HVDC MULTI-INFEED PERFORMANCE
|
|
- Lucinda Gilmore
- 5 years ago
- Views:
Transcription
1 MULTI-INFEED PERFORMANCE Göran Andersson, Paulo Fischer de Toledo and Göte Liss ABB Power Systems S Ludvika, Sweden 1 Abstract The number of power system configurations with two or more links feeding power to different points in the same network area is increasing as the total number of links in the world increases. This gives rise to a greater interest in studying the performance of such applications. A very special and extreme case of multi-infeed is the asynchronous interconnection of the Scandinavian (the NORDEL) network to Continental Europe, today by 6 cable poles, but probably using more poles in the future. A number of technical aspects specifically related to multiinfeed configurations must be considered: - Is coordination of recovery control needed? - How can DC power modulation for stabilization be established? - Infeed by two or more DC transmissions to one and the same network area often means that a large amount of power is fed into a network that is relatively weak, thus risking voltage instability. - The consequence of feeding a large amount of power into a weak network must be considered. - How effective is the electrical separation between inverters in reducing the risk of mutual commutation failures? 2 Introduction In a few places in the world, two or more transmission systems terminate electrically close to each other in the same network. The most extreme example of this kind of transmission system is of course multiple bipole infeed, not only to the same network but to the same place in the network. This can be found in Brazil, where the Itaipu transmission constitutes a double bipole scheme transmitting 6300 MW in all from the Itaipu power station to Ibiuna outside São Paulo. It is quite clear that there has to be mutual interference between the two inverters in this case and an network disturbance which causes commutation failures in one bipole affects the other bipole in the same way. The situation is of course the same for a normal bipole. However, if the DC links terminate at separate places, i.e., if the inverters are electrically separated by impedances in the network, the interaction will always be less than in the previous case. This is what we normally mean by multi-infeed, and problems are then reduced compared with multiple bipoles ending up at the same place. 3 The Northern Europe Cable Schemes The most obvious example of multi-infeed networks are to be found in Scandinavia and between Scandinavia and Continental Europe; and more are to come. U.K. NETHER- LANDS NORWAY DENMARK GERMANY SWEDEN POLAND FINLAND Figure 1. Existing and planned links in Northern Europe. Fig. 1 shows a map of the area mentioned above with the existing links, as well as those which are to come in the near future. It is clear that the interesting geographical areas from the point of view of multi-infeed are the north of the Danish peninsula, Southern Norway and the European continent. The five cables terminating in the north of Jutland, namely Skagerrak I, II and III from Norway, and Konti-Skan I and II from Sweden, have been in operation for a number of years. The two cables crossing each other in the Baltic Sea are the Kontek project from the island of Zealand in Denmark to Rostock in the Germany and the Baltic Cable from the far south of Sweden to the Lübeck area, also in Germany. Both have come into operation recently. Finally, there are three extremely long cables in Fig. 1 running from Norway to the north-west of Germany and the Nederlands. This scheme will be implemented in the near future. As can be seen in Fig. 2, two of the Skagerrak cables are connected to the 150 network, while the third terminates in the 400 network. Thus there is a transformer with its impedance between the two converter stations. Already here we can see a multi-infeed configuration. Further, the two Konti-Skan cables are connected to the two different systems in Denmark with a transformer in between. The Konti-Skan terminals and the Skagerrak terminals are interconnected by lines with their impedances.
2 The Skagerrak/Konti-Skan system is obviously a sophisticated multi-infeed arrangement which was planned both in the simulator and through computer simulation using a transient stability program. NORWAY this occurence, an existing telecommunication link was used to send an order from one station to the other to increase the commutation margin reference just before an intentional switching operation was to be carried out. The detrimental consequence of the strong electrical coupling between the two converter sites was reduced significantly by this measure. This solution will not help where there is protective switching of apparatuses but such cases are of course much rarer than intentionally controlled switchings and can be accepted. Kristiansand SWEDEN 5 Simulator Study for Skagerrak I, II & III and Konti-Skan II Skagerrak DENMARK (Jutland) Tjele 150 Vester Hassing Konti-skan to Germany Gothenburg 400 An simulation study of the dynamic performance of the multi-infeed scheme with simultaneous operation of the Skagerrak III, Skagerrak I & II and Konti-Skan II transmissions has been performed. The main purpose of the study was to determine any restriction that had to be imposed for the configuration. An equivalent of the system model representing the Tjele and Vester Hassing area was derived in the transient stability program. This includes the main busses and synchronous machine model as shown in Fig. 3 and was developed with the criterion of providing similarity to the results of a complete network model. Figure 2. Detail map for the Skagerrak/Konti Skan arrangements. 4 Characteristics of the Skagerrak/Konti-Skan Systems In conjunction with the fundamental frequency overvoltage study for this configuration, performed with the transient stability program, it was found that, in extreme conditions, the Jutland network suffered from voltage instability if a large amount of power was fed into the Danish peninsula. The fault case when this actually occured was a fault on and loss of the 400 line from Tjele, the converter site for the Skagerrak cables, southwards to Germany. This caused a transition from a relative strong network on the peninsula to a very weak one. It would have been necessary to reduce the total amount of transmitted power on the DC line in order to achieve a successful recovery after the fault. Although the configuration discussed here is a typical multi-infeed arrangement, the phenomenon mentioned whould, of course, also have happened if all the DC power was delivered to the same point in the Danish network. There has never been any reason to study this eventuality. The fault case is question was also studied in the simulator and the same behaviour was found. However, the critical level of transmitted power was slightly higher here, %, than in the computer study. The fact that the four infeed points are separated by impedances makes the situation rather less critical than if the power had been fed into one and the same point. The last section of this report deals with some theoretical aspects concerning how the risk of voltage instability depends on the degree of electrical coupling between the inverters in a multi-infeed scheme. A more typical multi-infeed phenomenon experienced in this scheme is the mutual electrical coupling of disturbances between the converter sites. It was observed that switching a filter or transformer in the Konti-Skan converter station could cause a commutation failure in the Skagerrak station. It should be noted that reinsertion resistors were not installed in the switches. To avoid Figure 3. A five-bus equivalent of the Jutland network for the simulator. The results of the study showed that the systems can be safely operated with no restrictions where there is a normal network configuration. Fig. 4 shows a typical recovery of each transmission system after a three-phase solid fault in the Tjele 400 network. In this model the converters in Norway and Sweden are rectifiers, and Tjele and Vester Hassing are the inverters. Nominal power transmission was assumed for this case. In the case where the inverter network is assumed to be very weak the study has indicated high risk of repeated voltage collapses and commutation failures. Operating restrictions were imposed on this configuration. 6 The Baltic Cable/ Kontek/Great Belt Schemes Baltic Cable and Kontek are two DC cables crossing each other in the south of the Baltic Sea. Baltic Cable has one converter station in the south of Sweden and the other close to Lübeck in the former West Germany. Kontek runs between the island of Zealand in Denmark and Rostock in what was previously East
3 Figure 4. Simulator recordings of the recovery after a solid 3- phase fault at the 400 bus in Tjele. Germany. Zealand is connected to Sweden by a number of cables and is, accordingly, synchronous with Sweden, Norway and Finland. The interconnection between Lübeck and Rostock is normally a 400 line and the two places are not strongly separated electrically. Here again we see a multi-infeed system; however, less complex than the previous one. A project which is probably going to be implemented in the near future is the Great Belt link connecting Zealand to the other large Danish island, Fyn. The latter is synchronous with the Jutland network and the converter station here will have a powerful connection, via a 400 line, to Northern Germany. 7 Simulator Study for the Baltic Cable/ Kontek/Great Belt Schemes This study was carried out in order to identify and investigate possible system interactions between the system and the three links which connect the south of Denmark, southern Sweden, northern Germany and the Jutland peninsula. Special attention was given to the risk of commutation failures in each of the systems. A demonstration of the performance during recovery of system faults was made and verification was also carried out of the overall stability of the system in some special weakened network configurations. A suitable network equivalent, including 23 buses and 8 generators provided by the concerned utilities, was used and is shown in Figs. 5 and 6. The models included the actual plant data for the Baltic Cable and Kontek projects. Regarding the Great Belt link, due to the similarity of this project to the Kontek transmission, the same data were used, but with the appropriate figure for the cable length. An important general result of the study was that the system has proved to have an overall acceptable performance. Both Kontek and Baltic Cable performed as expected during system disturbances. Thus the basic control and parameters were found to be adequate in these projects. With respect to the Great Belt link, some adjustments of the controls had to be made in order to ensure safer operation. In this project the DC cable is shorter than those of the Kontek and Baltic Cable links. Due to this characteristic, the system presented a rather fast recovery time from system faults and also the capability of transmitting a significant amount of power during asymmetric faults. As a result of these observations, some necessary changes to the settings of the current control amplifier and voltage dependent current limiter were introduced. In general, the three systems presented a number of mutual interactions. In quite a few configurations that were elec- Figure 5. A 13 bus equivalent for the synchronous Nordel network with Baltic Cable, Kontek and the Great Belt project. trically closely connected, an fault in the vicinity of one inverter bus can produce commutation failures in the neighbouring transmission link. It was also observed in an another load flow configuration that a trip of one link can produce commutation failure in the other ones. This is a consequence of a sudden load rejection with an accompanying voltage phase shift in the network which can make the converters lose their commutation margin. Figure 6. A 10 bus equivalent for the synchronous Northern UCPT network with the same projects as in Figure 4. In a particular network configuration, the result of the study showed that during the recovery of the systems from faults in a weak system, with a consequential split of a bus in the Nordel area, the systems displayed a tendency towards dynamic instability, see Fig.7. In this configuration, where all three transmission systems feed rated power into the Nordel equivalent (power direction: north/east), the fault case proved to be very severe. It has consequently been verified that a damping controller function,
4 tion will very briefly review these concepts and propose an extension of these that is applicable to multi-infeed systems. Figure 7. Simulator recordings for the Baltic Cable / KONTEK / Great Belt study. similar to that existing in the Kontek link, if implemented in the Great Belt link, would have a positive impact in increasing the damping of the generators connected in the Nordel area. Another alternative and possible complementary solution considered in the study was to introduce some kind of run back of DC power in the Great Belt controls. There is also one more network configuration where an asymmetric fault close to the Great Belt rectifier converter bus (ELS bus) may cause commutation failure in the Kontek link during the fault, or during the recovery of the system, when the fault is cleared. The configuration used in this fault case assumes rated power flow from the Nordel area, which means that all three links have a common rectifier equivalent. This result again shows an example of a strong interaction between the systems. In this particular fault case, it has been observed that the Great Belt link is well able to operate and transmit power from an unsymmetrical network. This affects the receiving network in that it accepts a significant injection of harmonics. To avoid this interaction, i.e., to avoid an fault being transmitted between areas through the links, the power flow through the Great Belt link was limited during faults. Further control changes were also made to avoid power overshoots during the clearance of the fault. The basic conclusion from this study verification was that the Nordel system presents a satisfactory performance during transients, although there is some interaction between the systems. With appropriate control tuning and control strategy implemented in the Great Belt link, the obtained interactions will be minimized to an acceptable level without severe restrictions. In the Kontek and Baltic Cable links, there will be no special change in the controls. The performance here is adequate. 8 Analysis of Voltage/Power Stability As the complexity of the interconnected /DC power systems increases, there is a need for a systematic approach to analyze the various stability limits of the system. One stability limit that is of great importance, particularly when the system is weak as compared with the rating of the converters, is the voltage/power stability limit. For a single converter feeding into an power system, the risk of voltage/power instability has been extensively studied over the years, and a comprehensive overview of this topic is given in [1]. One of the main results presented in [1] consists of the analytical criteria for voltage/power stability represented by the Effective Short-Circuit Ratio (ESCR), or the Voltage Sensitivity Factor (VSF). This sec- 8.1 Analysis of Single-Infeed System In the analysis of the voltage/power stability in the considered time frame, the system can be represented by an impedance determined by the short circuit capacity. A motivation for and discussion of the validity of this model can be found in [1]. It can be shown that when the system short circuit capacity is lowered, i.e., the equivalent impedance is increased, the system ultimately becomes unstable. This stability limit is dependent on parameters of the converters, e.g. commutation reactance and commutation margin, but also to a large extent on the control strategy. It is found that constant power control with constant commutation margin control encounters the stability limit first, i.e., for the highest ESCR value, but that this limit can be extended to lower ESCR values by use of more sophisticated controls. However, these more sophisticated controls require operation with higher commutation margins and the converters, converter transformer and reactive comensation must be upgraded accordingly, which involves extra cost. Typical values where instability is reached for standard controls are for ESCR values of around 1.5 (SCR» 2) and lower. A useful measure of the voltage/power stability is given by the Voltage Sensitivity Factor (VSF) defined by: VSF = U Q where Q is a small reactive power injection at the commutation bus and U the corresponding change in the magnitude of the voltage at the commutation bus. A small and positive value of VSF indicates stable operation and an increasing value of VSF corresponds to a decreasing stability margin. When VSF becomes infinite, transition to unstable operation occurs, and a negative value of VSF is found in the unstable region. The fact that VSF goes to infinity at the stability limit is unattractive from an analytical point of view and therefore 1/VSF is often studied instead. 8.2 Analysis of Multi-Infeed Systems The above analysis will now be extended to multi-infeed systems, as reported in [2]. To demonstrate the method, a system with two converter stations according to Fig. 8 will be used, but the method can be applied to systems with any number of converter stations. In this paper, only the main results of the method are given and the reader is referred to [2] for a more detailed derivation of and motivation for the method. In analogy with VSF, the following relationship between reactive power injections at the commutation buses and voltage magnitude changes can be derived as: Q 1 Q 2 = J R U 1 U 1 U 2 U 2 where J R is the 2 by 2 reduced Jacobian matrix. It is easily seen that J R corresponds to 1/VSF as defined above. In (2) the relative voltage changes have been introduced. Equation (2) can be written in compact form as: Q = J R U U where Q and U now are vectors with two components each. The stability of the system is determined by the eigenvalues of J R : (1) (2) (3)
5 * Positive eigenvalues indicate stability and if any eigenvalue becomes negative the unstable regime is encountered. ESCR2 It can be shown that, for the considered system, positive eigenvalues correspond to a situation where a reactive power injection in any of the commutation buses results in voltage magnitude increases at the buses in the system. z 1 θ 1 P 1, Q 1 U 1 δ 1 Q d1 P d1 I d1 U d ESCR1= 1.06, PBR= 0.5 p x x Pz 12 Stable x P ESCR Unstable E 1 ψ 1 P 12,Q 12 b c z 12 (p.u.) E 2 ψ 2 z 12 θ 12 P 21,Q 21 Q d2 P d2 I d2 U d2 Figure 10. Stable and unstable regions of the system in Figure 9. (PBR is the ratio between the rated powers of stations 1 and 2.) z 2 θ 2 P 2, Q 2 U 2 δ 2 Figure 8. Model of interconnected /DC system with two converter stations. 8.3 Practical Application The above method will now be demonstrated for a practical case. Consider the situation in Fig. 9. z 12 Fig. 9 illustrates a situation where an subsystem, subsystem 2, exists in the vicinity of /DC. A new link is planned for and with that an interconnection with /DC is also envisaged, perhaps to export the then excess power of /DC to system 1. Here, the system planner would be interested to know the relationship between the coupling impedance, z 12, and the ESCR of /DC for stable operation of the integrated / DC system. The rating of station 2 is twice that of station 1. In the z 12 -ESCR2 plane the border line between stable and unstable operation is shown in Fig. 10. b c2 /DC Planned interconnection /DC Figure 9. Planning of a new link and interconnection. When calculating the graph in Fig. 10 the following assumptions have been made: First, that there is constant power control with constant commutation margin in both stations. Furthermore, parts of the original are included in z 12, which explains the relatively low value of ESCR1, i.e., From Fig. 9 it is clearly seen that the stronger the interconnection is, i.e., the lower the value of z 12 is, the lower is the value of ESCR2 needed for stable operation. (Note that the ESCR2 value in Fig. 9 is calculated from the power rating of station 1. If calculated based on station 2, the value will be half of that indicated.) Depending on the costs and other parameters of the system, the system planner can decide which choice of ESCR2 and z 12 in the stable region gives the optimum solution. Simulations involving a transient stability program with a detailed representation of the stations and their controls verify the stability regions in Fig. 10; i.e., the point indicated by p is stable whereas pescr and pz12 are unstable. 8.4 Concluding Remarks The method described above is a generalization of the method of analysis used for single-infeed systems. The method has recently been proposed and work is currently going on concerning the implications and use of the method. It is the intention that it should be a powerful and useful method for the system planner in the future when analyzing and designing multi-infeed systems. References [1] Guide for Planning DC Links Terminating at System Locations Having Low Short-Circuit Capacities, Part I: /DC Interaction Phenomena, Cigré-IEEE Joint WG, ( ), Cigré Technical Brochure 68, Paris, France, [2] Denis Lee Hau Aik and Göran Andersson, Voltage Stability Analysis of Multi-Infeed Systems. To be presented at IEEE SPM 1996.
6
HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN
HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN Summary Capacitor Commutated Converters (CCC) were introduced to the HVDC market
More informationA new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant alternating voltage
21, rue d Artois, F-758 PARIS B4_16_212 CIGRE 212 http : //www.cigre.org A new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant
More informationLARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS
LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS Giuseppe Di Marzio NTNU giuseppe.di.marzio@elkraft.ntnu.no Olav B. Fosso NTNU olav.fosso@elkraft.ntnu.no Kjetil Uhlen SINTEF
More informationA cost effective hybrid HVDC transmission system with high performance in DC line fault handling
2, rue d Artois, F-758 PARIS B4-7 CIGRE 28 http : //www.cigre.org A cost effective hybrid HVDC transmission system with high performance in DC line fault handling Mats Andersson, Xiaobo ang and ing-jiang
More informationPower System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )
21, rue d Artois, F-75008 PARIS SECURITY AND RELIABILITY OF ELECTRIC POWER SYSTEMS http : //www.cigre.org CIGRÉ Regional Meeting June 18-20, 2007, Tallinn, Estonia Power System Reliability and Transfer
More informationStability Improvement for Central China System
Stability Improvement for Central China System Kjell-Erik Högberg, Marie Ericsson, Abhay Kumar, Kerstin Lindén and Wen Weibing. Abstract--The stability study has been performed investigating the conditions
More informationINVESTIGATION INTO THE HARMONIC BEHAVIOUR OF MULTIPULSE CONVERTER SYSTEMS IN AN ALUMINIUM SMELTER
INVESTIGATION INTO THE HARMONIC BEHAVIOUR OF MULTIPULSE CONVERTER SYSTEMS IN AN ALUMINIUM SMELTER Abstract S Perera, V J Gosbell, D Mannix, Integral Energy Power Quality Centre School of Electrical, Computer
More informationC1-207 TRANSMISSION CAPACITY INCREASE BY RETURNING POWER SYSTEM STABILIZERS
21, rue d'artois, F-75008 Paris http://www.cigre.org C1-207 Session 2004 CIGRÉ TRANSMISSION CAPACITY INCREASE BY RETURNING POWER SYSTEM STABILIZERS STEFAN ELENIUS* JUSSI JYRINSALO SIMO JOKI-KORPELA HELSINKI
More informationChapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two
Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead
More informationA NEW APPROACH FOR MODELING COMPLEX POWER SYSTEM COMPONENTS IN DIFFERENT SIMULATION TOOLS
A NEW APPROACH FOR MODELING COMPLEX POWER SYSTEM COMPONENTS IN DIFFERENT SIMULATION TOOLS Per-Erik Bjorklund Jiuping Pan Chengyan Yue Kailash Srivastava ABB Power Systems ABB Corporate Research ABB Corporate
More information. Voltage stability of multi-infeed power system
2006 International Conference on Power System Technology 1 Study of coordinate Control method to Improve Stability on Multi Infeed HVDC system Su Su *, Kiyotaka Ueda *, Member IEEJ, Kazuyuki Tanaka *,
More informationAnalysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.
Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link. Mr.S.B.Dandawate*, Mrs.S.L.Shaikh** *,**(Department of Electrical Engineering, Walchand College of
More informationELEMENTS OF FACTS CONTROLLERS
1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are
More informationANALYTICAL AND SIMULATION RESULTS
6 ANALYTICAL AND SIMULATION RESULTS 6.1 Small-Signal Response Without Supplementary Control As discussed in Section 5.6, the complete A-matrix equations containing all of the singlegenerator terms and
More informationTor Rolv Time, Øystein Kirkeluten STATNETT Oslo, Norway
RAISING STABILITY LIMITS IN THE NORDIC POWER TRANSMISSION SYSTEM Kjetil Uhlen, Magni Þ. Pálsson SINTEF Energy Research Trondheim, Norway kjetil.uhlen@energy.sintef.no Tor Rolv Time, Øystein Kirkeluten
More informationDynamic stability of power systems
Dynamic stability of power systems Dr Rafael Segundo Research Associate Zurich University of Applied Science segu@zhaw.ch SCCER School- Shaping the Energy Transition Engelberg, 20 October 2017 Agenda Fundamentals
More informationVoltage Source Converter Modelling
Voltage Source Converter Modelling Introduction The AC/DC converters in Ipsa represent either voltage source converters (VSC) or line commutated converters (LCC). A single converter component is used to
More informationAORC Technical meeting 2014
http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi
More informationImprovement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System
Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System 1 Ramesh Gantha 1, Rasool Ahemmed 2 1 eee Kl University, India 2 AsstProfessor, EEE KL University,
More informationFacilitating Bulk Wind Power Integration Using LCC HVDC
21, rue d Artois, F-758 PARIS CIGRE US National Committee http : //www.cigre.org 213 Grid of the Future Symposium Facilitating Bulk Wind Power Integration Using LCC HVDC A. HERNANDEZ * R.MAJUMDER W. GALLI
More informationHVDC Multi-infeed Commutation Failure Analysis within the Brazilian System with the Insertion of Bipoles A and B
HVDC Multi-infeed Commutation Failure Analysis within the Brazilian System with the Insertion of Bipoles A and B José A. Jardini Renato Biase Ricardo L. V. Arnez John F. Graham Liu Guijun Contents Introduction
More informationAbout the High-Frequency Interferences produced in Systems including PWM and AC Motors
About the High-Frequency Interferences produced in Systems including PWM and AC Motors ELEONORA DARIE Electrotechnical Department Technical University of Civil Engineering B-dul Pache Protopopescu 66,
More informationChapter 10: Compensation of Power Transmission Systems
Chapter 10: Compensation of Power Transmission Systems Introduction The two major problems that the modern power systems are facing are voltage and angle stabilities. There are various approaches to overcome
More information1400 MW New Zealand HVDC Upgrade: Introducing Power Modulation Controls and Round Power Mode
1400 MW New Zealand HVDC Upgrade: Introducing Power Modulation Controls and Mode Simon P. Teeuwsen Network Consulting Siemens AG Erlangen, Germany simonp.teeuwsen@siemens.com Abstract The existing HVDC
More informationADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION
23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB
More informationA Real-Time Platform for Teaching Power System Control Design
A Real-Time Platform for Teaching Power System Control Design G. Jackson, U.D. Annakkage, A. M. Gole, D. Lowe, and M.P. McShane Abstract This paper describes the development of a real-time digital simulation
More informationImproving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC)
International Journal of Scientific and Research Publications, Volume 2, Issue 5, May 2012 1 Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC) K. Manoz
More informationArvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India
e t International Journal on Emerging Technologies 4(1): 10-16(2013) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Control of Synchronous Generator Excitation and Rotor Angle Stability by
More informationTransient Stability in Low Frequency Railways with Mixed Electronic and Rotational Generation
LICENTIATE T H E SIS Transient Stability in Low Frequency Railways with Mixed Electronic and Rotational Generation John Laury Electric Power Engineering Transient Stability in Low Frequency Railways with
More informationJRC MODIFIED VOLTAGE CONTROL LAW FOR LOW FREQUENCY RAILWAY POWER SYSTEMS
Proceedings of the 27 IEEE/ASME Joint Rail Conference JRC27 April 4-7, 27, Philadelphia, PA, USA JRC27-2224 MODIFIED VOLTAGE CONTROL LAW FOR LOW FREQUENCY RAILWAY POWER SYSTEMS John Laury Electric Power
More informationCurso de Transmissão em Corrente Continua Rio de Janeiro, de Junho, 2007
Curso de Transmissão em Corrente Continua Rio de Janeiro, 13 15 de Junho, 2007 DC Harmonic Filters Page 1 of 9 1 Function of the DC-Side Harmonic Filters Harmonic voltages which occur on the dc-side of
More informationSimulative Study into the Development of a Hybrid HVDC System Through a Comparative Research with HVAC: a Futuristic Approach
Engineering, Technology & Applied Science Research Vol. 7, No. 3, 2017, 1600-1604 1600 Simulative Study into the Development of a Hybrid HVDC System Through a Comparative Research with HVAC: a Futuristic
More informationPower Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)
Power Plant and Transmission System Protection Coordination Loss-of of-field (40) and Out-of of-step Protection (78) System Protection and Control Subcommittee Protection Coordination Workshop Phoenix,
More informationIncreasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC)
Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC) K. Manoz Kumar Reddy (Associate professor, Electrical and Electronics Department, Sriaditya Engineering College, India)
More informationDesign and Simulation of Passive Filter
Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt
More informationZambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years
21, rue d Artois, F-758 PARIS B4-18 CIGRE 216 http : //www.cigre.org Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years T G MAGG, Power System
More informationInvestigation of negative sequence injection capability in H-bridge Multilevel STATCOM
Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM Ehsan Behrouzian 1, Massimo Bongiorno 1, Hector Zelaya De La Parra 1,2 1 CHALMERS UNIVERSITY OF TECHNOLOGY SE-412
More informationModle 6 : Preventive, Emergency and Restorative Control. Lecture 29 : Emergency Control : An example. Objectives. A simple 2 machine example
Modle 6 : Preventive, Emergency and Restorative Control Lecture 29 : Emergency Control : An example Objectives In this lecture you will learn the following An example to illustrate the system angular instability
More informationUSE OF HVDC MULTI TERMINAL OPTIONS FOR FUTURE UPGRADE OF THE NATIONAL GRID
USE OF HVDC MULTI TERMINAL OPTIONS FOR FUTURE UPGRADE OF THE NATIONAL GRID JOS ARRILLAGA Emeritus Professor, FIEE, FIEEE, MNZM 2/77 HINAU STREET, RICCARTON CHRISTCHURCH ARRILLJ@ELEC.CANTERBURY.AC.NZ TELEPHONE
More informationThe Baltic Ring Study Transmission System Simulations in the Baltic Sea Region
The Baltic Ring Study Transmission System Simulations in the Baltic Sea Region Dr. Hans Knudsen NESA, Denmark Lars-Ove Ellus Vattenfall Transmission AB, Sweden Mikko Koskinen Fingrid, Finland Dr. Matthias
More informationPlanning the Next Nelson River HVDC Development Phase Considering LCC vs. VSC Technology
21, rue d Artois, F-75008 PARIS B4-103 CIGRE 2012 http : //www.cigre.org Planning the Next Nelson River HVDC Development Phase Considering LCC vs. VSC Technology D.A.N. JACOBSON 1, P. WANG 1, C. KARAWITA
More informationApplication Example Document ID: SA Rev. - September 24, 2004
Application Example Rev. - September 24, 2004 1 Summary Phasor based control of braking resistors A case study applied to large power oscillations experienced in the Swedish grid 1997 Phasor measurement,
More informationCable Compensation of a Primary-Side-Regulation (PSR) Power Supply
Lion Huang AN011 April 014 Cable Compensation of a Primary-Side-Regulation (PSR) Power Supply Abstract Cable compensation has been used to compensate the voltage drop due to cable impedance for providing
More informationAndrea Zanchettin Automatic Control 1 AUTOMATIC CONTROL. Andrea M. Zanchettin, PhD Winter Semester, Linear control systems design Part 1
Andrea Zanchettin Automatic Control 1 AUTOMATIC CONTROL Andrea M. Zanchettin, PhD Winter Semester, 2018 Linear control systems design Part 1 Andrea Zanchettin Automatic Control 2 Step responses Assume
More informationS.A.Soman. Power Swing Detection, Blocking and Out of Step Relaying. Department of Electrical Engineering IIT Bombay. Power System Protection
Department of Engineering IIT Bombay Power Swing Detection, and Relaying Power Swing Detection, and Out of Step Relaying 1 2 3 4 5 Setting of 6 7 8 Power Swing Detection, and Out of Step Relaying Power
More informationUNIVERSITY OF CAMBRIDGE INTERNATIONAL EXAMINATIONS Cambridge International Level 3 Pre-U Certificate Principal Subject
UNIVERSITY OF CAMBRIDGE INTERNATIONAL EXAMINATIONS Cambridge International Level 3 Pre-U Certificate Principal Subject www.xtremepapers.com PHYSICS 9792/02 Paper 2 Part A Written Paper May/June 2011 PRE-RELEASED
More information1
Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive
More informationThe Thyristor based Hybrid Multiterminal HVDC System
The Thyristor based Hybrid Multiterminal HVDC System Chunming Yuan, Xiaobo Yang, Dawei Yao, Chao Yang, Chengyan Yue Abstract In the multiterminal high voltage dc current (MTDC) transmission system, the
More informationIntegration of Wind Generation into Weak Grids
Integration of Wind Generation into Weak Grids Jason MacDowell GE Energy Consulting NERC ERSTF Atlanta, GA December 10-11, 2014 Outline Conventional and Power Electronic (PE) Sources Stability limitations
More informationModelling of VSC-HVDC for Slow Dynamic Studies. Master s Thesis in Electric Power Engineering OSCAR LENNERHAG VIKTOR TRÄFF
Modelling of VSC-HVDC for Slow Dynamic Studies Master s Thesis in Electric Power Engineering OSCAR LENNERHAG VIKTOR TRÄFF Department of Energy and Environment Division of Electric Power Engineering Chalmers
More informationTransient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme
I J E E E C International Journal of Electrical, Electronics ISSN No. (Online) : 2277-2626 and Computer Engineering 2(1): 7-12(2013) Transient stability improvement by using shunt FACT device (STATCOM)
More informationTransient Stability Analysis of Multimachine System Using Statcom
IOSR Journal of Engineering (IOSRJEN) e-issn: 2250-3021, p-issn: 2278-8719 Vol. 3, Issue 5(May. 2013), V3 PP 39-45 Transient Stability Analysis of Multimachine System Using Statcom Sujith. S, T.Nandagopal
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationNERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell
Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June
More informationPower Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer
Power Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer C.GOPI*, M.KISHOR** *(Department. of Electrical and Electronics Engineering, SVPCET, Puttur)
More informationESB National Grid Transmission Planning Criteria
ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and
More informationAnalysis of the Effectiveness of Grid Codes for Offshore Wind Farms Connected to Onshore Grid via VSC-Based HVDC
Conference of the Wind Power Engineering Community Analysis of the Effectiveness of Grid Codes for Offshore Wind Farms Connected to Onshore Grid via VSC-Based HVDC Moritz Mittelstaedt, Andreas Roehder,.Hendrik
More informationMODEL POWER SYSTEM TESTING GUIDE October 25, 2006
October 25, 2006 Document name Category MODEL POWER SYSTEM TESTING GUIDE ( ) Regional Reliability Standard ( ) Regional Criteria ( ) Policy ( ) Guideline ( x ) Report or other ( ) Charter Document date
More informationEH2741 Communication and Control in Electric Power Systems Lecture 2
KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationPOWER QUALITY ENHANCEMENT BY DC LINK SUPPLIED INDUSTRIAL SYSTEM
POWER QUALITY ENHANCEMENT BY DC LINK SUPPLIED INDUSTRIAL SYSTEM A.Karthikeyan Dr.V.Kamaraj Sri Venkateswara College of Engineering Sriperumbudur, India-602105. Abstract: In this paper HVDC is investigated
More informationAssessment of Saturable Reactor Replacement Options
Assessment of Saturable Reactor Replacement Options D.T.A Kho, K.S. Smith Abstract-- The performance of the dynamic reactive power compensation provided by the existing variable static compensation (STC)
More informationLab 1. Objectives. Single Line Diagram. Methodology. Observations. Jon Jawnsy Yu 26 October 2009
Lab 1 Objectives In this lab, our objective is to simulate a simple single machine infinite bus configuration using the PowerWorld Simulator software. We design a local generator system (a synchronous
More informationTransient Stability Improvement Of Power System With Phase Shifting Transformer
INTERNATIONAL JOURNAL OF TECHNOLOGY ENHANCEMENTS AND EMERGING ENGINEERING RESEARCH, VOL 3, ISSUE 3 19 Transient Stability Improvement Of Power System With Phase Shifting Transformer Jyothi Varanasi, Aditya
More informationDelayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines
Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,
More informationEffects and Mitigation of Post-Fault Commutation Failures in Line-Commutated HVDC Transmission System
IEEE International Symposium on Industrial Electronics (ISIE 9) Seoul Olympic Parktel, Seoul, Korea July 5-8, 9 Effects and Mitigation of Post-Fault Commutation Failures in Line-Commutated HVDC Transmission
More informationNERC Protection Coordination Webinar Series June 30, Dr. Murty V.V.S. Yalla
Power Plant and Transmission System Protection ti Coordination Loss-of-Field (40) and Out-of of-step Protection (78) NERC Protection Coordination Webinar Series June 30, 2010 Dr. Murty V.V.S. Yalla Disclaimer
More informationProtection from Voltage Sags and Swells by Using FACTS Controller
Protection from Voltage Sags and Swells by Using FACTS Controller M.R.Mohanraj 1, V.P.Suresh 2, G.Syed Zabiyullah 3 Assistant Professor, Department of Electrical and Electronics Engineering, Excel College
More informationTopics in JNTU Syllabus Modules and Sub Modules Lecture. Basic characteristics L21 T1-Ch4, T2-Ch14 Characteristics. Modification of the control
SESSION PLAN Sl. Topics in JNTU Syllabus Modules and Sub Modules UNIT-III 9 Principal of DC link control Introduction Steady state equivalent circuit of a 2 terminal DC link Lecture L20 Suggested Books
More informationTerms defined in this Appendix are written in italics in the Agreement and its Appendices.
Appendix 1 of System Operation Agreement 1 (10) Definitions Terms defined in this Appendix are written in italics in the Agreement and its Appendices. The active reserve is divided into automatic active
More informationTesting Power Sources for Stability
Keywords Venable, frequency response analyzer, oscillator, power source, stability testing, feedback loop, error amplifier compensation, impedance, output voltage, transfer function, gain crossover, bode
More informationExtensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network
Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example
More informationDYNAMIC PERFORMANCE OF THE EAGLE PASS BACK-TO-BACK HVDC LIGHT TIE. Å Petersson and A Edris ABB Power Systems AB, Sweden and EPRI,USA
DYNMI PERFORMNE OF THE EGLE PSS K-TO-K HVD LIGHT TIE Å Petersson and Edris Power Systems, Sweden and EPRI,US INTRODUTION Eagle Pass ack-to-ack (t) Tie is a Voltage Source converter (VS) -based tie interconnecting
More informationAdaptive Flux-Weakening Controller for IPMSM Drives
Adaptive Flux-Weakening Controller for IPMSM Drives Silverio BOLOGNANI 1, Sandro CALLIGARO 2, Roberto PETRELLA 2 1 Department of Electrical Engineering (DIE), University of Padova (Italy) 2 Department
More informationZ-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION
Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION 1 Arsha.S.Chandran, 2 Priya Lenin 1 PG Scholar, 2 Assistant Professor 1 Electrical & Electronics Engineering 1 Mohandas College of Engineering
More informationJonathan (Xiangmin) Gao - GE Grid Solutions Douglas Rust - Dandsco LLC Presented by: Tom Ernst GE Grid Solutions
Jonathan (Xiangmin) Gao - GE Grid Solutions Douglas Rust - Dandsco LLC Presented by: Tom Ernst GE Grid Solutions PRC-001: System protection coordination PRC-019: Coordination with voltage regulating control
More informationPAPER-II (Subjective)
PAPER-II (Subjective) 1.(A) Choose and write the correct answer from among the four options given in each case for (a) to (j) below: (a) Improved commutation in d.c machines cannot be achieved by (i) Use
More informationDoctor of Philosophy
Voltage Interactions and Commutation Failure Phenomena in Multi-Infeed HVDC Systems By: A Thesis Submitted to the Faculty of Graduate Studies in Partial Fulfillment of the Requirements for the Degree of
More informationISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS
ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS INDO-US Workshop October 2009, I.I.T. Kanpur INTRODUCTION Electric Power Systems are very large, spread over a wide geographical area
More informationHarnessing of wind power in the present era system
International Journal of Scientific & Engineering Research Volume 3, Issue 1, January-2012 1 Harnessing of wind power in the present era system Raghunadha Sastry R, Deepthy N Abstract This paper deals
More informationElectrical Power Systems
Electrical Power Systems CONCEPT, THEORY AND PRACTICE SECOND EDITION SUBIR RAY Professor MVJ College of Engineering Bangalore PHI Learning Pfcte tofm Delhi-110092 2014 Preface xv Preface to the First Edition
More informationHarmonic Distortion Levels Measured at The Enmax Substations
Harmonic Distortion Levels Measured at The Enmax Substations This report documents the findings on the harmonic voltage and current levels at ENMAX Power Corporation (EPC) substations. ENMAX is concerned
More informationLiterature Review for Shunt Active Power Filters
Chapter 2 Literature Review for Shunt Active Power Filters In this chapter, the in depth and extensive literature review of all the aspects related to current error space phasor based hysteresis controller
More informationSetting and Verification of Generation Protection to Meet NERC Reliability Standards
1 Setting and Verification of Generation Protection to Meet NERC Reliability Standards Xiangmin Gao, Tom Ernst Douglas Rust, GE Energy Connections Dandsco LLC. Abstract NERC has recently published several
More informationPHYSICS (PRINCIPAL) 9792/02 Paper 2 Written Paper For Examination from 2016 SPECIMEN INSERT
Cambridge International Examinations Cambridge Pre-U Certifi cate www.xtremepapers.com PHYSICS (PRINCIPAL) 9792/02 Paper 2 Written Paper For Examination from 2016 SPECIMEN INSERT *0123456789* The question
More informationLV DC DISTRIBUTION NETWORK WITH DISTRIBUTED ENERGY RESOURCES: ANALYSIS OF POSSIBLE STRUCTURES
LV DC DISTRIBUTION NETWORK WITH DISTRIBUTED ENERGY RESOURCES: ANALYSIS OF POSSIBLE STRUCTURES Alessandro AGUSTONI Enrico BORIOLI Morris BRENNA * Giuseppe SIMIOLI Enrico TIRONI * Giovanni UBEZIO * Politecnico
More informationA Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 16, NO. 5, SEPTEMBER 2001 603 A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions
More informationReal-time Decentralized Voltage Stability Monitoring and Protection against Voltage Collapse
Real-time Decentralized Voltage Stability Monitoring and Protection against Voltage Collapse Costas Vournas National Technical University of Athens vournas@power.ece.ntua.gr 1 Outline Introduction to Voltage
More informationPutting a damper on resonance
TAMING THE Putting a damper on resonance Advanced control methods guarantee stable operation of grid-connected low-voltage converters SAMI PETTERSSON Resonant-type filters are used as supply filters in
More informationNew Techniques for the Prevention of Power System Collapse
New Techniques for the Prevention of Power System Collapse F. A. Shaikh, Ramanshu Jain, Mukesh Kotnala, Nickey Agarwal Department of Electrical & Electronics Engineering, Krishna Institute of Engineering
More informationA Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks
A Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks C. D. TSIREKIS Hellenic Transmission System Operator Kastoros 72, Piraeus GREECE
More informationAPPENDIX-A HVDC MILE STONE. 1965:Mercury-arc valveprojectcommissioned:konti-kan(250mw),sakuma
APPENDIX-A HVDC MILE STONE 1954:First HVDV Project Gotland 1 in Sweden. 1965:Mercury-arc valveprojectcommissioned:konti-kan(250mw),sakuma (300MW) (image) and NewZealand (600 MW).Development starts on HVDC
More informationImplementation of Revised IEEE Standard 1547
MAY 31, 2017 HOLYOKE, MASSACHUSETTS Implementation of Revised IEEE Standard 1547 Presentation to ISO-TO Operations Committee David Forrest Key Points As New England adds significant amounts of Distributed
More informationDynamic Stability Improvement of Power System with VSC-HVDC Transmission
Dynamic Stability Improvement of Power System with VSC-HVDC Transmission A Thesis submitted in partial fulfilment of the Requirements for the Award of the degree of Master of Technology In Industrial Electronics
More information1. Introduction to Power Quality
1.1. Define the term Quality A Standard IEEE1100 defines power quality (PQ) as the concept of powering and grounding sensitive electronic equipment in a manner suitable for the equipment. A simpler and
More informationPV CURVE APPROACH FOR VOLTAGE STABILITY ANALYSIS
373 PV CURVE APPROACH FOR VOLTAGE STABILITY ANALYSIS 1 Neha Parsai, 2 Prof. Alka Thakur 1 M. Tech. Student, 2 Assist. Professor, Department of Electrical Engineering SSSIST Shore, M.P. India ABSTRACT Voltage
More informationA New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated
More informationCHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS
84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial
More informationR10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours
Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions
More informationCoordinating Power Oscillation Damping Control using Wide Area Measurements
1 Coordinating Power Oscillation Damping Control using Wide Area Measurements E. Johansson, K. Uhlen, Member, IEEE, A. B. Leirbukt, Member, IEEE, P. Korba, Member, IEEE, J. O. Gjerde, Member, IEEE, L.
More information