency is improved Regulation, control, monitoring and optimisation of operational systems, e.g. room automation or HVAC

More information

B25A20FAC SERIES BRUSHLESS SERVO AMPLIFIERS Model: B25A20FAC 120VAC Single Supply Operation

B25A20FAC SERIES BRUSHLESS SERVO AMPLIFIERS Model: B25A20FAC 120VAC Single Supply Operation B25A20FAC Series B25A20FAC SERIES BRUSHLESS SERVO AMPLIFIERS Model: B25A20FAC 120VAC Single Supply Operation FEATURES: All connections on front of amplifier Surface-mount technology Small size, low cost,

More information

D.C. BRUSHLESS MOTORS DRIVE. BLD07-IT Service Manual

D.C. BRUSHLESS MOTORS DRIVE. BLD07-IT Service Manual D.C. BRUSHLESS MOTORS DRIVE BLD07-IT Service Manual INTECNO s.r.l. Via Caduti di Sabbiuno n. 9/E 40011 Anzola Emilia (BO) - Italy tel. 051.19985350 fax 051.19985360 www.intecno-srl.com INDEX Description

More information

EDBEMV!PZi. Ä!PZiä. Electromagnetic compatibility. Global Drive Basic information on controller applications in plants and machinery

EDBEMV!PZi. Ä!PZiä. Electromagnetic compatibility. Global Drive Basic information on controller applications in plants and machinery EDBEMV!PZi Ä!PZiä L Electromagnetic compatibility Global Drive Basic information on controller applications in plants and machinery 2003 Lenze Drive Systems GmbH Without written approval of Lenze Drive

More information

Variable Frequency Drive / Inverter (0.4 ~ 280kW)

Variable Frequency Drive / Inverter (0.4 ~ 280kW) Variable Frequency Drive / Inverter (0.4 ~ 280kW) & Standard Features Configuration Comparison Comparison Table Enclosure IP00 IP20 NEMA 1 Rating Single phase 0.4 2.2kW 0.4 1.5kW Three phase 0.4 4kW Constant

More information

About this Manual: Chapter 1 provides a summary of the Servo System and all gains used for the Servo System loops.

About this Manual: Chapter 1 provides a summary of the Servo System and all gains used for the Servo System loops. About this Manual: This guide describes the installation and startup procedures of the Servo System so that it can be efficiently put in actual operation in a short time. This guide provides detailed descriptions

More information

Contactors and Contactor Assemblies

Contactors and Contactor Assemblies s for Switching Motors Technical data General data Permissible mounting position The contactors are designed for operation on a vertical mounting surface. C and DC operation S3 3RT14 46 For DC operation

More information

ASP-X2. Accelus Panel. Control Modes Current (torque, force)

ASP-X2. Accelus Panel. Control Modes Current (torque, force) 2-AXIS DIGITAL SERVOAMPLIFIER for BRUSHLESS/BRUSH MOTORS Control Modes Current (torque, force) Opto-Isolated Command Interface (per channel) ±0V Current control input Enable input Buffered encoder outputs

More information

8V General information. 2 Order data 8V

8V General information. 2 Order data 8V 8V80.00-8V80.00- General information Modular mechanical design using plug-in modules Integrated line filter Integrated or optional external braking resistor All connections are made using plug-in connectors

More information

8V General information. 2 Order data 8V

8V General information. 2 Order data 8V 8V05.00-8V05.00- General information Modular mechanical design using plug-in modules Integrated line filter Integrated braking resistor All connections are made using plug-in connectors Integrated electronic

More information

Industrial Electrician Level 3

Industrial Electrician Level 3 Industrial Electrician Level 3 Industrial Electrician Unit: C1 Industrial Electrical Code I Level: Three Duration: 77 hours Theory: Practical: 77 hours 0 hours Overview: This unit is designed to provide

More information

General-Purpose AC Servo. MELSERVO-J4 Servo amplifier INSTRUCTION MANUAL (TROUBLE SHOOTING)

General-Purpose AC Servo. MELSERVO-J4 Servo amplifier INSTRUCTION MANUAL (TROUBLE SHOOTING) General-Purpose AC Servo MELSERVO-J4 Servo amplifier INSTRUCTION MANUAL (TROUBLE SHOOTING) K Safety Instructions Please read the instructions carefully before using the equipment. To use the equipment

More information

ADJUSTABLE SPEED DRIVES VF-S11 Sords Electric

ADJUSTABLE SPEED DRIVES VF-S11 Sords Electric ADJUSTABLE SPEED DRIVES VF-S11 The Next Generation of Micro Inverters is Here. The S11 provides maximum torque with precise speed control. It features an easy-to-use, quiet and compact design. In addition,

More information

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103383_en_00 1 Description PHOENIX CONTACT - 06/2008 Features QUINT POWER power supply units highest system

More information

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300 Monitoring Technique VARIMETER IMD Insulation monitor RN 5897/300 0274214 Your Advantages For mobile generator sets according to DIN VDE 0100-551 Preventive fire and system protection Detection of symmetric

More information

Computer-14d - xx - 144a

Computer-14d - xx - 144a POWER FACTOR REGULATOR Computer-14d - xx - 144a INSTRUCTION MANUAL ( M 981 602 / 98B ) (c) CIRCUTOR S.A. -------- POWER FACTOR REGULATOR COMPUTER- 14d --------- Page 2 1.- POWER FACTOR REGULATORS COMPUTER-14d-144a

More information

Troubleshooting Alarm Displays Warning Displays

Troubleshooting Alarm Displays Warning Displays 10 10.1 Alarm Displays............................................10-2 10.1.1 List of Alarms...................................................... 10-2 10.1.2 of Alarms............................................

More information

NXL HVAC APPLICATION MANUAL Programming manual for NXL HVAC drives

NXL HVAC APPLICATION MANUAL Programming manual for NXL HVAC drives NXL HVAC APPLICATION MANUAL Programming manual for NXL HVAC drives Page 2 (68) Index Honeywell HVAC Application (Software [ALFIQ105] Ver.2.09) INDEX 1. INTRODUCTION... 3 2. CONTROL I/O... 3. HVAC APPLICATION

More information

INSTALLATION MANUAL NE2110, NE2120 D.C. SERVO CONTROLLERS

INSTALLATION MANUAL NE2110, NE2120 D.C. SERVO CONTROLLERS INSTALLATION MANUAL NE2110, NE2120 D.C. SERVO CONTROLLERS NORWIN ELECTRONICS LIMITED Unit 6, Industrial Estate, Station Road, Gamlingay, Sandy, Bedfordshire. SG19 3HB Telephone: 01767 651485 Fax: 01767

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

Absolute Encoders - Singleturn

Absolute Encoders - Singleturn The Sendix 5 and Sendix 7 singleturn encoders with SSI or BiSS-C interface and optical sensor technology can achieve a resolution of max. 7 bits. These encoders are also available with an optional SinCos

More information

Thermistor motor protection relays

Thermistor motor protection relays Thermistor motor protection relays Content Benefits and advantages... / 68 Selection table... / 68 Ordering details CM-MSE... / 69 CM-MSS... / 69 CM-MSN... / 7 PTC sensor C0... / 7 Technical data... /

More information

MCR-T-UI(/NC) MCR-T-UI-E(/NC)

MCR-T-UI(/NC) MCR-T-UI-E(/NC) MCR-T-UI(/) MCR-T-UI-E(/) Programmable Temperature Transducers for Resistance Thermometers and Thermocouples INTERFACE ata Sheet 00_0_en PHOENIX CONTACT - 0/00 escription A universal temperature measuring

More information

BLD75-1. Bilevel Step Motor Driver. User s Guide. #L010125

BLD75-1. Bilevel Step Motor Driver. User s Guide.   #L010125 BLD75-1 Bilevel Step Motor Driver User s Guide A N A H E I M A U T O M A T I O N #L010125 1 Features Unipolar Operation 10 Amps per Phase Operating Current (Kick Current) 7 Amps per Phase Standstill Current

More information

Isolated, Frequency Input 5B45 / 5B46 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Isolated, Frequency Input 5B45 / 5B46 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM Isolated, Frequency Input 5B45 / 5B46 FEATURES Isolated Frequency Input. Amplifies, Protects, Filters, and Isolates Analog Input. Generates an output of 0 to +5V proportional to input frequency. Model

More information

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual INDEX A AC Drive Cover: 1 6 Dimensions: 2 4 External Parts and Labels: 1 6 Heat Sink Fins: 1 6 Input Mode Switch (Sink/Source): 1 6 Introduction to DuraPulse GS3 AC drive: 1 3 Keypad: 1 6 Model Number

More information

PACSystems* RX3i IC695MDL765

PACSystems* RX3i IC695MDL765 March 2011 PACSystems* RX3i IC695MDL765 Digital Output Module with Diagnostics 16-Channel The 24/125 volt DC 2A Smart Digital Output module, IC695MDL765, provides 16 discrete outputs in two isolated groups

More information

ADJUSTABLE SPEED DRIVES. AS1 Drive

ADJUSTABLE SPEED DRIVES. AS1 Drive ADJUSTABLE SPEED DRIVES AS1 Drive Toshiba s New ASD Product Line The AS1 drive builds on Toshiba s history of supplying powerful, reliable, and versatile drives. We have combined our best drive features

More information

DigiFlex Performance Servo Drive DPRAHIR-060A400

DigiFlex Performance Servo Drive DPRAHIR-060A400 DigiFlex Performance Servo Drive DPRAHR-060A400 Description Power Range The DigiFlex Performance (DP) Series digital servo drives are designed to drive brushed and brushless servomotors. These fully digital

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

Excitation Systems. Service Generators SIPOL. Transistorized Excitation Systems for Synchronous Generators. Power Generation

Excitation Systems. Service Generators SIPOL. Transistorized Excitation Systems for Synchronous Generators. Power Generation Excitation Systems Service Generators Transistorized Excitation Systems for Synchronous Generators Power Generation Operating Characteristics High availability Reliability Digital control facilities Very

More information

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class HITACHI SJ1 Series Inverter Quick Reference Guide Single-phase Input 2V Class Three-phase Input 2V Class Three-phase Input 4V Class Hitachi Industrial Equipment Systems Co., Ltd. Manual No. NB5821XD Dec.

More information